Daytona Beach Pier Building Renovation Jun 2010 SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

Size: px
Start display at page:

Download "Daytona Beach Pier Building Renovation Jun 2010 SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS"

Transcription

1 SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the following components and accessories: 1. Direct-expansion cooling. 2. Hot-gas reheat. 3. Electric-heating coils. 4. Integral, space temperature controls. 5. Roof curbs. 1.3 DEFINITIONS A. RTU: Rooftop unit. As used in this Section, this abbreviation means packaged, outdoor, central-station air-handling units. This abbreviation is used regardless of whether the unit is mounted on the roof or on a concrete base on ground. B. Supply-Air Fan: The fan providing supply air to conditioned space. "Supply air" is defined as the air entering a space from air-conditioning, heating, or ventilating apparatus. C. Supply-Air Refrigerant Coil: Refrigerant coil in the supply-air stream to absorb heat (provide cooling) during cooling operations. "Supply air" is defined as the air entering a space from airconditioning, heating, or ventilating apparatus. 1.4 SUBMITTALS A. Product Data: Include manufacturer's technical data for each RTU, including rated capacities, dimensions, required clearances, characteristics, furnished specialties, and accessories. B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection. 1. Wiring Diagrams: Power, signal, and control wiring. C. Coordination Drawings: Plans and other details, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved: PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

2 1. Structural members to which RTUs will be attached. 2. Roof openings 3. Roof curbs and flashing. D. Field quality-control test reports. E. Operation and Maintenance Data: For RTUs to include in emergency, operation, and maintenance manuals. F. Warranty: Special warranty specified in this Section. 1.5 QUALITY ASSURANCE A. ARI Compliance: 1. Comply with ARI 210/240 and ARI 340/360 for testing and rating energy efficiencies for RTUs. 2. Comply with ARI 270 for testing and rating sound performance for RTUs. B. ASHRAE Compliance: 1. Comply with ASHRAE 15 for refrigeration system safety. 2. Comply with ASHRAE 33 for methods of testing cooling and heating coils. C. NFPA Compliance: Comply with NFPA 90A and NFPA 90B. D. UL Compliance: Comply with UL E. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. 1.6 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to replace components of RTUs that fail in materials or workmanship within specified warranty period. 1. Warranty Period for Compressors: Manufacturer's standard, but not less than five years from date of Substantial Completion. 2. Warranty Period for Control Boards: Manufacturer's standard, but not less than three years from date of Substantial Completion. PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

3 PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated in the schedule at the end of this section or a comparable product by one of the following: 1. AAON, Inc. 2. Addison Products Company. 3. Carrier Corporation. 4. Engineered Air. 5. Lennox Industries Inc. 6. McQuay International. 7. Trane; American Standard Companies, Inc. 8. YORK International Corporation. 2.2 CASING A. General Fabrication Requirements for Casings: Formed and reinforced double-wall insulated panels, fabricated to allow removal for access to internal parts and components, with joints between sections sealed. B. Exterior Casing Material: G90 galvanized steel on both sides with factory-painted finish on the exterior side, with pitched roof panels and knockouts with grommet seals for electrical and piping connections and lifting lugs. 1. Exterior Casing Thickness: inch thick for 6-ton size and smaller and inch thick for larger sizes. 2. Finish: Corrosion resistant polyurethane paint exceeding 2,500 hour salt spray test. C. Inner Casing Fabrication Requirements: 1. Inside Casing: G90 galvanized steel, inch thick for 6-ton size and smaller and inch thick for larger sizes. D. Casing Insulation and Adhesive: 2-inch double wall foam panel cabinet construction. Comply with NFPA 90A or NFPA 90B. 1. Material: Rigid polyurethane foam. 2. Thickness: 2 inch. 3. R-value: 13 minimum. 4. Thermal breaks: casing constructed with thermal breaks so no metal contact from inside to outside. E. Condensate Drain Pans: Double sloped stainless-steel sheet, a minimum of 2 inches deep, and complying with ASHRAE PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

4 1. Double-Wall Construction: Fill space between walls with foam insulation and seal moisture tight. 2. Drain Connections: Threaded nipple both sides of drain pan. F. Airstream Surfaces: Surfaces in contact with the airstream shall comply with requirements in ASHRAE FANS A. Direct-Driven Supply-Air Fans: Double width, backward inclined, centrifugal; with permanently lubricated, motor resiliently mounted in the fan inlet. Aluminum or painted-steel wheels, and galvanized- or painted-steel fan scrolls. B. Condenser-Coil Fan: Propeller, mounted on shaft of permanently lubricated motor. C. Fan Motor: Comply with requirements in Division 15 Section "Motors." 2.4 COILS A. Supply-Air Refrigerant Coil: 1. Copper-plate fin and seamless copper tube in steel casing with equalizing-type vertical distributor. a. Polymer strip shall prevent all copper coils from contacting steel coil frame or condensate pan. 2. Coil Split: Interlaced. 3. Polymer E-Coated. 4. Condensate Drain Pan: Stainless steel formed with pitch and drain connections complying with ASHRAE B. Outdoor-Air Refrigerant Coil: 1. Copper-plate fin and seamless copper tube in steel casing with equalizing-type vertical distributor. a. Polymer strip shall prevent all copper coils from contacting steel coil frame or condensate pan. 2. Polymer E-Coated. C. Hot-Gas Reheat Refrigerant Coil: 1. Copper-plate fin and seamless copper tube in steel casing with equalizing-type vertical distributor. a. Polymer strip shall prevent all copper coils from contacting steel coil frame or condensate pan. PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

