1 SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL July No. OC REVISED EDITI-B Indoor unit [Model names] PLFY-PVAM-E PLFY-PVAM-E PLFY-PVAM-E PLFY-PVAM-E PLFY-PVAM-E PLFY-PVAM-E PLFY-PVAM-E [Service Ref.] PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK Revision: RoHS PARTS LIST is added. Some descriptions have been modified. Please void OC REVISED EDITI-A. Note: This manual does not cover outdoor units. When servicing them, please refer to the outdoor unit s service manual. RoHS compliant products have <> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List. CTENTS INDOOR UNIT. SAFETY PRECAUTI. PART NAMES AND FUNCTIS. SPECIFICATIS. -WAY AIR FLOW SYSTEM. OUTLINES AND DIMENSIS. WIRIN DIARAM. REFRIERANT SYSTEM DIARAM. TROUBLE SHOOTIN. DISASSEMBLY PROCEDURE. PARTS LIST. RoHS PARTS LIST. OPTIAL PARTS

2 SAFETY PRECAUTI CAUTIS RELATED TO NEW REFRIERANT Cautions for units utilizing refrigerant RC Do not use the existing refrigerant piping. The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant deterioration of the new unit. Use liquid refrigerant to charge the system. If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop. Use low residual oil piping If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result. Store the piping to be used during installation indoors with keep both ends sealed until just before brazing. (Store elbows and other joints in a plastic bag.) If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result. Use ESTR, ETHER or HAB as the lubricant to coat flares and flange connection parts. If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc. Do not use a refrigerant other than RC. If another refrigerant (R, etc.) is used, the chlorine in the refrigerant may cause the lubricant deterioration. Use a vacuum pump with a reverse flow check valve. The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricant deterioration. Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released. [] Cautions for service After recovering the all refrigerant in the unit, proceed to working. Do not release refrigerant in the air. After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.

3 [] Refrigerant recharging () Refrigerant recharging process Direct charging from the cylinder. RC cylinder are available on the market has a syphon pipe. Leave the syphon pipe cylinder standing and recharge it. (By liquid refrigerant) Unit ravimeter () Recharge in refrigerant leakage case After recovering the all refrigerant in the unit, proceed to working. Do not release the refrigerant in the air. After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant. [] Service tools Use the below service tools as exclusive tools for RC refrigerant. No. Tool name Specifications auge manifold Only for RC. Use the existing fitting SPECIFICATIS. (UNF/) Use high-tension side pressure of.mpa or over. Charge hose Electronic scale Only for RC. Use pressure performance of.mpa or over. as leak detector Use the detector for Ra or RC. Adapter for reverse flow check. Attach on vacuum pump. Refrigerant charge base. Refrigerant cylinder. For RC Top of cylinder (Brown) Cylinder with syphon Refrigerant recovery equipment.

4 Cautions for units utilizing refrigerant RA Do not use the existing refrigerant piping. The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant deterioration of the new unit. Use low residual oil piping If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result. Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.) If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of compressor. Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigerant oil applied to flares and flange connections. If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc. Charge refrigerant from liquid phase of gas cylinder. If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered. Use a vacuum pump with a reverse flow check valve. Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc. Use the following tools specifically designed for use with RA refrigerant. The following tools are necessary to use RA refrigerant. Tools for RA auge manifold Flare tool Charge hose Size adjustment gauge as leak detector Vacuum pump adaptor Torque wrench Electronic refrigerant charging scale Keep the tools with care. If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of compressor. Do not use a charging cylinder. If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered. Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released. Do not use refrigerant other than RA. If other refrigerant (R etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.

5 [] Cautions for service () Perform service after collecting the refrigerant left in unit completely. () Do not release refrigerant in the air. () After completing service, charge the cycle with specified amount of refrigerant. () When performing service, install a filter drier simultaneously. Be sure to use a filter drier for new refrigerant. [] Additional refrigerant charge When charging directly from cylinder Check that cylinder for RA on the market is syphon type. Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.) Unit ravimeter [] Service tools Use the below service tools as exclusive tools for RA refrigerant. No. Specifications auge manifold Only for RA Use the existing fitting specifications. (UNF/) Use high-tension side pressure of.mpa or over. Charge hose Only for RA Use pressure performance of.mpa or over. Electronic scale as leak detector Use the detector for Ra, RC or RA. Adaptor for reverse flow check Attach on vacuum pump. Refrigerant charge base Refrigerant cylinder Only for RA Top of cylinder (Pink) Cylinder with syphon Refrigerant recovery equipment

6 PART NAMES AND FUNCTIS Indoor Unit Filter Remove dust and pollutants from return air Horizontal Air Outlet Sets airflow horizontal automatically during cooling or dehumidifying. rille Auto Air Swing Vane Disperses airflow up and down and adjusts the angle of airflow direction. Air Intake Returns air from room. Wired remote controller On the controls are set, the same operation mode can be repeated by simply pressing the / button. Operation buttons Set Temperature buttons / button Down Up Fan Speed button Timer Menu button (Monitor/Set button) Mode button (Return button) Filter button (<Enter> button) TEMP. / Test Run button Set Time buttons Check button (Clear button) Back MENU / FILTER Ahead Timer On/Off button (Set Day button) BACK PAR-MAA MITOR/SET DAY CLOCK OPERATI CHECK TEST CLEAR Airflow Up/Down button Louver button ( Operation button) Opening the door. To preceding operation number. Ventilation button ( Operation button) To next operation number.

7 Display For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit. Identifies the current operation Shows the operating mode, etc. * Multilanguage display is supported. Day-of-Week Shows the current day of the week. Time/Timer Display Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time remaining. Sensor indication Displayed when the remote controller sensor is used. Locked indicator Indicates that remote controller buttons have been locked. Clean The Filter indicator Comes on when it is time to clean the filter. Centrally Controlled indicator Indicates that operation of the remote controller has been prohibited by a master controller. Timer Is Off indicator Indicates that the timer is off. Temperature Setting Shows the target temperature. F C TIME SUN M TUE WED THU FRI SAT TIMER Hr AFTER AFTER ERROR CODE F C LYHr. Up/Down Air Direction indicator The indicator shows the direction of the outcoming airflow. One Hour Only indicator Displayed if the airflow is set to weak and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airflow direction also changes. FUNCTI FILTER WEEKLY SIMPLE AUTO Room Temperature display Shows the room temperature. Louver display Indicates the action of the swing louver. Does not appear if the louver is stationary. (Power On indicator) Indicates that the power is on. Timer indicators The indicator comes on if the corresponding timer is set. Fan Speed indicator Shows the selected fan speed. Ventilation indicator Appears when the unit is running in Ventilation mode. Caution Only the Power on indicator lights when the unit is stopped and power supplied to the unit. If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the Not Available message. If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not present at the parent unit. When power is turned for the first time, it is normal that PLEASE WAIT is displayed on the room temperature indication (For max. minutes). Please wait until this PLEASE WAIT indication disappear then start the operation.

8 SPECIFICATIS -. SPECIFICATIS Item PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK Power Cooling capacity Heating capacity Electric characteristic Cooling Current Heating Exterior (munsell symbol) Dimensions Heat exchanger F a n Input Fan No Air flow W External static pressure Fan motor output Insulator Air filter Pipe dimensions Cooling Heating Height Width Depth as side Liquid side Unit drain pipe size Noise level W Product weight V Hz kw kw kw kw A A mm mm mm k/min Pa kw [mm(in.) [mm(in.) [mm db kg Unit : alvanized sheets with gray heat insulation rills : ABS resin Munsell<.Y./.> [.(/") [.(/") Single phase --V Hz Single phase V Hz... <> <> <> Cross fin Turbo fan ---. Polyethylene sheet PP honey comb fabric O.D. (PVC pipe VP- connectable) <> ---. [.(/") / [.(/") (Compatible) [.(/")/[.(/") (Compatible) [.(/") [.(/") --- <> Note. Rating conditions(jis B ) Cooling : Indoor : D.B. C W.B.. C outdoor : D.B. C Heating : Indoor : D.B. C outdoor : D.B. C W.B. C Note. The number indicated in < > is just for the grille. W. Air flow and the noise level are indicated as High-Medium-Medium-Low.

9 Power Item Cooling capacity Heating capacity Electric characteristic Cooling Current Heating Exterior (munsell symbol) Heat exchanger F a n Input Dimensions Fan No Air flow W External static pressure Fan motor output Insulator Air filter Pipe dimensions Cooling Heating Height Width Depth as side Liquid side Unit drain pipe size Noise level W Product weight V Hz kw kw kw kw A A mm mm mm k/min Pa kw [mm(in.) [mm(in.) [mm db kg PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK <> ---..(/") --- <> Single phase --V Hz Single phase V Hz Unit : alvanized sheets with gray heat insulation rills : ABS resin Munsell<.Y./.> <> <> Cross fin Turbo fan --- Polyethylene sheet PP honey comb fabric [.(/") / [.(/") (Compatible).(/") O.D. (PVC pipe VP- connectable) --- <>. <> Note. Rating conditions(jis B ) Cooling : Indoor : D.B. C W.B.. C outdoor : D.B. C Heating : Indoor : D.B. C outdoor : D.B. C W.B. C Note. The number indicated in < > is just for the grille. W. Air flow and the noise level are indicated as High-Medium-Medium-Low.

10 -. ELECTRICAL PARTS SPECIFICATIS Model Parts name Room temperature thermistor Symbol TH PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK Resistance :/k", :/.k", :/.k", :/.k", :/.k", :/.k" Liquid pipe thermistor TH Resistance :/k", :/.k", :/.k", :/.k", :/.k", :/.k" as pipe thermistor Fuse (Indoor controller board) TH FUSE Resistance :/k", :/.k", :/.k", :/.k", :/.k", :/.k" V.A Fan motor (with inner-thermostat) MF Inner-thermostat -pole OUTPUT W DBPMS : i : : i : Fan motor capacitor C.+ V Vane motor MV MSBPCM DCV "/phase Drain-up mechanism Drain sensor Linear expansion valve Electric heater (Condensation proof) Power supply terminal block Transmission terminal block MA remote controller terminal block DP DS LEV H TB TB TB PLD-ME- INPUT /.W R/Hr Thermistor resistance :/k", :/.k", :/.k", :/.k", :/.k", :/.k" DCV Stepping motor drive port dimension." (~pulse) EDM-YME V.W (L, N, ;) Rated to V A W (M, M, S) Rated to V A W (, ) Rated to V A W W Note : Refer to WIRIN DIARAM for the supplied voltage.

