Temperature Distribution of Rotary Heat Recovery Units

Size: px
Start display at page:

Download "Temperature Distribution of Rotary Heat Recovery Units"

Transcription

1 Temperature Distribution of Rotary Heat Recovery Units Bjørn R. Sørensen, dr.ing. Narvik University College, P.O.Box 385, N-8505 Narvik, Norway Corresponding SUMMARY This paper deals with measurements of temperature distribution of rotary heat recovery units. A special grid of thermocouples has been made to measure air temperature in equally distributed sampling points on each side of a heat recovery wheel. Air flow rates and the amount of recirculation air (leakage) were measured using a tracer gas. The results show that the temperature profile is generally dependent on both the rotational speed of the wheel and the flow rate. Measurements also show that the placement of temperature sensors in the duct can be significant, since wrong placements may lead to both faulty or non-optimized control of the units, and wrong readings of the temperature efficiency. Propitious sensor placements have been proposed. INTRODUCTION There are many types of air-to-air heat recovery units (HRU) which are in use in ventilation systems (see for instance Schild [1]). Rotary heat recovery exchangers are widely used, and the units are known for their high efficiency and trouble-free operation. Temperature efficiencies above 80% are not uncommon. For balanced ventilation systems, the recovered heat power can be at the same rate. Unfortunately these units are also infamous for transmission of polluted air from exhaust to supply. Due to the rotation of the device, there will always be a direct and indirect connection between exhaust and fresh supply air. Crosscontamination through rotary heat recovery units comes from two mechanisms; (1) Leakage, (2) Carryover. The former is dependent on the differential static pressure across the wheel, and the placement of supply and exhaust fans may affect its value significantly. The latter (carryover) occurs as a result of air being entrained within the wheel volume. Contaminated air is then carried into the other, clean air stream. The degree of carryover air is strongly dependent on whether the unit has a purge section or not. Rotor speed is normally relatively low and in a range of 3-15 rpm. The cross sectional temperature distribution on the supply or discharge side of a rotary HRU is in many cases non-uniform. This means that placement of temperature sensors for control or for calculation of energy transfer and efficiencies is crucial. SITE DESCRIPTION AND MEASUREMENT SETUP Flow and temperature measurements where performed in a laboratory test ventilation system (the heat recovery AHU part of the system is shown in figure 1). This is a ABB EC2000 unit with a non-hygroscopic rotary wheel. Flow rates where measured with a tracer gas. A tracer gas (SF 6 ) was released into the air, and concentrations upstream and downstream of the dosing points determined the flow rate and cross-contamination of the heat recovery unit (according to figure 2).

2 Figure 1. The AHU subsystem containing the rotary heat recovery unit Figure 2. Flow measurement setup and tracer gas sampling points, Eian/Sørensen [2] Figure 3. Temperature sampling points

3 The temperature measurement system (refer to figure 3) consisted of: Three grids of thermocouples on the intake and supply side (grid T1, T2 and T3), each containing 6 sample points (figure 3 and 4) Three grids of thermocouples on the exhaust and discharge side (grid A1, A2 and A3), each containing 6 sample points Temperature in the ducts T0, T4, A0 and A4. A NI1000 mean temperature sensor on the exhaust side (this sensor was not used in this study) Figure 4. Picture of a thermocouple grid in front of the rotary heat recovery unit. RESULTS AND DISCUSSION Flow rates Figure 5 shows the flow rates that were measured for different speeds of the fan and heat recovery unit. Figure 6 shows the percentage return air being recirculated to the supply side. Flow rate (m3/h) Flow rate - exhaust 100% rotary speed 50% rotary speed 0% rotary speed Cross contamination (%) 100 % 90 % 80 % 70 % 60 % 50 % 40 % 30 % 20 % 100% rotary speed 50% rotary speed 0% rotary speed % 0 0 % 20 % 40 % 60 % 80 % 100 % Fan speed (% of max) 0 % 0 % 20 % 40 % 60 % 80 % 100 % Fan speed (% of max) Figure 5. Flow rates measured in the exhaust Figure 6. Cross contamination (%)

