M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014

Size: px
Start display at page:

Download "M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014"

Transcription

1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications Elena Carroll, Administrator, Technical Projects Date: July 8, 2014 Subject: NFPA 76 First Draft TC FINAL Ballot Results (F2015 Cycle) According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. 28 Members Eligible to Vote 4 Not Returned (Backstrom, Campos, Custer, Meyring) 23 Affirmative on All Revisions 1 Affirmative with Comment on one or more Revisions (Kasiski, Lang) 1 Negative on one or more Revisions (Kasiski) 0 Abstentions The attached report shows the number of affirmative, negative, and abstaining votes as well as the explanation of the vote for each first revision. There are two criteria necessary for each first revision to pass ballot: (1) simple majority and (2) affirmative 2 /3 vote. The mock examples below show how the calculations are determined. (1) Example for Simple Majority: Assuming there are 20 vote eligible committee members, 11 affirmative votes are required to pass ballot. (Sample calculation: 20 members eligible to vote 2 = = 11) (2) Example for Affirmative 2 /3: Assuming there are 20 vote eligible committee members and 1 member did not return their ballot and 2 members abstained, the number of affirmative votes required would be 12. (Sample calculation: 20 members eligble to vote 1 not returned 2 abstentions = 17 x 0.66 = = 12 ) As always please feel free to contact me if you have any questions.

2 of 126 7/8/2014 9:49 AM First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ] This standard provides requirements for fire protection of telecommunications facilities where telecommunications, including landline, cable, wireless, and satellite telecommunication services such as telephone (landline, wireless) transmission, data transmission, internet transmission, voice- /voice, voice over internet protocol (VoIP), transmission internet, data, and video transmission that are rendered to the public. Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Apr 23 12:42:22 EDT 2014 Committee Statement Committee Statement: Response Message: Ballot Results This item has passed ballot Due to changes in the industry, the scope has been modified to include additional transmission methods. 28 Eligible Voters 4 Not Returned 23 Affirmative All 1 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A.

3 Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. Affirmative with Comment Lang, Scott R. Change the word "including" to "providing" so that the sentence makes more sense. of 126 7/8/2014 9:49 AM

4 of 126 7/8/2014 9:49 AM First Revision No. 53-NFPA [ Section No ] 1.1.2* This standard shall specifically exclude small outdoor Provisions for small structures that are normally unoccupied and that house telecommunications equipment, including on-grade, walk-in cabinets, ; on-grade huts, ; cell huts, ; and controlled environmental vaults (CEVs), are provided in Chapter 11. Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Apr 23 16:35:38 EDT 2014 Committee Statement Committee Statement: See FR 55. Response Message: Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P.

5 Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. of 126 7/8/2014 9:49 AM

6 of 126 7/8/2014 9:49 AM First Revision No. 31-NFPA [ Section No ] 1.3.2* For purposes of application of NFPA 101 and NFPA 5000, telecommunications facilities shall be classified as special- purpose or as industrial low occupancy, respectively industrial occupancies. Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Apr 23 10:01:09 EDT 2014 Committee Statement Committee Statement: The terminology was updated per the occupancy terms used in NFPA 101 and Response Message: Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W.

7 Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. of 126 7/8/2014 9:49 AM

8 of 126 7/8/2014 9:49 AM First Revision No. 30-NFPA [ Sections 1.3.3, ] The provisions of this standard shall not be applied retroactively to facilities, equipment, structures, or installations that were existing or approved for construction or installation prior to the effective date of the standard * Building alterations or new equipment installations in existing facilities shall provide a reasonable level of fire protection for the changed purposes of the facility. Supplemental Information File Name FR_30_1.4_edited.docx Description changes accepted Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Apr 23 08:41:01 EDT 2014 Committee Statement Committee Statement: Response Message: The new section on retroactivity clarifies and emphasizes the intent of the document as it applies to existing and altered facilities. Public Input No. 62-NFPA [Section No. 1.1 [Excluding any Sub-Sections]] Public Input No. 63-NFPA [Section No. 1.3] Public Input No. 65-NFPA [Section No ] Public Input No. 66-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M.

9 Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. of 126 7/8/2014 9:49 AM

10 1.4 Retroactivity. The provisions of this standard reflect a consensus of what is necessary to provide an acceptable degree of protection from the hazards addressed in this standard at the time this standard was issued Unless otherwise specified, the provisions of this standard shall not apply to telecommunications facilities that existed or were approved for construction or installation prior to the effective date of this standard Building alterations or new equipment installations in existing facilities shall provide a reasonable level of fire protection for the changed purposes of the facility Fire protection systems in excess of the features required in this standard shall be permitted to be left in service, removed, or abandoned in place Fire protection systems abandoned in place shall be clearly identified as no longer being in service The provisions of Chapters 9 and 10 shall apply to new and existing telecommunications facilities In those cases where the authority having jurisdiction determines that the existing situation presents an unacceptable degree of risk, the authority having jurisdiction shall be permitted to apply retroactively any portions of this standard deemed appropriate The retroactive requirements of this standard shall be permitted to be modified if their application clearly would be impractical in the judgment of the authority having jurisdiction and only where it is clearly evident that a reasonable degree of safety is provided.

