FIREGUARD COLOR CHART

Size: px
Start display at page:

Download "FIREGUARD COLOR CHART"

Transcription

1 FIREGUARD COLOR CHART Standard Color FIREGUARD 20, 60, 90, 180 #55 Platinum Optional Colors Available at Additional Cost #63 Sandalwood #53 Rose #62 Nile #77 Almond #64 Colonial Blue #33 Toast

2 FIRE DOOR SELECTION GUIDE This guide will assist the specifier in selecting the most appropriate assembly and related options based on: Fire rating required. Special requirements for access control/security. FIRE RATINGS: 3. Won-Door FireGuard is listed as a fire-rated door (NFPA 252) with ratings up to 3 hours. Door Model Fire Rating Won-Door FireGuard Minutes Won-Door FireGuard 60 1 Hour Won-Door FireGuard /2 Hours Won-Door FireGuard Hours Won-Door FireGuard is also listed as a 450 temperature rise door (NFPA 252) with a 1 1/2 hour rating for use in stairwell enclosure applications Door Model Fire Rating Won-Door FireGuard 90TR 1 1/2 Hour Temperature Rise Won-Door FireGuard is also listed as a moveable fire wall (ASTM E-119) in straight, single parting configurations. Door Model Fire Rating Won-Door FireGuard MFWI 1 Hour Won-Door FireGuard MFWII 2 Hours SPECIAL REQUIREMENTS (OPTIONAL): 3. a. b. Exit Hardware may be specified at multiple locations along the door assembly to allow exiting from a space where a single exit device would not be sufficient. (see details on page 35) Vision Panels may be specified to meet code requirements for smoke barriers. (see details on page 33) Access Control Options. Where required, the Won-Door FireGuard assembly can be equipped to provide two levels of access control. (: Access Control is disabled when the door is in fire mode.): Level 1 Access Control Disabled Exit Hardware When the door is in the normal supervisory mode, the door s exit hardware is programmed to be inactive (it is active in emergency mode only). In addition, the closing system will seek the closed position. If an attempt is made to force the door off its closed limit, it immediately re-closes and sounds an alarm. The alarm can sound locally or remotely. When the door re-closes, the clutch engages for approximately 5 minutes to resist further attempts to force it open. A key switch or other access device is required to open/close the door, therefore specifiers must determine the type and location of the device(s) and specify the required boxes, conduit and wiring in the electrical section of the specification. (See pages 28, 29) For increased security, the standard sliding jamb and quick release jamb stops can be replaced with a heavygauge steel sliding jamb and rigid Z-shaped fixed jamb stops. An additional 25 mm of pocket depth is required. Level 2 Access Control Electromagnetic Locking Device An electromagnetic locking clutch is added to the closing system and provides 182 kg to 227 kg of resistance to opening. A key switch or other access device is required to open/close the door, therefore specifiers must determine the type and location of the device(s) and specify the required boxes, conduit and wiring in the electrical section of the specification. (See pages 28, 29) USING OTHER TYPES OF ACCESS DEVICES (OPTIONAL) In the access control applications, other types of operating devices can be added including numeric keypads, push button and infrared operating devices, providing they are capable of receiving a low voltage signal via stranded 18gauge wire in conduit to the Won-Door automatic closing system control box. Additional operating device contacts can be added as required. These access devices should be defined, provided, and installed under the respective specification section. ADVANCED SYNCHRONIZED LOGISTICS (ASL) (OPTIONAL) The REMOTE CONTROL AND STATUS PC STATION will monitor and control up to 120 FireGuard assemblies and consists of a dedicated personal computer and customized software designed to indicate door status information and to provide remote operation of the doors. (See page 30)

3 Specifications FireGuard 20, 60, 90, 180 SECTION Horizontal Sliding, Accordion-Type Fire Doors SPECIFICATIONS: PART 1 GENERAL 01 SUMMARY OF WORK A. Division 0 and Division 1, as indexed, apply to this section. B. Furnish and install all horizontal sliding, accordion-type fire doors shown on the drawings and specified herein. 02 RELATED SECTIONS A. All headers, support structures, surrounding insulation, jambs, storage pockets, pocket doors, access doors, blocking and trim shall be furnished and installed by other sections. B. All electrical wire, wiring, conduit and electrical boxes shall be furnished and installed by electrical section. C. [All track, soffit, chain guide and wall mounted striker posts shall be painted by Section Color shall be selected by the architect.] D. [(: The following paragraph should be included when 04 Option P, ASL-Advanced Synchronized Logistics, is specified) Regarding 04 Option P The Microsoft Windows based PC shall be supplied by the owner. Wiring from the computer to the doors shall be furnished and installed by the electrical section and shall consist of one (1) USOC RJ14-6POS 4 wire jack per line, up to eight (8) lines, installed near the computer. From the computer, each line shall daisy chain up to 32 doors together with one (1) USOC RJ14-6POS 4 wire jack installed on the back wall of the storage pocket for each door. Wire used in the daisy chain shall be a minimum of CAT 3 twisted 2 pair cable. Each line shall be 1219 meters or less in length.] E. [(: The following paragraph should be included when 04 Option J, individual LCD door status display panel, is specified) Regarding 04 Option J One (1) USOC RJ14-6POS 4 wire jack shall be supplied at the back of the storage pocket and shall be tied to the 4 square junction box adjacent to the door with CAT 3 twisted 2 pair cable. The junction box, RJ14 jack and wire shall be furnished and installed by the electrical section. Termination to the LCD panel shall be by punch down block and shall be by the electrical section as per the manufacturer s instructions. If the LCD panel is supplied with 04 Option J, then the CAT 3 twisted 2 pair cable can be terminated in parallel with the ASL wiring in the same USOC RJ14-6POS 4 wire jack.] 03 QUALITY ASSURANCE A. Installation shall be performed by factory trained and certified installers with a minimum of three years experience installing accordion-type fire doors. B. Fire doors shall be tested in accordance with China Test standard GB , listed by Underwriters Laboratories, and FM global for ratings as indicated, when tested in accordance with the requirements of UL 10B and ASTM E Fire doors shall comply with the requirements of the International Building Code Congress and NFPA C. Automatic closing system shall be tested in accordance with China Test standard GB and listed by Underwriters Laboratories and FM Global in accordance with the requirements of UL 864 and be intended for use with assembly in compliance with NFPA 80, Chapter 9, Section 9.4. D. Fire doors used for smoke and draft control shall bear the S mark on the fire door label and shall be tested in compliance with China Test standard GB1410 E. Fire doors used at the point of access to an elevator shall bear the S mark on the fire door label shall be tested in compliance with China Test standard GB1410 Brackets [ ] indicate specifier s option