4 A large amount of recirculated return air was measured. The large amount of return air was mainly a result of the rotary HRU having no purge sector and an unfavorable placement of the fans in the system. This resulted in a low static pressure on the intake side of the HRU and a relative high pressure on the exhaust side, forcing air to cross to the supply side. The latter caused a 12-15% air recirculation. It was also noticed that the amount of recirculation increased significantly with increased speed of the HRU wheel. This indicates that carryover air stands for a large amount of total recirculation. Furthermore, at low fan speeds, the relative amount of recirculated air increased significantly. While the fans were running at only 20% of maximum speed, and the HRU was at full speed, there were almost no fresh outdoor air on the supply side (90% recirculation). Thus this confirms the importance of obtaining proper pressure conditions around the rotating wheel. The results also suggest that for VAV systems running on low fan speeds, the amount of return air can become very high and thus unacceptable. Measurements with the HRU not rotating show an almost constant amount of recirculated air (independent of fan speed). Hence, the increase of recirculation was mainly caused by carryover air in the rotating wheel. Furthermore, the amount of carryover air from the supply to the exhaust was quite noticeable, as can be seen in figure 5 (since flow rates on the exhaust side varied with the speed of the rotating wheel). Similar measurements were performed on the supply side of the HRU, showing that the ventilation system was very good balanced with respect to supply and exhaust flow rates. Temperature measurements Relative speed (%) 120 % 100 % 80 % 60 % 40 % 20 % 0 % Fan speed HRU w heel speed Time (min) Figure 7: Fan and HRU wheel speeds (% of max) during temperature measurements Two measurements series were performed, each resulting in responses from altered fan speeds (0-100% of max, 20% step) and HRU wheel speeds (0%, 10%, 20%, 40%, 60% and 100% of max), see figure 7. The outdoor temperature was fairly constant around 0 C. Figure 8 shows the temperature measurements as a function of time from grid T2 (supply side, closest to the wheel) for measurement series 2. At a first glance, it is obvious that the temperature varied quite noticeable across the section/grid for a given fan and HRU wheel speed. If looking closer it is possible to see the variations in temperature due to the alternations of the wheel rotary speed. The most conspicuous temperature drops happened when the rotary HRU was shut down to 0% speed. When this occurred, the temperature on the supply side naturally dropped towards the outdoor temperature. In figure 9-12, the results have been arranged so that they correspond to the location of the actual sampling point. The two upper rows of graphs correlate to the grids on the supply side of the HRU wheel, grid T2 and T3, while the two lower rows of graphs correlate to the grids on the discharge side, grid A2 and A3. In addition, the duct temperatures (T4 and A4) are plotted on the supply and discharge graphs respectively. Since these sampling points are located away from the wheel (in the ducts), they are used as references to decide whether a

5 temperature value is too low or too high in the grids. Each graph has been numbered in accordance with the setup given by figure 3. The direction of the HRU is also shown. Figure 9 and 10 show steady state temperature levels (according to the variations in fan speed and wheel speed defined by figure 7) for each sampling point at 20% respectively 100% fan speed, as a function of the relative HRU wheel speed. Likewise, figure 11 and 12 show temperature levels for each sampling point at 20% respectively 100% HRU speed, as a function of the relative fan speed. Temperature ( C) Grid T Time (min) Figure 8. Temperature measurements, grid T2 (supply side, close to wheel). From figure 9 and 10 it can be seen that the HRU speed is of minor importance as long as it is above 20% (in this case, 20% speed corresponds to an absolute speed of 2.25 rpm). Furthermore, while the fans run on low speed (20% of max) the cross sectional stratification bedding is small on the supply side, and the temperature distribution is fairly uniform. As the HRU speed is increased, temperatures on the supply side decrease slightly. Most likely this is caused by the large increase of recirculation air (refer to the flow measurements discussed earlier). However, in a system with an efficient purge sector this tendency will not show. On the discharge side, the distributions are more scattered, with highest values near the center line of the wheel. When the fan speed is increased (figure 10), the cross sectional temperatures on both the supply and discharge sides of the wheel become increasingly scattered, and a cross sectional stratification is revealed. In this situation, the air is warmest near the center line of the wheel. From the next two figures (figure 11 and 12) it can be seen that the fan speed of course affect the temperature levels significantly. While the fans run on low speed (20% of max) the cross sectional stratification bedding is small on the supply side, and the temperature distribution is fairly uniform. There is however a tendency of high temperatures near the center of the unit and low temperature around the edges. On the discharge side, the warmest air is near the edge of the wheel, close to the center line. Table 1 shows a simple summary of the temperature levels from figure 9-12, as a color map of grid T2 and A2. Levels are shown as +/- differences from the duct levels T4 and A4, which are believed to be more representative for the actual air temperature. Table 1. Map of temperatures ( C) close to HRU wheel (supply and discharge side). Fig. 9, fan 20% Fig. 10, fan 100% Fig. 11, HRU 20% Fig 12, HRU 100% Varying HRU Varying HRU Varying fan Varying fan Supply Discharge T2-1 T2-2 T2-3 T2-4 T2-5 T2-6

6 Figure 9. Air temperatures, T2-T4 and A2-A4 (supply and discharge sides) as a function of HRU rotational speed at 20% fan speed (HRU view from intake side). Figure 10. Air temperatures, T2-T4 and A2-A4 (supply and discharge sides) as a function of HRU rotational speed at 100% fan speed (HRU view from intake side).

7 Figure 11. Air temperatures, T2-T4 and A2-A4 (supply and discharge sides) as a function of relative fan speed at 20% HRU rotational speed (HRU view from intake side). Figure 12. Air temperatures, T2-T4 and A2-A4 (supply and discharge sides) as a function of relative fan speed at 100% HRU rotational speed (HRU view from intake side).

