Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA)

Size: px
Start display at page:

Download "Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA)"

Transcription

1 Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA) M E M O R A N D U M DATE: October 3, 2017 TO: Principal and Alternate Members of the Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA) FROM: Chelsea Rubadou, Staff Liaison SUBJECT: AGENDA PACKAGE NFPA 750 Second Draft Meeting (A2018) Enclosed is the agenda for the NFPA 750 Second Draft meeting of the Technical Committee on Water Mist Fire Suppression Systems, which will be held on Monday, October 16 th through Tuesday, October 17 th, 2017 in Charleston, SC. Please review the attached Committee Inputs for NFPA 750 and Public Inputs for NFPA 25 in advance, and if you have suggestions, please come prepared with proposed language and respective technical substantiation. In particular, several of the Public Inputs that were submitted to NFPA 25 change ITM frequency. The technical substantiation for any revision to those requirements in NFPA 25 will be critical to support the Committee s action and allow the public to be fully aware of the basis of the decision. If you have any questions prior to the meeting, please do not hesitate to contact me at: Office: (617) crubadou@nfpa.org For administrative questions, please contact Yiu Lee at (617)

2 Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA) NFPA 750 Second Draft Meeting (Annual 2018) Monday, October 16 to Tuesday, October 17, 2017 Courtyard Charleston Historic District 125 Calhoun Street Charleston, SC Call to Order 8:00 am ET (10/16) 2. Introductions and Attendance 3. Chairman Comments 4. Approval of Previous Meeting Minutes AGENDA Monday, October 16, 2017 a) First Draft Meeting, Memphis, TN on Oct 25-26, 2016 b) Task Group Report out to WAM-AAA on May 3, 2017 c) Task Group Report out to WAM-AAA on June 19, Staff Liaison Presentation on NFPA Revision Process and A2018 Cycle 6. Task Group Reports a) Task Group on Annex D (will address while reviewing Committee Inputs) Purpose: Larry Fisher to review the applicability of the updated reference in Annex E to Section D.1.2. Since D.1.2 mentions Parts 2, 3, 4, and 5 we need to make sure that the new Annex reference covers the same material. b) Task Group on NFPA 20 Purpose: Task Group 6 to review current water mist language in NFPA 20 and develop any necessary public comments for submittal by this committee. Members: Robert Stubblefield - Chair, Jerry Back, Brad Stillwell, Zach Magnone, and Tom Reser. c) Task Group on NFPA 25 Purpose: Task Group 5 to review current water mist language in NFPA 25 and develop any necessary public inputs for submittal by this committee. Members: Eric Houin - Chair, Dan Hubert, Brad Stillwell, Sean Cutting, Kerry Bell,

3 Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA) NFPA 750 Second Draft Meeting (Annual 2018) Monday, October 16 to Tuesday, October 17, 2017 Courtyard Charleston Historic District 125 Calhoun Street Charleston, SC and Jeff Hebenstreit. 7. Preparation of the Second Draft a) Review Committee Inputs (quantity = 5) i. See supplementary material attached for CI-46. Review Water Mist Guidelines draft. ii. See supplementary material attached for CI-47. Review work completed by Larry Fisher (Task Group on Annex D). b) Create Second Revisions 8. New Business a) Review the response from the NFPA 25 Technical Committee on the 6 Public Inputs that WAM-AAA submitted, and create Public Comments for NFPA 25. See attached PI s 193, 200, 201, 202, 203, and 204 for NFPA Adjournment Please submit requests for additional agenda items to the chair and staff liaison at least seven days prior to the meeting.

4 Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA) NFPA 750 Second Draft Meeting (Annual 2018) Monday, October 16 to Tuesday, October 17, 2017 Courtyard Charleston Historic District 125 Calhoun Street Charleston, SC Key Dates for the Annual 2018 Revision Cycle Public Input Closing Date June 29, 2016 Final Date for First Draft Meeting December 7, 2016 Posting of Ballot by January 25, 2017 First Draft Ballot Due Date February 15, 2017 Posting of First Draft Report for Public Comment March 1, 2017 Public Comment Closing Date May 10, 2017 Final Date for Second Draft Meeting November 8, 2017 Posting of Ballot by December 20, 2017 Ballots due by January 10, 2018 Posting of Second Draft Report for NITMAM Review January 24, 2018 Closing Date for Notice of Intent to Make a Motion (NITMAM) February 21, 2018 Issuance of Consent Document (No NITMAMs) April 29, 2018 NFPA Annual Meeting June 14, 2018 Issuance of Document with NITMAM August 14, 2018 Technical Committee deadlines are in bold.

5 MINUTES NFPA Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA) October 25-26, 2016 First Draft Meeting Springhill Suites Memphis Downtown, 85 West Court Avenue, Memphis, Tennessee Date: October 25, Call to Order. Meeting was called to order by Chair Bob Kasiski at 8:05 AM. 2. Building Safety Message. Building safety was discussed and exits identified by Chair Bob Kasiski. 3. Self-Introductions of Members and Guests. Attendance was taken. Committee members then guests introduced themselves. Those who were present at the meeting or via Adobe connect are listed below:

6 MINUTES NFPA Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA) October 25-26, 2016 First Draft Meeting Springhill Suites Memphis Downtown, 85 West Court Avenue, Memphis, Tennessee 4. Chairman Comments. Bob Kasiski, FM Global, Chair of Committee, stated that he would temporarily step down as Chair for actions associated with Public Items 67, 68, 69, 70, 72, 73, and 74. During that period of committee action, Robert Stubblefield, AREVA Inc., Principal Committee Member, will act as Chair to ensure impartiality. 5. Approval of Previous Meeting Minutes. Meeting minutes recorded for the previous Committee meeting held January 29-31, 2013 in Palm Beach Gardens, Florida were approved by committee vote. 6. Committee Training: Overview of NFPA Revision Process and the A2018 Cycle. Overview training for committee provided by Chelsea Tuttle, Staff Liaison. 7. Committee Action on Public Inputs and the Preparation of First Draft. 8. Committee Forms Task Group 1: Purpose: Task Group 1 to develop revised language for excess pressure and to develop technical justification relating to PI 75. Members: Joe Barter - Chair, Dan Hubert, Eric Houin, Brad Stillwell, and Zach Magnone. 9. Task Group 1 Report: Task Group 1 reported on work with recommendations to resolve PI 75 with identified justification for committee action (see CI 2). Task group will continue to develop language for Second Draft Meeting. 10. Chair Temporarily Steps Down: At 10:50 am, Bob Kasiski temporarily steps down as Chair for Committee Action on PI 67, 68, 69, 70, 72, 73, and 74. Robert Stubblefield, Principal Member, assumes Chair temporarily for action on the items above.

7 MINUTES NFPA Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA) October 25-26, 2016 First Draft Meeting Springhill Suites Memphis Downtown, 85 West Court Avenue, Memphis, Tennessee 11. Committee Forms Task Group 2: Purpose: Task Group 2 to develop proposed partial reorganization of Chapter 7 to accommodate changes with respect to PI 68. Members: Bob Kasiski - Chair, Dan Hubert, Eric Houin, and Zach Magnone. 12. Interim Chair Rescinded: At 12:20 pm, Interim Chair, Robert Stubblefield restores Bob Kasiski as Chair of the Committee. 13. Break for Lunch: 12:30 to 1:30 PM 14. Committee Action on Public Inputs and the Preparation of First Draft, cont. 15. Task Group 2 Report: Task Group 2 reported on work with recommendations to create First Revisions to support action on PI 68 and to resolve PI 68 with identified justification for committee action. 16. Committee Forms Task Group 3: Purpose: Task Group 3 to develop proposed language to address changes with respect to PI 78. Members: Joe Barter - Chair, Jason Jones, Ruediger Kopp, Jeff Hebenstreit, Larry Fisher, and Robert Upson. 17. Task Group 3 Report: Task Group 3 reported on work with recommendations to support action on PI Committee Forms Task Group 4: Purpose: Task Group 4 to develop proposed updates to address changes and revisions to referenced documents throughout NFPA 750 with respect to PI 2. Members: Brad Stillwell - Chair, Jason Jones, Paul Felch, Ruediger Kopp, Jeff Hebenstreit, Robert Upson, Jon Carpenter, and Larry Fisher. 19. Adjournment of Tuesday Meeting: The meeting was adjourned at 5:30 PM. Date: October 26, Call to Order. Meeting was called to order by Chair Bob Kasiski at 8:10 AM. 2. Committee Action on Public Inputs and the Preparation of First Draft, cont.

8 MINUTES NFPA Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA) October 25-26, 2016 First Draft Meeting Springhill Suites Memphis Downtown, 85 West Court Avenue, Memphis, Tennessee 3. Task Group 4 Report: Task Group 4 compiled a list of updated references relative to the proposed changes in PI 2 for committee action. 4. New Business: Committee action on new business relative to the development of the First Draft and NFPA 20 Technical Committees with respect relevant water mist criteria and pending changes in both documents that may impact NFPA Break for Lunch: 12:30 to 1:30 PM 6. Committee Action on New Business, cont. 7. Committee Forms Task Group 5: Purpose: Task Group 5 to review current water mist language in NFPA 25 and develop any necessary public inputs for submittal by this committee. Members: Eric Houin - Chair, Dan Hubert, Brad Stillwell, Sean Cutting, Kerry Bell, Jeff Hebenstreit, and Lance Harry. 8. Committee Forms Task Group 6: Purpose: Task Group 6 to review current water mist language in NFPA 20 and develop any necessary public comments for submittal by this committee. Members: Robert Stubblefield - Chair, Jerry Back, Brad Stillwell, Zach Magnone, and Tom Reser. 9. Adjournment of Meeting: The meeting was adjourned at 2:52 PM.

