1 Technical Committee on Telecommunications Facilities () M E M O R A N D U M DATE: February 20, 2014 TO: Principal and Alternate Members of the Technical Committee on Telecommunications Facilities () FROM: Jon Hart, Fire Protection Engineer/NFPA Staff Liaison SUBJECT: AGENDA PACKAGE NFPA 76 Second Draft Meeting (F2015) Enclosed is the agenda for the NFPA 76 Second Draft meeting of the Technical Committee on Telecommunications Facilities, which will be held on Thursday, March 26, 2015 and Friday, March 27, 2015, at the Holiday Inn Houston Northwest Willowbrook, in Houston, TX. Please review the attached comments in advance, and if you have alternate suggestions, please come prepared with proposed language and respective substantiation. If you have any questions prior to the meeting, please do not hesitate to contact me at: Office: (617) jhart@nfpa.org For administrative questions, please contact Elena Carroll at (617) I look forward to working with everyone.
2 Technical Committee on Telecommunications Facilities () NFPA 76 Second Draft Meeting (Fall 2015) Thursday, March 26, 2015 through Friday, March 27, 2015 Holiday Inn Houston Northwest Willowbrook Tomball Parkway, Houston, TX AGENDA Wednesday March 25, 2015 HP Facility Tour Thursday, March 26 and Friday, March 27, Call to Order of NFPA 76 Second Draft Meeting 2. Chairman Comments 3. Introductions and Attendance 4. Approval of Previous Meeting Minutes 5. Staff Liaison Presentation 6. Preparation of the Second Draft Review Public Comments Create Second Revisions 7. New Business 8. Adjournment (By 12:00 pm on 3/27) Please submit requests for additional agenda items to the chair and staff liaison at least seven days prior to the meeting.
3 Technical Committee on Telecommunications Facilities () NFPA 76 Second Draft Meeting (Fall 2015) Thursday, March 26, 2015 through Friday, March 27, 2015 Holiday Inn Houston Northwest Willowbrook Tomball Parkway, Houston, TX Key Dates for the Fall 2015 Revision Cycle Public Input Closing Date January 3, 2014 Final Date for First Draft Meeting June 13, 2014 Posting of First Draft and Ballot August 1, 2014 Final First Draft Posted September 5, 2014 Public Comment Closing Date November 14, 2014 Final Date for Second Draft Meeting May 1, 2015 Posting of Second Draft and Ballot June 12, 2015 Final Second Draft Posted July 17, 2015 NITMAM Closing Date August 21, 2015 Issuance of Document with No NITMAM November 10, 2015 NFPA Annual Meeting (Las Vegas) June 2016 Issuance of Document with NITMAM August 4, 2016
4 Technical Committee on Telecommunications Facilities () NFPA 76 Second Draft Meeting (Fall 2015) Thursday, March 26, 2015 through Friday, March 27, 2015 Holiday Inn Houston Northwest Willowbrook Tomball Parkway, Houston, TX Note from the Staff Liaison Dear Technical Committee Members: We are very pleased that you will be participating in the processing of the 2016 Edition of NFPA 76, Standard for the Fire Protection of Telecommunications Facilities. Development of this document would not be possible without the participation of volunteers like you. Meeting Preparation Committee members should review the published Public Comments prior to the meeting and to be prepared to act on each item. Handout materials should be submitted to the chair and staff liaison at least seven days prior to the meeting. Only one posting of the Public Comments will be made; it will be arranged in section/order and will be pre-numbered. This will be posted to the NFPA 76 Document Information page ( under the Next Edition tab. If you have trouble accessing the website please contact Elena Carroll at Mandatory Materials: Last edition of the standard Meeting agenda Public Comments Committee Officers' Guide (Chairs) Roberts Rules of Order (Chairs; An abbreviated version may be found in the Committee Officer s Guide) Optional Materials: NFPA Annual Directory NFPA Manual of Style
5 Technical Committee on Telecommunications Facilities () NFPA 76 Second Draft Meeting (Fall 2015) Thursday, March 26, 2015 through Friday, March 27, 2015 Holiday Inn Houston Northwest Willowbrook Tomball Parkway, Houston, TX Regulations and Guiding Documents All committee members are expected to behave in accordance with the Guide for the Conduct of Participants in the NFPA Codes and Standards Development Process. All actions during and following the committee meetings will be governed in accordance with the NFPA Regulations Governing the Development of NFPA Standards. Failure to comply with these regulations could result in challenges to the standards-making process. A successful challenge on procedural grounds could prevent or delay publication of the document. The style of the document must comply with the Manual of Style for NFPA Technical Committee Documents.
6 Technical Committee on Telecommunications Facilities () NFPA 76 Second Draft Meeting (Fall 2015) Thursday, March 26, 2015 through Friday, March 27, 2015 Holiday Inn Houston Northwest Willowbrook Tomball Parkway, Houston, TX General Procedures for Meetings Use of tape recorders or other means capable of producing verbatim transcriptions of any NFPA Committee Meeting is not permitted. Attendance at all NFPA Committee Meetings is open. All guests must sign in and identify their affiliation. Participation in NFPA Committee Meetings is generally limited to committee members and NFPA staff. Participation by guests is limited to individuals, who have received prior approval from the chair to address the committee on a particular item, or who wish to speak regarding public proposals or comments that they submitted. The chairman reserves the right to limit the amount of time available for any presentation. No interviews will be allowed in the meeting room at any time, including breaks. All attendees are reminded that formal votes of committee members will be secured by letter ballot. Voting at this meeting is used to establish a sense of agreement, but only the results of the formal letter ballot will determine the official action of the committee. Note to Special Experts: Particular attention is called to Section 3.3(e) of the NFPA Guide for the Conduct of Participants in the NFPA Codes and Standards Development Process in the NFPA Directory. This section requires committee members to declare any interest they may represent, other than their official designation as shown on the committee roster. This typically occurs when a special expert is retained by and represents another interest category on a particular subject. If such a situation exists on a specific issue or issues, the committee member shall declare those interests to the committee and refrain from voting on any action relating to those issues. Smoking is not permitted at NFPA Committee Meetings.
