SMARTWIRE MKII INSTALLATION MANUAL HARD-WIRED NURSE CALL SYSTEM. SmartWire MK2 Nurse Call Installation Manual v1.8.doc

Size: px
Start display at page:

Download "SMARTWIRE MKII INSTALLATION MANUAL HARD-WIRED NURSE CALL SYSTEM. SmartWire MK2 Nurse Call Installation Manual v1.8.doc"

Transcription

1 SMARTWIRE MKII HARD-WIRED NURSE CALL SYSTEM INSTALLATION MANUAL

2 1. CONTENTS 1. CONTENTS EQUIPMENT LIST INTRODUCTION CABLE SPECIFICATION COMPONENTS...5 TYPE A (CALL, SOCKET AND CANCEL UNIT)...5 Example TYPE B (CALL AND CANCEL UNIT)...6 Example PATIENT CORD-SET...7 SHOWER PULL SWITCHES...7 CORRIDOR/DOOR LAMPS (MULTICOLOURED)...7 SOUNDERS...8 SMARTLITE DISPLAYS...8 WIRELESS REMOTE DISPLAYS SYSTEM CABLING WIRING DIAGRAM 1 CEILING PULL CORD WIRING DIAGRAM 2 COMMON CORRIDOR LIGHT WIRING DIAGRAM 3 DISPLAY CONTROLLER INTERFACE WIRING DIAGRAM 4 - ZONING DISPLAYS...13 DISPLAY CONTROLLER INTERFACE TO LED DISPLAY WIRING WIRING DIAGRAM 5 - INTERFACING RADIO RECEIVERS WIRING DIAGRAM 6 - INTERFACING EXTERNAL DEVICES CONFIGURING LED DISPLAY DESCRIPTIONS...16 CONFIGURING DISPLAY MESSAGES TECHNICAL NOTES...17 SYSTEM POLLING...17 DISPLAY CONTROLLER INTERFACE...17 MASTER UNIT BUFFER...17 SYSTEM LOW BATTERY REPORTING (CLIENT CODE 9917)...17 BACKUP BATTERY REQUIREMENTS SYSTEM SETTINGS...18 MASTER CONTROLLER INTERFACE...18 MASTER CONTROLLER INTERFACE DIP-SWITCH SETTINGS...18 DIP SWITCH LOCATIONS ON MASTER UNIT AND CALL POINT...19 Setting Call Types DIP Switches 6, 7 & Setting Call Types DIP Switches 6, 7 & 8 (Continue)...21 Setting Call Points Numbers (Client Codes) DIP-Switches 1 to Setting Call Points Numbers Continued

3 16. SMARTWATCH XP SOFTWARE SETUP...24 SETTING UP THE PORT...24 SYSTEM CLIENT CODE (CLIENT CODE 9917)...25 SETTING UP SMARTLINK CLIENTS...26 APPENDIX 1 - CABLING GUIDELINES...27 SYSTEM WIRING GUIDELINES BASED ON CURRENT CONSUMPTION CALL POINTS PLACED AT END OF SINGLE CABLE RUN SUCCESSIVE ADDITION OF CALL POINTS ON SINGLE CABLE RUN...28 SYSTEM CONFIGURATIONS AND LIMITATIONS...29 LINE BOOSTERS...29 CABLING EXAMPLE...29 APPENDIX 2 CALCULATING BACKUP BATTERY REQUIREMENTS...30 CURRENT CONSUMPTION FIGURES PER COMPONENT...30 BATTERY CALCULATION EXAMPLE...30 APPENDIX 3 RS232 TO RS485 CONVERTER FOR LED DISPLAY...31 POWERING THE CONVERTER...31 CABLING...31 EXTERNAL CONNECTIONS...31 INTERNAL CONNECTIONS...32 INTERNAL LINK SETTINGS...32 APPENDIX 4 LED DISPLAYS...33 POWER SUPPLY...33 CURRENT CONSUMPTION...33 AUDIO...33 DATA CONNECTION...33 APPENDIX 5 - AUTOTEX AM...34 AUTOTEX AM FAQ CONTINUED...35 APPENDIX 6 RADIO NURSE CALL RECEIVER INSTALLATION...36 MODES OF OPERATION...36 ANY KEY OPERATION...36 PROGRAMMED KEY OPERATION...36 PROGRAMMING RADIO KEYS INTO RECEIVER...37 REMOVING RADIO KEYS FROM RECEIVER...37 LED OPERATION...37 SPECIFICATIONS...37 NOTES

4 2. EQUIPMENT LIST A SmartWire Nurse Call System consists of the following equipment: 1. Master Controller Interface Unit 2. Serial Extension Cable 2 m (DB9 M - DB9 F) 3. DB9 M to DB25 F adaptor 4. 12V DC 1.5A Regulated Plug Pack 5. Installation Manual Note: Hardwired Call Points (sold separately) ATTENTION If using a power supply other than the one provided, please make sure it is equipped with an earth connection. Switch-mode type power supplies with an Earth connection are also acceptable. 3

5 3. INTRODUCTION The SmartWire Nurse Call System complies with Australian Standard AS for Hard- Wired Patient Alarm Systems. SmartWire Nurse Call System is a Bus-connected system, with 4 wires connecting most of the components. The bus communicates to the SmartLink Monitoring Software via a Master Controller Unit. Some items (e.g. overdoor lamps) can be directly wired to intelligent Type A Call Points serving for independent operation in the event of a bus failure. A single bus with one Master Controller Unit can carry information relating to a maximum of 240 individually identifiable Call Point numbers. A maximum of 4 SmartWire Master Controller Units may be connected to SmartLink s Monitoring Software enabling 960 individual call points to be monitored. Each of these individual Call Points (Client Codes) can be assigned to signal 5 different types of call: 1. Patient Call 2. Wet Area (Patient Call) 3. Emergency 4. Staff Assist 5. Nurse Presence 4. CABLE SPECIFICATION Recommended cable type is 6-core multi-strand cable (6Cx14x0.20mm) All wiring must be in accordance with AS3000 for electrical installations (wiring) Please refer to section 6 for more details on System Cabling 4

6 5. COMPONENTS TYPE A (Call, Socket and Cancel unit) Type A units connect directly to the Main Bus and provide up to a maximum of three functions on one plate (including the cord-set socket which is always a standard Patient Call, but have the intelligence to generate any type of call (fully programmable). They can be used as a hub unit where several types of calls are desired from the one SmartWire Call Point number (i.e. Client Code) location. They are backlit and capable of operating a multicoloured door lamp. The MKII Type A call points also have the added features of Call Escalation and Common Corridor Light Assignment. Right: Patient Call with socket plug Left: Staff Assist call with Patient Cord-Set Example 1 In a rest home room with en-suite, the Type A unit would be located at the bed, and Type B units would be used in the WC and shower. MAIN BUS MAIN BUS TYPE A Call, Socket & Cancel (Staff Assist) DOOR LAMP (Yellow) SOUNDER (if required) More Wet Area Units (if required) TYPE B Call & Cancel (Wet Area Call) TYPE B Call & Cancel (Wet Area Call) 5

7 TYPE B (Call and Cancel unit) The type B units have no intelligence, and are simply plates carrying push buttons and lights. They can only be connected in series to a Type A Call Point and are backlit. Several Type B plates can be connected to a type A unit, but they must all be of the same type of Call. Right: Nurse Presence Call Type B units must all have the same function and Call Point number (Client Code) associated with them. For example, it is NOT possible to have the Wet Area Call Points and a Nurse Presence call point connected to the same Type A unit. If Nurse Presence was required, another Type A unit would be needed in the room, and this in turn could support further Type B units, to make Emergency Calls for example (see Example 2). Example 2 The room illustrated in Example 2 is capable of making all five types of calls using 2 different caller IDs (one per Type A branch from the Main Bus). MAIN BUS MAIN BUS TYPE A Call, Socket & Cancel (Staff Assist) TYPE A Call, Socket & Cancel (Nurse Presence) Patient Cord-Set (Patient Call) DOOR LAMP (Yellow) SOUNDER (if required) More Wet Area Units (if required) TYPE B Call & Cancel (Patient Call) TYPE B Call & Cancel (Patient Call) More Emergency Units (if required) 6

8 Patient Cord-Set A Patient Cord-Set can be plugged into any Type A (Call and Cancel units), and will generate a Patient Call if unplugged. If a Type A Call Point does not have a Cord Set plugged into its socket during power up it will assume that a patient cordset will not be used and hence will not generate an alarm. However, once a Patient cord-set is plugged into the Type A, it will expect the Patient Cord-Set to be continuously connected. Removal of the Cord-Set will generate an Alarm of type Patient Call. Resetting the power of the Type A call point will cause the Type A call point to return to its original state. Right: Patient Cord-Set (cord length not to scale) Left: Patient Cord-Set plug (plug not to scale) Shower Pull Switches A Shower Pull Switch may be ceiling or wall mounted, and contains a reassurance light, but no Cancel switch. When used in a shower or WC room, the Cancel button on the Type B (Call and Cancel unit) beside the WC can be used to Cancel the shower pull. If used in a stand-alone shower or bathroom, the pull switch should be used in conjunction with a Type A (Call and Cancel unit) installed in the same room. Shower pull switches are fitted with breakable links in the cords. Right: Pull Cord hanging from ceiling Corridor/Door Lamps (Multicoloured) Where required, lamps can be installed and wired directly back to the Type A Call and Cancel points they serve. A single lamp is capable of displaying the appropriate Green, Amber and Red light conditions depending on the type of call. The corridor light is a Tri-State LED that requires 3 connections at all times. The three connections are labelled +, G, R, or positive, Green and Red. The combination of these two colours forms the third colour Amber. Right: Multicoloured corridor light in its OFF state. 7

