FUNCTIONAL PROFILE: GOLDen GATE Lonworks FTT-10, TBLZ , Version 5.00 GOLD Sizes 04-80, Version C, Program Version 5.00

Size: px
Start display at page:

Download "FUNCTIONAL PROFILE: GOLDen GATE Lonworks FTT-10, TBLZ , Version 5.00 GOLD Sizes 04-80, Version C, Program Version 5.00"

Transcription

1 FUNCTIONAL PROFILE: GOLDen GATE Lonworks FTT-10, TBLZ , Version 5.00 GOLD Sizes 04-80, Version C, Program Version 5.00 Specifications are subject to alteration without notice. 1

2 General This document describes the profile at the GOLD-LON interface. The LON interface is a separate communication unit that solely transfers data to and from the control system in the GOLD air handling unit. This edition of the GOLD-LON interface should be used for monitoring GOLD units sizes ver. C, across a LON bus. It is not possible to override the physical inputs of the GOLD air handling unit, only monitor them across the LON bus. The temperature and air flow set points can be adjusted across the LON network. The functions in the GOLD control system can be adjusted, enabled or disabled. The integrated switching clock can also be set to the current time. The interface is normally equipped with a Transceiver for Twisted Pair Open Topology (TP/FT-10). This is a ready-to-use module, developed and accepted by Echelon. The LON software in the interface supports the self-documentation and Wink function and thus helps with installing nodes across a network manager. The network variables are to SNVT Standard. The LON Interface can be illustrated as follows: Figure 1 Functional profile LON- Interface Object GOLD- Air Handling Unit 2 Specifications are subject to alteration without notice.

3 Power-Up State All the input variables have a 0 reading before communication with the GOLD air handling unit has been established. When communication with the GOLD unit has been in progress for about 10 seconds, all the input variables have been upgraded with the values from the GOLD air handling unit s internal Flash. This means that the input variables are always upgraded after a power failure and therefore always indicate the current value, as long as the communication is OK. LED/Keyed Functions Normal operation: The Module Status LED will flash green. The Serial Status LED will flash green whenever ackowledged communication with the GOLD takes place. Service: The Service LED will flash if the node has not been configured. Configuration is normally carried out by a LON manager. While the LON manager is configuring the node, the operator will be requested to depress servicepin to identify the node. The node has integrated self-identification and self-description of the parameters. Wink Function This command can be used for identifying the GOLD Air handling unit. The Serial Status LEDs green and red flash alternately for 15 seconds while the Wink command is being transmitted to the LON interface. This input variable can be used for checking whether the LON network is intact up to the LON interface and for identifying a specific air handling unit if several units are connected to the same network. Specifications are subject to alteration without notice. 3

4 Figure 2 Functional profile number 8080 of LonMark Unit Ventilator object details (variables not implemented in GOLD are greyed). Hardware Output Unit Ventilator Controler number 8080 nv1 nvispacetemp SNVT_temp_p Mandatory Network Variables nv21 nv22 nv23 nvospacetemp SNVT_temp_ nvoeffectsetp SNVT_temp_p nvoeffectsetp SNVT_temp_p nv2 nv3 nv4 nv5 nv6 nv7 nv8 nv9 nv10 nv11 nv12 nv13 nv14 nv15 nv16 nv17 nv18 nv19 nv20 nv21 nvisetpoint SNVT_temp_p nvisetptoffset SNVT_temp_p nvisetptshift SNVT_temp_p nvioccschedule SNVT_tod_event nvioccmancmd SNVT_occupancy nvioccsensor SNVT_occupancy nviapplicmode SNVT_hvac_mode nviheatcool SNVT_hvac_Mode nvifanspeedcmd SNVT_switch nvicomprenable SNVT_switch nviauxheatenable SNVT_switch nvieconenable SNVT_switch nvienergyholdoff SNVT_switch nvivalveoverride SNVT_switch nviemergoverride SNVT_hvac_emerg nvisourcetemp SNVT_temp_p nvioutdoortemp SNVT_temp_p nvispacerh SNVT_lev_percent nvioutsiderh SNVT_lev_percent nvispaceco2 SNVT_ppm Optional Network Variables nv24 nv25 nv26 nv27 nv28 nv29 nv30 nv31 nv32 nv33 nv34 nv35 nv36 nv37 nv38 nv39 nv40 nvoeffectoccup SNVT_occupancy nvoheatcool SNVT_hvac_mode nvosetpoint SNVT_temp_p nvosetpshift SNVT_temp_setp nvofanspeed SNVT_switch nvodischairtemp SNVT_temp_p nvoloadabsk SNVT_power_kilo nvoterminalload SNVT_lev_percent nvoheatprimary SNVT_lev.percent nvoheatsecondary SNVT_lev_percent nvocoolprimary SNVT_lev_percent nvooadamper SNVT_lev_percent nvospacerh SNVT_lev_percent nvooutdoorrh SNVT_lev_percent nvooutdoortemp SNVT_temp_p nvospaceco2 SNVT_ppm nvoenergyholdoff SNVT_switch Configuration Properties nc49 Send Heartbeat (mandatory) nc60 Occupancy Temperature Setpoints (mandatory) nc52 Minimum Send Time (optional) nc48 Receive Hartbeat (optional) nc17 Location Label (optional) nc34 Local Bypass Time (optional) nc35 Manual Override Time (optional) nc23 Outdoor Air Damper Minimum Position (optional) nc42 Space CO2 Limit (optional) nc36 Space Humidity Setpoint (optional) nc59 Number of Heating/Cooling Valves (optional) See following pages Manufacturer Defined Section See following pages Hardware Input 4 Specifications are subject to alteration without notice.

5 Overview, parameters Extract air filter pressure level nvoea_filterlev EA filter pressure level limit nvoea_filterair Operation mode 1 nvounitopm2_00-18 Communication operation mode nvicomoperation Operation mode 2 nvounitopm3_00-22 Operation output nvoop_relay Low speed output nvols_relay High speed output nvohs_relay Damper output nvodamper_relay Present tripped alarm nvoactive_alarm A-alarm nvoa_alarm_relay B-alarm nvob_alarm_relay Alarm reset nvialarm_reset EA Airflow nvoef_flow EA Fan level nvoef_speed EA Low speed airflow setpoint nvief_lsflow EA High speed airflow setpoint nvief_hsflow Outdoor temperature nvoouttemp Supply air filter pressure level nvosa_filterlev SA filter pressure level limit nvosa_filterair Heat exchange reglutator nvoheatprimaryre EA Duct pressure nvoef_pressure EA Low speed pressure setpoint nvief_lspressure EA High speed pressure setpoint nvief_hspressure SA Airflow nvosf_flow SA Fan level nvofanspeed SA Low speed airflow setpoint nvisf_lsflow SA High speed airflow setpoint nvisf_hsflow EA/Room temperature nvoeatemp EA/Room temperature setpoint nvieatempset SA Min temperature setpoint nviminsatemp SA Max temperature setpoint nvimaxsatemp SA Duct pressure nvosf_pressure SA Low speed pressure point nvisf_lspressure SA High speed pressure point nvisf_hspressure SA Temperature nvosatemp SA Temperature setpoint nvisetpoint ERS 1 Diff nviers1diff Cooling level nvocoolprimary Cool output 1 nvocool_1_relay Cool output 2 nvocool_2_relay Reheat level nvoheatsecondary Heat output nvoheat_relay Anti frost temperature nvofrosttemp Specifications are subject to alteration without notice. 5