11 Model Parts name Room temperature thermistor Liquid pipe thermistor Symbol TH TH PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK Resistance :/k", :/.k", :/.k", :/.k", :/.k", :/.k" Resistance :/k", :/.k", :/.k", :/.k", :/.k", :/.k" as pipe thermistor Fuse (Indoor controller board) TH FUSE Resistance :/k", :/.k", :/.k", :/.k", :/.k", :/.k" V.A Fan motor (with inner-thermostat) MF -pole OUTPUT W DBPMS Inner-thermostat -pole OUTPUT W DPMS : i : : i : Fan motor capacitor Vane motor Drain-up mechanism Drain sensor Linear expansion valve Electric heater (Condensation proof) Power supply terminal block Transmission terminal block MA remote controller terminal block C MV DP DS LEV H TB TB TB.+ V.+ V MSBPCM DCV "/phase PLD-ME- INPUT /.W R/Hr Thermistor resistance :/k", :/.k", :/.k", :/.k", :/.k", :/.k" DCV Stepping motor drive port dimension." (~pulse) EDM-YME V.W (L, N, ;) Rated to V A W (M, M, S) Rated to V A W (, ) Rated to V A W W Note : Refer to WIRIN DIARAM for the supplied voltage. -WAY AIR FLOW SYSTEM -. PLACEMENT OF THE AIR OUTLETS For this grille, the blowout direction comes in patterns. Also, by setting the dip switches (SWA and SWB) on the circuit board to the appropriate settings, you can adjust the air flow and speed. Select the settings from Table according to the location in which you want to install the unit. ) Decide on the pattern of the airflow direction. <Table > -direction -direction -direction Note. Blowout direction pattern Pattern Factory setting Pattern One air outlet fully closed Pattern Two air outlet fully closed For and -directional, please use the air outlet shutter plate (option).

12 ) According to the number of air outlets and height of the ceiling to install the unit, be sure to set the up switches (SWA, SWB) on the circuit board to the appropriate setting. Correspondence of ceiling heights to numbers of air outlets. SW V V SW SWA SW SW RD.DIIT ND.DIIT ST.DIIT SWB SWC (RED) ADDRESS CN SW CNECTI No. (RED) ADDRESS CN A.B PLFY-P P P P PVAM-E SWA SWB Standard High ceiling direction direction direction.m.m.m.m.m.m PLFY-P PVAM-E SWA SWB Standard direction.m direction.m direction.m High ceiling.m.m.m High ceiling.m.m High ceiling.m.m -. FRESH AIR INTAKE (Installation of site) At the time of installation, use the duct holes (cutout) located at the positions shown in following diagram, as and when required. Note : Be sure to addmm to the dimensions in the diagram that are marked with a w if installing a multi function casement (Option) Fresh air intake hole Fresh air intake hole diagram - {. Burring hole _ { Burring hole pitch w _ { (Cut out hole) Refrigerant pipe Drain pipe Ceiling surface -. INTERLOCKIN OPERATI METHOD WITH DUCT FAN (Booster fan) Whenever the indoor unit is operating, the duct fun also operates. ()Connect the optional multiple remote controller adapter(pac-saha-e)to the connector CN on the indoor controller board. ()Drive the relay after connecting the V DC relay between the Yellow and Orange connector lines. MB: Electromagnetic switch power relay for duct fan. X: Auxiliary relay (For DC V, coil rating :.W or below) CN on indoor controller board reen Connector (P) Red Brown Be sure to secure insulation material by tape and such Yellow Orange Package side Multiple remote controller adapter PAC-SAHA-E Indoor controller board CN ~ Installation at site MB Be sure to secure insulation material by tape and such Distance between indoor controller board and relay must be within m. Multiple remote controller adapter PAC-SAHA-E CN

13 -. FRESH AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS l PLFY-P P P P PVAM-E Multifunction casement + Standard filter Static pressure [Pa] Air flow [m /min] Multifunction casement + High efficiency filter Static pressure [Pa] Air flow [m /min] - intakes - intakes intake - intake - - Taking air into the unit Static pressure [Pa] Air flow [m /min] How to read curves Curve in the graphs. Q Q Duct characteristics at site B A A E C A D C Q Planned amount of fresh air intake <m /min> A Static pressure loss of fresh air intake duct system with air flow amount Q B <Pa> Forced static pressure at air conditioner inlet with air flow amount Q <Pa> C Static pressure of booster fan with air flow amount Q <Pa> D Static pressure loss increase amount of fresh air intake dust system for air flow amount Q <Pa> E Static pressure of indoor unit with air flow amount Q <Pa> Qa Estimated amount of fresh air intake with out D <m /min> PLFY-P PVAM-E Multifunction casement + Standard filter Q Qa Multifunction casement + High efficiency filter Static pressure [Pa] - - intakes Air flow [m /min] Static pressure [Pa] - - Air flow [m /min] intakes - intake - intake - - Taking air into the unit Static pressure [Pa] Air flow [m /min]

14 OUTLINES AND DIMENSIS PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK Unit : mm Liquid pipe as pipe _ { { Detail drawing of fresh air intake - {. Burring hole w Branch duct hole (Cut out hole) - {. Burring hole { Burring hole pitch { (Cut out hole) Ceiling surface Fresh air intake Branch duct hole Suspension bolt M or W/ ~ Ceiling hole ~ Suspension bolt pitch Terminal block Feeding hole (Drain pump) ~ Suspension bolt pitch ~ ~ ~ Drain pipe VP-connection (O.D.{) A B Ceiling hole Branch duct ho ~ Suspension bolt lower edge Power line entry Control wire entry Ceiling surface + High efficiency filter & Multi function + Air intake grille Air intake hole rille Drain hole M NOTES :. When servicing, electrical parts box may be disassembled. Make the wires loose enough when connecting heater power supply wire, remote controller wire, and indoor/outdoor unit connecting wire.. Detaching corner panel makes it possible to adjust the height of body with the grille attached.. Caution for attaching optional Muliti function casement and optional High efficiency filter : ) Space behind the ceiling shall be high enough as specified in the table below. P-P P-P ) Add extra mm to the dimensions of w in the figure. ) Mount both High efficiency filter and Multi function casement together.. When connecting branch duct, be sure to insulate the heat. (Otherwise, it causes dew to from or drop.) Air outlet hole M Air outlet hole M M Auto vane Air intake hole Vane motor Models Liquid Pipe as Pipe PLFY-PVAM-E.UK [. [. PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK [. / [. (Compatible) [. / [. (Compatible) [. PLFY-PVAM-E.UK [. PLFY-PVAM-E.UK PLFY-PVAM-E.UK [./[. (Compatible) A B

15 WIRIN DIARAM w PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK [LEEND] SYMBOL NAME P.B INDOOR POWER BOARD I.B INDOOR CTROLLER BOARD CN CNECTOR HUMIDIFIER CN DAMPER CN REMOTE SWITCH CN HA TERMINAL-A CN CENTRALLY CTROL CN REMOTE INDICATI SW SWITCH CAPACITY CODE SW FUNCTI SETTIN SW MODEL SELECTI ZNR VARISTOR FUSE FUSE(.A/V) F.C FAN PHASE CTROL X AUX.RELAY DRAIN WATER LIFTIN-UP MACH. X FAN MOTOR LED POWER SUPPLY(I.B) LED POWER SUPPLY(I.B) PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK SYMBOL C MF MV DP DS H TB TB TB TH TH TH LEV NAME CAPACITOR(FAN MOTOR) FAN MOTOR(WITH INNER THERMO.) VANE MOTOR DRAIN PUMP DRAIN SENSOR DEW PREVENTI HEATER TERMINAL POWER SUPPLY BLOCK TRANSMISSI MA-REMOTE CTROLLER THERMISTOR ROOM TEMP.DETECTI (:/k",:/.k") PIPE TEMP.DETECTI/LIQUID (:/k",:/.k") PIPE TEMP.DETECTI/AS (:/k",:/.k") LINEAR EXPANSI VALVE w The part name of symbol I.B is SPCB. SYMBOL NAME A.B CIRCUIT BOARD SW SWITCH FUNCTI SETTIN SW VOLTAE SELECTI SW ADDRESS SETTIN ST DIIT SW ADDRESS SETTIN ND DIIT SW CNECTI NO. SWA CEILIN HEIHT SELECTOR SWB DISCHARE OUTLET NUMBER SELECTOR SWC OPTI SELECTOR Position of TB,TB,TB,C. (For Control box) TB C TB SW SWA SWB V V SW SW SW SW SWC O RD.DIIT ND.DIIT ST.DIIT TB (RED) ADDRESS CN CNECTI No. I.B (RED) ADDRESS CN A.B RED FAN (WHT) (RED) DAMPER CN FC MF C WHT BLK LED on indoor controller board for service Mark LED RILLE MV MV MV MV Meaning Main power supply Power supply for MA-Remote controller WHT RED YLW ORN BRN BLU Function Main power supply(indoor unit:-v) power on lamp is lit Power supply for MA-Remote controller on lamp is lit TH TH TH LED NOTES:.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit..in case of using MA-Remote controller, please connect to TB.(Remote controller wire is non-polar.).in case of using M-NET, please connect to TB.(Transmission line is non-polar.).symbol[s] of TB is the shield wire connection..symbols used in wiring diagram above are, :terminal block, :connecter..the setting of the SW dip switches differs in the capacity. For the detail, refer to the table below..please set the switch SW according to the power supply voltage. Set SW to V side when the power supply is and volts. When the power supply is volts, set SW to V side. YLW YLW H BLU RED POWER D.U.M CND CNP (RED) (BLU) FUSE X HUMIDIFIER CN (WHT) ZNR (RN) VANE CNV (RED) ADDRESS CN X DP YLW YLW BRN BRN X X BLK WHT (RN) REMOTE (WHT) CENTRALLY INDICATI CTROL (RED) CN CN ADDRESS CN SW SW POWER CNDK (RED) LEV (WHT) LEV CN (AC-V) (DC.V) CNSK(RED) CNS (WHT) TRANS BLK WHT BLK BLK DS BLK BLK P.B CND (WHT) LED HA (WHT) REMOTE CN SWITCH (WHT) CN CNA (BLU) REMOC LED BLK BLK CNM (BLU) M-NET (WHT) (BLK) (WHT) (RED) SW DRAIN AS LIQUID INTAKE CN CN CN CN See fig: TB RED L BLU N RN/YLW BLU BLU ORN ORN } TB M M S (SHIELD) TB PVAM PVAM PVAM PVAM PVAM PVAM PVAM POWER SUPPLY ~/N -V Hz V Hz BREAKER (A) FUSE(A) PULL BOX TO NEXT INDOOR UNIT TO OUTDOOR UNIT BC CTROLLER } REMOTE CTROLLER DC-V TO MA-REMOTE CTROLLER DC.-V SW <fig: > SW

16 REFRIERANT SYSTEM DIARAM PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK as pipe thermistor TH Strainer (#mesh) as pipe Liquid pipe thermistor TH Flare connection Heat exchanger Liquid pipe Linear expansion valve Strainer (#mesh) Strainer (#mesh) Strainer (#mesh) Room temparature thermistor TH Item Capacity PLFY-P, PVAM-E PLFY-PVAM-E PLFY-P, PVAM-E PLFY-P, PVAM-E as pipe [.(/'') [.(/'')/[.(/'') [.(/'') [.(/'')/[.(/'') Liquid pipe [.(/'') [.(/'')/[.(/'') [.(/'') [.(/'')

17 TROUBLE SHOOTIN -. HOW TO CHECK THE PARTS PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK Parts name Room temperature thermistor (TH) Liquid pipe thermistor (TH) as pipe thermistor (TH) Check points Disconnect the connector then measure the resistance using a tester. (Surrounding temperature :~:) Normal.k"~.k" Abnormal Open or short Refer to the next page for the details. Vane motor(mv) White M Orange Red Blue Yellow Fan motor(mf) Measure the resistance between the terminals using a tester. (Surrounding temperature :~:) Connector Red Yellow Red Blue Red Orange Red White Normal Abnormal " Open or short Measure the resistance between the terminals using a tester. Relay connector Red White Black Motor terminal or Relay connector Red-Black White-Black Normal PLFY-P VAM-E.UK,,,,,."."."." Abnormal Open or short Protector Linear expansion valve(lev) Drain pump(dp) Blue M Brown Yellow White Red Orange Relay connector Yellow Yellow Disconnect the connector then measure the resistance valve using a tester. Normal White-Red Yellow-Brown Orange-Red Blue-Brown k" i% Measure the resistance between the terminals using a tester. (Surrounding temperature :~:) Normal Abnormal " Open or short Abnormal Open or short Refer to the next page for the details. Drain sensor(ds) Measure the resistance after minutes have passed since the power supply was intercepted. (Surrounding temperature :~:) Normal.k"~.k" Abnormal Open or short Refer to the next page for the details.