11 of 126 7/8/2014 9:49 AM First Revision No. 54-NFPA [ Section No ] Chapters 1, 4, 9, and 10 shall apply to all telecommunications facilities within the scope of this standard except those covered by Chapter 11, regardless of the design approach taken. Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Apr 23 16:36:54 EDT 2014 Committee Statement Committee Statement: See FR 55. Response Message: Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W.

12 Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 0 of 126 7/8/2014 9:49 AM

13 1 of 126 7/8/2014 9:49 AM First Revision No. 1-NFPA [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA NFPA 1, Fire Code, edition. NFPA 10, Standard for Portable Fire Extinguishers, edition. NFPA 12A, Standard on Halon 1301 Fire Extinguishing Systems, edition. NFPA 13, Standard for the Installation of Sprinkler Systems, edition. NFPA 14, Standard for the Installation of Standpipe and Hose Systems, edition. NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, edition. NFPA 30, Flammable and Combustible Liquids Code, edition. NFPA 37, Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines, edition. NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work, edition. NFPA 54, National Fuel Gas Code, edition. NFPA 58, Liquefied Petroleum Gas Code, edition. NFPA 70, National Electrical Code, edition. NFPA 72, National Fire Alarm and Signaling Code, edition. NFPA 80, Standard for Fire Doors and Other Opening Protectives, edition. NFPA 80A, Recommended Practice for Protection of Buildings from Exterior Fire Exposures, 2012 edition. NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, edition. NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, edition. NFPA 101, Life Safety Code, edition. NFPA 220, Standard on Types of Building Construction, edition. NFPA 241, Standard for Safeguarding Construction, Alteration, and Demolition Operations, edition. NFPA 252, Standard Methods of Fire Tests of Door Assemblies, 2012 edition. NFPA 257, Standard on Fire Test for Window and Glass Block Assemblies, 2012 edition. NFPA 262, Standard Method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces, edition. NFPA 750, Standard on Water Mist Fire Protection Systems, edition. NFPA 780, Standard for the Installation of Lightning Protection Systems, edition. NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, edition. NFPA 5000, Building Construction and Safety Code, edition. Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ]

14 Street Address: City: State: Zip: Submittal Date: Tue Apr 22 07:48:31 EDT 2014 Committee Statement Committee Statement: Update references. Response Message: Public Input No. 28-NFPA [Section No. 2.2] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy 2 of 126 7/8/2014 9:49 AM

15 3 of 126 7/8/2014 9:49 AM Slagle, Charles Ziegler, Thomas F.

16 First Revision No. 2-NFPA [ Section No. 2.3 ] 2.3 Other Publications ANSI ATIS Publications. American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY ANSI T1.307, Fire Resistance Criteria Ignitability Requirements for Equipment Assemblies, Ancillary Non-Metallic Apparatus, and Fire Spread Requirements for Wire and Cable, 2003 Alliance for Telecommunications Industry Solutions, 1200 G Street NW, Suite 500, Washington, DC ATIS , Fire Resistance Criteria Ignitability Requirements for Equipment Assemblies, Ancillary Non-Metallic Apparatus, and Fire Spread Requirements for Wire and Cable, ANSI T1.319, Equipment Assemblies Fire Propagation Risk Assessment Criteria, 2002 ATIS , Equipment Assemblies Fire Propagation Risk Assessment Criteria, ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA ASTM E 84 E84, Standard Test Method for Surface Burning Characteristics of Building Materials, Rev A. ASTM E 814 E814, Standard Test Method for Fire Tests of Penetration Firestop Systems, Rev A. ASTM E 1537 E1537, Standard Test Method for Fire Testing of Upholstered Furniture, ASTM E 1966 E1966, Standard Test Method for Fire Resistive Joint Systems, CSA Publications. Canadian Standards Association, 5060 Spectrum Way, Mississauga, Ontario, L4W 5N6, Canada. C22.2 No , Test Methods for Electrical Wires and Cables, UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL ANSI/UL 44, Thermoset-Insulated Wires and Cables, ANSI/UL 83, Thermoplastic-Insulated Wire and Cables, ANSI/UL 444, Communications Cables, 2008, revised ANSI/UL 568, Nonmetallic Cable Tray Systems, 2002, reaffirmed UL 723, Standard for Test For Surface Burning Characteristics of Building Materials, ANSI/UL 900, Standard for Air Filter Units, 2004, revised ANSI/UL 1277, Electrical Power and Control Tray Cables with Optional Optical-Fiber Members, ANSI/UL 1651, Optical Fiber Cable, ANSI/UL 1666, Standard Test for Flame Propagation Height of Electrical and Optical-Fiber Cables Installed Vertically in Shafts, ANSI/UL 1685, Standard for Vertical Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables, 2007, including revisions through July 7, ANSI/UL 2024, Signaling Optical Fiber and Communication Cable Raceways and Cable Routing Assemblies and Communications Raceways, ANSI/UL , Application Guideline Information Technology Equipment Safety Part 1: General Requirements, of 126 7/8/2014 9:49 AM