7 Technical Committee Roster
8 Address List No Phone Telecommunications 02/17/2015 Jonathan Hart Steve C. Dryden Chair AMEC 2677 Buford Highway Atlanta, GA SE 7/16/2003 Robert G. Backstrom Principal UL LLC 333 Pfingsten Road Northbrook, IL RT 1/15/1999 Leonard Belliveau, Jr. Principal JENSEN HUGHES 117 Metro Center Blvd., Suite 1002 Warwick, RI SE 1/15/1999 Jeffrey A. Betz Principal AT&T Corporation CRE National Standards-Fire Protection 7 Stoney Hill Road PO Box 109 Brookside, NJ U 1/17/1997 Michael J. Bosma Principal The Viking Corporation 210 North Industrial Park Road Hastings, MI National Fire Sprinkler Association Alternate: Jon R. Ackley Voting Alt. to NFSA Rep. M 1/18/2001 Richard L. P. Custer Principal Arup Fire 955 Massachusetts Avenue, Suite 402 Cambridge, MA SE 1/17/1997 Mickey L. Driggers Principal CenturyLink 700 West Mineral Avenue, UT E28.36 Denver, CO Alternate: Edward G. Bond U 7/16/2003 Ronald A. Durgin Principal Mohave County Development Services 3250 East Kino Avenue PO Box 7000 Kingman, AZ E 07/29/2013 Robert P. Gardner Principal Marsh Risk Consulting PO Box Kansas City, MO I 7/23/2008 Kirk W. Humbrecht Principal Phoenix Fire Systems, Inc. 744 West Nebraska Street Frankfort, IL Fire Suppression Systems Association Alternate: Paul R. Nelson IM 10/1/1999 Jonathan G. Ingram Principal UTC/Kidde-Fenwal, Inc. 400 Main Street Ashland, MA M 10/28/2008 Stanley Kaufman Principal CableSafe, Inc./OFS PO Box Atlanta, GA Society of the Plastics Industry, Inc. M 3/21/2006 1
9 Address List No Phone Telecommunications 02/17/2015 Jonathan Hart Scott R. Lang M 10/28/2008 Principal Honeywell International System Sensor Division 3825 Ohio Avenue St. Charles, IL National Electrical Manufacturers Association Alternate: Luis A. Barros Chad Mariska Principal APS Fire 400 North Walnut Street Broken Arrow, OK National Association of Fire Equipment Distributors Alternate: William D. Johnson IM 08/11/2014 Randall R. McCarver Principal Telcordia Technologies (Ericsson) 444 Hoes Lane, 4D-660 Piscataway, NJ U 07/29/2013 Jack McNamara Principal Bosch Security Systems 130 Perinton Parkway Fairport, NY Automatic Fire Alarm Association, Inc. Alternate: A. M. Fred Leber M 03/07/2013 William Meyring Principal 3M Company 3M Center Building B-7 Saint Paul, MN Alternate: Mark W. Lund M 03/07/2013 Thomas F. Norton Principal Norel Service Company, Inc. 37 Buckmaster Drive Concord, MA IM 4/3/2003 Daniel J. O'Connor Principal Aon Fire Protection Engineering 4 Overlook Point Lincolnshire, IL Alternate: Ronald A. Stein I 1/17/1997 Ronald D. Ouimette Principal Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, NJ Alternate: Daniel P. Finnegan M 10/10/1998 Brad Pradel Principal Liberty Mutual National Accounts Property 2100 Walnut Hill Lane, Suite 100 Irving, TX Alternate: Shaun A. Brasseau I 3/4/2008 Charles A. Quillin Principal HSB Professional Loss Control 1616 Catron Road Union City, TN Alternate: Darrell M. Franchuk I 4/14/2005 Rodger Reiswig Principal Tyco/SimplexGrinnell 3640 Haddington Court Apopka, FL Tyco Fire Suppression & Building Products M 7/26/2007 Buddy Rice Principal Deer Park Fire Marshals Office 2211 East X Street Deer Park, TX E 10/29/2012 2
10 Address List No Phone Telecommunications 02/17/2015 Jonathan Hart Thomas F. Ziegler Principal Verizon One Verizon Way, 3rd Floor Mail Code: VC53S451 Basking Ridge, NJ U 10/3/2002 Robert Kasiski Voting Alternate FM Global 1151 Boston Providence Turnpike PO Box 9102 Norwood, MA Voting Alt. to FM Rep. I 8/9/2011 Jon R. Ackley Alternate Dalmatian Fire, Inc West 73rd Street Indianapolis, IN National Fire Sprinkler Association Principal: Michael J. Bosma M 8/2/2010 Luis A. Barros Alternate Honeywell/System Sensor 3825 Ohio Avenue St. Charles, IL National Electrical Manufacturers Association Principal: Scott R. Lang M 03/03/2014 Edward G. Bond Alternate Centurylink Capital Blvd., NCWKFR0321 Wake Forest, NC Principal: Mickey L. Driggers U 03/03/2014 Shaun A. Brasseau Alternate Liberty Mutual Property 1009 Collegeville Road Collegeville, PA Principal: Brad Pradel I 03/03/2014 Daniel P. Finnegan Alternate Siemens Industry, Inc. Building Technologies Division Fire & Security 2953 Exeter Court West Dundee, IL Principal: Ronald D. Ouimette M 3/4/2009 Darrell M. Franchuk Alternate HSB Professional Loss Control NW 88th Ave Road Reddick, FL Principal: Charles A. Quillin I 3/1/2011 William D. Johnson IM 08/11/2014 Alternate Mid State Fire Equipment Inc. 297 Washington Blvd. NE Lake Placid, FL National Association of Fire Equipment Distributors Principal: Chad Mariska A. M. Fred Leber Alternate LRI Fire Protection Engineering, Inc. Yonge Eglinton Center 2300 Yonge Street, Suite 2100 PO Box 2372 Toronto, ON M4P 1E4 Automatic Fire Alarm Association, Inc. Principal: Jack McNamara M 07/29/2013 Mark W. Lund Alternate 3M Company 3M Center, Building 223-2N-20 St. Paul, MN Principal: William Meyring M 10/28/2008 Paul R. Nelson Alternate Orr Protection Systems, Inc Interchange Drive Louisville, KY Fire Suppression Systems Association Principal: Kirk W. Humbrecht IM 8/2/2010 3
11 Address List No Phone Telecommunications 02/17/2015 Jonathan Hart Ronald A. Stein Alternate Aon Global Risk Consultants 4801 Main Street, Suite 350 Kansas City, MO Principal: Daniel J. O'Connor I 1/1/1997 Thomas G. Cleary Nonvoting Member National Institute of Standards & Technology 100 Bureau Drive, Stop 8664 Gaithersburg, MD RT 1/15/1999 Shmuel Netanel Nonvoting Member Eidan Safety Engineers Group 11 Moshe Levi St. Rishon Le Zion, Israel SE 1/17/1997 Jonathan Hart Staff Liaison National Fire Protection Association 1 Batterymarch Park Quincy, MA /25/2011 4
12 Technical Committee Distribution
13 Distribution by % Telecommunications Name Company Representation Class Office Ronald A. Durgin Mohave County Development E Principal Services Buddy Rice Deer Park Fire Marshals Office E Principal Voting Number 2 Percent 8% Robert P. Gardner Marsh Risk Consulting MARSH I Principal Daniel J. O'Connor Aon Fire Protection Engineering AON I Principal 02/17/2015 Brad Pradel Liberty Mutual National Accounts Property I Principal Charles A. Quillin HSB Professional Loss Control I Principal Robert Kasiski FM Global FM I Voting Alternate Voting Number 5 Percent 19% Kirk W. Humbrecht Phoenix Fire Systems, Inc. FSSA IM Principal Chad Mariska APS Fire NAFED IM Principal Thomas F. Norton Norel Service Company, Inc. IM Principal Voting Number 3 Percent 12% Michael J. Bosma The Viking Corporation NFSA M Principal Jonathan G. Ingram UTC/Kidde-Fenwal, Inc. UTC M Principal Stanley Kaufman CableSafe, Inc./OFS SPI M Principal Scott R. Lang Honeywell International NEMA M Principal Jack McNamara Bosch Security Systems AFAA M Principal William Meyring 3M Company M Principal Ronald D. Ouimette Siemens Building Technologies, Inc. M Principal Rodger Reiswig Tyco/SimplexGrinnell TYCO M Principal Voting Number 8 Percent 31% Robert G. Backstrom UL LLC UL RT Principal Voting Number 1 Percent 4% Steve C. Dryden AMEC SE Chair Leonard Belliveau, Jr. JENSEN HUGHES SE Principal
14 Distribution by % Telecommunications Tuesday 2 17, Tuesday Name Company Representation Class Office Richard L. P. Custer Arup Fire SE Principal Voting Number 3 Percent 12% Jeffrey A. Betz AT&T Corporation U Principal Mickey L. Driggers CenturyLink U Principal Randall R. McCarver Telcordia Technologies (Ericsson) U Principal Thomas F. Ziegler Verizon U Principal Voting Number 4 Percent 15% Total Voting Number 26
15 Previous Meeting Minutes
16 MINUTES NFPA Technical Committee on Telecommunications () April 22-24, 2014 First Draft Meeting Holiday Inn, Inner Harbor Baltimore, MD 1. Call to Order. The meeting was called to order at 1:30 pm (Eastern) on Tuesday, April 22, 2014 by Committee Chair, Steve Dryden. 2. Attendance and Introductions: Attendance was taken and those present at the meeting introduced themselves and stated who they represent on the committee. Those who were present at the meeting are listed below:
17 3. Chairman Comments: Steve Dryden spoke to the agenda for the meeting and provided opening comments. 4. Minutes Approval: The minutes of the April 11-13, 2011 ROC Meeting in Dallas, TX were approved as distributed in the Agenda Package. 5. Staff Liaison Presentation: Barry Chase gave the staff presentation for the meeting which included general meeting procedures and a review of the Fall 2015 revision cycle. 6. Development of First Draft: The committee reviewed all public input (PI) and resolved them by either providing a committee statement or by creating a first revision (FR) based on the PC. Other First Revisions were created. See the First Draft and First Draft report for the official committee actions. These will be available at 7. New Business: Task Groups: -A Task Group was formed to look at referenced documents within NFPA 76. Chair: R. McCarver. Members: J. Betz and B. Rice. -A Task Group on SUS, small unoccupied spaces, was be formed. Chair: R. Stein. Members: M. Driggers and J. Betz 8. Next Meeting: The next meeting of the TC will be the second draft meeting in the F2015 cycle and will likely take place in the February/March time frame in The committee preference is to hold this meeting in a location in the South of the U.S. 9. Meeting Adjourned: The meeting was adjourned at 2:00 pm on April 24, 2014.
