Fixed Electrical Instillation Inspection
|
|
- Jacob Jefferson
- 6 years ago
- Views:
Transcription
1 Fixed Electrical Installation Inspection Fixed Electrical Instillation Inspection Client: Contact: Company Name Name Report No.: Survey Date: 26 TH of January 2012 Contact: Liam Taylor Donal Guinan Tel:
2 Contents Introduction Page 2 Executive Summary Page 3 Inspection Detail & Results Page 4-18 Inspection & Report compiled by: Mr. Gerald O Farrell BEng in Electronic Engineering, MSc Electrical Power Systems ger@conditionmonitoring.ie Signature Mr. Liam Taylor Taylor Condition Monitoring Ltd. Enterprise & Technology Park, Creagh, Ballinasloe Co. Galway ltaylor@conditionmonitoring.ie Signature
3 Introduction A fixed electrical Survey was carried out at XXXXXX, in on the 9 th January 2012 in accordance with ECTI Regulations and the Safety, Health and Welfare at Work (General Application) Regulations 2007, Part 3: Electricity. The inspection consisted of: A visual inspection was conducted on all main components of the fixed electrical installation. Items identified as requiring corrective action following the visual inspection were identified and are contained in the following report. The earth loop impedance of a proportion of the plants sockets were measured and assessed against in accordance with Annex 61F of the National Rules for Electrical Installations (4 th edition ET101:2008). The operating characteristics of a proportion of the plants RCDs were verified by injecting a test residual current and recording the time of operation by means of a proprietary instrument specifically designed for the purpose. The values obtained were assessed in accordance with Annex 61G of the National Rules for Electrical Installations (4 th edition ET101:2008). The results of this inspection together with comments and recommended corrective action, which when implemented will ensure that all main components of fixed electrical installation are in compliance with ETCI Regulations and the Safety, Health and Welfare at Work (General Application) Regulations 2007, Part 3: Electricity. Limitations The inspection was carried out where practicable at the discretion of the Inspecting Engineer, taking into account availability and accessibility. Cables concealed within trunking and conduits, or cables and conduits concealed under floors, in inaccessible roof spaces and generally within the fabric of the building or underground, were not visually inspected.
4 Executive Summary The panels at the XXXXXXX plant in are in good condition with some work required to bring all panels up to compliance with ETCI regulations. A procedure needs to be put in place to ensure that all fuses, MCB s and isolators are satisfactorily identified and labelled. As alterations are completed, legends and labelling should be reviewed and an annual inspection carried out. All updated legends should be dated and the previous revision discarded. There is evidence of strip connectors being used. This is not a good practice and should be discontinued. There is a potentially dangerous situation where some cable terminations have been left exposed. These could become live and cause a serious electrical shock or a fault condition. In any facility, it is important that standards are maintained to a high level. This includes maintenance and any alteration to panels or plant. It is important that all new installations or alterations are completed to a high standard and that this standard is maintained. This shall ensure a minimum amount of downtime of equipment due to faults and breakdowns and a safe plant for personnel to work in. The office was found to have insufficient earth bonding at its distribution board. This led to failures of the earth fault loop impedance of the circuits within this installation. The onsite electrical contractor sorted this issue immediately. An annual testing of the earth loop impedance and RCD trip protection should be put in place and the results recorded. This would ensure an unsafe situation does not occur.
5 Facility Inspection Detail & Results Periodic Inspections are completed on Electrical Installations to provide, so far as reasonably practicable for: 1) Protection against damage to property by fire and heat from an electrical defect. 2) Safety of persons against effects of electrical shock and burns. 3) Confirmation the installation is not damaged or deteriorated to impair safety. 4) The identification of installation defects and non-compliance with regulations. The following report identifies areas of the XXXXX plant in that had a visual inspection of the fixed electrical installation and the remedial action that is required as a result of this inspection.
6 1.01 Powerhouse/Main Switch Room Location / Equipment List Visual Insp. Action Plan Ref. No. Main Incomer CT Chamber Power Factor Correction Unit Action Required Power Factor Correction Isolator DB at Main Incomer Action Required Power Factor Correction Unit The PFC unit should be labelled. There are cables cut off at bottom of the panel as shown in photo 1, these should be removed. Photo The distribution board for this panel is not labelled. Current Electricity at Work regulation 78 (a) requires the identification of electrical equipment, by way of labelling or otherwise, in order to prevent danger arising from confusion, mistaken identity or some other cause. Regulation 78(c) requires all electrical circuits are suitably identified at their source to allow those circuits to be safely and securely de-energised and isolated.
