FDU71KXE6 FDU90KXE6 FDU112KXE6 FDU140KXE6 FDU224KXE6 FDU280KXE6

Size: px
Start display at page:

Download "FDU71KXE6 FDU90KXE6 FDU112KXE6 FDU140KXE6 FDU224KXE6 FDU280KXE6"

Transcription

1 Manual No. '08 KX-T-117S Spec Sheet INVERTER DRIVEN MULTI-INDOOR UNIT CLIMATE CONTROL SYSTEM Alternative refrigerant R410A use models (OUTDOOR UNIT) FDC112KXEN6 (1phase) FDC140KXEN6 (1phase) FDC155KXEN6 (1phase) FDC112KXES6 (3phase) FDC140KXES6 (3phase) FDC155KXES6 (3phase) (INDOOR UNIT) FDT28KXE6 FDT36KXE6 FDT45KXE6 FDT56KXE6 FDT71KXE6 FDT90KXE6 FDT112KXE6 FDT140KXE6 FDT160KXE6 FDTC22KXE6 FDTC28KXE6 FDTC36KXE6 FDTC45KXE6 FDTC56KXE6 FDTW28KXE6 FDTW45KXE6 FDTW56KXE6 FDTW71KXE6 FDTW90KXE6 FDTW112KXE6 FDTW140KXE6 FDTQ22KXE6 FDTQ28KXE6 FDTQ36KXE6 FDTS45KXE6 FDTS71KXE6 FDU71KXE6 FDU90KXE6 FDU112KXE6 FDU140KXE6 FDU224KXE6 FDU280KXE6 FDUM22KXE6 FDUM28KXE6 FDUM36KXE6 FDUM45KXE6 FDUM56KXE6 FDUM71KXE6 FDUM90KXE6 FDUM112KXE6 FDUM140KXE6 FDQS22KXE6 FDQS28KXE6 FDQS36KXE6 FDQS45KXE6 FDQS56KXE6 FDK22KXE6 FDK28KXE6 FDK36KXE6 FDK45KXE6 FDK56KXE6 FDK71KXE6 FDE36KXE6 FDE45KXE6 FDE56KXE6 FDE71KXE6 FDE112KXE6 FDE140KXE6 FDFL28KXE6 FDFL45KXE6 FDFL71KXE6 FDFU28KXE6 FDFU45KXE6 FDFU56KXE6 FDFU71KXE6

2

3 OUTDOOR UNIT (FDC) FDC112KXEN6 FDC140KXEN6 FDC155KXEN6 FDC112KXES6 FDC140KXES6 FDC155KXES6 RoHS

4 FDC 112/140/155 KXEN6 FDC 112/140/155 KXES6 Dimensions All measurements in mm. B Terminal block A L2 Intake L1 L3 Intake outlet Service space L4 Minimum installation space Mark A B C D E F Item Service valve connection (gas side) Service valve connection (liquid line) Pipe/cable draw-out port Drain discharge port Anchor bolt hole Cable draw-out port ø5/8" (15.88) (flare) ø3/8" (9.52) (flare) 4 places ø20 x 3 places M10 x 4 places ø30 x 3 places B A F A Notes: (1) It must not be surrounded by walls on the four sides. (2) The unit must be fixed with anchor bolts. An anchor bolt must not protrude more than 15mm. (3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction. (4) Leave a 1m or larger space above the unit. (5) A wall in front of the blower outlet must not exceed the units height. (6) The unit name plate is attached on the lower right corner of the front panel C C L1 I Open II Open II 500 L Open E L L F 38 1m overhead clearance required C D C VIEW A 3

