1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M TO: FROM: Technical Committee on Road Tunnel and Highway Fire Protection Sarah Caldwell, Project Administrator DATE: January 6, 2016 SUBJECT: NFPA 502 SD TC Ballot Circulation (A2016) The receipt due date of January 4, 2016 for the NFPA 502 Second Draft ballot has passed. In accordance with the NFPA Regulations Governing the Development of NFPA Standards, the preliminary Second Draft ballot results are attached for your review. These results include explanation of negative votes, abstentions and votes with comments. 30 Members Eligible to Vote 4 Ballots Not Returned (Colella, Dalton, Debs, Fitzpatrick) If you wish to change your vote, the change must be received at NFPA prior to January 13, Members who did not return a ballot initially may do so now. Changes to ballot votes should be submitted through the NFPA Vote.net Ballot Site. The return of ballots is required by the Regulations Governing the Development of NFPA Standards. Revised 11/15
2 Results by Revision SR-1, Chapter 2, See SR-1 Affirmative 22 Affirmative with Comment 4 I agree with the specified NFPA Codes. SR-21, New Section after , See SR-21 Affirmative 22 Affirmative with Comment 4 I agree with the new definition. Page 1 of 17
3 SR-18, Section No , See SR-18 Affirmative 21 Affirmative with Comment 5 The factors listed are appropriate, however: the terma 'holistic mutidisciplinary' adds nothing to the clause and is not addressed through any of the listed factors; the form of item (1) is inconsistent with the remainder of the list; item (10) appears redundant to (9); item (18) should likely be included under item (3) in that traffic mix is speaking to the potential to cargo vehicle; traffic mix and volume (item 3) are separate issues. I agree wirh the list of items. Page 2 of 17
4 SR-7, Section No. 6.2 [Excluding any Sub-Sections], See SR-7 Affirmative 20 Affirmative with Comment 3 Negative 3 William G. Connell Proposed change adds confusion as to when this Chapter applies and is also creates a conflict with Paragraph While the intent of the proposed edits are reasonable, the wording is confusing and runs contrary to the subsequent clauses which defines fire/life safety requirements in terms of bridge or elevated highway length. I think that the the length is the most important factor. Page 3 of 17
5 SR-8, Section No , See SR-8 Affirmative 22 Affirmative with Comment 4 I agree with the term chapter. Page 4 of 17
6 SR-9, Section No , See SR-9 Affirmative 19 Affirmative with Comment 4 The revised arrangement is sensible; however, it is presumed that 'life safety' is still an objective in protecting the facility structure. Also, though not the subject of the proposed revision the mention of minimizing 'economic impact' extends beyond the stated scope of the standard. The intention and meaning of it are understood and absolutely shoudl be considered in facility design, but are broader context than should be directly addressed within the standard. This sort of consideration should be dealt with in normative text within the standard annexes, specifically in reference to section Negative 3 Ahmed Kashef one of the functional requirements should be "to maintain fire safety" William G. Connell I agree with the original definition. The undefined phrase "acceptable means" in is unenforceable and therefore inappropriate in the context of this paragraph. Page 5 of 17
7 SR-11, Section No , See SR-11 Affirmative 20 Affirmative with Comment 4 I agree with the new definition. Negative 2 William G. Connell The proposed revision to implies the possibility that a bridge or elevated highway collapse might NOT impact life saftey or have unacceptable implications. The proposed revision is incorrectly stated and introduces unenforcable language by use of the phrase "unacceptable implications" which is not defined. The proposed language in terms of using the selected design fire to define the timetemperature exposure does not have an agreed basis. Where there are limited test results that provide both transient temperature and heat release rate data, this may be done. Otherwise, analysis of the design conditions to determine the exposure conditions resulting from a particular design fire heat release rate history. Page 6 of 17
8 SR-6, Section No , See SR-6 Affirmative 21 Affirmative with Comment 3 Negative 2 Ahmed Kashef (c) should not include [assuming a minimum cover of 25 mm (1 in.)] "The material shall meet the fire protection requirements with less than 5 percent humidity by weight and also when fully saturated with water, in accordance with the approved time-temperature curve." no reason given for the 5 percent humidity requirement. I agree with original definition. Page 7 of 17
9 SR-19, New Section after A , See SR-19 Affirmative 20 Affirmative with Comment 5 Discussion of risk analysis is where it would be appropriate to discuss issues relating to operational continuity, down-time/repair time, repair costs, economic impact. It is within the risk context that fire safety provisions in excess of the minimum required for life safety would be identified as being necessary for satisfying economic objectives. Such discussion can be expanded upon in future revisions if deemed appropriate by the committee. Igor Y. Maevski Misleading standard language: "Risk analysis should be conducted as an adjunct to, and not a substitute for, qualified professional judgment". Negative 1 I do not agree with risk analysis. Page 8 of 17