4 Specifications FireGuard 20, 60, 90, 180 SECTION Horizontal Sliding, Accordion-Type Fire Doors 04 SUBMITTALS A. Refer to Section Shop Drawings and Submittals. B. Indicate required stacking depth, storage pocket width and height of header above finished floor. Show installation details, layout, and electrical requirements. 05 DELIVERY, STORAGE, AND HANDLING A. Deliver to the job site in manufacturer's original, unopened package. 06 COORDINATION BY GENERAL CONTRACTOR A. Coordinate the efforts of the various trades affected by the work of this section. Assure accurate installation of header, jamb, and trim. Provide field dimensions for fabrication. Supervise unloading and handling of materials. B. Permanent power shall be in-place and ready for final connection when fire doors are erected. Assure access to and proper clearance for motor operators. C. After testing the fire alarm system, automatic-closing fire doors shall be re-set to the original positions. D. Store boxes flat (not more than three high) in a dry area and protect from elements that may damage materials. Replace damaged materials at no cost to the owner. 07 WARRANTY A. Materials and installation shall be warranted against defects in workmanship for a period of one (1) year from the date of substantial completion. B. [A Manufacturers Service Agreement shall cover years 2 thru 5 and include regularly scheduled testing and inspection of all door functions. The Service Agreement will include [select one: annual, semi-annual, quarterly or monthly] visits to inspect, test and perform all required maintenance. All service and maintenance functions are performed by factory-trained service technicians.] C. [A comprehensive owner training seminar will be conducted by a factory trained service technician. The owner training shall include horizontal sliding, accordion-type fire door operation, care, maintenance, testing and trouble-shooting.] SPECIFICATIONS: PART 2 PRODUCTS 01 MANUFACTURER AND MODEL A. Horizontal sliding accordion-type fire doors shall be Won-Door FireGuard model WDFG[select one: 20, 60, 90, or 180] (number designates minutes of fire rating)(china classification code GFYJ FY3-Cx-S-203) as manufactured by Won-Door Corporation, Salt Lake City, Utah. (: Add suffix S for smoke and draft OR suffix E if door is used at the point of access to an elevator.) B. Products of other manufacturers demonstrating complete compliance with each of the fire rating and performance criteria of the product specified will be considered for approval. Minimum proof of compliance shall include UL 864 9th edition listing, UL test report and independent testing agency report documenting compliance with IBC Section and NFPA 80, Chapter 9. Written requests for substitutions will be considered by the architect up to ten days prior to the bid date. C. [No substitutions allowed.] 02 FIRE RATING A. Fire Doors shall be tested in accordance with China Test standard GB and listed by Underwriters Laboratory as special purpose fire doors having a fire resistive rating up to three hours in accordance with the requirements of UL 10B and ASTM E-2074.

5 Specifications FireGuard 20, 60, 90, 180 SECTION Horizontal Sliding, Accordion-Type Fire Doors 03 REMOTE MONITORING AND CONTROL (: Remote Monitoring and Control may be specified under 04 Option P) A. Fire doors shall be capable of being remotely monitored and controlled by a personal computer (PC). Information displayed on the computer shall indicate the voltage of the battery, AC line voltage and error conditions. Status information shall indicate whether the door(s) is closed, open, closing, opening, stopped, blocked or locked. Access using the Fire Exit Hardware shall be indicated as well as when the door(s) has received a fire signal. 04 MATERIALS A. Construction: shall consist of two parallel, accordion-type walls of panels independently suspended with no floor tracks, pantographs, or interconnections except at the lead-post. B. Panels shall be formed of 24-gauge (.7 mm) enamel coated steel V-grooved for strength and resilience. Panels shall be connected by full height 24-gauge (.7 mm) enamel coated steel hinges. Panels shall be modular in design and capable of in-place repair-ability. C. Suspension System: shall consist of two 14-gauge cold rolled steel (or 3 mm aluminum) tracks on 203 mm centers attached to the overhead structural support. Each lead post shall be suspended by an 8wheel ball bearing trolley. Each panel shall be suspended by a steel hanger pin and a ball bearing roller. D. Lead-posts: shall be of 24-gauge (.7 mm) cold rolled steel and shall be connected by specially formed steel panels. An internally mounted stabilizer bar shall keep lead-posts plumb and in proper alignment during operation and insure a tight fitting closure. E. Perimeter Seals: shall consist of continuous extruded vinyl sweeps attached to the top and bottom of the fire door to form a smoke and draft seal. F. Hanging weight shall be 27 kg/m G. Automatic Closing System shall consist of the following: Microprocessor based Electronic Control box with these features: a. Ability to monitor dual power sources continually for peak performance including: i. Detect a missing battery, bad battery, or low battery condition. ii. Detect if the charging circuit is bad. iii. Detect fuse failures. iv. Detect high or low AC conditions. b. Ability to monitor the health of the drive train including: i. Direction errors, obstruction errors, hindrance errors, and position errors. ii. Active daily path checks, by actually closing and opening to assure a clear path and proper operation. iii. Ability to monitor a passive input such as an infrared light beam to assure the closing path is clear. c. Ability to monitor inputs including: i. Sticky door block, exit hardware, patron hardware, and key switches. ii. Key switch mis-wires where key open and key close are both on simultaneously. d. Ability to self-monitor the health of: i. Internal volatile and non-volatile memory. ii. Proper operation of firmware. Brackets [ ] indicate specifier s option

6 Specifications FireGuard 20, 60, 90, 180 SECTION Horizontal Sliding, Accordion-Type Fire Doors e. Ability to run a watch dog monitoring circuit which will force a software restart in the event the software hangs, including the ability to track the number of resets that occur for diagnostic purposes. f. Ability to record the number of times the door has closed, opened, lost communication with external microprocessors, and the number of times the controller has been reset manually. g. Ability to monitor ambient temperature and lockout the operating devices once the environment at the door becomes untenable. h. Ability to enter a security mode to help control access through the door including: i. The ability to automatically re-close and secure itself after a legitimate patron access has occurred. ii. The ability to unlock and revert to a fire door in a fire alarm condition, including the ability to re-lock automatically after the fire alarm condition has cleared. i. Ability to withstand voltages up to 120 volts AC on the fire alarm input circuit without damage including the ability to indicate that the alarm circuit has not been wired as a dry contact, no voltage circuit when errant voltages are applied to the circuit. j. Ability to communicate with other microprocessors on the system via an internal bus system, including but not limited to microprocessors on the motor drive, in the leading edge of the door, and on a wall mounted display panel adjacent to the door. k. Ability to indicate trouble or supervised information both locally and at a remote location. Motor Operator Assembly including: a. A DC gear-motor, drive sprocket, clutch, and position sensors. The motor shall drive the fire door by means of a chain attached to a stabilizer bar trolley each time the door operates including the initial closing cycle. A door control momentary rocker switch shall be mounted on one side of the door near the lead post and shall have the following functions: Pressing the upper portion of the switch shall close the door and/or clear fault conditions. Pressing the lower portion of the switch shall open the door and/or temporarily mute the local horn. For doors using wall mounted key switches, 04 Option I, a color coordinated cover plate shall be provided to fill the hole left when the rocker switch is removed or not used. The control box shall be equipped with a service switch that performs the following functions: a. When the switch is off with AC power present, the controller shall emit an audible coded sound indicating the system is out of service. In this mode all normal functions shall cease including motor and communications. b. When the switch is off and AC power is not present, the controller shall enter a sleep mode during which the system shall use the battery to monitor the AC line for power but do nothing else. c. When the switch is moved from the off position to the on position, the controller shall enter a calibrate mode where it emits a coded audible alert indicating that the door needs to be closed to complete the calibration sequence. As soon as the door is closed, the controller shall automatically stop the audible alert, and resume all normal functions and monitoring. Leading Edge Obstruction Detector: Brackets [ ] indicate specifier s option