5 4 FDC 112/140/155 KXEN6 Earth leakage breaker Circuit breaker POWER SOURCE 1~ V 50Hz 1~220V CM1 60Hz DM RD RD WH BL INVERTER PCB TB7 TB1 PWB2 I P M TB8 V U MS CM1 3~ Color mark Mark BR RD WH BL TB L1 N CM RD WH GN GN TB2 RD TB5 CNACT1 (WH) BL TB9 W TB10 TB11 TB6 CNI2 (WH) CNI4 (WH) RD BL BL BL BL + - F1(30A) L1 L1 L2 A/F MODULE Color 1. Instructions for correct operation Brown Red White Blue P N2 RD RD C1 BL NOISE L1i FILTER Ni E2 RD + PWB3 L1o WH No CN1 (WH) CN2 (Y) E1 CT WH WH GN RD BL F3 (4A/250V) RD BL RD CNA1 (WH) CNA2 (GN) CNI1 (WH) CNI3 (WH) Mark OR Y Y/GN Before you turn on power, please carefully read the installation manual and the operation manual supplied with the unit. Please check the following points before operation. This unit is designed exclusively for use with R410A. Do not use any refrigerant other than R410A. To protect the compressor, turn on power for the air conditioner 6 hours before operation so as to warm up sufficiently the dome temperature of compressor. Open the service valve of liquid pipe at first. Secondarily open the one of gas pipe. Before you operate the unit, make sure again that the service valve are in open position. WH CNW () Please note that the pressure values detected at the charge port in the unit and the gas service valve are different during the cooling operation and the heating operation. High pressure is replaced with the low pressure depending on whether it is in the cooling or heating operation. You should test run the unit before starting normal operation to see if the addresses are set correctly and if the indoor electronic expansion valve operates properly. For more information, please refer to the technical manual. CH1 CNR1 (WH) BR WH NETWORK CONNECTOR BR WH CNSL1,2 CNX1 (Y) CNN1 (RD) RD 20S RD CNX2 () CONTROL PCB PWB1 A1 WH A2 WH CNQ1 (BR) Color Black Orange Yellow Yellow/Green TB B1 B2 7SEG 63H Error Indication Outdoorunit LED Green Red 3-time 5-time 6-time 2-time Dark 2-time 3-time PSH WH CNL1 (BL) SIGNAL LINE RD ON ON CNS1 () OFF OFF WH CNL2 (WH) SW1 SW SW4 PSL RD CNZ1 (RD) LINE OUT RD BR SW tû EEVH M CNEEV1 (RD) 8 tû J10 SW5 WH SW7 J13 SW8 CNTH (WH) tû RD BR EEVSC M CNEEV2 (BL) Y Y CNF1 (WH) CNF2 (GN) tû tû tû CNP1 (Y) LINE IN Tho-R1 Tho-D1 Tho-S Tho-A Tho-SC Tho-H Tho-P1 7-segment display E30 E31 E32 E36 E37 E38 E39 E40 E41 E42 E43 E45 Ð E48 E49 E51 E53 E54 E56 E58 E59 E60 E63 BETWEEN THE INDOOR UNIT AND THE OUTDOOR UNIT BETWEEN THE OUTDOOR UNITS J15 SW BL OR Y W (BL) tû U (RD) Inspection WH BL OR Y 2 1 LED2 V (WH) CM LED1 CHECKER CNE WH OR LED3 A1 B1 A2 B2 FMo1 M BR BL RD 4 1 CNFAN1 (WH) PC (RS232C) Unmatched indoor/outdoor connection Duplicating outdoor unit address No. Outdoor unit address setting error Power supply phase interruption Td error (Tho-D1) Liquid pack error Heat exchanger sensor 1 disconnection (Tho-R1) Overcooling coil sensor 1 disconnection (Tho-SC) Overcooling coil sensor 2 disconnection (Tho-H) Outdoor air temperature sensor disconnection (Tho-A) Td sensor 1 disconnection (Tho-D1) High pressure switch operation (63H1-1) Power transistor overheat (CM1) (5-time/hour) Current cut (CM1) Too many units connected Too many units connected beyond capacity Transmission error between inverter and outdoor unit PCB (CM1) Auto address and remote control address are mixed in the same network. FM01 error Low pressure error (PSL operated) Power transistor overheat (CM1) (Continued for 15 min.) Suction pipe temperature sensor disconnection (Tho-S) Low pressure sensor disconnection (PSL)/output error High pressure sensor disconnection (PSH)/output error Power transistor temperature sensor 1 disconnection (Tho-P1) Active filter temperature sensor disconnection Anomalous compressor induced voltage and torque (CM1) Compressor startup error (CM1) Compressor position detection error (CM1) Outdoor unit emergency stop error CNV Mark Name C Electrolytic capacitor CH Crankcase heater CM Compressor motor CNA~Z Connector CT Current sensor DM Diode module EEVSC Electronic expansion valve (For overcooling) EEVH Electronic expansion valve (For heating) FMo1 Fan motor F Fuse PSH High pressure sensor IPM Intelligent power module J10 Superlink terminal setting (spare/normal) J13 External input switch (pulse/level) J15 Defrost start temperature (cold weather district/normal) L Reactor LED1 Indicator lamp (Red-Inspection indicator) LED2 Indicator lamp (Green-Microcomputer normality indication) LED3 Indicator lamp (Green-For service) PSL Low pressure sensor SW1 Outdoor unit No. (ten's place number) SW2 Outdoor unit No. (one's place number) SW3-1 Inspection LED reset SW3-5 Check operation start SW3-7 Forced cooling/heating switching SW4-7 Demand switching SW4-8 Demand switching SW5-1 Test run start (normal/start) SW5-2 Test run cooling setting (heating/cooling) SW5-3 Pump down (normal/valid) SW5-5 Superlink protocol setting (new/previous) SW7 (Button) Data erasing/writing SW8 (Button) 7-seg display UP, one's place number SW9 (Button) 7-seg display UP, ten's place number TB Terminal board Tho-A Thermistor (outdoor air temperature) Tho-D Thermistor (discharge pipe) Tho-P1 Thermistor (power transistor) Tho-R1 Thermistor (heat exchanger) Tho-S Thermistor (suction pipe) Tho-SC Thermistor (sub-cooling coil, liquid) Tho-H Thermistor (sub-cooling coil, gas) 20S 4-way valve coil 63H1-1 High pressure switch (Protection) 3. 7-segment display Select the code No. for each item by pressing SW9 for ten's place and SW8 for one's place. Code No. Item displayed C00 CM1 operation frequency C02 Tho-A outdoor air temperature C03 Tho-R1 heat exchanger temperature 1 C07 Tho-D1 discharge pipe temperature (CM1) C12 Tho-P1 power transistor temperature (CM1) C14 Tho-SC overcooling coil temperature 1 C15 Tho-H overcooling coil temperature 2 C16 Tho-S suction pipe temperature C18 CT1 (CM1) current C20 EEVH heating expansion valve aperture C22 EEVSC overcooling coil expansion valve aperture C23 FM01 actual r.p.m. C25 PSH high pressure sensor C26 PSL low pressure sensor C40 Number of connected indoor units C41 Capacity of connected indoor units C42 Number of indoor units with thermostat ON C43 Total request frequency C44 Integrated time of compressor operation (CM1)