5 2. Polymer E-Coated. D. Electric-Resistance Heating: 1. Open Heating Elements: Resistance wire of 80 percent nickel and 20 percent chromium, supported and insulated by floating ceramic bushings recessed into casing openings, fastened to supporting brackets, and mounted in galvanized-steel frame. Terminate elements in stainless-steel machine-staked terminals secured with stainless-steel hardware. 2. Overtemperature Protection: Disk-type, automatically reset, thermal-cutout, safety device; serviceable through terminal box. 3. Overcurrent Protection: Manual-reset thermal cutouts, factory wired in each heater stage. 4. Control Panel: Unit mounted with disconnecting means and overcurrent protection. Include the following controls: a. Magnetic or Mercury contactors. b. Step Controller: Pilot lights and override toggle switch for each step. c. Time-delay relay. d. Airflow proving switch. 2.5 REFRIGERANT CIRCUIT COMPONENTS A. Number of Refrigerant Circuits: as indicated in the Schedule. B. Compressor: Hermetic, variable-capacity scroll, mounted on vibration isolators; with internal overcurrent and high-temperature protection, internal pressure relief, and crankcase heater. C. Refrigeration Specialties: 1. Refrigerant: R-407C or R-410A. 2. Expansion valve with replaceable thermostatic element. 3. Refrigerant filter/dryer. 4. Manual-reset high-pressure safety switch. 5. Automatic-reset low-pressure safety switch. 6. Minimum off-time relay. 7. Automatic-reset compressor motor thermal overload. 8. Brass service valves installed in compressor suction and liquid lines. 9. Low-ambient kit high-pressure sensor. 10. Fully modulating hot-gas reheat control valves. 2.6 AIR FILTRATION A. Minimum arrestance according to ASHRAE 52.1, and a minimum efficiency reporting value (MERV) according to ASHRAE Pleated: Minimum 90 percent arrestance, and MERV 7. PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

6 2.7 DAMPERS A. Outdoor-Air Damper: Linked damper blades, for 0 to 25 percent outdoor air, with motorized damper and filter. 2.8 ELECTRICAL POWER CONNECTION A. Provide for single connection of power to unit with unit-mounted disconnect switch accessible from outside unit and control-circuit transformer with built-in overcurrent and phase loss protection. 2.9 CONTROLS A. Control devices, including sensors, transmitters, relays, switches, thermostats, humidistats, CO2 sensor, operators, actuators, and valves, shall be manufacturer's standard items to accomplish indicated control functions SEQUENCE OF OPERATION A. HVAC Modes of Operation 1. Cooling 2. Heating 3. Ventilation 4. Dehumidification 5. Off B. Cooling Mode: 1. Cooling is enabled when the temperature at the Mode Enable Sensor rises one deadband above the Cooling Setpoint. Cooling is disabled when the Mode Enable temperature falls one deadband below the Cooling Setpoint. The setpoint and deadband are user adjustable. 2. Once in the Cooling Mode the unit will stage or modulate cooling to maintain the Supply Air Temperature at the Active Supply Air Cooling Setpoint (See Reset Temperature Sources section for explanation). C. Heating Mode: 1. Staged Electric. 2. Multiple stages of heating: (See Relay Outputs Section) subject to minimum run times, minimum off times, staging up and staging down delays. 3. Heating is enabled when the temperature at the Mode Enable Sensor falls one deadband below the Heating Setpoint. Heating is disabled when the Mode Enable temperature rises one deadband above the Heating Setpoint. 4. Once in the Heating Mode the unit will stage or modulate heating to maintain the Supply Air Temperature at the Active Supply Air Heating Setpoint (See Reset Temperature Sources section for explanation). PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

7 D. Ventilation Mode: 1. This is only available in the Occupied Mode of operation and is generated anytime there is no demand for heating or cooling. The supply fan operates for recirculation. E. Dehumidification Mode: 1. Dehumidification is enabled based on a Space Humidity Setpoint from a Space Humidity Sensor. 2. Once in DX Dehumidification, cooling is staged to maintain the Evaporator Coil Suction Temperature at the Coil Suction Temperature Setpoint so as to achieve the maximum dehumidification. A Coil Suction Pressure Sensor is required and is factory installed. 3. Dehumidification can be selected as a priority mode; otherwise it is only available when heating and cooling demands are satisfied. 4. Reheat is always controlled to the Active Supply Air Temperature Setpoint which will be different during Heating, Cooling, or Vent Modes. During Vent Mode the Supply Air Temperature Setpoint is calculated to be halfway between the HVAC Mode Setpoints. 5. Reheat options are modulating or fixed hot gas reheat, field wired downstream duct heat, and, in certain applications, unit heat. F. Off Mode 1. Occurs in the Unoccupied Mode when there is no heating, cooling or dehumidification demand. 2. Supply fan is off and the outside air damper is closed. G. Mode Enable Sensor Options: The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options shall be available: 1. Space Air Temperature Sensor 2. Return Air Temperature Sensor H. Supply Air Temperature Setpoint Reset: The controller shall be configured to use various sources to reset the Supply Air Temperature Setpoint. Since the Supply Air Temperature Setpoints are not fixed during reset, they are Active Supply Air Temperature Setpoints. The following options are available. 1. Return Air Temperature a. The controller will automatically modulate the Supply Air Setpoint to deliver the desired Control Cooling or Heating Setpoint for the selected reset temperature 2. Space Air temperature a. The controller shall automatically modulate the Supply Air Setpoint to deliver the desired Control Cooling or Heating Setpoint for the selected reset temperature b. The Slide Adjust feature on the Space Sensor can be used to remotely raise or lower the SAT/Reset Source heating and cooling setpoints. 3. Remote SAT Reset (0-5 VDC or (0-10 VDC w/resistor network)) PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