9 NFPA 750 Teleconference Meeting; Report from Task Grp on NFPA 20 on Public Comment Submission A teleconference meeting was held on Wednesday, 3-May, 2017 convening at 2:00 pm to discuss the findings of the Task Group established to determine if Public Comments need to be submitted to the NFPA 20 (Standard for the Installation of Stationary Pumps for Fire Protection) Technical Committee. The basis of the Public Comments would be for revisions to NFPA 20 that relate to fire pumps used in water mist system. The following individuals were present on teleconference call: Technical Committee Members Bob Kasiski Chair Paul Anastasia Principal Bob Stubblefield Principal Gerry Back Principal Robert Upson Principal Bob Ballard Principal Kerry Bell Voting Alternate Larry Fisher Principal Larry Carmen Alternate Dan Hubert Principal Sean Ramsey Alternate Brad Stilwell Principal Hong-Zeng (Bert) Yu Alternate NFPA Barry Chase Janna Shapiro Guests Tom Reser Derek Wickersham Jason Jones Brian Jones Gene Hill Staff Liaison Staff Liaison Fire Lion Global Fike Fike Fike Fike Barry Chase was acting as Staff Liaison for NFPA in the absence of Chelsea Rubadou, NFPA 750 Staff Liaison Barry Chase confirmed 9 Technical Committee members are eligible to vote should a vote be taken. Bob Kasiski, Chair identified the objective of the meeting was to discuss the findings of the Task Group to determine if Public Comments need to be submitted to the NFPA 20 (Standard for the Installation of Stationary Pumps for Fire Protection) Technical Committee. The Task Group was established at the 1 st Draft Meeting of NFPA 750 held on October 2016 in Memphis, TN. The Task Group is Chaired by Bob Stubblefield. Bob Stubblefield, Task Group Chair provided a verbal report to the Technical Committee members based upon the Task Group meeting that was held on 7-April, 2017 as follows: NFPA 750, Section states that the pump needs to be sized to meet required capacity and pressure. NFPA 750, Section states that the pump needs to be sized to meet 110% of the required capacity and pressure. NFPA 20 and 25 all refer to 150% of the system capacity for pump Inspection, Testing and Maintenance o Chapter 15 of NFPA 750 points to NFPA 25 for Inspection, Testing and Maintenance Page 1 of 2

10 NFPA 750 Teleconference Meeting; Report from Task Grp on NFPA 20 on Public Comment Submission In FR-17, Section (General Requirements) for NFPA 20 The available flow and pressure at the fire pump discharge at the lowest permissible suction pressure shall be a minimum of 100% of rated flow. o Our Technical Committee needs to confirm the correct value of 100 vs 110% before submitting a Public Comment to NFPA 20. The Task Group by itself could not identify which is the correct value. o A Public Comment only needs to submit to NFPA 20 if our Technical Committee agrees that 110% is the correct requirement Thanks to the Task Group which comprised of Gerry Back, Tom Reser and Bob Stubblefield. Bob Kasiski and Chelsea Rubadou also participated in the Task Group meeting. Discussion followed between the various Technical Committee members facilitated by Bob Stubblefield, Gerry Back and Bob Kasiski. The basis of the discussion was determining the basis of the pump capacity in NFPA 750, the impact that pump pressure has to properly form water droplets at the nozzle and the impact this has on both positive displacement pumps used in high pressure water mist system and centrifugal pumps used in low pressure water mist systems. Based upon the discussion a motion was made and seconded; The available flow and pressure at the fire pump discharge shall be adequate to meet 100% of the maximum fire protection demand A roll call ballot was taken with the following results: Aye : 4 votes Nay : 5 votes Motion Failed Further discussion determined it is the intent of NFPA 750 to have two different requirements, one which is to address the capacity of the water supply (110%) and the second is to address the capacity of the pump (100%). In addition, depending upon the type of pump, this needs to take into account the performance curve of the pump. It was mutually agreed upon that further clarification is needed for the Chapter 12 Water Supply requirements to differentiate from the requirements of Chapter 4. Based upon that discernment the Technical Committee came to consensus that a Public Comment to NFPA 20 is not warranted. The proposed 1 st Revisions of NFPA 750 will be reviewed to determine if it will be permissible to add these clarifications in the 2 nd Draft of NFPA 750. Barry Chase reminded the committee of the following dates: o Public Comment closing date for NFPA 20 and NFPA 750: May 10, 2017 o Public Input closing date for NFPA 25: June 28, 2017 The meeting was adjourned at 3:20 pm Page 2 of 2

11 NFPA 750 Task Group Report out to TC on Public Inputs for NFPA 25 June 19, 2017 Attendance: Joseph Barter, Robert Kasiski, Bob Ballard, Milosh Puchovsky, Lari Laakso, Tom Ziegler, Kerry Bell, Michael Koczera, Eric Houin, Dennis Taylor, Larry Fisher, Gerald Back, Larry Carmen, Anthony Cacioppo, Bob Upson, Sean Ramsey, Sean Cutting, Chelsea Rubadou Began at 11:00 AM ET The Technical Committee reviewed the draft document, which included a full rewrite of Chapter 12 of NFPA 25. o The Technical Committee made edits o The Technical Committee voted to submit all 6 Public Inputs Kerry, Bob K., and Eric H. to decide which of them will submit the Public Inputs before the closing date. Kerry will be at the NFPA 25 meeting. Adjourned 11:45 AM ET

12

13

14 Water-Based Fire Protection Systems Standard for the Inspection, Testing, and Maintenance of

15

16 Alternative Arrangements for Halon Fire-Extinguishing Systems in Machinery Spaces and Pump-Rooms Amendments to the Test Method for Equivalent Water-Based Fire-Extinguishing Systems for Machinery Spaces of Category A and Cargo Pump-Rooms Contained in MSC/Circ. 668 Revised Guidelines for Approval of Sprinkler Systems Approval Standard for Water Mist Systems Standard for Water Mist Nozzles for Fire Protection Service Fixed firefighting systems watermist systems design and installation International Code for Application of Fire Test Procedures

17 Application of Safety Instrumentation to the Process Industries

18 Water-Based Fire Protection Systems Standard for the Inspection, Testing, and Maintenance of

19

20 Alternative Arrangements for Halon Fire-Extinguishing Systems in Machinery Spaces and Pump-Rooms Amendments to the Test Method for Equivalent Water-Based Fire-Extinguishing Systems for Machinery Spaces of Category A and Cargo Pump-Rooms Contained in MSC/Circ. 668 Revised Guidelines for Approval of Sprinkler Systems Approval Standard for Water Mist Systems Standard for Water Mist Nozzles for Fire Protection Service Fixed firefighting systems watermist systems design and installation International Code for Application of Fire Test Procedures

21 Application of Safety Instrumentation to the Process Industries

22 M E M O R A N D U M To: NFPA 750 Technical Committee From: L E Fisher, US Coast Guard Date: 1 September 2017 Re: Update of Reference in Annex D ISA Publication Currently, Annex D, Reliability, of NFPA 750, cites International Society of Automation (ISA) S84.01, Application of Safety Instrumentation to the Process Industries, for predictive techniques that may be used to determine the reliability of water mist systems. Accordingly, Annex E listed the reference. However, First Revision No. 36-NFPA is an update to the current edition of the ISA reference, ISA P1, Functional Safety: Safety Instrumented Systems for the Process Industry Sector - Part 1: Framework, Definition, Systems, Hardware and Software Requirements, The question was raised whether the material in Annex D.1.2 still reflects the new ISA reference or does it need to be updated. The standard currently set forth in Annex D is the 1996 edition. In 2004, the ISA, along with the European Committee for Electrotechnical Standardization and ANSI, updated and harmonized the international standards for process safety instrumentation, resulting in the adoption of IEC The US version of this standard is ANSI/ISA , Functional Safety: Safety Instrumented Systems for the Process Industry Sector. This standard includes significant updates and a different organization than the 1996 version, requiring an update to its reference in Annex D. Basically, the computational techniques for determining reliability of systems, namely simple equations, fault tree analysis, Markov analysis and Logic Solvers, that were in Parts 2, 3, 4 and 5 of the 1996 reference are now referenced in Part 3 of the 2004 version. Further, a technical report, ISA- TR , Safety Integrity Level (SIL) Verification of Safety Instrumented Functions, provides guidance on using these techniques to estimate the reliability of systems. Thus, Annex D.1.2 needs to be updated. The following is suggested: D.1.2 Predictive Techniques. Predictive techniques outlined in ISA-S84.01, Application of Safety Instrumentation to the Process Industries ISA-TR , Safety Integrity Level (SIL) Verification of Safety Instrumented Functions, provide guidance to determine the safety integrity level (SIL) of a protection system. The main document establishes SILs needed for various safety systems (SIS). Parts 2, 3 and 4 of ISA-S84.01This technical report provides information on three different methods for determining reliability that can be applied to water mist systems: simplified equations, fault tree analysis, and Markov analysis, and Logic Solvers. Part 5 of ISA-S84.01 determines the probability of failure on demand (PFD) of Logic Solvers via Markov analysis.