18 Public Comments
19 1 of 35 1/12/2015 3:00 PM Public Comment No. 2-NFPA [ Section No ] ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2013 Rev A ASTM E814, Standard Test Method for Fire Tests of Penetration Firestop Systems, 2013 Rev A 2013a. ASTM E1537, Standard Test Method for Fire Testing of Upholstered Furniture, ASTM E1966, Standard Test Method for Fire Resistive Joint Systems, 2007 ( 2011). Statement of Problem and Substantiation for Public Comment date updates Related Item Public Input No. 1-NFPA [Section No ] Submitter Information Verification Submitter Full Name: Marcelo Hirschler Organization: GBH International Street Address: City: State: Zip: Submittal Date: Thu Sep 18 18:59:24 EDT 2014
20 2 of 35 1/12/2015 3:00 PM Public Comment No. 4-NFPA [ Section No ] Cable Telecommunications. One- and two-way communications service provided over a network, generally through optical fiber -optic and coaxial cable. Statement of Problem and Substantiation for Public Comment This editorial change correlates with National Electrical Code Article 770 which refers to optical fiber cables, not fiber-optic cables. Related Item First Revision No. 37-NFPA [Section No ] Submitter Information Verification Submitter Full Name: Stanley Kaufman Organization: CableSafe, Inc./OFS Affilliation: SPI Street Address: City: State: Zip: Submittal Date: Fri Oct 10 02:32:19 EDT 2014
21 3 of 35 1/12/2015 3:00 PM Public Comment No. 21-NFPA [ Section No. 8.8 ] 8.8 Telecommunications Equipment Ignition and Fire Resistance Performance * General. Where needed to achieve an objective of a performance-based design permitted by Chapter 5 or to meet the prescriptive requirements permitted by Chapters 6 and 7, the telecommunications equipment, cables, wiring, and associated components shall comply with the provisions of Section Wire and Cables Telecommunications cables shall be listed to the requirements of ANSI/UL Telecommunications wires shall be listed to the requirements for cross-connect wire in ANSI/UL Optical fiber cables shall be listed to the requirements of ANSI/UL Wires and cables intended for powering signal-processing equipment and insulated ground wires shall be listed to the requirements of ANSI/UL 1277, ANSI/UL 44, or ANSI/UL 83 or shall be specifically listed for the purpose Communications raceways shall be listed to the requirements of ANSI/UL Cable routing assemblies shall be listed to the requirements of UL Nonmetallic cable trays shall be listed to the requirements of ANSI/UL Raised Floor and Ceiling Cavity Plenums Wires and cables intended for powering signal-processing equipment, telecommunications cables, optical fiber cables, and insulated ground wires installed in plenums shall be listed as having a maximum flame spread of 1.52 m (5.0 ft), a maximum peak optical density of 0.50, and a maximum average optical density of when tested in accordance with NFPA 262 or Flame and Smoke Test in the Appendix to CSA C22.2 No. 0.3-M-1996 (FT6 Rating) Communications raceways installed in plenums shall be listed as having a maximum flame spread of 1.52 m (5.0 ft), a maximum peak optical density of 0.50, and a maximum average optical density of when tested per ANSI/UL 2024 or the flame and smoke test in CSA C22.2 No. 0.3, Appendix B (FT6 Rating) Cable routing assemblies shall be listed to the requirements of UL 2024.
22 * Nonmetallic cable trays used in plenums shall be listed for use in plenums Risers Telecommunications cables, optical fiber cables, wires and cables intended for powering signal-processing equipment, insulated ground wires, communications raceways, and nonmetallic cable trays installed vertically between floors in a building shall comply with ANSI/UL These cables shall demonstrate limited smoke generation by testing in accordance with ANSI/UL Telecommunications cables, optical fiber cables, wires and cables intended for powering signal-processing equipment, and insulated ground wires meeting the requirements of shall be permitted Communications raceways meeting the requirements of shall be permitted Cable routing assemblies meeting the requirements of shall be permitted Cable routing assemblies shall be listed to the requirements of UL Cable routing assemblies meeting the requirements of shall be permitted Installations Other Than Risers and Plenums. Installations of telecommunications wires and cables, optical fiber cables, wires and cables intended for powering signal-processing equipment, and insulated ground wires in spaces other than risers or plenums shall comply with or or Telecommunications wires and cables, optical fiber cables, wires and cables intended for powering signal-processing equipment, and insulated ground wires shall be listed as not spreading fire to the top of the tray and shall demonstrate limited smoke generation in the vertical-tray flame test in ANSI/UL Telecommunications wires and cables, optical fiber cables, wires and cables intended for powering signal-processing equipment, and insulated ground wires shall be listed as meeting the requirements of the FT-4 test in CSA Vertical Flame Test Cables in Cable Trays in the Test Methods for Electrical Wires and Cables, C22.2 No. 0.3-M-1996, with char length not to exceed 1.5 m (4 ft 11 in.). These cables shall demonstrate limited smoke generation by testing in accordance with ANSI/UL Telecommunications cables, optical fiber cables, wires and cables intended for powering signal-processing equipment, and insulated ground wires meeting the requirements of or shall be permitted Communications raceways shall not spread fire to the top of the tray in the vertical-tray flame test in ANSI/UL Cable routing assemblies shall be listed to the requirements of UL Cable routing assemblies and communications raceways meeting the requirements of or shall be permitted. 4 of 35 1/12/2015 3:00 PM
23 5 of 35 1/12/2015 3:00 PM Cable routing assemblies meeting the requirements of or shall be permitted * Major Telecommunications Equipment Systems. Major telecommunications equipment shall be classified as follows: (1) Level A. Equipment that meets the fire resistance criteria specified in Telcordia GR-63-CORE, following the methodologies specified in ATIS and ATIS (2) Level B. Equipment that meets the requirements of UL only, and does not qualify for Level A classification (3) Level C. Equipment that does not meet the requirements of either Level A or Level B Nonlabeled Wire, Cable, and Telecommunications Equipment. Where wire, cable, and telecommunications equipment are not labeled to indicate compliance with the requirements of Section 8.8, the documentation regarding compliance with the fire resistance criteria specified in Section 8.8 shall be readily available. Statement of Problem and Substantiation for Public Comment Fire resistance is defined as a property assessing the ability of a material, product, or assembly to withstand fire or give protection from it for a period of time. This chapter addresses fire performance requirements. Related Public Comments for This Document Related Comment Public Comment No. 22-NFPA [Section No. A.8.8.3] Related Item First Revision No. 20-NFPA [Section No ] Relationship Submitter Information Verification Submitter Full Name: Marcelo Hirschler Organization: GBH International Street Address: City: State: Zip: Submittal Date: Fri Nov 14 14:19:13 EST 2014
24 6 of 35 1/12/2015 3:00 PM Public Comment No. 17-NFPA [ Section No ] Wires and cables intended for powering signal-processing equipment, telecommunications cables, optical fiber cables, and insulated ground wires installed in plenums shall be listed as having a maximum flame spread of m (5.0 ft) or less, a maximum peak optical density of 0.50 or less, and a maximum average optical density of or less when tested in accordance with NFPA 262 or Flame and Smoke Test in the Appendix to CSA C22.2 No. 0.3-M-1996 (FT6 Rating). Statement of Problem and Substantiation for Public Comment This public comment does not extract language from NFPA 90A but simply makes the requirements identical. Note that CSA FT6 is not referenced in NFPA 90A because it has not kept up with the advances incorporated into NFPA 90A. Standards Council has stated that NFPA 90A has jurisdiction over the requirements for materials in plenums. This public comment does not incorporate any material or products that are not already referenced in NFPA 76. Related Item Public Input No. 3-NFPA [Section No ] Public Input No. 5-NFPA [Section No ] Submitter Information Verification Submitter Full Name: Marcelo Hirschler Organization: GBH International Street Address: City: State: Zip: Submittal Date: Fri Nov 14 13:45:25 EST 2014