10 SR-10, New Section after A.6.2.2, See SR-10 Affirmative 22 Affirmative with Comment 4 I agree with new definition. Page 9 of 17
11 SR-5, Section No. A.7.3.2, See SR-5 Affirmative 19 Affirmative with Comment 5 David M. Plotkin Last (1), "6 mm", not "6 m". The proposed text provides useful context and examples. However: (1) Are there only British or European standards concerning water ingress. If not, what are the appropriate or equivalent North American standards. (2)There is a typographical error in the last section: "The diameter should be limited to a maximum of 6 m (1?4 in.)..." The SI units should read as 6 mm. comment 1:...speed limits; amount of cycles to be determined... (the 's' behind cycles is now missing) comment 2:...limited to a maximum of 6 mm (1?4 in.) to reduce... (the second 'm' of 6 mm is now missing) Negative 2 Igor Y. Maevski I do not aree with the new definition. References to STUVA Guideline, British Standards and other nations' documents and specifications should be avoided. The standard should be developed as a stand alone document. Extraction the important language from other documents is acceptable with references to those documents. Terminology of emergency time/temperature certification is unclear. Page 10 of 17
12 SR-14, Section No. A , See SR-14 Affirmative 20 Affirmative with Comment 6 William G. Connell In para (4) the new reference CIE 193, Emergency Lighting in Road Tunnels, should be added to Chapter 2 References. The proposed language relating to 'wayfinding lighting' is helpful and useful, but appears out of place in the context of the subject matter of the leading paragraph of A Or rather, the leading paragraph covering travel speeds should more appropriately be incoroporated with A ; the wayfinding lighting discussion, pertaining to the egress pathway, belongs withi A I agree with the new definitions. Page 11 of 17
13 SR-20, Section No. B.2.6, See SR-20 Affirmative 19 Affirmative with Comment 3 I agree with the new definition. Negative 3 William G. Connell The maximum SIL level of 78dBLeq is extremely difficult and likely impossible to attain in road tunnels equipped with jet fans and/or fixed fire suppression systems both of which must be assumed active during an emergency. Although the revised text limits the prescriptive content of the proposed Annex and defers to NFPA 72 where appropriate, as written the language may still be interpreted to impose noise limitations within the tunnel that may not be practical in that environment. As written, the language implies that some level of noise limitations are required as there will either be uamplified or amplified communications. Audible or voice communication systems are not requirements under Chapter 7; as such the proposed language (while not statutory being in Annex B) imposes restrictions that are not aligned with trainway requirements. The efforts of the working group are recognized; it is preferrable that the work done to date is not lost. The issue can be addressed through inclusion of an additional sub-clause that identifies noise levels appropriate to trainways not utilizing audible communication systems (such as pain thresholds or similar). Igor Y. Maevski This eliminates the previously established minimum requirements (criteria) for noise levels and replaces it with the discussion on specific case of reliance upon unamplified speech. Page 12 of 17
14 Abstain 1 The proposed clause:"sound pressure level from all active systems measured inside a tunnel along the path of evacuation at any point 5 ft (1.52 m) above the walking surface speech intelligibility of fixed voice communication systems to achieve a measured speech transmission index (STI) of not less than 0.45 [0.65 common intelligibility scale (CIS)] and an average STI of not less than 0.5 (0.7 CIS) as per D in NFPA 72. Refer to Annex D of NFPA 72 for further information on speech intelligibility for voice communication systems." is not properly phrased because there is a disjoint between the SPL at the start of the proposed clause and the STI values mentioned. Page 13 of 17
15 SR-13, Section No. D.1, See SR-13 Affirmative 21 Affirmative with Comment 5 The research to date, as reviewed by the committee, supports the proposed changes. However, given the variation in K1 it is suggested that the form of the equation is incorrect in that K1 is not constant and has a functional relationship to heat release rate. As such, revisions to the form of equation D.1 should be explored by the committee working group for the next standard cycle. I agree with the new definition of critical control velocity. Page 14 of 17
16 SR-3, Sections E.5.7, E.5.8, E.5.9, See SR-3 Affirmative 21 Affirmative with Comment 5 The additional information provides useful summaries from which additional research reviews can be undertakan. To be useful references need to be provided, so it need sto be verified that the corresponding report titles are incorporated either in Annex E or in Annex M. The editors are advised that there are various typographical and grammatical errors within the second revision that should be addressed prior to publication. I agree with this comment. Page 15 of 17