7 Specifications FireGuard 20, 60, 90, 180 SECTION Horizontal Sliding, Accordion-Type Fire Doors a. Shall be pressure sensitive such that each contact with an obstruction shall cause the door to stop, reverse enough to remove pressure on the leading edge, pause, and then re-close when in an alarm condition. The leading edge obstruction detector shall be fully functional at all times, including during the initial closing cycle. b. Constant pressure to the leading edge in the direction of opening shall, while the door is opening under motor power, continue to open under motor power until the leading edge is released. This is termed motor assisted opening. c. Constant pressure to the leading edge while not under motor power shall prevent motor operation and allow the door to be opened manually. 6. Exit Hardware shall be located on both sides of each fire door. a. In emergency mode, a slight pressure on the hardware will cause the door to open a minimum of 813 mm, pause for 3 seconds, and then automatically close. b. The open distance shall be field programmable, up to the entire opening width, if the local authority requires an opening larger than 813 mm. c. The pause before re-close shall be field programmable, up to 30 seconds, if the local authority requires a longer pause time. d. The exit hardware shall have the ability when not in the emergency (fire) mode or the security (lock) mode to be used to open the door and move it back into the storage pocket. e. The exit hardware shall be field programmable to provide access control. When programmed, the exit hardware shall not respond when pressed until activated by signal from smoke detector or fire alarm. 7. Suffix E doors shall include the following extras; track seals, anti-sway brackets every five feet or less across the opening, modified lead post trolleys and foil tape between the panels and the smoke liner. OPTIONS H. [Vision Panel shall consist of frame and clear glass assembly with listings from Underwriters Laboratory up to 1 1/2 hours]. (: required only in smoke barriers in Group I occupancies.) I. [A Key switch module shall be provided.] (: required for doors equipped with Access Control devices.) J. [An individual LCD door status display panel shall be provided adjacent to the door to indicate in the English language the status of the door, i.e. door position and trouble conditions. It shall have a port that allows easy access to a diagnostic tool for the purposes of field programming the door to customized settings. When used with the ASL system, it shall be compatible and not disrupt the ASL communications] (: Electrical requirements for the LCD panel can be found in 02 Option E) K. [Air Pressure Resistance. When the differential pressure on the two sides of the fire resistant and smoke resistant shutter is 20 Pa, the amount of smoke leaked through when it is in a standard state (20 deg C) shall not be greater than 0.2 m3 (m2*min).] L. [An infrared light beam shall be provided on non-curved doors to monitor the opening path. In the event that an object is placed in the path of the door for more than 4 minutes, the beam shall cause the door to sound an alarm indicating a path obstruction.] Brackets [ ] indicate specifier s option

8 Specifications FireGuard 20, 60, 90, 180 SECTION Horizontal Sliding, Accordion-Type Fire Doors M. [Acoustic Insulation: Interior surfaces of both walls shall be completely covered with a continuous blanket of.454 kg density foil-backed fiberglass fastened in place with steel spring-clips]. (: When specifying insulated doors, contact the manufacturer for pocket depths, hanging weight and size limitations.) OPTIONS - ACCESS CONTROL/MONITORING (: Level 1 and Level 2 Access Control options are independent systems and may not be specified in conjunction with each other) N. [Level 1 Access Control. The Exit Hardware shall not respond when pressed until activated by signal from smoke detector or fire alarm. Upgrades to the fire door for this level of access control shall include a heavy-gauge steel sliding jamb and rigid jamb stops.] (: at least one key-switch required.) O. [Level 2 Access Control. An Electromagnetic lock shall be added to the motor operator assembly to provide kg of resistance to manual opening until activated by a signal from fire alarm. When the fire alarm is cleared, the door returns to normal access control. Upgrades to the fire door for this level of access control shall include a heavy-gauge steel sliding jamb, rigid jamb stops and 10-gauge steel vertical reinforcement to the lead post.] (: at least one key-switch required.) P. [Advanced Synchronized Logistics- an integrated building asset management system (ASL), as manufactured by Won-Door Corporation, shall be furnished and installed to continuously control and monitor the status of up to 256 doors. ASL shall consist of a Multi-port On-site Monitor box, a serial cable, a 12-volt power supply and software on CD-ROM media. Installation, jacks, a computer (PC) and wiring shall be provided by others.] (: Electrical requirements for the ASL system can be found in 02 Option D) 05 COLOR A. Color shall be manufacturer s standard #55 Platinum. B. [Color shall be selected from manufacturer's optional colors at additional cost.] C. [Color shall be selected by architect and field painted by others.] SPECIFICATIONS: PART 3 EXECUTION 3.01 PREPARATION BY GENERAL CONTRACTOR A. Openings shall be to the dimensions specified, plumb and level. B. Headers shall be parallel with the finished floor within ±3 mm tolerance over the entire length of the opening. C. Manufacturer shall make available to the general contractor a DVD showing door opening preparation INSPECTION A. Inspect openings prepared for fire doors and surrounding conditions. Immediately notify the architect, in writing, of any unacceptable conditions INSTALLATION A. Install fire doors in accordance with manufacturer's instructions for clearance and fastenings. B. Adjust for smooth, quiet operation. Verify that all operations are functional and meet the requirements of applicable codes and regulations.

9 C. Upon completion of the installation, general contractor shall protect fire doors from damage and shall replace or repair subsequent damage so that doors are acceptable to the architect at no additional cost to the owner. D. Installation shall be performed by factory trained and certified installers with a minimum of three years experience installing accordion-type fire doors DEMONSTRATION A. Manufacturer s onsite field technician shall demonstrate the operation of the doors to the General Contractor. A DVD outlining the operation, scheduled maintenance, basic troubleshooting and care of the door system shall be provided to the owner by the door manufacturer. Copyright 2011 by Won-Door Corporation, all rights reserved. END OF SECTION Brackets [ ] indicate specifier s option

10 This page intentionally left blank.

11 STRAIGHT DOOR HEAD DETAIL STANDARD HEAD w/pocket MOUNTED MOTOR CAD FILE: FGHD1METRIC STANDARD HEAD w/pocket MOUNTED MOTOR CAD FILE: FGHD mm dia. threaded rod with nuts and washers by others. (457 mm O.C. in opening, 305 mm O.C. in stack area.) 1 layer 19 mm x 438 mm continuous plywood and 2 layers 19 mm x 381 mm continuous plywood. Stagger joints, glue and screw 610 mm O.C. with 2 #7 x 41 mm screws. [OR] 12 mm X 457 mm steel plate. Provide rated construction on each side corresponding to rating required for opening by others. (: 1 hour condition shown. To view additional rated conditions, visit our Two layers 16 mm x 457 mm x continuous type X gypsum board and three layers 12 mm x 92 mm type X gypsum board terminating 305 mm into the pocket. All gypsum to be furnished, installed, finished, and field painted by others. Motor operator unit. (Mounted at back of pocket. (See page 14) Structural support or anchorage by others. Structural support is not limited to concrete deck. Minimum dimension required to meet U.L. compliance. The dimension may be increased to further recess the head condition if required. L-shaped trim piece with pre-finished white color to match track by Won-Door. (Provides transition from track to gypsum soffit.) Brackets [ ] indicate specifier s option

12 STRAIGHT DOOR PLAN VIEW SINGLE PARTING SINGLE PARTING CAD FILE: FGPL1METRIC Provide rated construction on each side corresponding to rating required for opening by others. (: 1 hour condition shown. To view additional rated conditions, visit our Sliding jamb assembly. Exit Hardware. Blocking by others. Sliding jamb stops mounted 127 mm back from face of pocket. Non-rated pocket cover door by others. (See page 26, 27) Door bumper by others required when spring loaded hinge is not used by others. (See page 27) Maintain 229 mm clearance on each side of the centerline of the door. Fire rated bulkhead above, drop or flush with ceiling. Striker by Won-Door recessed into rated construction and caulked by others. Center striker pocket on door centerline. Brackets [ ] indicate specifier s option *To determine pocket depth, see the Instructions on page 17 and Pocket Depth Calculation Chart on page 18.