23 The average probability of failure of a system at various SILs is shown in Table D.1.2. [Also suggest deleting Table D.1.2, which is of no use unless you are using the reference anyway]. The user of the system should designate the safety level desired based on either dollar loss or personal injury. Where a high level of safety is required, the analysis should be done by an independent third party. For lower safety levels, the manufacturer could do the analysis. The U.S. Navy used reliability studies to evaluate the reliability of halon systems for shipboard use. Approval for service was dependent on a reliability study. The main advantage to the analysis was the identification of single points of failure. Failure rates were determined for the systems designed, but these appeared to be less meaningful than identifying single points of failure. Reliability was improved by eliminating abort valves and installing a manual actuation system to bypass the time delay for the predischarge alarm. Manual activation was acceptable because the protected areas onboard ship are constantly occupied. E ISA Publications. Instrumentation, Systems, and Automation The International Society of Automation, 67 T.W. Alexander Drive, P.O. Box 12277, Research Triangle Park, NC ISA-S84.01, Application of Safety Instrumentation to the Process Industries, 1996 ISA-TR , Safety Integrity Level (SIL) Verification of Safety Instrumented Functions.

24 National Fire Protection Association Report 1 of 13 10/3/2017, 2:26 PM Public Input No. 193-NFPA [ Sections 12.1, 12.2, 12.3 ] Sections 12.1, 12.2, Inspection and Testing Components and Systems All components and systems shall be inspected and tested to verify that they function as intended Water mist systems that are equipped with an additive system shall be tested with the specific additive system engaged or used during the acceptance testing Common Components and Valves. Common components and valves shall be inspected, tested, and maintained in accordance with Chapter Requirements.

25 National Fire Protection Association Report 2 of 13 10/3/2017, 2:26 PM The components of typical water mist systems to be inspected and tested are provided in Table Table Mist Systems Additive storage cylinders Item Task Weekly Monthly Quarterly Inspect general condition, corrosion. Semiannually Annually Other Inspect quantity of additive agent. Test quality of additive agent. Test additive injection, full discharge test. Compressed gas cylinders Inspect support frame and cylinder restraints. Inspect cylinder pressure (unsupervised). Inspect cylinder pressure (supervised). Confirm cylinder control valve is open.

26 National Fire Protection Association Report 3 of 13 10/3/2017, 2:26 PM Inspect cylinder capacity and pressure rating. Inspect cylinder compliance specification. Confirm compressed gas meets specifications (moisture, cylinder pressure). Hydrostatic test cylinders. Control equipment Inspection, testing, and maintenance in accordance with the requirements of NFPA years Enclosure features, interlocks Inspect enclosure integrity. Plant air, compressors, and receivers Inspect air pressure (unsupervised). Inspect air pressure (supervised). Start compressor. Check compressor/receiver capacity, changes. Inspect compressed air moisture content.

27 National Fire Protection Association Report 4 of 13 10/3/2017, 2:26 PM Clean filters, moisture traps. Test full capacity, duration, and any changes in other demands. Pneumatic valves Inspect cylinder valves, master release valves. Inspect all tubing associated with release valves. Test solenoid release of master release valve. Test manual release of master release valve. Test operation of slave valves. Reset all pneumatic cylinder release valves. Test on-off cycling of valves intended to cycle.

28 National Fire Protection Association Report 5 of 13 10/3/2017, 2:26 PM Pumps and drivers Inspection, testing, and maintenance in accordance with the requirements of NFPA 20 and NFPA 25. Standby pump Inspect and empty the moisture trap, oil injection (pneumatic). Inspect compressed gas supply, inlet air pressure. Inspect outlet water (standby) pressure. Test start/stop pressure settings for standby pressure. System control valves Inspection, testing, and maintenance in accordance with the requirements of NFPA 25. Ventilation Test interlocked systems (e.g., ventilation shutdown). Test shutdown of fuel/lubrication systems. Water mist system piping and nozzles Water recirculation tank Inspection, testing, and maintenance in accordance with NFPA 25. Inspect sample of nozzle screens and strainers (see of NFPA 750). Inspect water level (unsupervised). After discharge

29 National Fire Protection Association Report 6 of 13 10/3/2017, 2:26 PM Inspect water level (supervised). Inspect supports, attachments. Test low water level alarm. Inspect water quality, drain, flush, and refill. Test operation of float-operated valve. Test pressure at outlet during discharge. Test backflow prevention device (if present). Inspect and clean filters, strainers, cyclone separator. Water storage cylinder Inspect water level (load cells). (high pressure)

30 National Fire Protection Association Report 7 of 13 10/3/2017, 2:26 PM Inspect water level (unsupervised). Inspect support frame/restraints. Inspect vent plugs at refilling. Inspect cylinder pressure on discharge. Inspect filters on refill connection. Water storage tanks Inspect water level (unsupervised). Inspect water level (supervised). Confirm sight glass valves are open. Inspect tank gauges, pressure.

31 National Fire Protection Association Report 8 of 13 10/3/2017, 2:26 PM Inspect all valves, appurtenances. Drain tank, inspect interior, and refill. Inspect tank condition (corrosion). Inspect water quality. Inspect water temperature. Water supply (general) Inspect source pressure. Extreme weather Inspect source quality (*first year). * Test source pressure, flow, quantity, duration.

32 National Fire Protection Association Report 9 of 13 10/3/2017, 2:26 PM Water mist nozzles shall be inspected from the floor level annually Any water mist nozzle that shows signs of any of the following shall be replaced: (1) Leakage (2) Corrosion (3) Physical damage (4) Loss of fluid in the glass bulb heat responsive element (5)* Loading (6) Painting, unless painted by the water mist nozzle manufacturer Any water mist nozzle that has been installed in the incorrect orientation shall be corrected by repositioning the branch line, drop, or sprig, or shall be replaced Water mist nozzles with glass bulbs shall be replaced if the bulbs are empty of fluid Water mist nozzles installed in concealed spaces such as above suspended ceilings shall not require inspection Water mist nozzles installed in areas that are inaccessible for safety considerations due to process operations shall be inspected during each scheduled shutdown Stock, furnishings, or equipment closer to the water mist nozzle than permitted by the clearance specified in the manufacturer s installation instructions shall be corrected The supply of spare automatic water mist nozzles shall be inspected annually for the correct number and type of water mist nozzles as required by NFPA * Where required by this section, sample automatic water mist nozzles shall be submitted to a recognized testing laboratory acceptable to the authority having jurisdiction for functional testing Automatic water mist nozzles that have been in service for 20 years shall be replaced, or representative samples shall be tested and then retested at 10-year intervals * Where water mist nozzles are subjected to harsh environments, including corrosive atmospheres and corrosive water supplies, they shall be either replaced or representative samples tested on a 5-year basis *

33 National Fire Protection Association Report 10 of 13 10/3/2017, 2:26 PM A representative sample of water mist nozzles for testing per shall consist of a minimum of four water mist nozzles or 1 percent of the number of water mist nozzles per individual water mist nozzle sample, whichever is greater Where one water mist nozzle within a representative sample fails to meet the test requirement, all water mist nozzles within the area represented by that sample shall be replaced Maintenance General Maintenance shall be performed to keep the system equipment operable or to make repairs Where required by the manufacturer, maintenance shall be performed on devices not described in this standard As-built system installation drawings, original acceptance test records, and device manufacturer's maintenance bulletins shall be retained to assist in the proper care of the system and its components Replacement components shall be in accordance with the manufacturer's specifications and the original system design Spare components shall be accessible and shall be stored in a manner to prevent damage or contamination * After each system operation, a representative sample of operated water mist nozzles in the activated zone shall be inspected After each system operation due to fire, the system filters and strainers shall be cleaned or replaced Where applicable to the type of water mist system, scheduled maintenance shall be performed as outlined in Table Table Maintenance Frequencies Item Activity Frequency Water tank Drain and refill Annually System Flushing Annually Strainers and filters Clean or replace as required After system operation Water Mist Nozzles * Replacement water mist nozzles shall have the proper characteristics for the application intended, including the nozzle model and temperature rating.

34 National Fire Protection Association Report 11 of 13 10/3/2017, 2:26 PM Only new water mist nozzles shall be used to replace existing water mist nozzles * A supply of spare water mist nozzles (never fewer than three) shall be maintained on the premises so that any water mist nozzles that have operated or been damaged in any way can be promptly replaced The water mist nozzles shall correspond to the manufacturer(s), models, and temperature ratings of the water mist nozzles in the property The automatic water mist nozzles shall be kept in a cabinet located where the temperature will at no time exceed 100 F (38 C) The stock of spare thermally activated nozzles shall include all types and ratings installed and shall be as follows: (1) For systems having fewer than 50 nozzles, not fewer than 3 nozzles (2) For systems having 50 to 300 nozzles, not fewer than 6 nozzles (3) For systems having 301 to 1000 nozzles, not fewer than 12 nozzles (4) For systems having over 1000 nozzles, not fewer than 24 nozzles * Where required by the manufacturer, a special water mist nozzle wrench shall be provided and kept in the cabinet to be used for the removal and installation of nozzles One water mist nozzle wrench shall be provided for each type of nozzle installed Protective Coverings Water mist nozzles protecting spray areas and mixing rooms in resin application areas installed with protective coverings shall continue to be protected against overspray residue so that they will operate in the event of fire * Water mist nozzles installed as described in shall be protected using cellophane bags having a thickness of in. (0.076 mm) or less or thin paper bags Coverings shall be replaced periodically so that heavy deposits of residue do not accumulate Water mist nozzles shall not be altered in any respect or have any type of ornamentation, paint, or coatings applied after shipment from the manufacturer Automatic water mist nozzles used for protecting commercial-type cooking equipment and ventilating systems shall be replaced annually.