17 SR-12, New Section after L.1, See SR-12 Affirmative 20 Affirmative with Comment 6 Haukur Ingason Change the ref in M7 Ingason, H. et al. Development of a test method for fire detection in road tunnels, SP Report, 13, SP Technical Research Institute of Sweden, to a better ref: H. Ingason, G. Appel, J. Gehandler, Y. Z. Li, H. Nyman, P. Karlsson, and M. Arvidson, Development of a test method for fire detection in road tunnels, Fire Technology, SP Report 2014:13, SP Technical Research Institute of Sweden. The proposed language pertaining to automatic fire detection within tunnels is useful and warrants inclusion within the standards. In future cycles, the committee should look to provide additional references as the current list is incomplete. Of particular interest would be ones discussing unwanted alarms (sources and mitigation)and relative performance of detection technologies. I agree with this comment. Page 16 of 17
18 SR-2, Chapter M, See SR-2 Affirmative 21 Affirmative with Comment 5 Haukur Ingason You can delete these ref. in N as they are also given later in N2 "Ingason, H. et al. Development of a test method for fire detection in road tunnels, SP Report, 13, SP Technical Research Institute of Sweden, Ingason H., G. Appel, and Y. Z. Li, Large Scale Fire Tests with Fixed Fire Fighting System in Runehamar Tunnel, SP Technical Research Institute of Sweden, 2014." N.1.2.8: - The address has changed into: Efectis Group, Brandpuntlaan Zuid 16, 2665 NZ, Bleiswijk, the Netherlands - A reference has forgotten. As agreed during the meeting in Dallas, there must be a reference to report Efectis-R0894(E), "Investigation of fire in the Lloydstraat car park, Rotterdam," N.2: Nieman, B., Cracking on the Unheated... (Nieman is written with single 'n' at the end; delete the last 'n') I agree with references. Page 17 of 17
MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities
More informationMEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and
More informationTECHNICAL COMMITTEE ON FIRE CODE
TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Building Service and
More informationM E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic
More informationMEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Portable Fire Extinguishers
More informationNational Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Residential Occupancies Kelly
More informationM E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Correlating Committee on Combustible Dusts Susan
More informationMEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fundamentals of Fire
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 2 FROM: Kimberly Shea, Administrator,
More informationNational Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Construction
More informationNFPA Technical Committee on Fire Tests
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Tracy
More informationSecond Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement
of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections
More informationNational Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Residential
More informationM E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The
More informationNational Fire Protection Association
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M (AMENDMENT) TO: FROM: Technical Committee on Mercantile
More informationMEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for
More information1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Pumps Patti
More informationChanges in NFPA
Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration
More informationMEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Correlating Committee on Signaling Systems for
More informationMEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fire Code (FCC-AAA) Gregory
More informationPublic Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification
Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the
More informationCommittee on NFPA 85
Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter
More informationFirst Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement
of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52
More informationM E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Supervising Station
More informationPublic Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input
of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August
More informationMEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 17 From: Kimberly Shea, Project Administrator
More informationMEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants
More informationM E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter
More informationFact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems:
Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems: Compatibility and connectivity assessment of system components Guide to BS EN 54-13:2017 Fire Detection and alarm systems: Compatibility