25 7 of 35 1/12/2015 3:00 PM Public Comment No. 18-NFPA [ Section No ] Communications raceways installed in plenums shall be listed as having a maximum flame spread of m (5.0 ft) or less, a maximum peak optical density of 0.50 or less, and a maximum average optical density of or less when tested per in accordance with ANSI/UL 2024 or the flame and smoke test in CSA C22.2 No. 0.3, Appendix B (FT6 Rating). Statement of Problem and Substantiation for Public Comment This public comment simply slightly revises the requirements by incorporating language that corresponds to the language from NFPA 90A, which has jurisdiction over materials in plenums, in accordance with Standards Council. The reference to the CSA standard is being removed because it has not kept up to date with the changes in NFPA standards. Related Item Public Input No. 3-NFPA [Section No ] Public Input No. 5-NFPA [Section No ] Submitter Information Verification Submitter Full Name: Marcelo Hirschler Organization: GBH International Street Address: City: State: Zip: Submittal Date: Fri Nov 14 13:51:12 EST 2014
26 Public Comment No. 16-NFPA [ Section No ] Cable routing assemblies shall be listed to the requirements of UL Statement of Problem and Substantiation for Public Comment Both the NEC and NFPA 90A (which has jurisdiction over materials in plenums) do not allow cable routing assemblies to be used in plenums unless tested by the default criteria. Cable routing assemblies can be used in trays and risers but not in plenums unless tested as any other material in a plenum. UL 2024 uses a less severe fire test that ASTM E84 (25/50), the default test, and NFPA 90A has rejected its use for cable routing assemblies. I am a committee member of NFPA 90A. This public comment introduces the requirements from NFPA 90A for materials in plenums. The requirements for noncombustible or low flame spread and smoke based on testing to ASTM E84 are those that apply to all materials and products not otherwise mentioned with specific requirements. An alternate public comment adds the specific requirements for all default materials (including cable routing assemblies) in plenums, per NFPA 90A. Related Public Comments for This Document Related Comment Public Comment No. 20-NFPA [Section No ] Related Item Public Input No. 3-NFPA [Section No ] Public Input No. 5-NFPA [Section No ] Relationship Submitter Information Verification Submitter Full Name: Marcelo Hirschler Organization: GBH International Street Address: City: State: Zip: Submittal Date: Fri Nov 14 13:41:43 EST of 35 1/12/2015 3:00 PM
27 9 of 35 1/12/2015 3:00 PM Public Comment No. 20-NFPA [ Section No ] Cable routing assemblies shall be listed for use in plenums and shall be constructed of materials that are either noncombustible or that exhibit a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or with ANSI/UL 723, Standard Test Method for Surface Burning Characteristics of Building Materials. Also, update the references to the requirements of UL ASTM E84 (2014) and to ANSI/UL 723 (2008, revised 2013) within the sections in Chapter 2 on ASTM and UL referenced standards.. Statement of Problem and Substantiation for Public Comment Both the NEC and NFPA 90A (which has jurisdiction over materials in plenums) do not allow cable routing assemblies to be used in plenums unless tested by the default criteria. Cable routing assemblies can be used in trays and risers but not in plenums unless tested as any other material in a plenum. UL 2024 uses a less severe fire test that ASTM E84 (25/50), the default test, and NFPA 90A has rejected its use for cable routing assemblies. I am a committee member of NFPA 90A. This public comment introduces the requirements from NFPA 90A for materials in plenums. The requirements for noncombustible or low flame spread and smoke based on testing to ASTM E84 are those that apply to all materials and products not otherwise mentioned with specific requirements. Related Public Comments for This Document Related Comment Public Comment No. 16-NFPA [Section No ] Public Comment No. 19-NFPA [Section No ] Related Item Public Input No. 3-NFPA [Section No ] Public Input No. 5-NFPA [Section No ] Relationship Submitter Information Verification Submitter Full Name: Marcelo Hirschler Organization: GBH International Street Address:
28 10 of 35 1/12/2015 3:00 PM City: State: Zip: Submittal Date: Fri Nov 14 14:10:37 EST 2014
29 11 of 35 1/12/2015 3:00 PM Public Comment No. 19-NFPA [ Section No ] * Nonmetallic cable trays used in plenums shall be listed for use in plenums and shall be constructed of materials that are either noncombustible or that exhibit a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or with ANSI/UL 723, Standard Test Method for Surface Burning Characteristics of Building Materials. Also, update the references to ASTM E84 (2014) and to ANSI/UL 723 (2008, revised 2013) within the sections in Chapter 2 on ASTM and UL refernced standards. Statement of Problem and Substantiation for Public Comment This introduces the requirements from NFPA 90A for materials in plenums. The requirements for noncombustible or low flame spread and smoke based on testing to ASTM E84 are those that apply to all materials and products not otherwise mentioned with specific requirements. Related Public Comments for This Document Related Comment Public Comment No. 20-NFPA [Section No ] Related Item Public Input No. 3-NFPA [Section No ] Public Input No. 5-NFPA [Section No ] Relationship Submitter Information Verification Submitter Full Name: Marcelo Hirschler Organization: GBH International Street Address: City: State: Zip: Submittal Date: Fri Nov 14 13:56:47 EST 2014
30 12 of 35 1/12/2015 3:00 PM Public Comment No. 5-NFPA [ Section No ] * Removal or Storage of Combustibles. Combustibles shall not be removed from stored in telecommunications equipment areas or shall be stored appropriately areas except in protected storage rooms, noncombustible enclosed storage cabinets or bins, noncombustible covered refuse containers, or listed self-extinguishing-type trash receptacles. Statement of Problem and Substantiation for Public Comment The Technical Committee clarified that the removal of combustibles was addressing telecommunications equipment areas, but they deleted the frequency of removal, which was confusing. We believe the Technical Committee intends that combustibles not be stored in these areas. This revision clarifies the provision and gets to the heart of the matter. Related Item First Revision No. 35-NFPA [Section No ] Submitter Information Verification Submitter Full Name: Jim Muir Organization: Clark County, Washington, Building Safety Division Affilliation: NFPA's Building Code Development Committee (BCDC) Street Address: City: State: Zip: Submittal Date: Fri Oct 31 11:29:38 EDT 2014
31 13 of 35 1/12/2015 3:00 PM Public Comment No. 7-NFPA [ Section No ] 9.1.4* Heat-Producing Appliances. The use of portable heat-producing appliances shall not be located permitted in any telecommunications equipment area, computer room, individual office areas, individual office cubicles, storage areas, or shipping areas. Statement of Problem and Substantiation for Public Comment Computer rooms, individual office areas, individual office cubicles, storage areas, or shipping areas are not unique to telecommunications facilities. This Standard should only address fire hazards unique to the telecommunications equipment occupancy. More general hazards are already addressed in other NFPA standards. Requirements regarding heat producing appliances in other areas belong in NFPA , which provides general fire protection requirements. There are unintended restrictions in which exceed the requirements of NFPA 1 for no discernible reason in telecommunications equipment areas. An example of an unintended restriction is a heat-producing tool such as a soldering iron or heat shrink device. Related Item Public Input No. 76-NFPA [Section No ] Submitter Information Verification Submitter Full Name: Randall McCarver Organization: Telcordia (Ericsson) Affilliation: AT&T, CenturyLink Street Address: City: State: Zip: Submittal Date: Tue Nov 11 15:14:54 EST 2014
32 14 of 35 1/12/2015 3:00 PM Public Comment No. 6-NFPA [ Section No ] Flexible electrical cords shall be adequate to carry the anticipated current amperage and shall be listed. Statement of Problem and Substantiation for Public Comment The term amperage is defined per section 3.1 as the ordinarily accepted meaning. There is no confusion with the original term. Related Item First Revision No. 39-NFPA [Section No ] Submitter Information Verification Submitter Full Name: Jim Muir Organization: Clark County, Washington, Building Safety Division Affilliation: NFPA's Building Code Development Committee (BCDC) Street Address: City: State: Zip: Submittal Date: Fri Oct 31 11:35:41 EDT 2014