13 STRAIGHT DOOR PLAN VIEW BI-PARTING BI-PARTING CAD FILE: FGPL2METRIC Provide rated construction on each side corresponding to rating required for opening by others. (: 1 hour condition shown. To view additional rated conditions, visit our Sliding jamb assembly. Exit Hardware. Blocking by others. Sliding jamb stops mounted 127 mm back from face of pocket. Non-rated pocket cover door by others. (See page 26, 27) Door bumper by others. Bumper required when spring loaded hinge is not used. (See page 27) Maintain 229 mm clearance on each side of the centerline of the door. Fire rated bulkhead above, drop or flush with ceiling. Brackets [ ] indicate specifier s option *To determine pocket depth, see the Instructions on page 17 and Pocket Depth Calculation Chart on page 18.

14 STRAIGHT DOOR ELEVATION SIDE VIEW STANDARD POCKET MOUNTED MOTOR CAD FILE: FGELEV1METRIC Top of door track. (Fabrication height.) Ceiling line. Motor operator assembly. Folding fire door by Won Door. Storage pocket. Electronic control box by Won Door. [Optional keyswitch by Won Door. (See page 3] Fire exit hardware. (Allows passage through the door when closed.) Two 102 mm x 102 mm junction boxes surface mounted side by side on back wall of pocket 305 mm above finished floor for required electrical connections. Brackets [ ] indicate specifier s option

15 STRAIGHT DOOR ELEVATION FRONT VIEW STRAIGHT DOOR CAD FILE: FGELEV4METRIC 3. Fabrication height/field dimension height taken from top of track to top of finished floor. Finished floor. (Carpet, tile, etc.) Sub floor. (Concrete, etc.) Door Profile Widths: Stacked Width: 406 mm Extended Width: 292 mm

16 STRAIGHT DOOR HEAD DETAIL STEEL PAN HEADER STEEL PAN HEAD w/pocket MOUNTED MOTOR CAD FILE: SPHFGHD1METRIC mm threaded rods, Steel Pan Header and track assembly by Won-Door. Provide rated construction on each side corresponding to rating required for opening by others. (: 1 hour condition shown. To view additional rated conditions, visit our Motor operator unit. (Mounted at back of pocket. (See page 14) Minimum dimension required to meet U.L. compliance. The dimension may be increased to further recess the head condition if required. The Steel Pan Header System may be specified for straight doors less than 9144 mm wide and 3048 tall.

17 POCKET DEPTH CHART INSTRUCTIONS Single Parting Straight Doors The term CLEAR OPENING WIDTH on the Pocket Depth Calculation Chart refers to the distance from the front of the storage pocket to face of the striker. To determine the pocket depth requirement of a door: Determine the door s CLEAR OPENING WIDTH Find the appropriate range for that width (From-To columns) 3. Refer to the Single (for single parting) column. 4. Consult the Options Affecting Pocket Depth section below the chart to determine how optional equipment affects stack requirements. Example below: Pocket depth for FireGuard 60 single parting door w/ 2540 mm clear opening (in the range from 2489 mm to 2692 mm). Minimum pocket depth = 965 mm. Clear Opening Width Min. Pocket Depth From: To: Single Bi-Part Bi Parting Straight Doors Bi part doors require two storage pockets. Instead of using the total CLEAR OPENING WIDTH when referring to the stack chart, use 1/2 of the CLEAR OPENING WIDTH (which is the distance from the front of storage pocket on one side to the center of the door opening), then follow the same instructions listed in single parting (above) to determine the pocket depth requirement. For bi parting doors, a motor operator can be placed in each pocket to increase the maximum door size for a standard pocket mounted motor. For unequal bi parting doors, consult the factory. Example below: Pocket depth for FireGuard 60 bi parting door with 4775 mm clear opening width. Look up 2386 mm on stack chart (1/2 of 4775). Min. pocket depth = 1067 mm for each pocket. Clear Opening Width Min. Pocket Depth From: To: Single Bi-Part List of Options Affecting Pocket Depth Once you have determined the appropriate depth requirements using the chart on the next page, consult the Options Affecting Pocket Depth section below the chart. Optional equipment such as the access control sliding jambs, vision panels, and multiple exit hardware will also affect pocket depth as will pocket cover doors in excess of 51 mm thick.

18 STRAIGHT DOOR POCKET DEPTH CALCULATION CHART FireGuard 20, 60, 90, 180 *For bi parting doors: Use Clear Opening Width Single Bi1/2 the clear opening width. Minimum Pocket Depth is Parting Parting From: To: affected by door height The charts on this page show Minimum Pocket Depths for doors 3048 mm in height or less Minimum Pocket Depths for taller doors are shown Height Single Bi-Part below For doors over 3048 mm in height, if the Minimum Pocket Depth shown on the charts for the required width is less than that shown above use the appropriate value from above instead. If it is not, use the value shown on the charts. For doors over 4572 mm in height, the minimum pocket width of 508 mm is required For doors over 6096 mm in height, please consult the factory. The above chart is for straight door openings less than 183 m For straight doors openings 2 greater than 183 m, please consult the factory. Clear Opening Width Single BiParting Parting From: To: OPTIONS AFFECTING POCKET DEPTH: Access Control sliding jamb: Add 25 mm to pocket depth. Pocket Cover Door: Above charts allow for 51 mm thick cover door. Add appropriate amount if cover door and finish materials are thicker than 51 mm. (See page 26, 27) Vision Panel: Add 152 mm to pocket depth. Additional exit hardware: Add 25 mm to pocket depth for each exit device. Maximum of 3 sets of exit hardware per door leaf. FireGuard SE for doors used at the point of access to an elevator: Minimum stack depth is 813 mm.