6 NV Index SNVT No SNVT Name SNVT Description Min/Max SNVT type nvialarm_reset Alarm Reset Act 0-1 SNVT_switch nvoalarm_reset Alarm Reset Resets tripped alarms nvisf_boost_func SF Boost Act 0-1 SNVT_switch nvosf_boost_func SF Boost Setting for activating the boost function for the supply air fan nvief_boost_func EF Boost Act 0-1 SNVT_switch nvoef_boost_func EF Boost Setting for activating the boost function for the extract air fan nvihx_defr_func Defrost Heat X Act 0-1 SNVT_switch nvohx_defr_func Defrost Heat X Setting for activating the defrost function for the rotary heat exchanger nvicool_op_func Cool In Auto Act 0-1 SNVT_switch nvocool_op_func Cool In Auto Setting for cooling between off and auto operation nvinh_func Intrmt Nght Heat Act 0-1 SNVT_switch nvonh_func Intrmt Nght Heat Setting for activating the intermittent night heat function nvinh_damp_func Damper funct Act 0-1 SNVT_switch nvonh_damp_func Damper funct Setting for activating the damper output relay during int. night heat nvisc_func Smr Nght Cool Act 0-1 SNVT_switch nvosc_func Smr Nght Cool Setting for activating the summer night cool function nvitempdisp_func Temp Disp offset Act 0-1 SNVT_switch nvotempdisp_func Temp Disp offset Setting for activating the external temperature displacement function nvitempcomp_func Out Temp Comp Act 0-1 SNVT_switch nvotempcomp_func Out Temp Comp Setting for activating the outdoor temperature compensation function nviflowcomp_func Out Flow Comp Act 0-1 SNVT_switch nvoflowcomp_func Out Flow Comp Setting for activating the outdoor airflow compensation function nviautos/w_func Auto Summer/Winter Act 0-1 SNVT_switch nvoautos/w_func Auto Summer/Winter Setting for activating the automatic switch between summer/winter time function nvits_func Time Chan. Func Act 0-1 SNVT_switch nvots_func Time Chan. Func Setting for switch clock function type. 0=Stop - low speed - high speed. 1=Low speed - high speed nviint_fire_func Int Fire Al Act 0-1 SNVT_switch nvoint_fire_func Int Fire Al Setting for activating the internal fire alarm function nviext_alr1_func Ext Al1 Cond Func Act 0-1 SNVT_switch nvoext_alr1_func Ext Al1 Cond Func Setting for external alarm number 1 condition to be activated. 0= alarm at closed input. 1= alarm at open input nviext_alr2_func Ext Al2 Cond Func Act 0-1 SNVT_switch nvoext_alr2_func Ext Al2 Cond Func Setting for external alarm number 2 condition to be activated. 0= alarm at closed input. 1= alarm at open input nvidewpoint_func Dewpoint Act 0-1 SNVT_switch nvodewpoint_func Dewpoint Setting for activating the dewpoint regulator funktion nvidehumid_func Dehumid Act 0-1 SNVT_switch nvodehumid_func Dehumid Setting for activating the dehumid regulator funktion nviext_fire_func Ext Fire Al Act 0-1 SNVT_switch nvoext_fire_func Ext Fire Al Setting for external fire resetting function. 0=Manual. 1=Automatic nviext_alr1_refu Ext Al1 Res Func Act 0-1 SNVT_switch nvoext_alr1_refu Ext Al1 Res Func Setting for external alarm 1 resetting function. 0=Manual. 1=Automatic nviext_alr2_refu Ext Al2 Res Func Act 0-1 SNVT_switch nvoext_alr2_refu Ext Al2 Res Func Setting for external alarm 2 resetting function. 0=Manual. 1=Automatic. 6 Specifications are subject to alteration without notice.

7 nvitemp_alr_func Temp Alarm Func Act 0-1 SNVT_switch nvotemp_alr_func Temp Alarm Func Setting for activating temperature below setpoint alarm function (no.80) nvinh_op_func Intrmt Nght Heat OP Act 0-1 SNVT_switch nvonh_op_func Intrmt Nght Heat OP Setting for selecting the intermittent night heat output function. 0=IQnomic 1=IQnomic nvoheat_relay Pmp Heat 0-1 SNVT_switch Status for relay output nvocool_1_relay Cool SNVT_switch Status for relay output nvocool_2_relay Cool SNVT_switch Status for relay output nvols_relay Low Spd 0-1 SNVT_switch Status for relay output nvohs_relay High Spd 0-1 SNVT_switch Status for relay output nvoa_alarm_relay Alrm A 0-1 SNVT_switch Status for relay output nvob_alarm_relay Alrm B 0-1 SNVT_switch Status for relay output nvoop_relay Operating 0-1 SNVT_switch Status for relay output nvodamper_relay Damper 0-1 SNVT_switch Status for relay output nvoext_ls_inp Ext Low Spd 0-1 SNVT_switch Status for digital input nvoext_hs_inp Ext High Spd 0-1 SNVT_switch Status for digital input nvoext_alarm1inp Ext Alrm A 0-1 SNVT_switch Status for digital input nvoext_alarm2inp Ext Alrm B 0-1 SNVT_switch Status for digital input nvoext_fire_inp Ext Fire 0-1 SNVT_switch Status for digital input nvoext_stop_inp Ext Stop 0-1 SNVT_switch Status for digital input nvodip1 DIL SNVT_switch Status for dip switch setting nvodip2 DIL SNVT_switch Status for dip switch setting nvodip3 DIL SNVT_switch Status for dip switch setting nvodip4 DIL SNVT_switch Status for dip switch setting nvodip5 DIL SNVT_switch Status for dip switch setting nvodip6 DIL SNVT_switch Status for dip switch setting nvochx_relay C.HX. Pump output 0-1 SNVT_switch Status for coil heat exchanger pump output nvorhx_rotation R.HX rotation monitor 0-1 SNVT_switch Status from the rotation detector nvoxzone_heat_re Xzone heat output 0-1 SNVT_switch Status for relay output nvoxzone_cool_r1 Xzone cool output SNVT_switch Status for relay output nvoxzone_cool_r2 Xzone cool output SNVT_switch Status for relay output nvopreheat_relay Pre-heat output 0-1 SNVT_switch Status for relay output nvoalarmout Alarm Out SNVT_alarm Location = GOLD. Object ID = Alarm number (0-200). Alarm type = Contains either no alarm or an unspecified alarm. Priority level = alarm priority (No comm.=3, A=1, B=2 and none=0). Index to SNVT = Not used. Always set at 0. Value = Not used Always set at 0. Year, month, day = Date when alarm tripped. Alarm limit = Not used. Always set at nvosf_flow Sup AF l/s SNVT_flow Present supply airflow. Specifications are subject to alteration without notice. 7