7 1.02 Control Room Main Board Location / Equipment List Visual Insp. Action Plan Ref. No. Cableway Distribution Action Required 1.01 Sw./Fuse 1 Vacuum Sw./Fuse 2 Shed Supply Sw./Fuse 3 Conveyor Panel Sw./Fuse 4 Monson Isolation Distribution Action Required Main MCCB Incoming cableway Garo Junction boxes x 2 Action Required Dryer 2 Control Panel Monson Control Panel Action Required Silo Fans Action Required SWEGMA Action Required Dryer Burner (Kiln) Control Panel Action Required The cables shown in photo 1 are left dangling in this panel. It would be good practice to bolt these cables together and to earth. Photo 1
8 1.022 Control Room Dist. Board The identification of all components in this distribution board have not been identified as shown in photo 2. Photo Garo Junction Boxes There are two Garo junction boxes located at the side of this panel. These junction boxes should be labelled as to their function Monson Control Panel At the Monson control panel, a cable has been left exposed as can be seen in photo 3. This is a dangerous situation and needs to be rectified immediately Photo 3
9 1.025 Silo Fans Control Panel The labelling is poor on this panel as can be seen in photo 4. Current Electricity at Work regulation 78 (a) requires the identification of electrical equipment, by way of labelling or otherwise, in order to prevent danger arising from confusion, mistaken identity or some other cause. The labelling on this panel is insufficient to comply with this regulation. Photo 4 There are strip connecters used in this panel. The correct panel terminals should be used to connect cables. This panel needs to be cleaned out, it is full of a strawy substance SWEGMA There are strip connecters used in this panel. The correct panel terminals should be used to connect cables. There is a wire left exposed in this panel and could be live. This needs to be terminated in a suitable manner.
10 1.027 Kiln Control Panel There are black cables and also a yellow cable used as an earth. This installation does not comply with ETCI regulation as shown in photo 5. This cable should be sleeved as per ETCI regulation Supplementary colour marking or the cables replaced entirely with green/yellow coloured cable. Photo 5 Loop Impedance & RCD Operation Test Results SOCKET LOOP IMPEDANCE TEST DATA ETCI Regulation requires that the effectiveness of the measures for fault protection by automatic disconnection of supply is verified. This verification can be determined by measuring or calculating the earth fault loop impedance of the circuits within an installation. The table below are the results of the sockets tested and assessed against in accordance with Annex 61F of the National Rules for Electrical Installations (4 th edition ET101:2008). Test Socket Location Socket Voltage Loop Impedance /Fail No. Test Results 1 Main Sw Room 222V 0.23 Ω PASS 2 Control Room 220V 0.1 Ω PASS >8.28 Ω FAIL Loop impedance test were conducted using a ROBIN digital PSC Loop tester, Model no. KMP 4120
11 Test No. 3: The office sockets all tested in excess of 8Ω. This is a serious situation and required immediate attention. The manager of the office was informed and we also discussed the results with the on-site electrical contractor, Noel Fitzgerald of Millennium Electrical. He checked the cable earth bond and found these to be insufficiently bonded. He replaced the earth bond and the earth loop impedance at the distribution board measured 0.35Ω on his instrument. All the socket circuits should be measured to ensure they comply with ETCI Regulation VERIFICATION OF OPERATION OF RCD s For compliance with , the operating characteristics of RCDs should be verified by injecting a test residual current and recording the time of operation by means of a proprietary instrument specifically designed for the purpose. Tests were carried out using a UNITEST Telaris 0100 plus. The values obtained were assessed in accordance with Annex 61G of the National Rules for Electrical Installations (4 th edition ET101:2008). Area Panel Location Socket Location Phones only socket under stairs 30 ma Trip time / Fail FAIL 5 x rated residual operating current verification / Fail FAIL Corridor 51 ms 13 ms Socket FAIL FAIL below DB Lobby 50 ms 13 ms Reception 39 ms 13 ms Front office off of reception 44 ms 13 ms Back office 38 ms 13 ms off of reception Canteen 38 ms 12 ms Canteen 38 ms 12 ms Locker room 39 ms 14 ms
(date) except for the departures, if any, detailed as follows: Name (CAPITALS) N/A. Name (CAPITALS) N/A
Electrical Installation & Test Engineers DETAILS OF THE CLIENT Client / Freshco Food Stores, Kiln Park Business Estate, Milton Keynes, MK3 5FS ELECTRICAL INSTALLATION CERTIFICATE Issued in accordance with
More informationThe extent of liability of the signatory/signatories is limited to the work described above as the subject of this certificate.