6 5 FDC 112/140/155 KXES6 Earth leakage breaker Circuit breaker POWER SOURCE 3N~ V 50Hz 3N~380V 60Hz GL CNR (WH) RD TB7 R2 R1 WH K G + INVERTER PCB PWB2 I P M TB8 V U MS CM1 3~ Color mark Mark BR RD WH BL BL TB9 W DM - TB RD L1 WH L2 BL L3 N GN TB5 TB6 CNW2 (WH) CNW1 (WH) CNI2 (WH) CNO1 (RD) Brown Red White Blue ~ ~ ~ RD BL RD BL RD BL RD BL U L1 5 Color 1. Instructions for correct operation C + C1 RD 6 L1i L2i L3i N RD + L1o C2 NOISE FILTER PWB3 WH L2o BL L3o CT BL WH RD BL F3 (4A/250V) RD BL CN1 (WH) CN2-2 (Y) No E1 CNM1 (GR) CNI1 (WH) CNA1 (WH) Mark OR Y Y/GN CNA2 (GN) Before you turn on power, please carefully read the installation manual and the operation manual supplied with the unit. Please check the following points before operation. This unit is designed exclusively for use with R410A. Do not use any refrigerant other than R410A. To protect the compressor, turn on power for the air conditioner 6 hours before operation so as to warm up sufficiently the dome temperature of compressor. Open the service valve of liquid pipe at first. Secondarily open the one of gas pipe. Before you operate the unit, make sure again that the service valve are in open position. WH WH Please note that the pressure values detected at the charge port in the unit and the gas service valve are different during the cooling operation and the heating operation. High pressure is replaced with the low pressure depending on whether it is in the cooling or heating operation. You should test run the unit before starting normal operation to see if the addresses are set correctly and if the indoor electronic expansion valve operates properly. For more information, please refer to the technical manual. GN RD CONTROL PCB PWB1 CH1 CNW () CNR1 (WH) BR BR WH NETWORK CONNECTOR WH CNSL1,2 WH CNX1 (Y) CNN1 (RD) RD 20S RD A1 WH B1 A2 WH B2 CNX2 () CNQ1 (BR) Color Black Orange Yellow Yellow/Green TB 7SEG 63H Error Indication PSH WH RD CNL1 (BL) ON OFF ON OFF WH CNS1 () Outdoorunit LED 7-segment Green Red display E30 3-time 5-time 6-time 2-time Dark 2-time 3-time SIGNAL LINE BETWEEN THE INDOOR UNIT AND THE OUTDOOR UNIT BETWEEN THE OUTDOOR UNITS CNL2 (WH) SW1 SW SW4 PSL RD CNZ1 (RD) SW2 LINE OUT RD BR CNEEV1 (RD) tû EEVH M 8 J10 SW5 1 tû WH BL OR Y SW7 2 3 J13 SW8 4 RD BR CNTH (WH) tû Y Y CNF1 (WH) CNF2 (GN) CNP1 (Y) LINE IN Tho-R1 Tho-D1 Tho-S Tho-A Tho-SC Tho-H Tho-P1 E31 E32 E36 E37 E38 E39 E40 E41 E42 E43 E45 Ð E48 E49 E51 E53 E54 E56 E58 E59 E60 E63 W (BL) EEVSC M CNEEV2 (BL) J15 SW tû U (RD) Inspection WH BL OR Y A1 A2 2 1 V (WH) CM B1 B2 LED2 LED1 CHECKER tû CNE WH OR LED3 FMo1 M BR CNFAN1 (WH) tû BL RD 4 1 PC (RS232C) Unmatched indoor/outdoor connection Duplicating outdoor unit address No. Outdoor unit address setting error Power supply phase interruption Td error (Tho-D1) Liquid pack error Heat exchanger sensor 1 disconnection (Tho-R1) Overcooling coil sensor 1 disconnection (Tho-SC) Overcooling coil sensor 2 disconnection (Tho-H) Outdoor air temperature sensor disconnection (Tho-A) Td sensor 1 disconnection (Tho-D1) High pressure switch operation (63H1-1) Power transistor overheat (CM1) (5-time/hour) Current cut (CM1) Too many units connected Too many units connected beyond capacity Transmission error between inverter and outdoor unit PCB (CM1) Auto address and remote control address are mixed in the same network. FM01 error Low pressure error (PSL operated) Power transistor overheat (CM1) (Continued for 15 min.) Suction pipe temperature sensor disconnection (Tho-S) Low pressure sensor disconnection (PSL)/output error High pressure sensor disconnection (PSH)/output error Power transistor temperature sensor 1 disconnection (Tho-P1) Active filter temperature sensor disconnection Anomalous compressor induced voltage and torque (CM1) Compressor startup error (CM1) Compressor position detection error (CM1) Outdoor unit emergency stop error CNV tû Mark C CH CM CNA~Z CT DM EEVSC EEVH FMo1 F PSH IPM J10 J13 J15 L LED1 LED2 LED3 PSL SW1 SW2 SW3-1 SW3-5 SW3-7 SW4-7 SW4-8 SW5-1 SW5-2 SW5-3 SW5-5 SW7 (Button) SW8 (Button) SW9 (Button) TB Tho-A Tho-D Tho-P1 Tho-R1 Tho-S Tho-SC Tho-H 20S 63H segment display Select the code No. for each item by pressing SW9 for tenõs place and SW8 for oneõs place. Code No. C00 C02 C03 C07 C12 C14 C15 C16 C18 C20 C22 C23 C25 C26 C40 C41 C42 C43 C44 Name Electrolytic capacitor Crankcase heater Compressor motor Connector Current sensor Diode module Electronic expansion valve (For overcooling) Electronic expansion valve (For heating) Fan motor Fuse High pressure sensor Intelligent power module Superlink terminal setting (spare/normal) External input switch (pulse/level) Defrost start temperature (cold weather district/normal) Reactor Indicator lamp (Red-Inspection indicator) Indicator lamp (Green-Microcomputer normality indication) Indicator lamp (Green-For service) Low pressure sensor Outdoor unit No. (tenõs place number) Outdoor unit No. (oneõs place number) Inspection LED reset Check operation start Forced cooling/heating switching Demand switching Demand switching Test run start (normal/start) Test run cooling setting (heating/cooling) Pump down (normal/valid) Superlink protocol setting (new/previous) Data erasing/writing 7-seg display UP, oneõs place number 7-seg display UP, tenõs place number Terminal board Thermistor (outdoor air temperature) Thermistor (discharge pipe) Thermistor (power transistor) Thermistor (heat exchanger) Thermistor (suction pipe) Thermistor (sub-cooling coil, liquid) Thermistor (sub-cooling coil, gas) 4-way valve coil High pressure switch (Protection) Item displayed CM1 operation frequency Tho-A outdoor air temperature Tho-R1 heat exchanger temperature 1 Tho-D1 discharge pipe temperature (CM1) Tho-P1 power transistor temperature (CM1) Tho-SC overcooling coil temperature 1 Tho-H overcooling coil temperature 2 Tho-S suction pipe temperature CT1 (CM1) current EEVH heating expansion valve aperture EEVSC overcooling coil expansion valve aperture FM01 actual r.p.m. PSH high pressure sensor PSL low pressure sensor Number of connected indoor units Capacity of connected indoor units Number of indoor units with thermostat ON Total request frequency Integrated time of compressor operation (CM1)

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

65

66

67

68

69

70

71

72

73

74

75

76

77

78

79

6. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air cooled cooling only type)

6. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air cooled cooling only type) 6. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air cooled cooling only type) (OUTDOOR UNIT) (INDOOR UNIT) SKM222CENG-L SKM252CENG-L SKM402CENG-L 221 CONTENTS 6.1 GENERAL INFORMATION... 223 6.1.1

More information

TECHNICAL MANUAL. INVERTER MULTI-SPLIT SYSTEM RESIDENTIAL AIR-CONDITIONERS (Split system, air to air heat pump type)

TECHNICAL MANUAL. INVERTER MULTI-SPLIT SYSTEM RESIDENTIAL AIR-CONDITIONERS (Split system, air to air heat pump type) Manual No.'14 SCM-T-167 updated November 27, 2014 TECHNICL MNUL INVERTER MULTI-SPLIT SYSTEM RESIDENTIL IR-CONDITIONERS (Split system, air to air heat pump type) (OUTDOOR UNIT) SCM40ZM-S 45ZM-S 50ZM-S 60ZM-S

More information

11. WALL MOUNTED TYPE PACKAGED AIR CONDITIONER Split system, Air cooled cooling only type

11. WALL MOUNTED TYPE PACKAGED AIR CONDITIONER Split system, Air cooled cooling only type 11. WALL MOUNTED TYPE PACKAGED AIR CONDITIONER ( Split system, Air cooled ) cooling only type FDKN8CEN-S, FDKN8CEP-S, FDKN8CEN FDKN8CEP, FDKN258CEN-S, FDKN258CEP-S FDKN258CEN, FDKN258CEP, FDKN8CEN FDKN8CEP,

More information

4. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air to air heat pump type)

4. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air to air heat pump type) 4. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air to air heat pump type) (OUTDOOR UNIT) SCM68ZA (INDOOR UNIT) SKM22ZA SKM25ZA SKM28ZA SKM32ZA SKM40ZA SKM50ZA SRRM40ZA 117 CONTENTS 4.1 GENERAL INFORMATION...