35 National Fire Protection Association Report 12 of 13 10/3/2017, 2:26 PM Where automatic water mist nozzles are used and annual examination shows no buildup of grease or other material on the nozzles, the nozzles shall not be required to be replaced Training All persons who might be expected to inspect, test, maintain, or operate water mist systems shall be trained thoroughly in the functions they are expected to perform Refresher training shall be provided as recommended by the manufacturer or by the authority having jurisdiction. Additional Proposed Changes File Name Description Approved Public_Input_for_NFPA_25_- _Chapter_12_Global.docx Revised Chapter 12 Water Mist Systems pdf Statement of Problem and Substantiation for Public Input IMO Testing Program on automatic sprinkler and water mist systems As Chair of the NFPA 750 Technical Committee, I am submitting a Public Input on behalf of the NFPA 750 Technical Committee. The attached Public Input passed ballot with the 2/3 majority stated in NFPA regulations. The Public Input being submitted for the revision of Chapter 12 is to change the existing Table and requirements to be aligned with the format used in the other chapters of NFPA 25. There are neither changes in frequencies nor current requirements in this Public Input, with the exception of Tasks from the current Tabled and are being converted to text requirements. Text requirements for tasks are based upon existing similar requirements for water spray (Chap 10), foam systems (Chap 11). In addition, the new Table has been updated to include reference to those appropriate Chapters and sections (Chap. 8 and 13) for water mist systems within the NFPA 25 Standard. Additional requirements have added to added to Chapter 12 for the usage of compressed air cylinders with water mist systems not previously addressed by NFPA 25. As noted previously, the frequency in has been changed to address operational matters identified in the field. The basis for this change is Agenda Item 20 from the 94th Session of the Maritime Safety Committee, 12-September, 2014 of the International Maritime Organization (MSC 94/20/2). Please note in our submission due to difficulties working with the TerraView software it may not be apparent, but it is the intention to have the current Table and deleted and replaced with the Table identified in the Public Input submission. Submitter Information Verification Submitter Full Name: Robert Kasiski Organization: FM Global Affilliation: NFPA 750 Technical Committee

36 National Fire Protection Association Report 13 of 13 10/3/2017, 2:26 PM Street Address: City: State: Zip: Submittal Date: Tue Jun 27 16:38:39 EDT 2017 Copyright Assignment I, Robert Kasiski, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Input in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Input and that I have full power and authority to enter into this copyright assignment. By checking this box I affirm that I am Robert Kasiski, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature

37 Chapter 12 Water Mist Systems 12.1 Inspection and Testing. General Minimum Requirements This chapter shall provide the minimum requirements for the routine inspection, testing, and maintenance of water mist systems only Table shall be used to determine the minimum required frequencies for inspection, testing, and maintenance Common Components and Valves. Common components and valves shall be inspected, tested, and maintained in accordance with Chapter Impairments. The procedures outlined in Chapter 15 shall be followed where an impairment to protection occurs Hose Connections. Hose connections shall be inspected, tested, and maintained in accordance with Chapters 6 and Components and Systems All components and systems shall be inspected and tested to verify that they function as intended Water mist systems that are equipped with an additive system shall be tested with the specific additive system engaged or used during the acceptance testing Common Components and Valves. Common components and valves shall be inspected, tested, and maintained in accordance with Chapter Requirements. The components of typical water mist systems to be inspected and tested are provided in Table Table Mist Systems

38 Semi-. Item Task Weekly Monthly Quarterly annually Annually Additive storage cylinders Compressed gas cylinders Control equipment Inspect general condition, corrosion. Inspect quantity of additive agent. Test quality of additive agent. Test additive injection, full discharge test. Inspect support frame and cylinder restraints. Inspect cylinder pressure (unsupervised). Inspect cylinder pressure (supervised). Confirm cylinder control valve is open. Inspect cylinder capacity and pressure rating. Inspect cylinder compliance specification. Confirm compressed gas meets specifications (moisture, cylinder pressure). Hydrostatic test cylinders. Inspection, testing, and maintenance in accordance with the Other 5 12 years

39 Semi-. Item Task Weekly Monthly Quarterly annually Annually Enclosure features, interlocks Plant air, compressors, and receivers Pneumatic valves requirements of NFPA 72. Inspect enclosure integrity. Inspect air pressure (unsupervised). Inspect air pressure (supervised). Start compressor. Check compressor/receiver capacity, changes. Inspect compressed air moisture content. Clean filters, moisture traps. Test full capacity, duration, and any changes in other demands. Inspect cylinder valves, master release valves. Inspect all tubing associated with release valves. Test solenoid release of master release valve. Test manual release of master release valve. Other

40 Semi-. Item Task Weekly Monthly Quarterly annually Annually Pumps and drivers Standby pump System control valves Ventilation Test operation of slave valves. Reset all pneumatic cylinder release valves. Test on-off cycling of valves intended to cycle. Inspection, testing, and maintenance in accordance with the requirements of NFPA 20 and NFPA 25. Inspect and empty the moisture trap, oil injection (pneumatic). Inspect compressed gas supply, inlet air pressure. Inspect outlet water (standby) pressure. Test start/stop pressure settings for standby pressure. Inspection, testing, and maintenance in accordance with the requirements of NFPA 25. Test interlocked systems (e.g., ventilation shutdown). Test shutdown of fuel/lubrication systems. Other

41 Semi-. Item Task Weekly Monthly Quarterly annually Annually Water mist system piping and nozzles Water recirculation tank Water storage cylinder. (high pressure) Inspection, testing, and maintenance in accordance with NFPA 25.. Inspect sample of nozzle screens and strainers (see of NFPA 750). Inspect water level (unsupervised). Inspect water level (supervised). Inspect supports, attachments. Test low water level alarm. Inspect water quality, drain, flush, and refill. Test operation of float-operated valve. Test pressure at outlet during discharge. Test backflow prevention device (if present). Inspect and clean filters, strainers, cyclone separator. Inspect water level (load cells). Inspect water level (unsupervised). Other After discharge

42 Semi-. Item Task Weekly Monthly Quarterly annually Annually Water storage tanks Water supply (general) Inspect support frame/restraints. Inspect vent plugs at. refilling. Inspect cylinder pressure on discharge. Inspect filters on refill connection. Inspect water level (unsupervised). Inspect water level (supervised). Confirm sight glass valves are open. Inspect tank gauges, pressure. Inspect all valves, appurtenances. Drain tank, inspect interior, and refill. Inspect tank condition (corrosion). Inspect water quality. Inspect water temperature. Inspect source pressure. Inspect source quality. (*first year). Test source pressure, flow, quantity, duration. * Other Extreme weather

43 Table Summary of Water Mist System Inspection, Testing, and Maintenance Inspection Item Frequency Reference Additive storage cylinders Quarterly/Semiannually Air compressors and receivers Monthly Chapter 13 (see ) Backflow preventers Chapter 13 (see ) Compressed gas storage cylinders, hoses, support and restraint Compressed gas storage cylinder valve and pressure Quarterly/Annually/Every 5 years Monthly/Quarterly Control equipment NFPA 72 Detection systems NFPA 72 Enclosure features, interlocks Semiannually , , , , , , Fire pumps and drivers Chapter 8 Gauges (piping system) Quarterly Chapter 13 (see ) Hangers, braces and supports Nozzles Annually and after each system discharge or activation Annually and after each system discharge or activation Pneumatic valves Monthly Pneumatic valve tubing Quarterly Pneumatically operated standby pumps Strainers and filters Monthly After each system discharge or activation System control valves Annually Chapter 13 System piping, tubing and fittings Annually and after each system discharge or activation

44 Item Frequency Reference Water recirculation tanks Monthly/Quarterly/Annually Water storage cylinders (high pressure) Quarterly/Semiannually/Annually Water storage tanks Chapter 9 Water supply Quarterly/Annually Testing Additives and injection system Air compressors and receivers , , , , , , Annually , Annually Chapter 13 (see ) Backflow preventers Chapter 13 (see ) Compressed gas storage cylinder 5-12 years Control equipment Detection systems Fire pumps and drivers Gauges (piping system) 5 years Hoses 5 years Interlocks Annually Nozzles, Automatic At 5 years and every 5 years thereafter Nozzles, Open Annually Pneumatic valves Semiannually Pneumatic valve solenoid releases Pneumatically operated standby pumps Annually Quarterly Strainers and filters Annually System control valves Annually Water mist system Annually Chapter 8 (see 8.3), Chapter 13 (see , )

45 Item Frequency Reference Water recirculation tanks Annually Water storage cylinders (high pressure) 5-12 years Water storage tanks Water supply Annually Maintenance Air compressors and receivers Annually Chapter 13 (see ) Backflow preventers Chapter 13 (see ) Control equipment NFPA 72 Detection systems NFPA 72 Fire pumps and drivers Chapter 8 (see 8.5) Pneumatically operated standby pumps Strainers and filters Every 5 years Annually and after each system discharge Water mist system Annually Water tanks Annually Inspection Water Mist Nozzles Water mist nozzles shall be inspected from the floor level annually Any water mist nozzle that shows signs of any of the following shall be replaced: (1) Leakage (2) Corrosion

46 (3) Physical damage (4) Loss of fluid in the glass bulb heat responsive element (5) *Loading (6) Painting, unless painted by the water mist nozzle manufacturer Any water mist nozzle that has been installed in the incorrect orientation shall be corrected by repositioning the branch line, drop, or sprig, or shall be replaced Water mist nozzles with glass bulbs shall be replaced if the bulbs are partially or fully empty of fluid Water mist nozzles installed in concealed spaces such as above suspended ceilings shall not require inspection Water mist nozzles installed in areas that are inaccessible for safety considerations due to process operations shall be inspected during each scheduled shutdown Stock, furnishings, or equipment closer to the water mist nozzle than permitted by the clearance specified in the manufacturer s installation instructions shall be corrected Open nozzles shall be removed, inspected and cleaned during the flushing procedure for the mainline strainer The supply of spare automatic water mist nozzles shall be inspected annually for the correct number and type of water mist nozzles as required by NFPA Strainers and filters Mainline strainers and filters shall be flushed until clear after each operation or flow test Individual water mist nozzle strainers and filters shall be inspected and cleaned after each operation or flow test All strainers and filters shall be inspected and cleaned in accordance with the manufacturer s instructions Damaged or corroded parts or assemblies shall be replaced or repaired System Piping, Tubing and Fittings.