More informationThe Use of Public Address System to Improve Tunnel Safety - Current Practices. Lim Hock Tay
The Use of Public Address System to Improve Tunnel Safety - Current Practices Lim Hock Tay Content 1 Introduction 2 3 Overview of Survey Responses Discussion 4 Conclusion PIARC International Conference
More informationAustralian Standard. Degrees of protection provided by enclosures (IP Code) AS IEC Ed 2.1:2001 AS 60529
AS 60529 2004 IEC 60529 Ed 2.1:2001 AS 60529 Australian Standard Degrees of protection provided by enclosures (IP Code) This Australian Standard was prepared by Committee EL-026, Protective Enclosures
More informationTechnical Committee on Electrical Equipment Evaluation. ROC Meeting Agenda September 28-29, 2010 Providence, RI
Technical Committee on Electrical Equipment Evaluation ROC Meeting Agenda September 28-29, 2010 Providence, RI Item 10-09-1 Call to Order Item 10-09-2 Introductions Item 10-09-3 Staff Remarks Item 10-09-4
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Standpipes Elena
More informationCirculation Report for SIG-TMS Comments Document # 72
1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15
More informationCommittee on 51A M E M O R A N D U M. NFPA Technical Committee on Industrial and Medical Gases
Committee on 51A M E M O R A N D U M To: From: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant Date: June 14, 2010 Subject: NFPA 51A ROC Letter Ballot Circulation
More informationRequirements for ships carrying hydrogen and compressed natural gas vehicles
Lloyd's Register briefing IMO FP 55 Summary report for clients Overview The 55 th session of the IMO Fire Protection Sub Committee (FP) was held from 25 th to 29 th July 2011, at the IMO headquarters in
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Technical Committee on Testing and Maintenance
More informationPublic Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification
Public Comment No. 2-NFPA 73-2014 [ Section No. 4.1.3 ] 4.1.3 Unused Openings. 4.1.3.1 Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or
More informationM E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities
More information9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification
Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry
More informationThe Technical Committee on Commissioning and Integrated Testing
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: The Technical Committee on Commissioning and Integrated Testing
More informationQuestions/Comments for Richard Roux from Webinar on 7/11/13
Questions/Comments for Richard Roux from Webinar on 7/11/13 Below are the questions and comments from the July 11, 2013 webinar 2013 NFPA 72: Design and Installation Requirements for Mass Notification
More information2004 AUSTRALIAN STANDARDS UPDATE
2004 AUSTRALIAN STANDARDS UPDATE PREPARED by Peter Parsons Chairman of SAI FP-002 Chairman of ISO TC 21/SC 3 TSP Strategic Product Management Kjell Jawerth Chairman FPA Aust. TC/2 Member SAI FP-002 TSP
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations
More information9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification
of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked
More informationAddressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards
Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Wayne D. Moore, P.E., CFPS, SET Vice President JENSEN HUGHES 117 Metro Center Boulevard, Suite 1002
More informationThe Technical Committee on Fire Service Training
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: The Technical Committee on Fire Service Training Stacey Van
More informationPage 1 of 9 First Revision No. 2-NFPA 99B-2012 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard for Portable
More informationMEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Emergency Power Supplies Kelly
More informationStandards Council Meeting AGENDA. Hotel Mazarin 730 Bienville Street New Orleans, LA (504) April 10-11, 2018
Standards Council Meeting AGENDA Hotel Mazarin 730 Bienville Street New Orleans, LA 70130 (504) 581-7300 April 10-11, 2018 18-4-1 Act on the issuance of proposed Tentative Interim Amendment (TIA) to revise
More informationDiane D. Matthews, Administrator, Technical Projects. The September 19, 2013 date for receipt of the NFPA 5000 Second Draft Ballot has passed.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Fire Protection Features Diane D. Matthews,
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Technical Committee on Fundamentals of Fire
More informationProposed Changes to NFPA
2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture
More informationa guide to the interpretation of
a guide to the interpretation of EN50136-1-1 & EN50136-2-1 for alarm transmission systems & equipment June 2007 For other information please contact: British Security Industry Association t: 0845 389 3889
More informationAustralian Standard. Water mist fire protection systems System design, installation and commissioning AS
AS 4587 1999 Australian Standard Water mist fire protection systems System design, installation and commissioning This Australian Standard was prepared by Committee FP/12, Aqueous Fire Protection Systems.