17 5 of 126 7/8/2014 9:49 AM Other Publications. California Technical Bulletin 133, Flammability Test Procedure for Seating Furniture for Use in Public Occupancies. Merriam-Webster s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, Telcordia GR-63-CORE, Network Equipment Building System (NEBS) Requirements: Physical Protection, Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 08:08:25 EDT 2014 Committee Statement Committee Statement: Update references. Response Message: Public Input No. 1-NFPA [Section No ] Public Input No. 25-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W.

18 Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 6 of 126 7/8/2014 9:49 AM

19 7 of 126 7/8/2014 9:49 AM First Revision No. 3-NFPA [ Section No. 2.4 ] 2.4 References for Extracts in Mandatory Sections. NFPA 70, National Electrical Code, edition. NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, edition. NFPA 101, Life Safety Code, edition. NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants, edition. NFPA 921, Guide for Fire and Explosion Investigations, edition. NFPA 5000, Building Construction and Safety Code, edition. Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 08:41:19 EDT 2014 Committee Statement Committee Statement: Update extracts. Response Message: Public Input No. 26-NFPA [Section No. 2.4] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L.

20 Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 8 of 126 7/8/2014 9:49 AM

21 9 of 126 7/8/2014 9:49 AM First Revision No. 4-NFPA [ Section No ] Cable Routing Assembly. A single channel or connected multiple channels, as well as associated fittings, forming a structural system that is used to support, and route and protect high densities of wires and cables, typically communications wires and cables, optical fiber and data (Class 2 and Class 3) cables, data cables associated with information technology and communications equipment, Class 2 and Class 3 cables, and power-limited fire alarm cables. [70, ] Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 08:45:42 EDT 2014 Committee Statement Committee Statement: Updated extract. Response Message: Public Input No. 12-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A.

22 Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 0 of 126 7/8/2014 9:49 AM

23 1 of 126 7/8/2014 9:49 AM First Revision No. 37-NFPA [ Section No ] Cable TV Telecommunications. One- and two-way communications service provided over a video network, generally through fiber-optic and coaxial cable. Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Apr 23 12:45:08 EDT 2014 Committee Statement Committee Statement: The definition has been modified to reflect current industry nomenclature. Response Message: Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W.

24 Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 2 of 126 7/8/2014 9:49 AM

25 3 of 126 7/8/2014 9:49 AM First Revision No. 5-NFPA [ Section No ] Contractor. One who contracts on predetermined terms to provide labor and materials and who is responsible for performance of a construction job in accordance with construction documents. [5000, ] Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 08:51:04 EDT 2014 Committee Statement Committee Statement: Update extract. Response Message: Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W.

26 Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 4 of 126 7/8/2014 9:49 AM

27 5 of 126 7/8/2014 9:49 AM First Revision No. 6-NFPA [ Section No ] Firestop. A specific system, device, or construction consisting of the materials that fill the openings around penetrating items such as cables, cable trays, conduits, ducts, pipes, and their means of support through the wall or floor openings to prevent the spread of fire. [5000, ] Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 08:51:38 EDT 2014 Committee Statement Committee Statement: Update extract. Response Message: Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P.

28 Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 6 of 126 7/8/2014 9:49 AM

29 7 of 126 7/8/2014 9:49 AM First Revision No. 7-NFPA [ Section No ] Communications Raceway. An enclosed channel of nonmetallic materials designed expressly for holding communications wires and cables typically communications wires and cables and optical fiber and data (Class 2 and Class 3) in plenum, riser, and general-purpose applications. [ 70, 2014] Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 08:58:56 EDT 2014 Committee Statement Committee Statement: Optical fiber raceways have been replaced by communications raceways. Response Message: Public Input No. 13-NFPA [Section No ] Public Input No. 14-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A.

30 Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 8 of 126 7/8/2014 9:49 AM

31 9 of 126 7/8/2014 9:49 AM First Revision No. 8-NFPA [ Section No ] Smoke Control. A system that utilizes fans to produce pressure differences so as to manage smoke movement. [90A, ] Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 09:02:39 EDT 2014 Committee Statement Committee Statement: Update extract. Response Message: Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W.