9 Sounders Sounders are connected directly to the bus, and have a limited amount of intelligence. Their operation complies with the Standard s requirement that sounders and corridor lights should continue to operate if the main communication bus fails. The sounder monitors data on the bus and beeps according to the highest priority alarm. Right: Sounder with piezo-alarm output facing SmartLite Displays The SmartLite displays can run directly off the SmartWire Master Unit or from the SmartWire bus using a Display Controller Interface. Messages associated with a call point (Client Code) are displayed on the SmartLite Display when that particular call is initiated. Messages are prioritised in the order: Emergency, Staff Assist, Patient Call (Wet Area), Patient Call, followed by Nurse Presence. Zoning of messages is also possible with the use of the Display Controller Interface. SmartLite Displays can be either single or double sided for wall or ceiling mounted requirements respectively. (Supports RS232 and RS485 inputs) Above: SmartLite Display (Refer to Appendix 1 & 2) Wireless Remote Displays The Wireless Remote Displays are used to display SmartLink Alarm Calls on a BetaBrite or SmartLite LED display sent via POCSAG pager messaging. Alarms can be paged to a specific Cap Code recognised by the Remote Display Wireless Decoder which will then display the call with appropriate colours and priority for nurse call applications. SmartLink Alarm Calls are generated using SmartLink s Monitoring Software (SmartWatch XP). For more information, refer to the Remote Display Wireless Decoder Installation Manual or contact SmartLink International. (Supports only RS232 inputs) Above: BetaBrite Display with Remote Display Wireless Decoder unit 8

10 6. SYSTEM CABLING The system communicates via 4 wire bus system (+, -, A, B). Recommended wiring is 6-core multi-strand (6Cx14x0.20) flexible security cable. We recommend using the additional 2 cores to double up on the supply lines (+ and -) to reduce voltage drops. DO NOT use twisted pair cable such as CAT5 as this will interfere with SmartWire bus communications. For details on system cabling please refer to APPENDIX 1. 9

11 7. WIRING DIAGRAM 1 Ceiling Pull Cord The Ceiling Pull Cord, when activated, shorts the C terminal on the Type A Call Point to ground (-) causing an Alarm. The Alarm may be cancelled from the Type B Call points connected in parallel or in certain instances from the Type A Cancel button. As a general rule it is always advisable to connect Ceiling Pull Cords in parallel with a Type B Call Point as the ceiling pull cords do not have the ability to cancel Alarms. 10

12 8. WIRING DIAGRAM 2 Common Corridor Light Enabling the Common Corridor Light option (via DIP switches 6, 7, & 8) on the Call Point allows a single Corridor lamp to be activated upon activation of any of the Call points on the Common Corridor line. Setting a Type A Call Point to operate in this mode voids the use of Type B Call Points from that particular Type A Call Point. Please refer to the Section labeled Setting Call Types for activation of this mode. 11

13 9. WIRING DIAGRAM 3 Display Controller Interface The Display Controller Interface can be placed anywhere along the main bus to drive SmartLite LED displays. Each Display Controller can store Messages for up to 240 Call points on the SmartWire MKII bus. The Display Controller allows Zoning of displayed messages by only displaying information relevant to Certain Call Points. Each Display Controller Interface can drive up to 2 displays using direct RS 232 and up to 32 displays using an RS232 to RS485 converter. 12

14 10. WIRING DIAGRAM 4 - Zoning Displays The Display Controller Interfaces can be used to break up the system into zones, allowing only messages for certain call points to be displayed on specific LED displays. Each Display Controller Interface can drive a maximum of TWO displays up to 15 metres. Display Controller Interface to LED Display Wiring 13

15 11. WIRING DIAGRAM 5 - Interfacing Radio Receivers Typical Installation of the Radio Nurse Call Receiver onto a SmartWire MKII system The radio receiver is designed to work with the existing nurse call systems. The radio receiver interfaces through the local call point bus which makes integration extremely simple. The command messages of a radio key will activate the alarm through the local call point connections C and D. There is no requirement to program the radio keys as the radio messages will be validated by command and device type only. The radio receiver can be operated in two modes: Any Key Operation Mode and Programmed Key Only Mode. If operated in Any Key Mode the radio receiver will accept any SmartLink radio keys. If operated in Programmed Key Only Mode the radio receiver will only accept SmartLink keys that have been previously checked into the receiver (Maximum 40). Refer to APPENDIX 6 for more information on setting up a Radio Receiver. 14

16 12. WIRING DIAGRAM 6 - Interfacing External Devices External Devices such as Intercom Systems may be interfaced to the SmartWire MKII system by the use of a generic Modular Relay Board. The basic function of the relay board is to either short the C terminal on the Type A call point to Ground (for an activation) or to short the D terminal to Ground (for a cancellation). Other Proprietary SmartLink systems such as the Dementia and Patient Profiler or the SmartWalk system may be interfaced to the SmartWire system using the same principle. Note that the TR terminal on the Modular Relay Board is used to trigger the activation and cancellation of alarms. 15

17 13. CONFIGURING LED DISPLAY DESCRIPTIONS A 13 character SmartLite display can be connected to the SmartWire Master Unit or the Display Controller Interface. Call point alarms will be displayed with different colour messages for different types of alarm. Alarms will be displayed in priority and updated every 10 seconds. Only the highest priority messages are displayed. LED Display Alarm Priority Call Type Colour 1 EMERGENCY Red 2 STAFF ASSIST Yellow 3 PATIENT CALL, WET AREA & CORD OUT Yellow 4 NURSE PRESENCE Green The default text for each call point is CALL ID call point number. For example: CALL ID 25 will be displayed when call point 25 is programmed to CALL. If there are any EMERGENCY Alarms, only the Emergency Alarm messages are displayed. If there is more than 1 Emergency message, each message is displayed for 10 seconds. If there are no emergency messages, the next highest priority messages are displayed. Configuring Display Messages The call point descriptions can be changed by creating a HyperTerminal connection with: Baud Rate 9600, Data Bits 8, Parity None, Stop bits 1 Plug the PC running HyperTerminal to the RS232 Communication port on the SmartWire MKII and press the Enter key. The following prompt will appear: Enter Call point Number:_ Follow prompts to change display text. Enter Call point Number (1-240): 12<CR> CALL ID 12 Enter call point name or <CR> to keep: ROOM 1<CR> Enter Call point Number: _ Example strings: CALL call point 6 ROOM 6 EMERGENCY call point 8 BATH 8 NOTES: The display edit feature will time out after 60 seconds or when an <ENQ> character is received and a time out message is displayed. If <CR> is pressed when entering call point number, all 240 call point strings are displayed. Maximum call point description is 13 characters. 16

18 14. TECHNICAL NOTES System Polling When the Master Unit is powered up, it will poll all the Call Points on the Main Bus and store the addresses in its non-volatile EEPROM memory. If the Master finds that a Call Point is disconnected or damaged, it will report a POWER Disconnect alarm with the associated Client Code of the Call Point to the Monitoring Software. It is only reported once and is deemed to be removed from the system so as to prevent a removed call point being reported as Power Disconnect forever. When the Call Point is connected back onto the Main Bus, the Master unit will recognise it and cancel the POWER Disconnect alarm. If a new call point is added to the system while powered down, it will be detected on power up and reported as Power Disconnect restore. A new system will report all call points connected to it the first time it is powered up. Display Controller Interface The display controller controls the LED display through an RS232 connection. Although the master unit can also carry out this task of controlling a LED display the Display Controller Interface is required in some installations where more than one LED display is required. The Display Controller Interface connects to the main bus and listens-in on the messages transmitted by the call points and sends the corresponding messages to the LED display. The Display Controller Interface uses the same hardware as the master unit with transmitter of the bus A removed and brown out voltage reduced from 7.5V to 6V. Master Unit Buffer In the event that communications between the SmartWire master unit and the monitoring PC is broken, the master unit buffers all alarms that are activated or cancelled. When the communication between the SmartWire master and monitoring PC is re-established the SmartWire system reports the record of which call points were activated and cancelled along with the present state of the system. System Low Battery Reporting (Client Code 9917) The Master Unit continuously monitors its supply voltage. When it detects that the supply voltage has dropped below 9.5V, it will report a BATTERY Low alarm with the Client Code Once the supply voltage exceeds 11.5V the BATTERY Low alarm is Cancelled. The SmartWire MKII has a brownout voltage of 7.5V, the master powers up once the supply exceeds 8.7V. Backup Battery Requirements The selection of a suitable backup battery involves knowing the current consumption of the entire system in standby and alarm states. To determine the total current consumption, you will need to know the quantity and configuration of the different types components used in the system. See APPENDIX 2 for details. 17