More information

Keeps Flashing. Keeps Flashing. Flashes Twice. Keeps Flashing. Keeps Flashing. Stays Off. Keeps Flashing. Stays Off. Keeps Flashing.

Keeps Flashing. Keeps Flashing. Flashes Twice. Keeps Flashing. Keeps Flashing. Stays Off. Keeps Flashing. Stays Off. Keeps Flashing. ERROR CODES R410A Black = All R410A Red = FD Split 1, 2 Series R410A Blue = KX4 & KXR4 Series R410A (does not cover SRK & SCM MODELS) Error Code Indoor Circuit Board Red LED Green LED Outdoor Circuit Board

More information

SRK20ZFX-S, 25ZFX-S, 35ZFX-S, 50ZFX-S

SRK20ZFX-S, 25ZFX-S, 35ZFX-S, 50ZFX-S Manual No. 06. SRK-T. 051 TECHNICAL MANUAL Collection data INVERTER WALL MOUNTED TYPE ROOM AIR-CDITIER ( Split system, air to air heat pump type ) SRK20ZFX-S, 25ZFX-S, 35ZFX-S, 50ZFX-S CTENTS 1. GENERAL

More information

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type)

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) TECHNICAL MANUAL & PARTS LIST DRAFT INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) SRK20ZD-S - 1 - INDOOR UNIT Model SRK20ZD-S OUTDOOR UNIT Model SRC20ZD-S REMOTE

More information

Installer manual AMS 10

Installer manual AMS 10 Installer manual LE LEK LEK K 6 / 108 / 1012 / 1016 K LE Air/water heat pump UN IHB EN 17492 331942 Table of Contents 1 Important information System solution Safety information Serial number Recovery

More information

Installer manual NIBE F , 12, 16 kw UK 1x230V Air/water heat pump IHB GB LEK LEK LEK

Installer manual NIBE F , 12, 16 kw UK 1x230V Air/water heat pump IHB GB LEK LEK LEK Installer manual 8, 12, 16 kw UK 1x230V Air/water heat pump IHB GB 1512-3 231846 Table of Contents 1 Important information Safety information 2 Delivery and handling 2 2 5 Compressor heater Start-up and

More information

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER ( Split system, air to air heat pump type )

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER ( Split system, air to air heat pump type ) Manual No. 06. SRK-T. 060 INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER ( Split system, air to air heat pump type ) SRK20ZG-S, SRK25ZG-S, SRK35ZG-S, SRK50ZG-S CONTENTS 1 GENERAL INFORMATION... 1 1.1

More information

TECHNICAL MANUAL. INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS (Split system, air to air heat pump type)

TECHNICAL MANUAL. INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS (Split system, air to air heat pump type) Manual No.'13 SRK-T-144 updated March 12,2014 TECHNICAL MANUAL INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS (Split system, air to air heat pump type) SRK20ZMX-S 25ZMX-S 35ZMX-S 50ZMX-S 60ZMX-S

More information

1. WALL MOUNTED TYPE ROOM AIR-CONDITIONER Split system, Air to air heat pump type

1. WALL MOUNTED TYPE ROOM AIR-CONDITIONER Split system, Air to air heat pump type 1. WALL MOUNTED TYPE ROOM AIR-CONDITIONER Split system, Air to air heat pump type ( ) SRK25GZ-L1, SRK35GZ-L1, SRK502Z-L 1 CONTENTS 1.1 GENERAL INFORMATION... 3 1.1.1 Specific features... 3 1.1.2 How to

More information

Part 3 Troubleshooting

Part 3 Troubleshooting Part Troubleshooting What is in this part? This part contains the following chapters: Chapter See page Troubleshooting 2 Error Codes: Hydro-box 7 Error Codes: Outdoor Units Error Codes: System Malfunctions

More information

TECHNICAL MANUAL INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS

TECHNICAL MANUAL INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS TECHNICAL MANUAL INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS CONTENTS 1. SPECIFICATIONS... 3 2. EXTERIOR DIMENSIONS... 7 (1) Indoor units... 7 (2) Outdoor units... 8... 10 3. ELECTRICAL WIRING...

More information

Кондиционеры Mitsubishi Heavy

Кондиционеры Mitsubishi Heavy Кондиционеры Mitsubishi Heavy Техническое руководство Кондиционеры настенного типа SRK28HD, SRK40HD INDOOR UNIT Models SRK28HD, SRK40HD OUTDOOR UNIT Model SRC28HD REMOTE CONTROLLER Model SRC40HD GENERAL

More information

INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONER ( Split system, air to air heat pump type )

INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONER ( Split system, air to air heat pump type ) Manual No. 10. SRK-T- 102 INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CDITIER ( Split system, air to air heat pump type ) SRK25ZG-SS, SRK35ZG-SS, SRK50ZG-SS SRK63ZE-SS, SRK71ZE-SS - 3 - TABLE OF CTENTS

More information

TECHNICAL MANUAL. INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS (Split system, air to air heat pump type) SRK25ZJP-S SRK35ZJP-S SRK50ZJP-S

TECHNICAL MANUAL. INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS (Split system, air to air heat pump type) SRK25ZJP-S SRK35ZJP-S SRK50ZJP-S Manual No.'10 SRKT100 TECHNICAL MANUAL INVERTER WALL MOUNTED TYPE RESIDENTIAL AIRCONDITIONERS (Split system, air to air heat pump type) SRK25ZJPS SRK35ZJPS SRK50ZJPS CONTENTS 1. SPECIFICATIONS... 3 2.

More information

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2 Revision F: "How to check miswiring and serial signal error" has been corrected (11-5. M ). OBH648 REVISED EDITION-E is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH648 REVISED EDITION-F Models

More information

WALL MOUNTED TYPE ROOM AIR-CONDITIONER

WALL MOUNTED TYPE ROOM AIR-CONDITIONER TECHNICAL MANUAL & PARTS LIST DRAFT WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) SRK50HE-S, SRK56HE-S (Split system, air cooled cooling only type) SRK50CE-S, SRK56CE-S

More information

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC Revision F: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH590 REVISED EDITION-E. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED EDITION-F

More information

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E Revision E: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH629 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-E Models

More information

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 Indoor unit service manual MSZ-DM VA Series (OBH750) CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES

More information

TECHNICAL MANUAL INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS

TECHNICAL MANUAL INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS updated, 20 TECHNICAL MANUAL INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS CONTENTS. SPECIFICATIONS... 3 2. EXTERIOR DIMENSIONS... 6 () Indoor units... 6 (2) Outdoor units... 7 (3) Remote control...