19 CURVED DOOR HEAD DETAIL CURVED HEAD w/pocket MOUNTED MOTOR CAD FILE: FGHD3METRIC mm dia. threaded rod with nuts and washers by others. (457 mm O.C. in opening, 305 mm O.C. in stack area.) 3 layers 19 mm x 457 mm continuous plywood and 2 layers 16 mm x 140 mm continuous plywood. Stagger joints, glue and screw 610 mm O.C. with 2 #7 x 41 mm screws. 2 layers 16 mm x 178 mm continuous type X gypsum board by others. 2 layers 16 mm x 171 mm continuous type X gypsum board by others. Three layers 12 mm x 92 mm type X gypsum board terminating 305 mm into the pocket. All gypsum to be furnished, installed finished, and field painted by others. Motor operator unit. (Mounted at back of pocket. See page 14.) Structural support or anchorage by others. (Structural support is not limited to concrete deck.) Provide rated construction on each side corresponding to rating required for opening by others. (: 1 hour condition shown. To view additional rated conditions, visit our Minimum dimension required to meet U.L. compliance. The dimension may be increased to further recess the head condition if required. L shaped trim piece with pre finished white color to match track by Won Door. (Provides transition from track to gypsum soffit.) Brackets [ ] indicate specifier s option

20 CURVED DOOR PLAN VIEW SINGLE PARTING CURVED DOOR CAD FILE: FGPL1CURVEDMETRIC Provide rated construction on each side corresponding to rating required for opening by others (: 1 hour condition shown. To view additional rated conditions, visit our Sliding jamb assembly. 3. Exit Hardware. 4. Blocking by others. 5. Sliding jamb stops mounted 127 mm back from face of pocket. 6. Non-rated pocket cover door by others. (See page 26, 27) 7. Door bumper by others. Bumper required when spring loaded hinge is not used. (See page 27) 8. Maintain 229 mm clearance on each side of the centerline of the door. 9. Fire rated bulkhead above, drop or flush with ceiling. 10. Striker by Won-Door recessed into rated construction and caulked by others. Brackets [ ] indicate specifier s option *To determine pocket depth, see Instructions on page 24 and Pocket Depth Calculation Chart on page 25. Minimum radius is 1524 mm. Standard radii are 1524 mm and 3048 mm. Custom curves greater than 1524 mm and multiple curves are available.

21 CURVED DOOR PLAN VIEW BI-PARTING CURVED DOOR CAD FILE: FGPL2CURVEDMETRIC Provide rated construction on each side corresponding to rating required for opening by others. (: 1 hour condition shown. To view additional rated conditions, visit our Sliding jamb assembly. Exit Hardware. Blocking by others. Sliding jamb stops mounted 127 mm back from face of pocket. Non-rated pocket cover door by others. (See page 26, 27) Door bumper by others. Bumper required when spring loaded hinge is not used. (See page 27) Maintain 229 mm clearance on each side of the centerline of the door. Fire rated bulkhead above, drop or flush with ceiling. Brackets [ ] indicate specifier s option *To determine pocket depth, see Instructions on page 24 and Pocket Depth Calculation Chart on page 25. Minimum radius is 1524 mm. Standard radii are 1524 mm and 3048 mm. Custom curves greater than 1524 mm and multiple curves are available.

22 CURVED DOOR GUIDELINES 3. Centerline of header. (Radius of curved track is determined by measuring the centerline of the header.) Centerline of outside track. Centerline of inside track. Standard 1524 mm and 3048 mm radius with custom curves greater than 1524 mm and multiple curves available. Templates of header radii are supplied to the field upon request.

23 CURVED DOOR ELEVATION FRONT VIEW CURVED DOOR CAD FILE: FGELEV5 3. Fabrication height/field dimension height taken from top of track to top of finished floor. Finished floor. (Carpet, tile, etc.) Sub floor. (Concrete, etc.) Door Profile Widths: Stacked Width: 406 mm Extended Width: 292 mm

24 POCKET DEPTH CHART INSTRUCTIONS Single Parting Curved Doors The term CLEAR OPENING WIDTH on the Pocket Depth Calculation Chart refers to the distance from the front of the storage pocket to face of the striker. To determine the pocket depth requirement of a door: Determine the door s CLEAR OPENING WIDTH Find the appropriate range for that width (From-To columns) 3. Refer to the Single (for single parting) column. 4. Consult the Options Affecting Pocket Depth section below the chart to determine how optional equipment affects stack requirements. Example below: Pocket depth for FireGuard 60 single parting door w/ 2540 mm clear opening (in the range from 2489 mm to 2692 mm). Minimum pocket depth = 991 mm. Clear Opening Width Min. Pocket Depth From: To: Single Bi-Part Bi Parting Curved Doors Bi part doors require two storage pockets. Instead of using the total CLEAR OPENING WIDTH when referring to the stack chart, use 1/2 of the CLEAR OPENING WIDTH (which is the distance from the front of storage pocket on one side to the center of the door opening), then follow the same instructions listed in single parting (above) to determine the pocket depth requirement. For bi parting doors, a motor operator can be placed in each pocket to increase the maximum door size for a standard pocket mounted motor. For unequal bi parting doors, consult the factory. Example below: Pocket depth for FireGuard 60 bi parting door with 4775 mm clear opening width. Look up 2388 mm on stack chart (1/2 of 4775 mm). Min. pocket depth = 1067 mm for each pocket. Clear Opening Width Min. Pocket Depth From: To: Single Bi-Part List of Options Affecting Pocket Depth Once you have determined the appropriate depth requirements using the chart on the next page, consult the Options Affecting Pocket Depth section below the chart. Optional equipment such as the access control sliding jambs, vision panels, and multiple exit hardware will also affect pocket depth as will pocket cover doors in excess of 51 mm thick.

25 CURVED DOOR POCKET DEPTH CALCULATION CHART FireGuard 20, 60, 90, 180 Clear Opening Width Single BiParting Parting From: To: m2, please consult the factory. *For bi parting doors: Use 1/2 the clear opening width. Minimum Pocket Depth is affected by door height. The charts on this page show Minimum Pocket Depths for doors 3048 mm in height or less. For single parting doors mm in height, the minimum pocket depth is 940 mm. For bi-parting doors mm in height the minimum pocket depth is 1168 mm. For doors over 3962 mm in height, if the Minimum Pocket Depth shown on the charts for the required width is less than that shown above use the appropriate value from above instead. If it is not, use the value shown on the charts. For doors over 4572 mm in height, the minimum pocket width of 508 mm is required. For doors over 4572 mm in height, please consult the factory. The above chart is for curved door openings less than 154 m For curved doors openings greater than Clear Opening Width Single BiParting Parting From: To: OPTIONS AFFECTING POCKET DEPTH: Access Control sliding jamb: Add 25 mm to pocket depth. Pocket Cover Door: Above charts allow for 51 mm thick cover door. Add appropriate amount if cover door and finish materials are thicker than 51 mm. (See page 26, 27) Vision Panel: Add 152 mm to pocket depth. Additional exit hardware: Add 25 mm to pocket depth for each exit device. Maximum of 3 sets of exit hardware per door leaf. FireGuard SE for doors used at the point of access to an elevator: Minimum stack is 813 mm for single parting doors and 940 mm for bi-parting doors.