32 Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 0 of 126 7/8/2014 9:49 AM

33 First Revision No. 9-NFPA [ Section No. 3.7 ] 3.7 Performance-Based Approach Definitions Analysis Sensitivity Analysis. An analysis performed to determine the degree to which a predicted output will vary given a specified change in an input parameter, usually in relation to models. [5000, ] Uncertainty Analysis. An analysis performed to determine the degree to which a predicted value will vary. [5000, ] 3.7.2* Exposure Fire. A fire that starts at a location that is remote from the area being protected and grows to expose that which is being protected. [101, ] 3.7.3* Fire Model. Mathematical prediction of fire growth, environmental conditions, and potential effects on structures, systems, or components based on the conservation equations or empirical data. [805, ] 3.7.4* Fire Scenario. A set of conditions that defines the development of fire, the spread of combustion products throughout a building or portion of a building, the reactions of people to fire, and the effects of combustion products. [101, ] Fuel Load. The total quantity of combustible contents of a building, space, or fire area, including interior finish and trim, expressed in heat units or the equivalent weight in wood. [921, ] Incapacitation. A condition under which humans do not function adequately and become unable to escape untenable conditions. [101, ] Occupant Characteristics. The abilities or behaviors of people before and during a fire. [101, ] 3.7.8* Performance Criteria. Threshold values on measurement scales that are based on quantified performance objectives. [101, ] Proposed Design. A design developed by a design team and submitted to the authority having jurisdiction for approval. [101, ] Safe Location. A location remote or separated from the effects of a fire so that such effects no longer pose a threat. [101, ] Safety Factor. A factor applied to a predicted value to ensure that a sufficient safety margin is maintained. [101, ] Safety Margin. The difference between a predicted value and the actual value where a fault condition is expected. [101, ] Verification Method. A procedure or process used to demonstrate or confirm that the proposed design meets the specified criteria. [101, ] Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: 1 of 126 7/8/2014 9:49 AM

34 2 of 126 7/8/2014 9:49 AM City: State: Zip: Submittal Date: Tue Apr 22 09:07:17 EDT 2014 Committee Statement Committee Statement: Update extracts. Response Message: Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F.

35 3 of 126 7/8/2014 9:49 AM First Revision No. 49-NFPA [ Section No ] A depowering procedure shall be developed in accordance with Section Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Apr 23 15:04:03 EDT 2014 Committee Statement Committee Statement: The topic is adequately covered in 10.6, which applies to all facilities. Response Message: Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G.

36 Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 4 of 126 7/8/2014 9:49 AM

37 5 of 126 7/8/2014 9:49 AM First Revision No. 32-NFPA [ Section No ] * Minimum sensitivity settings above ambient air-borne airborne levels for the VEWFD systems installed shall be as follows: (1) Alert condition includes the following: (a) (b) Air-sampling systems: 0.65 percent per meter ( 0.2 percent per foot) obscuration (effective sensitivity at each port) Spot-type sensors: 0.65 percent per meter ( 0.2 percent per foot) obscuration (2) Alarm condition includes the following: (a) (b) Air-sampling systems: 3.2 percent per meter ( 1.0 percent per foot) obscuration (effective sensitivity at each port) Spot-type sensors: 3.2 percent per meter ( 1.0 percent per foot) obscuration Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Apr 23 10:28:43 EDT 2014 Committee Statement Committee Statement: Added the metric units for obscuration. Response Message: Public Input No. 11-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William

38 Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 6 of 126 7/8/2014 9:49 AM

39 7 of 126 7/8/2014 9:49 AM First Revision No. 33-NFPA [ Section No ] The minimum alarm sensitivity setting at the sensor or port used for EWFD in telecommunications equipment areas shall be 5.0 percent per meter ( 1.5 percent per foot). Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Apr 23 10:31:53 EDT 2014 Committee Statement Committee Statement: Added the metric units for obscuration. Response Message: Public Input No. 10-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P.

40 Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 8 of 126 7/8/2014 9:49 AM

41 9 of 126 7/8/2014 9:49 AM First Revision No. 59-NFPA [ New Section after ] Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Apr 24 11:31:23 EDT 2014 Committee Statement Committee Statement: Response Message: This section is reserved for future requirements, in recognition of evolving technologies. The committee invites comments on how to address in-cabinet detection. Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G.

42 Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 0 of 126 7/8/2014 9:49 AM

43 1 of 126 7/8/2014 9:49 AM First Revision No. 34-NFPA [ Section No ] Where provided, water mist fire protection systems shall be installed in accordance with the requirements of NFPA 750 and tested and maintained in accordance with the requirements of NFPA 25. Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Apr 23 10:36:45 EDT 2014 Committee Statement Committee Statement: Response Message: Water mist systems require maintenance in accordance with NFPA 25 to ensure proper operation. Public Input No. 9-NFPA [New Section after ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M.