47 Water mist system distribution pipe and fittings shall be inspected annually from the floor level Pipe and fittings shall be free of mechanical damage, leakage, and corrosion Water mist system distribution piping shall not be subjected to external loads by materials either resting on the pipe or hung from the pipe Pipe and fittings installed in concealed spaces such as above suspended ceilings shall not require inspection Pipe and fittings installed in areas that are inaccessible for safety considerations due to process operations shall be inspected during each scheduled shutdown Hangers, Braces, and Supports. A See A Water mist system distribution pipe hangers, braces, and supports shall be inspected annually from the floor level Hangers, braces, and supports shall not be damaged, loose, or unattached Hangers, braces, and supports that are damaged, loose, or unattached shall be replaced or refastened * Hangers, braces, and supports installed in concealed spaces such as above suspended ceilings shall not require inspection. A Examples of hangers and seismic braces installed in concealed areas include some floor/ceiling or roof/ceiling assemblies, pipe chases, and other inaccessible areas Hangers, braces, and supports installed in areas that are inaccessible for safety considerations due to process operations shall be inspected during each scheduled shutdown High Pressure Storage Cylinder Assemblies (Gas and Water) All cylinders and mounting brackets shall be fastened securely in accordance with the manufacturer s requirements Quarterly, compressed gas cylinders shall be inspected to proper securement.

48 Annually, high pressure water cylinders shall be inspected to proper securement * Compressed gas cylinders continuously in service without discharging shall be given a complete external visual inspection every 5 years or more frequently if required. The visual inspection shall be in accordance with Section 3 of CGA C-6, except that the cylinders need not be emptied or stamped while under pressure. Inspections shall be made only by competent personnel, and the results recorded on both of the following: (1) A record tag permanently attached to each cylinder (2) A suitable inspection report A These guidelines apply only to the external inspection of containers continuously in service in the water mist system and should not be confused with the DOT retest requirements for visual inspection described in 49 CFR. Proper recordkeeping is an important part of every inspection. The inspector should be guided by the following outline to ensure that the minimum information is recorded: 1. Record tag. A record tag should be attached to every container being inspected for future reference. The record tag should be marked with the date of inspection (month/year), name of individuals(s) and company performing the inspection, container serial number, condition of the container (paint, corrosion, dents, gouges, etc.), and disposition. 2. Inspection report. The following information should be recorded on an inspection report: date of inspection (month/year), name of individual(s) and company performing the inspection, DOT specification number, container serial number, date of manufacture, date of previous inspection and/or test, type of protective coating, surface condition (corrosion, dents, gouges, fire damage, etc.), and disposition (satisfactory, repaint, repair, scrap, etc.). A sample of a suitable inspection report form can be found in Appendix A of CGA C A completed copy of the inspection report shall be furnished to the owner of the system or an authorized representative. These records shall be retained by the owner for the life of the system Annually, visually inspect the cylinder for the proper specification, capacity and pressure rating The pressure in the high pressure storage containers shall be within the water mist manufacturer s specifications Unsupervised pressure in compressed gas cylinders shall be inspected monthly Supervised pressure in compressed gas cylinders shall be inspected quarterly.

49 The cylinder pressure on the discharge side of a high pressure water storage container shall be inspected annually The water level in the high pressure storage containers shall be within the water mist manufacturer s specifications Unsupervised water levels in high pressure cylinders shall be inspected quarterly Supervised water levels in high pressure cylinders shall be inspected semiannually Annually, visually inspect the vent plugs on high pressure water storage containers to ensure the vent is not ruptured or open Annually, visually inspect the filter on high pressure water storage containers to ensure it is clean Monthly, visually inspect the cylinder and control valves to confirm that they are in the proper position per the manufacturer s specification Annually, visually inspect all hoses used as a part of the system for damage Pneumatic Valves and Tubing Monthly, visually inspect all pneumatic cylinder valves for damage Quarterly, visually inspect all pneumatic tubing for damage Additive Storage Cylinders Quarterly, visually inspect the storage cylinder for external corrosion or damage Semiannually, inspect the quantity of the additive agent Water Recirculation Tanks All tank attachments and supports shall be secure in accordance with the manufacturer s requirements The water level in recirculation tanks shall be within the water mist manufacturer s specifications.

50 Unsupervised water levels in recirculation tanks shall be inspected monthly Supervised water levels in recirculation tanks shall be inspected quarterly Annually, inspect the water quality and drain, flush and refill as necessary Annually, visually inspect filters, strainers and cyclone separator and clean as necessary Pneumatically Operated Standby Pumps Monthly, visually inspect and empty the moisture trap Monthly, visually inspect the compressed gas supply and inlet air pressure in accordance with the manufacturer s specifications Monthly, visually inspect the outlet water (standby) pressure in accordance with the manufacturer s specifications Monthly, visually inspect the oil level on air regulator units in accordance with the manufacturer s specifications Water Supply Quarterly, visually inspect water supply pressure to determine that it is within the water mist manufacturer s specifications Inspect the water quality semiannually for the first year and then annually thereafter Enclosures and Interlocks. Semiannually, inspect the integrity of the enclosure and interlocks Testing Nozzles, Automatic * [NOTE: Change Annex numbering from A to A ] Where required by this section, sample automatic water mist nozzles shall be submitted to a recognized testing laboratory acceptable to the authority having jurisdiction for functional testing

51 Automatic water mist nozzles that have been in service for years shall be replaced, or representative samples shall be tested and then retested at 10 5-year intervals * Where water mist nozzles are subjected to harsh environments, including corrosive atmospheres and corrosive water supplies, they shall be either replaced or representative samples tested on a 5-year basis. A A These environments include outdoor weather conditions and portions of any area where corrosive vapors prevail. Harsh water environments include water supplies that are chemically reactive. An example of a corrosive atmosphere is a marine environment. The testing requirements for these types of environments are also described in the International Maritime Organization s Guidelines for the Maintenance and Inspection of Fire Protection Systems and Appliances, MSC.1/Circular * [NOTE: Change Annex numbering from A to A ] A representative sample of water mist nozzles for testing per or shall consist of a minimum of four water mist nozzles or 1 percent of the number of water mist nozzles per individual water mist nozzle sample, whichever is greater Where one water mist nozzle within a representative sample fails to meet the test requirement, all water mist nozzles within the area represented by that sample shall be replaced Automatic water mist nozzles that need to be replaced shall be in accordance with the requirements of Nozzles, Open Water mist nozzles installed to protect application areas without protective coverings shall be capable to operate and protect the hazard with an overspray residue in the event of a fire Where water mist nozzles are subjected to environments with residues, including corrosive atmospheres and corrosive water supplies, they shall be either replaced or representative samples tested on a 1-year basis. A See A A representative sample of water mist nozzles for testing per shall consist of a minimum of three water mist nozzles or 1 percent of the number of water mist nozzles per individual water mist nozzle sample, whichever is greater Where one water mist nozzle within a representative sample fails to meet the test requirement, all water mist nozzles within the area represented by that sample shall be replaced.

52 Strainers and Filters. Mainline strainers (basket or screen) shall be flushed until clear after each operation or flow test Additives. Samples of the additive shall be submitted in accordance with the manufacturer s recommended sampling procedures for evaluation of quality to its specification Operational Test Performance with Additives Operational tests shall be conducted to ensure the injection rate of the additive for the water mist system responds as designed, both automatically and manually The test procedures shall simulate anticipated emergency events so the response of the water mist system can be evaluated Where a discharge from the system discharge devices would create a hazardous condition or conflict with local requirements, an approved alternate method to achieve full flow conditions shall be permitted It shall be permissible to test the full flow discharge from the water mist system with additive using water only in lieu of the additive Response Time. Under Test conditions, the automatic fire detection systems, when exposed to a test source, shall operate within the requirements of NFPA 72 for the type of detector provided, and the response time shall be recorded Discharge Time. The time lapse between operation of detection systems and water delivery time to the protected area shall be recorded for open discharge devices Compressed Gas Storage Cylinders Gas cylinders designed in accordance with U.S. Department of Transportation (DOT), Canadian Transport Commission (CTC), or similar containers shall not be recharged without retesting if more than 5 years have elapsed since the date of last test A completed copy of the test report shall be furnished to the owner of the system or an authorized representative. These records shall be retained by the owner for the life of the system Control Equipment Operational tests shall be conducted to ensure the control equipment for the water mist system responds as designed, both automatically and manually Conduct annual operational testing in accordance with the requirements of NFPA 72.

53 Where a discharge from the system discharge devices would create a hazardous condition or conflict with local requirements, an approved alternate method to achieve full flow conditions shall be permitted Detection Systems Operational tests shall be conducted to ensure the control equipment for the water mist system responds as designed, both automatically and manually Conduct annual operational testing of the initiating devices for detection in accordance with the requirements of NFPA Response Time. Under Test conditions, the automatic fire detection systems, when exposed to a test source, shall operate within the requirements of NFPA 72 for the type of detector provided, and the response time shall be recorded Discharge Time. The time lapse between operation of detection systems and water delivery time to the protected area shall be recorded for open discharge devices Fire Pumps and Drivers Fire pumps shall be tested in accordance with the requirements of High pressure diesel and electric main pressure fire pumps shall be tested weekly or as permitted by an approved risk analysis in accordance with the manufacturer s requirements Water mist systems that are powered by or operated by pressurized gas (normally air or nitrogen) cylinders or pressure vessels shall be tested quarterly or determined by an approved risk analysis in accordance with the manufacturer s specifications using pressurized gas and water from either the primary cylinders or pressure vessels and/or tanks or by using temporary/test cylinders or tanks to verify nozzle flows (no blockage, fully developed spray pattern) upon operation Hoses All hose shall be tested every 5 years All hose shall be tested at times the maximum container pressure at 130 F (54.4 C). The testing procedure shall be as follows: (1) The hose is removed from any attachment. (2) The hose assembly is then placed in a protective enclosure designed to permit visual observation of the test. (3) The hose must be completely filled with water before testing.