8 Placement of temperature sensors in the duct The ideal placement of a temperature sensor used for Supply control or efficiency calculations is away from the wheel so it is not affected by stratified air nor by radiation from the wheel media. However, this is rarely convenient or possible, so the compromise must be to find a spot near the wheel (on all sides) that approximately resembles the actual air temperature as if it was measured away and shielded from the device. From table 1, an assessment of sensor placement is possible. For this actual HRU wheel Discharge it seems most appropriate to place the supply side and Figure 13. Placement of sensors discharge side sensors as shown by the yellow spots in figure 13. It should also be mentioned that the temperatures on the exhaust and intake side of the wheel were fairly uniform, but small variations can be expected due to radiation from the wheel and in cases with leakage. A similar assessment may be required here. Possible sources of error Measurements should be carried out on several different heat recovery units. Also, the number of repeated measurements series are low, and it is thus not possible to establish a basis for categorical conclusions. Nevertheless, the results serve to pinpoint typical tendencies. CONCLUSIONS The flow rate measurements results suggest that for ventilation systems running on low fan speeds (VAV), the amount of recirculation of air from the exhaust to the supply can, due to carryover, become very high and thus unacceptable. The rotational speed of the heat recovery unit has shown to be of minor importance as long as the wheel is rotating. For this particular case, above 20% of maximum speed. The ideal placement of a temperature sensor used for control or efficiency calculations is away from the wheel so it is not affected by cross-sectional stratification bedding, nor by radiation from the wheel media. For the particular HRU in question, measurement results suggest that the sensors on the supply and discharge side should be placed approximately in the middle of the AHU duct, or displaced to the sides. FURTHER WORK This work represents the first report in a project on air-to-air heat recovery devices carried out at Narvik University College. Future work will address temperature and energy efficiency, transient conditions, control, modelling and simulation. REFERENCES 1. Schild P G Air-to-Air Heat Recovery in Ventilation Systems. AIVC Ventilation Information Paper no Eian P. K., Sørensen B. R. 1996, Bestemmelse av ventilasjonens effektivitet med sporgassanalyse. Report (in Norwegian), Narvik University College, ISBN

THE IMPORTANCE OF THE DESICCANT RESULTS OF CROSS-CONTAMINATION TESTING ON DESICCANTS

THE IMPORTANCE OF THE DESICCANT RESULTS OF CROSS-CONTAMINATION TESTING ON DESICCANTS THE IMPORTANCE OF THE DESICCANT RESULTS OF CROSS-CONTAMINATION TESTING ON DESICCANTS Preface This report summarizes the results of a performance testing program conducted in accordance with ASHRAE Standard

More information

Heat Recovery Units. Heat Recovery 1

Heat Recovery Units. Heat Recovery 1 Heat Recovery Units Heat Recovery 1 Heat Recovery Unit Why? A heat recovery unit (HRU) can help make mechanical ventilation more cost effective by reclaiming energy from exhaust airflows. HRUs use air-to-air

More information

AIR HANDLING THERMAL CONDITIONS

AIR HANDLING THERMAL CONDITIONS AIR HANDLING THERMAL CONDITIONS Parts of air handling unit (=AHU): Outdoor air grille Air chamber Outdoor air damper Filter Heat recovery unit Heating coil Fan Sound absorber Mixing chamber Per-heating

More information

European Parliament and of the Council with regard to energy labelling of residential ventilation units. (Text with EEA relevance) (2016/C 416/06)

European Parliament and of the Council with regard to energy labelling of residential ventilation units. (Text with EEA relevance) (2016/C 416/06) C 416/16 EN Official Journal of the European Union 11.11.2016 Commission communication in the framework of the implementation of Commission Regulation (EU) No 1253/2014 implementing Directive 2009/125/EC

More information

THE EVALUATION OF MULTI-ZONE AIR FLOW PATTERN AND VENTILATION RATES WITH TRACER GAS METHODS IN APARTMENT HOUSE

THE EVALUATION OF MULTI-ZONE AIR FLOW PATTERN AND VENTILATION RATES WITH TRACER GAS METHODS IN APARTMENT HOUSE THE EVALUATION OF MULTI-ZONE AIR FLOW PATTERN AND VENTILATION RATES WITH TRACER GAS METHODS IN APARTMENT HOUSE DW Yoon 1, JY Sohn 2, SD Kim 3 and HS Kim 4 1 Dept. of Building Equipment and System Engineering,

More information

Mystery of Sustainable Heat Exchange Material Heat Recovery Ventilator(HRV)

Mystery of Sustainable Heat Exchange Material Heat Recovery Ventilator(HRV) Mystery of Sustainable Heat Exchange Material Heat Recovery Ventilator(HRV) 1 Contents Why Heat Recovery Ventilator(HRV) is required Type of Heat Recovery Ventilator Feature of MITSUBISHI ELECTRIC Lossnay