33 15 of 35 1/12/2015 3:00 PM Public Comment No. 8-NFPA [ Section No [Excluding any Sub-Sections] ] The delivery, storage, construction, and cleanup associated with building construction and alteration work shall be performed in accordance with NFPA 241 or an equivalent standard. Statement of Problem and Substantiation for Public Comment First revision No. 41 allows for the use of an equivalent standard to NFPA 241 in Section 9.4. The same language should appear in also. The annex text already provides some additional standards that may be referenced. Related Item Public Input No. 83-NFPA [Section No ] First Revision No. 41-NFPA [Section No. 9.4 [Excluding any Sub-Sections]] Submitter Information Verification Submitter Full Name: Randall McCarver Organization: Telcordia (Ericsson) Affilliation: AT&T, CenturyLink, Verizon Street Address: City: State: Zip: Submittal Date: Tue Nov 11 15:22:31 EST 2014
34 Public Comment No. 9-NFPA [ Section No. 9.6 ] 9.6 * Physical Security A key box(es), where required by the authority having jurisdiction, shall be listed and installed in an accessible location The operator of the premises shall immediately notify the authority having jurisdiction and provide the new key(s) when a lock shall be changed or re-keyed, and a key(s) to that lock shall be contained in the key box. Statement of Problem and Substantiation for Public Comment Key boxes are not unique to telecommunications facilities. The requirements in NFPA 1 specifically address the use of key boxes in more detail than do those in Section 9.6. NFPA 76 should only address fire hazards unique to the telecommunications equipment occupancy. More general hazards are already addressed in other NFPA standards. NFPA 1 is the fundamental document that provides general fire protection requirements. It is the definitive standard and should be the only one that contains general requirements. Repeating requirements already in NFPA 1 leads to confusion and conflicting enforcement when requirements of one document diverge from the other, which occurs because they are not on the same revision cycle. NFPA 76 was a stand-alone document that is now a Standard referenced in NFPA 1, the primary governing document for general fire prevention. Related Item Public Input No. 85-NFPA [Section No. 9.6] Public Input No. 86-NFPA [Section No. A.9.6] Submitter Information Verification Submitter Full Name: Randall McCarver Organization: Telcordia (Ericsson) Affilliation: AT&T, CenturyLink Street Address: City: State: Zip: Submittal Date: Tue Nov 11 15:32:43 EST of 35 1/12/2015 3:00 PM
35 Public Comment No. 10-NFPA [ Section No. 9.7 ] 9.7 Means of Egress. All means of egress shall be maintained in accordance with the requirements of NFPA 101. Statement of Problem and Substantiation for Public Comment This requirement is not unique to telecommunications facilities. NFPA 76 should only address fire hazards unique to the telecommunications equipment occupancy. More general hazards are already addressed in other NFPA standards. NFPA 1 is the fundamental document that provides general fire protection requirements. It is the definitive standard and should be the only one that contains general requirements. Repeating requirements already in NFPA 1 leads to confusion and conflicting enforcement when requirements of one document diverge from the other, which occurs because they are not on the same revision cycle. NFPA 76 was a stand-alone document that is now a Standard referenced in NFPA 1, the primary governing document for general fire prevention. Related Item Public Input No. 87-NFPA [Section No. 9.7] Submitter Information Verification Submitter Full Name: Randall McCarver Organization: Telcordia (Ericsson) Affilliation: AT&T, CenturyLink Street Address: City: State: Zip: Submittal Date: Tue Nov 11 15:37:33 EST of 35 1/12/2015 3:00 PM
36 Public Comment No. 11-NFPA [ Sections 9.8.1, 9.8.2, 9.8.3, 9.8.4, ] Sections 9.8.1, 9.8.2, 9.8.3, 9.8.4, Displays, holiday trees, or other decorations shall not be allowed to obstruct corridors, exit ways, or other means of egress Natural cut holiday trees shall not be permitted Artificial holiday trees, displays, and decorations shall be labeled or otherwise identified or certified by the manufacturer as being flame retardant or flame resistive Only listed electric lights and wiring shall be used on holiday trees and similar decorations Electric lights shall be prohibited on metal artificial trees, displays, and other decorations not labeled for the use of listed lights. Statement of Problem and Substantiation for Public Comment Section 9.8 already prohibits displays, holiday trees or other decorations in telecommunication areas. Sections through contain requirements not unique to telecommunications facilities. NFPA 76 should only address fire hazards unique to the telecommunications equipment occupancy. More general hazards are already addressed in other NFPA standards. NFPA 1 is the fundamental document that provides general fire protection requirements. It is the definitive standard and should be the only one that contains general requirements. Repeating requirements already in NFPA 1 leads to confusion and conflicting enforcement when requirements of one document diverge from the other, which occurs because they are not on the same revision cycle. NFPA 76 was a stand-alone document that is now a Standard referenced in NFPA 1, the primary governing document for general fire prevention. Related Item Public Input No. 88-NFPA [Sections 9.8.1, 9.8.2, 9.8.3, 9.8.4, 9.8.5] Submitter Information Verification Submitter Full Name: Randall McCarver Organization: Affilliation: Street Address: City: State: Telcordia (Ericsson) AT&T, CenturyLink 18 of 35 1/12/2015 3:00 PM
37 19 of 35 1/12/2015 3:00 PM Zip: Submittal Date: Tue Nov 11 15:39:26 EST 2014
38 Public Comment No. 12-NFPA [ Section No. 9.9 ] 9.9 * Open Flame Devices In nontelecommunications areas, the use of solid-fueled heat sources for warming of food trays shall be permitted and shall be constantly attended and operated with the approval of management Other open flames shall only be permitted as otherwise stated in this document Portable fire extinguishers shall be provided in accordance with NFPA 10. Statement of Problem and Substantiation for Public Comment Section 9.9 contains requirements not unique to telecommunications facilities. NFPA 76 should only address fire hazards unique to the telecommunications equipment occupancy. More general hazards are already addressed in other NFPA standards. NFPA 1 is the fundamental document that provides general fire protection requirements. It is the definitive standard and should be the only one that contains general requirements. Repeating requirements already in NFPA 1 leads to confusion and conflicting enforcement when requirements of one document diverge from the other, which occurs because they are not on the same revision cycle. NFPA 76 was a stand-alone document that is now a Standard referenced in NFPA 1, the primary governing document for general fire prevention. Related Item Public Input No. 89-NFPA [Section No. 9.9] Public Input No. 90-NFPA [Section No. A.9.9] Submitter Information Verification Submitter Full Name: Randall McCarver Organization: Telcordia (Ericsson) Affilliation: AT&T, CenturyLink Street Address: City: State: Zip: Submittal Date: Tue Nov 11 15:42:03 EST of 35 1/12/2015 3:00 PM
39 Public Comment No. 13-NFPA [ Section No ] 9.11 * Vacant Areas. Vacant areas or spaces in a building shall be reviewed annually for the fire risk. Statement of Problem and Substantiation for Public Comment The term vacant areas or spaces is ambiguous. Is a space vacant when it is no longer being used, but contains retired-in-place equipment? Vacant spaces are not unique to telecommunications facilities. All facilities are vulnerable to the hazards of combustible material stored in vacant spaces. However if those spaces contain stored material, they are not vacant and therefore not covered by Section If the space is truly vacant (i.e., clean and empty floor to ceiling and wall to wall) then there are no additional fire protection measures necessary. The risk is already minimized. In addition, the requirement is vague. It gives no guidance as to what an annual review for the fire risk consists of and what should be done with any findings. Related Item Public Input No. 91-NFPA [Section No. 9.11] Public Input No. 92-NFPA [Section No. A.9.11] Submitter Information Verification Submitter Full Name: Randall McCarver Organization: Telcordia (Ericsson) Affilliation: AT&T, CenturyLink, Verizon Street Address: City: State: Zip: Submittal Date: Tue Nov 11 15:44:02 EST of 35 1/12/2015 3:00 PM