This safety certificate is an important and valuable document which should be retained for future reference DETAILS OF THE CLIENT Client / DETAILS OF THE INSTALLATION Extent of the installation covered
More informationLevel 3 NVQ Diploma in Domestic Plumbing and Heating ( /025)
City & Guilds Tutor Training Guidance Level 3 6189 NVQ Unit 305/025 Understand and carry out electrical work on domestic plumbing and heating systems and components April 2013 This document is for tutors
More informationDCP3/ DETAILS OF THE CLIENT ADDRESS OF THE INSTALLATION
Issued in accordance with British Standard 7671 - Requirements for Electrical Installationsby a Domestic Installer enrolled with NICEIC, Warwick House, Houghton Hall Park, Houghton Regis, Dunstable LU5
More informationPAC1500Xi PORTABLE APPLIANCE CHECKER
PAC1500Xi PORTABLE APPLIANCE CHECKER OPERATING INSTRUCTIONS 211A912 CONTENTS 1) Safety... 1 2) Introduction & Description... 2 3) Applications... 2 4) Test Sequence... 3 5) Visual Inspection... 3 6) Earth
More informationPeriodic inspection reporting - recommendation codes for domestic and similar electrical installations
4 Periodic inspection reporting - recommendation codes for domestic and similar electrical installations This is one of a series of Best Practice Guides produced by the Electrical Safety Council* in association
More informationELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET
Candidate Code No. EASQ 3017 For Board Use Only Result Date Int Result Date Int ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ
More informationConsumer unit replacement in domestic and similar premises
Consumer unit replacement in domestic and similar premises 6 Issue 2 The Electrical Safety Council is indebted to the following organisations for their contribution and/or support to the development of
More informationGuide to Condition Reports for Domestic Electrical Installations
Guide to Condition Reports for Domestic Electrical Installations Guide to condition reports for domestic electrical installations Courtesy of Greater Manchester Fire and Rescue Service What is an electrical
More informationAmendment Number 3 of BS how it might affect you
Amendment Number 3 of BS7671 2008 - how it might affect you Geoff Cronshaw provides us with a look ahead at the proposals of Amendment 3 to BS 7671:2008 IET Wiring Regulations and the resulting changes
More informationELECTRONIC SECURITY THEORY/REGULATIONS EXAMINATION 19 November 2011
Candidate Code No. ESAI 27 For Board Use Only Result Date Result Date Int ELECTRONIC SECURITY THEORY/REGULATIONS EXAMINATION 19 November 2011 QUESTION AND ANSWER BOOKLET Time Allowed: 3 Hours INSTRUCTIONS
More informationGuide to condition reports for domestic electrical installations.
Guide to condition reports for domestic electrical Courtesy of Greater Manchester Fire and Rescue Service What is an electrical installation? An electrical installation is a fixed wiring system made up
More informationINSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS: RESIDUAL CURRENT DEVICES
INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS: RESIDUAL CURRENT DEVICES [The basis of this article was first published in Wiring Matters in issue 15, Summer 2005 and reflected the requirements of
More informationThe Legal Obligations of Employers to Maintain all Electrical Installations in a Safe Condition
The Legal Obligations of Employers to Maintain all Electrical Installations in a Safe Condition Issued in the interests of safety by The Legal Obligations of Employers to Maintain all Electrical Installations
More informationCode of Practice // For the installation, inspection and testing of electrical installations tel/fax:
Code of Practice // For the installation, inspection and testing of electrical installations tel/fax: 0870 241 7687 email: mpba@mpba.biz Introduction // This code of practice provides guidance for manufacturers,
More informationContents The IET Regulations, BS 7671, and this Guide 1.1 The need for this Electrician s Guide 1.2 The IET Regulations BS 7671
Contents 1 The IET Regulations, BS 7671, and this Guide 1 1.1 The need for this Electrician s Guide 1 1.2 The IET Regulations BS 7671 2 1.2.1 International basis 2 1.2.2 The Seventeenth Edition 3 1.2.3
More informationUser Information Sheet 008 : 2010
User Information Sheet 008 : 2010 Formerly UIS008, July 2009 ELECTRICAL INSTALLATIONS ASSOCIATED WITH BULK LPG INSTALLATIONS 1. Introduction This Information Sheet describes some of the principles and
More informationAllianz Engineering Inspection Services Ltd. Electrical Services. Product Information
Allianz Engineering Inspection Services Ltd Electrical Services Product Information Electrical Testing and Inspection Services The Electricity at Work Regulations (EaWR) states that all electrical systems
More informationAn overview of the main proposals in BS th Edition. Electrical Contractors Association
An overview of the main proposals in BS 7671 17 th Edition Electrical Contractors Association Why have Regulations Behold the electrician standing there. Soot, soil & verdigris defile his greasy hair.