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASY9USCCW ASY9USCCW ASY12USCCW Outdoor unit AOY9USCC AOY9UFCC AOY12USCC CONTENTS SPECIFICATIONS................................... 1

More information

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467. SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-HC35VA- E2 and MUZ-HC35VAB- E2 have been added. Please void OBH467 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH467 REVISED EDITION-B

More information

ERROR CODES R22 & R407C Units Black = All Units Red = 4, 5, 6 & 7 Series Blue = 8 Series Green = KX / KX2 / KXR

ERROR CODES R22 & R407C Units Black = All Units Red = 4, 5, 6 & 7 Series Blue = 8 Series Green = KX / KX2 / KXR ERROR CODES R22 & R407C Units Black = All Units Red = 4, 5, 6 & 7 Series Blue = 8 Series Green = KX / KX2 / KXR Receiver Unit [if applicable] Error Code No indication Check Indications Indoor Circuit Board

More information

TECHNICAL MANUAL. PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) MULTI-TYPE (V-MULTI) PACKAGED AIR-CONDITIONER

TECHNICAL MANUAL. PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) MULTI-TYPE (V-MULTI) PACKAGED AIR-CONDITIONER Manual No. '06 PAC, KX-T-110 TECHNICAL MANUAL Collection data PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) FDUMVA201HEN2R 251HEN2R 302HEN2R 402HEN2R 502HEN2R 602HEN2R MULTI-TYPE (V-MULTI)

More information

CASSETTE type INVERTER MULTI AIR CONDITIONER. Models AUY12LBAB AUY14LBAB AOY18LMAK2

CASSETTE type INVERTER MULTI AIR CONDITIONER. Models AUY12LBAB AUY14LBAB AOY18LMAK2 INVERTER MULTI AIR CONDITIONER CASSETTE type Models Indoor unit AUY12LBAB AUY14LBAB Outdoor unit AOY18LMAK2 CONTENTS SPECIFICATIONS..................... 1 OUTLINE AND DIMENSIONS........... 2 REFRIGERANT

More information

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Wireless type Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Wireless type Models HFC. Revision E: REVISED EDITION-E R410A Revision E: MUZ-GB50VA- E3 has been added. Please void OB455 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB455 REVISED EDITION-E Wireless type Models MUZ-GB50VA - E1 MUZ-GB50VA -

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC Revision A: MUZ-HM09/12NA- U8, MUZ-HM09/12NA2- U8, MUZ-HM15/18NA- U1, MUZ-HM15/18NA2- U1 and MUZ-HM24NA2- U1 have been added. Please void OBH747. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A.

More information

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1 SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH

More information

Digital Inverter 4 series 8 & 10HP

Digital Inverter 4 series 8 & 10HP E6-H Digital Inverter 4 series 8 & 0HP High static duct type Indoor unit RAV-SM2244DTP-E RAV-SM2804DTP-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E Contents. Line up... 2. Indoor unit (High static duct

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC Revision E: MUZ-FH25VE- E4, ER4, ET3, MUZ- FH35VE- E3, ER3, ET3 and MUZ- FH50VE- E2, ER2, ET2 have been added. Please void OBH624 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624

More information

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Models HFC

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Models HFC Revision G: Errors in TROUBLESHOOTING have been corrected. Please void OB455 REVISED EDITION-F. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB455 REVISED EDITION-G Models MUZ-GB50VA - E1 MUZ-GB50VA

More information

MUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service manual MSZ-EF VE Series (OBH589)

MUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service manual MSZ-EF VE Series (OBH589) SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 Models MUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service

More information

Air Conditioner SVC MANUAL(Exploded View)

Air Conditioner SVC MANUAL(Exploded View) Internal Use nly http://biz.lgservice.com Air Conditioner SVC MANUAL(Exploded View) MDEL : AUUW423D[LUU425HV] CAUTIN Before Servicing the unit, read the safety precautions in General SVC manual. nly for

More information

3.2 E1 Outdoor Unit PCB Abnormality E4 Actuation of Low Pressure Sensor E5 Compressor Motor Lock 3 52

3.2 E1 Outdoor Unit PCB Abnormality E4 Actuation of Low Pressure Sensor E5 Compressor Motor Lock 3 52 Error Codes: Outdoor Units Error Codes: Outdoor Units Part. What Is in This Chapter? Introduction Overview In the first stage of the troubleshooting sequence, it is important to correctly interpret the

More information

CASSETTE type INVERTER MULTI AIR CONDITIONER

CASSETTE type INVERTER MULTI AIR CONDITIONER INVERTER MULTI AIR CONDITIONER CASSETTE type Models Indoor unit AUY12LBAB AUY14LBAB Outdoor unit AOY18LMAK2 CONTENTS SPECIFICATIONS..................... 1 OUTLINE AND DIMENSIONS........... 2 REFRIGERANT

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629.

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-A Models MUZ-SF25VE - E1 MUZ-SF42VE

More information

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH502 Wireless type Models MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA Indoor unit service manual MSZ-D NA Series (OBH501) MSY-D

More information

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1 SPLIT-TYPE AIR CONDITIONERS Revision D: Changing defrost finish temperature has been corrected (10-1.). Please void OBH516 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED

More information

TABLE OF CONTENTS ERSQ-AAY1

TABLE OF CONTENTS ERSQ-AAY1 Daikin Altherma High Temperature Outdoor units ERSQ-AAY1 TABLE OF CONTENTS ERSQ-AAY1 1 Features............................................................ 6 2 Specifications......................................................

More information

TECHNICAL MANUAL. INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS (Split system, air to air heat pump type) SRK25ZMP-S SRK35ZMP-S SRK45ZMP-S

TECHNICAL MANUAL. INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS (Split system, air to air heat pump type) SRK25ZMP-S SRK35ZMP-S SRK45ZMP-S Manual No.'13 SRK-T-140 updated September 30, 2014 TECHNICAL MANUAL INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CDITIERS (Split system, air to air heat pump type) SRK25ZMP-S SRK35ZMP-S SRK45ZMP-S Service

More information

VRF inverter multi-system Air-Conditioners. 50Hz 13KX02E EU/EEA

VRF inverter multi-system Air-Conditioners. 50Hz 13KX02E EU/EEA 2013 VRF inverter multi-system ir-conditioners 50Hz 13KX02E EU/EE R4 History of Technologies more efficient, more sophisticated KX2 KX4 KX6 (8~12HP) 2 Line Up Contents Introduction 4~15 Outdoor units 16~47

More information

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. Please void OBH733 REVISED EDITION-A. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH733 REVISED EDITION-B Models MUZ-GL09NA

More information

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A Revision E: Capacity corrections have been corrected [7-1. 2), 3)]. OBH502 REVISED EDITION-D is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH502 REVISED EDITION-E Models MUZ-D30NA / - 1 / -

More information

SERVICE MANUAL MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-F.