26 POCKET COVER DOOR GUIDELINES Pocket cover doors are not required, but may be used to aesthetically conceal Won Door Fireguard doors. When properly done, they add to the continuity of the project and provide anonymity to the installation. Won Door Corporation does not manufacture or install pocket cover doors. Therefore, they should be specified in a separate specification section. Unless specifically required by the Authority Having Jurisdiction, pocket doors need not be fire rated, but solid core doors are preferable for reasons of durability. The door thickness and covering material is at the discretion of the designer. Many covering materials have been successfully used including: plastic laminates, wood veneers, vinyl, paint, bronze, stainless steel, and marble. If the aggregate thickness of the pocket cover door exceeds 51 mm, however, the additional thickness must be added to the calculation of the pocket depth (see Pocket Depth Calculation Chart on page 17,24.) Some basic criteria for the successful design of pocket cover doors are listed below: Doors must be side hinge swinging and must swing at least 90. When in the open position, pocket doors may not encroach on the 457 mm minimum opening width required for the pocket. Designing notches on either side of the pocket opening to accommodate the cover door thickness will prevent this (see Pocket Cover Door Detail on page 27.) Cover doors must be operable with less than 268 kg of lateral force. As the Won Door FireGuard door is activated, the leading edge will make contact with the cover door and push it open. 268 kg is the normal operating force required for egress type swinging doors and only if the cover door is unusually heavy would special considerations need to be taken. 3. When activated, pocket doors should remain in the open position so as not to obstruct the path of the Won Door FireGuard door when it is closing. 4. Won Door recommends specifying either (a) a spring action such as the Hager #1257 (with reversed spring action)to hold the cover door open when activated or (b) a continuous hinge such as a Stanley #314. a. The reversed spring action in the Hager #1257 butt hinge makes the cover door selfopening rather than self closing. Cover doors without spring action hinges may swing back into the operating path of the Won Door FireGuard and cause damage or obstruct emergency operation. b. For aesthetic considerations, a continuous hinge is preferable because it does not protrude beyond the face of the pocket cover door and therefore presents a hinge less appearance. When a continuous hinge is used, however, a bumper is required. The bumper prevents the pocket door from swinging back in to the operating path of the Won Door FireGuard. Won door does not provide bumpers, but its design is shown on page A magnetic catch not to exceed kg can serve to keep the pocket cover doors in the closed position when the Won Door Fireguard door is not in use. Positive latches such as hooks or throw bolts are not permitted because they prevent the Won door FireGuard door from pushing the cover door open during operation. 6. A door frame is not required although one may be used. For aesthetic considerations, however, a frame less design may be preferable because it leaves only two slight reveals at the door edges and provides a less noticeable pocket door installation.

27 POCKET COVER DOOR DETAIL Provide fire rated construction corresponding to rating required for opening by others. Blocking for sliding jamb stops centered at 127 mm from face of pocket by others. Spring action hinge or continuous hinge by others. Non-rated pocket cover door by others. Magnetic catch (not to exceed kg) by others. Bumper (mounted on inside of pocket cover door 76 mm above finished floor) by others. Bumpers must be specified when non-spring action hinges are used.

28 POCKET MOUNTED MOTOR OPERATOR ELECTRICAL DIAGRAM : Cable lengths referred to in this detail are actual cable lengths, not straight line distances. If cable length exceeds 7.62 wire meters, consult the factory. Key switch is required with access control.

29 LARGE DOOR MOTOR OPERATOR ASSEMBLY WIRING DIAGRAM : Cable lengths referred to in this detail are actual cable lengths, not straight line distances. If cable length exceeds 7.62 wire meters, consult the factory.

30 ASL ADVANCED SYNCHRONIZED LOGISTICS The PC-based remote display provides central control and monitoring capabilities for up to 120 fire doors. The display screen monitors current status of each door (closed, closing, open, opening, stopped, blocked, access using fire exit hardware, or locked), battery voltage, and AC line voltage. The remotely located PC allows all monitored Won-Door FireGuard doors to be opened or closed from a central control station. Doors equipped with optional magnetic locks may also be remotely locked or unlocked. Changes in door status are displayed on the monitor when doors are in fire mode or a malfunction is detected. The Remote control and Status Display Station is a dedicated PC for use with Won-Door Fireguard assemblies only.

31 OPTIONAL KEY SWITCH 3. Key switch module. Plaster ring by others. 102 mm x 102 mm x 64 mm electrical box by others. Key switches are optional except with access control options. For safety reasons, a key switch must be installed within line-of-sight of the operation of the Won-Door FireGuard door.

32 CCOM ROCKER SWITCH CCOM rocker switch is included when a key switch is not specified. The switch is used to open and close the door and to reset and silence door faults.

33 OPTIONAL VISION PANEL 3. Ceiling line. 1 1/2-hour U.L. listed Vision Panel. Required only for smoke barrier applications in Group I occupancies. Maximum size is 146 mm x 67 mm. Exit hardware. Add 152 mm to pocket depth for vision panel (except when the vision panel is required to be closer than 1219 mm to the leading edge of the door or 2438 mm on a curved door. In these cases, contact the factory for details.)

34 OPTIONAL SINGLE DOOR DISPLAY 3. Single door display module. Plaster ring by others. 102 mm x 102 mm x 64 mm electrical box by others. The Single Door Display communicates door status & fault information to building tenants. Mounted in a standard 102 mm x 102 mm recessed J box.

35 OPTIONAL MULTIPLE EXIT HARDWARE DETAIL Top of track. Ceiling line. Finished floor. Exit hardware. (In sets, one on each side of the door, or one side only.) Up to three (3) sets of exit hardware per leaf may be specified at any horizontal locations on the door (example above shows two sets in front of a bank of elevators). Upon activation of the exit hardware, the FireGuard door will open to a field-programmable distance. Add 25 mm to stack or pocket depth for each set of exit hardware.

36

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC SECTION 08 35 13.23 ACCORDION FOLDING FIRE DOORS PART 1 GENERAL 1.01 SUMMARY OF WORK A. Division 0 and 1, as indexed, apply to this section. B. Furnish and install

More information

/WON BuyLine 3726 WON-DOOR. FireGuard. The ORIGINAL horizontal sliding accordion fire door.

/WON BuyLine 3726 WON-DOOR. FireGuard. The ORIGINAL horizontal sliding accordion fire door. 08 11 73/WON BuyLine 3726 WON-DOOR FireGuard TM The ORIGINAL horizontal sliding accordion fire door. Fire Safety by Design Founded in 1962, the Won-Door Corporation introduced the world s most durable

More information

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials. B B11.0 DIVISION 08 - OPENINGS SECTION 08 17 00 INTEGRATED DOOR OPENING ASSEMBLIES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and

More information

Won-Door FireGuard T H E P E R F E C T F I T I N A V A R I E T Y O F A P P L I C A T I O N S

Won-Door FireGuard T H E P E R F E C T F I T I N A V A R I E T Y O F A P P L I C A T I O N S Won-Door FireGuard T H E P E R F E C T F I T I N A V A R I E T Y O F A P P L I C A T I O N S Fire Safety By Design O N L Y T H E W O N - D O O R F I R E G U A R D C A N cover wide spans* heights up to

More information

Solutions for Common Problems

Solutions for Common Problems Solutions for Common Problems Security for exterior automatic sliding doors while maintaining egress requirements Solutions for maintaining Security, Fire, & Egress requirements Troubleshooting basic automatic

More information

University of Rochester October 17, 2008 Brooks Landing Business Center

University of Rochester October 17, 2008 Brooks Landing Business Center SECTION 087100 - DOOR HARDWARE PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Commercial door hardware. 2. Cylinders for doors specified in other Sections. 1.2 SUBMITTALS A. Product

More information

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR SECTION 08734 COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead

More information

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR SECTION 08 71 13 LOW ENERGY AUTOMATIC OPERATORS Specifier Note: Coordinate and edit articles

More information

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening. DIVISION 8 OPENINGS SECTION 08 33 23 PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead coiling counter fire doors. 1.2 RELATED SECTIONS A. Section 05500 - Metal Fabrications: Support framing and framed opening.