44 Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 2 of 126 7/8/2014 9:49 AM

45 3 of 126 7/8/2014 9:49 AM First Revision No. 60-NFPA [ New Section after ] Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Apr 24 11:37:00 EDT 2014 Committee Statement Committee Statement: Response Message: This section is reserved for future requirements, in recognition of evolving technologies. The committee invites comments on how to address in-cabinet suppression. Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G.

46 Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 4 of 126 7/8/2014 9:49 AM

47 5 of 126 7/8/2014 9:49 AM First Revision No. 20-NFPA [ Section No ] Nonmetallic communications raceways and nonmetallic optical fiber raceways Communications raceways shall be listed to the requirements of ANSI/UL Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 15:37:20 EDT 2014 Committee Statement Committee Statement: Response Message: Optical fiber raceways have been replaced by communications raceways in the 2014 NEC. Communications raceways are, by definition, nonmetallic. Public Input No. 15-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A.

48 Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 6 of 126 7/8/2014 9:49 AM

49 7 of 126 7/8/2014 9:49 AM First Revision No. 21-NFPA [ Section No ] Optical fiber cable Cable routing assemblies other than raceways shall be listed to the requirements of UL Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 15:38:33 EDT 2014 Committee Statement Committee Statement: Response Message: The text was changed to correlate with the definition of a cable routing assembly per the NEC. Public Input No. 16-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M.

50 Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 8 of 126 7/8/2014 9:49 AM

51 9 of 126 7/8/2014 9:49 AM First Revision No. 22-NFPA [ Section No ] Nonmetallic communications raceways and nonmetallic optical fiber raceways Communications raceways installed in plenums shall be listed as having a maximum flame spread of 1.52 m (5.0 ft), a maximum peak optical density of 0.50, and a maximum average optical density of when tested per ANSI/UL 2024 or Flame and Smoke Test in the Appendix to the flame and smoke test in CSA C22.2 No. 0.3-M-1996, Appendix B (FT6 Rating). Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 15:54:16 EDT 2014 Committee Statement Committee Statement: Optical fiber raceways have been replaced by communications raceways in the NEC. Communications raceways are, by definition, nonmetallic. Also, removed the edition year from the reference to CSA C22.2 No Response Message: Public Input No. 17-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J.

52 Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 0 of 126 7/8/2014 9:49 AM

53 1 of 126 7/8/2014 9:49 AM First Revision No. 23-NFPA [ Section No ] Cable routing assemblies other than raceways shall be listed to the requirements of UL Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 15:56:22 EDT 2014 Committee Statement Committee Statement: UL 2024 covers cable routing assemblies and communications raceways. Response Message: Public Input No. 18-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W.

54 Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 2 of 126 7/8/2014 9:49 AM

55 3 of 126 7/8/2014 9:49 AM First Revision No. 24-NFPA [ Section No ] Telecommunications cables, optical fiber cables, wires and cables intended for powering signalprocessing equipment, insulated ground wires, nonmetallic communications raceways, nonmetallic optical fiber raceways, and nonmetallic cable trays installed vertically between floors in a building shall comply with ANSI/UL These cables shall demonstrate limited smoke generation by testing in accordance with ANSI/UL Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 15:58:32 EDT 2014 Committee Statement Committee Statement: Response Message: Optical fiber raceways have been replaced by communications raceways in the NEC. Communications raceways are, by definition, nonmetallic. Public Input No. 19-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L.

56 Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 4 of 126 7/8/2014 9:49 AM

57 5 of 126 7/8/2014 9:49 AM First Revision No. 25-NFPA [ Section No ] Communications raceways and optical fiber raceways meeting the requirements of shall be permitted. Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 16:02:26 EDT 2014 Committee Statement Committee Statement: Optical fiber raceways have been replaced by communications raceways in the NEC. Response Message: Public Input No. 20-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P.

58 Humbrecht, Kirk W. Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 6 of 126 7/8/2014 9:49 AM

59 7 of 126 7/8/2014 9:49 AM First Revision No. 26-NFPA [ Section No ] Cable routing assemblies other than raceways shall be listed to the requirements of UL Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 16:09:22 EDT 2014 Committee Statement Committee Statement: UL 2024 includes cable routing assemblies and communications raceways. Response Message: Public Input No. 21-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P. Humbrecht, Kirk W.