More information

Custom Air Handler Solutions Custom Units to Meet Your Unique Design Needs

Custom Air Handler Solutions Custom Units to Meet Your Unique Design Needs Custom Units to Meet Your Unique Design Needs Engineered for flexibility and performance Contents Horizontal Configuration....1 Horizontal with Standard Economizer Configuration...2 Stacked Configuration...3

More information

ASHRAE JOURNAL ON REHEAT

ASHRAE JOURNAL ON REHEAT Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide

More information

NATIONAL INSTITUTES of HEALTH FUME HOOD TESTING PROTOCOL. For CONSTANT VOLUME FUME HOODS

NATIONAL INSTITUTES of HEALTH FUME HOOD TESTING PROTOCOL. For CONSTANT VOLUME FUME HOODS NATIONAL INSTITUTES of HEALTH FUME HOOD TESTING PROTOCOL For CONSTANT VOLUME FUME HOODS PART I. GENERAL Test identified below was created by Farhad Memarzadeh of the National Institutes of Health in 1997

More information

Adding More Fan Power Can Be a Good Thing

Adding More Fan Power Can Be a Good Thing This article was published in ASHE Journal, May 14. Copyright 14 ASHE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of

More information

THE EFFECT OF ENTHALPY RECOVERY VENTILATION ON THE RESIDENTIAL INDOOR CLIMATE

THE EFFECT OF ENTHALPY RECOVERY VENTILATION ON THE RESIDENTIAL INDOOR CLIMATE THE EFFECT OF ENTHALPY RECOVERY VENTILATION ON THE RESIDENTIAL INDOOR CLIMATE Bart Cremers Zehnder Group Nederland Lingenstraat 2 8028 PM Zwolle, The Netherlands bart.cremers@zehndergroup.com ABSTRACT

More information

Cooling the Data Center

Cooling the Data Center Article development led by queue.acm.org doi:10.1145/1721654.1721671 What can be done to make cooling systems in data centers more energy efficient? by Andy Woods Cooling the Data Center Power generation

More information

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx Case Study: Furman University Charles H. Townes Center for Science Michael K. Mantai, PE, CCP President System WorCx AIA Quality Assurance Learning Objectives 1. Case study example of Chilled Beam technology

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

How to ensure Thermal Comfort in buildings with CFD

How to ensure Thermal Comfort in buildings with CFD How to ensure Thermal Comfort in buildings with CFD Using CFD Simulations to analyze and improve HVAC Systems Simulation in your browser How to Ensure Thermal Comfort in Buildings with CFD How to use CFD

More information

Air Handling Units. T F E.

Air Handling Units.  T F E. Air Handling Units Extract from BS EN ISO 15138:2007 Petroleum & natural gas industries- Offshore production installations-heating, ventilation & air-conditioning. A.12.1 Function Installations provided

More information

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA Ninth International IBPSA Conference Montréal, Canada August 15-18, 25 SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS Chaoqin Zhai 1, Xiaohong

More information

Residential ventilation concepts based on the idea of displacement airflow distribution

Residential ventilation concepts based on the idea of displacement airflow distribution A strategy for reducing energy demand Student: Aris Gkitzias (I.D:4180380) Mentors: Dr. Regina Bokel, Ir. John van der Vliet MSc graduation project Department of Building Technology, faculty of architecture

More information

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems FEMA Recommendations are based upon Live Fire Testing of Prep Stations

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

The Current (2017) State of the Art for Air Leakage in Ductwork

The Current (2017) State of the Art for Air Leakage in Ductwork The Current (2017) State of the Art for Air Leakage in Ductwork Over the last ten years there has been a major shift in the way ASHRAE has approached air leakage in ductwork. This is reflected in the latest

More information

Material and rotor description.

Material and rotor description. Material and rotor description. Why we use aluminum series 8000? Due the very good manufacturing characteristics and resistance against corrosion AMARANT has chosen to use the 8000 series alloy both for

More information

Bill McCullough. Director ERV Products. Dallas, TX

Bill McCullough. Director ERV Products. Dallas, TX Bill McCullough Director ERV Products Dallas, TX TOPICS 1. ERV Definition & Benefit 2. Indoor Air Quality 3. Energy Efficiency 4. ERV Technology & Operation 5. Stand-Alone ERVs 6. Compact ERVs What is

More information

Computing Services Center

Computing Services Center Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed

More information

EC Plug Fans EC FanGrid Retrofits for High Efficiency Air Handling Units

EC Plug Fans EC FanGrid Retrofits for High Efficiency Air Handling Units GET A GRID ON EC Plug Fans EC FanGrid Retrofits for High Efficiency Air Handling Units EC Plug Fans for HVAC Efficiency Using an EC FanGrid Continuous and consistent airflow is essential to virtually every

More information

GAS DETECTOR LOCATION. Ø.Strøm and J.R. Bakke, GexCon AS, Norway

GAS DETECTOR LOCATION. Ø.Strøm and J.R. Bakke, GexCon AS, Norway AUTHOR BIOGRAPHICAL NOTES GAS DETECTOR LOCATION Ø.Strøm and J.R. Bakke, GexCon AS, Norway Øyvind Strøm graduated in 1996 from Stavanger University College with a M.Sc. degree in Offshore Safety Technology.