18 <Thermistor characteristic graph> Thermistor for lower temperature Room temperature thermistor(th) Liquid pipe temperature thermistor(th) as pipe temperature thermistor(th) < Thermistor for lower temperature > Thermistor R=k' ± % Fixed number of B=K ± % Rt=exp { ( +t ) } : k' :.k' :.k' :.k' :.k' :.k' Resistance (K") - - Temperature (:) Thermistor for drain sensor < Thermistor for drain sensor > Thermistor R=.k' ±% Fixed number of B=K ±% Rt=exp { ( +t ) } :.k' :.k' :.k' :.k' :.k' :.k' :.k' Linear expansion valve Operation summary of the linear expansion valve. Linear expansion valves open/close through the use of a stepping motor after receiving the pulse signal from the indoor controller board. Valve position can be changed in proportion to the number of pulse signals. <Connection between the indoor controller board and the linear expansion valve> Relay connector Resistance (K") - Temperature (:) Controller board DCV Linear expansion valve Brown White Blue M [ Brown [ [ [ Yellow Red Orange Red Blue Orange Yellow White Drive circuit [ [ [ [ Connector(CN) Note : Since the number of the connector at the controller board side and the relay connector are different, follow the color of the lead wire.

19 <Output pulse signal and the valve operation> Output (Phase) { { { { Output ➁ Linear expansion valve operation Open Valve position (capacity) A E Close Open D C Closing a valve : Opening a valve : The output pulse shifts in above order.. When linear expansion valve operation stops, all output phase become.. At phase interruption or when phase does not shift in order, motor does not rotate smoothly and motor will locks and vibrates. Outdoor unit RA model : pulse Outdoor unit R/RC model : pulse Opening a valve all the way When the switch is turned on, pulse closing valve signal will be send till it goes to point A in order to define the valve position. When the valve moves smoothly, there is no noise or vibration occurring from the linear expansion valves : however, when the pulse number moves from E to A or when the valve is locked, more noise can be heard than in a normal situation. Noise can be detected by placing the ear against the screw driver handle while putting the screw driver tip to the linear expansion valve. Close B Pulse number Extra tightening (~ pulse) ➂ Trouble shooting Symptom Operation circuit failure of the micro processor. Linear expansion valve mechanism is locked. Short or breakage of the motor coil of the linear expansion valve. Valve doesn't close completely. Wrong connection of the connector or contact failure. Check points Disconnect the connector on the controller board, then connect LED for checking. k" LED When power is turned on, pulse signals will output for seconds. There must be some defects in the operation circuit if the LED does not light while the signals are output or keeps lighting even after the signals stop. Motor will idle and make a ticking noise when the motor is operated while the linear expansion valve is locked. This ticking sound is the sign of the abnormality. Measure the resistance between each coil (white-red, yellowbrown, orange-red, blue-brown) using a tester. It is normal if the resistance is in the range of Ω ±%. To check the linear expansion valve, operate the indoor unit in fan mode and at the same time operate other indoor units in cooling mode, then check the pipe temperature <liquid pipe temperature> of the indoor unit by the outdoor multi controller board operation monitor. During fan operation, linear Thermistor (Liquid pipe) Linear expansion expansion valve is closed completely and if there is any leaking, detecting temperature of the thermistor will go lower. If the detected temperature is much lower than the temperature indicated in the remote controller, valve it means the valve is not closed all the way. It is not necessary to exchange the linear expansion valve, if the leakage is small and not affecting normal operation. Check the color of lead wire and missing terminal of the connector. Countermeasures Exchange the indoor controller board at drive circuit failure. Exchange the linear expansion vale. Exchange the linear expansion valve. If large amount of thermistor is leaked, exchange the linear expansion valve. Disconnect the connector at the controller board, then check the continuity.

20 -. FUNCTI OF DIP SWITCH Switch Pole Function Operation by switch Effective timing Remarks Thermistor <Room temperature detection> position Built-in remote controller Indoor unit Address board Filter clogging detection Provided Not provided <At delivery> Filter cleaning,hr hr Fresh air intake Effective Not effective SW Switching remote Indicating if the Indicating fan operation Under Note : controller display thermostat is / Function suspension w Fan operation at Heating setting Humidifier control Always operated while the heat in w Operated depends on the condition w mode. w Heater thermostat is Air flow set in case of Low w Extra low w operating. Heat thermostat Setting air flow w Depends on SW- w SW -=, SW -= Setting air flow. Auto restart function Effective Not effective SW -=, SW -= Indoor fan stop. Power / by breaker Effective Not effective Capacity SW Capacity SW Capacity SW Indoor controller board SW Capacity code setting ~ P P P P P Before power supply Set while the unit is off. <At delivery> Set for each capacity. P P Heat pump / Cooling only Louver / humidifier w Cooling only Available Heat pump Not available Indoor controller board Set while the unit is off. <At delivery> SW Function setting Vane Vane swing function Vane horizontal angle Vane cooling limit angle setting w Changing the opening of linear expansion valve when the thermostat is Heat degrees up Superheat setting temperature w Sub cool setting temperature Available Available Second setting Horizontal angle Effective Not effective ()degrees degrees Not available Not available First setting Down B, C Not effective Effective ()degrees degrees Under suspension P, P : SW- = SW- = P~P : SW- = SW- = Note : w At cooling mode, each angle can be used only hour. w The numerical valve in the parentheses shows the case which the R outdoor unit is connected. w SW- setting Only for PLFY-P VAM, SW is used to change whether the humidifier functions or not. (Fixed the louver function less.) SW Model Selection (Setting for PLFY series) ~ In case replacing the indoor controller board, make sure to set the switch to the factory-preset status, which is shown below. Before power supply Indoor controller board

21 Switch Pole Operation by switch Effective timing Remarks SWA Ceiling height selector SWB Discharge outlet number selector ~ (High ceiling) (High ceiling) (Standard) ( direction) ( direction) ( direction) Ceiling height can be changed depends on SWB setting. PLFY-P,P,P,P,PVAM-E SWA High High SWB Standard ceiling ceiling direction direction direction.m.m.m PLFY-P, PVAM-E SWA SWB direction direction direction Standard.m.m.m.m.m.m.m.m High ceiling.m.m.m High ceiling.m.m Under operation or suspension Address board <At delivery> Address board <At delivery> Address board SWC Option selector Option Standard When attach the optional high performance filter elements (multi function casement) to the unit, be sure to attach it to the option side in order to prevent the airflow reducing. Option Standard <At delivery> SW st digit address setting SW nd digit address setting Rotary switch SW SW Address setting should be done when M-NET Remote controller is being used. Address board Address can be set while the unit is stopped. <At delivery> SW SW Address board SW Connection No. setting Rotary switch E D C B SW A F This is the switch to be used when the indoor unit is operated with R series outdoor unit as a set. Before power supply <At delivery> SW E D C B A F Address board SW Voltage Selection V V If the unit is used at the V or V area, set the voltage to V. If the unit is used at the V, set the voltage to V. <At delivery> V V

22 -. TEST POINT DIARAM --. Indoor controller board PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK CND Connect to the indoor power board (CNS).-.V DC (Pin (+)) CNM Connect to the terminal block (TB) (M-NET transmission connecting wire) -V DC (non-polar) CNA Connect to the terminal block (TB) (MA-Remote controller connecting wire) Between to.-v DC (Pin (+)) CN Pipe temperature thermistor/as (TH) CN Pipe temperature thermistor/liquid (TH) LED Main power supply (Indoor unit : -V) CND Power supply for indoor controller board Between to -V AC CNP Drain pump output (DP) Between to -V AC FUSE.A V CNDK Connect to the indoor power board (CNSK) Between to -V AC LED Power supply for MA-Remote controller CN Room temperature thermistor (TH) CN Connector (Remote switch) SW Model selection CN Linear expansion valve output (LEV) CN Drain sensor (DS) SW Function setting CN Centrally control SW Capacity setting CN Remote indication CNV Vane motor output (MV) CN Connecter(Humidifier) FAN Fan motor output (MF) CN Connector (Damper)

23 --. Indoor power board PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK CNS Connect to the indoor power board (CND) Between to.-.v DC (Pin (+)) CNSK Connect to the indoor controller board (CNDK) Between to -V AC --. Circuit board PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK SW Function setting SW Voltage selector SWA Ceiling hight selector SWB Discharge outlet number selector SW address setting nd digit SW address setting st digit SWC Option selector

24 DISASSEMBLY PROCEDURE PLFY-P//////VAM-E.UK OPERATIN PROCEDURE Be careful on removing heavy parts. PHOTOS&ILLUSTRATIS. Removing the air intake grille () Slide the knob of air intake grille to the direction of the arrow to open the air intake grille. () Remove the string hook from the panel to prevend the grille from dropping. () Slide the shaft in the hinge to the direction of the arrow and remove the air intake grille. Figure Air intake grille Air intake grille knob rille. Removing the fan guard () Open the air intake grille. () Remove the screws of fan guard. Photo Screws Fan guard Air intake grille. Removing the room temperature thermistor ()Remove the fan guard.(see photo ) () Remove the screw( ) in the room temperature thermistor holder to remove the holder and the room temperature thermistor. () Remove the screw from the bell mouth, and unscrew the another screws (fixed to the oval hole which has different diameter) to remove the bell mouth. () Hold the holder claw, and remove the room temperature thermistor and holder. () Disconnect the connector (red) in the indoor control board. Photo Bell mouth Screws Room temperature thermistor Air intake grille. Removing the electrical box () Remove the fan guard.(see photo ) () Remove the lead wire of the vane motor from the clamp, and disconnect the white connector (P). () Remove the room temperature thermistor with the holder. () Remove the bell mouth.(see photo ) () Disconnect the relay connector in the electrical box. Red (P) for fan motor power supply White (P) for pipe temperature detection / liquid thermistor Black (P) for pipe temperature detection / gas thermistor Blue (P) for drain pump White (P) for drain sensor () Remove the screws from the electrical box, loosen another screws to remove the box. <Electrical parts in the electrical box> Indoor controller board power supply board Terminal block (Power supply) Terminal block (Transmission) Terminal block (MA remote controller) Capacitor Circuit(address) board Photo Electrical box Power supply board Circuit (address) board Connector Turbo fan Nut Indoor controller board Capacitor Connector Terminal block