More informationELECTRICAL APPLIANCE SERVICEPERSON EXAMINATION 19 November 2016 QUESTION AND ANSWER BOOKLET
Candidate Code No. EAS 1081 For Board Use Only Result Date Int Result Date Int ELECTRICAL APPLIANCE SERVICEPERSON EXAMINATION 19 November 2016 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time
More informationProject Briefing Document. Section 3 Electrical Services design guide and specifications
ESTATES SUPPORT SERVICE Project Briefing Document Section 3 Electrical Services design guide and specifications Issue 1.1 June 2014 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor...
More informationMains Power Filter 970MF10 970MF20. Installation Instructions
Mains Power Filter Installation Instructions and Table of Contents 1.0 Warnings... 3 2.0 Introduction... 3 3.0 Quick Installation Overview... 3 4.0 Typical Installations... 3 5.0 Protection Concepts...
More informationElectrical Management
5 WHS PROCEDURE P23-01 Page 1 of 9 Issue: 2 1. Intent The Salvation Army Australia Eastern Territory (TSA-AUE) is committed to the provision of a safe, healthy and injury free environment within the mission
More informationGuide to: 17 th Edition Consumer Units
Guide to: 17 th Edition Consumer Units Introduction For well over one hundred years the Wiring Regulations have provided the rules which must be followed to make sure that electrical installations are
More informationELECTRICAL SAFETY for GAS ENGINEERS ACV. Do a GOOD JOB Take care of YOURSELF STAND OUT from the competition 2018 ISSUE 1. sterling4gas.co.
ELECTRICAL SAFETY for GAS ENGINEERS 238.7 ACV Do a GOOD JOB Take care of YOURSELF STAND OUT from the competition 2018 ISSUE 1 sterling4gas.co.uk 01536 400802 QUESTIONS GAS ENGINEERS SHOULD ASK... 1. How
More informationReplacing a consumer unit in domestic premises where lighting circuits have no protective conductor
Replacing a in domestic premises where lighting circuits have no protective conductor This is one of a series of Best Practice Guides produced by the Electrical Safety Council* in association with leading
More informationAlan Wells Technical and Standards Director Certsure LLP trading as NICEIC
Introduction Alan Wells Technical and Standards Director Certsure LLP trading as NICEIC Who are Certsure? Where do we come from? 1923 - A National Register created 1956 - NICEIC established as a Charity
More informationCommissioning Methodologies (CM) MUBS-09 Duct Mounted Temperature & Humidity Sensor Testing Method Statement
Client: Project Name: Project No: Area: Drawing No s: Date: Sheet: 1 of 5 Check Conducted By: Signature: Check Approved By: Signature: INTRODUCTION AI - Analogue Input: (...) The on-site commissioning
More informationEDA Scottish Section Regional Business Forum
EDA Scottish Section Regional Business Forum 1 The trade association for Electrical Contractors in Scotland Founded in 1900 as the Electrical Contractors Association of Scotland Over 1200 members SELECT
More informationLC3000 Level Controller Installation and Maintenance Instructions
4025550/12 IM-P402-36 AB Issue 12 LC3000 Level Controller Installation and Maintenance Instructions 1. General safety information LC3000 NORM ALARM TEST 2. General product information 3. Installation 4.
More informationFlame Rod Manual. Publication Rev A
Publication INTRODUCTION This manual contains information for the Flame Rod Flame Detection system from Forney Corporation, 16479 North Dallas Parkway, Suite 600 Addison, TX 75001. All personnel should
More informationEQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT
EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/18 Introduction to the Report The following report contains
More information3 o/c2 The symbol used to show that a BS 88 device has a motor circuit application is a gg b gm c l z d I 2.