SERVICE MANUAL MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-F. Revision F: The descriptions of the expansion valve coil have been corrected. (10-4.) Some descriptions have been modified. Please void OBH543 REVISED EDITION-E. OUTDOOR UNIT SERVICE MANUAL HFC utilized

More information

PMFY-P-VBM-E. Ceiling cassette (1-way flow type) R410A Data G8 1. SPECIFICATIONS EXTERNAL DIMENSIONS CENTER OF GRAVITY 1-100

PMFY-P-VBM-E. Ceiling cassette (1-way flow type) R410A Data G8 1. SPECIFICATIONS EXTERNAL DIMENSIONS CENTER OF GRAVITY 1-100 Ceiling cassette (-way flow type) RA Data G8 -P-VBM-E. SPECIFICATIONS - 98. EXTERNAL DIMENSIONS - 99 3. CENTER OF GRAVITY -. ELECTRICAL WIRING DIAGRAMS -. SOUND LEVELS -. Sound levels -. NC curve 6. TEMPERATURE/AIRFLOW

More information

WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type)

WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) Manual No. 03 SRK-T-030 TECHNICAL MANUAL Collection data WALL MOUNTED TYPE ROOM AIR-CDITIER (Split system, air to air heat pump type) SRK28HBE, SRK40HBE, SRK50HBE CTENTS 1 GENERAL INFORMATI... 1 1.1 Specific

More information

SERVICE MANUAL MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA - U1 MSZ-GL18NA - U1 MSZ-GL24NA - U1

SERVICE MANUAL MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA - U1 MSZ-GL18NA - U1 MSZ-GL24NA - U1 Revision B: 3. SPECIFICATION has been corrected. Please void OBH732 REVISED EDITION-A. INDOOR UNIT SERVICE MANUAL. OBH732 REVISED EDITION-B Models MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA

More information

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 MSZ-GE60VA - E1 MSZ-GE71VA - E1 INDOOR UNIT. No.

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 MSZ-GE60VA - E1 MSZ-GE71VA - E1 INDOOR UNIT. No. SPLIT-TYPE AIR CONDITIONERS Revision E: Detail of the indoor fan speed control in COOL or DRY operation has been added (9-1.3, 9-2.3). Please void OBH515 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL.

More information

SERVICE MANUAL MXZ-2A40VA - MXZ-2A52VA - MXZ-3A54VA - MXZ-3A54VA - MXZ-4A71VA - MXZ-4A71VA - MXZ-4A80VA - E1 OUTDOOR UNIT. No. OB377 REVISED EDITION-A

SERVICE MANUAL MXZ-2A40VA - MXZ-2A52VA - MXZ-3A54VA - MXZ-3A54VA - MXZ-4A71VA - MXZ-4A71VA - MXZ-4A80VA - E1 OUTDOOR UNIT. No. OB377 REVISED EDITION-A SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Revision : A MXZ-A5/A7VA- MXZ-A0/A5VA- Please void OB77 E E has been added. has been added. OUTDOOR UNIT SERVICE MANUAL HFC utilized R0A No. OB77 REVISED EDITION-A

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CLM97 CLM7 CLM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No.

More information

SERVICE MANUAL 42QHF009DS* 42QHF012DS* 42QHF018DS* 42QHF022DS* 38QUS009DS* 38QUS012DS* 38QUS018DS* 38QUS022DS* Indoor unit.

SERVICE MANUAL 42QHF009DS* 42QHF012DS* 42QHF018DS* 42QHF022DS* 38QUS009DS* 38QUS012DS* 38QUS018DS* 38QUS022DS* Indoor unit. SERVICE MANUAL Indoor unit Outdoor unit 42QHF009DS* 42QHF012DS* 42QHF018DS* 42QHF022DS* 38QUS009DS* 38QUS012DS* 38QUS018DS* 38QUS022DS* INDEX PART1 GENERAL INFORMATION PART2 ELECTRICAL DIAGRAM PART3 TROUBLE

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 19,100 BTU/h,200 BTU/h 30,600 BTU/h Outdoor Model No. CU-3KE19NBU CU-4KE24NBU

More information

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy SPLIT-TYPE AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL. OBH589 Models MSZ-EF22VEW - MSZ-EF22VEW - E1 MSZ-EF25VEW - E1 MSZ-EF22VEB - E1 MSZ-EF35VEW - E1 MSZ-EF22VES E1 - MSZ-EF42VEW - E1 MSZ-EF25VEW - E1

More information

INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air to air heat pump type)

INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air to air heat pump type) TECHNICAL MANUAL & PARTS LIST DRAFT INVERTER MULTISPLIT SYSTEM ROOM AIRCONDITIONER (Air to air heat pump type) (Outdoor unit) SCM45ZDS SCM60ZDS SCM80ZDS (Indoor unit) SKM22ZDS SKM25ZDS SKM28ZDS SKM5ZDS

More information

SERVICE SUPPORT HANDBOOK. w w w. m h i a a. c o m. a u

SERVICE SUPPORT HANDBOOK. w w w. m h i a a. c o m. a u SERVICE SUPPORT HANDBOOK w w w. m h i a a. c o m. a u The information contained within this Service Support Handbook is for the use by qualified licenced personnel only. Additionally, the information presented

More information

ASU18RLF ASU24RLF AOU18RLXFWH AOU24RLXFWH CONTENTS WALL MOUNTED TYPE ROOM AIR CONDITIONER FOR EXTRA LOW TEMP. DISTRICT

ASU18RLF ASU24RLF AOU18RLXFWH AOU24RLXFWH CONTENTS WALL MOUNTED TYPE ROOM AIR CONDITIONER FOR EXTRA LOW TEMP. DISTRICT WALL MOUNTED TYPE ROOM AIR CONDITIONER FOR EXTRA LOW TEMP. DISTRICT Indoor unit ASU8RLF ASURLF Outdoor unit AOU8RLXFWH AOURLXFWH CONTENTS SPECIFICATIONS.................... DIMENSIONS........................

More information

CASSETTE type SPLIT TYPE AIR CONDITIONER. (60Hz) AUU18RCLX AUU24RCLX AUU36RCLX AUU42RCLX AOU18RLX AOU24RLX AOU36RLX AOU42RLX CONTENTS.