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

ARCHITECTURAL SPECIFICATIONS

ARCHITECTURAL SPECIFICATIONS 1 B9.1 In Ground Page 1 of 6, Aug 12 DIVISION 08 - OPENINGS SECTION 08 71 13 POWER DOOR OPERATORS Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section

More information

YOUR SINGLE SOURCE FOR EMERGENCY RESPONSE CLOSURE PRODUCTS

YOUR SINGLE SOURCE FOR EMERGENCY RESPONSE CLOSURE PRODUCTS YOUR SINGLE SOURCE FOR EMERGENCY RESPONSE CLOSURE PRODUCTS Coiling Fire Doors Firemiser Insulated Fire Doors SmokeShield Fire Doors SmokeShield Firemiser Doors Coiling Counter Fire Doors SmokeShield Counter

More information

INSTALLATIONN GUIDE & OPERATION MANUAL

INSTALLATIONN GUIDE & OPERATION MANUAL INSTALLATION INSTRUCTIONS ECO # 1569 REVISION #0006 FCS SERIES MODEL 5025, 5045,7525 & 7545 INSTALLATION INSTRUCTIONS BY: DATE: 01/23/2013 INSTALLATIONN GUIDE & OPERATION MANUAL MOTOR OPERATOR (V3.02 Controls)

More information

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System. SMOKE GUARD SYSTEM MODEL 400 SPECIFICATION Smoke Guard, Inc. 287 N. Maple Grove Boise, ID 83704 Toll Free: 800.574.0330 Fax: 208.376.1600 e-mail: info@smokeguard.com website: http://www.smokeguard.com/

More information

A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings.

A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. DIVISION 26 ELECTRICAL SECTION 26 51 13 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. B. Luminaire

More information

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System. SMOKE GUARD SYSTEM MODEL 600 REV. 3 SPECIFICATION Smoke Guard, Inc 287 Maple Grove Boise, ID 83704 Toll Free: 800.574.0330 Fax: 208.639.7851 e-mail: info@smokeguard.com website: http://www.smokeguard.com/

More information

1. Items known commercially as finish hardware or builders hardware, required for swing, sliding, or folding doors.

1. Items known commercially as finish hardware or builders hardware, required for swing, sliding, or folding doors. PART 1 - GENERAL 1.1 SUMMARY: A. Section Includes: SECTION 08710 FINISH HARDWARE 1. Items known commercially as finish hardware or builders hardware, required for swing, sliding, or folding doors. 2. Types

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

SECTION Overhead Coiling Doors

SECTION Overhead Coiling Doors SECTION 08 33 00 Overhead Coiling Doors To display hidden notes to specifier, select tools/ options/ view/ hidden text. GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

Carey Automatic Door, LLC 1 - PNEUMATIC OPERATOR FOR SINGLE SWINGING DOOR

Carey Automatic Door, LLC 1 - PNEUMATIC OPERATOR FOR SINGLE SWINGING DOOR Carey Automatic Door, LLC 1 - PNEUMATIC OPERATOR FOR SINGLE SWINGING DOOR IN for Doors Swinging under Operator OUT for Doors Swinging away from Operator Packages 1, 2 & 3 Packages 4, 5 & 6 FACTORS TO CONSIDER

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS FEBRUARY 2005MARCH 2007

UNIVERSITY OF ROCHESTER DESIGN STANDARDS FEBRUARY 2005MARCH 2007 SECTION 08710 - DOOR HARDWARE 1.1 SUMMARY A. Door hardware required for swinging doors. No pocket or folding doors permitted at U of R. 1.2 SUBMITTALS A. Hardware Schedule: To be coordinated with doors,

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

SECTION AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER

SECTION AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER SECTION 08 3493 AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Smoke detector-activated, vertical closing fire barrier conveyor system closure.

More information

Architectural Specification Sheet

Architectural Specification Sheet Architectural Specification Sheet 1. General 1.01 Summary A. commercial low energy automatic swing door operator that consists of: -Aluminum housing -Electro-mechanical motor -Operator control assembly

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

Port of St Helens SIA Aircraft Hanger Scappoose, OR

Port of St Helens SIA Aircraft Hanger Scappoose, OR Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System. SMOKE GUARD SYSTEM MODEL 200 SPECIFICATION Smoke Guard inc. 287 N. Maple Grove Boise, ID 83704 Toll Free: 800.574.0330 Fax: 208.639.7851 e-mail: info@smokeguard.com website: http://www.smokeguard.com/

More information

SECTION OVERHEAD COILING FIRE DOORS

SECTION OVERHEAD COILING FIRE DOORS SECTION 08331 OVERHEAD COILING FIRE DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on round Windows logo in top left corner,

More information

SECTION OVERHEAD COILING FIRE DOORS 641 SERIES OVERHEAD COILING COUNTER FIRE DOORS

SECTION OVERHEAD COILING FIRE DOORS 641 SERIES OVERHEAD COILING COUNTER FIRE DOORS SECTION 08331 OVERHEAD COILING FIRE DOORS 641 SERIES OVERHEAD COILING COUNTER FIRE DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft

More information

ARCHITECTURAL SPECIFICATIONS

ARCHITECTURAL SPECIFICATIONS 1 G4.1 Entrance System Page 1 of 6, August 2017 DIVISION 10 - SPECIALTIES SECTION 10450 PEDESTRIAN CONTROL DEVICES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements.

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. Minimum lighting control (base scope of work) shall include all corridors. The lighting in all the corridors shall be turned on (if not already on) if

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

DIVISION 10 SPECIALTIES

DIVISION 10 SPECIALTIES DIVISION 10 SPECIALTIES 11/11 SECTION 10 21 13.16 PLASTIC LAMINATE TOILET COMPARTMENTS PART 1 - GENERAL 1.01 SECTION INCLUDES Plastic laminate toilet compartments, urinal screens, head rail braced. 1.02

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION: RELEASE DEVICES MADE IN THE U.S.A. RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: The "WPS" World Power Series, Time Delay Release

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION 087100 - DOOR HARDWARE PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Commercial door hardware. 1.2 SUBMITTALS A. Product Data: For each type of product indicated. B. Other

More information

2. Interior doors shall be not less than 18 gauge steel.

2. Interior doors shall be not less than 18 gauge steel. DIVISION 8 - DOORS AND WINDOWS 08100 METAL DOORS AND FRAMES 1. Exterior doors shall be not less than 16 gauge steel. The top channel of each metal door shall be solid without pockets which collect dirt

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION 1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation

More information

SECTION INCLINE WHEELCHAIR LIFTS. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

SECTION INCLINE WHEELCHAIR LIFTS. Display hidden notes to specifier by using Tools / Options / View / Hidden Text. SECTION 14 42 13 INCLINE WHEELCHAIR LIFTS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Indoor inclined platform wheelchair lifts.

More information

About the Instructor & Presenter:

About the Instructor & Presenter: About the Instructor & Presenter: Paul G. Baillargeon, AHC, FDAI Vice President, Technical Consulting Door Security & Safety Foundation A noted veteran in the door and hardware industry, Mr. Baillargeon

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for detention furniture.