8 a. The controller shall proportionally reset the Supply Air Setpoint from the SAT/Reset Source setpoints to the Remote SAT Reset setpoints during the Heating or Cooling Mode based on a 0-5VDC signal from another BAS system. b. When this feature is used the Slide Adjust feature on the Space Sensor is not available. I. Coil Suction Temperature Setpoint Reset 1. During dehumidification the controller shall automatically reset the Coil Suction Temperature Setpoint within a ± 5 range based on the space or return air humidity sensor condition changing ± 5 % from the humidity setpoint. J. Occupied Operation: 1. Internal week schedule with 2 start/stops per day available 2. Remote Forced Occupied contact closure 3. Pushbutton Override button on a Space Sensor (Override length is user adjustable) 4. Monitoring an external Orion scheduling device 5. Forced Occupied command from an Orion Operator Interface device K. Unoccupied Operation 1. Uses only space conditions for mode selection 2. Uses Night Setback Setpoints for heating and cooling calls and normal dehumidification setpoints for dehumidification calls. 3. If there is no call for heating, cooling or dehumidification the unit will be off. L. Space Sensor Operation 1. Sensor with Override and Setpoint Slide Adjust. a. Allow space setpoint adjustment of up to ± 6 F. 2. The Slide Adjust can adjust the setpoint of whichever temperature sensor is configured as the controlling sensor, even if it is not the installed Space Sensor. If Space Temperature is the SAT/Reset Source, then the Slide Adjust will adjust the HVAC Mode Enable setpoints and the SAT/Reset Source setpoints simultaneously. 3. During Unoccupied hours the Override Button can be used to force the unit back into the Occupied Mode (by pressing the button for less than 3 seconds) for a user-defined override duration of up to 8.0 hours. Pressing the button between 3 and 10 seconds cancels the override. M. Outdoor Air Lockouts 1. Mechanical cooling is disabled when the Outdoor Air Temperature is below the Cooling Lockout Setpoint. 2. Mechanical heating is disabled when the Outdoor Air Temperature is above the Heating Lockout Setpoint. N. Temperature Protection PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

9 1. Activated when the Supply Air Temperature (SAT) rises above the High Cutoff Temperature (immediate) or drops below the Low Cutoff Temperature (for 10 minutes) both of which are user adjustable. This mode shuts off the unit (with a 3 minute fan off delay) until the mode is cancelled. 2. This mode is cancelled when the SAT drops 10 degrees below the High Cutoff Temperature Setpoint or rises 10 degrees above the Low Temp Cutoff Temperature Setpoint, or when the unit changes back into Occupied Operation. O. Relay Outputs: Provide 20 output relays that that are configurable for the controller (Relay #1 is reserved for the Supply Fan and is not configurable). The configuration options are as follows: 1. Heating Stages: Economizer (Indicator or additional function) 2. On/Off Hot Gas Reheat: Alarm (Indicator or additional function) P. Scheduling 1. Utilizes a Real Time Clock with an internal power source that allows the controller to keep time and allows for scheduling. 2. Has an internal 7 day schedule with 2 start/stops per day. 3. Allows scheduling of up to 14 holiday periods per year. Q. Alarm Detection and Reporting 1. Continuously performs self diagnostics during normal operations to determine if any operating failures have occurred. 2. These failure (alarms) can be reported to a wall mounted System Manager (requires a MiniLink Polling Device), a hand-held Modular Service Tool, the Tactio SI Touchscreen Interface, or to a computer running Prism II software. 3. Diagnostic LEDs on the controller will generate blink codes for certain alarm conditions. 4. The following are the available alarm designations for the Controller: R. Trend Logging a. No Supply Sensor b. Bad outdoor Air Temp c. Space Sensor Failure d. Mechanical Cooling Failure e. Mechanical Heating Failure f. Fan Proving Alarm g. Dirty Filter Alarm h. Smoke Alarm i. Low Supply Air Alarm j. High Supply Air Alarm k. Low Control Temp Alarm l. High Control Temp Alarm 1. Continuously maintains an Internal Trend Log in memory on the controller which records a fixed set of values at a user-defined interval log positions (timed retrievals) are available on the controller. 3. Once these positions are full, it begins overwriting the oldest data. PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

10 4. Values can be retrieved using the Prism II graphical front-end software program. 5. With Prism running continuously, values can be saved to the computer hard drive at regular intervals to keep from losing data. 6. The following are the fixed items, when used, that can be logged: a. Date b. Time c. Space Temperature d. Return Air Temperature e. Outdoor Air Temperature f. Active Cooling Setpoint g. Active Heating Setpoint h. Supply Air Temperature i. Active Supply Air Temp Setpoint j. Outdoor Air Humidity k. Indoor Air Humidity l. Duct Static Pressure m. Building Static Pressure n. Economizer Signal Percentage o. Supply Fan VFD/Bypass Damper Signal Percentage p. Exhaust Fan VFD/Exhaust Damper Signal Percentage q. Modulating Heat Signal Percentage r. Modulating Cool Signal Percentage s. On Board Relay Status (BIT Pattern) t. Expansion Board Relay Status (BIT Pattern) 2.11 ACCESSORIES A. Electric heater with integral thermostat maintains minimum 50 deg F temperature in gas burner compartment. B. Duplex, 115-V, ground-fault-interrupter outlet with 15-A overcurrent protection. Include transformer if required. Outlet shall be energized even if the unit main disconnect is open. C. Low-ambient kit using damper or variable-speed condenser fans for operation down to 35 deg F. D. Coil guards of painted, galvanized-steel wire ROOF CURBS A. Materials: Galvanized steel with corrosion-protection coating, watertight gaskets, and factoryinstalled wood nailer; complying with NRCA standards. 1. Curb Insulation and Adhesive: Comply with NFPA 90A or NFPA 90B. a. Materials: ASTM C 1071, Type I or II. b. Thickness: 2 inches. PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