60 Ingram, Jonathan G. Kasiski, Robert Kaufman, Stanley Lang, Scott R. McCarver, Randall R. McNamara, Jack Norton, Thomas F. O'Connor, Daniel J. Ouimette, Ronald D. Pradel, Brad Reiswig, Rodger Rice, Buddy Slagle, Charles Ziegler, Thomas F. 8 of 126 7/8/2014 9:49 AM

61 9 of 126 7/8/2014 9:49 AM First Revision No. 27-NFPA [ Section No ] Nonmetallic communications raceways and nonmetallic optical fiber Communications raceways shall not spread fire to the top of the tray in the vertical-tray flame test in ANSI/UL Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Apr 22 16:10:20 EDT 2014 Committee Statement Committee Statement: Optical fiber raceways have been replaced by communications raceways. Response Message: Public Input No. 22-NFPA [Section No ] Ballot Results This item has passed ballot 28 Eligible Voters 4 Not Returned 24 Affirmative All 0 Affirmative with Comments 0 Negative with Comments 0 Abstention Not Returned Backstrom, Robert G. Campos, Peter M. Custer, Richard L. P. Meyring, William Affirmative All Allen, Thomas L. Belliveau, Jr., Leonard Betz, Jeffrey A. Bosma, Michael J. Driggers, Mickey L. Dryden, Steve C. Durgin, Ronald A. Franchuk, Darrell M. Gardner, Robert P.

M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle)

M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications

More information

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ]

First Revision No. 36-NFPA [ Section No. 1.1 [Excluding any Sub-Sections] ] of 71 6/11/2014 8:20 AM First Revision No. 36-NFPA 76-2014 [ Section No. 1.1 [Excluding any Sub-Sections] ] This standard provides requirements for fire protection of telecommunications facilities where

More information

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Helicopter Facilities

More information

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Second Revision No. 3-NFPA [ Section No. 2.3 ] Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler

More information

Technical Committee on Telecommunications Facilities (TEL-AAA)

Technical Committee on Telecommunications Facilities (TEL-AAA) Technical Committee on Telecommunications Facilities () M E M O R A N D U M DATE: February 20, 2014 TO: Principal and Alternate Members of the Technical Committee on Telecommunications Facilities () FROM:

More information

12/21/2015 National Fire Protection Association Report

12/21/2015 National Fire Protection Association Report http://submittals.nfpa.org/terraviewweb/viewerpage.jsp?id=232 2012.ditamap&toc=false&draft=true 1/9 Public Comment No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Industrial and Medical Gases

More information

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM 1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

Second Revision No. 1 NFPA [ Chapter 2 ]

Second Revision No. 1 NFPA [ Chapter 2 ] Second Revision No. 1 NFPA 232 2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be

More information

MEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Emergency Power Supplies. NFPA 111 First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Emergency Power Supplies Kelly

More information

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels

More information

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference

Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference Matthews, Diane Subject: Location: Start: End: Show Time As: Recurrence: Meeting Status: Organizer: Required Attendees: Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference http://nfpa.adobeconnect.com/rpbmeet/

More information

Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

Change all instances of flame resistant (hypobaric) to Limited-Combustible (material) in all instances in the document. 1 of 9 10/21/2015 1:22 PM First Revision No. 3-NFPA 99B-2015 [ Global Input ] Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.

More information

MEMORANDUM. NFPA Technical Committee on Hazard and Risk of Contents and Furnishings. NFPA 556 First Draft TC FINAL Ballot Results (A2015)

MEMORANDUM. NFPA Technical Committee on Hazard and Risk of Contents and Furnishings. NFPA 556 First Draft TC FINAL Ballot Results (A2015) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Hazard and Risk of Contents

More information

Public Comment No. 1-NFPA [ Section No ]

Public Comment No. 1-NFPA [ Section No ] Page 1 of 7 Public Comment No. 1-NFPA 556-2014 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA, 19428-2959. ASTM D2859, Standard

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Building Service and

More information

Correlating Committee on Automatic Sprinkler Systems

Correlating Committee on Automatic Sprinkler Systems Correlating Committee on Automatic Sprinkler Systems M E M O R A N D U M DATE: May 14, 2014 TO: FROM: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems Matt Klaus,

More information

First Revision No. 1-NFPA [ Chapter 2 ]

First Revision No. 1-NFPA [ Chapter 2 ] First Revision No. 1-NFPA 499-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this recommended practice

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document 1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical on Laser Fire Protection Kimberly

More information

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Protected Premises Fire Alarm

More information

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Water Additives

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25

More information

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Alternative Approaches to

More information

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018) M EM O RA N D UM TO: FROM: DATE: SUBJECT: Correlating Committee on Combustible Dusts Yiu Lee, Project Administrator January 27, 2017 NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

More information

MEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Initiating Devices for Fire

More information

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement 1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

M E M O R A N D U M. NFPA 270 First Draft Technical Committee FINAL Ballot Results (F2017)

M E M O R A N D U M. NFPA 270 First Draft Technical Committee FINAL Ballot Results (F2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Tests Kelly

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101

Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101 Standard Compared 2012 Changes of the International Building Code and National Fire Protection Association- 101 For the Florida Building Commission And the Fire Code Advisory Council Introduction The scope

More information

Page 1 of 13 Second Revision No. 1-NFPA 326-2014 [ Section No. 2.3.1 ] 2.3.1 ACGIH Publications. American Conference of Governmental Industrial Hygienists, 1330 Kemper Meadow Drive, Cincinnati, OH 45240-1634.