25 OPERATIN PROCEDURE. Removing the fan motor () Remove the fan guard.(see photo ) () Remove the bell mouth.(see photo ) () Remove the electrical box.(see photo ) () Remove the turbo fan nut, washer and radiation cap(p, P). () Pull out the turbo fan. () Disconnect the connector of the fan motor lead wire. () Remove the nuts of the fan motor. Photo PHOTOS&ILLUSTRATIS Fan motor Nut Nut Connector. Removing the pipe temperature detection / liquid thermistor and the pipe temperature detection / gas thermistor () Remove the fan guard.(see photo ) () Remove the bell mouth.(see photo ) () Remove the electrical box.(see photo ) () Remove the turbo fan. () Remove the screw of the service panel. () Remove the service panel. () Remove the pipe temperature detection / liquid thermistor and the pipe temperature detection / gas thermistor which are inserted into the holder installed to the thin copper pipe. () Disconnect the each -pin white(liquid) and black(gas) connector. Photo Pipe temperature detection / gas thermistor Service entrance Pipe temperature detection / liquid thermistor. Removing the panel () Remove the air intake grille.(see figure ) Corner panel (See figure ) () Remove the screw of the corner. () Slide the corner panel to the direction of the arrow, and remove the corner panel. Panel (See photo ) () Disconnect the connector that connects with the unit. () Remove the screws from the panel and loose another screws, which fixed to the oval hole, have different diameter. () Rotate the panel a little to remove the panel. (Slide the panel so that the screw comes to a large diameter of the oval hole, which has two different diameters.) Figure Corner panel Photo Connector Screw Screw Corner panel Panel Screw Panel. Removing the drain pan () Remove the panel. (See photo ) () Remove the drain plug (Larger one), drain the remaining water in the drain pan. () Remove the corner cover. ( screws) () Remove the bell mouth. (See photo ) () Remove the electrical box. (See photo ) () Remove the lead wire holder. ( screw) () Remove the screws and pull out the drain pan. w Pull out the left and right of the pan gradually. Be careful not to crack or damage the pan. Photo Screw Drain pan Screw Screw Screw Lead wire holder Drain plug(larger one) Corner cover

26 OPERATIN PROCEDURE PHOTOS&ILLUSTRATIS. Removing the drain pump and drain sensor () Remove the panel. (See photo ) () Remove the fan guard. (See photo ) () Remove the bell mouth. (See photo ) () Remove the electrical box. (See photo ) () Remove the drain pan. (See photo ) () Cut the drain hose band with scissors and pull out the drain hose from the drain pump. () Loosen the screw A ( screws) and remove the screw B ( screw). Slide the drain pump in the direction of the arrow C and remove it. () Remove the drain sensor with its holder from the drain pump. Photo Screw A Drain hose Fixing band C Drain pump Drain sensor Screw B. Removing the heat exchanger () Remove the panel. (See photo ) () Remove the fan guard. (See photo ) () Remove the bell mouth. (See photo ) () Remove the electrical box. (See photo ) () Remove the drain pan. (See photo ) () Remove the turbo fan. (See photo ) () Remove the screws of the piping cover, and pull out piping cover. () Remove the screws of the outer wall cover, and pull out the outer wall cover. () Remove the screw of the coil support. () Remove the screws of the coil. () Pull out the heat exchanger. Photo Heat exchanger Coil support Coil support Coil screws Coil support Photo Screw Outer wall cover Piping cover Screws of piping cover

27 PARTS LIST (non-rohs compliant) PANEL PARTS PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK TEMP. / Part number that is circled is not shown in the figure. Q'ty/set No. Part No. Part Name PLFY- Specification Remarks P, P, P, P (Drawing No.) P, P, P VAM-E.UK S E S E S E S E S E S E S E S E S E S E AIR OUTLET RILLE AUTO VANE CORNER PANEL CORNER PANEL L.L FILTER RILLE ASSY VANE MOTOR VANE BUSH EAR (VANE) EAR (MOTOR) Including H S KW S E REMOTE CTROLLER SCREW ASSY PAR-MAA Wiring Diagram Symbol MV Recommended Q'ty Unit Price Amount

28 FUNCTIAL PARTS PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK MOTOR CAP SPL WASHER THERMISTOR (AS) THERMISTOR (LIQUID) No. Parts No. Parts Name S S E S S E S E S K S E S E S E S E S E S J S N S E S E S E S E S A S BASE DW LE DRUM ASSY LE TURBO FAN SPL WASHER HEAT EXCHANER HEAT EXCHANER HEAT EXCHANER HEAT EXCHANER LINEAR EXPANSI VALVE THERMISTOR (LIQUID) THERMISTOR (AS) MOTOR CAP INNER COVER ASSY LE FAN MOTOR MOTOR MOUNT DRUM ASSY Specification DBPMS PLFY-P VAM-E.UK Q'ty / set Remarks (Drawing No.) LEV TH TH MF Price Wiring Recom- Diagram Symbol mended Q'ty Unit Amount

29 FUNCTIAL PARTS PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK SPL WASHER THERMISTOR (AS) THERMISTOR (LIQUID) No. Parts No. Parts Name Specification S S E S S S E S E S E S K S E S E S E S J S N S E S E S E S E S E S A S S BASE DW LE DRUM ASSY DRUM ASSY LE TURBO FAN TURBO FAN SPL WASHER HEAT EXCHANER HEAT EXCHANER LINEAR EXPANSI VALVE THERMISTOR (LIQUID) THERMISTOR (AS) INNER COVER ASSY INNER COVER ASSY LE FAN MOTOR FAN MOTOR MOTOR MOUNT DRUM ASSY DRUM ASSY DBPMS DPMS Q'ty / set PLFY-P VAM-E.UK Remarks (Drawing No.) LEV TH TH MF MF Price Wiring Recom- Diagram Symbol mended Q'ty Unit Amount

30 FUNCTIAL PARTS PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK FUSE DRAIN PLU DRAIN PLU CAPACITOR POWER SUPPLY TERMINAL BLOCK TRANSMISSI TERMINAL BLOCK MA-REMOTE CTROLLER TERMINAL BLOCK THERMISTOR (ROOM) No. Parts No. Parts Name Specification S E S A S E S E S K S E S E S S E S S E S E S E S B S S B S S S S A S A DRAIN PAN DRAIN SOCKET DRAIN PUMP DRAIN SENSOR DRAIN SENSOR HOLDER CTROL BOX POWER BOARD FUSE INDOOR CTROLLER BOARD CTROL COVER ASSY FAN UARD THERMISTOR (ROOM) ADDRESS CABLE ADDRESS BOARD MA-REMOTE CTROLLER TERMINAL BLOCK TRANSMISSI TERMINAL BLOCK POWER SUPPLY TERMINAL BLOCK FAN MOTOR CAPACITOR CORNER COVER DRAIN PLU DRAIN PLU.A V P(, ) P(M, M, S) P(L, N, ;).+ V Q'ty / set Remarks PLFY-P VAM-E.UK (Drawing No.),,, DP DS P.B FUSE I.B w TH A.B TB TB TB C Price Wiring Recom- Diagram Symbol mended Q'ty Unit Amount w The part name of symbol I.B is SPCB.

31 FUNCTIAL PARTS PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK FUSE DRAIN PLU DRAIN PLU CAPACITOR POWER SUPPLY TERMINAL BLOCK TRANSMISSI TERMINAL BLOCK MA-REMOTE CTROLLER TERMINAL BLOCK THERMISTOR (ROOM) No. Parts No. Parts Name S E S E S A S E S E S K S E S E S S E S S E S E S E S B S S B S S T S E S S A S A DRAIN PAN DRAIN PAN DRAIN SOCKET DRAIN PUMP DRAIN SENSOR DRAIN SENSOR HOLDER CTROL BOX POWER BOARD FUSE INDOOR CTROLLER BOARD CTROL COVER ASSY FAN UARD THERMISTOR (ROOM) ADDRESS CABLE ADDRESS BOARD MA-REMOTE CTROLLER TERMINAL BLOCK TRANSMISSITERMINAL BLOCK POWER SPPLY TERMINAL BLOCK FAN MOTOR CAPACITOR FAN MOTOR CAPACITOR CORNER COVER DRAIN PLU DRAIN PLU Specification.A V P(, ) P(M, M, S) P(L, N,;).+ V.+ V, Q'ty / set PLFY-P VAM-E.UK Remarks (Drawing No.) DP DS P.B FUSE I.B w TH A.B TB TB TB C C Price Wiring Recom- Diagram Symbol mended Q'ty Unit Amount w The part name of symbol I.B is SPCB.

32 RoHS PARTS LIST PANEL PARTS PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK TEMP. / Part number that is circled is not shown in the figure. RoHS No. Q'ty/set Part No. Part Name PLFY- Remarks Specification P, P, P, P (Drawing No.) P, P, P VAM-E.UK S E S E S E S E S E S E S E S E S E S E AIR OUTLET RILLE AUTO VANE CORNER PANEL CORNER PANEL L.L FILTER RILLE ASSY VANE MOTOR VANE BUSH EAR (VANE) EAR (MOTOR) Including H S KW S E REMOTE CTROLLER SCREW ASSY PAR-MAA Wiring Diagram Symbol MV Recommended Q'ty Unit Price Amount

33 FUNCTIAL PARTS PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK MOTOR CAP SPL WASHER THERMISTOR (AS) THERMISTOR (LIQUID) No. Parts No. Parts Name RoHS S S E S S E S E S K S E S E S E S E S E S J S N S E S E S E S E S A S BASE DW LE DRUM ASSY LE TURBO FAN SPL WASHER HEAT EXCHANER HEAT EXCHANER HEAT EXCHANER HEAT EXCHANER LINEAR EXPANSI VALVE THERMISTOR (LIQUID) THERMISTOR (AS) MOTOR CAP INNER COVER ASSY LE FAN MOTOR MOTOR MOUNT DRUM ASSY Specification DBPMS PLFY-P VAM-E.UK Q'ty / set Remarks (Drawing No.) LEV TH TH MF Price Wiring Recom- Diagram Symbol mended Q'ty Unit Amount

34 FUNCTIAL PARTS PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK SPL WASHER THERMISTOR (AS) THERMISTOR (LIQUID) No. Parts No. Parts Name Specification RoHS S S E S S S E S E S E S K S E S E S E S J S N S E S E S E S E S E S A S S BASE DW LE DRUM ASSY DRUM ASSY LE TURBO FAN TURBO FAN SPL WASHER HEAT EXCHANER HEAT EXCHANER LINEAR EXPANSI VALVE THERMISTOR (LIQUID) THERMISTOR (AS) INNER COVER ASSY INNER COVER ASSY LE FAN MOTOR FAN MOTOR MOTOR MOUNT DRUM ASSY DRUM ASSY DBPMS DPMS Q'ty / set Remarks Wiring Recommended PLFY-P VAM-E.UK (Drawing Diagram Price Symbol No.) Q'ty Unit Amount LEV TH TH MF MF