11 2. Application: Factory applied with adhesive and mechanical fasteners to the internal surface of curb. a. Liner Adhesive: Comply with ASTM C 916, Type I. b. Mechanical Fasteners: Galvanized steel, suitable for adhesive attachment, mechanical attachment, or welding attachment to duct without damaging liner when applied as recommended by manufacturer and without causing leakage in cabinet. c. Liner materials applied in this location shall have air-stream surface coated with a temperature-resistant coating or faced with a plain or coated fibrous mat or fabric depending on service air velocity. d. Liner Adhesive: Comply with ASTM C 916, Type I. B. Curb Height: 14 inches CAPACITIES AND CHARACTERISTICS A. Refer to Schedules at the end of this Section for capacities, characteristics, and additional basis of design criteria. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of RTUs. B. Examine roughing-in for RTUs to verify actual locations of piping and duct connections before equipment installation. C. Examine roofs for suitable conditions where RTUs will be installed. D. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. Roof Curb: Install on roof structure or concrete base, level and secure, according to NRCA's "Low-Slope Membrane Roofing Construction Details Manual," Illustration "Raised Curb Detail for Rooftop Air Handling Units and Ducts. Install RTUs on curbs and coordinate roof penetrations and flashing with roof construction specified in Division 7 Section "Roof Accessories." Secure RTUs to upper curb rail, and secure curb base to roof framing with anchor bolts. B. Install wind and seismic restraints according to manufacturer's written instructions. PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

12 3.3 CONNECTIONS A. Install condensate drain, minimum connection size, with trap and indirect connection to nearest roof drain or area drain. B. Install piping adjacent to RTUs to allow service and maintenance. C. Duct installation requirements are specified in other Division 15 Sections. Drawings indicate the general arrangement of ducts. The following are specific connection requirements: 1. Install ducts to termination at top of roof curb. 2. Remove roof decking only as required for passage of ducts. Do not cut out decking under entire roof curb. 3. Connect supply ducts to RTUs with flexible duct connectors specified in Division 15 Section "Duct Accessories." 4. Install return-air duct continuously through roof structure. 3.4 FIELD QUALITY CONTROL A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections. Report results in writing. 1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing. Report results in writing. B. Tests and Inspections: 1. After installing RTUs and after electrical circuitry has been energized, test units for compliance with requirements. 2. Inspect for and remove shipping bolts, blocks, and tie-down straps. 3. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. 4. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. C. Remove and replace malfunctioning units and retest as specified above. 3.5 STARTUP SERVICE A. Engage a factory-authorized service representative to perform startup service. B. Complete installation and startup checks according to manufacturer's written instructions and do the following: 1. Inspect for visible damage to unit casing. 2. Inspect for visible damage to compressor, coils, and fans. 3. Inspect internal insulation. 4. Verify that labels are clearly visible. PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

13 5. Verify that clearances have been provided for servicing. 6. Verify that controls are connected and operable. 7. Verify that filters are installed. 8. Clean condenser coil and inspect for construction debris. 9. Remove packing from vibration isolators. 10. Verify lubrication on fan and motor bearings. 11. Inspect fan-wheel rotation for movement in correct direction without vibration and binding. 12. Start unit according to manufacturer's written instructions. a. Start refrigeration system. b. Do not operate below recommended low-ambient temperature. c. Complete startup sheets and attach copy with Contractor's startup report. 13. Inspect and record performance of interlocks and protective devices; verify sequences. 14. Operate unit for an initial period as recommended or required by manufacturer. 15. Calibrate thermostats. 16. Adjust and inspect high-temperature limits. 17. Inspect outdoor-air dampers for proper stroke and interlock with return-air dampers. 18. Start refrigeration system and measure and record the following when ambient is a minimum of 15 deg F above return-air temperature: a. Coil leaving-air, dry- and wet-bulb temperatures. b. Coil entering-air, dry- and wet-bulb temperatures. c. Outdoor-air, dry-bulb temperature. d. Outdoor-air-coil, discharge-air, dry-bulb temperature. 19. Inspect controls for correct sequencing of heating, mixing dampers, refrigeration, and normal and emergency shutdown. 20. Measure and record the following minimum and maximum airflows. Plot fan volumes on fan curve. a. Supply-air volume. b. Return-air volume. c. Relief-air volume. d. Outdoor-air intake volume. 21. Simulate maximum cooling demand and inspect the following: a. Compressor refrigerant suction and hot-gas pressures. b. Short circuiting of air through condenser coil or from condenser fans to outdoor-air intake. 22. Verify operation of remote panel including pilot-light operation and failure modes. Inspect the following: a. Low-temperature safety operation. b. Filter high-pressure differential alarm. c. Firestat alarms. PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

14 23. After startup and performance testing and prior to Substantial Completion, replace existing filters with new filters. 3.6 CLEANING AND ADJUSTING A. Occupancy Adjustments: When requested within 12 months of date of Substantial Completion, provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to two visits to site during other-than-normal occupancy hours for this purpose. B. After completing system installation and testing, adjusting, and balancing RTU and airdistribution systems, clean filter housings and install new filters. 3.7 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain RTUs. Refer to Division 1 Section "Demonstration and Training." 3.8 SCHEDULES A. Schedules: Refer to the following schedules for additional basis of design criteria. PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