19 15. SYSTEM SETTINGS Master Controller Interface Master Interface Units act as an interface between the SmartLink Monitoring Software and the SmartWire Hard-wired Nurse Call System. Each Master Unit can handle up to 240 individual Call Point numbers which are allocated to Type A and Type C units only (Type B units share call points numbers with type A units and should NOT be included in this count). A maximum of 4 Master Interface Units can be used per SmartLink Monitoring Software installation providing a total of 960 individual Call Point numbers (Client Codes). Master Controller Interface DIP-Switch Settings The eight by 2-way DIP-Switch on the Master Unit shall be used to define the following: SmartLink Receiver (Address) Number defaulted to 1 Master Interface Modes of operation defaulted to Ademco + Checksum Client Codes (when added with Call Point numbers) defaulted to 7000 Default setting: Switch 1 and 5 in the ON position Client Codes Master Interface Modes SmartLink Receiver Address SmartLink Receiver Numbers Switch Switch CLIENT CODE Switch INTERFACE MODES PREFIX Ademco Call Point Ademco + Checksum Call Point Reserved Call Point Reserved Call Point

20 DIP Switch Locations on Master Unit and Call Point Default Jumper settings: Jumper 3 (Rx): short Jumper 4 (TEST): open Default DIP Switch settings: 1. ON 2. OFF 3. OFF 4. OFF 5. ON 6. OFF 7. ON 8. OFF 19

21 Call Point DIP-Switch Settings The eight by 3-way DIP-Switch on each Type A Call Point is used to define the following: Call Points Numbers (used with the Master Unit settings to determine the Client Code) Call Types (determine the Call Types of that particular Call Points) Call Types Call Points (Client Codes) Setting Call Types DIP Switches 6, 7 & 8 DIP-Switches 6, 7 & 8 determine the Call Type of that particular Type A unit as well as the Type B unit connected to it. As mentioned previously the available Call Types are: Patient Call, Wet Call Area, Staff Assist, Nurse Present and Emergency Call. Each Type A call unit has three available inputs that can be used to activate Calls and Alarms: Main (local button on Type A and call units) Remote (one or more Type B units connected directly to a Type A call unit) Socket (used for Patient Cord-Set and always activates a normal Patient Call) 20

22 Setting Call Types DIP Switches 6, 7 & 8 (Continue) The available Call Type combinations are defined in the table below: DIP-Switch Settings Main (Type A) Call/Alarm Source and associated Call Types Remote Socket (Type B) (Cord-Set) Nurse Present Nurse Present Patient Call Nurse Present Patient Call Patient Call Nurse Present Wet Area Patient Call 0-0 Nurse Present Staff Assist Patient Call Nurse Present Emergency Patient Call Patient Call Nurse Present Patient Call Patient Call Patient Call Patient Call Patient Call Wet Area Patient Call Patient Call Staff Assist Patient Call Patient Call Emergency Patient Call Nurse Present - Patient Call Patient Call - Patient Call Wet Area - Patient Call Staff Assist - Patient Call Emergency - Patient Call These five configurations allow Common Corridor Lamp connections. (See Common Corridor Wiring Diagram.) Staff Assist Nurse Present Patient Call Staff Assist Patient Call Patient Call Staff Assist Wet Area Patient Call Staff Assist Staff Assist Patient Call Staff Assist Emergency Patient Call Emergency Nurse Present n/a Emergency Patient Call n/a Emergency Wet Area n/a Emergency Staff Assist n/a Emergency Emergency n/a Escalate Escalate Patient Call Escalation Call Type Setting jumpers 6, 7, & 8 on a Call point to ( ) respectively assigns the call point to be of Type Escalation. The first press of the Alarm button will cause the Cancel button to flash once, and send a call of Type Patient Call, a second press will cause the Cancel button to flash twice and will send a call of Type Staff Assist and a Third (and final) press will cause the Cancel button to flash three times and send a call of Type Emergency. Any Corridor lights attached to the Call point will reflect the state of the Call point i.e. 2 presses will flash Amber, 3 presses will flash Red. Calls are displayed on over-door lamps in order of Priority (Emergency, Staff Assist, Wet Area, Patient Call followed by Nurse Present). Socket is not available with Emergency Call Points in regulation with Hard-Wired Nurse Call Speciation AS

23 Setting Call Points Numbers (Client Codes) DIP-Switches 1 to 5 By setting the 3-way DIP-Switches 1 to 5, each Call unit can be allocated a Call Point Number that is used to determine the SmartLink Client Code. The appropriate DIP-Switch settings are defined in the table below: DIP-Switch Settings DIP-Switch Settings DIP-Switch Settings Call Call Call Point Point Point

24 Setting Call Points Numbers Continued DIP-Switch Settings DIP-Switch Settings DIP-Switch Settings Call Call Call Point Point Point

25 16. SMARTWATCH XP SOFTWARE SETUP Setting up the Port 1. Ensure you are logged on as Maintenance User 2. Select Ports from the Interfaces Menu. 3. Click New and type SmartWire Nurse Call as the Name. 4. Select SmartLink Receiver as the Protocol. 5. Select Direct RS-232 as the Type. 6. Select an available COM for the Serial Port and ensuring your Master Unit is connected to that port. 7. Select <None> as the Flow control. 8. Click Save, then Refresh and Close when completed. 24

26 9. Now select SmartLink Receiver and then Ports from the Interfaces Menu. 10. Click/Highlight SmartWire Nurse Call. 11. Select 9600 as the Baud rate, Data=8, Parity=None & Stop= Click Save and then Close when completed. System Client Code (Client Code 9917) Low supply voltage conditions are reported to the SmartLink Monitoring software on Client Code To save confusion it is recommended that the system administrator enters a new Client with code 9917 named SmartWire Master Interface. All additional clients entered added onto the SmartWire MKII bus must be replicated on the monitoring software, otherwise the client will be listed as <unknown>. 25

27 Setting up SmartLink Clients The records of individual clients are stored in the following window. Simply click Clients (or SmartLink Clients under the Edit Menu). IMPORTANT: The Name and Code fields are the minimum required to add a SmartLink Client. Each Client must have a unique Code between 0001 to Some Codes are fixed in to various other SmartLink Products and Systems. For SmartWire Nurse Call System, simply start at 7001 or consult your hardware manuals for further details. 1. To add a new SmartLink Client, simply click New. 2. Enter a Name to appear on the main Clients list and on the client alarms screen. 3. Enter a Client Code starting at 7001 as the unique four digit identifier for each selected client. 4. Enter the Phone number for the location if applicable. Leave this field blank for systems that do not require telephone number. 5. Enter the Address for the location if applicable. Leave this field blank for systems that do not require an Address. 6. Select the Recipient to which messages regarding Call/Emergency activations and Cancels will be sent if applicable. 7. Select the Maintenance to which system and maintenance messages eg. Low Battery, Mains Fail, etc (see SmartLink Call Types) are sent. 8. Check the Expect Check In box and enter a period in days if the client equipment is required to call in within the specified period (primarily for Medi-Call Dialer units only). 9. Use Notes to annotate pertinent facts regarding this Client. 10. Enter a description for each of the Zone Fields. Zone (or Channel) names should match the actual SmartLink Devices. For example, Medi-Call Diallers and SmartLine Wireless Systems can handle up to 8 separate wireless devices which can be programmed to report on each of the available zones. 11. Click Save and then Close when completed. 26

28 APPENDIX 1 - Cabling Guidelines System wiring guidelines based on current consumption The following tables have been provided to assist installers in determining max cable lengths and components per single run of cable that is part of a larger star configuration. The figures found in the tables have been calculated for 6Cx14x0.2 cable, using the extra 2 cores to double up on the supply lines. The use of any other type of cable or configuration will void these figures. Table 1 - Component Current Consumption SmartWire MKII Component Standby Current (ma) Alarm Current (ma) Current Consumption Relative to Type A Type A Call Point < 4 6 Type B Call Point 1 2 1/3 of a Type A call point Patient Bed Cord 1 2 1/3 of a Type A call point Corridor Light (steady) Nurse Presence, Patient Call times a Type A call point Corridor Light (flashing) Staff Assist, Emergency times a Type A call point Sounder (1 beep/second) times a Type A call point Display Controller < times a Type A call point Master <30 30 N/A 1. Call Points placed at end of Single Cable Run (All call points are connected at end of the cable run, no successive call points) All calculations are based on the Type A call point. These may be substituted by any other component listed in the above table (taking into account the relative consumption). Table 2 - Call points placed at end of cable run 27 Distance (m) Max Number of Type A call points at end of cable run

29 2. Successive addition of Call Points on Single Cable Run (Call points are connected at every 100 m intervals) Table 3 Two Type A call points placed every 100 metres Distance (m) Voltage (V) Number of call points Current used (ma) Current available (ma) Table 4 Five Type A call points placed every 100 metres Distance (m) Voltage (V) Number of call points Current used (ma) Current available (ma) Table 5 - Ten Type A call points placed every 100 metres Distance (m) Voltage (V) Number of call points Current used (ma) Current available (ma) Table 6 - Twenty Type A call points placed every 100 metres Distance (m) Voltage (V) Number of call points Current used (ma) Current available (ma) Table 7 - Forty Type A call points placed every 100 metres Distance (m) Voltage (V) Number of call points Current used (ma) Current available (ma)