35 FUNCTIAL PARTS PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK FUSE DRAIN PLU DRAIN PLU CAPACITOR POWER SUPPLY TERMINAL BLOCK TRANSMISSI TERMINAL BLOCK MA-REMOTE CTROLLER TERMINAL BLOCK THERMISTOR (ROOM) No. Parts No. Parts Name RoHS S E S A S E S E S K S E S E S S E S S E S E S E S B S S B S S S S A S A DRAIN PAN DRAIN SOCKET DRAIN PUMP DRAIN SENSOR DRAIN SENSOR HOLDER CTROL BOX POWER BOARD FUSE INDOOR CTROLLER BOARD CTROL COVER ASSY FAN UARD THERMISTOR (ROOM) ADDRESS CABLE ADDRESS BOARD MA-REMOTE CTROLLER TERMINAL BLOCK TRANSMISSI TERMINAL BLOCK POWER SUPPLY TERMINAL BLOCK FAN MOTOR CAPACITOR CORNER COVER DRAIN PLU DRAIN PLU Specification.A V P(, ) P(M, M, S) P(L, N, ;).+ V Q'ty / set Remarks PLFY-P VAM-E.UK (Drawing No.),,, DP DS P.B FUSE I.B w TH A.B TB TB TB C Price Wiring Recom- Diagram Symbol mended Q'ty Unit Amount w The part name of symbol I.B is SPCB.

36 FUNCTIAL PARTS PLFY-PVAM-E.UK PLFY-PVAM-E.UK PLFY-PVAM-E.UK FUSE DRAIN PLU DRAIN PLU CAPACITOR POWER SUPPLY TERMINAL BLOCK TRANSMISSI TERMINAL BLOCK MA-REMOTE CTROLLER TERMINAL BLOCK THERMISTOR (ROOM) No. Parts No. Parts Name RoHS S E S E S A S E S E S K S E S E S S E S S E S E S E S B S S B S S T S E S S A S A DRAIN PAN DRAIN PAN DRAIN SOCKET DRAIN PUMP DRAIN SENSOR DRAIN SENSOR HOLDER CTROL BOX POWER BOARD FUSE INDOOR CTROLLER BOARD CTROL COVER ASSY FAN UARD THERMISTOR (ROOM) ADDRESS CABLE ADDRESS BOARD MA-REMOTE CTROLLER TERMINAL BLOCK TRANSMISSITERMINAL BLOCK POWER SPPLY TERMINAL BLOCK FAN MOTOR CAPACITOR FAN MOTOR CAPACITOR CORNER COVER DRAIN PLU DRAIN PLU Specification.A V P(, ) P(M, M, S) P(L, N, ;).+ V.+ V Q'ty / set Remarks PLFY-P VAM-E.UK (Drawing No.), DP DS P.B FUSE I.B w TH A.B TB TB TB C C Price Wiring Recom- Diagram Symbol mended Q'ty Unit Amount w The part name of symbol I.B is SPCB.

37 OPTIAL PARTS -. MULTI FUNCTI CASEMENT Part No. PAC-STM-E -. AIR OUTLET SHUTTER PLATE ( sets) Part No. PAC-SSP-E -. HIH EFFICIENCY FILTER (PAC-STM-E is required in using this optional part.) Part No. PAC-SKF

38

39

40 TM HEAD ICE : TOKYO BLD., --, MARUNOUCHI, CHIYODA-KU TOKYO -, JAPAN ccopyright MITSUBISHI ELECTRIC ENINEERIN CO., LTD. Distributed in Jul.. No. OC REVISED EDITI-B PDF Distributed in Sep.. No. OC REVISED EDITI-A PDF Distributed in May. No. OC PDF Made in Japan New publication, effective Jul. Specifications subject to change without notice

TECHNICAL & SERVICE MANUAL. Wall Mounted. Series PKFY PKFY-P20VAM-A PKFY-P25VAM-A R407C R22 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No.

TECHNICAL & SERVICE MANUAL. Wall Mounted. Series PKFY PKFY-P20VAM-A PKFY-P25VAM-A R407C R22 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. SPLIT-TYPE, HEAT PUMP AIR CDITIERS 00 No. OC TECHNICAL & SERVICE MANUAL Series PKFY Wall Mounted R07C R Indoor unit [Model names] PKFY-P0VAM-A [Service Ref.] PKFY-P0VAM-A CTENTS INDOOR UNIT. SAFETY PRECAUTI.

More information

PKFY-P32VGM-E PKFY-P40VGM-E PKFY-P50VGM-E

PKFY-P32VGM-E PKFY-P40VGM-E PKFY-P50VGM-E SPLIT-TYPE, HEAT PUMP AIR CDITIERS July 00 No. OC0 REVISED EDITI-A TECHNICAL & SERVICE MANUAL Series PKFY Wall Mounted R0A R0C R [Model names] PKFY-PVGM-E PKFY-P0VGM-E PKFY-P0VGM-E [Service

More information

Floor Standing PFFY-P20VKM-E PFFY-P20VKM-ER1 PFFY-P25VKM-E PFFY-P25VKM-ER1 PFFY-P32VKM-E PFFY-P32VKM-ER1 PFFY-P40VKM-E PFFY-P40VKM-ER1

Floor Standing PFFY-P20VKM-E PFFY-P20VKM-ER1 PFFY-P25VKM-E PFFY-P25VKM-ER1 PFFY-P32VKM-E PFFY-P32VKM-ER1 PFFY-P40VKM-E PFFY-P40VKM-ER1 SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL November 008 No. OC0 REVISED EDITI-A Series PFFY Indoor unit [Model names] PFFY-P0VKM-E PFFY-PVKM-E PFFY-PVKM-E PFFY-P0VKM-E Floor Standing

More information

PKFY-P15VBM-E PKFY-P20VBM-E PKFY-P20VBM-ER1 PKFY-P25VBM-E PKFY-P25VBM-ER1

PKFY-P15VBM-E PKFY-P20VBM-E PKFY-P20VBM-ER1 PKFY-P25VBM-E PKFY-P25VBM-ER1 SPLIT-TYPE, HEAT PUMP AIR CDITIERS November No. OCH REVISED EDITI-A TECHNICAL & SERVICE MANUAL RA R7C R Indoor unit [Model names] PKFY-PVBM-E PKFY-PVBM-E PKFY-PVBM-E [Service Ref.] PKFY-PVBM-E PKFY-PVBM-E

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL RESET SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. OC0 TECHNICAL & SERVICE MANUAL Series SLZ Ceiling Cassettes R0A Indoor unit [Model names] SLZ-A09AR SLZ-AAR SLZ-A8AR [Service Ref.] SLZ-A09AR.TH SLZ-AAR.TH

More information

PLFY-P15VCM-E3.TH PLFY-P20VCM-E3.TH PLFY-P25VCM-E3.TH PLFY-P32VCM-E3.TH PLFY-P40VCM-E3.TH

PLFY-P15VCM-E3.TH PLFY-P20VCM-E3.TH PLFY-P25VCM-E3.TH PLFY-P32VCM-E3.TH PLFY-P40VCM-E3.TH SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL June 04 No. Indoor unit [Model Name] PLFY-PVCM-E PLFY-P0VCM-E PLFY-PVCM-E PLFY-PVCM-E PLFY-P40VCM-E R40A [Service Ref.] PLFY-PVCM-E.TH PLFY-P0VCM-E.TH

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL RA December 22 No. OCH REVISED EDITI-C Indoor unit [Model names] PKFY-PVBM-E PKFY-P2VBM-E PKFY-P2VBM-E [Service Ref.] PKFY-PVBM-E PKFY-PVBM-ER2

More information

TECHNICAL & SERVICE MANUAL. Ceiling Concealed

TECHNICAL & SERVICE MANUAL. Ceiling Concealed STAND BY DEFROST CHECK CLOCK ON OFF NOT AVAILABLE FILTER CHECK MODE TEST RUN FUNCTION SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL Series SEZ Ceiling Concealed R40A.OC0 REVISED EDITION-A

More information

PMFY-P-VBM-E. Ceiling cassette (1-way flow type) R410A Data G8 1. SPECIFICATIONS EXTERNAL DIMENSIONS CENTER OF GRAVITY 1-100

PMFY-P-VBM-E. Ceiling cassette (1-way flow type) R410A Data G8 1. SPECIFICATIONS EXTERNAL DIMENSIONS CENTER OF GRAVITY 1-100 Ceiling cassette (-way flow type) RA Data G8 -P-VBM-E. SPECIFICATIONS - 98. EXTERNAL DIMENSIONS - 99 3. CENTER OF GRAVITY -. ELECTRICAL WIRING DIAGRAMS -. SOUND LEVELS -. Sound levels -. NC curve 6. TEMPERATURE/AIRFLOW

More information

Ceiling Cassettes PLH-3AKH1.UK PLH-3AKH.UK PLH-4AKHS1.UK PLH-4AKHS.UK PLH-5AKHS1.UK PLH-5AKHS.UK PLH-6AKHS1.UK PLH-6AKHS.UK

Ceiling Cassettes PLH-3AKH1.UK PLH-3AKH.UK PLH-4AKHS1.UK PLH-4AKHS.UK PLH-5AKHS1.UK PLH-5AKHS.UK PLH-6AKHS1.UK PLH-6AKHS.UK T AVAILABLE C AMPM AMPM SPLIT-TYPE, HEAT PUM PAIR CDITIERS No. OC REVISED EDITI-A TECHNICAL & SERVICE MANUAL Series PLH Indoor unit [Model names] PLH-3AK PLH-3AKH PLH-AKS PLH-AKHS PLH-5AKS PLH-5AKHS PLH-6AKS

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL No. OCH468 REVISED EDITI-A HFC utilized R4A June 2 [Model name] MXZ-8B48NA PAC-AKA5BC PAC-AKA3BC (Indispensable

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CDITIERS December No. OCH7 REVISED EDITI-B TECHNICAL & SERVICE MANUAL RA R7C R Indoor unit [Model names] PKFY-PVKM-E PKFY-PVKM-E [Service Ref.] PKFY-PVKM-E.TH PKFY-PVKM-ER.TH

More information

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA PEAD-RP100EA(2) PEAD-RP125EA PEAD-RP140EA

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA PEAD-RP100EA(2) PEAD-RP125EA PEAD-RP140EA SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 005 SERVICE MANUAL Series PEAD R7C/RA Service ref. Models RP35EA() RP50EA RPEA RP7EA RP00EA() RP5EA RPEA NOTE: This manual describes only service data