54 (4) Pressure then is applied at a rate-of-pressure rise to reach the test pressure within 1 minute. The test pressure is then maintained for 1 full minute. Observations are then made to note any distortion or leakage. (5) If the test pressure has not dropped or if the couplings have not moved, the pressure is released. The hose assembly is considered to have passed the hydrostatic test if no permanent distortion has taken place. (6) Hose assembly passing the test must be completely dried internally. If heat is used for drying, the temperature must not exceed the manufacturer s specifications. (7) Hose assemblies failing a hydrostatic test must be marked and destroyed and be replaced with new assemblies. (8) Each hose assembly passing the hydrostatic test is marked to show the date of test Interlocks Conduct annual testing to confirm the operation of the interlock for ventilation, if required Conduct annual testing to confirm the operation of the interlock for fuel or lubrication systems, if required Pneumatic Valves Operational tests shall be conducted to ensure the pneumatic valves for the water mist system respond as designed, both automatically and manually Conduct semiannual testing of the pneumatic valves for operation in accordance with the manufacturer s instructions: (1) Slave valves (2) Valves intended to cycle on-off Reset all pneumatic cylinder release valves after testing Pneumatic Valve Solenoid Releases Operational tests shall be conducted to ensure the pneumatic valve solenoid releases for the water mist system responds as designed, both automatically and manually Conduct annual testing of the pneumatic solenoid valve releases for operation in accordance with the manufacturer s instructions: (1) Electric release

55 (2) Manual release Pneumatically Operated Standby Pumps Pumps (booster pumps, jockey pumps or transfer pumps) used in the water mist system which are not main pressure pumps shall be operated to demonstrate support of their design function for the main pressure pumps Standby pumps shall be operated at least annually to demonstrate their system flow support when the main pressure pumps are tested System control valves. Each control valve for a zone of protection by the water mist system shall be operated annually through its full range and returned to its normal position Water Mist System. Water mist systems shall be operated annually in accordance with the manufacturer s instructions * Test Preparation. Precautions shall be taken to prevent damage to property during the test. A See A Operational Test Performance. Operational tests shall be conducted to ensure the water mist system responds as designed, both automatically and manually Where the nature of the protected property is such that water cannot be discharged into the occupancy or onto the hazard, an operational test shall be conducted from a test connection with an orifice equivalent to the friction loss for the total number of nozzles * Response Time. A Test methods are as follows: 1. Some detection circuits can be permitted to be deliberately desensitized in order to override unusual ambient conditions. In such cases, the response required in can be permitted to be exceeded. 2. Testing of integrating tubing systems can be permitted to be related to this test by means of a standard pressure impulse test specified by the listing laboratory. One method of testing heat detection uses a radiant heat surface at a temperature of 300 F (149 C) and a capacity of 350 watts at a distance of 1 in. (25 mm) but not more than 2 in. (50 mm) from the nearest part of the detector. This method of testing with an electric test set should not be used in hazardous locations. Other test methods can be permitted to be employed, but the results should be obtained under these conditions.

56 Under test conditions, the detection systems, shall operate with the specifications from the Acceptance Test and These response times shall be recorded Discharge Time. The time lapse between operation of detection systems and water delivery time to the protected area shall be recorded * Discharge Patterns. A Water mist nozzles can be of different sizes and types. Some may be more susceptible to internal obstructions than others * The water discharge patterns from all of the open water mist nozzles shall be observed to ensure that patterns are not impeded by plugged nozzles, to ensure that nozzles are correctly positioned, and to ensure that obstructions do not prevent discharge patterns from fully developing. A * See Where the nature of the protected property is such that water cannot be discharged, the nozzles shall be inspected for proper orientation and the system tested with air to ensure that the nozzles are not obstructed Where obstructions occur, the piping and nozzles shall be cleaned and the system retested Pressure Readings Pressure readings shall be recorded at the hydraulically most remote nozzle or test connection to ensure the water flow has not been impeded by partially closed valves or by plugged strainers or piping For water mist systems with a deluge valve, a second pressure reading shall be recorded at the deluge valve to ensure the water supply is adequate Readings shall be compared to the hydraulic design pressures to ensure the original system design requirements are met and the water supply is adequate to meet the design requirements Where the hydraulically most remote nozzle is inaccessible, nozzles shall be permitted to be checked visually without taking a pressure reading on the most remote nozzle Where the reading taken at the riser indicates that the water supply has deteriorated, a gauge shall be placed on the hydraulically most remote nozzle and the results compared with the required design pressure Multiple Systems. The maximum number of systems expected to operate in case of fire shall be tested simultaneously to inspect the adequacy of the water supply.

57 Return to Service. After the full flow test, the water mist system shall be returned to service in accordance with the manufacturer s instructions Water Recirculation Tanks Operational tests shall be conducted to ensure water recirculation tanks for the water mist system responds as designed, both automatically and manually. (10.3.3) Conduct annual testing for operation in accordance with the manufacturer s instructions: (1) Float operated valves (2) Backflow prevention device, when present Pressure reading shall be recorded at the outlet of the recirculation tank during the operational discharge test of the water mist system Water Storage Cylinders (High Pressure) Water cylinders used with high pressure for power to deliver the water mist, or those that become pressurized at activation or water delivery or as the water source for a water mist system shall be tested in accordance with applicable current pressure vessel standard or code. A A source for test requirements is the most current FSSA Cylinder Service Guide. This is the same requirements that are applicable to cylinders, pressure tanks or pressure vessels used for pressurized gas agents Water cylinders design in accordance with U.S. Department of Transportation (DOT), Canadian Transport Commission (CTC), or similar containers shall not be recharged without retesting if more than 5 years have elapsed since the date of last test A completed copy of the test report shall be furnished to the owner of the system or an authorized representative. These records shall be retained by the owner for the life of the system Water Storage Tanks. Water storage tanks or cylinders shall be tested in accordance with the requirements of Water Supply. Conduct annual testing in accordance with 7.3 to verify the source: (1) pressure (2) flow (3) quantity (4) duration Maintenance.

58 General Maintenance shall be performed to keep the system equipment operable or to make repairs Where required by the manufacturer, maintenance shall be performed on devices not described in this standard As-built system installation drawings, original acceptance test records, and device manufacturer's maintenance bulletins shall be retained to assist in the proper care of the system and its components Replacement components shall be in accordance with the manufacturer's specifications and the original system design Spare components shall be accessible and shall be stored in a manner to prevent damage or contamination * After each system operation, a representative sample of operated water mist nozzles in the activated zone shall be inspected After each system operation due to fire, the system filters and strainers shall be cleaned or replaced Annually, a water tank used to supply a water mist system shall be drained and refilled Annually, a water mist system with open nozzles shall be flushed Other maintenance intervals shall be permitted depending on the results of the visual inspection and operating tests. Table Maintenance Frequencies Item Activity Frequency Water tank Drain and refill Annually System Flushing Annually Strainers and filters Clean or replace as required After system operation Water Mist Nozzles * Replacement water mist nozzles shall have the proper characteristics for the application intended, including the nozzle model and temperature rating Only new water mist nozzles shall be used to replace existing water mist nozzles *

59 A supply of spare water mist nozzles (never fewer than three) shall be maintained on the premises so that any water mist nozzles that have operated or been damaged in any way can be promptly replaced The water mist nozzles shall correspond to the manufacturer(s), models, and temperature ratings of the water mist nozzles in the property The automatic water mist nozzles shall be kept in a cabinet located where the temperature will at no time exceed 100 F (38 C) The stock of spare thermally activated nozzles shall include all types and ratings installed and shall be as follows: (1) For systems having fewer than 50 nozzles, not fewer than 3 nozzles (2) For systems having 50 to 300 nozzles, not fewer than 6 nozzles (3) For systems having 301 to 1000 nozzles, not fewer than 12 nozzles (4) For systems having over 1000 nozzles, not fewer than 24 nozzles * Where required by the manufacturer, a special water mist nozzle wrench shall be provided and kept in the cabinet to be used for the removal and installation of nozzles One water mist nozzle wrench shall be provided for each type of nozzle installed Protective Coverings Water mist nozzles protecting spray areas and mixing rooms in resin application areas installed with protective coverings shall continue to be protected against overspray residue so that they will operate in the event of fire * Water mist nozzles installed as described in shall be protected using cellophane bags having a thickness of in. (0.076 mm) or less or thin paper bags Coverings shall be replaced periodically so that heavy deposits of residue do not accumulate Water mist nozzles shall not be altered in any respect or have any type of ornamentation, paint, or coatings applied after shipment from the manufacturer Automatic water mist nozzles used for protecting commercial-type cooking equipment and ventilating systems shall be replaced annually Where automatic water mist nozzles are used and annual examination shows no buildup of grease or other material on the nozzles, the nozzles shall not be required to be replaced.

60 Pneumatically Operated Standby Pumps. Pneumatically operated standby pumps shall be rebuilt every five years or as specified by the manufacturer Training All persons who might be expected to inspect, test, maintain, or operate water mist systems shall be trained thoroughly in the functions they are expected to perform Refresher training shall be provided as recommended by the manufacturer or by the authority having jurisdiction.