Sample Questions - C&G 2382 17th Edition PaperB 1 o/c1 Electrical installation design shall take into account a electromagnetic disturbances b direct lightning strikes c current world copper prices d local
More informationSAFETY AND OPERATING MANUAL
SAFETY AND OPERATING MANUAL Original instructions 2 General Safety Warnings WARNING! Read all safety warnings and all instructions. Failure to follow the warnings and instructions may result in electric
More informationModuflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU
Moduflex Dry Air System Desiccant Air P3TJA13A1AN - P3TJA13A7AN EN USER GUIDE (Original Language) NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU LV LT RU SL TR MT CONTENTS 1 Safety Information...2 1.1
More informationOverfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland
Scully Intellitrol Safety Manual Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options TÜVRheinland Functional Safety Type Approved FS IEC 61508 Certified SIL 2 / SIL
More information1 of 12 7/26/14, 5:10 PM
TIO Program Scripps Cardiovascular Institute - Tower Inc 4 Architectural, Mechanical, Plumbing, Electrical Original Approved TIO: (Download Attachment) Notice of Start of Construction Date: 2011-04-01
More informationInstruction Manual ET0002 / Version 1.0. Heating Tape
Instruction Manual ET0002 / Version 1.0 Heating Tape Contents Introduction 3 General Description 3 Important Safety Advice 4 Electrical Requirements 4 Before Use 5 Prepare Surface 5 Visual Inspection and
More informationDUCT AIR HEATER WITH BUILT-IN CONTROLS. Installation & User Instructions. Stock Ref T T T3
DUCT AIR HEATER WITH BUILT-IN CONTROLS Installation & User Instructions Stock Ref. 105 31 100 T1 105 31 125 T1 105 31 150 T1 105 31 200 T1 105 31 250 T1 105 31 315 T1 Stock Ref. 105 31 315 T3 105 31 400
More informationSECTION ISOLATED POWER SYSTEMS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to
More informationBS Outcomes 6
BS7671 2015 Outcomes 6 Inspection and testing 6.1 Identify the general requirements for inspection and testing of installations 6.2 State the need for diagrams, charts or tables to be available e prior
More informationES8. Candidate Code No. For Board Use Only. Result Date Int. Result Date Int
ES8 Candidate Code No. For Board Use Only Result Date Int Result Date Int ELECTRICAL WORKERS REGISTRATION BOARD ELECTRONIC SECURITY THEORY/REGULATIONS EXAMINATION 9 September 2006 QUESTION AND ANSWER BOOKLET
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-25781-1 IEC 61010-1:2010 SOUTH AFRICAN NATIONAL STANDARD Safety requirements for electrical equipment for measurement, control, and laboratory use Part 1: General requirements This national
More informationEQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT
EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory South Panishail, Kashimpur, Joydebpur, Gazipur Joydebpur, Gazipur 04 May 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 04 May
More informationELECTRICAL SERVICE TECHNICIAN EXAMINATION 12 September 2015 QUESTION AND ANSWER BOOKLET
EST 2066 Candidate Code No. For Board Use Only Result Date Int Result Date Int ELECTRICAL SERVICE TECHNICIAN EXAMINATION 12 September 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Two Hours INSTRUCTIONS
More informationTesting and Calibration Report
07/02/2011 Testing and Calibration Report for and on behalf of: Dr Jones Jones Surgery Newport Gwent NP20 2DX Your Next Test Date February 2012 Call: 01633 213366 Email:calibration@millermedicalsupplies.com
More informationNon-domestic gas installations (Edition 2)
Irish Standard I.S. 820:2010 Non-domestic gas installations (Edition 2) NSAI 2010 No copying without NSAI permission except as permitted by copyright law. I.S. xxx: Irish Standard national specification
More informationFlostop TS D7E and A8E. Operation Manual
Flostop TS D7E and A8E Operation Manual United Kingdom Spectron Gas Control Systems Ltd, Unit 4, ATU1, University of Warwick science Park, Coventry, +44 (0) 24 7641 6234 sales@spectron-gcs.com Germany
More informationNewport City Council Bettws High School Fire Fighting Performance Specification CONTRACT C1
Fire Fighting Performance Specification CONTRACT C1 Fire Fighting Performance Specification August 2008 4 Pierhead Street, Capital Waterside, CF10 4QP Tel +44 2920 473727 Fax +44 2920 472277 This report
More informationResidual Current Devices
Residual devices F200 Series UL 1053 Residual devices F200 Series Residual Current Devices Description The F200 Series residual devices offer a wide range of product for all of your fault protection needs.