More information

PEFY-P20VMS-E, PEFY-P40VMS-E PEFY-P25VMS-E, PEFY-P50VMS-E PEFY-P32VMS-E, PEFY-P63VMS-E

PEFY-P20VMS-E, PEFY-P40VMS-E PEFY-P25VMS-E, PEFY-P50VMS-E PEFY-P32VMS-E, PEFY-P63VMS-E 2006 Air-Conditioners TECHNICAL & SERVICE MANUAL Models PEFY-P20VMS-E, PEFY-P40VMS-E PEFY-P25VMS-E, PEFY-P50VMS-E PEFY-P2VMS-E, PEFY-P6VMS-E For use with R40A, R407C, & R22 Safety Precautions Read before

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH530 Models MU-GE50VB- E1 - E1 Indoor unit service manual MS/MSH-GE VB Series (OBH529) CONTENTS 1. TECHNICAL CHANGES 2 2. PART

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL AIR CONDITIONERS 0 TECHNICAL & SERVICE MANUAL Models P0VMA(L)-E, P5VMA(L)-E, PVMA(L)-E, P40VMA(L)-E, P50VMA(L)-E, P6VMA(L)-E P7VMA(L)-E P80VMA(L)-E P00VMA(L)-E P5VMA(L)-E P40VMA(L)-E Safety Precautions

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS TECHNICAL & SERVICE MANUAL R07C Outdoor unit [model names] No.OC6 REVISED EDITION-B PUH-PVGAA PUH-P.6VGAA PUH-P.6YGAA PUH-PVGAA PUH-PYGAA

More information

TECHNICAL & SERVICE MANUAL. Floor Standing Type. Series PFFY. For use with the R407C & R22. Air-Conditioners For Building Application

TECHNICAL & SERVICE MANUAL. Floor Standing Type. Series PFFY. For use with the R407C & R22. Air-Conditioners For Building Application Air-Conditioners For Building Application 00 TECHNICAL & SERVICE MANUAL Series PFFY Floor Standing Type Models PFFY-P0VLEM-A,PFFY-P0VLRM-A PFFY-PVLEM-A,PFFY-PVLRM-A PFFY-PVLEM-A,PFFY-PVLRM-A

More information

SERVICE MANUAL PCH-P50GAH PCH-P60GAH PCH-P71GAH PCH-P100GAH PCH-P125GAH PCH-P140GAH. May 2008

SERVICE MANUAL PCH-P50GAH PCH-P60GAH PCH-P71GAH PCH-P100GAH PCH-P125GAH PCH-P140GAH. May 2008 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS SERVICE MANUAL May 008 No. OC8 REVISED EDITION-B Indoor unit [Model names] [Service Ref.] PCA-RP0A PCA-RP0A PCA-RP0A# PCA-RP0A PCA-RP0A

More information

SERVICE MANUAL. Series PEA SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS CONTENTS

SERVICE MANUAL. Series PEA SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS CONTENTS SPLIT-TYPE, HEAT PUMP AIR CDITIERS 0 SERVICE MANUAL Series PEA Model name PEA-RP00GAQ PEA-RP0GAQ PEA-RP00GAQ PEA-RP00GAQ This manual describes only service data of the indoor units. CTENTS

More information

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-SP100JA(L) PEAD-SP125JA(L) PEAD-SP140JA(L) Models PEAD-SP71JA(L) <indoor unit>

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-SP100JA(L) PEAD-SP125JA(L) PEAD-SP140JA(L) Models PEAD-SP71JA(L) <indoor unit> SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 4 SERVICE MANUAL Series PEAD R4A Models PEAD-SP7JA(L) PEAD-SPJA(L) PEAD-SP5JA(L) PEAD-SPJA(L) NOTE: This manual describes only service data of the indoor

More information

SLZ-KF25VA.TH SLZ-KF35VA.TH SLZ-KF50VA.TH SLZ-KF60VA.TH

SLZ-KF25VA.TH SLZ-KF35VA.TH SLZ-KF50VA.TH SLZ-KF60VA.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL October 205 No. Indoor unit [Model Name] SLZ-KF25VA SLZ-KF35VA SLZ-KF50VA SLZ-KF60VA [Service Ref.] SLZ-KF25VA.TH SLZ-KF35VA.TH SLZ-KF50VA.TH

More information

SERVICE MANUAL MUX-A22WV - E1 HFC. Multi system type Model SPLIT-TYPE, AIR CONDITIONER. No. OB318 R410A CONTENTS. Revision A: MUX-A22WV -

SERVICE MANUAL MUX-A22WV - E1 HFC. Multi system type Model SPLIT-TYPE, AIR CONDITIONER. No. OB318 R410A CONTENTS. Revision A: MUX-A22WV - SPLIT-TYPE, AIR CDITIER Revision A: MUX-AWV - E can be connected to MSC-A07/AYV - E. PARTS LIST has partially modified. Please void OB8. SERVICE MANUAL Multi system type Model HFC utilized R40A. OB8 REVISED

More information

CASSETTE type INVERTER MULTI AIR CONDITIONER. Models AUY12LBAB AUY14LBAB AOY18LMAK2

CASSETTE type INVERTER MULTI AIR CONDITIONER. Models AUY12LBAB AUY14LBAB AOY18LMAK2 INVERTER MULTI AIR CONDITIONER CASSETTE type Models Indoor unit AUY12LBAB AUY14LBAB Outdoor unit AOY18LMAK2 CONTENTS SPECIFICATIONS..................... 1 OUTLINE AND DIMENSIONS........... 2 REFRIGERANT

More information

Series PEAD SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS R32/R410A PEAD-SM100JA(L) PEAD-SM125JA(L) PEAD-SM140JA(L) Models PEAD-SM71JA(L)

Series PEAD SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS R32/R410A PEAD-SM100JA(L) PEAD-SM125JA(L) PEAD-SM140JA(L) Models PEAD-SM71JA(L) SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 2018 SERVICE MANUAL Series PEAD R32/R4A Models PEAD-SM71JA(L) PEAD-SM0JA(L) PEAD-SM125JA(L) PEAD-SM1JA(L) NOTE: This manual describes only service data

More information

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type)

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) TECHNICAL MANUAL & PARTS LIST DRAFT INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) SRK20ZD-S - 1 - INDOOR UNIT Model SRK20ZD-S OUTDOOR UNIT Model SRC20ZD-S REMOTE

More information

SERVICE MANUAL MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 INDOOR UNIT. No. OBH529. Models

SERVICE MANUAL MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 INDOOR UNIT. No. OBH529. Models SPLIT-TYPE AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL. OBH529 Models MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 service manual MU-GA VB Series (OB386) MUH-GA VB Series

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL October 202 No. OCH446 REVISED EDITION-E HFC utilized R40A [Model name] PUMY-P00VHMB PUMY-P25VHMB PUMY-P40VHMB PUMY-P00VHMB-BS

More information

SERVICE MANUAL MSC-GA20VB - (WH) MSC-GA25VB - (WH) MSC-GA35VB - (WH) Wireless type Models

SERVICE MANUAL MSC-GA20VB - (WH) MSC-GA25VB - (WH) MSC-GA35VB - (WH) Wireless type Models SPLIT-TYPE, AIR CONDITIONERS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MSC-GA0VB - (WH) E MSC-GAVB - (WH) E MSC-GAVB - (WH). OB8 Indication of model name MSC-GA0VB -

More information

FLOOR CONSOLE / UNDER CEILING DUAL type

FLOOR CONSOLE / UNDER CEILING DUAL type SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL type Models Indoor unit ABU8RULX ABURULX Outdoor unit AOU8RLX AOURLX CONTENTS SPECIFICATIONS... OUTLINE AND DIMENSIONS... REFRIGERANT

More information

FLOOR CONSOLE / UNDER CEILING DUAL type (60Hz)

FLOOR CONSOLE / UNDER CEILING DUAL type (60Hz) SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL type (60Hz) Models Indoor unit MSYF Outdoor unit MRUYF CONTENTS SPECIFICATIONS... OUTLINE AND DIMENSIONS... REFRIGERANT SYSTEM DIAGRAM...

More information

PKA-RP60FAL PKA-RP71FAL PKA-RP100FAL PKH-P60FALH PKH-P71FALH PKH-P100FALH

PKA-RP60FAL PKA-RP71FAL PKA-RP100FAL PKH-P60FALH PKH-P71FALH PKH-P100FALH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS May 005 No.OC33 SERVICE MANUAL Indoor unit [Model names] PKA-RP60FAL PKA-RP7FAL PKA-RP00FAL [Service Ref.] PKA-RP60FAL PKA-RP7FAL PKA-RP00FAL

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASY9USCCW ASY9USCCW ASY12USCCW Outdoor unit AOY9USCC AOY9UFCC AOY12USCC CONTENTS SPECIFICATIONS................................... 1

More information

SERVICE MANUAL MLZ-KA25VA - MLZ-KA35VA - MLZ-KA50VA - E1 INDOOR UNIT. No. OBH483. Ceiling cassette type Models

SERVICE MANUAL MLZ-KA25VA - MLZ-KA35VA - MLZ-KA50VA - E1 INDOOR UNIT. No. OBH483. Ceiling cassette type Models CEILING CASSETTE TYPE, HEAT PUMP AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL. OBH483 Ceiling cassette type Models E1 MLZ-KA25VA - E1 MLZ-KA35VA - MLZ-KA50VA - E1 Outdoor unit service manual MXZ-A VA Series

More information

CASSETTE type INVERTER MULTI AIR CONDITIONER

CASSETTE type INVERTER MULTI AIR CONDITIONER INVERTER MULTI AIR CONDITIONER CASSETTE type Models Indoor unit AUY12LBAB AUY14LBAB Outdoor unit AOY18LMAK2 CONTENTS SPECIFICATIONS..................... 1 OUTLINE AND DIMENSIONS........... 2 REFRIGERANT

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 12 TECHNICAL & SERVICE MANUAL Series SEZ Model name SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KDVA(L) SEZ-KDVA(L) SEZ-KD71VA(L) INDOOR UNIT ON/OFF TEMP TEMP.

More information

AA PLA-RP AA2 PEAD-RP EA PEAD-RP EA2 PEAD-RP GA PKA-RP GAL PKA-RP FAL PCA-RP GA PCA-RP HA PSA-RP GA

AA PLA-RP AA2 PEAD-RP EA PEAD-RP EA2 PEAD-RP GA PKA-RP GAL PKA-RP FAL PCA-RP GA PCA-RP HA PSA-RP GA SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL DATA BOOK [Model names] [Model names] PLA-RP AA PLA-RP AA PEAD-RP EA PEAD-RP EA PEAD-RP GA PKA-RP GAL PKA-RP FAL PCA-RP GA PCA-RP

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 2010 SERVICE MANUAL PEA-RP200GAQ PEA-RP250GAQ PEA-RP400GAQ PEA-RP500GAQ. [Model names] CONTENTS

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 2010 SERVICE MANUAL PEA-RP200GAQ PEA-RP250GAQ PEA-RP400GAQ PEA-RP500GAQ. [Model names] CONTENTS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 00 SERVICE MANUAL [Model names] PEA-RP00GAQ PEA-RP50GAQ PEA-RP400GAQ PEA-RP500GAQ This manual describes only service data of the indoor units. CONTENTS Indoor unit.