More information

MEMORANDUM. NFPA Technical Committee on Handling and Conveying of Dusts, Vapors, and Gases. NFPA 654 Second Draft TC FINAL Ballot Results (A2016)

MEMORANDUM. NFPA Technical Committee on Handling and Conveying of Dusts, Vapors, and Gases. NFPA 654 Second Draft TC FINAL Ballot Results (A2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Handling and Conveying

More information

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Fire Alarm

More information

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic

More information

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 1-NFPA 36-2013 [ Global Input ] Revise the document to eliminate the use of "Exception" text. The use of "Exception" text is inconsistent with the Manual of Style. Exception text should

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

Throughout standard remove references to the following and replace with the following:

Throughout standard remove references to the following and replace with the following: of 35 12/3/2015 7:13 AM Public Input No. 1-NFPA 90A-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/UL and replace with UL. (2) ANSI/ASHRAE

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document National Fire Protection Association Report of 113 http://submittals.nfpa.org/terraviewweb/contentfetcher?commentpara... 2/9/2016 10:50 AM Public Input No. 1-NFPA 87-2015 [ Global Input ] Throughout standard

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

First Revision No. 20-NFPA [ Section No ]

First Revision No. 20-NFPA [ Section No ] of 25 7/15/2015 8:30 AM First Revision No. 20-NFPA 56-2015 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by NFPA

More information

Technical Committee on Record Protection (REA-AAA)

Technical Committee on Record Protection (REA-AAA) Technical Committee on Record Protection (REA-AAA) DATE: September 8, 2015 TO: FROM: M E M O R A N D U M Principal and Alternate Members of the Technical Committee on Record Protection (REA-AAA) Audrey

More information

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document

Public Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document of 79 1/27/2016 2:09 PM Public Input No. 1-NFPA 59-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/API and replace with API. (2) ANSI/UL

More information

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016 TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES NFPA 610 First Draft Meeting October 17-18, 2016 Westin Kansas City at Crown Center 1 East Pershing Road Kansas City, MO, 64108 Conference Call Access:

More information

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

WORKING DRAFT OF COMMITTEE MEETING OUTPUT WORKING DRAFT OF COMMITTEE MEETING OUTPUT CONTENT NOT FINAL SUBJECT TO REVISION PRIOR TO LETTER BALLOT AND PUBLICATION OF SECOND DRAFT REPORT Document: NFPA 221 Revision Cycle: A2014 Meeting Date: 5/20/2013

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 14 From: Kimberly Shea, Project Administrator

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Portable Fire Extinguishers

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard

More information

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017)

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Code Kelly Carey,

More information

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application. 1.3.1 This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except

More information

MEMORANDUM. NFPA 99 Second Draft Correlating Committee FINAL Ballot Results (A2017)

MEMORANDUM. NFPA 99 Second Draft Correlating Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Correlating Committee on Health Care Facilities Elena

More information

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Supervising Station

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Furnishings

More information

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities

More information

M E M O R A N D U M. Technical Committee on Flash Fire Protective Garments

M E M O R A N D U M. Technical Committee on Flash Fire Protective Garments National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Flash Fire Protective

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

First Revision No. 15-NFPA [ Chapter 2 ]

First Revision No. 15-NFPA [ Chapter 2 ] Page 1 of 28 First Revision No. 15-NFPA 91-2013 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard

More information

Public Input No. 3-NFPA [ Chapter 2 ]

Public Input No. 3-NFPA [ Chapter 2 ] Public Input No. 3-NFPA 655-2014 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

M E M O R A N D U M. NFPA 1911 Second Draft Technical Committee FINAL Ballot Results (F2016 Cycle)

M E M O R A N D U M. NFPA 1911 Second Draft Technical Committee FINAL Ballot Results (F2016 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Department Apparatus

More information

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input Public Input No. 4-NFPA 111-2016 [ Section No. 1.1.4.1 ] 1.1.4.1 * This standard shall not cover the following: (1) Application of the SEPSS (2) Distribution wiring (3) Systems having total outputs less

More information

Remove the "Exception" text to be consistent with direction provided in the MOS.