30 System Configurations and Limitations The following are limitations based on 3 different configurations. The first configuration puts emphasis on large area coverage with minimum call points whereas the last configuration puts emphasis on small area coverage with max number of call points. Depending on your requirements you may choose either of the configurations. Table 8 - Large Area Coverage with Minimum Call Points SmartWire MKII Component Max quantity per entire star configured bus Type A Call Point 50 Sounder (1 beep/second) 20 Display Controller 5 Max TOTAL cable run (metres) 4000 Table 9 - Medium Area Coverage SmartWire MKII Component Max quantity per entire star configured bus Type A Call Point 120 Sounder (1 beep/second) 30 Display Controller 5 Max TOTAL cable run (metres) 3200 Table 10 - Small Area Coverage with Maximum Call Points SmartWire MKII Component Max quantity per entire star configured bus Type A Call Point 240 Sounder (1 beep/second) 40 Display Controller 10 Max TOTAL cable run (metres) 1600 Line Boosters In situations where the maximum component count or cable run has been exceeded, Line Boosters may be used to reduce the effects of system capacitance on bus communication by reducing signal rise times. For further information please contact SmartLink International Pty Ltd. Cabling Example Requirement: Medium sized hospital requires a hard wired nurse call system for its existing 90 beds. The installation also requires 4 LED displays, and 20 sounders. The installation should also be able to cater for an additional 30 beds in its new wing that will be located approx 800m from the master unit. Solution: Taking into consideration the future expansion and the number of call points required we would use figures from Table 9 Medium Area coverage. This will enable us to have a total of 120 call points, with 30 sounders, 5 display controllers and a total cable run of 3200 metres. Assuming that on average 20 call points would be required every 100 metres for the existing wings, and using figures from Table 6, we would require two runs of 200m cable. For the proposed new wing that will be located 800 meters away, we would use 3 separate runs of 800m cable each supporting 10 call points (figures taken from Table 2). So the overall total cable run would be 2800m, which is well within specification. 29

31 APPENDIX 2 Calculating Backup Battery Requirements Batteries must be installed in accordance with the manufacturer s recommendations. The Australian Standards for Hard-Wired Patient Alarm Systems states: Battery backup shall be sufficient to provide a minimum of 10 min operation with the capacity to supply an additional 50% of the power requirements with 25% of the loops operative. Rechargeable batteries shall be capable of being fully recharged from a fully discharged condition within 24h. Each battery container shall be legibly and durably marked with the month and year of installations, e.g. 1/98 meaning January Current Consumption Figures per Component We suggest that you use the following allowances when calculating battery capacity: SmartWire MKII Component Standby Current (ma) Alarm Current (ma) Type A Call Point < 4 6 Type B Call Point 1 2 Patient Bed Cord 1 2 Corridor Light (steady) Nurse Presence, Patient Call 0 30 Corridor Light (flashing) Staff Assist, Emergency 0 15 Sounder (1 beep/second) 1 10 Display Controller <30 30 Master <30 30 Battery Calculation Example For example, if we have a system with 50 Type A call points (25 Patient Call and 25 Emergency) with each having corridor lamps, 30 bed side plugs, 40 Type B call points, 10 sounders, 5 display controllers, and 1 master then our total max current consumption in alarm state shall be: Type A call points: 25 x 6 = 150 Steady Patient Call Corridor Lights 25 x 30 = 750 Flashing Emergency Corridor Lights 25 x 15 = 375 Bed side plugs 30 x 2 = 60 Type B call points 40 x 2 = 80 Sounders 10 x 10 = 100 Display controllers 5 x 30 = 150 Master controller 1 x 30 = 30 TOTAL Current 1695 ma Using a standard 12V Lead-acid battery with a 7 Ah capacity will power the entire system for approx 4 hours in a worst case scenario where all call points are in alarm state. This would be more than enough to satisfy the requirements of the Australian Standards for Hard Wired Patient Alarm Systems. 30

32 APPENDIX 3 RS232 to RS485 Converter for LED Display Part Number Maximum cable length (RS485) Maximum cable length (RS232) Max Displays per Converter Power Supply Dimensions Weight Temperature range RS232-LED 1200 m 15 m 32 displays External regulated supply (6 15 V DC, 50mA) 63mm (h) x 56mm (w) x 16 mm (d) 40 grams -20 to 60 degrees Celsius (5% to 95% humidity) Powering the Converter The converter may be powered off the same supply as the SmartWire system provided it satisfies the requirements. Cabling Cabling between the converter and the LED Display should be done using a single twisted pair. External Connections (RS232 side) Pin 1 Cable shield Pin 2 Tx (in) Pin 7 Ground (RS485 side) Pin 1 Cable shield Pin 7 GND Pin 18 (B) RS485 Pin 19 (A) RS485 Pin 20 +V supply 31

33 Internal Connections Internal Link Settings Internal Link Settings of the RS232 to RS485 Converter Link No. Description Setting LK1 Auto/Manual Link AUTO LK2 Echo On/Off Link ON LK3 RS422/RS485 Link RS485 LK4 Low/High Link High LK5 RTS/DTR RTS LK6 CTS No Link LK7 CD/DTR No Link 32

34 Appendix 4 LED Displays The SmartLite display panel features a multi-colour LED display, for communicating messages of different priorities. Particularly suited to light commercial environments it comes complete with mounting hardware to suspend the unit from ceilings. It also features an integrated audio amplifier and speaker built into the unit for distributing alert sounds. Communication with the device is via serial cable, which may operate in either RS232 or RS485 modes. Power supply Supplied as standard is a switch mode earthed supply with an output rating of 3.5A. Current Consumption Normal use: 400 ma, Heavy use: 1200 ma, Standby: 50mA Note for a Double Sided Display these figures are approximately double. Connection is via a DC jack (2.1mm pin). Polarity is +ve on the pin and ground on the shell. Audio A single channel linear audio amplifier delivers 0.5W RMS into a 57 mm speaker. Connection is via a 3.5mm mono jack. The input impedance is 470 ohms; the input level should be between 2 to 8 Vp-p. A volume control is provided on the back of the display. For long distances, shielded cable is recommended. Data Connection The SmartLite display panel provides connections for RS232 and RS485 serial data. Data format is 9600,N,8,1. RS485 requires connection to A, B, and ground, RS232 requires connection only to Data and Ground. If the SmartLite is being connected to a Remote Display Pocsag Decoder using RS232, a straight through 6-way CAT5 cable may be used. When hard wiring long distances in RS485 mode, then the recommended is CAT5 shielded. SmartLite Display Data Connections (View looking into socket) Ground B (RS-485) Data (RS-232) B (RS-485) A (RS-485) A (RS-485) Weight 1.9 Kg (single sided) 2.7 kg (double sided) Dimensions (L x W x H): 727 mm x 37 mm x 94 mm (single sided) 727 mm x 50 mm x 94 mm (double sided) 33

35 Appendix 5 - Autotex AM 34

36 Autotex AM FAQ Continued What is a Microbe Microbes are single celled organisms that are too small to be seen with the naked eye and must be viewed through a microscope. The naked eye is only able to detect the presence of microbes once they have multiplied to the hundreds of thousands. And under the right conditions, some microbes can double in number every minutes. Types of microbes include bacteria, algae and fungi or mold. Is Autotex AM with Microban antimicrobial technology safe? Yes - Microban has undergone extensive independent laboratory testing and has a long history of safe use. Will scratching or scuffing the film diminish the effectiveness of the AM function No - Because the antimicrobial agent is evenly distributed throughout the texture, its effectiveness is constant even if the surface is damaged. Do we still have to clean the film Yes -Autotex AM provides continuous antimicrobial protection however if dirt or residue build up on the surface bacteria can grow on top of the build up. Normal cleaning practices should therefore be maintained. Does the anti microbial protection begin working immediately? The antimicrobial function of Autotex AM begins to work as soon as the microorganism comes into contact with the product surface. It then works continuously to maintain a consistently lower bio-burden than would be expected on a product without antimicrobial protection. Under the right conditions, microbes on an untreated surface can double every 20 minutes! Does the antimicrobial leach or migrate from the film? No - The antimicrobial is permanently locked into the texture and can not leach or migrate from the film. What is the Microban Certification Programme? The Microban brand promise to consumers is to deliver continuous, durable and effective antimicrobial protection. To ensure this is fulfilled, Autotex AM has been subjected to extensive testing prior to commercialization and is manufactured under stringent quality assurance guide lines in addition film samples from every production making undergo a rigorous testing programme carried out by LawLabs a leading, independent inspection body who are responsible for overseeing and regulating the Microban Certification Programme. Does the use of antimicrobials cause resistant strains of microorganisms? No - After more than 30 years of use in numerous consumer, industrial and medical applications around the world, there has been no evidence of resistant strain development. Will the film irritate, is it sensitizing? No - Autotex AM will not irritate skin and is not sensitizing. Is Autotex AM approved for use in food contact applications? No. What cleaning products can be used with Autotex AM? As far as we are certain, normal cleaning products can be safely used with Autotex with Microban. However, complete compatibility with all cleaning products can not be guaranteed and so in cases of doubt you should contact your local Autotype representative for further information. 35