More information

HVAC Water chiller selection and optimisation of operation

HVAC Water chiller selection and optimisation of operation HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water

More information

VERSO Air Handling Units

VERSO Air Handling Units Energy efficient solutions for profitable indoor climate VERSO-S air supply units VERSO-R air handling units equipped with regeneration system VERSO-P air handling units equipped with recuperation system

More information

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling The cooling capacity of the Thermo Active Building System combined with acoustic ceiling Peter Weitzmann, Technical consultant, BuildDesk A/S; peter.weitzmann@builddesk.dk Emanuele Pittarello, MSc, International

More information

This summarises results from our inspection of the Rendering Plant air extraction system at the Imlay meat works on 12 December 2013.

This  summarises results from our inspection of the Rendering Plant air extraction system at the Imlay meat works on 12 December 2013. Aurecon New Zealand Limited Level 1, 102 Customhouse Quay Wellington 6011 PO Box 1591 Wellington 6140 New Zealand T F E W +64 4 472 9589 +64 4 472 9922 wellington@aurecongroup.com aurecongroup.com 3 February

More information

SUSPENDED AIR HANDLING UNIT WITH ROTARY HEAT EXCHANGER

SUSPENDED AIR HANDLING UNIT WITH ROTARY HEAT EXCHANGER SUSPENDED AIR HANDLING UNIT WITH ROTARY HEAT EXCHANGER Energy Recovery Ventilation Specialist Beijing Holtop Artificial Environment Technology Co., Ltd ISO 9001: 2000 Approved Company COMPANY BRIEF INTRODUCTION

More information

4.0 Mechanical Redesign

4.0 Mechanical Redesign 4.0 Mechanical Redesign As my depth area of research, I have performed a detailed analysis of the existing air handling units and the existing conditions of the FIT Science Lab. After one semester of breaking

More information

Trane CDQ Desiccant Dehumidification

Trane CDQ Desiccant Dehumidification Engineering Bulletin Trane CDQ Desiccant Dehumidification September 2004 CLCH-PRB020-EN Preface This engineering bulletin presents the Trane CDQ desiccant dehumidification system. It explains the features

More information

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this lecture are to: 1. Importance of complete vapour compression refrigeration

More information

Ventilation System Description. September 8, 2000 HETA

Ventilation System Description. September 8, 2000 HETA September 8, 2000 HETA 99-0250 Harry Enoch, Ph.D. Director, Environmental Health and Safety University of Kentucky 252 East Maxwell Street Lexington, KY 40506-0314 Dear Dr. Enoch: On June 7, 1999, the

More information

Existing Mechanical System Operation

Existing Mechanical System Operation majority of the air handlers. There are louvers along the north side of the building that allow for outdoor air to come in and feed the air handlers. On levels 4-8 the research laboratories are variable

More information

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement International Conference Passive and Low Energy Cooling 651 Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic VAV Systems One of the Systems Series July 2012 TRG-TRC014-EN VAV Systems One of the Systems Series A publication of Trane Preface VAV Systems A Trane Air Conditioning Clinic Figure

More information

APPLICATION, INSTALLATION, AND MAINTENANCE MANUAL CA2XRT, CA3XRT, CA4XRT

APPLICATION, INSTALLATION, AND MAINTENANCE MANUAL CA2XRT, CA3XRT, CA4XRT 4510 Helgesen Drive, Madison, WI 53718 (608) 221-4499, (800) 627-4499, Fax: (608) 221-2824 support@renewaire.com www.renewaire.com APPLICATION, INSTALLATION, AND MAINTENANCE MANUAL CA2XRT, CA3XRT, CA4XRT

More information

THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS

THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS Prepared for the: RPIC/SLCan Sustainable Labs Regional Workshop Presented by: THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY

More information

EU Air Handling Units with SEMCO EXCLU-SIEVE

EU Air Handling Units with SEMCO EXCLU-SIEVE EU Air Handling Units with SEMCO EXCLU-SIEVE The acquisition of US based Semco has given us the opportunity to include a new range of rotary heat exchangers in our EU air handling unit range. Hygienic

More information

Poultry Housing Tips Radiant Tube Heater Floor Heating Patterns Volume 17 Number 5 April, 2005

Poultry Housing Tips Radiant Tube Heater Floor Heating Patterns Volume 17 Number 5 April, 2005 The University of Georgia Cooperative Extension Service College of Agricultural and Environmental Science/Athens, Georgia 30602-4356 Poultry Housing Tips Radiant Tube Heater Floor Heating Patterns Volume