Remove the Exception text to be consistent with direction provided in the MOS. of 37 1/11/2017 7:38 AM Public Input No. 9-NFPA 88A-2015 [ Global Input ] Remove the "Exception" text to be consistent with direction provided in the MOS. The current language in 88A has numerous section

More information

MEMORANDUM. Technical Committee on Fundamentals of Combustible Dusts. NFPA 652 First Draft Technical Committee FINAL Ballot Results (A2018)

MEMORANDUM. Technical Committee on Fundamentals of Combustible Dusts. NFPA 652 First Draft Technical Committee FINAL Ballot Results (A2018) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Combustible

More information

Page 1 of 9 First Revision No. 2-NFPA 99B-2012 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard for Portable

More information

M E M O R A N D U M. NFPA Technical Committee on Fire Department Apparatus. Yvonne Smith, Project Administrator. Date: June 4, 2014

M E M O R A N D U M. NFPA Technical Committee on Fire Department Apparatus. Yvonne Smith, Project Administrator. Date: June 4, 2014 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Fire Department

More information

Committee Input No. 60-NFPA [ Sections , ]

Committee Input No. 60-NFPA [ Sections , ] Page 1 of 15 Committee Input No. 60-NFPA 34-2013 [ Sections 3.3.7.1, 3.3.7.2 ] Sections 3.3.7.1, 3.3.7.2 3.3.7.1 Combustible Liquid. A Any liquid that has a closed-cup flash point at or above 100 F (37.8

More information

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM

First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Water Additives

More information

TECHNICAL COMMITTEE ON FIRE CODE

TECHNICAL COMMITTEE ON FIRE CODE TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2

More information

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12.

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12. 2/18/2016 National Fire Protection Association Report Committee Input No. 70 NFPA 54 2015 [ Section No. 12.5 ] This was a First Revision that failed ballot. 12.5 Type of Venting System to Be Used. 12.5.1

More information

Page 1 of 40 First Correlating Revision No. 15-NFPA 72-2014 [ Global Input ] 10.5.4 Plans Examiners and Inspectors. 10.5.4.1 Fire alarm system and emergency communications system plans and specifications

More information

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM

First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] Submitter Information Verification. Committee Statement 11/18/2016 2:25 PM of 28 11/18/2016 2:25 PM First Revision No. 3-NFPA 51B-2016 [ New Section after 1.5 ] 1.6 Units and Formulas. 1.6.1 The units of measure in this standard are presented first in U.S. customary units (inch-pound

More information

M E M O R A N D U M. NFPA Technical Committee on Water Spray Fixed Systems

M E M O R A N D U M. NFPA Technical Committee on Water Spray Fixed Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Water Spray

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Residential Sprinkler

More information

First Revision No. 1-NFPA 30A-2015 [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

First Revision No. 1-NFPA 30A-2015 [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement of 35 1/21/2016 7:56 AM First Revision No. 1-NFPA 30A-2015 [ Section No. 1.1.3 ] 1.1.3* This code shall not apply to those motor fuel dispensing facilities where only liquefied petroleum gas (LP-Gas),

More information

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Correlating Committee on Signaling Systems for

More information

SAF-BCF SECOND REVISIONS WITH STATEMENTS

SAF-BCF SECOND REVISIONS WITH STATEMENTS Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level

More information

(a) Flame shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2440 mm 3660 mm) wall. Flashover shall not occur.

(a) Flame shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2440 mm 3660 mm) wall. Flashover shall not occur. First Revision No. 1-NFPA 501-2015 [ Section No. 5.3.1.3 ] 5.3.1.3 The following conditions shall be met when an interior finish material is tested using the test protocol of NFPA 286, Standard Methods

More information

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement First Revision No. 1-NFPA 259-2016 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D5865, Standard Test Method

More information

Page 1 of 126 First Revision No. 113-NFPA 45-2013 [ Global Input ] Change all references to Material Safety Data Sheets (MSDS) to Safety Data Sheets (SDS) Submittal Date: Thu May 09 11:40:44 EDT 2013 Response

More information

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 496-2014 [ Section No. 5.2.2 ] 5.2.2 Where When the enclosure has been opened or if the protective gas supply has failed to maintain the required positive pressure, the enclosure

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Construction

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

M E M O R A N D U M. NFPA Technical Committee on Fire Safety and Emergency Symbols. NFPA 170 Second Draft TC FINAL Ballot Results (F2014)

M E M O R A N D U M. NFPA Technical Committee on Fire Safety and Emergency Symbols. NFPA 170 Second Draft TC FINAL Ballot Results (F2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Fire Safety

More information

SUBJECT: NFPA 302 Second Draft TC Final Ballot Results (A2014)

SUBJECT: NFPA 302 Second Draft TC Final Ballot Results (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Motor Craft Lawrence B. Russell, Staff

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

Public Input No. 48-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 48-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 62 8/4/17, 2:42 PM Public Input No. 48-NFPA 45-2017 [ Section No. 1.1.2 ] 1.1.2 This standard shall apply to all educational laboratory units and instructional laboratory units in which any quantity

More information