8 nvosf_flowreg Sup AF reg l/s SNVT_flow Present supply airflow regulator setpoint nvoef_flow Ext AF l/s SNVT_flow Present extract airflow nvoef_flowreg Ext AF reg l/s SNVT_flow Present extract airflow regulator setpoint nvosf_pressure Sup air duct pres Pa SNVT_press_p Present supply air duct pressure nvosf_press_reg Sup air duct pres reg Pa SNVT_press_p Present supply air duct pressure regulator setpoint nvoef_pressure Ext air duct pres Pa SNVT_press_p Present extract air duct pressure nvoef_press_reg Ext air duct pres reg Pa SNVT_press_p Present extract air duct pressure regulator setpoint nvosf_boost_lev In sig supp air VAV dmnd or bst func % SNVT_lev_percent Present input signal for supply air VAV demand or boosting function nvosf_boost_reg SA VAV dmnd regulator % SNVT_lev_percent Present supply air VAV demand regulator setpoint nvoef_boost_lev In sig EA VAV dmnd or bst func % SNVT_lev_percent Present input signal for extract air VAV demand or boosting function nvoef_boost_reg In sig EA VAV dmnd or bst func % SNVT_lev_percent Present supply air VAV demand regulator setpoint nvofanspeed Fan Speed Output % SNVT_switch Present running level for the supply air fan nvoef_speed Run lvl ext air fan % SNVT_switch Present running level for the extract air fan nvosf_effect Consm lev for sup air fan W SNVT_power Present power consumption level for the supply air fan nvoef_effect Consm lev for ext air fan W SNVT_power Present power consumption level for the extract air fan nvosfp SFP SNVT_lev_percent SFP supply air + extract air nvosf_frequency Freq sup air fan Hz SNVT_freq_hz Present frequency level for the supply air fan nvoef_frequency Freq ext air fan Hz SNVT_freq_hz Present frequency level for the extract air fan nvosf_voltage Volt sup air fan 0-500V SNVT_volt Present voltage level for the supply air fan nvoef_voltage Volt ext air fan 0-500V SNVT_volt Present voltage level for the extract air fan nvosf_current Current sup air fan A SNVT_amp Present current level for the supply air fan nvoef_current Current ext air fan A SNVT_amp Present current level for the extract air fan nvosf_fan_press Sup air pres Pa SNVT_press_p Present airflow pressure in the supply air fan inlet nvoef_fan_press Ext air pres Pa SNVT_press_p Present airflow pressure in the extract air fan inlet nvoeffectsetpt Effective Setpoint Output (sup air) C SNVT_temp_p Present supply air temperature regulator setpoint nvoeatempset_reg Ext air temp regulator C SNVT_temp_p Present extract air temperature regulator setpoint nvosatemp Sup air temp C SNVT_temp_p Present supply air temperature nvoeatemp Ext air/room temp in unit C SNVT_temp_p Present extract air/room temperature in the unit nvoouttemp Outd air temp in unit C SNVT_temp_p Present outdoor air temperature in the unit nvispacetemp Space Temperature Input C SNVT_temp_p nvospacetemp Space Temperature Input C SNVT_temp_p Present room temperature external from the unit. nvispacetemp Not used in present SW version. Se also nviroomtempcomse NV index nvooutdoortemp Outdoor Air Temperature Output C SNVT_temp_p Present outdoor air temperature external from the unit nvofrosttemp Anti frost temp C SNVT_temp_p Present anti frost temperature for water reheating coils nvotempsens3 Tempsens C SNVT_temp_p Present temperature for temp sensor no nvotempsens4 Tempsens C SNVT_temp_p Present temperature for temp sensor no nvoheatprimary Prim Heat Output % SNVT_lev_percent Present running level of heat exchange. 8 Specifications are subject to alteration without notice.

9 nvoheatsecondary Sec Heat Output % SNVT_lev_percent Present level of reheat nvosfdownreg Lev sup air dwn reg % SNVT_lev_percent Present level of supply airflow down regulation nvoexreg Lev extra reg seq % SNVT_lev_percent Present level of the extra regulation sequence nvocoolprimary Primary Cool Output % SNVT_lev_percent Present level of cooling nvoheatboost Lev heat boost % SNVT_lev_percent Present level of heating boost nvocoolboost Lev cool boost % SNVT_lev_percent Present level of cooling boost nvohx_pressure Press drop rot heat exchr Pa SNVT_press_p Present pressure drop for the rotary heat exchanger nvohx_pressalr Press drop alarm lmt rot heat exchr Pa SNVT_press_p Present pressure drop alarm limit for the rotary heat exchanger nvohx_temp_cont HX temp inside control C SNVT_temp_p Present temperature inside the control unit for the rotary heat exchanger nvoeffectred Lev elctr rhtrs % SNVT_lev_percent Present level of max output signal for electrical reheaters, active during low supply airflow nvofrostsetop Anti frost temp set operation C SNVT_temp_p Present anti frost temperature setpoint for water reheating coils during unit operation nvofrostsetstop Anti frost temp set stop C SNVT_temp_p Present anti frost temperature setpoint for water reheating coils when the unit is in stop nvofrostallimit Anti frost temp alarm limit C SNVT_temp_p Setting of antifrost temperature alarm limit nvosa_filterlev Sup air flt prs drop Pa SNVT_press_p Present supply air filter pressure drop nvosa_filteralr Sup air flt prs drop alrm lev Pa SNVT_press_p Present supply air filter pressure alarm limit nvosa_filterlevn Sup air flt prs drop new Pa SNVT_press_p Supply air filter pressure saved from calibration nvoea_filterlev Ext air flt prs drop Pa SNVT_press_p Present extract air filter pressure drop nvoea_filteralr Ext air flt prs drop alrm lev Pa SNVT_press_p Present extract air filter pressure alarm limit nvoea_filterlevn Ext air flt prs drop new Pa SNVT_press_p Extract air filter pressure saved from calibration nvotempdisplace Temp displacement frm inpt sig C SNVT_temp_p Present temperature displacement from input signal nvobattype Reheat coil type 0-20 SNVT_count Present connected reheat coil type nvocoolstep_rem Time btwn cool step shift 0-600s SNVT_time_sec Present time between cool step shift nvocool1_res_rem Time btwn strts of cool rly s SNVT_time_sec Present time between two starts of cool relay nvocool2_res_rem Time btwn strts of cool rly s SNVT_time_sec Present time between two starts of cool relay nvocpuver Prog ver main ctrl unit SNVT_count Present programversion for the main control unit nvoweekday Day of week SNVT_date_day Present weekday for the unit s internal clock nvoextendls_hour Extnd low spd hour 0-23 SNVT_time_hour Present time for extended low speed operation nvoextendls_min Extnd low spd min 0-59 SNVT_time_min Present time for extended low speed operation nvoextendhs_hour Extnd high spd hour 0-23 SNVT_time_hour Present time for extended high speed operation nvoextendhs_min Extnd high spd min 0-59 SNVT_time_min Present time for extended high speed operation nvosf_optime Sup air fan op time days SNVT_count Present operation time for the supply air fan, measured in minutes and present in days (24h) nvoef_optime Ext air fan op time days SNVT_count Present operation time for the extract air fan, measured in minutes and present in days (24h) nvocool_optime Cooling op time days SNVT_count Present operation time for cooling, measured in minutes and present in days (24h). Specifications are subject to alteration without notice. 9