More informationBUTLER COUNTY RURAL ELECTRIC COOPERATIVE ALLISON, IOWA
SERVICE AND METER-RELATED DOCUMENTS BUTLER COUNTY RURAL ELECTRIC COOPERATIVE ALLISON, IOWA TABLE OF CONTENTS Document Page(s) CT & PT Cabinet Rated Overhead/Underground 2-3 Self-Contained Meter Service
More informationELECTRICAL SAFETY INSPECTION REPORT
ELECTRICAL SAFETY INSPECTION REPORT MUAZUDDIN TEXTILES LTD. Plot # 235/236, East Chandura, Shafipur, Kaliakor, Gazipur, Bangladesh. Factory List: 1. Inspected by: Younten Jamtsho Report Generated by: Stabak
More informationInventory + Check In
Inventory + Check In Date of Report Reference No 10071175 Tenant's Name Prepared By Mr Bond Mr Smith The Inventory Manager ltd Warrington Greater Manchester M28 2SZ 0844 725 2000 paul@theinventorymanager.co.uk
More informationData Bulletin. Determining the Cause of AFCI Tripping Class 760
Data Bulletin 0760DB0204 06/2002 Cedar Rapids, IA, USA Determining the Cause of AFCI Tripping Class 760 Retain for future use. INTRODUCTION DANGER HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This document
More informationINSTALLATION OPERATION - MAINTENANCE MANUEL FANS WITH CABINET
INSTALLATION OPERATION - MAINTENANCE MANUEL FANS WITH CABINET VENCO Havalandırma ve Makina San.ve Tic. A.Ş. 2004. Cad. No:5 45400 OSB Turgutlu MANİSA / TÜRKİYE Tel: 0090 (236) 332 5070 Fax: 0090 (236)
More informationOperating Instructions
Bracken Hill South West Industrial Estate Peterlee Co Durham SR8 2SW ENGLAND Tel: +44(0)191 5863511 www.seaward.co.uk sales@seaward.co.uk service@seaward.co.uk Part Number 347A550 Revision 1 2006 Seaward
More informationUnderstanding and implementing an electrical safety regime in your organisation. Dispelling the myths and promoting a risk-based approach
Understanding and implementing an electrical safety regime in your organisation Dispelling the myths and promoting a risk-based approach Presented by: Richard Slade Who are we? Market leaders in the manufacture
More informationUEE30811 Q-Tracker Work Tasks
UEE30811 Q-Tracker Work Tasks UEENEEC020B Participate in electrical work and competency development activities Q-Tracker requirements: 40 hours of practical training. 1. Comply with electrical industry/enterprise
More informationSystems of inspecting the existing building and the procedures of auditing engineering plans. M. Mostafa
Systems of inspecting the existing building and the procedures of auditing engineering plans M. Mostafa 2 Agenda 1. Introduction 2. Why inspection? 3. Initial Verification 4. Periodic verification 5. Reference
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60364-4-41 Fifth edition 2005-12 GROUP SAFETY PUBLICATION Low-voltage electrical installations Part 4-41: Protection for safety This English-language version is derived from
More informationTYPE TR Duct Ducting type
SUPPLEMENTARY INSTRUCTION BOOKLET GB140c AIR HEATER TYPE TR Duct Ducting type YOU MUST READ THIS DOCUMENT BEFORE COMMENCING INSTALLATION. THE USER MUST BE INSTRUCTED IN USING THE APPLIANCE. KEEP THIS DOCUMENT
More informationInventory + Check In
Inventory + Check In Date of Report Reference No 1007903 Tenant's Name Prepared By Mr Bond Mr Smith The Inventory Manager Ltd 31a Hazelhurst Road Worsley Greater Manchester M28 2SZ 0844 725 2000 paul@theinventorymanager.co.uk
More informationSECTION AUTOMATIC TRANSFER SWITCHES
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph
More informationTempest TP420/180 Electric Pressure Washer
Please dispose of packaging for the product in a responsible manner. It is suitable for recycling. Help to protect the environment, take the packaging to the local amenity tip and place into the appropriate
More informationA. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationCAUTION - READ THESE INSTRUCTIONS BEFORE USING THE MACHINE
User instructions Model X46 Escalator and Travelator cleaner CAUTION - READ THESE INSTRUCTIONS BEFORE USING THE MACHINE 03-7845-0000 Iss.1 07/04 Fig 1 Fig 2 2 Contents Page 1 Product information... 4 1.1
More informationWelcome to Hager Presentation
Welcome to Hager Presentation Topics Intro to Hager Group Circuit Protection Enclosures Q&A IIEE Manila 4 th August 17 13.03.2009 2 Company presentation Who we are Hager Group is a leading provider of
More informationSOUTH DUBLIN COUNTY COUNCIL Traffic Management Centre Roads (Traffic and Transportation) Department