40 22 of 35 1/12/2015 3:00 PM Public Comment No. 14-NFPA [ Section No ] The pre-fire plan shall be reviewed and updated annually and where as personnel changes, management structure realignment, or facility changes occur. Statement of Problem and Substantiation for Public Comment Neither OSHA regulations covering emergency action plans nor NFPA 101 emergency plans require annual review. There is nothing unique about a telecommunications facility that requires annual review. The requirement is vague. No guidance is provided as to what constitutes an annual review. Related Item Public Input No. 93-NFPA [Section No ] Submitter Information Verification Submitter Full Name: Randall McCarver Organization: Telcordia (Ericsson) Affilliation: AT&T, CenturyLink, Verizon Street Address: City: State: Zip: Submittal Date: Tue Nov 11 15:46:48 EST 2014
41 23 of 35 1/12/2015 3:00 PM Public Comment No. 23-NFPA [ Section No. A ]
42 A The temperatures in hot aisles can exceed 37.8 C (100 F), which is often the listing limit on many types of detectors. 24 of 35 1/12/2015 3:00 PM
43 25 of 35 1/12/2015 3:00 PM A Smoke Detector Sensitivity and Spacing Guidance for Protection of Signal Processing Equipment in High Airflow Areas General For smoke detections systems to detect products of combustion, the products must travel from the source to a sensor or port and arrive there in sufficient density to be detectable. Products of combustion follow forced air streams early in the development of a fire, or overheat condition, when the influence of mechanical systems is greater than the buoyant forces of the fire or overheat condition. Detection system sensors or ports installed in the paths of cooling air exhaust from the cooled equipment can be expected to respond to a small fire in the equipment sooner than sensors or ports located outside of the ventilation air envelope. To be effective, the detection equipment installed within the ventilation air envelope should be suitable for the temperatures, air velocities and other conditions present. If suitable detection equipment cannot be installed within the exhaust ventilation air envelope, a fire in the cooled equipment should be expected to grow to a size at which its energy is sufficient to overcome the mechanical forces of the HVAC containment system. In the presence of aisle containment systems used to enhance the effectiveness of cooling signal processing equipment, sensors or ports located in hot aisles or in the above ceiling plenum may be effective. Regardless, sensors or ports located on the ceiling in signal processing equipment areas are a basic requirement and contribute to effective detection over a broad range of signal processing equipment area configurations. Listed signal processing equipment has inherent fire resistant characteristics. Failing or overheated components or connections may lead to smoldering events that produce smoke but tend to remain small due to the very low electrical voltages present at the board level in the signal processing equipment. Exceptions may occur when a source of energy external to the signal processing equipment drives increasing involvement of the materials present. In such exceptional cases, flaming fires may result. Automatic fire and smoke detection systems installed to detect smoldering events and/or flaming fires in signal processing equipment areas are more effective in detecting flaming fires than smoldering events due to the respective release rates of combustion products and the effects of forced air flow on the products of combustion. The greater the air flow, which dilutes and channels detectable products of combustion, the less effective will be the performance of the detection system. Damage or losses that may result from smoldering events or flaming fires in signal processing equipment prior to detection are likely to be greater in the presence of greater forced air flow due to the likely decrease in detection system performance. Smoke Detection Systems for Very Early Warning Where a smoke detection system is installed for the primary purpose of summoning responsible people to the presence of a small signal processing equipment fire, or electrical event that produces smoke, the system should be arranged with high sensitivity and close spacing to achieve response to low density products of combustion suspended in air with reasonable stability and tolerance of the environment. Smoke Detection Systems to Initiate Operation of HVAC Dampers or to Close Openings in Fire Rated Walls Where smoke a smoke detection system is installed for the primary purpose of initiating operation of dampers, shutters, doors or other closures in the event of a fire in an SIGNAL PROCESSING EQUIPMENT area, the system should be arranged with medium sensitivity and spacing less than listed spacing to assure the integrity of fire resistive barriers. Smoke Detection Systems to Initiate Release of a Fire Suppression Agent Where smoke a smoke detection system is installed for the primary purpose of initiating the release of a fire suppression agent into an SIGNAL PROCESSING EQUIPMENT Area, the system should be arranged with low sensitivity, spacing less than listed spacing, and should include a form of logical confirmation of the presence of products of combustion to assure that a single indication does not release the agent.. Sensitivity and Spacing Ranges
M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications
More informationM E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications
More informationResolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.
Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in
More information2016 Annual Revision Cycle Consent Document NFPA 75
2016 Annual Revision Cycle Consent Document NFPA 75 The Committee on Electronic Computer Systems produced a Technical Committee Report that received at least one Notice of Intent to Make a Motion (NITMAM)
More informationPublic Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item
Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels
More informationSecond Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement
Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard
More informationFirst Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes
First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25
More informationTECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting
TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, 2014 9:00 AM - 5:00 PM EST Web/Teleconference Meeting 1. Welcome. George Seuss, Chair 2. Introductions and Update
More informationFirst Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes
First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application. 1.3.1 This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except
More informationSecond Revision No. 3-NFPA [ Section No. 2.3 ]
Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler
More informationThroughout standard remove references to the following and replace with the following:
of 35 12/3/2015 7:13 AM Public Input No. 1-NFPA 90A-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/UL and replace with UL. (2) ANSI/ASHRAE
More informationPublic Input No. 1-NFPA 90B-2015 [ Chapter 2 ]
Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered
More informationPublic Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document
1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two
More information12/21/2015 National Fire Protection Association Report
http://submittals.nfpa.org/terraviewweb/viewerpage.jsp?id=232 2012.ditamap&toc=false&draft=true 1/9 Public Comment No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents
More informationM E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities
More informationFirst Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ]
of 71 6/11/2014 8:20 AM First Revision No. 36-NFPA 76-2014 [ Section No. 1.1 [Excluding any Sub-Sections] ] This standard provides requirements for fire protection of telecommunications facilities where
More informationCorrelating Committee on Automatic Sprinkler Systems
Correlating Committee on Automatic Sprinkler Systems M E M O R A N D U M DATE: May 14, 2014 TO: FROM: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems Matt Klaus,
More informationPage 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input
Public Input No. 4-NFPA 111-2016 [ Section No. 1.1.4.1 ] 1.1.4.1 * This standard shall not cover the following: (1) Application of the SEPSS (2) Distribution wiring (3) Systems having total outputs less
More informationM E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Furnishings
More informationTECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016
TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES NFPA 610 First Draft Meeting October 17-18, 2016 Westin Kansas City at Crown Center 1 East Pershing Road Kansas City, MO, 64108 Conference Call Access:
More informationNFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES 1.