More information

Room Air Conditioner Service and Parts Manual

Room Air Conditioner Service and Parts Manual Cool Dry Temp Mode Room Air Conditioner Service and Parts Manual F Fan Speed hr Timer 0n 0ff Money Saver Fan Only Auto Swing Power CP06 CP08 93011401_01 CONTENTS 1. PREFACE 1.1 SAFETY PRECAUTIONS...2 1.2

More information

CEILING type (60Hz) SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models

CEILING type (60Hz) SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models SPLIT TYPE ROOM AIR CONDITIONER CEILING type (60Hz) Models Indoor unit ABU6RSLX Outdoor unit AOU6RLX CONTENTS SPECIFICATIONS....................... OUTLINE AND DIMENSIONS............. REFRIGERANT SYSTEM

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF97R5IAA CAF98MR5IAA CAF127R5IAA CAF128MR5IAA CAF187R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. CAF97R5IAA CAF127R5IAA CAF187R5IAA CAF98MR5IAA CAF128MR5IAA

More information

RC-54CA RO-50CA RC-54HA RO-50HA. SPLIT TYPE AIR CONDITIONER CASSETTE TYPE (50Hz) Indoor unit Outdoor unit

RC-54CA RO-50CA RC-54HA RO-50HA. SPLIT TYPE AIR CONDITIONER CASSETTE TYPE (50Hz) Indoor unit Outdoor unit SPLIT TYPE AIR CONDITIONER CASSETTE TYPE (50Hz) Indoor unit Outdoor unit RCW-54CB RO-50CA RC-54CA RO-50CA RC-54HA RO-50HA CONTENTS SPECIFICATIONS OUTLINE AND DIMENTIONS CIRCUIT DIAGRAM REFRIGERANT SYSTEM

More information

SERVICE TECHNICAL GUIDE

SERVICE TECHNICAL GUIDE SPLIT-TYPE, HEAT PUMP AIR CDITIERS SERVICE TECHNICAL GUIDE [Model names] PLA-RP AA PKA-RP GAL PKA-RP FAL PCA-RP GA PEA-RP EA PEAD-RP EA PEAD-RP GA [Model names] PUHZ-RP VHA

More information

SERVICE MANUAL. Wireless type Models MS-GA50VB - MS-GA60VB - MS-GA80VB - SPLIT-TYPE, AIR CONDITIONERS. No. OB369 CONTENTS

SERVICE MANUAL. Wireless type Models MS-GA50VB - MS-GA60VB - MS-GA80VB - SPLIT-TYPE, AIR CONDITIONERS. No. OB369 CONTENTS SPLIT-TYPE, AIR CONDITIONERS SERVICE MANUAL Wireless type Models MS-GA50VB - MS-GA60VB - MS-GA80VB - E E E (WH) (WH) (WH). OB69 CONTENTS Indication of model name MS-GA50VB - E MS-GA60VB - E MS-GA80VB -

More information

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH502 Wireless type Models MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA Indoor unit service manual MSZ-D NA Series (OBH501) MSY-D

More information

SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz)

SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz) SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz) Indoor unit MS6YF Outdoor unit MR6YF CONTENTS SPECIFICATIONS... OUTLINE AND DIMENSIONS... REFRIGERANT SYSTEM DIAGRAM.... CIRCUIT DIAGRAM... INDOOR PCB

More information

SEZ-KD25VAQ.TH SEZ-KD35VAQ.TH SEZ-KD50VAQ.TH SEZ-KD60VAQ.TH SEZ-KD71VAQ.TH

SEZ-KD25VAQ.TH SEZ-KD35VAQ.TH SEZ-KD50VAQ.TH SEZ-KD60VAQ.TH SEZ-KD71VAQ.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL December No.HWE0 REVISED EDITION-B Indoor unit [Model names] SEZ-KD25VAQ SEZ-KD35VAQ SEZ-KDVAQ SEZ-KDVAQ SEZ-KD71VAQ [Service Ref.] SEZ-KD25VAQ.TH

More information

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A Revision E: Capacity corrections have been corrected [7-1. 2), 3)]. OBH502 REVISED EDITION-D is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH502 REVISED EDITION-E Models MUZ-D30NA / - 1 / -

More information

CASSETTE type SPLIT TYPE AIR CONDITIONER. (60Hz) AUU18RCLX AUU24RCLX AUU36RCLX AUU42RCLX AOU18RLX AOU24RLX AOU36RLX AOU42RLX CONTENTS.

CASSETTE type SPLIT TYPE AIR CONDITIONER. (60Hz) AUU18RCLX AUU24RCLX AUU36RCLX AUU42RCLX AOU18RLX AOU24RLX AOU36RLX AOU42RLX CONTENTS. SPLIT TYPE AIR CONDITIONER CASSETTE type (60Hz) Models Indoor unit AUU8RCLX AUURCLX AUU6RCLX AUURCLX Outdoor unit AOU8RLX AOURLX AOU6RLX AOURLX CONTENTS SPECIFICATIONS... DIMENSIONS... REFRIGERANT SYSTEM

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information

Installation Instructions

Installation Instructions 0908HN50 Lossnay Energy Recovery Ventilator Model: LGH-50RSDC-E (0-0V 50Hz) Installation Instructions (For use by dealer/contractor) Contents Safety precautions... Outline drawings... Standard installation

More information

TECHNICAL & SERVICE MANUAL. Ceiling Cassettes

TECHNICAL & SERVICE MANUAL. Ceiling Cassettes RESET RESET SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS TECHNICAL & SERVICE MANUAL Series SLH/SL Indoor unit [Model names] SLH-AR SLH-.6AR SLH-AR SL-AR SL-.6AR SL-AR Ceiling Cassettes

More information

SERVICE MANUAL MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA - U1 MSZ-GL18NA - U1 MSZ-GL24NA - U1

SERVICE MANUAL MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA - U1 MSZ-GL18NA - U1 MSZ-GL24NA - U1 Revision B: 3. SPECIFICATION has been corrected. Please void OBH732 REVISED EDITION-A. INDOOR UNIT SERVICE MANUAL. OBH732 REVISED EDITION-B Models MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA OUTDOOR AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA DR_AS049EF_02 2017.10.11 Notices: Product

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CDITIERS 004 TECHNICAL & SERVICE MANUAL R40A Outdoor unit [model names] PUHZ-RP.6VHA PUHZ-RPVHA PUHZ-RP.5VHA PUHZ-RP3VHA PUHZ-RP4VHA PUHZ-RP5VHA PUHZ-RP6VHA [Service Ref.] PUHZ-RP.6VHA

More information

SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE

SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE Indoor unit ABYF8LAT ABYF8LAT ABYF8LAT ABYF8LAT ABYF8LBT ABYF8LBT ABYFLAT ABYFLAT ABYFLAT ABYFLAT ABYFLBT ABYFLBT Outdoor unit AOYA8LACL

More information

Room Air Conditioner CP06 & CP08. Chill 115 Volts. Service & Parts Manual THE EXPERTS IN ROOM AIR CONDITIONING _02

Room Air Conditioner CP06 & CP08. Chill 115 Volts. Service & Parts Manual THE EXPERTS IN ROOM AIR CONDITIONING _02 Room Air Conditioner Service & Parts Manual 2014-2015 CP06 & CP08 Chill 115 Volts THE EXPERTS IN ROOM AIR CONDITIONING 93011401_02 CONTENTS 1. PREFACE 1.1 SAFETY PRECAUTIONS...2 1.2 INSULATION RESISTANCE

More information

DUCT type. Большая библиотека технической документации каталоги, инструкции, сервисные мануалы, схемы.

DUCT type. Большая библиотека технической документации   каталоги, инструкции, сервисные мануалы, схемы. SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type Models Indoor unit Outdoor unit RD-25CA RD-25HA RD-30CA RD-30HA RO-25CA RO-25HA RO-30CA RO-30HA C O N T E N T S SPECIFICATIONS.............................................

More information

GUG-01SL-E GUG-02SL-E GUG-03SL-E

GUG-01SL-E GUG-02SL-E GUG-03SL-E 1604876HE5501 DIRECT EXPANSION COIL UNIT FOR LOSSNAY MODELS: GUG-01SL-E GUG-02SL-E GUG-03SL-E Installation Instructions DIRECT EXPANSION COIL UNIT FOR LOSSNAY MODELS: GUG-01SL-E GUG-02SL-E GUG-03SL-E Installation

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE9NB4U & CZ-18BT1U CS-MKE12NB4U & CZ-18BT1U CS-KE18NB4UW & CZ-18BT1U DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 9,000BTU / h 11,900BTU / h 17,500BTU

More information

WALL MOUNTED TYPE ROOM AIR-CONDITIONER

WALL MOUNTED TYPE ROOM AIR-CONDITIONER TECHNICAL MANUAL & PARTS LIST DRAFT WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) SRK50HE-S, SRK56HE-S (Split system, air cooled cooling only type) SRK50CE-S, SRK56CE-S

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE,HEAT PUMP AIR CDITIERS 1997 No. OC135 TECHNICAL & SERVICE MANUAL Series PCH Ceiling Suspended Indoor unit [Models names] [Service Ref.] PCH-2GKHA PCH-2.5GKHA PCH-3GKHA PCH-4GKHSA PCH-5GKHSA

More information

KSGD-01W/S SEMI CONDUCTOR STAND ALONE REFRIGERANT LEAK DETECTOR. Instructions for :- KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector

KSGD-01W/S SEMI CONDUCTOR STAND ALONE REFRIGERANT LEAK DETECTOR. Instructions for :- KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector Issue 1 KSGD-01W/S SEMI CONDUCTOR STAND ALONE REFRIGERANT LEAK DETECTOR Installation Manual Instructions for :- For safe and correct use please read the installation manuals supplied with the equipment.

More information

PKA-RP60KAL.TH PKA-RP71KAL.TH PKA-RP100KAL.TH

PKA-RP60KAL.TH PKA-RP71KAL.TH PKA-RP100KAL.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS SERVICE MANUAL May 2011 No. OCH452 REVISED EDITION-A Indoor unit [Model names] PKA-RP60KAL PKA-RP71KAL PKA-RP100KAL [Service Ref.] PKA-RP60KAL.TH

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A TECHNICAL & SERVICE MANUAL SA 183A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. SA-183A 1 851 006 96 Destination Australia SA 183A REFERENCE NO. SM700514 IMPORTANT! Please Read Before

More information

SERVICE MANUAL MSC-A07YV - (WH) MSC-A09YV - (WH) MSC-A12YV - (WH) HFC. Wireless type Models

SERVICE MANUAL MSC-A07YV - (WH) MSC-A09YV - (WH) MSC-A12YV - (WH) HFC. Wireless type Models SPLIT-TYPE, AIR CONDITIONERS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MSC-A07YV - (WH) E MSC-A09YV - (WH) E MSC-AYV - (WH) HFC utilized R40A. OB39 CONTENTS Indication

More information

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467. SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-HC35VA- E2 and MUZ-HC35VAB- E2 have been added. Please void OBH467 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH467 REVISED EDITION-B

More information

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 Indoor unit service manual MSZ-DM VA Series (OBH750) CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE OUTDOOR AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE DR_AS037EF_01 2016.12.05 Notices: Product

More information

MUH-24RV - MSH-30RV -

MUH-24RV - MSH-30RV - SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models Refer to the Service Manual OB85 REVISED EDITION C when MSH-8RV- E is connected with MXZ-NV- E or MXZ-NV- E as multi system units.