More information

Big Board Rework. Joerg Nolte Ersa GmbH Wertheim, Germany

Big Board Rework. Joerg Nolte Ersa GmbH Wertheim, Germany Big Board Rework Joerg Nolte Ersa GmbH Wertheim, Germany Abstract As indicated in previous abstracts to the rework topic, customer demands in the field of PCB repair are constantly increasing. Lately technical

More information

2. HEAT EXCHANGERS MESA

2. HEAT EXCHANGERS MESA 1. INTRODUCTION Multiport minichannel and microchannel aluminium tubes are becoming more popular as components in heat exchangers. These heat exchangers are used in various industrial applications and

More information

Heating and Air-Conditioning Testing II. Climatic Test Bench

Heating and Air-Conditioning Testing II. Climatic Test Bench Heating and Air-Conditioning Testing II Climatic Test Bench Heating and Air-Conditioning Testing II Climatic Test Bench Content IAV's Climatic Test Benches 4 Mobile Coolant Circuit 6 Evaporator Air Treatment

More information

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Mingsheng Liu, Ph.D., P.E. Energy Systems Laboratory Texas A&M University College Station, Texas

More information

THE PROMISE THE PROOF HEATEX AIR-TO-AIR HEAT EXCHANGERS

THE PROMISE THE PROOF HEATEX AIR-TO-AIR HEAT EXCHANGERS E THE PROMISE THE PROOF HEATEX AIR-TO-AIR HEAT EXCHANGERS ROTARY HEAT EXCHANGERS Heatex offers a broad range of rotary heat exchangers covering the complete application span from small residential installations

More information

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608) FORM ASX-40021 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SM-501 Series Smoke Detectors, Model EXSAC and EXSAD (Ionization), EXSAJ and EXSAK (Photoelectric) Air Specialties Express, 448 S. Main

More information

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Siddharth Jain, Yogesh Deshpande, Atul Bokane, Arun Kumar Santharam, and Deepak Babar, Halliburton Abbreviations: Computational

More information

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications Heat Recovery Ventilation Systems Data Sheet PA600LI The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications Houses ranging in size from 100 300 M2

More information

REMOVAL OF AIR BORN MICRO-ORGANISM

REMOVAL OF AIR BORN MICRO-ORGANISM REMOVAL OF AIR BORN MICRO-ORGANISM Imtech DryGenic helps industries to produce better quality products in a bacteria-free, clean and controlled temperature/humidity environment while minimising utility

More information

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS ARE BASED UPON LIVE FIRE TESTING OF PREP STATIONS

More information

M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys. Enabling Wellbeing

M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys. Enabling Wellbeing M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys Enabling Wellbeing M.A.R.V.E.L. revolutionises energy footprint in galleys The M.A.R.V.E.L.* is the first truly intelligent,

More information

Mikael Börjesson Product manager. Commercial air handling units Ventilation functionality Building management system integration

Mikael Börjesson Product manager. Commercial air handling units Ventilation functionality Building management system integration Mikael Börjesson Product manager Commercial air handling units Ventilation functionality Building management system integration Topics Presentation of the new generation of compact air handling units,

More information

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 SAE Alternate Refrigerant Cooperative Research Program Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 To: Alternate Refrigerant Task Force Members From: Ward Atkinson

More information

VERSO Air Handling Units

VERSO Air Handling Units VERSO Air Handling Units Energy efficient solutions for profitable indoor climate VERSO Air Handling Units VERSO-S air supply units VERSO-R air handling units equipped with regeneration system VERSO-P

More information

Purdue e-pubs. Purdue University

Purdue e-pubs. Purdue University Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 206 Experimental Investigation of the Refrigerant Flow Distribution Characteristic

More information

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications Heat Recovery Ventilation Systems Data Sheet PA600LI The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications Houses ranging in size from 100 300 M2

More information

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120 1 General The heat exchanger control system is a control system for 380 W step motors

More information

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction: Refrigeration Systems Theoretical hours: 2 Practical hours: 2 Units: 6 COOLING TOWERS First 10 minutes: review the last lecture. Then explain the new lecture, solve an example. Last 10 minutes review the

More information

Benefits Offered by Passive Dehumidification Wheel Speed Control

Benefits Offered by Passive Dehumidification Wheel Speed Control Benefits Offered by Passive Dehumidification Wheel Speed Control White paper By John Fischer Benefits Offered by Passive Dehumidification Wheel Speed Control The most significant advantage of the Pinnacle

More information

CHAPTER 4. HVAC DELIVERY SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer

More information

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE Satoru Ito 1, Keisuke Tsukada 1, Nobuyoshi Tsuzuki 2, Takao Ishizuka 3 and Hiroshige Kikura 3 1 Department of nuclear Engineering, Graduate

More information

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat Abstract Axial flow fans, while incapable of developing high pressures, they are well suitable for handling large volumes of air at relatively