SOUTH DUBLIN COUNTY COUNCIL Roads (Traffic and Transportation) Department TECHNICAL SPECIFICATION 4 SDCC-TS-04 SIGNAL INSTALLATION REQUIREMENTS REQUIREMENTS FOR THE DESIGN AND INSTALLATION OF TRAFFIC CONTROL
More informationNeil Hewitt Electrical & Air Conditioning P/L
VISUAL SAFETY EXAMINATION / INSPECTION CHECKLIST Examination / inspection checklist Customer:... Date:... Address:... Phone:...... Mobile:... Contact:... Inspection Activity Yes No NA General Basic protection
More informationSECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)
SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill
More informationINITIAL ELECTRICAL ASSESSMENT REPORT (EAR)
INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Address: 687, Al-Haj Nurl Amin Sowdagar Lane CDA, R/A, Road No 20, South Agrabad Chittagong Chittagong Bangladesh 03 Apr 2014 The Alliance for Bangladesh
More informationINITIAL ELECTRICAL ASSESSMENT REPORT (EAR)
INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: Karardi, Shibpur, Narsingdi Narsingdi Dhaka Bangladesh Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/15 10 Apr 2016 Introduction
More informationREGULATED QUALIFICATIONS FRAMEWORK (RQF)
REGULATED QUALIFICATIONS FRAMEWORK (RQF) QUALIFICATION SPECIFICATION: LCL Level 3 Certificate in Installing Testing and Ensuring Compliance of Electrical Installations in Dwellings 601/7876/0 (QiW (C00/0752/8))
More informationPopcorn Warmer Cabinet
Popcorn Warmer Cabinet Copyright July 2016 Future Products Group Limited. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or
More informationSPECIFICATION GUIDELINE FROST PROTECTION FOR PIPES. Tender Specification. Engineering Specification for Pipe Frost Protection. Contents.
Tender Specification Package #: Trace Heating Engineering Specification for Pipe Frost Protection Contents Y24 Trace heating 2 Appendix A Schematics & Drawings 8 Prepared by: Authorised by: Issued
More informationRE-PR3-E-27 3-Phase Panel Mount 27kW
Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting
More informationINSTRUCTIONS AND WARRANTY
INSTRUCTIONS AND WARRANTY MODEL NO. RHHD20 RUSSELL HOBBS 2000W PROFESSIONAL HAIR DRYER Congratulations on purchasing our Russell Hobbs 2000W Professional Hair dryer. Each unit is manufactured to ensure
More information1U ULTRA Compact System
en atel Supervisory Module SM32 Load 60 00 A IE C60947-2 G B140 4 8.2 CHNT NB1-63 C32 23 0/40 0 V e NaT el OK enatel RM 1848 enatel RM 1848 Battery 60 00A IE C60947-2 G B1 4 04 8.2 CHNT NB 1-63 C32 23
More informationStudent Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationRequirements for Electrical Installations
BRITISH STANDARD BS 7671:2008 + Amendment 1:2011 (Corrigendum June 2013) Requirements for Electrical Installations IET Wiring Regulations Seventeenth Edition ISBN-13: 978-1-84919-730-4 BS 7671 Requirements
More informationNext Generation Corona Discharge Installation & Operation Manual
Next Generation Corona Discharge Installation & Operation Manual 4-2319-01 Rev.A IMPORTANT SAFETY INSTRUCTIONS READ & FOLLOW ALL INSTRUCTIONS Read this manual completely before attempting installation.
More informationElectrical Protection and Transportation Installations for Non-domestic Buildings
Unit 53: Electrical Protection and Transportation Installations for Non-domestic Buildings Unit code: H/601/1392 QCF level: 5 Credit value: 15 Aim This unit provides learners with an opportunity to develop
More informationManaging Ex Asset Integrity
Managing Ex Asset Integrity White Paper Electrical Considerations for Hazardous Areas Authors: D Evans / T Jones February 2015 www.cpengineering.co.uk T: +44 (0)1792 897002 Copyright 2015 C&P Engineering
More informationDOMESTIC INSTALLATIONS COMMERCIAL INSTALLATIONS LIGHTING SOLAR PV REPAIRS LANDLORDS SWITCH ON TO SWH ELECTRICAL SOLUTIONS
DOMESTIC INSTALLATIONS COMMERCIAL INSTALLATIONS LIGHTING SOLAR PV REPAIRS LANDLORDS SWITCH ON TO SWH ELECTRICAL SOLUTIONS SWH ELECTRICAL SOLUTIONS Domestic INSTALLATIONS Expert and reliable electrical
More informationINSTRUCTIONS MODEL: MWB
Page 1 of 8 INSTRUCTIONS MODEL: MWB SAFETY INSTRUCTIONS INSTALLATION INSTRUCTIONS OPERATION INSTRUCTIONS MAINTENANCE INSTRUCTIONS WARRANTY INFORMATION DISPOSAL INFORMATION Customer Information MODEL NUMBER:
More informationInstruction Manual April sitrans AS 100
Instruction Manual April 2005 sitrans AS 100 Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment.