10 nvohx_optime HeatX op time days SNVT_count Present operation time for heat exchange, measured in minutes and present in days (24h) nvoheat_optime Reheat op time days SNVT_count Present operation time for reheat, measured in minutes and present in days (24h) nvoactive_alarm Alrm SNVT_count Present tripped alarm number with highest priority nvodelay_alarm1 Delayed Alrm SNVT_count Present active alarm in delay nvodelay_alarm2 Delayed Alrm SNVT_count Present active alarm in delay nvodelay_alarm3 Delayed Alrm SNVT_count Present active alarm in delay nvosf_size Sup air fan size SNVT_count Present supply air fan size nvoef_size Ext air fan size SNVT_count Present extract air fan size nvounitopm2_00 Stop 0-1 SNVT_switch Operation mode 2=Stop nvounitopm2_01 Ext Stop 0-1 SNVT_switch Operation mode 2=Ext. Stop nvounitopm2_02 Com Stop SNVT_switch Operation mode 2=Com. Stop nvounitopm2_03 High spd 0-1 SNVT_switch Operation mode 2=High speed nvounitopm2_04 Smrnight Cool 0-1 SNVT_switch Operation mode 2=Summer night cooling nvounitopm2_05 Int nightheat 0-1 SNVT_switch Operation mode 2=Int. night heat nvounitopm2_06 Lw spd 0-1 SNVT_switch Operation mode 2=Low speed nvounitopm2_07 Ext high spd 0-1 SNVT_switch Operation mode 2=Ext. high speed nvounitopm2_08 Com high spd 0-1 SNVT_switch Operation mode 2=Com. high speed nvounitopm2_09 Switch clk stop 0-1 SNVT_switch Operation mode 2=Switch clock=stop nvounitopm2_10 High spd 0-1 SNVT_switch 1Operation mode 2=High speed nvounitopm2_11 Lw spd 0-1 SNVT_switch Operation mode 2=Low speed nvounitopm2_12 High spd 0-1 SNVT_switch Operation mode 2=High speed nvounitopm2_13 Ext Lw spd 0-1 SNVT_switch Operation mode 2=Ext. low speed nvounitopm2_14 Com Lw spd 0-1 SNVT_switch Operation mode 2=Com. low speed nvounitopm2_15 Lw spd 0-1 SNVT_switch Operation mode 2=Low speed nvounitopm2_16 Switch clk stop 0-1 SNVT_switch Operation mode 2=Switch clock=stop nvounitopm2_17 Lw spd stop 0-1 SNVT_switch Operation mode 2=Low speed=stop nvounitopm2_18 Com Stop SNVT_switch Operation mode 2=Com. Stop nvounitopm3_ SNVT_switch Operation mode 3=Not used nvounitopm3_01 Coold air recovery 0-1 SNVT_switch Operation mode 3=Coold air recovery nvounitopm3_02 Cooling boost 0-1 SNVT_switch Operation mode 3=Cooling boost nvounitopm3_03 SA down reg 0-1 SNVT_switch Operation mode 3=SA down regulation nvounitopm3_04 HX defr 0-1 SNVT_switch Operation mode 3=HX defrosting nvounitopm3_05 Anti frost func. Act 0-1 SNVT_switch Operation mode 3=Anti frost func. active nvounitopm3_06 Effect reduct 0-1 SNVT_switch Operation mode 3=Effect reduction nvounitopm3_07 Startup 0-1 SNVT_switch Operation mode 3=Startup nvounitopm3_08 Zero cal 0-1 SNVT_switch Operation mode 3=Zero calibration Specifications are subject to alteration without notice.

11 nvounitopm3_09 Ext Lw spd 0-1 SNVT_switch Operation mode 3=Extended low speed nvounitopm3_10 Ext High spd 0-1 SNVT_switch Operation mode 3=Extended high speed nvounitopm3_11 Air adjust 0-1 SNVT_switch Operation mode 3=Air adjustment nvounitopm3_12 Cooling off 0-1 SNVT_switch Operation mode 3=Cooling off nvounitopm3_13 Purging R.HX 0-1 SNVT_switch Operation mode 3=Purging R.HX nvounitopm3_14 Ext R.HX. Op 0-1 SNVT_switch Operation mode 3=Extended R.HX. op nvounitopm3_15 Filter cal 0-1 SNVT_switch Operation mode 3=Filter calibration nvounitopm3_16 RH.HX cal 0-1 SNVT_switch Operation mode 3=R.HX. calibration nvounitopm3_17 Morning bst 0-1 SNVT_switch Operation mode 3=Morning boost nvounitopm3_18 Heat bst 0-1 SNVT_switch Operation mode 3=Heating boost nvounitopm3_19 Alrm 0-1 SNVT_switch Operation mode 3=Alarm nvounitopm3_20 CoolDX press red 0-1 SNVT_switch Operation mode 3=CoolDX pressure reduction nvounitopm3_21 Startup EA fan 0-1 SNVT_switch Operation mode 3=Startup extract air fan nvounitopm3_22 Fan heat retention 0-1 SNVT_switch Operation mode 3=Fan heat retention nvounitopm1_stop Stop 0-1 SNVT_switch Present manual operation set on the unit s handterminal, Stop nvounitopm1_auto Auto 0-1 SNVT_switch Present manual operation set on the unit s handterminal, Auto operation nvounitopm1_ls LS 0-1 SNVT_switch Present manual operation set on the unit s handterminal, Manual low speed nvounitopm1_hs HS 0-1 SNVT_switch Present manual operation set on the unit s handterminal, Manual high speed nvoheatprimaryre Heat exchange reg % SNVT_lev_percent Present level of heat exchange regulator RX/CX/PX nvoea_humidity Extract air-humidity % SNVT_lev_percent Present level of extract air-humidity nvoea_humidity_t Extract air-humidity temp C SNVT_temp_p Present temperature inside extract air-humidity sensor nvoea_dewpoint Extract air-dewpoint C SNVT_temp_p Calculated extract air-dewpoint nvochilled_w_t Chilled water temp C SNVT_temp_p Present chilled water temperature nvochilled_w_t_r Chilled water temp reg C SNVT_temp_p Present chilled water temperature regulator setpoint nvochilled_w_rel Chilled water output % SNVT_lev_percent Present level of chilled water output nvosa_dewpoint_r Supply air-dewpoint reg C SNVT_temp_p Present supply air-dewpoint regulator setpoint nvosa_humidity Supply air-humidity % SNVT_lev_percent Present level of supply air-humidity nvosa_humidity_t Supply air-humidity temp C SNVT_temp_p Present temperature inside supply air-humidity sensor nvosa_dewpoint Supply air-dewpoint C SNVT_temp_p Calculated supply air-dewpoint nvochx_temp C.HX. Temp C SNVT_temp_p Present temperature of coil heat exchanger nvophx_temp_1 P.HX. Temp C SNVT_temp_p Present temperature 1 of plate heat exchanger nvophx_temp_2 P.HX. Temp C SNVT_temp_p Present temperature 2 of plate heat exchanger nvopchx_humidity P/C.HX. Humidity % SNVT_lev_percent Present level of air-humidity in plate/coil heat exchanger nvorhx_eff R.HX. Efficiency % SNVT_lev_percent Calculated level of rotary heat exchanger efficiency nvochx_valve_op C.HX. Valve output % SNVT_lev_percent Present level of coil heat exchanger valve output. Specifications are subject to alteration without notice. 11