37 Appendix 6 Radio Nurse Call Receiver Installation MODES OF OPERATION The Radio Nurse Call Receiver can be programmed to operate in two different modes: 1. Any Key Operation Mode, where the Radio Nurse Call Receiver will accept signals from any SmartLink radio keys or, 2. Programmed Key Operation Mode, where the SmartLink radio keys (maximum of 40) must be programmed into the Radio Nurse Call Receiver before being accepted. ATTENTION: Pressing the CANCEL button on any radio key will cancel any active alarms that may have been activated by another radio key. This is true in either mode of operation whether it be Any Key or Programmed Key modes. Any Key Operation This operation mode allows the radio nurse call to operate with any Smartlink radio keys. To enable this mode remove any links on the terminal block between terminals Z1 and 0V. Refer to PCB layout shown below. Programmed Key Operation This operation mode allows the radio nurse call to operate with programmed Smartlink radio keys only. To enable this mode place a link on the terminal block between terminals Z1 and 0V. Refer to PCB layout shown below. Accepted Wireless SmartLink Devices PCB Layout Wireless Call Points/Pendants Universal waterproof pendants Wireless Wall mount call points Box style pendants Wireless Devices Wireless smoke detector (Ver 1.2 or higher) 36

38 Programming Radio Keys into Receiver To Program the Radio Keys into the Receiver do the following: 1. Link the program mode shunt J11, the radio receiver will then be in learn mode, LED will double flash once. 2. Activate the radio key that will operate radio nurse call. The LED will fast flash for each radio message and long flash on the third message to acknowledge the radio key is programmed. 3. Radio receiver is now programmed. 4. To program a second device, repeat above steps (up to 40 radio keys can be programmed) 5. Programming a 41st device will erase the 40th device so that there are no more than 40 devices programmed. Removing Radio Keys from Receiver To erase all devices, activate any pre-programmed radio key 5 times in program mode with the erase pin (pin 5 of J5) linked to program mode pin. LED will fast flash continuously to indicate successful erase operation. LED Operation Normal Mode Idle Alarm Device Alarm, PIR or Reed Switch LED State Fast flash every second Steady ON for the duration of the alarm Momentary Program Mode LED State Activation of a radio key Double fast flash once 1 st and 2 nd radio messages 10 ms fast flash 3 rd radio message 2 sec long flash A programmed key message 2 sec long flash Specifications Size Weight Operating Voltage Quiescent Current Alarm Current Frequency Radio Inputs 75 x 115 x 20 mm 70 grams 7 16 Volts DC 8 ma 16 ma MHz 24 or 56 bit ON, OFF, PANIC 37

39 Notes Call Point Number Description Date 38

40 Call Point Number Description Date 39

41 Call Point Number Description Date 40

42 Call Point Number Description Date 41

43 Call Point Number Description Date 42

44 Call Point Number Description Date 43

45 Call Point Number Description Date 44

46 Copyright SmartLink International Pty Ltd March 2009 Level 1, New Street, Brighton VIC 3186 AUSTRALIA Tel: Fax: smartlink@smartlink.com.au Web Site: To the best of our knowledge, the information contained in this manual is correct at the time of print. SmartLink International Pty Ltd reserve the right to make changes to the features and specifications at any time without prior notice in the course of product development. 45

SMARTWALK DEMENTIA WANDERING SYSTEM

SMARTWALK DEMENTIA WANDERING SYSTEM A division of NESS CORPORATION PTY LTD SMARTWALK DEMENTIA WANDERING SYSTEM SWD Door Responder SWD Resonator SWD-PET (Sold Separately) SWD-PET-BAND (Sold Separately) INSTALLATION MANUAL 1. CONTENTS 1. CONTENTS...1

More information

Wireless Call Point ( )

Wireless Call Point ( ) Wireless Call Point (100-821) INSTALLATION MANUAL Wireless Call Point Installation Manual Rev2.1 TABLE OF CONTENTS 1. Introduction... 2 FEATURES:...2 2. Normal Operation... 3 3. LED Indicator...3 4. Physical

More information

A1UL PERS. Personal Emergency Response System. For Technical Support Please Contact Your Service Provider Or Distributor

A1UL PERS. Personal Emergency Response System. For Technical Support Please Contact Your Service Provider Or Distributor A1UL PERS Personal Emergency Response System TABLE OF CONTENTS 1. READ THIS FIRST... 1 2. SYSTEM OVERVIEW.. 1 3. COMPONENTS 2 4. UNIT OPERATION! Standby Mode.. 3! Emergency Activation. 3! Answering Incoming

More information

HRX Technical Manual. Version 1.2

HRX Technical Manual. Version 1.2 HRX 5000 Technical Manual Version 1.2 Contents: Specification...2 Connectors...5 RS-485 Network Connectors (J6 and J7)...5 RS-232 to Printer (J19)...6 RS-232 to PC (J8)...7 TCP/IP...8 Power (J21)...9 Fire

More information

MEDI-CALL UNIT INSTALLATION MANUAL. Medi-Call V2.0 - V2.7 Installation Manual

MEDI-CALL UNIT INSTALLATION MANUAL. Medi-Call V2.0 - V2.7 Installation Manual MEDI-CALL UNIT INSTALLATION MANUAL Medi-Call V2.0 - V2.7 Installation Manual Copyright SmartLink International Pty Ltd February 2006 475 Nepean Highway, Brighton VIC 3186 Australia Telephone: +61 3 9596

More information

User Guide. HTM Nurse Call. In the event of requiring assistance, please contact your Installer/Supplier.

User Guide. HTM Nurse Call. In the event of requiring assistance, please contact your Installer/Supplier. HTM 08-03 Nurse Call User Guide In the event of requiring assistance, please contact your Installer/Supplier. Alarm Radio Monitoring Ltd Brunel Road, Leominster, Herefordshire. HR6 0LX tel: 01568 610 016

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

Power Wave. 8 Zone Control Communicator. Crow Electronic Engineering P/L. Ver:8.54. Installation & Programming Guide.

Power Wave. 8 Zone Control Communicator. Crow Electronic Engineering P/L. Ver:8.54. Installation & Programming Guide. Power Wave 8 8 Zone Control Communicator Crow Electronic Engineering P/L Ver:8.54 Installation & Programming Guide 8 November 2000 Crow ( Aust ) Electronic Engineering Pty Ltd Corporate Head Office: 429

More information

Eclipse Nursecall Systems Ltd. Clipper Plus & Clipper ID. Document V.2.1b (Basic) ENS. Freedom Through Technology

Eclipse Nursecall Systems Ltd. Clipper Plus & Clipper ID. Document V.2.1b (Basic) ENS. Freedom Through Technology Ltd. Clipper Plus & Clipper ID Document V..b (Basic) ENS Freedom Through Technology Contents Terms of the document... 3 Introduction... 3 Network and wiring... Global Wiring architecture... Power... 5

More information

MEDI-MINDER USER MANUAL

MEDI-MINDER USER MANUAL MEDI-MINDER USER MANUAL TABLE OF CONTENTS TABLE OF CONTENTS... 1 INTRODUCTION... 1 SMARTLINK FEATURES... 2 USING SMARTLINK... 3 SPECIAL FUNCTIONS... 5 DISPLAYS AND WARNINGS... 6 SPECIFICATIONS... 7 INTRODUCTION

More information

PERS-3600 PERSONAL EMERGENCY REPORTING SYSTEM INSTALLATION & OPERATION INSTRUCTIONS

PERS-3600 PERSONAL EMERGENCY REPORTING SYSTEM INSTALLATION & OPERATION INSTRUCTIONS PERS-600 PERSONAL EMERGENCY REPORTING SYSTEM BY BY INSTALLATION & OPERATION INSTRUCTIONS (760) 8-7000 USA & Canada (800) -587 & (800) 9-0 Toll Free FAX (800) 68-0 www.linearcorp.com CONTENTS CONTROL AREA

More information

OPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL

OPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL ap15_2manual04/22/13 Page 1 4/22/2013 1 Serial Number : Option: OPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL Micro Seven, Inc. 1095-K N.E. 25th Hillsboro, OR 97124 U.S.A. phone: 503-693-6982

More information

X64 Wireless Training

X64 Wireless Training X64 Wireless Training IDS Contents 1 Contents Features 3 Wireless Hardware 4 IDS & Duevi integration PCB 5 LED operation 5 Wireless Device Hardware setup 6 Location 260 7 LED Keypad Instructions 7 Adding

More information

Power Wave Zone Alarm Panel V8.5. Installation Manual

Power Wave Zone Alarm Panel V8.5. Installation Manual Power Wave - 8 8 Zone Alarm Panel V8.5 Installation Manual 7 December 2001 Crow (Aust) Electronic Engineering Pty Ltd Corporate Head Office: 429 Nepean Hwy, Brighton East, Vic., 3187 Australia Phone: +61

More information

Simplex Panel Interface Guide

Simplex Panel Interface Guide Simplex Panel Interface Guide February 2016 SATEON Software Integrations Simplex Panel Interface Guide Issue 1.0, released February 2016 Disclaimer Copyright 2016, Grosvenor Technology. All rights reserved.