More information

SERVICE MANUAL R410A PUHZ-SP100VHA.UK PUHZ-SP125VHA.UK PUHZ-SP125VHA PUHZ-SP140VHA.UK PUHZ-SP140VHA PUHZ-SP100YHA.UK PUHZ-SP100YHA PUHZ-SP125YHA.

SERVICE MANUAL R410A PUHZ-SP100VHA.UK PUHZ-SP125VHA.UK PUHZ-SP125VHA PUHZ-SP140VHA.UK PUHZ-SP140VHA PUHZ-SP100YHA.UK PUHZ-SP100YHA PUHZ-SP125YHA. SPLIT-TYPE, HEAT PUMP AIR CDITIERS SERVICE MANUAL R40A January 05 No. OCH566 REVISED EDITI-A Outdoor unit [Model Name] PUHZ-SP00VHA PUHZ-SP5VHA PUHZ-SP40VHA PUHZ-SP00YHA PUHZ-SP5YHA PUHZ-SP40YHA [Service

More information

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit SPLIT TYPE AIR CONDITIONER CASSETTE type (50Hz) Models Indoor unit Outdoor unit RCW-12HA RO-12HB C O N T E N T S SPECIFICATIONS........................................ 1 OUTLINE AND DIMENSIONS..............................

More information

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 MSZ-GE60VA - E1 MSZ-GE71VA - E1 INDOOR UNIT. No.

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 MSZ-GE60VA - E1 MSZ-GE71VA - E1 INDOOR UNIT. No. SPLIT-TYPE AIR CONDITIONERS Revision E: Detail of the indoor fan speed control in COOL or DRY operation has been added (9-1.3, 9-2.3). Please void OBH515 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL.

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CITIERS TECHNICAL & SERVICE MANUAL January 00 No. OC REVISE EITI-A Indoor unit [Model names] PCH-AK PCH-.AK PCH-AK PCH-AK PCH-AK PCH-AK PCH-AKH PCH-.AKH PCH-AKH PCH-AKH PCH-AKH

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC Revision E: MUZ-FH25VE- E4, ER4, ET3, MUZ- FH35VE- E3, ER3, ET3 and MUZ- FH50VE- E2, ER2, ET2 have been added. Please void OBH624 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624

More information

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1 OUTDOOR UNIT. No. OB381. Models HFC

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1 OUTDOOR UNIT. No. OB381. Models HFC FLOOR AND CEILIN TYPE AIR CONDITIONERS Revision B: The fan guard for MUCFH-A 60VBhas been changed. Please void OB8 REVSED EDITION-A. E OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A. OB8 REVISED EDITION-B

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL For Extra Cold Climate Area INDOOR ASU18RLF ASU24RLF OUTDOOR AOU18RLXFWH AOU24RLXFWH DR_AS014EF_04 2017.03.10 Notices: Product specifications

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338 TECHNICAL & SERVICE MANUAL SA 128S5 FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-128S5-A 1 851 004 09 General (50Hz) & Europe SA 128S5 REFERENCE NO. SM700338 IMPORTANT!

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629.

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-A Models MUZ-SF25VE - E1 MUZ-SF42VE

More information

PEFY-P40VMH-E,PEFY-P50VMH-E PEFY-P63VMH-E,PEFY-P71VMH-E PEFY-P80VMH-E,PEFY-P100VMH-E PEFY-P125VMH-E,PEFY-P140VMH-E PEFY-P200VMH-E,PEFY-P250VMH-E

PEFY-P40VMH-E,PEFY-P50VMH-E PEFY-P63VMH-E,PEFY-P71VMH-E PEFY-P80VMH-E,PEFY-P100VMH-E PEFY-P125VMH-E,PEFY-P140VMH-E PEFY-P200VMH-E,PEFY-P250VMH-E Air-Conditioners For Building Application 004 TECHNICAL & SERVICE MANUAL Series PEFY Ceiling Concealed Models PEFY-P40VMH-E,PEFY-P50VMH-E PEFY-P6VMH-E,PEFY-P7VMH-E PEFY-P80VMH-E,PEFY-P00VMH-E

More information

SERVICE MANUAL MUH-GA50VB- MUH-GA50VB - MUH-GA60VB - MUH-GA80VB - E1 OUTDOOR UNIT. No. OB368 REVISED EDITION-B. Wireless type Models HFC.

SERVICE MANUAL MUH-GA50VB- MUH-GA50VB - MUH-GA60VB - MUH-GA80VB - E1 OUTDOOR UNIT. No. OB368 REVISED EDITION-B. Wireless type Models HFC. Revision:B - E has been added. SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Please void OB68 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A. OB68 REVISED EDITION-B Wireless type Models E -

More information

Service Manual & Installation Manual

Service Manual & Installation Manual GE Consumer & Industrial Appliances Service Manual & Installation Manual Split System Air Conditioner Model numbers: GE AIR F24 GE AIR F34 GE AIR F41 1 2 3 Introduction and Features Model Remarks GE AIR

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT:. TRIAL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. 38.7107.102. 0.8180.611.02 09/2012 IMPORTANT! Please read before installation This air conditioning

More information

SERVICE MANUAL MUZ-GB50VA - MUZ-GB50VA - E2 OUTDOOR UNIT. No. OB455 REVISED EDITION-D. Wireless type Models HFC

SERVICE MANUAL MUZ-GB50VA - MUZ-GB50VA - E2 OUTDOOR UNIT. No. OB455 REVISED EDITION-D. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Revision D: RoHS PARTS LIST has been changed. Please void OB455 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A. OB455 REVISED EDITION-D Wireless

More information

SERVICE MANUAL MUH-A18WV - MUH-A24WV - MUH-A30WV - E1. Wireless type Models HFC

SERVICE MANUAL MUH-A18WV - MUH-A24WV - MUH-A30WV - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Revision A: Resistance of LEV (Expansion valve) has been modified. Power input and others have been added to SPECIFICATION. Method of check of R.V. coil has been

More information

SERVICE MANUAL PUHZ-ZRP250YKA3.UK R410A. No. OCH680. November 2017 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. Outdoor unit [Model Name]

SERVICE MANUAL PUHZ-ZRP250YKA3.UK R410A. No. OCH680. November 2017 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. Outdoor unit [Model Name] SPLIT-TYPE, HEAT PUMP AIR CDITIERS SERVICE MANUAL R40A November 07 No. Outdoor unit [Model Name] PUHZ-ZRP00YKA3 PUHZ-ZRP50YKA3 [Service Ref.] PUHZ-ZRP00YKA3.UK PUHZ-ZRP50YKA3.UK Note: This manual describes

More information

PUHY-P-Y(S)JM-A PFAV-P-VM-E(-F)

PUHY-P-Y(S)JM-A PFAV-P-VM-E(-F) AIR CONDITIONING SYSTEMS MODEL PUHY-P-Y(S)JM-A PFAV-P-VM-E(-F) DATA BOOK Contents!. General Cautions. Indoor Unit Line-up. Temperature range. Notes on selecting equipments () Notes on using the Fresh

More information

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2 Revision F: "How to check miswiring and serial signal error" has been corrected (11-5. M ). OBH648 REVISED EDITION-E is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH648 REVISED EDITION-F Models

More information

Installation & Maintenance Manual

Installation & Maintenance Manual Installation & Maintenance Manual INVERTER-DRIVEN MULTI-SPLIT SYSTEM HEAT PUMP AIR CDITIERS - SET-FREE SERIES - Type In-the-Ceiling (Duct) Model RPI-3.0FSN2SQ RPI-4.0FSN2SQ RPI-5.0FSN2SQ RPI-6.0FSN2SQ

More information

SERVICE Manual FREE JOINT MULTI AIR CONDITIONER

SERVICE Manual FREE JOINT MULTI AIR CONDITIONER FREE JOINT MULTI AIR CONDITIONER INDOOR UNIT MH020FPEA MH023FPEA MH026FPEA MH035FPEA MH052FPEA MH8VP2-09 MH9VP2-07 MH9VP2-2 MH026FKEA MH035FKEA MH052FDEA OUTDOOR UNIT MH8VP2X MH9VP2X MH052FXEA2 MH068FXEA4

More information

Part 3 Troubleshooting

Part 3 Troubleshooting Part Troubleshooting What is in this part? This part contains the following chapters: Chapter See page Troubleshooting 2 Error Codes: Hydro-box 7 Error Codes: Outdoor Units Error Codes: System Malfunctions

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 19,100 BTU/h,200 BTU/h 30,600 BTU/h Outdoor Model No. CU-3KE19NBU CU-4KE24NBU

More information

PKA-RP35HAL PKA-RP50HAL

PKA-RP35HAL PKA-RP50HAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS March 2009 No. OCH453 SERVICE MANUAL Indoor unit [Model names] PKA-RP35HAL PKA-RP50HAL [Service Ref.] PKA-RP35HAL PKA-RP50HAL NOTE: This

More information

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E SPLIT-TYPE AIR CONDITIONERS Revision E: MFZ-KA5VA- E5, MFZ-KA35VA- E5 and MFZ-KA50VA- E5 have been added. Please void OB409 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OB409 REVISED EDITION-E Models

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E Revision E: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH629 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-E Models

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513 TECHNICAL & SERVICE MANUAL SA 123A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-123A 1 851 006 95 Australia SA 123A REFERENCE NO. SM700513 IMPORTANT! Please Read Before

More information

SERVICE MANUAL. R410A Outdoor unit [model names] SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS April 2007

SERVICE MANUAL. R410A Outdoor unit [model names] SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS April 2007 SPLIT-TYPE, HEAT PUMP AIR CDITIERS SPLIT-TYPE, AIR CDITIERS April 007 No.OC379 REVISED EDITI-C SERVICE MANUAL R0A Outdoor unit [model names] PU-P7VHA PU-P7YHA PU-P00VHA PU-P00YHA PU-P5YHA PU-P0YHA PUH-P7VHA

More information

SERVICE MANUAL R410A. June 2014 AIR TO WATER HEAT PUMP. No. OCH562. Outdoor unit [Model Name] [Service Ref.] PUHZ-W112VHA PUHZ-W112VHA-BS CONTENTS

SERVICE MANUAL R410A. June 2014 AIR TO WATER HEAT PUMP. No. OCH562. Outdoor unit [Model Name] [Service Ref.] PUHZ-W112VHA PUHZ-W112VHA-BS CONTENTS AIR TO WATER HEAT PUMP June 204 No. SERVICE MANUAL R40A Outdoor unit [Model Name] PUHZ-W2VHA Salt proof model PUHZ-W2VHA-BS [Service Ref.] PUHZ-W2VHA PUHZ-W2VHA-BS Note: This manual describes service data

More information