12 nvophx_bypass_op P.HX. bypass output % SNVT_lev_percent Present level of plate heat exchanger bypass output nvosa_pfilterlev Sup air preflt prs drop Pa SNVT_press_p Present supply air prefilter pressure drop nvosa_pfilteralr Sup air preflt prs drop alrm lev Pa SNVT_press_p Present supply air prefilter pressure alarm limit nvosa_pfiltlevn Sup air preflt prs drop new Pa SNVT_press_p Supply air prefilter pressure saved from calibration nvoea_pfilterlev Ext air preflt prs drop Pa SNVT_press_p Present extract air prefilter pressure drop nvoea_pfilteralr Ext air preflt prs drop alrm lev Pa SNVT_press_p Present extract air prefilter pressure alarm limit nvoea_pfiltlevn Ext air preflt prs drop new Pa SNVT_press_p Extract air prefilter pressure saved from calibration nvoxzoneheatsec Xzone Sec Heat Output % SNVT_lev_percent Present level of Xzone reheat nvoxzonefrosttem Xzone Anti frost temp C SNVT_temp_p Present anti frost temperature for water reheating coils nvoxzonecoolprim Xzone Primary Cool Output % SNVT_lev_percent Present level of Xzone cooling nvoxzonecoolstep Time btwn Xzone cool step shift 0-600s SNVT_time_sec Present time between Xzone cool step shift nvoxzonecool1res Time btwn strts of Xzone cool rly s SNVT_time_sec Present time between two starts of Xzone cool relay nvoxzonecool2res Time btwn strts of Xzone cool rly s SNVT_time_sec Present time between two starts of Xzone cool relay nvoxz_satemp_reg Xzone SA temp reg C SNVT_temp_p Present Xzone supply air temperature regulator setpoint nvoxz_eatemp_reg Xzone EA temp reg C SNVT_temp_p Present Xzone extract air temperature regulator setpoint nvoxzone_sa_temp Xzone SA temp C SNVT_temp_p Present Xzone supply air temperature nvoxzone_ea_temp Xzone EA/Room temp C SNVT_temp_p Present Xzone extract air/room temperature nvopreheat_temp Pre-heat air temp C SNVT_temp_p Present pre-heating air temperature nvopreheat_level Pre-heat level % SNVT_lev_percent Present level of pre-heating nvopreheatfrostt Pre-heat anti frost temp C SNVT_temp_p Present anti frost temperature for water pre-heating coils nvoreco2_co2_inp ReCO2 CO2 input % SNVT_lev_percent Present input signal for ReCO2 CO nvoreco2_intdamp ReCO2 internal damper output % SNVT_lev_percent Present output signal for ReCO2 internal damper nvoreco2_extdamp ReCO2 external damper output % SNVT_lev_percent Present output signal for ReCO2 external damper nvoreco2_outairf ReCO2 outdoor airflow l/s SNVT_flow Present ReCO2 outdoor airflow nvoreco2_oaf_reg ReCO2 outdoor airflow reg l/s SNVT_flow Present ReCO2 outdoor airflow regulator setpoint nvoreco2_oafpres ReCO2 outdoor airflow press Pa SNVT_press_p Present ReCO2 outdoor airflow pressure nvopreheatoptime Preheat operation time SNVT_count Present operation time for preheat, measured in minutes and present in days (24h) nvoxz_cooloptime Xzone cool operation time SNVT_count Present operation time for Xzone cooling, measured in minutes and present in days (24h) nvoxz_reheatopti Xzone reheat operation time SNVT_count Present operation time for Xzone reheat, measured in minutes and present in days (24h) nvisf_lsflow Sup air flow lw spd l/s SNVT_flow nvosf_lsflow Sup air flow lw spd Supply airflow setpoint for the unit when running in low speed operation nvisf_hsflow Sup air flow high spd l/s SNVT_flow nvosf_hsflow Sup air flow high spd Supply airflow setpoint for the unit when running in high speed operation nvisf_maxflow SA Max speed AF l/s SNVT_flow nvosf_maxflow SA Max speed AF Supply airflow max. limit for the unit when the low/high speed operation setpoint is altered by boosting function etc nvisf_minflow SA Min speed AF l/s SNVT_flow nvosf_minflow SA Min speed AF Supply airflow min. limit for the unit when the low/high speed operation setpoint is altered when running in fan regulation mode VAV demand Specifications are subject to alteration without notice.

13 nvief_lsflow Ext AF lw spd l/s SNVT_flow nvoef_lsflow Ext AF lw spd Extract airflow setpoint for the unit when running in low speed operation nvief_hsflow Ext AF high spd l/s SNVT_flow nvoef_hsflow Ext AF high spd Extract airflow setpoint for the unit when running in high speed operation nvief_maxflow EA Max spd airflow l/s SNVT_flow nvoef_maxflow EA Max spd airflow Extract airflow max. limit for the unit when the low/high speed operation setpoint is altered by boosting function etc nvief_minflow EA Min spd airflow l/s SNVT_flow nvoef_minflow EA Min spd airflow Extract airflow min. limit for the unit when the low/high speed operation setpoint is altered when running in fan regulation mode VAV demand nvisf_lspressure SA Low spd pres Pa SNVT_press_p nvosf_lspressure SA Low spd pres Supply air duct pressure setpoint for the unit when running in low speed operation nvisf_hspressure SA High spd pres Pa SNVT_press_p nvosf_hspressure SA High spd pres Supply air duct pressure for the unit when running in high speed operation nvisf_maxspeed SA Max spd output sig % SNVT_lev_percent nvosf_maxspeed SA Max spd output sig Max. limit for the supply air fan speed when running in pressure regulation mode nvisf_maxpress SA Max spd pres Pa SNVT_press_p nvosf_maxpress SA Max spd pres Supply air duct pressure max. limit for the unit when the low/high speed operation setpoint is altered by boosting function etc nvief_lspressure EA Low spd pres Pa SNVT_press_p nvoef_lspressure EA Low spd pres stat Extract air duct pressure setpoint for the unit when running in low speed operation nvief_hspressure EA High spd pres Pa SNVT_press_p nvoef_hspressure EA High spd pres Extract air duct pressure setpoint for the unit when running in high speed operation nvief_maxspeed EA Max spd output sig % SNVT_lev_percent nvoef_maxspeed EA Max spd output sig Max. limit for the extract air fan speed when running in pressure regulation mode nvief_maxpress EA Max spd pres Pa SNVT_press_p nvoef_maxpress EA Max spd pres Extract air duct pressure max. limit for the unit when the low/high speed operation setpoint is altered by boosting function etc nvisf_lsdemand SA Low spd dmnd % SNVT_lev_percent nvosf_lsdemand SA Low spd dmnd Supply air setpoint for the 0-10V input signal on terminal for the unit when running in low speed operation nvisf_hsdemand SA High spd dmnd % SNVT_lev_percent nvosf_hsdemand SA High spd dmnd Supply air setpoint for the 0-10V input signal on terminal for the unit when running in high speed operation nvief_lsdemand EA Low spd dmnd % SNVT_lev_percent nvoef_lsdemand EA Low spd dmnd Extract air setpoint for the 0-10V input signal on terminal for the unit when running in low speed operation nvief_hsdemand EA High spd dmnd % SNVT_lev_percent nvoef_hsdemand EA High spd dmnd Extract air setpoint for the 0-10V input signal on terminal for the unit when running in high speed operation nvisf_flowzone SA AF reg zone SNVT_lev_percent nvosf_flowzone SA AF reg zone Supply airflow regulation zone setting in % of the present airflow setpoint that the regulator is allowed to work within nvisf_flowfactor SA AF C-fct SNVT_multiplier nvosf_flowfactor SA AF C-fct Supply airflow regulator affection setting nvief_flowzone EA AF reg zone SNVT_lev_percent nvoef_flowzone EA AF reg zone Extract airflow regulation zone setting in % of the present airflow setpoint that the regulator is allowed to work within nvief_flowfactor EA AF C-fct SNVT_multiplier nvoef_flowfactor EA AF C-fct Extract airflow regulator affection setting nvisf_presszone SA Pres reg zone SNVT_lev_percent nvosf_presszone SA Pres reg zone Supply air pressure regulation zone setting in % of the present duct pressure setpoint that the regulator is allowed to work within. Specifications are subject to alteration without notice. 13