CASSETTE type SPLIT TYPE AIR CONDITIONER. (60Hz) AUU18RCLX AUU24RCLX AUU36RCLX AUU42RCLX AOU18RLX AOU24RLX AOU36RLX AOU42RLX CONTENTS. SPLIT TYPE AIR CONDITIONER CASSETTE type (60Hz) Models Indoor unit AUU8RCLX AUURCLX AUU6RCLX AUURCLX Outdoor unit AOU8RLX AOURLX AOU6RLX AOURLX CONTENTS SPECIFICATIONS... DIMENSIONS... REFRIGERANT SYSTEM

More information

SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz)

SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz) SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz) Indoor unit MS6YF Outdoor unit MR6YF CONTENTS SPECIFICATIONS... OUTLINE AND DIMENSIONS... REFRIGERANT SYSTEM DIAGRAM.... CIRCUIT DIAGRAM... INDOOR PCB

More information

Ductless Split Air Conditioner

Ductless Split Air Conditioner Ductless Split Air Conditioner Service Manual Indoor AW09ESVHA AWESVHA AW8ESVHA AWESVHA Outdoor U09ESVHA UESVHA U8ESVHA UESVHA Design may vary by model number. Please read this manual before using the

More information

SEZ-KD25VAQ.TH SEZ-KD35VAQ.TH SEZ-KD50VAQ.TH SEZ-KD60VAQ.TH SEZ-KD71VAQ.TH

SEZ-KD25VAQ.TH SEZ-KD35VAQ.TH SEZ-KD50VAQ.TH SEZ-KD60VAQ.TH SEZ-KD71VAQ.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL December No.HWE0 REVISED EDITION-B Indoor unit [Model names] SEZ-KD25VAQ SEZ-KD35VAQ SEZ-KDVAQ SEZ-KDVAQ SEZ-KD71VAQ [Service Ref.] SEZ-KD25VAQ.TH

More information

WALL MOUNTED TYPE ROOM AIR-CONDITIONER

WALL MOUNTED TYPE ROOM AIR-CONDITIONER Manual No. '06 SRK -T-058C Collection data WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) SRK28HJ SRK40HJ CONTENTS 1 GENERAL INFORMATION... 1 1.1 Specific features...

More information

SERVICE MANUAL INDOOR UNIT

SERVICE MANUAL INDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision A: MSZ-SF25/35/42/50VE- E2 and MSZ-SF25/35/ 42/50VE- EN2 have been added. Please void OBH600. INDOOR UNIT SERVICE MANUAL. OBH600 REVISED EDITION-A Models MSZ-SF25VE

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL KS1872 + C1872 + CL1872 KS2472 + C2472 + CL2472 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KS1872 KS2472 Product

More information

PUHY-P-Y(S)JM-A PFAV-P-VM-E(-F)

PUHY-P-Y(S)JM-A PFAV-P-VM-E(-F) AIR CONDITIONING SYSTEMS MODEL PUHY-P-Y(S)JM-A PFAV-P-VM-E(-F) DATA BOOK Contents!. General Cautions. Indoor Unit Line-up. Temperature range. Notes on selecting equipments () Notes on using the Fresh

More information

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA OUTDOOR UNIT. No. OBH543. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA OUTDOOR UNIT. No. OBH543. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 Models MUZ-FE09NA MUZ-FE12NA Indoor unit service manual MSZ-FE NA Series (OBH542) CONTENTS 1. TECHNICAL CHANGES 2 2. PART

More information

Ductless Split Air Conditioner

Ductless Split Air Conditioner Ductless Split Air Conditioner Service Manual Indoor HSU09VHG(DB)-W HSUVHG(DB)-W HSU8VHH(DB)-W HSUVHG(DB)-W Outdoor HSU09VHG(DB)-G HSUVHG(DB)-G HSU8VHH(DB)-G HSUVHG(DB)-G Design may vary by model number.

More information

SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE

SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE Indoor unit ABYF8LAT ABYF8LAT ABYF8LAT ABYF8LAT ABYF8LBT ABYF8LBT ABYFLAT ABYFLAT ABYFLAT ABYFLAT ABYFLBT ABYFLBT Outdoor unit AOYA8LACL

More information

Small VRF system. for light commercial and home use SERVICE MANUAL

Small VRF system. for light commercial and home use SERVICE MANUAL Small VRF system for light commercial and home use SERVICE MANUAL CONTENTS 1. TEST RUN 1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS... 01-01 1-2 TEST RUN METHOD... 01-03 1-2-1 Check Items Before

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH Revision D: Capacity corrections have been corrected [7-1. 2), 3)]. OBH684 REVISED EDITION-C is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH684 REVISED EDITION-D Models MUZ-FH06NA MUZ-FH09NA

More information

CEILING type (60Hz) SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models

CEILING type (60Hz) SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models SPLIT TYPE ROOM AIR CONDITIONER CEILING type (60Hz) Models Indoor unit ABU6RSLX Outdoor unit AOU6RLX CONTENTS SPECIFICATIONS....................... OUTLINE AND DIMENSIONS............. REFRIGERANT SYSTEM

More information

WALL MOUNTED TYPE ROOM AIR-CONDITIONER

WALL MOUNTED TYPE ROOM AIR-CONDITIONER Manual No. 03. SRK-T. 031 TECHNICAL MANUAL Collection data WALL MOUNTED TYPE ROOM AIR-CDITIER (Split system, air to air heat pump type) SRK20HC-S, SRK28HC-S, SRK40HC-S - 3 - CTENTS 1. GENERAL INFORMATI...

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models CONTENTS

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models CONTENTS SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASY9USCCW ASY9USCCW ASY12USCCW Outdoor unit AOY9USCC AOY9UFCC AOY12USCC CONTENTS SPECIFICATIONS.................. 1 OUTLINE AND DIMENSIONS.........

More information

Simple Self-Diagnosis by Malfunction Code

Simple Self-Diagnosis by Malfunction Code Detail Division 0 Indoor Unit System Others A C E F H J L P U M 7 8 9 External device activated (unified) Protection devices activated (unified) of Miswiring of Shortage of amount ( unit) Shortage of External

More information

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA 0.8180.472.0 07/2005 Page 1. SPECIFICATIONS 3 1-1 Unit Specifications 3 1-2 Major Component Specifications 4 2. DIMENSIONAL DATA 6 2-1 Unit Dimensions 6 3. ELECTRICAL

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASY9USCCW ASY9USCCW ASY12USCCW Outdoor unit AOY9USCC AOY9UFCC AOY12USCC CONTENTS SPECIFICATIONS.................. 1 OUTLINE AND DIMENSIONS.........

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 12 TECHNICAL & SERVICE MANUAL Series SEZ Model name SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KDVA(L) SEZ-KDVA(L) SEZ-KD71VA(L) INDOOR UNIT ON/OFF TEMP TEMP.

More information

SERVICE MANUAL MS-GF20VA MS-GF25VA MS-GF35VA MS-GF50VA MS-GF60VA MS-GF80VA INDOOR UNIT. No. OBH621 REVISED EDITION-A. Models

SERVICE MANUAL MS-GF20VA MS-GF25VA MS-GF35VA MS-GF50VA MS-GF60VA MS-GF80VA INDOOR UNIT. No. OBH621 REVISED EDITION-A. Models SPLIT-TYPE AIR CONDITIONERS Revision A: MS-GF50VA- E1, MS-GF60VA- E1 and MS-GF80VA- E1 have been added. Please void OBH621. INDOOR UNIT SERVICE MANUAL. OBH621 REVISED EDITION-A Models MS-GF20VA MS-GF25VA

More information

SERVICE MANUAL MXZ-A18WV - MXZ-A26WV - MXZ-A32WV - E1 HFC. Inverter-controlled multi system Models SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No.