61 E MARITIME SAFETY COMMITTEE 94th session Agenda item 20 MSC 94/20/2 12 September 2014 Original: ENGLISH ANY OTHER BUSINESS In-service testing of automatic sprinkler systems on passenger ships findings and proposed actions required to assure effective operation in emergency situations Submitted by the Bahamas SUMMARY Executive summary: This document updates the Committee on findings from the testing programme on automatic sprinkler systems on passenger ships implemented by the Bahamas and proposes urgent action to address the findings Strategic direction: 5.1 High-level action: Planned output: No related provisions Action to be taken: Paragraph 20 Related documents: MSC 92/INF.10 and SEE 1/21, paragraph Introduction 1 At MSC 92 the Bahamas introduced document MSC.92/INF.10, bringing to the attention of the Committee the Bahamas' concerns regarding failures of sprinklers to operate during testing on board ships in service. MSC 92 referred the document to SSE 1 for consideration. 2 SSE 1 noted the content of document MSC.92/INF.10 without taking any actions. This document updates the Committee on the progress of the testing of automatic sprinkler systems (here and after systems) on Bahamian flagged ships and current findings as of August 2014 and proposes urgent action. Background 3 The Committee will recall that the Revised Guidelines for the maintenance and inspection of fire protection systems and appliances (MSC.1/Circ.1432) contained enhanced guidance including paragraph relating to annual operational testing of sprinkler heads to "test a minimum of two automatic sprinklers or automatic water mist nozzles for proper operation". I:\MSC\94\20-2.doc

Technical Committee on Water Mist Fire Suppression Systems

Technical Committee on Water Mist Fire Suppression Systems Date: January 29, 2013 1. Call to Order. Meeting was called to order by Chair Larry Owen at 8:00 AM. 2. Building Safety Message. Building safety was discussed and exits identified by Chair Larry Owen.

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical on Fluidized Bed Boilers AGENDA Web/Teleconference 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of Members and Guests 3. Approval of Minutes from

More information

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016 TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES NFPA 610 First Draft Meeting October 17-18, 2016 Westin Kansas City at Crown Center 1 East Pershing Road Kansas City, MO, 64108 Conference Call Access:

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information

Page 1 of 190 Public Input No. 22-NFPA 55-2013 [ Global Input ] Throughout the document, delete ANSI from ANSI/ASME B31.3. Current Text: (multiple locations) ANSI/ASME B31.3 (found in Subsections: 2.3.2

More information

Correlating Committee on Automatic Sprinkler Systems

Correlating Committee on Automatic Sprinkler Systems Correlating Committee on Automatic Sprinkler Systems M E M O R A N D U M DATE: May 14, 2014 TO: FROM: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems Matt Klaus,

More information

TECHNICAL COMMITTEE ON FIRE CODE

TECHNICAL COMMITTEE ON FIRE CODE TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

NFPA 101 SAF-RES PUBLIC COMMENTS

NFPA 101 SAF-RES PUBLIC COMMENTS Page 134 of 195 Public Comment No. 3-NFPA 101-2013 [ Section No. 28.7.6.1 ] 28.7.6.1 New draperies, curtains, and other similar loosely hanging furnishings and decorations shall be flame resistant as demonstrated

More information

MSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017

MSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017 Procedure Number: E1-03 Revision Date: 02/16/2017 References: S. T. Brady, CDR, Chief, Engineering Division a. National Fire Protection Association (NFPA) 750, 1996 Edition, Standard on Water Mist Fire

More information

TECHNICAL COMMITTEE ON FIRE PUMPS

TECHNICAL COMMITTEE ON FIRE PUMPS TECHNICAL COMMITTEE ON FIRE PUMPS MEMORANDUM TO: FROM: Technical Committee on Fire Pumps Joanne Goyette, on behalf of C. Duffy / R. P. Benedetti DATE: May 2, 2011 SUBJECT: Letter Ballot on Proposals to

More information

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input of 201 1/13/2014 12:51 PM Public Input No. 88-NFPA 20-2013 [ New Section after 3.3.38.10 ] Add New Defination 3.3.28.11 Multiple Stage Multiple Port Pump. A single driver pump with multiple impellers operating

More information

Committee Input No. 9-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement

Committee Input No. 9-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement Committee Input No. 9-NFPA 2001-2016 [ Global Input ] Incorporate revisions per the attached file. Supplemental Information File Name 2001-CI_9.pdf Description Data and specific revisions presented at

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

Introductions made by the Chair, committee members, NFPA Staff Liaison, Jacqueline Wilmot and Dan Gorham of the Fire Protection Research Foundation.

Introductions made by the Chair, committee members, NFPA Staff Liaison, Jacqueline Wilmot and Dan Gorham of the Fire Protection Research Foundation. NFPA Technical Committee On Fire Hose NFPA 1961 Minutes Task Group Update Underwriters Laboratory November 15 th - 16 th 2016 Tuesday, November 15 th, 2016 Meeting called to order at 8:07 AM by Chairman

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

NFPA Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems

NFPA Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems San Antonio, TX October 12-14, 2016 The following are the meeting minutes from the third meeting of the Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems held in San Antonio,

More information

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture

More information

9/15/ Cantara Lane Vista, CA (760)

9/15/ Cantara Lane Vista, CA (760) 28 th Annual AHCA/FHEA SEMINAR Sprinkler System Inspection, Testing & Maintenance 1 Speaker Information: Bob Caputo, CFPS, CET Vice President Fire & Life Safety America 657 Cantara Lane Vista, CA 92081

More information

BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT

BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT Guidance and Instructions for Ship-owners, Managers, Masters, Bahamas Recognised Organisations and Bahamas Approved Nautical Inspectors Note: This

More information

SECTION FM-200 FIRE SUPPRESSION SYSTEM

SECTION FM-200 FIRE SUPPRESSION SYSTEM SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to

More information

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT 58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the

More information

Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA)

Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA) Technical Committee on Water Mist Fire Suppression Systems (WAM-AAA) M E M O R A N D U M DATE: September 29, 2016 TO: Principal and Alternate Members of the Technical Committee on Water Mist Fire Suppression

More information

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES SHIPPING NOTICE Maritime Authority of the Cayman Islands Head Office 3 rd Floor, Government Administration Building, 133 Elgin Avenue PO Box 2256, Grand Cayman, KY1-1107, Cayman Islands Tel: +1 345 949

More information

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS I. Introduction. This is the Motions Committee Report on Standards in the Fall 2013 Revision Cycle. The report identifies Certified

More information

Technical Committee on Multiple Burner Boilers

Technical Committee on Multiple Burner Boilers Technical Committee on Multiple Burner Boilers AGENDA Salt River Project PERA Club 1 Continential Drive Tempe, AZ January 14-15, 2014 1. Chair s welcome, call to order, and opening remarks at 8:00 a.m.

More information

Slide 2 NFPA 25: 2017

Slide 2 NFPA 25: 2017 Slide 1 Changes for 2017 NFPA 25 Handbook Supplement 8 contains a table highlighting the significant technical changes to NFPA 25 for the 2017 edition, along with a brief comment regarding the reason for

More information

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System 1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering

More information

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Building/Business Name: Address of Property: Inspector Name: Joe Price THE CORNERSTONE 1425 NE 7TH AVENUE PORTLAND OR Date

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless

More information

Public Safety [661] Chapter 226, Liquefied Petroleum Gas, Amended for Application within the State of Iowa

Public Safety [661] Chapter 226, Liquefied Petroleum Gas, Amended for Application within the State of Iowa Public Safety [661] Chapter 226, Liquefied Petroleum Gas, Pursuant to the authority of Iowa Code section 101.1, the State Fire Marshal hereby adopts new Chapter 226, Liquefied Petroleum Gas, Iowa Administrative

More information

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 An Engineered Carbon Dioxide Fire Suppression System shall be installed to meet a minimum design concentration of %, by volume in all designated spaces/areas to be protected.

More information

COMDTPUB P NVIC JUNE 1995

COMDTPUB P NVIC JUNE 1995 COMDTPUB P16700.4 NVIC 3-95 19 JUNE 1995 NAVIGATION AND VESSEL INSPECTION CIRCULAR NO. 3-95 Electronic Version for Distribution on the World Wide Web Subj: PERIODIC INSPECTION AND TESTING OF FIXED HALON

More information

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Item No. Subject 13-6-1 Call to Order (8:00 A.M) 13-6-2 Roll Call 13-6-3 Approval

More information

ISO INTERNATIONAL STANDARD. Fire protection Automatic sprinkler system Part 9: Requirements and test methods for water mist nozzles

ISO INTERNATIONAL STANDARD. Fire protection Automatic sprinkler system Part 9: Requirements and test methods for water mist nozzles INTERNATIONAL STANDARD ISO 6182-9 First edition 2005-11-01 Fire protection Automatic sprinkler system Part 9: Requirements and test methods for water mist nozzles Protection contre l'incendie Systèmes

More information

Page 1 of 12 Input No. 62-NFPA 409-2013 [ Section No. 3.3.9 ] 3.3.9 Hangar Building Cluster. A group of buildings with more than one area for the storage and servicing of aircraft and all attached or contiguous

More information

Page 1 of 198 Public Input No. 88-NFPA 20-2013 [ New Section after 3.3.38.10 ] Add New Defination 3.3.28.11 Multiple Stage Multiple Port Pump. A single driver pump with multiple impellers operating in

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

Public Comment No. 7-NFPA 30A-2013 [ Section No ]

Public Comment No. 7-NFPA 30A-2013 [ Section No ] Page 1 of 13 Public Comment No. 7-NFPA 30A-2013 [ Section No. 6.4.2 ] 6.4.2 Additional Proposed Changes Each pump shall have installed on the discharge side a listed leak detection device that will provide

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical Committee on Fluidized Bed Boilers AGENDA NFPA Headquarters 1 Batterymarch Park Quincy, MA 02169 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd

Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd Abstract Session Four Functional safety: the next edition of IEC 61511 Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd The functional safety standard IEC 61511 provides a framework for managing

More information

Australian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS

Australian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS AS 4214 2002 (Incorporating Amendment No. 1) AS 4214 2002 Australian Standard Gaseous fire extinguishing systems This Australian Standard was prepared by Committee FP-011, Gaseous Fire Protection. It was

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Tuesday, March 10; All Day Wednesday, March 11; All Day DRURY PLAZA HOTEL San Antonio Riverwalk 0. Administrative. A. Meeting Schedule.