More information

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment

More information

CORPORATION PTY LTD MEDI-LINK

CORPORATION PTY LTD MEDI-LINK division of NESS CORPORTION PTY LTD MEDI-LINK USER MNUL Medi-Link User Manual V1.08 division of NESS CORPORTION PTY LTD Copyright SmartLink International October 2011 Unit 4/56 Norcal Rd, Nunawading VIC

More information

P2267 NETWORK INTERFACE

P2267 NETWORK INTERFACE P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61

More information

Alarm Control Panel WIC-16Z4P WIC-5Z2P. Installation & Operation User Manual

Alarm Control Panel WIC-16Z4P WIC-5Z2P. Installation & Operation User Manual WIC-16Z4P WIC-5Z2P Installation & Operation User Manual Page : 1/34 INDEX # Function Page 1 Abort Current Communication and Clear Reporting Queue (*59) 13 2 Abort Current Communications (*59) 10 3 Account

More information

CC408. Quick Reference Guide Solution 880

CC408. Quick Reference Guide Solution 880 CC408 EN Quick Reference Guide Solution 880 CC408 Quick Reference Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems Pty Ltd ( Bosch

More information

(Updated Defaults) (Covers Ver: 8.64 and above)

(Updated Defaults) (Covers Ver: 8.64 and above) Power Wave - 8 8 Zone Alarm Panel V8.71 / 8.72 (Updated Defaults) (Covers Ver: 8.64 and above) Installation Manual 10-December-2003 Crow (Aust) Electronic Engineering Pty Ltd Corporate Head Office: 429

More information

HRX3000. Technical Manual

HRX3000. Technical Manual HRX3000 Technical Manual Contents: Specification...2 Connectors...3 Power (J21)...3 RS-485 Network Connectors (J6 and J7)...4 RS-232 to PC (J8)...5 Printer and Fire Alarm Panel (J19)...6 TCP/IP...8 Modem

More information

ADE Gen4. Speech Dialler Engineering Information. Description. Features

ADE Gen4. Speech Dialler Engineering Information. Description. Features ADE Gen4 Speech Dialler Engineering Information Description The Informa is a Speech Dialler for use with intruder alarm systems. When the control panel recognises an alarm it triggers the Informa. The

More information

Contents. Glossary

Contents. Glossary Contents Glossary ------------------------------------------------------------------------------------------------------ 6 1. Introduction to the IDS 1632 -------------------------------------------------------------

More information

EC-P Zone Intruder Alarm System

EC-P Zone Intruder Alarm System EC-P10 10-20 Zone Intruder Alarm System Installation Manual Contents 1. System Overview... 4 System Configuration... 4 Control Panel... 5 Remote Keypads... 5 EC-LED Remote Keypad... 5 EC-LCD Remote Keypad...

More information

600 Range Dialer Installation Manual. Version 1.0

600 Range Dialer Installation Manual. Version 1.0 600 Range Dialer Installation Manual Version 1.0 The information contained is supplied without liability for any errors or omissions. No part may be reproduced or used except as authorised by contract

More information

D3 Wireless temperature alarm & monitoring system family. tek-troniks

D3 Wireless temperature alarm & monitoring system family. tek-troniks D3 Wireless temperature alarm & monitoring system family tek-troniks D3 Wireless temperature alarm & monitoring system family No server or dedicated pc No ongoing cloud costs or licencing fees. Fully web

More information

Fratech Multipath-IP

Fratech Multipath-IP Rev 2.0 (May 2013) Installer Manual 1 Current Part Numbers: Fratech Multipath-IP E-Link STU PCB & Accessory Kit only In Metal Enclosure with Power Supply 998325-PK 998325-XS Installer Manual This document

More information

ERS-3600B. PERS-3600B Personal Emergency Reporting System

ERS-3600B. PERS-3600B Personal Emergency Reporting System PERS-3600B Personal Emergency Reporting System ERS-3600B A Complete Emergency System For Comprehensive Care The Linear PERS-3600B includes a built-in speakerphone and reminder message capability, providing

More information

Installation & Programming Guide

Installation & Programming Guide Alert Version 8 Zone Control Arrowhead Alarm Products Ltd Installation & Programming Guide Proudly Designed and Manufactured in New Zealand Arrowhead Alarm Products Ltd PHONE: (09) 579 7506 FAX: (09) 579

More information

Voice Board. Installation and Programming Guide. Runner 4/8,PowerWave 4/8/16 &, Elite64. Add-on Board For Storing Recorded Voice Messages

Voice Board. Installation and Programming Guide. Runner 4/8,PowerWave 4/8/16 &, Elite64. Add-on Board For Storing Recorded Voice Messages ELECTRONIC ENGINEERING LTD. Voice Board Runner 4/8,PowerWave 4/8/16 &, Elite64 Add-on Board For Storing Recorded Voice Messages And listen-in. Installation and Programming Guide. P/N 7101372 Rev. C V.K

More information

TYDOM 315. * _Rev.2* GSM domotics transmitter. 1. Presentation

TYDOM 315. * _Rev.2* GSM domotics transmitter. 1. Presentation TYDOM 5 GSM domotics transmitter ) Présentation. Presentation Delta Dore hereby declares that the equipment complies with the essential requirements and other relevant provisions of the R&TTE Directive

More information

Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts

Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS Feature Charts Control Panels FEATURE CHART LYNX Plus (L3000) (Supported Feature) (Not Supported) N/A (Not Applicable) LYNX Touch (L5210)

More information

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual Revision 1.03 8 November 2013 JVA Technologies Ethernet General Purpose IO Technical Manual www.jva-fence.com.au Table of Contents INTRODUCTION...3 Scope and Purpose...3 Glossary...3 SPECIFICATIONS...4

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

Pipo Communications. Model ST-888. DTMF ANI/ENI Display Decoder

Pipo Communications. Model ST-888. DTMF ANI/ENI Display Decoder Pipo Communications Model ST-888 DTMF ANI/ENI Display Decoder 1516 Cassil Place Hollywood, California 90028-7106 Phone: 323-466-5444 Fax: 323-466-1520 www.pipo.cc Manual # 68-9888 May 1, 2002 Rev. 5/02

More information

80 CHANNELS WIRELESS RECEIVER WITH LCD DISPLAY M1.1.1-Hx.x-F1.1-ENG [AN] [SPV] MADE IN ITALY INSTALLATION AND USE MANUAL

80 CHANNELS WIRELESS RECEIVER WITH LCD DISPLAY M1.1.1-Hx.x-F1.1-ENG [AN] [SPV] MADE IN ITALY INSTALLATION AND USE MANUAL RX808-LCD 80 CHANNELS WIRELESS RECEIVER WITH LCD DISPLAY 14.12-M1.1.1-Hx.x-F1.1-ENG [AN] [SPV] MADE IN ITALY INSTALLATION AND USE MANUAL WARNINGS Installation: This device must be installed only by qualified

More information

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.

The system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices. FireCell Radio Hub Fully addressable Wireless activation Third party approved (EN54) 2-way radio communication Loop powered Diagnostics port Range in excess of 150 metres Overview The model FCX-500-001

More information

Preface. Thank you for purchasing our GSM Security Alarm System ( The System )! The System will keep your home and property safe around the clock.

Preface. Thank you for purchasing our GSM Security Alarm System ( The System )! The System will keep your home and property safe around the clock. Preface Thank you for purchasing our GSM Security Alarm System ( The System )! The System will keep your home and property safe around the clock. The GSM Security Alarm ( The Alarm ) adopts the most advanced

More information

NESS 5000 SERIES DIALLER

NESS 5000 SERIES DIALLER NESS 5000 SERIES DIALLER INSTALLATION MANUAL This manual is designed to provide the installation instructions on the NESS SECURITY PRODUCT'S 5000 SERIES Dialler. For complete details on the warranty or

More information

Controllers. Centralization of Access Control Devices Made Easy. Installer Guide

Controllers. Centralization of Access Control Devices Made Easy. Installer Guide Controllers Centralization of Access Control Devices Made Easy Installer Guide CONTENTS 1 INTRODUCTION 3 The Overview of Hardware 5 The Overview of Installation & Communications 7 Installations with door

More information

installation & operation manual

installation & operation manual installation & operation manual TABLE OF CONTENTS INTRODUCTION... 2 FEATURES... 2 PROGRAMMING CONTACT ID... 3 INSTALLATION... 3 OPENING THE HAWK COVER... 3 POWER SUPPLY... 5 CHECK AC... 5 DRY CONTACTS

More information

V1.0. Smart Home Alarm System. User Manual. APP download via QR Code scanning. Please read the manual carefully before using.