15 BASIS OF DESIGN ROOFTOP UNITS SCHEDULE PLAN IDENTIFICATION: RTU-1 RTU-2 RTU-3 LOCATION: BALLROOM REST RNT #1, 2 RESTAURANT #3 TYPE/ARRANGEMENT: SC / DNFLW SC / DNFLW SC / DNFLW MANUFACTURER: AAON AAON AAON MOD. NO.: RN EB19* RN EB19* RN EB19* AIR FLOW CFM / WG: CAPACITY TONS: TC / SC MBH: / / / LAT CAPACITY MBH: EER: ENT AIR TEMP DB / WB F: / / / LVG AIR TEMP DB / WB F: / / / EVAP COIL - SF / ROWS / FPI / FPM 19.9 / 6 / 12 / / 6 / 12 / / 6 / 14 / OUTSIDE AIR CFM:: REHEAT COIL CAP MBH: LVG AIR DB / WB F: 73.0 / / / Rh - %: REFRIGERANT: R-410A R-410A R-410A SUPPLY FAN MOTOR BHP / HP - TYPE: 3.89 / / / 2.0 RPM / WHEEL WIDTH: 1307 / / / 15.0 REHEAT KW / MBH: 45.0 / / / 51.2 STAGES / FLA: 2 / / / 41.6 COMPRESSOR QTY: CONDENSER FANS QTY: UNIT - VOLTS/PHASE/Hz: 208/3/60 208/3/60 208/3/60 MCA/MOCP: 187 / / / 70 UNIT FLA: WEIGHT POUNDS: ACCESSORIES/REMARKS: *COMPLETE AAON MODEL NUMBER: RTU-1 BALLRM: RN EB19-162:L000-E0H-DDG-B00-CH0CHBE-00-00A0000AB RTU-2 RESTRNT 1, 2: RN EB19-152:L000-E0H-DRF-B00-CH0CHBE-00-00A0000AB RTU-3 RESTRNT 3: RN EB19-121:L000-E0H-DBD-B00-CD0AHBE-00-00A0000AB PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

16 BASIS OF DESIGN ROOFTOP UNITS SCHEDULE PLAN IDENTIFICATION: RTU-4 RTU-5 RTU-6 LOCATION: KITCHEN GIFT SHOP OUTSIDE AIR TYPE/ARRANGEMENT: SC / DNFLW SC / DNFLW SC / DNFLW MANUFACTURER: AAON AAON AAON MOD. NO.: RN EB19* RM-A EB19* RN EB19* AIR FLOW CFM / WG: CAPACITY TONS: TC / SC MBH: / / / LAT CAPACITY MBH: EER: ENT AIR TEMP DB / WB F: 77.3 / / / LVG AIR TEMP DB / WB F: / / / EVAP COIL - SF / ROWS / FPI / FPM 19.9 / 6 / 12 / / 6 / 12 / / 6 / OUTSIDE AIR CFM:: REHEAT COIL CAP MBH: LVG AIR DB / WB F: / / / Rh - %: REFRIGERANT: R-410A R-410A R-410A SUPPLY FAN MOTOR BHP / HP - TYPE: 6.38 / / / 2.0 RPM / WHEEL WIDTH: 1279 / / / 27.4 REHEAT KW / MBH: 45.1 / / / STAGES / FLA: 2 / / / COMPRESSOR QTY: CONDENSER FANS QTY: UNIT - VOLTS/PHASE/Hz: 208/3/60 208/3/60 208/3/60 MCA/MOCP: 195 / / / 175 UNIT FLA: WEIGHT POUNDS: ACCESSORIES/REMARKS: *COMPLETE AAON MODEL NUMBER: RTU-4 KITCHEN: RN EB19-162:L000-E0H-DEH-B00-CH0CHBE-00-00A0000AB RTU-5 GIFT SHOP : RM-A EB19-121:L000-E0H-0BD-BA0-CD0AHBE-00-00A0000AB RTU-6 OSA: RN EB19-162:L00E-00H-DQP-B00-CH0CHBF-00-00A0000AB PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

17 BASIS OF DESIGN ROOFTOP UNITS SCHEDULE PLAN IDENTIFICATION: RTU-7 LOCATION: SKY LOUNGE TYPE/ARRANGEMENT: SC / DNFLW MANUFACTURER: AAON MOD. NO.: RN FB19* AIR FLOW CFM / WG: 1.25 CAPACITY TONS: 7.5 TC / SC MBH: / LAT CAPACITY MBH: EER: 10.7 ENT AIR TEMP DB / WB F: / LVG AIR TEMP DB / WB F: / EVAP COIL - SF / ROWS / FPI / FPM 8.5 / 6 / 14 / 300 OUTSIDE AIR CFM:: 500 REHEAT COIL CAP MBH: 54 LVG AIR DB / WB F: / Rh - %: 50 REFRIGERANT: R-410A SUPPLY FAN MOTOR BHP / HP - TYPE: 1.54 / 2.0 RPM / WHEEL WIDTH: 2157 / 15.0 REHEAT KW / MBH: 15.0 / 51.2 STAGES / FLA: 1 / 41.6 COMPRESSOR QTY: 1 CONDENSER FANS QTY: 1 UNIT - VOLTS/PHASE/Hz: 208/3/60 MCA/MOCP: 61 / 70 UNIT FLA: 49 WEIGHT POUNDS: 1149 ACCESSORIES/REMARKS: *COMPLETE AAON MODEL NUMBER: RTU-7 SKY LNGE: RN FB19-121:L000-E0H-DBD-B00-CD0A0BE-00-00A0000AB PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