More informationPublic Comment No. 1-NFPA [ Section No ]
Page 1 of 7 Public Comment No. 1-NFPA 556-2014 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA, 19428-2959. ASTM D2859, Standard
More information1. Welcome. Robert Smith, Chair. 2. Introductions and Update of Committee Roster. (attached)
TECHNICAL COMMITTEE ON WATER-COOLING TOWERS NFPA 214 (F2015) Second Draft Meeting Agenda February 17, 2014 10:00 AM - 1:00 PM EST Web/Teleconference Meeting 1. Welcome. Robert Smith, Chair 2. Introductions
More informationPublic Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input
Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.
More informationTechnical Committee on Record Protection (REA-AAA)
Technical Committee on Record Protection (REA-AAA) DATE: September 8, 2015 TO: FROM: M E M O R A N D U M Principal and Alternate Members of the Technical Committee on Record Protection (REA-AAA) Audrey
More informationFirst Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM
of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide
More informationNFPA Technical Committee on Building Systems. NFPA 900 First Draft Teleconference/Web Meeting AGENDA. Thursday, February 13, :00 a.m.
1. Call to Order: NFPA Technical Committee on Building Systems NFPA 900 First Draft Teleconference/Web Meeting AGENDA Thursday, February 13, 2014 11:00 a.m. Noon EDT Online meeting link: http://nfpa.adobeconnect.com/r366m2eaxx6/
More informationCommittee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM
1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:
More informationPublic Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]
8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.
More informationNFPA Technical Committee on Fire Tests FALL 2010 ROC MEETING MINUTES April 15-16, 2010 Southwest Research Institute San Antonio, TX
NFPA Technical Committee on Fire Tests FALL 2010 ROC MEETING MINUTES April 15-16, 2010 Southwest Research Institute San Antonio, TX 1. Call to Order. The meeting of the Technical Committee on Fire Tests
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and
More informationM E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter
More informationFirst Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM
1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling
More informationNFPA Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems
San Antonio, TX October 12-14, 2016 The following are the meeting minutes from the third meeting of the Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems held in San Antonio,
More informationFirst Revision No. 1-NFPA [ Chapter 2 ]
First Revision No. 1-NFPA 499-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this recommended practice
More informationTechnical Committee on Aircraft Fuel Servicing (AIF-AAA)
Technical Committee on Aircraft Fuel Servicing () DATE: February 13, 2014 TO: FROM: M E M O R A N D U M and Alternate Members of the Technical Committee on Aircraft Fuel Servicing () Barry Chase, NFPA
More informationPublic Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification
Public Comment No. 2-NFPA 73-2014 [ Section No. 4.1.3 ] 4.1.3 Unused Openings. 4.1.3.1 Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or
More informationRemove the "Exception" text to be consistent with direction provided in the MOS.
of 37 1/11/2017 7:38 AM Public Input No. 9-NFPA 88A-2015 [ Global Input ] Remove the "Exception" text to be consistent with direction provided in the MOS. The current language in 88A has numerous section
More informationPublic Comment No. 2-NFPA [ Section No ]
Public Comment No. 2-NFPA 16-2013 [ Section No. 3.3.6 ] 3.3.6* Foam-Water Sprinkler System. A piping network connected to a source of foam concentrate and to a water supply. The piping network is equipped
More informationREPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS
REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS I. Introduction. This is the Motions Committee Report on Standards in the Fall 2013 Revision Cycle. The report identifies Certified
More informationAgenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO
Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Item No. Subject 13-6-1 Call to Order (8:00 A.M) 13-6-2 Roll Call 13-6-3 Approval
More information1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input
Public Input No. 2-NFPA 259-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D 5865, Standard Test Method
More informationAdobe Connect - Invitation to NFPA 385 Second Draft Web Conference
Matthews, Diane Subject: Location: Start: End: Show Time As: Recurrence: Meeting Status: Organizer: Required Attendees: Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference http://nfpa.adobeconnect.com/rpbmeet/
More informationFIF AAA (F2014) Second Draft Meeting Web/Teleconference Meeting Agenda March 18, :00 5:00 p.m. ET
NFPA 804, Standard for Fire Protection for Advanced Light Water Reactor Electric Generating Plants, NFPA 805, Performance Based Standard for Fire Protection for Light Water Reactor Electric Generating
More informationROP MEETING MINUTES. 2. Introduction of Attendees. The following committee members and guests were in attendance. TECHNICAL COMMITTEE MEMBERS PRESENT
BLD/SAF-FIR 24-25 September 2009 ROP Meeting Minutes ROP MEETING MINUTES Building Code Life Safety Technical Committee on Fire Protection Features Thursday-Friday, September 24-25, 2009 Meeting Embassy
More informationPublic Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification
Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the
More informationCorrelating Committee on Health Care Facilities (HEA-AAC)
M E M O R A N D U M DATE: November 2, 2016 TO: and Alternate Members of the Correlating Committee on Health Care Facilities FROM: Jon Hart, Senior Fire Protection Engineer/NFPA Staff Liaison SUBJECT: AGENDA
More information1. Call to Order. The meeting was called to order at 1:05 PM. (See Enclosure A [Agenda])
FINAL MINUTES Healthcare Interpretations Task Force Tuesday, June 15, 2016 Mandalay Bay Convention Center South Convention Center, Level 2 Room Surf F Las Vegas, NV 1. Call to Order. The meeting was called
More information6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement
First Revision No. 1-NFPA 259-2016 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D5865, Standard Test Method
More informationWORKING DRAFT OF COMMITTEE MEETING OUTPUT
WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF SECOND DRAFT REPORT Document: NFPA 221 Revision Cycle: A2014 Meeting Date: 5/20/2013
More informationTechnical Committee on Mechanical Systems (HEA-MEC)
Technical Committee on Mechanical Systems () M E M O R A N D U M DATE: July 20, 2015 TO: and Alternate Members of the Technical Committee on Mechanical Systems () FROM: Jon Hart, Staff Liaison SUBJECT:
More informationPublic Input No. 3-NFPA [ Chapter 2 ]
Public Input No. 3-NFPA 655-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered
More informationPublic Comment No. 16-NFPA 13D-2014 [ Section No ]
of 52 9/22/2014 9:20 AM Public Comment No. 16-NFPA 13D-2014 [ Section No. 2.3.3 ] 2.3.3 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM
More informationTechnical Committee on Water Mist Fire Suppression Systems
Date: January 29, 2013 1. Call to Order. Meeting was called to order by Chair Larry Owen at 8:00 AM. 2. Building Safety Message. Building safety was discussed and exits identified by Chair Larry Owen.
More informationMEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Industrial and Medical Gases
More informationSecond Revision No. 1 NFPA [ Chapter 2 ]
Second Revision No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be
More informationMEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Protected Premises Fire Alarm
More informationChange all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.
1 of 9 10/21/2015 1:22 PM First Revision No. 3-NFPA 99B-2015 [ Global Input ] Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.
More informationMEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Fire Alarm
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org ROC MEETING AGENDA Technical Committee on Safety to Life from Fire on
More informationTechnical Committee on Dry and Wet Chemical Extinguishing Systems (DRY-AAA) Memorandum
Technical Committee on Dry and Wet Chemical Extinguishing Systems (DRY-AAA) Memorandum DATE: Tuesday, April 12, 2016 TO: Principal and Alternate Members of the Technical Committee on Dry and Wet Chemical
More informationFirst Revision No. 6-NFPA [ Section No. 2.2 ]
Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon
More information1. The meeting was called to order by Chair James Lathrop at 8:00 AM (CDT) on Wednesday, August 26, 2015.
MINUTES NFPA Technical Committee on Residential Occupancies NFPA 101 and NFPA 5000 First Draft Meeting Wednesday, August 26, 2015 InterContinental Milwaukee Milwaukee, WI 1. The meeting was called to order
More informationMEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Initiating Devices for Fire
More informationAgenda. If you are participating via Microsoft Live Meeting, here is the web address to join the Live Meeting:
Agenda NFPA Technical Committee on Manufactured Housing Fall 2012 Report on Comments Tuesday, April 10, 2012 from Noon to 5:00 PM Wednesday, April 11, 2012 from 8:00 AM to 5:00 PM (CDT) Hilton Garden Inn
More informationPublic Comment No. 32-NFPA 90A-2016 [ Section No ] Statement of Problem and Substantiation for Public Comment
of 53 11/9/2016 9:07 AM Public Comment No. 32-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA
More informationMEETING AGENDA High Rise Building Safety Advisory Committee
MEETING AGENDA High Rise Building Safety Advisory Committee Renaissance Blackstone Chicago 636 South Michigan Avenue, Chicago, IL 60605 May 13-14, 2014 Chicago, IL 1. Call to Order. Call the meeting to
More information"Spray area" is the term that is used throughout the document. This change is for consistency.
of 78 5/30/2014 2:08 PM Public Comment No. 39-NFPA 33-2013 [ Global Input ] For Chapter 18, replace "spray paint area" with "spray area". "Spray area" is the term that is used throughout the document.
More informationPublic Comment No. 2-NFPA [ Section No ]
Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard
More informationIntroductions made by the Chair, committee members, NFPA Staff Liaison, Jacqueline Wilmot and Dan Gorham of the Fire Protection Research Foundation.
NFPA Technical Committee On Fire Hose NFPA 1961 Minutes Task Group Update Underwriters Laboratory November 15 th - 16 th 2016 Tuesday, November 15 th, 2016 Meeting called to order at 8:07 AM by Chairman
More informationTECHNICAL COMMITTEE ON FIRE CODE
TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2
More informationReport on Public Input June 2014 NFPA 101
101 PI# 115 SAF-FUR (10.2.1.2) 10.2.1.2 Materials applied directly to the surface of walls and ceilings in a total thickness of less than 1 / 28 in. (0.9 mm) shall not be considered interior finish and
More informationPage 1 of 9 First Revision No. 2-NFPA 99B-2012 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard for Portable
More informationSAF-BCF SECOND REVISIONS WITH STATEMENTS
Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level
More informationMEETING AGENDA High Rise Building Safety Advisory Committee
MEETING AGENDA High Rise Building Safety Advisory Committee March 4, 2015 Teleconference/Web Meeting 1. Call to Order. Call the meeting to order by Chair, Jim Quiter, at 1:00 pm EST on Wednesday, March
More informationPublic Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input
of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August
More informationPublic Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification
Public Input No. 1-NFPA 36-2013 [ Global Input ] Revise the document to eliminate the use of "Exception" text. The use of "Exception" text is inconsistent with the Manual of Style. Exception text should
More informationMEETING MINUTES NFPA Technical Correlating Committee on Safety to Life January 6, 2011 ROC Meeting The Wyndham Phoenix, Phoenix, AZ
MEETING MINUTES NFPA Technical Correlating Committee on Safety to Life January 6, 2011 ROC Meeting The Wyndham Phoenix, Phoenix, AZ 1. Call to Order. The meeting was called to order by Chair William Koffel
More informationTechnical Committee on Incinerators and Waste Handling Systems
Technical Committee on Incinerators and Waste Handling Systems Date: April 27, 2017 To: From: Technical Committee on Incinerators and Waste Handling Systems Eric Nette, Staff Liaison/Engineer Re: Agenda
More informationTECHNICAL COMMITTEE MEMBERS PRESENT
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0770 www.nfpa.org MINUTES NFPA Technical on Fire Doors and Windows NFPA 80 and NFPA 105
More informationReport on First Revision June 2014 NFPA 5000
5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Standpipes Elena
More informationNFPA 550 ROP Meeting Minutes
NFPA 550 ROP Meeting Minutes NFPA Technical Committee on Fire Risk Assessment Methods (FIR-AAA) June 24, 2010 Microsoft Live Meeting 1. Call to order. The meeting was called to order at 1:00 PM on Monday,
More informationMEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Alternative Approaches to
More informationNFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda*
NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda* NFPA Standards presented for Action Wednesday, June 24, 2015 starting @ 2:00pm: NFPA 33, Standard for Spray Application Using Flammable or
More informationPage 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More informationTECHNICAL COMMITTEE MEMBERS WHO PARTICIPATED
MEETING MINUTES NFPA Correlating Committee on Safety to Life (SAF-AAC) November 7, 2013 Second Draft Meeting Embassy Suites Atlanta Hartsfield Airport Hotel Atlanta, GA 1. Call to Order. The meeting was
More informationChanges in NFPA
Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration
More informationFirst Revision No NFPA [ Section No ]
of 45 10/21/2015 8:54 AM First Revision No. 3501-NFPA 101-2015 [ Section No. 3.3.190.1 ] 3.3.196.1* Ambulatory Health Care Occupancy. An occupancy used to provide services or treatment simultaneously to
More information- Residential Fire Sprinkler -
- Residential Fire Sprinkler - Update as of September 15, 2014 The information provided is a state-by-state status of the 2009 IRC adoption and legislation activities as reported by HBA s. NAHB staff monitors
More informationNFPA Technical Committee on Fire Tests
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Tracy
More informationSecond Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement
of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections
More informationMEMORANDUM. NFPA Technical Committee on Hazard and Risk of Contents and Furnishings. NFPA 556 First Draft TC FINAL Ballot Results (A2015)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Hazard and Risk of Contents
More informationAir Moving Systems. Fire Safety Inspection and Testing of. NBSIR jan «1933. Washington, DC General Services Administration
National Bureau of Standards Gaithersburg, Maryland 2.0899 NBSIR 87-3660 jan «1933 Fire Safety Inspection and Testing of Air Moving Systems John H. Klote U.S. DEPARTMENT OF COMMERCE National Bureau of
More informationStandards and Safety Update
Standards and Safety Update Presented By: Michael J. Johnston Executive Director Standards and Safety, NECA Update Objectives Update on NFPA 70E and NECA Safety products Update on NECA S National Electrical
More information2015 Fall Revision Cycle Notice of a Consent Standard NFPA 102
2015 Fall Revision Cycle Notice of a Consent Standard NFPA 102 The Committee on Assembly Occupancies produced a First Revision Report for NFPA 102, Standard for Grandstands, Folding and Telescopic Seating,
More informationMinutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN
Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN Mr. Merton Bunker, Committee Chair, called the meeting to order at 8:05 on Wednesday September
More information