V1.0. Smart Home Alarm System. User Manual. APP download via QR Code scanning. Please read the manual carefully before using. V1.0 Smart Home Alarm System User Manual APP download via QR Code scanning Please read the manual carefully before using. Content FUNCTION PROFILE 2 THE SCHEMATIC GRAPH OF HOST 3 PROCESS OF BOOTING 6 OPERATION

More information

SMS8 Alarm Control Panel

SMS8 Alarm Control Panel SMS8 Alarm Control Panel 8 Zone Alarm Control Panel with LCD Keypad, Inbuilt Dialler for Back to Base Monitoring and SMS Messaging. Easy Operation Dialler SMS Messaging I n s t r u c t i o n s N517 Code

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

GLOBAL. InstallatIon & operation manual

GLOBAL. InstallatIon & operation manual InstallatIon & operation manual INDEX 1. INTRODUCTION... 5 2. FEATURES AND FUNCTIONS 2.1 Reporting Options... 2.2 Interfaces... 2.3 Programming... 2.4 Indicators and Controls...... 6 6 6 6 6 3. INSTALLATION...

More information

Security System. User s Guide for the Text Command Center

Security System. User s Guide for the Text Command Center User s Guide for the Text Command Center MY ALARM COMPANY IS: CALL BEFORE TEST: THIS SECURITY SYSTEM IS CONNECTED TO TELEPHONE NUMBER: THE SECURITY CONTROL PANEL IS CONNECTED TO THE PHONE JACK LOCATED:

More information

Alarm Panel [ PRELIMINARY HARDWARE MANUAL ] USER MANUAL. v1.0a. May 7, 2008 D-OC-UM

Alarm Panel [ PRELIMINARY HARDWARE MANUAL ] USER MANUAL. v1.0a. May 7, 2008 D-OC-UM Alarm Panel USER MANUAL [ PRELIMINARY HARDWARE MANUAL ] Visit our website at www.dpstelecom.com for the latest PDF manual and FAQs. May 7, 2008 D-OC-UM085.07010 v1.0a Revision History April 28, 2008 May

More information

T4000 Security Communicator

T4000 Security Communicator Inner Range T4000 Security Communicator 1 T4000 Security Communicator by Inner Range P/N: 998530 / 998530NZ 998530LT (Lite Version) Installation & Operation Manual. Rev: 1.5 Inner Range Pty. Ltd. www.innerrange.com

More information

MEDI-LINK USER MANUAL

MEDI-LINK USER MANUAL MEDI-LINK USER MNUL Medi-Link User Manual Rev1.2 division of NESS CORPORTION PTY LTD November 2015 Unit 4/56 Norcal Rd, Nunawading VIC 3131 ustralia Tel: +61 3 9875 6400 Facsimile: +61 3 9875 6422 Email:

More information

Version 1.03 January-2002 USER S MANUAL

Version 1.03 January-2002 USER S MANUAL Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...

More information

Solution 880 Operators Manual. Issue 1.00

Solution 880 Operators Manual. Issue 1.00 Solution 880 Operators Manual Issue 1.00 Solution 880 Operators Manual Copyright 1998 by, SYDNEY, AUSTRALIA Document Part Number MA408O Document ISSUE 1.00 Printed 15 June 1998 This documentation is provided

More information

PRODUCT CATALOGUE. Cape Town 18 Darter Road Blue Water Estate Kommetjie. Gauteng 245 Louis Botha Avenue Orchards Johannesburg

PRODUCT CATALOGUE.   Cape Town 18 Darter Road Blue Water Estate Kommetjie. Gauteng 245 Louis Botha Avenue Orchards Johannesburg PRODUCT CATALOGUE Cape Town 18 Darter Road Blue Water Estate Kommetjie Luke Fowles - 076 161 8124 luke@providenttech.co.za Frank Fowles - 082 445 1541 frank@providenttech.co.za www.providenttech.co.za

More information

TRINITY DUO IP HARDWIRED AND WIRELESS ALL-IN- ONE

TRINITY DUO IP HARDWIRED AND WIRELESS ALL-IN- ONE TRINITY DUO IP HARDWIRED AND WIRELESS ALL-IN- ONE What is Trinity Duo IP? Trinity Duo IP is the latest instalment to the Advance Call range. It is a 64 Input, 24 output Nurse Call controller, and 128 Wireless

More information

1. Introduction. 2. Product overview

1. Introduction. 2. Product overview 1. Introduction The AG400011 GSM Alarm panel is a control panel that is compatible with other H-net security devices from Everspring, such as wireless sensors, remote keyfobs, tags, and keypad. With this

More information

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide Digiplex System V2.14 / V2.2ACC Control Panel Programming Guide Table of Contents Getting Started...2 What Do I Do First?...2 How Do I Program the Control Panel?...2 Single Digit Entry Method...2 Multiple

More information

MEDI-MINDER USER MANUAL

MEDI-MINDER USER MANUAL MEDI-MINDER USER MANUAL TABLE OF CONTENTS TABLE OF CONTENTS...1 INTRODUCTION...1 MEDI-MINDER FEATURES...2 PENDANTS & DETECTORS... 3 USING MEDI-MINDER... 3 DISPLAYS AND WARNINGS...5 CELLULAR SIGNAL QUALITY...

More information

DCA4. Digitally controlled Audio Matrix. Current Thinking. Product Specification March Document Number DDC DCA ACS

DCA4. Digitally controlled Audio Matrix. Current Thinking. Product Specification March Document Number DDC DCA ACS DCA4 Digitally controlled Audio Matrix Product Specification March 2002 Current Thinking Document Number DDC DCA 7001 01 ACS Introduction Voice Alarm (VA) systems are the quickest way to evacuate the public

More information

GSM Alarm System. User s Manual. Profile. MOBILE CALL GSM Alarm System

GSM Alarm System. User s Manual. Profile. MOBILE CALL GSM Alarm System MOBILE CALL GSM Alarm System GSM Alarm System System disarmed 11/26/2013 User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. CONTENTS

More information

ezone Alert System ezone is a UK designed and manufactured care alerting system unlike any other comparably priced system.

ezone Alert System ezone is a UK designed and manufactured care alerting system unlike any other comparably priced system. ezone Alert System Specialist alerting system for the healthcare industry ezone is a UK designed and manufactured care alerting system unlike any other comparably priced system. ezone is designed around

More information

PROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX

PROGRAMMING GUIDE SPECTRA CONTROL PANELS V , 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX PROGRAMMING GUIDE SPECTRA CONTROL PANELS V1.2 1725, 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX TABLE OF CONTENTS HOW DO I PROGRAM THE SYSTEM?... 4 Single Digit Data Entry Method (Hexadecimal

More information

MG5000 V2.4 MG5050 V2.4 SP5500 V2.4 SP6000 V2.4 SP7000 V2.4. Programming Guide

MG5000 V2.4 MG5050 V2.4 SP5500 V2.4 SP6000 V2.4 SP7000 V2.4. Programming Guide MG5000 V2.4 MG5050 V2.4 SP5500 V2.4 SP6000 V2.4 SP7000 V2.4 Programming Guide We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com

More information

Wander-Alarm DOORWAY SENSORS

Wander-Alarm DOORWAY SENSORS Wander-Alarm DOORWAY SENSORS Doorway Master Sensor (Part No. MB-001) Doorway Controller/Sounder (Part No. DCS-003) Bracelet (Part No. TAG-W-002) INSTALLATION MANUAL 1. CONTENTS 1. CONTENTS...1 2. EQUIPMENT

More information

DATAssure. Laboratory wireless alarm & monitoring system

DATAssure. Laboratory wireless alarm & monitoring system DATAssure Laboratory wireless alarm & monitoring system Wireless alarm & monitoring system A new monitoring generation The DATAssure wireless monitoring system is used across a broad range of market sectors

More information

SECURIT 700L PLUS ENGINEERING MANUAL

SECURIT 700L PLUS ENGINEERING MANUAL SECURIT 700L PLUS ENGINEERING MANUAL C & K Systems Ltd 13/03/97 C031-096-02 NEW ENHANCED FEATURE SET Securit 700L PLUS Engineering instructions INTRODUCTION The Securit 700L is a microprocessor intruder

More information

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68) F A 1 7 0 0 c Testing the System Battery Test When AC power is present, the FA1700C runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL The LeakMonitor alarm panel is a microprocessor controlled fully adjustable alarm system suitable for multizone

More information

Medi-Minder Guardian USER MANUAL

Medi-Minder Guardian USER MANUAL Medi-Minder Guardian USER MANUAL 1 Table of Contents TABLE OF CONTENTS...2 INTRODUCTION...2 MEDI-MINDER GUARDIAN...3 PENDANTS AND DETECTORS...4 USING MEDI-MINDER GUARDIAN... 4 DISPLAYS AND WARNINGS...6

More information

IRIS Touch Firmware Enhancements and Additions from Version to Version

IRIS Touch Firmware Enhancements and Additions from Version to Version Overview IRIS Touch Firmware Enhancements and Additions from Version 1.14.3 to Version 1.19.1 This document details enhancements to the feature set of the IRIS Touch from firmware Version 1.14.3 to Version

More information

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Page 2 of 16 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Contents 1. Introduction... 4 2. Product Features... 4 3. Package