More informationWhy Selective Coordination is Mandatory -- It Fills the Reliability Hole --
Why Selective Coordination is Mandatory -- It Fills the Reliability Hole -- The NEC has mandatory selective coordination requirements for the following systems. Emergency Systems- Article 700 700.27 Legally
More informationBritish Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety
Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 15 FROM: Kimberly Shea DATE:
More informationSecond Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM
1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,
More informationIMO WORK PROGRAMME. Central control stations and safety centres on passenger ships. Submitted by Argentina and ICCL
INTERNATIONAL MARITIME ORGANIZATION E IMO MARITIME SAFETY COMMITTEE 82nd session Agenda item 21 MSC 82/21/18 29 August 2006 Original: ENGLISH WORK PROGRAMME Central control stations and safety centres
More informationCommittee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM
1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:
More informationISO Submissions on Revised Working Draft (N 348)
ISO/TC 145/SC 2/WG 1 N 359 Date: 2006-05-29 Source: ISO/TC 145/SC 2/WG 1 Secretariat Project: ISO 23601 Status: 20.20 (WD study initiated) Requested action: for discussion at next WG 1 meeting Distribution:
More informationM E M O R A N D U M. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action.
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Marshal Professional Qualifications Stacey Van Zandt DATE: July 13, 2010 SUBJECT: NFPA 1037 ROP TC Letter Ballot (F2011) The ROP letter ballot
More informationTECHNICAL COMMITTEE ON FIRE PUMPS
TECHNICAL COMMITTEE ON FIRE PUMPS MEMORANDUM TO: FROM: Technical Committee on Fire Pumps Joanne Goyette, on behalf of C. Duffy / R. P. Benedetti DATE: May 2, 2011 SUBJECT: Letter Ballot on Proposals to
More informationDevelopments in Australian Standard AS (Emergency Lighting)
Developments in Australian Standard AS2293.2 (Emergency Lighting) Russell Porteous Chief Executive Officer, Firewize Australian Standards Committee LG-007 Disclaimer Firewize policy is one of continuous
More informationUNIFIED INTERPRETATION OF PROVISIONS OF IMO SAFETY, SECURITY, AND ENVIRONMENT-RELATED CONVENTIONS
E SUB-COMMITTEE ON SHIP SYSTEMS AND EQUIPMENT 5th session Agenda item 12 SSE 5/12/4 4 January 2018 Original: ENGLISH UNIFIED INTERPRETATION OF PROVISIONS OF IMO SAFETY, SECURITY, AND ENVIRONMENT-RELATED
More informationMEMORANDUM. NFPA Technical Correlating Committee on Building Code. NFPA 5000 TCC Report on Proposals Letter Ballot (A2011)
MEMORANDUM TO: FROM: NFPA Technical Correlating Committee on Building Code Robert Solomon DATE: April 1, 2010 SUBJ: NFPA 5000 TCC Report on Proposals Letter Ballot (A2011) In accordance with the NFPA Regulations
More informationNFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities
Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing
More informationFact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems
Fact File 75 Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems INTRODUCTION... 3 BACKGROUND...