14 nvisf_pressfactor SA Pres C-fct SNVT_multiplier nvosf_pressfactor SA Pres C-fct Supply air pressure regulator affection setting nvief_presszone EA Pres reg zone SNVT_lev_percent nvoef_presszone EA Pres reg zone Extract air pressure regulation zone setting in % of the present duct pressure setpoint that the regulator is allowed to work within nvief_pressfactor EA Pres C-fct SNVT_multiplier nvoef_pressfactor EA Pres C-fct Extract air pressure regulator affection setting nvisf_demandpb SA Dmnd P-band SNVT_lev_percent nvosf_demandpb SA Dmnd P-band Supply air demand regulator P-band setting nvisf_demfactor SA Dmnd C-fct SNVT_multiplier nvosf_demfactor SA Dmnd C-fct Supply air demand regulator affection setting nvief_demandpb EA Dmnd P-band SNVT_lev_percent nvoef_demandpb EA Dmnd P-band Extract air demand regulator P-band setting nvief_demfactor EA Dmnd C-fct SNVT_multiplier nvoef_demfactor EA Dmnd C-fct Extract air demand regulator affection setting nviers1diff SA temp diff set ERS C SNVT_temp_p nvoers1diff SA temp diff set ERS 1 Supply air temperature difference setting accordning to the diagram for ERS nviers1brkpnt ERS 1 Brkepnt SNVT_temp_p C nvoers1brkpnt ERS 1 Brkepnt Breakpoint setting accordning to the diagram for ERS nviers2_x1 ERS 2 Brkepnt_X C SNVT_temp_p nvoers2_x1 ERS 2 Brkepnt_X1 Breakpoint X1 setting accordning to the diagram for ERS nviers2_y1 ERS 2 Brkepnt_Y C SNVT_temp_p nvoers2_y1 ERS 2 Brkepnt_Y1 Breakpoint Y1 setting accordning to the diagram for ERS nviers2_x2 ERS 2 Brkepnt_X C SNVT_temp_p nvoers2_x2 ERS 2 Brkepnt_X2 Breakpoint X2 setting accordning to the diagram for ERS nviers2_y2 ERS 2 Brkepnt_Y C SNVT_temp_p nvoers2_y2 ERS 2 Brkepnt_Y2 Breakpoint Y2 setting accordning to the diagram for ERS nviers2_x3 ERS 2 Brkepnt_X C SNVT_temp_p nvoers2_x3 ERS 2 Brkepnt_X3 Breakpoint X3 setting accordning to the diagram for ERS nviers2_y3 ERS 2 Brkepnt_Y C SNVT_temp_p nvoers2_y3 ERS 2 Brkepnt_Y3 Breakpoint Y3 setting accordning to the diagram for ERS nvisetpoint Temp stpnt Input (absolute) C SNVT_temp_p nvosetpoint Temp stpnt (absolute) C SNVT_temp_p Supply air temperature setting, for supply air temp regulation mode nvieatempset EA Temp C SNVT_temp_p nvoeatempset EA Temp Extract air/room temperature setting, for Extract air/room temp regulation mode nviminsatemp SA Min temp C SNVT_temp_p nvominsatemp SA Min temp Supply air min.setpoint during EA/room regulation mode nvimaxsatemp SA Max temp C SNVT_temp_p nvomaxsatemp SA Max temp Supply air max.setpoint during EA/room regulation mode nvisa_pb SA Temp P-band SNVT_temp_p nvosa_pb SA Temp P-band Supply air temperature regulator P-band setting nviea_pb EA Temp P-band SNVT_temp_p nvoea_pb EA Temp P-band Extract air/room temperature regulator P-band setting nvisa_hxfactor SA HX. Reg C-fct SNVT_multiplier nvosa_hxfactor SA HX. Reg C-fct Supply air heat exchange regulator affection setting Specifications are subject to alteration without notice.

15 nviea_hxfactor EA HX. Reg C-fct SNVT_multiplier nvoea_hxfactor EA HX. Reg C-fct Extract air/room heat exchange regulator affection setting nvisa_rhfactor SA Heat Reg C-fct SNVT_multiplier nvosa_rhfactor SA Heat Reg C-fct Supply air reheat regulator affection setting nviea_rhfactor EA Heat Reg C-fct SNVT_multiplier nvoea_rhfactor EA Heat Reg C-fct Extract air/room reheat regulator affection setting nvisa_exhfactor SA X Reg heat C-fct SNVT_multiplier nvosa_exhfactor SA X Reg heat C-fct Supply air extra regulation sequence for reheating regulator affection setting nvisa_excfactor SA X Reg cool C-fct SNVT_multiplier nvosa_excfactor SA X Reg cool C-fct Supply air extra regulation sequence for cooling regulator affection setting nviea_exhfactor EA X Reg heat C-fct SNVT_multiplier nvoea_exhfactor EA X Reg heat C-fct Extract air extra regulation sequence for reheating regulator affection setting nviea_excfactor EA X Reg cool C-fct SNVT_multiplier nvoea_excfactor EA X Reg cool C-fct Extract air extra regulation sequence for cooling regulator affection setting nvisa_redfactor SA Dwn Reg C-fct SNVT_multiplier nvosa_redfactor SA Dwn Reg C-fct Supply air reheat regulator affection setting nviea_redfactor EA Dwn Reg C-fct SNVT_multiplier nvoea_redfactor EA Dwn Reg C-fct Not used in present SW version nvisacoolfactor SA Cool reg C-fct SNVT_multiplier nvosacoolfactor SA Cool reg C-fct Supply air cool regulator affection setting nvieacoolfactor EA Cool reg C-fct SNVT_multiplier nvoeacoolfactor EA Cool reg C-fct Extract air/room cool regulator affection setting nvisacoolbfactor SA Clng bst C-fct SNVT_multiplier nvosacoolbfactor SA Clng bst C-fct Supply air cooling boost affection setting nvieacoolbfactor EA Clng bst C-fct SNVT_multiplier nvoeacoolbfactor EA Clng bst C-fct Extract air/room cooling boost regulator affection setting nvihxalarmlimit HX Pressure alarm set Pa SNVT_press_p nvohxalarmlimit HX Pressure alarm set Heat exchange pressure alarm limit setting (alarm no.38) nvipchx_def_pb P/C.HX. defrost P-band SNVT_temp_p nvopchx_def_pb P/C.HX. defrost P-band Plate/coil heat exchange defrost P-band setting nvipchx_def_fact P/C.HX. defrost C-factor SNVT_multiplier nvopchx_def_fact P/C.HX. defrost C-factor Plate/coil heat exchange defrost C-factor setting nvicooloff_set Cooling off AF set in % of max 10-50% SNVT_lev_percent nvocooloff_set Cooling off AF set in % of max Cooling off airflow setting in % of max. airflow nvisfdownregnz SA Down reg ntrl zone C SNVT_temp_p nvosfdownregnz SA Down reg ntrl zone Neutral zone setting before downregulation is permitted nvicoollimit1 Cool Outd temp limit C SNVT_temp_p nvocoollimit1 Cool Outd temp limit 1 Outdoor temperature limit setting for cooling stage nvicoollimit2 Cool Outd temp limit C SNVT_temp_p nvocoollimit2 Cool Outd temp limit 2 Outdoor temperature limit setting for cooling stage nvicoollimit3 Cool Outd temp limit C SNVT_temp_p nvocoollimit3 Cool Outd temp limit 3 Outdoor temperature limit setting for cooling stage 3. Specifications are subject to alteration without notice. 15