More information

TrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description

TrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description TrueCom Building Communications Systems 5115-Series 5115-9001, -9002 Area of Rescue Communications System Description The Simplex 5115-9001 and -9002 Area of Rescue Communications System provides buildings

More information

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0 User s Guide SUB-MA7240O-0001.OG.Solution40-111.doc Created: 6/05/03 Last Updated: 23/09/03 MA7240AO-0001 Version 1.0 2 Table Of Contents User List...6 Quick Reference..7 Features...7 Keypad User's Guide...8

More information

Ethernet General Purpose

Ethernet General Purpose Ethernet General Purpose Technical Manual Revision 1.03 8 November 2013 Pakton Technologies IO PAE224 Ethernet GPIO Manual.docx Page 1 of 22 Revision 1.03 Last updated 8/11/2013 Table of Contents INTRODUCTION...3

More information

WIRELESS SOLUTIONS FOR RESIDENCES. A Group brand

WIRELESS SOLUTIONS FOR RESIDENCES. A Group brand WIRELESS SOLUTIONS FOR RESIDENCES A Group brand WIRELESS TECHNOLOGY RELIABLE AND SAFE 2 TREX Wireless call system >page 04 D-POS Wandering alarm system >page 08 WALL Wall mounted calling devices >page

More information

Inner Range FE3000S. Serial GSM Modem. P/No: INSTALLATION MANUAL

Inner Range FE3000S. Serial GSM Modem. P/No: INSTALLATION MANUAL Revision 1.0 October. 2014 1 Inner Range FE3000S Serial GSM Modem. P/No: 998306 INSTALLATION MANUAL IMPORTANT NOTE: This Installation Manual is only relevant to Serial GSM Modems utilizing the G-Link PCB.

More information

Watchguard WGAP864 User Manual

Watchguard WGAP864 User Manual Watchguard WGAP864 User Manual v1.0 Issued September 2016 1 2 Table of Contents Glossary... 5 1. Introduction to your Watchguard WGAP864... 6 2. Before Operating your Alarm System... 6 3. Understanding

More information

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV CyCLO User Guide Version 2.00 19 th December 2017 REV 2.00 1 Contents 1. Hardware... 3 1.1. Introduction... 3 1.2. Electrical Specification... 3 1.3. Board Overview... 4 1.4. Electrical Installation...

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

Quantec NURSE CALL. Nurse call system & dementia care from Channel Safety Systems

Quantec NURSE CALL. Nurse call system & dementia care from Channel Safety Systems Quantec NURSE CALL Nurse call system & dementia care from Channel Safety Systems Quantec Nurse call system Designed in conjunction with a prestigious NHS Trust, the Quantec nurse call system is widely

More information

NurseCall Main Unit F.01U V User Manual

NurseCall Main Unit F.01U V User Manual NurseCall Main Unit F.01U.252.699 V1.1 2012.01 en User Manual NurseCall Main Unit Table of Contents en 3 Table of Contents 1 Safety instructions 6 1.1 Importance of safety instructions 6 1.2 Disregarding

More information

Quick Installation Manual LED Touch Keypad Autodial Wireless Alarm System

Quick Installation Manual LED Touch Keypad Autodial Wireless Alarm System Quick Installation Manual LED Touch Keypad Autodial Wireless Alarm System By shield4u http:// (Version 20110816) A. Alarm Understanding Away Disarm Home Emergency Function Signal Interpretation Buzzer

More information

Laptop / PC Programming Manual

Laptop / PC Programming Manual Laptop / PC Programming Manual Doc. # Fire PC Program rev B 01.07 This Document is property of Evax Systems, Inc. The Evax Fire Solutions Programmer Components 2 1.0 System Setup 4 1.1 Interface Setup

More information

Secure WANDERING INSTALLATION AND USAGE GUIDE

Secure WANDERING INSTALLATION AND USAGE GUIDE Secure WANDERING system C 4 7 0 5 8 2 E 6 9 3 INSTALLATION AND USAGE GUIDE Contents 2 Installation principle 2 System description 3 Device presentation and installation 3 Secure wandering system 6 Secure

More information

CC488. Quick Reference Guide Solution Ultima 880

CC488. Quick Reference Guide Solution Ultima 880 CC488 EN Quick Reference Guide Solution Ultima 880 CC488 Quick Reference Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems Pty

More information

Installation and ZONES: Operation Manual. Model: ON STI-34108

Installation and ZONES: Operation Manual. Model: ON STI-34108 N.O. COM N.C. + 12 V - IN + 12 V - OUT 500 ma 300 ma PLUG IN ADAPTER 12 V 500mA Trigger Output 12 V 75mA N.O. COM N.C. + 12 V - IN + 12 V - OUT 500 ma 300 ma PLUG IN ADAPTER 12 V 500mA Trigger Output 12

More information

Solution-6 Operators Manual Page 1 Preface Congratulations on selecting the Solution-6 security control system for your installation. So that you can obtain the most from your unit, we suggest that you

More information

System. For a better understanding of this product, please read this user manual thoroughly before using it.

System. For a better understanding of this product, please read this user manual thoroughly before using it. GSM Alarm System User s Manual For a better understanding of this product, please read this user manual thoroughly before using it. Chapter 1. Features Chapter 2. Control Panel Introduction Chapter 3.

More information

Elite 16D Version 16 Zone Controller Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand

Elite 16D Version 16 Zone Controller Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand 6 Elite 16D Version 16 Zone Controller Arrowhead Alarm Products Ltd Operating Guide 1 Proudly Designed and Manufactured in New Zealand CONTENTS Page No. INTRODUCTION 3 About your Alarm 3 OPERATING YOUR

More information

General Purpose IO Technical Manual

General Purpose IO Technical Manual General Purpose IO Technical Manual Revision 1.06 8 November 2013 Pakton Technologies PAE222 GPIO Manual.docx Page 1 of 21 Revision 1.06 Last updated 8/11/2013 Table of Contents INTRODUCTION...3 Scope

More information

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation The most user friendly Contents Section 1 Overview of System 1.1 Kit Contents 1.2 Tools Required 1.3 System Features Security Alarm System L S 4 0 0 Section 2 Planning your Installation 2.1 Location of

More information

2G & 3G GSM Door Contact Alarm

2G & 3G GSM Door Contact Alarm 2G & 3G GSM Door Contact Alarm www.gsm-activate.co.uk MODEL RF - PIR PAGE 1 Product Information Our 2G/3G GSM Door Contact Alarm is a standalone alarm system for smaller rooms inside properties. It will

More information

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE D (OPERATION) INITIATE A DYNAMIC BATTERY TEST The system tests the back-up battery once every 24 hours. The owner can initiate a dynamic battery test at any time with the following codes while the system

More information

ACP10 & ACP50 Security Systems

ACP10 & ACP50 Security Systems ACP10 & ACP50 Security Systems System Configuration LCD Keypad LCD Keypad LED Keypad LED Keypad 4-wire Bus ACP10 & ACP50 AEX10* AEX10* AEX10* AEX10* * ACP50 Only Control Panels The ACP10 control panel

More information

RC802/ B 8E1 Modular Fiber-Optic Multiplexer (Rev. M) User Manual

RC802/ B 8E1 Modular Fiber-Optic Multiplexer (Rev. M) User Manual RC802/804-240B 8E1 Modular Fiber-Optic Multiplexer (Rev. M) User Manual Raisecom Technology Co., Ltd. (04/2005) 1. Cautions Please read the following notices carefully before installing and using the device,

More information

Solution 6+6 Wireless - AE Operators Manual ISSUE 1.10

Solution 6+6 Wireless - AE Operators Manual ISSUE 1.10 Solution 6+6 Wireless - AE Operators Manual ISSUE 1.10 Solution 6+6 Wireless - AE Operators Manual Copyright 1997 by, SYDNEY, AUSTRALIA Document Part Number MA660O Document ISSUE 1.10 Printed 02 December

More information

FW-SIREN2EXT -8/9F FW-SIREN2CP -8/9F

FW-SIREN2EXT -8/9F FW-SIREN2CP -8/9F Wireless Siren System Installation Guide FW-SIREN2EXT -8/9F FW-SIREN2CP -8/9F P/N 7101866 Rev. 04 Jan 2010 Copyright Crow Engineering Ltd. 2008 The copyright of this document is owned by Crow Engineering

More information

16 ( Ver: Installation & Programming Guide. Power Wave 16 Zone Control Communicator. Crow Electronic Engineering (Australia) Pty Ltd

16 ( Ver: Installation & Programming Guide. Power Wave 16 Zone Control Communicator. Crow Electronic Engineering (Australia) Pty Ltd Power Wave 16 Zone Control Communicator 16 ( Ver: 6.28 ) This Manual is Preliminary. Please refer to the Condensed manual for additional information Crow Electronic Engineering (Australia) Pty Ltd Installation

More information

ZITON RADIO LOOP MODULE

ZITON RADIO LOOP MODULE ZITON RADIO LOOP MODULE PROGRAMMING MANUAL Table of Contents Section Page No 1.0 INTRODUCTION...3 1.1 System Design...3 1.2 Handling Precautions...3 1.3 Packaging:...3 2.0 MENU STRUCTURE...4 2.1 Menu Structure

More information