More informationPublic Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item
Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method
More informationMEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Alternative Approaches to
More information26 of 128 9/23/2014 9:25 AM
26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke
More informationAlarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)
4 of 326 11/21/2013 1:03 PM First Revision No. 161-NFPA 72-2013 [ Section No. 3.3.11 ] 3.3.11 Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)
More informationDelayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.
9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical
More informationCorrelating Committee on Automatic Sprinkler Systems
Correlating Committee on Automatic Sprinkler Systems M E M O R A N D U M DATE: May 14, 2014 TO: FROM: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems Matt Klaus,
More informationPage 1 of 40 First Correlating Revision No. 15-NFPA 72-2014 [ Global Input ] 10.5.4 Plans Examiners and Inspectors. 10.5.4.1 Fire alarm system and emergency communications system plans and specifications
More informationSecond Revision No. 1-NFPA [ Chapter 2 ]
of 42 12/18/2015 2:53 PM Second Revision No. 1-NFPA 502-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within
More informationPREVIEW COPY. Table of Contents. Annexes and Supplemental Materials Lesson One Article 90: Introduction and Purpose... 3
Table of Contents Lesson One Article 90: Introduction and Purpose... 3 Lesson Two Articles 100 and 105: Terms and Definitions... 17 Lesson Three Article 110: General Requirements for Work Practices...
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Notification
More informationPage 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation
More informationISA 18.2 WG8. Purpose Definitions Status. By: Lieven Dubois, Co-chair
ISA 18.2 WG8 Purpose Definitions Status By: Lieven Dubois, Co-chair About the presenter Lieven Dubois Studied Electronic Engineering in Belgium In industrial automation since 1982 First Alarm Management
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60533 Second edition 1999-11 Electrical and electronic installations in ships Electromagnetic compatibility Installations électriques et électroniques à bord des navires Compatibilité
More informationChanges in IEC Ed 2
1 Introduction As known IEC 61511 is the applicable standard for functional safety in the process industry. Defining the requirements for the specification, design, installation, operation and maintenance
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60533 Second edition 1999-11 Electrical and electronic installations in ships Electromagnetic compatibility Installations électriques et électroniques à bord des navires Compatibilité
More information1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M
National Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Industrial and Medical Gases Joanne
More informationM EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)
M EM O RA N D UM TO: FROM: DATE: SUBJECT: Correlating Committee on Combustible Dusts Yiu Lee, Project Administrator January 27, 2017 NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)
More information1. Revise , from what was done by Second Revision SR-95 (Annual 2014 revision cycle NFPA 101 Second Draft), to read as follows:
NFPA 101 -Proposed 2015 Edition Life Safety Code TIA Log No. 1130 Reference: 12.4.1, 13.4.1, A.12.4.1, and A.13.4.1 Comment Closing Date: April 18, 2014 Submitter: Jeffrey Tubbs, Arup and Michael DiMascio,
More informationMEMORANDUM. Subject: NFPA 1124 Proposed Tentative Interim Amendment (TIA) No. 1094
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Pyrotechnics Elena Carroll,
More informationRe: AHRI Comments on Proposed Addendum be to ASHRAE Standard 189.1
January 31, 2013 Standing Standard Project Committee (SSPC) 189.1 Re: AHRI Comments on Proposed Addendum be to ASHRAE Standard 189.1 Dear Members of SSPC 189.1: These comments are submitted by the Air-Conditioning,
More informationMEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Protected Premises Fire Alarm
More informationWORKING DRAFT OF COMMITTEE MEETING OUTPUT
WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF SECOND DRAFT REPORT Document: NFPA 502 Revision Cycle: A2016 Meeting Date(s): October
More informationImplementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA -
TF N 687rev1 2015-06-02 CONSTRUCTION SECTOR STANDARDIZATION GUIDANCE DOCUMENT Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA - 1 I - Drafting
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Notification Appliances
More information