16 nvicoolnz Temp reg ntrl zone C SNVT_temp_p nvocoolnz Temp reg ntrl zone Neutral zone setting before shift between heating and cooling nvisfcoolminflow SA Cool min air flow l/s SNVT_flow nvosfcoolminflow SA Cool min air flow Supply air min. air flow setting for cooling nviefcoolminflow EA Cool min air flow l/s SNVT_flow nvoefcoolminflow EA Cool min air flow Extract air min. air flow setting for cooling nvih_booststart Heating bst strt limit C SNVT_temp_p nvoh_booststart Heating bst strt limit Heating boost start temperature limit nvic_booststart Cooling bst strt limit C SNVT_temp_p nvoc_booststart Cooling bst strt limit Cooling boost (comfort) start temperature limit nvisa_filterlim SA Fltr alarm limit Pa SNVT_press_p nvosa_filterlim SA Fltr alarm limit Supply air filter pressure alarm limit setting nviea_filterlim EA Fltr alarm limit Pa SNVT_press_p nvoea_filterlim EA Fltr alarm limit Extract air filter pressure alarm limit setting nvinh_starttemp Int Nght ht room strt temp C SNVT_temp_p nvonh_starttemp Int Nght ht room strt temp Intermittent night heat function, extract air temperature setting for start nvinh_stoptemp Int Nght ht room stop temp C SNVT_temp_p nvonh_stoptemp Int Nght ht room stop temp Intermittent night heat function, extract air temperature setting for stop nvinh_satempset Int Nght ht SA temp C SNVT_temp_p nvonh_satempset Int Nght ht SA temp Intermittent night heat function, supply air temperature setpoint during night heat nvinh_sfflowset Int Nght ht SA airflow l/s SNVT_flow nvonh_sfflowset Int Nght ht SA airflow Intermittent night heat function, supply airflow setpoint during night heat nvinh_efflowset Int Nght ht EA airflow l/s SNVT_flow nvonh_efflowset Int Nght ht EA airflow Intermittent night heat function, extract airflow setpoint during night heat nvinc_starttemp Smr Nght cl room strt temp C SNVT_temp_p nvonc_starttemp Smr Nght cl room strt temp Summer night cool function, extract air temperature setting for start nvinc_stoptemp Smr Nght cl room stop temp C SNVT_temp_p nvonc_stoptemp Smr Nght cl room stop temp Summer night cool function, extract air temperature setting for stop nvinc_outlimit Smr nght cl outd temp lmt C SNVT_temp_p nvonc_outlimit Smr nght cl outd temp lmt Summer night cool function, outdoor temperature limit nvinc_satempset Smr nght cl SA temp C SNVT_temp_p nvonc_satempset Smr nght cl SA temp Summer night cool function, supply air temperature setpoint during summer night cool nvioutcomptempx1 Outd Temp Cmp Wntr X (- SNVT_temp_p 10.00) C nvooutcomptempx1 Outd Temp Cmp Wntr X1 Endpoint of winter compensation nvioutcomptempx2 Outd Temp Cmp Wntr X C SNVT_temp_p nvooutcomptempx2 Outd Temp Cmp Wntr X2 Startpoint of winter compensation nvioutcomptempy1 Outd Temp Cmp Wntr Y C SNVT_temp_p nvooutcomptempy1 Outd Temp Cmp Wntr Y1 Level of winter compensation at X nvioutcomptempx3 Outd Temp Cmp Wntr X C SNVT_temp_p nvooutcomptempx3 Outd Temp Cmp Wntr X3 Startpoint of summer compensation nvioutcomptempx4 Outd Temp Cmp Wntr X C SNVT_temp_p nvooutcomptempx4 Outd Temp Cmp Wntr X4 Endpoint of summer compensation nvioutcomptempy2 Outd Temp Cmp Wntr Y C SNVT_temp_p nvooutcomptempy2 Outd Temp Cmp Wntr Y2 Level of summer compensation at X Specifications are subject to alteration without notice.

17 nvioutcompflowx1 Outd Temp Cmp Wntr X (- SNVT_temp_p 10.00) C nvooutcompflowx1 Outd Temp Cmp Wntr X1 Endpoint of winter compensation nvioutcompflowx2 Outd Temp Cmp Wntr X C SNVT_temp_p nvooutcompflowx2 Outd Temp Cmp Wntr X2 Startpoint of winter compensation nvioutcompflowy1 Outd Temp Cmp Wntr Y % SNVT_lev_percent nvooutcompflowy1 Outd Temp Cmp Wntr Y1 Level of airflow compensation at X nviexregmaxsign X Reg. Seq max output % SNVT_lev_percent nvoexregmaxsign X Reg. Seq max output Maximum output signal setting for the extra regulation sequence nvieamintemp EA min temp alarm limit no C SNVT_temp_p nvoeamintemp EA min temp alarm limit no 40 Setting for min extract air /room temp alarm no nvisatempdev SA Deviation alarm limit C SNVT_temp_p nvosatempdev SA Deviation alarm limit Setting for supply air temperature below present setpoint, alarm no nvisfregmode SA Fan reg mode 0-3 SNVT_count nvosfregmode SA Fan reg mode Setting of regulation type for the supply air fan. 0=Airflow reg, 1=Pressure reg, 2=Demand reg, 3=Slave controlled by EA fan nviefregmode EA Fan reg mode 0-3 SNVT_count nvoefregmode EA Fan reg mode Setting of regulation type for the extract air fan. 0=Airflow reg, 1=Pressure reg, 2=Demand reg, 3=Slave controlled by SA fan nviers1step ERS Step 1-4 SNVT_count nvoers1step ERS Step Setting of curve when temperature is above breakpoint nvitempregmode Temp reg mode 0=ERS1 1=ERS2 2=SA 3=EA/Room 0-3 SNVT_count nvotempregmode Temp reg mode 0=ERS1 1=ERS2 2=SA 3=EA/Room Setting of temperature regulation type. 0=ERS 1 reg, 1=ERS 2 reg, 2=SA reg, 3=EA/Room reg nvicooloff_time Cooling off periode s SNVT_time_sec nvocooloff_time Cooling off periode Time setting for cooling off electrical heating coil nvicoolstep_time Cool step time 0-600s SNVT_time_sec nvocoolstep_time Cool step time Time setting between cool step shift nvicool_restart Cool restart time s SNVT_time_sec nvocool_restart Cool restart time Setting of time between two starts of the cool relays nvicoolregmode Cool regulation mode 0-6 SNVT_count nvocoolregmode Cool regulation mode Setting of cool regulation type 0=Controlled 0-10V 1=Controlled 10-0V 2=On/Off 1-step 3=On/Off 2-steps 4=On/Off 3-steps binary 5=CoolDX economi 6=CoolDX comfort nviheatboostmode Heat bst reg mode 0=Deac, 1=Act 0-1 SNVT_count nvoheatboostmode Heat bst reg mode 0=Deac, 1=Act Setting for heating boost function. 0=Deactive, 1=Active nvicoolboostmode Cooling bst reg mode 0-5 SNVT_count nvocoolboostmode Cooling bst reg mode Setting of cooling boost regulation type. 0=Inactive. 1=Comfort. 2=Economy. 3=Sequence. 4=Comfort+economy. 5=Economy+sequence nvifiltercalmode Filt clbr mode 0-5 SNVT_count nvofiltercalmode Filt clbr mode Setting for requiered filtercalibration. 0=Inactive. 1=SA+EA-Filter. 2=SA-Filter. 3=EA-Filter. 4=HX. 5=ReCO nviair_ad_time_m Air adjst min SNVT_time_min nvoair_ad_time_m Air adjst min Setting for amount of minutes to air adjustment function. Specifications are subject to alteration without notice. 17

FUNCTIONAL PROFILE: Gateway Lonworks FTT-10, TBLZ , Version 1.00 COMPACT Sizes 02-03, Program Version 1.00

FUNCTIONAL PROFILE: Gateway Lonworks FTT-10, TBLZ , Version 1.00 COMPACT Sizes 02-03, Program Version 1.00 FUNCTIONAL PROFILE: Gateway Lonworks FTT-10, TBLZ-4-1-1-41, Version 1.00 COMPACT Sizes 02-03, Program Version 1.00 Specifications are subject to alteration without notice. www.swegon.com General This document

More information

GOLD_E_LonWorks_140611

GOLD_E_LonWorks_140611 FUNCTIONAL PROFILE: GOLDen GATE Lonworks FTT-10, TBLZ-3-1-1-41, Version 1.00 GOLD RX/PX/CX/SD, GENERATION E Applicable to program version 1.10 and newer versions Specifications are subject to alteration

More information

Product Data. Voyager TM Rooftop air conditioner or heat pump unit with LonTalk communication interface for Voyager TM rooftop controls