18 AAON MODEL NUMBER LEGEND R ROOF TOP UNIT N NINTH GENERATION 025 / 013 / 007 / 005 / UNIT SIZE (NOMINAL TONS) VOLTS / 3 PHASE / 60 Hz 0 STANDARD INTERIOR PROTECTION E / F REFRIGERANT STYLE 410A VARIABLE CAPACITY SCROLL COMPRESSOR (E: HIGH EFFICIENCY) (F: STANDARD EFFIC) B AIR-COOLED CONDENSER (B: 6-ROW EVAP COIL) 1 (1: POLYMER E-COATED EVAP & COND) 9 COOL STAGING: MODULATING 1 VARIABLE COMPRESSOR; 1 ON/OFF 162 / 152 /121 (162: HEATING: ELECTRIC HEAT; kw; 2 STAGES) (152: ELECTRIC HEAT; kw; 2 STAGES) (121: ELECTRIC HEAT; 1-15 kw; 1 STAGES) L MOTORIZED OA DAMPER + RA OPENING 000 RA/EA BLOWER: STANDARD: NONE E OA CONTROL: DDC ACTUATOR 0 HEAT OPTIONS: STANDARD H MAINTENANCE OPTIONS: 115V CONVENIENCE OUTLET D / 0 (D: 1 SA BLOWER + INVERTER RATED MOTOR + VFD) (0: 1 SA BLOWER + STANDARD EFFICIENCY MOTOR) D / R / B / E / Q (D: SA BLOWER: 24 DIRECT DRIVE, PLENUM) (R: SA BLOWER: 22 DIRECT DRIVE) (B: SA BLOWER: 15 DIRECT DRIVE) (E & Q: SA BLOWER: 27 DIRECT DRIVE) G / F / D / H / P (G: 7.5 HP 1760 RPM) (F: 5 HP 1760 RPM) (D: 2 HP 1760 RPM) (H: 10 HP 1760 RPM) (P: 2 HP 1170 RPM) B B: METAL MESH OA PRE-FILTER 0 / A 0 & A: 2 PLEATED FILTER, 30% EFF 0 FILTER OPTIONS: STANDARD C REFRIGERATION CONTROL: FAN CYCLING H / D (H: REFRIGERATION OPTIONS: HOT GAS BYPASS LAG & MODULATING HOT GAS REHEAT) (D: REFRIGERATION OPTIONS: MODULATING HOT GAS REHEAT) 0 REFRIGERATION ACCESSORIES: STANDARD C / A POWER OPTIONS: POWER SWITCH: (C: 225 A) (A: 100 A) H & 0 SAFETY OPTIONS: REMOTE SMOKE DETECTOR TERMINALS- FILED INSTALLED DETECTOR B CONSTROLS: PHASE & BROWN OUT PROTECTION E / B SPECIAL CONTROLS: (E: CONSTANT VOLUME UNIT CONTROLLER-CV COOL + CV HEAT) (B: MAKE UP AIR UNIT CONTROLLER-CV COOL + CV HEAT) 000 PREHEAT: NONE 0 / A INTERIOR CABINET OPTIONS: DOUBLE WALL + R-13 FOAM INSULATION & STAINLESS STEEL DRAIN PAN A EXTERIOR CABINET OPTIONS: BASE INSULATION 0000 STANDARD ETL USA LISTING A CONTROL VENDOR: WATTMASTER CONTROLS B TYPE: STANDARE AAON GRAY PAINT END OF SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

Construction Standards Page

Construction Standards Page Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size...

More information

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components. Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 23 81 26 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

More information

C. Samples for Initial Selection: For units with factory-applied color finishes.

C. Samples for Initial Selection: For units with factory-applied color finishes. SECTION 238126- SPLIT-SYSTEM AIR-CONDITIONERS PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - Systems and Equipment. Page 238239-1 SECTION 238239 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

A. Section includes factory-packaged units capable of supplying up to 100 percent outdoor air and providing cooling and heating.

A. Section includes factory-packaged units capable of supplying up to 100 percent outdoor air and providing cooling and heating. SECTION 15850 PACKAGED DEDICATED OUTDOOR-AIR UNITS SPECIFIER: CSI MasterFormat 2004 number: 23 74 33. PART 1 GENERAL 1.1 RELATED SECTIONS A. 15960 Variable Frequency Drives. 1.2 SUMMARY A. Section includes

More information

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

Modular Supply Make-Up Air Unit

Modular Supply Make-Up Air Unit Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features

More information

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units TECHNICAL SPECIFICATIONS R7DA Series 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units 5.4 ISMRE Commercial System 81% Steady State Efficiency Standard Features Fits Pre-Existing Curbs High-Efficiency Low

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems. 15855 AIR HANDLING UNITS SPECIFIER: CSI MasterFormat 2004 number: 237313 PART 1 GENERAL 1.1 SUMMARY A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT SECTION 23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes packaged roof top unit, unit controls, remote panel, roof mounting curb and base, maintenance service,

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 WATER-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

SECTION (15767) - UNIT HEATERS

SECTION (15767) - UNIT HEATERS SECTION 23 82 39 (15767) - UNIT HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Unit Heaters. 2. Cabinet Unit Heaters. 3. Duct Heaters. 4. Baseboard Heaters. B. Related Sections: 1. Section

More information

VariCool VAV Engineering Guide

VariCool VAV Engineering Guide Engineering Guide Effective September 2017 Water-Cooled and Chilled Water, Variable Air Volume Contents Product Features... 3 UNIT FEATURES... 3 Product Features... 4 Marvel Plus Microprocessor Control

More information

SECTION ROOFTOP REPLACEMENT AIR UNITS

SECTION ROOFTOP REPLACEMENT AIR UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections, apply to this Section. B. Related