1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for detention furniture. SECTION 125500-WALL BED SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

SECTION XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

SECTION XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT. Display hidden notes to specifier by using Tools / Options / View / Hidden Text. SECTION 14 42 13 XPRESS II INCLINED WHEELCHAIR PLATFORM LIFT Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Indoor inclined platform

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

Linear Floor Heaters

Linear Floor Heaters Linear Floor Heaters The Price Linear Floor Heater family provides ultimate flexibility in terms of style, performance, and ease of installation. Using room-side heat virtually eliminates the requirement

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

A. Section Masonry Assemblies: Anchor placement in masonry.

A. Section Masonry Assemblies: Anchor placement in masonry. SECTION 14420 WHEEL CHAIR LIFT PART 1 - GENERAL 1.1 RELATED DOCUMENTS PART 1 GENERAL 1.1 SECTION INCLUDES A. Indoor inclined platform wheelchair lifts. 1.2 RELATED SECTIONS A. Section 04800 - Masonry Assemblies:

More information

SECTION NURSE CALL SYSTEM

SECTION NURSE CALL SYSTEM NURSE CALL SMARTCARE NURSE CALL SOLUTION Architectural Specifications Part 1 General SECTION 275223 - NURSE CALL SYSTEM 1.0 Summary 1.1 This section includes nurse call system and requirements for system

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

SOLID STATE SECURITIES, INC. THE SS90 SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL S S S S S S LISTED L * PATENT PENDING S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT U 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

2409/2900. Fire Guard

2409/2900. Fire Guard 2409/2900 Fire Guard Table of Contents Features and Additional Fire Opening Devices... 1 2409 Single-Point Hold Open Applications and Mounting Details... 2 2409 Track Assemblies, Arms and Components...

More information

15900 HVAC INSTRUMENTATION AND CONTROLS

15900 HVAC INSTRUMENTATION AND CONTROLS 15900 HVAC INSTRUMENTATION AND CONTROLS PART 1 GENERAL - Andover Controls BAS system is the standard for the University, and may be specified as a proprietary item. 1.0 RELATED DOCUMENTS A. Drawings and

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017 SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL S S S S S S S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED U 99Y9 RESET L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

SECTION ELEVATOR FIRE RATED SMOKE CONTAINMENT SYSTEM

SECTION ELEVATOR FIRE RATED SMOKE CONTAINMENT SYSTEM PART 1 - GENERAL 1.01 SUMMARY SECTION 08 34 84 ELEVATOR FIRE RATED SMOKE CONTAINMENT SYSTEM A. Section Includes: Fire protective elevator smoke containment curtain system designed to provide a tight-fitting,

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES SECTION 10 00 00 - SPECIALTIES 10 28 12 - TOILET PARTITIONS: Owner Preferences: Solid core phenolic, polymer based solid surfacing, and solid plastic toilet compartment and screen systems. No Stainless

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

Fire and Smoke Door Inspections Qualified Training 02/03/17

Fire and Smoke Door Inspections Qualified Training 02/03/17 Fire and Smoke Door Inspections Qualified Training 02/03/17 Basis of Requirements NFPA 101 requires annual fire and smoke door inspections (Section 18/19.2.2.2.1) Sections 18/19.2.2.1 require compliance

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

2408/2900. Fire Guard. SARGENT Manufacturing Company 2004, 2007 All rights reserved

2408/2900. Fire Guard. SARGENT Manufacturing Company 2004, 2007 All rights reserved Fire Guard SARGENT Manufacturing Company 2004, 2007 All rights reserved Fire Guard Table of Contents Features and Additional Fire Opening Devices............................1 2408 Single-Point Hold Open

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

EcoAisle Thermal Containment System

EcoAisle Thermal Containment System Guide Specifications EcoAisle Thermal Containment System THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) MASTERFORMAT. THIS SECTION MUST BE CAREFULLY

More information

B. Shop Drawings: Details of electrified door hardware, including wiring diagrams.

B. Shop Drawings: Details of electrified door hardware, including wiring diagrams. SECTION 087100 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Commercial door hardware for the following: a. Swinging doors. b. Other doors to the extent indicated. B. Related

More information

2408/2900. Fire Guard

2408/2900. Fire Guard 2408/2900 Fire Guard Table of Contents Features and Additional Fire Opening Devices... 1 2408 Single-Point Hold Open Applications and Mounting Details... 2 2408 Track Assemblies, Arms and Components...

More information

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL Firefly II Multi Voltage RELEASE DEVICES Firefly II & IIB-MV INSTALLATION MANUAL GENERAL DESCRIPTION: S/N The The Cookson Company Firefly II-MV time delay release devices are designed for use on rolling

More information

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-3 ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS Features: For use with doors or groups of doors that must interlock with each other to regulate control of accessing one area from another,

More information

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

SECTION DOOR HARDWARE

SECTION DOOR HARDWARE McClellan Blakemore Architects New Warehouse Facility for SECTION 08710 DOOR HARDWARE PART 1 GENERAL 1.01 SECTION INCLUDES A. Hardware for wood and hollow steel doors. B. Hardware for fire-rated doors.

More information

SECTION AIR DOORS

SECTION AIR DOORS SECTION 23 34 33 AIR DOORS Berner Series VSA air doors are designed for openings up to 12 ft for environmental separation and up to 10 ft for insect control. Berner Series VSB air doors are designed for

More information

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses PART 1 - GENERAL 1.1 SCOPE A. Through Class III Commodity Classification, up to 12.2m of single, double or multiple row rack storage, up to 14.6m building height (VanQuish Fire Sprinkler System). Cartoned

More information

A U TO S M O K E. Model AUTO SMOKE FIRE SHUT Flat Slats Fire Shut Rolling Doors

A U TO S M O K E. Model AUTO SMOKE FIRE SHUT Flat Slats Fire Shut Rolling Doors Model AUTO SMOKE Flat Slats Fire Shut Rolling Doors NOTE: For specifications, architects must choose from a variety of options. The standard choice will be shown first in plain text followed by the options

More information

1 P a g e w w w. s m o k e c o n t r o l. c o m. a u

1 P a g e w w w. s m o k e c o n t r o l. c o m. a u PROPRIETARY ITEM: FIBERHSIELD S AUTOMATIC OVERHEAD PERIMETER TYPE FABRIC FIRE CURTAIN This master specification should be read in conjunction with How to specify fire curtains technical guide to be published

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

Section Plaster Accessories

Section Plaster Accessories Section 09209 Plaster Accessories PART 1 - GENERAL 1.1 SUMMARY A. Related work specified elsewhere includes: 1. Rough carpentry. 2. Finish carpentry and millwork. 3. Metal support systems. 4. Furring and

More information

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5

More information

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL RELEASE DEVICES MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL The LiftMaster Fire Control (LM21-AFC) Release Device/Control Panel is UL/CUL listed normally energized fail-safe device incorporating

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

Fire Rated Door Assemblies: Compliant Designs

Fire Rated Door Assemblies: Compliant Designs Fire Rated Door Assemblies: Compliant Designs Steel Door Institute www.steeldoor.org AIA Provider #G389 Course #: SDIFIRE 1 HSW CE hour 1 Credit(s) earned on completion of this course will be reported

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint. (816) 373-4878 U1208-01/FAI29-029 (573) 751-2624 SECTION 2 105 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC PART 1 GENERAL 1.01 RELATED REQUIREMENTS SECTION 23 0913 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC A. Section 26 2717 - Equipment Wiring: Electrical characteristics and wiring connections. 1.02 ADMINISTRATIVE

More information

SECTION INTEGRATED DOOR ASSEMBLIES

SECTION INTEGRATED DOOR ASSEMBLIES SECTION 08 17 10 INTEG DOOR ASSEMBLIES SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Integrated

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information