More information

Important Considerations When Selecting a Fan for Forced Air Cooling. By: Jeff Smoot, CUI Inc

Important Considerations When Selecting a Fan for Forced Air Cooling. By: Jeff Smoot, CUI Inc Important Considerations When Selecting a Fan for Forced Air Cooling By: Jeff Smoot, CUI Inc Designing an appropriate thermal management solution requires a systemic approach; each component on a circuit

More information

WET POSITION BOOSTER FANS FOR REDUCED POWER CONSUMPTION AND OPTIMIZED ENVIRONMENTAL PERFORMANCE OF POWER STATIONS WITH FGD AND WET STACK

WET POSITION BOOSTER FANS FOR REDUCED POWER CONSUMPTION AND OPTIMIZED ENVIRONMENTAL PERFORMANCE OF POWER STATIONS WITH FGD AND WET STACK WET POSITION BOOSTER FANS FOR REDUCED POWER CONSUMPTION AND OPTIMIZED ENVIRONMENTAL PERFORMANCE OF POWER STATIONS WITH FGD AND WET STACK Authors: Lewis Maroti and David Anderson Alden Research Laboratory,

More information

Don t Turn Active Beams Into Expensive Diffusers

Don t Turn Active Beams Into Expensive Diffusers This article was published in ASHRAE Journal, April 2012. Copyright 2012 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be

More information

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance #1 Jaydev S. Bade, #2 Dr. Nitin U. Korde 1 Department of Mechanical Engineering, Savitribai Phule

More information

Incorporating Aluminum Honeycomb to Increase Efficiency of U-tube Removable Heat Exchanger

Incorporating Aluminum Honeycomb to Increase Efficiency of U-tube Removable Heat Exchanger Incorporating Aluminum Honeycomb to Increase Efficiency of U-tube Removable Heat Exchanger Daniel Soto 1 and Daniel Corona 2 California Polytechnic State University, San Luis Obispo, San Luis Obispo, California,

More information

How to improve air cooler vacuum steam condensers performance in the field

How to improve air cooler vacuum steam condensers performance in the field How to improve air cooler vacuum steam condensers performance in the field By Marc Ellmer ELFLOW BV The Netherlands Introduction Air cooled vacuum steam condensers (ACC s) are used to condense exhaust

More information

Improved Thermal Comfort & Energy Efficiency with low-pressure VAV diffusion design

Improved Thermal Comfort & Energy Efficiency with low-pressure VAV diffusion design Improved Thermal Comfort & Energy Efficiency with low-pressure VAV diffusion design Technical Paper A guide to the design of an effective low pressure VAV air distribution system By Noel de Villiers Pr.

More information

What is the correct type of fan: Axial, radial, diagonal?

What is the correct type of fan: Axial, radial, diagonal? Press News The theory and practice of small fans (1) What is the correct type of fan: Axial, radial, diagonal? Fans are as varied in their construction as they are in their applications. These "air-donors"

More information

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance Jong Min Choi, W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building

More information

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM Mingjie Zheng Research Laboratory, SANKO AIR CONDITIONING CO., LTD. Nagoya, 450-0003, JAPAN ABSTRACT In large

More information

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

Application of a hybrid control of expansion valves to a 3-ton large room cooling system 2123, Page 1 Application of a hybrid control of expansion valves to a 3-ton large room cooling system Christian K. Bach*, Eckhard A. Groll, James E. Braun Ray W. Herrick Laboratories, Purdue University,

More information

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Introduction: Energy use is the single largest operating expense in commercial office

More information

Understanding the different sources of undesirable moisture in HVAC systems can help prevent or solve moisture-related problems.

Understanding the different sources of undesirable moisture in HVAC systems can help prevent or solve moisture-related problems. providing insights for today s hvac system designer Engineers Newsletter volume 46 4 Condensation in Air-Handling Systems In HVAC systems, undesired moisture on surfaces can cause damage to building materials

More information

There are two devices used together for heating crude oil in petroleum refinery as in figure (1), and these devices are:

There are two devices used together for heating crude oil in petroleum refinery as in figure (1), and these devices are: Heating of Crude Oil 1.Introduction: There are two devices used together for heating crude oil in petroleum refinery as in figure (1), and these devices are: Heat Exchangers. Tube Still Heaters (Furnaces).