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

SECTION FAN COIL UNITS

SECTION FAN COIL UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

62DA,DB,DC,DD,DE,DF07-38

62DA,DB,DC,DD,DE,DF07-38 62D-3SB 62DA,DB,DC,DD,DE,DF07-38 DEDICATED VERTICAL OR HORIZONTAL 100% OUTDOOR AIR UNIT PERFORMANCE DATA UNIT DIMENSION PRINTS ACCESSORY DIMENSION PRINTS Copyright 2011 Carrier Corporation Syracuse, New

More information

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March GENERAL: 1. This section provides criteria for the design and installation of air handling units. DESIGN GUIDELINES: Design General 1. Location 1.1. For new construction, and existing buildings where possible,

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM SECTION 23 81 06 - PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. This Section includes equipment types that contain all the components of the refrigeration process within

More information

Modular Heating & Ventilating Unit Model IGX-HV

Modular Heating & Ventilating Unit Model IGX-HV Modular Heating & Ventilating Unit Model IGX-HV Indirect Gas-Fired Heating Evaporative Chilled Water DX Cooling October 2008 Product Features Model IGX-HV Indirect Gas-Fired Heating and Ventilating Unit

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS SECTION 23 62 13 - AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features: RL Packaged Rooftop Units, heat pumps and Outdoor air handling Units Features: Air-cooled condenser, water-cooled condenser, or patented AAON evaporative-cooled condenser, with capacities from 45-240 tons

More information

Submittal Data Performance Data Electrical Data

Submittal Data Performance Data Electrical Data ERMS Series Submittal Data Submittal Data Unit Designation: Job name: Architect: Engineer: Contractor: Performance Data Revision: 07/01/11 Cooling Capacity: EER: Heating Capacity: COP: Ambient Air Temp:

More information

Indirect Gas-Fired Make-Up Air

Indirect Gas-Fired Make-Up Air Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up

More information

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services Page 238216-1 Copyright 2003 and 2005 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 81 46 WATER-SOURCE UNITARY HEAT PUMPS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE CAS Product Specifications Single stage cooling capacity control on all models with Micro channel

More information

VertiCool Aurora Engineering Guide

VertiCool Aurora Engineering Guide Engineering Guide Effective August 2016 Air-Cooled, Water-Cooled and Water Source Heat Pump Contents Product Features... 3 Options... 4 Physical Data...5-6 Air-Cooled Performance Data (a) (b) (c)...7-8

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features: RZ PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS Features: Air-cooled condenser, water-cooled condenser, or evaporative-cooled condenser packaged rooftop units from 55-240 tons Water-source

More information

RT-OA TM Rooftop Outdoor-Air (DOAS)

RT-OA TM Rooftop Outdoor-Air (DOAS) RT-OA TM Rooftop Outdoor-Air (DOAS) A/C s & HEAT PUMPS Dedicated Outside-Air System (DOAS) Solutions Office Buildings, Schools, Hospitals, Restaurants, Gyms & Fitness Centers, Hotels, Retail Stores...!

More information

Your Home. Jacco & Assoc.

Your Home. Jacco & Assoc. Your Home Fan on with call for heating or cooling Heating on with call from space thermostat Stage as required to maintain The 75F Basics adj. - First stage of heating shall be heat pump Cooling on with

More information

SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT SECTION 23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT SPEC WRITER NOTE: 1. Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in the section and

More information

SECTION (15833) - HVAC POWER VENTILATORS

SECTION (15833) - HVAC POWER VENTILATORS PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

Direct Gas-Fired Make-Up Air Models DG and DGX

Direct Gas-Fired Make-Up Air Models DG and DGX Direct Gas-Fired Make-Up Air Models DG and DGX Commercial, Industrial and Kitchen Applications 800-48,000 cfm 4 in. wg External Static Pressure Direct Gas-Fired Heating Optional Cooling - Packaged DX (2.5

More information

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series.

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series. RN/RQ Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS RQ Series Features: Air-cooled or water-cooled condenser, with unit capacities

More information

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating Rooftop Ventilator with Packaged Cooling & Heating Models RV and RVE Institutional Commercial Industrial 800-1,500 cfm.0 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating Packaged

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

SECTION (15733) - DEDICATED OUTDOOR AIR UNITS

SECTION (15733) - DEDICATED OUTDOOR AIR UNITS PART 1 GENERAL 1.01 SUMMARY SECTION 23 74 33 (15733) - DEDICATED OUTDOOR AIR UNITS A. Section Includes: 1. Dedicated Outdoor-Air Units with Energy Recovery B. Related Sections: 1.02 REFERENCES 1. Section

More information

PAR5. Product Specifications

PAR5. Product Specifications TM PAR5 Product Specifications UP to 16 SEER, UP to 12.5 EER, PACKAGE AIR CONDITIONING UNITS, 2 5 TONS 208/230 Volt, 1 phase, 60 Hz 208/230 Volt, 3 phase, 60 Hz REFRIGERATION CIRCUIT Environmentally balanced

More information

SECTION AIR-SOURCE UNITARY HEAT PUMPS

SECTION AIR-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 81 43 AIR-SOURCE UNITARY HEAT PUMPS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

48PGD/E/F/L/M/N PG20-28

48PGD/E/F/L/M/N PG20-28 48/50PG-10SB 48PGD/E/F/L/M/N20-28 50PG20-28 SINGLE-PACKAGE COOLING UNITS WITH FACTORY-INSTALLED GAS HEAT SINGLE-PACKAGE COOLING UNITS WITH OPTIONAL ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINTS

More information

CxA to Answer this Section

CxA to Answer this Section EXHIBIT 01 91 13-3, SAMPLE Construction checklist items are to be completed as part of initial checkout and subsequent startup, preparatory to Functional testing. This checklist does not take the place