More informationSEMPEO SQA Unit Code H02H 04 Wiring electrical equipment and circuits
Overview This standard covers a range of basic competences that you need to wire up electrical equipment and circuits. It will prepare you for entry into the engineering or manufacturing sectors, creating
More informationSECTION GENERATOR PARALLELING CONTROLS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 23 13 GENERATOR PARALLELING CONTROLS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable
More informationER 52 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) EA 147M(c)(i) (1 mark) EA 147M(c)(ii)
ER 52 Electrician Regulations Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The marker can
More informationLegislation associated with Hazardous Locations. Pieter Coetzee ZONE 2 ZONE 1 ZONE 0. Be safe be Ex
Legislation associated with Hazardous Locations Pieter Coetzee ZONE 2 ZONE 0 ZONE 1 Be safe be Ex Contents History Introduction Occupational Health and Safety Act. (Act 85 of 1993) General Machinery Regulation
More informationMains Supply Guard User Manual
Mains Supply Guard User Manual Version 1.1 2016 Jansen Medicars Jansen Medicars Postbus 49 3600 AA Maarssen Netherlands Tel. +31 30 2613500 Fax. +31 30 2616714 URL www.medicars.com 2016 Jansen Medicars
More informationTAITA TAVETA UNIVERSITY P.O.BOX , VOI, KENYA Tel: TENDER NO: TTU/T/01A/
TAITA TAVETA UNIVERSITY P.O.BOX 635-80300, VOI, KENYA EMAIL: procurement@ttu.ac.ke; Tel: 020 8150257 TENDER NO: TTU/T/01A/2017-2018 CONSTRUCTION OF PROPOSED ADMINISTRATION BLOCK- TAITA TAVETA UNIVERSITY
More informationEQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT
EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory Sharoj Tower, Plot No, M-4/2, Section-14, Mirpur, Dhaka Dhaka Dhaka 20 May 2014 The Alliance for Worker Safety Page 1/18 20 May 2014 Introduction
More informationINITIAL ELECTRICAL ASSESSMENT REPORT (EAR)
INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Name: Tetlabo, Rupgonj, Narayangonj Rupgonj Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/22 27 May 2014 Introduction
More informationEQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT
EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Factory 50-60, Dakkhin Panishail. N.K. Link Road, Kashimpur, Gazipur Gazipur 08 May 2014 The Alliance for Bangladesh Worker Safety Page 1/23 08 May 2014
More informationINITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION
INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Assessor: Nalzani, Chandana Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Emkay Enterprises The Alliance for Worker Safety Page 1/13 Introduction to the Report
More informationELECTRICAL SAFETY INSPECTION REPORT
ELECTRICAL SAFETY INSPECTION REPORT FOPTEX (PVT.) LTD. PLOT# A/24-25, VSCIC HOSIERYFATULLAH, CHITTAGONG, BANGLADESH. Factory List: 1. Foptex (Pvt.) Ltd. Inspected by: Tashi Penjor Report Generated by:
More informationAustralian/New Zealand Standard
AS/NZS 3019:2007 AS/NZS 3019:2007 Australian/New Zealand Standard Electrical installations Periodic verification AS/NZS 3019:2007 This Joint Australian/New Zealand Standard was prepared by Joint Technical
More informationTT302 (200W) Wireless receiver Pull cord Dimmer
TT302 (200W) Wireless receiver Pull cord Dimmer Product Description The TT302 Wireless receiver allows you to convert a standard 1 way light switch or pull cord in to a taptile compatible Dimmer circuit
More informationInstructions for Robust Fiber Appendix 4 Robust sites and nodes. Ver 1.2
Instructions for Robust Fiber Appendix 4 Robust sites and nodes Ver 1.2 2 CONTENTS 1. Introduction 3 2. Sites and nodes 4 2.1 Classification of sites and nodes 4 2.2 Establishing sites and nodes 5 2.2.1
More information