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector NOTICE OF PROPOSED RULE DEVELOPMENT DEPARTMENT OF FINANCIAL SERVICES DIVISION OF STATE FIRE MARSHAL RULE CHAPTER: 69A-46, F.A.C. RULE: 69A-46.0165, F.A.C. RULE CHAPTER TITLE: Fire Protection System Contractors

More information

False Sense of Security???

False Sense of Security??? IS YOUR SPRINKLER SYSTEM GIVING YOU A FALSE SENSE OF SECURITY? Best Practices in Fire Safety An ASSE Virtual Symposium March 1 & 2, 2011 Walter S. Beattie CSP, CFPS, CSHM False Sense of Security??? Fire

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 0800 - COMMISSIONING OF FIRE SUPPRESSION SYSTEMS GENERAL 1.1 SUMMARY General 1. Work under this contract shall meet the requirements of Division 01, General Requirements, Conditions of Contract,

More information

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector Permit

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector Permit NOTICE OF PROPOSED RULE DEPARTMENT OF FINANCIAL SERVICES DIVISION OF STATE FIRE MARSHAL RULE CHAPTER: RULE CHAPTER TITLE: 69A-46, F.A.C. Fire Protection System Contractors and Systems RULE: RULE TITLE:

More information

Changes for the New Edition. Senior Engineer, NFPA NFPA

Changes for the New Edition. Senior Engineer, NFPA NFPA Changes for the New Edition Denise Beach Senior Engineer, NFPA NFPA Overview NFPA 58-2014 Substantive Changes TIAs 2017 Edition NFPA 58-2014 Substantive Changes Bulk and Industrial Plants 3.3.10 Bulk Plant.

More information

Australian Standard. Water mist fire protection systems System design, installation and commissioning AS

Australian Standard. Water mist fire protection systems System design, installation and commissioning AS AS 4587 1999 Australian Standard Water mist fire protection systems System design, installation and commissioning This Australian Standard was prepared by Committee FP/12, Aqueous Fire Protection Systems.

More information

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fire Code (FCC-AAA) Gregory

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

ISO 6183 INTERNATIONAL STANDARD. Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation

ISO 6183 INTERNATIONAL STANDARD. Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation INTERNATIONAL STANDARD ISO 6183 Second edition 2009-06-15 Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation Équipement de protection contre l'incendie

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

SPECIFICATION: ARGONITE Engineered Fire Suppression System

SPECIFICATION: ARGONITE Engineered Fire Suppression System 1. GENERAL SPECIFICATION 1.1 A total flooding, clean agent, fire suppression system, filled with Argonite agent shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61511-3 First edition 2003-03 Functional safety Safety instrumented systems for the process industry sector Part 3: Guidance for the determination of the required safety integrity

More information

ISO INTERNATIONAL STANDARD. Graphical symbols Safety colours and safety signs Part 2: Design principles for product safety labels

ISO INTERNATIONAL STANDARD. Graphical symbols Safety colours and safety signs Part 2: Design principles for product safety labels INTERNATIONAL STANDARD ISO 3864-2 First edition 2004-10-15 Graphical symbols Safety colours and safety signs Part 2: Design principles for product safety labels Symboles graphiques Couleurs de sécurité

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in

More information

NFPA 96, 2017 REVIEW SUMMARY

NFPA 96, 2017 REVIEW SUMMARY NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile

More information

Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA & NFPA 13/

Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA & NFPA 13/ Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA 25 2017 & NFPA 13/72 2016 The purpose of this guide is to help you determine if the system will work as

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.

More information

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection 1. GENERAL SPECIFICATION 1.1 A total flooding, Novec 1230 fluid, fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in

More information

ISO INTERNATIONAL STANDARD. Safety identification Escape and evacuation plan signs. Identification de sécurité Plans d'évacuation et de secours

ISO INTERNATIONAL STANDARD. Safety identification Escape and evacuation plan signs. Identification de sécurité Plans d'évacuation et de secours INTERNATIONAL STANDARD ISO 23601 First edition 2009-02-15 Safety identification Escape and evacuation plan signs Identification de sécurité Plans d'évacuation et de secours Reference number ISO 23601:2009(E)

More information

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 WET SPRINKLER Monthly Wet Sprinkler 2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 VISUALS [per NFPA 25-1998 ed] 1. Gauge (Ck for Condition, Normal Pressure) [per 2-2.4.1] 2. Valves

More information

NFPA 550 ROP Meeting Minutes

NFPA 550 ROP Meeting Minutes NFPA 550 ROP Meeting Minutes NFPA Technical Committee on Fire Risk Assessment Methods (FIR-AAA) June 24, 2010 Microsoft Live Meeting 1. Call to order. The meeting was called to order at 1:00 PM on Monday,

More information

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 AGENDA: Life Safety Code Referenced Publications Overview Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-21 21 03.00 10 February 2009) ---------------------------------- Preparing Activity: USACE Superseding UFGS-21 21 03.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard

More information

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER 0780-02-14 FIRE EXTINGUISHERS TABLE OF CONTENTS 0780-02-14-.01 Definitions 0780-02-14-.09 Restrictions 0780-02-14-.02 Standards

More information

U.S. Codes & Standards for Energy Storage Systems. Joe Cain, P.E. Chair, SEIA Codes & Standards Working Group

U.S. Codes & Standards for Energy Storage Systems. Joe Cain, P.E. Chair, SEIA Codes & Standards Working Group U.S. Codes & Standards for Energy Storage Systems Joe Cain, P.E. Chair, SEIA Codes & Standards Working Group Regulatory Update: U.S. Codes & Standards Agenda NFPA 70 (NEC) UL 1973 & 9540 Fire Codes NFPA

More information

Functional Safety: the Next Edition of IEC 61511

Functional Safety: the Next Edition of IEC 61511 HazAus2015/1507 Functional Safety: the Next Edition of IEC 61511 Mirek Generowicz Engineering Manager I&E Systems Pty Ltd Level 2, 445 Hay Street Perth WA 6000 Abstract The functional safety standard IEC

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1. A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated

More information

Page 1 of 73 Print Reload Page Close Show Cart Public Input No. 13-NFPA 170-2012 [ Global Input ] 3.3.3 Photoluminescent. A type of sign that is self-energized with respect to luminosity and requires no

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61511-1 First edition 2003-01 Functional safety Safety instrumented systems for the process industry sector Part 1: Framework, definitions, system, hardware and software requirements

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

System Test Report CLEAN AGENT

System Test Report CLEAN AGENT City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information

More information

NFPA 79 - Second Draft Meeting July 8-10, DoubleTree Hotel, Portland, ME

NFPA 79 - Second Draft Meeting July 8-10, DoubleTree Hotel, Portland, ME National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NFPA TECHNICAL COMMITTEE ON ELECTRICAL EQUIPMENT OF INDUSTRIAL

More information

DIVISION 21 FIRE SUPPRESSION

DIVISION 21 FIRE SUPPRESSION Table of Contents 21 00 00 FIRE SUPPRESSION...2 A. REFERENCE ABBREVIATIONS... 2 B. GENERAL... 2 C. DESIGN REQUIREMENTS... 2 D. DOCUMENTATION... 2 21 08 00 FIRE SUPPRESSION COMMISSIONING...2 A. PIPE CLEANING...

More information

3M Personal Safety Division. Standards Update. NFPA 1981/1982, 2018 Edition. March 30, 2018

3M Personal Safety Division. Standards Update. NFPA 1981/1982, 2018 Edition. March 30, 2018 3M Personal Safety Division Standards Update NFPA 1981/1982, 2018 Edition March 30, 2018 Standards Update NFPA 1981/1982, 2018 Edition The purpose of this presentation is to provide an update on the status

More information

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS June 20, 2011 TO: PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS SUBJECT: New Acceptance Criteria for Fixed Condensed Aerosol Fireextinguishing Systems, Subject AC432-0611-R1

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE PUMP REVIEW Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;

More information

FM-200 In-Cabinet Series

FM-200 In-Cabinet Series 1. GENERAL SPECIFICATION 1.1 A total flooding, In-Cabinet fire suppression system, employing FM-200 superpressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by

More information

DIRECTIVE NO: D-B

DIRECTIVE NO: D-B DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

Attachment 1. to ClassNK Technical Information No.TEC-0764 Malta Maritime Authority Date Revised 28 August 2008 Page 1 of 10 This Administration Requi

Attachment 1. to ClassNK Technical Information No.TEC-0764 Malta Maritime Authority Date Revised 28 August 2008 Page 1 of 10 This Administration Requi Subject Periodical Maintenance, Inspection and Testing for Fire Protection Systems, and Appliances and Compressed Gas Cylinders onboard Maltese Flagged Vessels (Partly Amended) To whom it may concern Technical

More information

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler

More information