More information

Chilled Water DOAS Fan Powered Terminal Units

Chilled Water DOAS Fan Powered Terminal Units Chilled Water DOAS Fan Powered Terminal Units CHILLED WATER DOAS FAN POWERED TERMINAL UNITS DOAS TERMINAL UNITS FEATURES AND BENEFITS MINIMUM VENTILATION CONTROL The DOAS unit provides the Designer, Owner

More information

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL PREPARED FOR: DATE: JOB NAME: WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL EQUIPMENT DETAILS ITEM TAG DESCRIPTION MODEL NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 EQUIPMENT

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. Design and specify refrigeration systems and equipment in accordance with "Energy Conservation Standards" stipulated in Section 15010, Basic

More information

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc. System Components with ` Emphasis on Packaged Rooftop Application and Installation Jerry Cohen President Jacco & Assoc. Agenda Define and relate in practical terms the following components: System Effect

More information

engineering guide FH Fan-Coil Units Low-Profile, Horizontal

engineering guide FH Fan-Coil Units Low-Profile, Horizontal engineering guide FH Fan-Coil Units Low-Profile, Horizontal FORM 115.26-EG7 (908) Table of contents FH Fan-Coil Units Low-Profile, Horizontal Features and Benefits... Construction Features... Standard

More information

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS.

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS. RN/RQ Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS RQ Series Features: Air-cooled or water-cooled condenser, with unit capacities

More information

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/ 1 of 3 Cooling Capacity [Btuh] 24,800 * Condensing Unit SEER: 13.0 ** Condensing Unit CFM: 1,600 Condenser Fan No./Type: 1/CENTRIFUGAL Diameter x Width [in]: 10x10 Drive: Adjustable Belt Motor HP: 0.5

More information

Weathermaster Series 48HJ004, 005, 006, 007, 008, 009, 012 & 014 COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

Weathermaster Series 48HJ004, 005, 006, 007, 008, 009, 012 & 014 COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS 48HJ-13SB Weathermaster Series 48HJ004, 005, 006, 007, 008, 009, 012 & 014 COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINT

More information

48TF GAS HEATING/ ELECTRIC COOLING UNITS

48TF GAS HEATING/ ELECTRIC COOLING UNITS 48TF-4SB 48TF004-014 GAS HEATING/ ELECTRIC COOLING UNITS PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS Copyright 2005 Carrier Corporation Syracuse, New York 13221 Form

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz Product Data 50HS Single-Package Heat Pump Units 50 Hz Nominal: 7 to 18 kw (2 to 5 Tons) Single-Package Heat Pump for Manufactured Housing/Residential and Light Commercial use. Features/Benefits One-piece

More information

A. This Section includes air-handling units with coils for indoor installations.

A. This Section includes air-handling units with coils for indoor installations. SECTION 237313 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes air-handling units with coils for indoor installations. 1.2 SUBMITTALS A. Product Data: For each type of indoor air-handling unit

More information

50HS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP UNITS W/OPTIONAL ELECTRIC HEAT

50HS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP UNITS W/OPTIONAL ELECTRIC HEAT -1SB 018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP S W/OPTIONAL ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED ROOF CURB DIMENSION PRINT 1997 Carrier

More information

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges. Service Literature The LGH/LCH high and standard efficiency 5, 0, 5 and 50 ton (, 0.7, 58. and 75.9 kw) units, are configure to order units (CTO) with a wide selection of factory installed options. The

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

Submittal Summary Page

Submittal Summary Page ate 05/24/2011 Project Name ouglas Middle School Project Number Client / Purchaser Submittal Summary Page Qty Tag # Model # escription 1 RTU- Cafeteria 15 Ton, Johnson Controls Series 20 Single Packaged

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES SECTION 15856 MODULAR AIR HANDLING UNITS PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. NFPA Compliance: Modular air handling units and components shall be designed, fabricated, and installed in compliance

More information

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A Publication No. WT-CSX-0616A Central Station Air Handling Units Complete HVAC Capability Horizontal Draw-Thru to Size 65 Vertical Draw-Thru to Size 50 1000 to 60,000 CFM Forward Curved or Airfoil Wheels

More information

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data July 28, 2008 Page 1 1 of 3 PROJECT: TAG: Gross Cooling Capacity [Btuh]: 37,800* Design CFM: 1,200 Seasonal

More information

Advance Release September 2009

Advance Release September 2009 Vertical Air Cooled DSV Series R 410A Model DSV096 DSV120 DSV144 DSV180 Nominal Cooling (Tons) 8 10 12 15 Refrigerant R 410A R 410A R 410A R 410A Cooling Performance Gross Cooling Capacity(Btu/h) 95,000*

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

TYPICAL CPA SPECIFICATIONS

TYPICAL CPA SPECIFICATIONS TYPICAL CPA SPECIFICATIONS 4/10/2017 UNIT CONSTRUCTION: Casing: The exterior casing of the unit shall be constructed of 18-gauge, G235 galvanized steel (optional stainless steel or aluminum), unpainted.

More information

48TM GAS HEATING/ELECTRIC COOLING UNITS

48TM GAS HEATING/ELECTRIC COOLING UNITS 48TM-4SB 48TM004-014 GAS HEATING/ELECTRIC COOLING UNITS PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS Copyright 2005 Carrier Corporation Syracuse, New York 13221 Form

More information

Roof Top Packaged Unit (RTU-1) Specification

Roof Top Packaged Unit (RTU-1) Specification Roof Top Packaged Unit (RTU-1) Specification Item Tag(s) Qty Description Model Number A2 10 Ton 1 10 Ton R410A PKGD Unitary Gas/Electric TRANE: YHC120F3RLA--07C1 Product Data - 10 Ton R410A PKGD Unitary

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz) DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage

More information

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information