More information

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY L Fang 1,2,, G Zhang 1,2 and PO Fanger 1,2 1 International Centre for Indoor Environment and Energy,

More information

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air Anna Pacak 1,*, Andrzej Jedlikowski 1, Demis Pandelidis 1, and Sergey Anisimov 1 1 Wrocław University of

More information

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation Downloaded from orbit.dtu.dk on: Mar 02, 2018 Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation Wu, Xiaozhou; Fang, Lei; Olesen, Bjarne

More information

Understanding Process Vacuum for Process Improvement

Understanding Process Vacuum for Process Improvement Understanding Process Vacuum for Process Improvement Through this article we wish to give practical tips to boost process capacity, increase product quality and reduce cycle time in batch or continuous

More information

Measuring And Understanding Energy Efficiency

Measuring And Understanding Energy Efficiency 28Mar2011 www.fahrenergy.co.uk P: 1 Measuring And Understanding Energy Efficiency Knowledge makes the difference. It is the base for improvements. INSTRUMENTS NEEDED... 1 INTRODUCTION... 2 ENERGY RECOVERY

More information

EP SERIES PACKAGED ENERGY RECOVERY SYSTEM ENERGY EFFICIENT AIR COMFORT

EP SERIES PACKAGED ENERGY RECOVERY SYSTEM ENERGY EFFICIENT AIR COMFORT ENERGY EFFICIENT AIR COMFORT EP SERIES PACKAGED ENERGY RECOVERY SYSTEM Certified total energy recovery performance (sensible and latent) up to 90% efficient. Double-wall panel construction eliminates exposed

More information

Air is our element. energy recovery our passion. Rotors overview. Quick guide GOST VDI 6022

Air is our element. energy recovery our passion. Rotors overview. Quick guide GOST VDI 6022 Rotors overview Quick guide GOST VDI 622 Rotors overview Rotor type Heat recovery Preferred application Wave heigh Thickness of material Condensations Rotor P/PT [ C] 1% Summer Winter 7 1 1-1 - [g/kg]

More information

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size) www.blowtech.in we make air move Blowtech Air Devices Pvt. Ltd. was founded in 1988 and quickly established

More information

Desiccant Cooling with Solar Energy

Desiccant Cooling with Solar Energy Desiccant Cooling with Solar Energy Gerrit Höfker 1,2, Ursula Eicker 2, Kevin Lomas 1, Herbert Eppel 1 1 De Montfort University Leicester, Institute of Energy and Sustainable Development 2 Hochschule für

More information

Microgrid Fault Protection Based on Symmetrical and Differential Current Components

Microgrid Fault Protection Based on Symmetrical and Differential Current Components Microgrid Fault Protection Based on Symmetrical and Differential Current Components Prepared for Public Interest Energy Research California Energy Commission Prepared by Hassan Nikkhajoei and Robert H.

More information

Air distribution for clean rooms. Clever and flexible.

Air distribution for clean rooms. Clever and flexible. Air distribution for clean rooms. Clever and flexible. X-CUBE CROFCU increases the efficiency The quasi plug-in construction of the X-CUBE CROFCU reduces the installation time on site considerably. More

More information

Environmentally Sound Solutions for Ventilation

Environmentally Sound Solutions for Ventilation NATO/CCMS Sustainable Building for Military Infrastructure Environmentally Sound Solutions for Ventilation Hans Martin Mathisen Energy Processes 2005-09-21 Outline of presentation Ventilation principles:

More information

Effect of Insulation on the Growth of Radish Plants- Cultivated Radish ( Raphanus sativus L.) Danielle Griggs, Meher Pandher, Avni Mehta, Meghan Royle

Effect of Insulation on the Growth of Radish Plants- Cultivated Radish ( Raphanus sativus L.) Danielle Griggs, Meher Pandher, Avni Mehta, Meghan Royle Effect of Insulation on the Growth of Radish Plants- Cultivated Radish ( Raphanus sativus L.) Danielle Griggs, Meher Pandher, Avni Mehta, Meghan Royle Section 1 June 10th, 2013 Mr. Fusco 1 Abstract: Research

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001 This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.

More information

Pharmaceutical Facility Design

Pharmaceutical Facility Design PhEn-602 Pharmaceutical Facility Design J. Manfredi Notes 9A PhEn-602 J. Manfredi 1 Primary & Secondary HVAC units Primary Primary air handling unit arrangement: One unit is responsible for all of the

More information

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop Energy-Savings Strategies for Rooftop VAV Systems Occupied set-point temperature Unoccupied set-point temperature Rooftop variable-air-volume (VAV) s are used to provide comfort in a wide range of building

More information

Review on Waste Heat Recovery Techniques in Air Conditioning Application

Review on Waste Heat Recovery Techniques in Air Conditioning Application International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Review Article Review

More information

11th Conference on Advanced Building Skins

11th Conference on Advanced Building Skins 11th Conference on Advanced Building Skins 10-11 October 2016, Bern, Switzerland ISBN: 978-3-98120539-8 Advanced Building Skins GmbH Hostettstr. 30 CH-6062 Wilen (Sarnen) Switzerland VAT: CHE-383.284.931

More information

Laboratory study of the effects of green roof systems on noise reduction at street levels for diffracted sound

Laboratory study of the effects of green roof systems on noise reduction at street levels for diffracted sound Laboratory study of the effects of green roof systems on noise reduction at street levels for diffracted sound Hongseok Yang 1), Minsung Choi 2), Jian Kang 3) 1) School of Architecture, University of Sheffield,

More information

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does

More information