SERVICE MANUAL MXZ-A18WV - MXZ-A26WV - MXZ-A32WV - E1 HFC. Inverter-controlled multi system Models SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Inverter-controlled multi system Models E MXZ-A8WV - E MXZ-A6WV - MXZ-AWV - E HFC utilized R40A No. OB9 Indication of model name MXZ-A8WV - E CONTENTS.

More information

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*R07LGC AO*R09LGC AO*R12LGC AO*R14LGC

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*R07LGC AO*R09LGC AO*R12LGC AO*R14LGC SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS*A07LGC AS*A09LGC AS*A2LGC AS*A4LGC AO*R07LGC AO*R09LGC AO*R2LGC AO*R4LGC R40A CONTENTS.

More information

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E SPLIT-TYPE AIR CONDITIONERS Revision E: MFZ-KA5VA- E5, MFZ-KA35VA- E5 and MFZ-KA50VA- E5 have been added. Please void OB409 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OB409 REVISED EDITION-E Models

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH530 Models MU-GE50VB- E1 - E1 Indoor unit service manual MS/MSH-GE VB Series (OBH529) CONTENTS 1. TECHNICAL CHANGES 2 2. PART

More information

IMPORTANT SAFETY NOTICE

IMPORTANT SAFETY NOTICE Order No: PAPAMY703052CE Indoor Unit CS-TE20TKEW CS-TE25TKEW CS-TE35TKEW CS-TE42TKEW Outdoor Unit CU-TE20TKE CU-TE25TKE CU-TE35TKE CU-TE42TKE Destination Europe Turkey Please file and use this manual together

More information

FLOOR CONSOLE / UNDER CEILING DUAL type (60Hz)

FLOOR CONSOLE / UNDER CEILING DUAL type (60Hz) SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL type (60Hz) Models Indoor unit MSYF Outdoor unit MRUYF CONTENTS SPECIFICATIONS... OUTLINE AND DIMENSIONS... REFRIGERANT SYSTEM DIAGRAM...

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF94R5 CAF124R5 SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. CAF94R5 387106979 CAF124R5 387106980 0.8180.361.0 07/2005 IMPORTANT! Please read before

More information

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-SP100JA(L) PEAD-SP125JA(L) PEAD-SP140JA(L) Models PEAD-SP71JA(L) <indoor unit>

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-SP100JA(L) PEAD-SP125JA(L) PEAD-SP140JA(L) Models PEAD-SP71JA(L) <indoor unit> SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 4 SERVICE MANUAL Series PEAD R4A Models PEAD-SP7JA(L) PEAD-SPJA(L) PEAD-SP5JA(L) PEAD-SPJA(L) NOTE: This manual describes only service data of the indoor

More information

SERVICE MANUAL MLZ-KA25VA - MLZ-KA35VA - MLZ-KA50VA - E1 INDOOR UNIT. No. OBH483. Ceiling cassette type Models

SERVICE MANUAL MLZ-KA25VA - MLZ-KA35VA - MLZ-KA50VA - E1 INDOOR UNIT. No. OBH483. Ceiling cassette type Models CEILING CASSETTE TYPE, HEAT PUMP AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL. OBH483 Ceiling cassette type Models E1 MLZ-KA25VA - E1 MLZ-KA35VA - MLZ-KA50VA - E1 Outdoor unit service manual MXZ-A VA Series

More information

FLOOR CONSOLE / UNDER CEILING DUAL type

FLOOR CONSOLE / UNDER CEILING DUAL type SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL type Models Indoor unit ABU8RULX ABURULX Outdoor unit AOU8RLX AOURLX CONTENTS SPECIFICATIONS... OUTLINE AND DIMENSIONS... REFRIGERANT

More information

SERVICE MANUAL MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA INDOOR UNIT. No. OBH746 REVISED EDITION-B. Models

SERVICE MANUAL MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA INDOOR UNIT. No. OBH746 REVISED EDITION-B. Models Revision B: 3-1. OPERATING RANGE has been modified. Please void OBH746 REVISED EDITION-A. INDOOR UNIT SERVICE MANUAL. OBH746 REVISED EDITION-B Models MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA

More information

SERVICE MANUAL MSZ-DM25VA - E1, ER1 MSZ-DM35VA - E1, ER1 INDOOR UNIT. No. OBH750. Models

SERVICE MANUAL MSZ-DM25VA - E1, ER1 MSZ-DM35VA - E1, ER1 INDOOR UNIT. No. OBH750. Models INDOOR UNIT SERVICE MANUAL. Models MSZ-DM25VA - E1, ER1 MSZ-DM35VA - E1, ER1 Outdoor unit service manual MUZ-DM VA Series (OBH751) MXZ-DM VA Series (OBH739) MSZ-DM25VA MSZ-DM35VA CONTENTS 1. TECHNICAL

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL MCAF88R5I + GRF86R5I MCAF48R5I + GRF46R5I FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. MCAF88R5I MCAF88R5IAA

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : SAP-CMRVEH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 0.0kW Outdoor Model No. SAP-CMRVEH-F Product Code No. 8 8 SAP-CMRVEH

More information

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy MUZ-GA35VAH - E1

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy MUZ-GA35VAH - E1 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MUZ-GA5VA - E MUZ-GA35VA - E MUZ-GA5VAH - MUZ-GA35VAH - E HFC utilized R40A. OB379 Indication of model name MUZ-GA5VA - E MUZ-GA35VA

More information

Product Data FEATURES AND BENEFITS. QHF 50Hz Heat Pump Inverter Single Phase 2.5kW to 8.0kW

Product Data FEATURES AND BENEFITS. QHF 50Hz Heat Pump Inverter Single Phase 2.5kW to 8.0kW 0Hz Heat Pump Inverter Single Phase.kW to 8.0kW turn to the experts Product Data FEATURES AND BENEFITS AVAILABLE SIZES: Nominal capacity are available from.kw through 8.0kW to meet the needs of residential

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL MCAF94R5IAA + GRF97R5I MCAF124R5IAA + GRF127R5I FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. MCAF94R5IAA

More information

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Cassette type Duct type Ceiling type INVERTER AO* G45LETL AO* G54LETL

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Cassette type Duct type Ceiling type INVERTER AO* G45LETL AO* G54LETL SPLIT TYPE ROOM AIR CONDITIONER Cassette type Duct type Ceiling type INVERTER SERVICE INSTRUCTION Models Indoor unit AU* G45LRLA AR* G45LMLA AR* G45LHTA AB* G45LRTA Outdoor unit AO* G45LETL AO* G54LETL

More information