Product Data. Voyager TM Rooftop air conditioner or heat pump unit with LonTalk communication interface for Voyager TM rooftop controls Voyager TM Rooftop air conditioner or heat pump unit with LonTalk communication interface for Voyager TM rooftop controls LonTalk Communication Interface April 2002 Overview Each Voyager rooftop air conditioner

More information

Tracer Controls. Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN

Tracer Controls. Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN Tracer Controls Tracer ZN.520: Unit Controller for Terminal Products TD-PRM001-EN 2 TD-PRM001-EN General Tracer ZN.520 unit controller is a microprocessor-based direct digital controller that controls

More information

Corp L (Supersedes 02/2008)

Corp L (Supersedes 02/2008) Service Literature Corp. 0627L5 0608 (Supersedes 02/2008) IMC LonTalk Module GENERAL The IMC LonTalk module allows communication between the Lennox IMC M17 (version 5.02 and higher) or M18 controller and

More information

Applications Application is compatible with Q1 Hardware. Compatible with Fan Coil Unit equipment up to 4 stages of cooling or heating, analog or floating-point valves or digital stages, discharge pressure/variable

More information

Applications Application is compatible with Q1 Hardware. Compatible with Heat Pump Unit equipment up to 4 stages of cooling or heating, analog or floating-point valves or digital stages, discharge pressure/variable

More information

Document # R00

Document # R00 Viconics VT7200 Series PIR Ready Zoning Thermostats General The VT7200 series PIR Ready low-voltage microprocessor-based zoning thermostats have been specifically designed to control either 0-10Vdc, staged,

More information

FUNCTION MANUAL, INSTALLATION GOLD RX/PX/CX/SD Generation F. Applicable to Program Version 1.27 and newer versions

FUNCTION MANUAL, INSTALLATION GOLD RX/PX/CX/SD Generation F. Applicable to Program Version 1.27 and newer versions FUNCTION MANUAL, INSTALLATION GOLD RX/PX/CX/SD Generation F Applicable to Program Version 1.27 and newer versions Content 1. Image Management...3 2. Main Setup...4 3. Filter Calibration...4 4. Functions...5

More information

Description of the functions, IQlogic

Description of the functions, IQlogic , IQlogic General Control...168 Status...168 IQnavigator hand-held terminal and image management...169 Dashboard...169 Main setup...170 Air flow Regulation mode...171 Boost...171 Unit...171 Air adjustment...171

More information

Operation and Maintenance Instructions GOLD LP

Operation and Maintenance Instructions GOLD LP Operation and Maintenance Instructions GOLD LP Applicable to program version 3.04 and newer versions The document was originally written in Swedish. We reserve the right to alter specifications without

More information

Modbus TCP/IP Version 4.0 and Modbus RTU Gateway Version 2.4

Modbus TCP/IP Version 4.0 and Modbus RTU Gateway Version 2.4 Modbus TCP/IP Version 4.0 and Modbus RTU Gateway Version 2.4 Overview ModBus can access single addresses or multiple addresses simultaneously; either reading or writing single bit values or 16-bit values.

More information

Controls LonMark DDC VAV Controller

Controls LonMark DDC VAV Controller Introduction This LonMark certified controller uses the Space Comfort Controller (SCC) profile to exchange information over a LonTalk network. Networks with LonMark certified controllers provide the latest

More information

Data Aire DAP TM III. LonWorks Protocol Integration Information

Data Aire DAP TM III. LonWorks Protocol Integration Information Data Aire DAP TM III LonWorks Protocol Integration Information Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-685 June 2009 Revision 1.0 Document 600-000-685

More information

Data Aire DAP TM III. LonWorks Protocol Integration Information

Data Aire DAP TM III. LonWorks Protocol Integration Information Data Aire DAP TM III LonWorks Protocol Integration Information Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-685 Feb 2011 Revision 2.0 Table of Contents 1 Introduction...

More information

Installation Instructions for the TBLZ-2-66 control box. for controlling two air handling units (Twin Function) GOLD RX

Installation Instructions for the TBLZ-2-66 control box. for controlling two air handling units (Twin Function) GOLD RX Installation Instructions for the TBLZ-2-66 control box. for controlling two air handling units (Twin Function) GOLD RX 04-120 1. General The TBLZ-2-66 accessory is a control system incorporated into a

More information

Operation and Maintenance Instructions GOLD RX/PX/CX/SD, Generation D

Operation and Maintenance Instructions GOLD RX/PX/CX/SD, Generation D Operation and Maintenance Instructions GOLD RX/PX/CX/SD, Generation D Applicable to program version 6.04 and newer versions GOLD PX GOLD RX GOLD CX GOLD SD The document was originally written in Swedish.

More information

Comfort and Light Controller Lonbox PZM4148

Comfort and Light Controller Lonbox PZM4148 Comfort and Light Controller Lonbox PZM4148 DIN or ready to go BOX Decentralized Boxes Look for DIN hardware Find software Design boxes Produce boxes Comfort and Light Controller PZM4148 The Lonbox PZM4148

More information

DESCRIPTION NOTE. Temperature and Humidity Sensors MODEL 1260B

DESCRIPTION NOTE. Temperature and Humidity Sensors MODEL 1260B Wall mount/indoor transmitter for temperature, relative humidity and two dry contact inputs. Dual dry-contact inputs allow integration of light switches, motion and occupancy sensors in any combination.

More information

C-series Controllers for air handling systems

C-series Controllers for air handling systems C-series Controllers for air handling systems Corrigo, C-series, is a range of digital controllers for air-handling systems designed to be easy to use and operate, having a large capacity, and a high degree

More information

Database for CTS6000 MODBUS

Database for CTS6000 MODBUS Database for CTS6000 MODBUS Valid for: LONcard SW1.7.4B, Variable List V2.02 Version 1.08-4, 01-05-2016 Contents Contents... 2 1. Installation... 3 1.1. Installation and operating instructions... 3 2.

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Modbus TCP Register List GreenManager for GreenMaster C-F Valid for firmware version 2.0 or later

Modbus TCP Register List GreenManager for GreenMaster C-F Valid for firmware version 2.0 or later Modbus TCP Register List GreenManager for GreenMaster C-F Valid for firmware version 2.0 or later Overview Modbus can access single adresses or multiple addresses simultaneously; either reading or writing

More information

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data. ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data. The RVA 46 Zone Controller can only be used in conjunction with a RVA47 controlled boiler installation. The RVA46 controller

More information

DESCRIPTION MODEL 1205/1205HA NOTE

DESCRIPTION MODEL 1205/1205HA NOTE Integrated Temperature, Relative Humidity and Dew Point Transmitter. Housed in a rugged stainless steel body offering excellent corrosion protection. RH Accuracy at 25 C:: Model 1205 2% typical / 3% maximum;

More information

Climatix LON communication with POL SNVTs for Twin Wheel application v1.x

Climatix LON communication with POL SNVTs for Twin Wheel application v1.x Climatix SNVTs for Twin Wheel application v1.x Table of contents 1 About this document...3 1.1 Revision history...3 1.2 Before you start...3 1.3 Reference documents...3 2 Application...4 2.1 General information...4

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR COMPACT AIR & COMPACT HEAT

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR COMPACT AIR & COMPACT HEAT INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR COMPACT AIR & COMPACT HEAT Applicable to program version 3.00 and newer versions COMPACT Air COMPACT Heat The document was originally written in Swedish. Registered

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

Installation Guide. ECL Comfort 210, application A Table of Contents

Installation Guide. ECL Comfort 210, application A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 4 2.1 Before you start.....................................................

More information

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. The RVA63 controller can be utilized to control the following system configurations via LPB communication. Equipment Required

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

1.0 Digital Controller

1.0 Digital Controller 1.0 Digital Controller...1 1.1 Display Function Keys...1 1.2 Thermostat Display...2 1.3 Controller hardware input output points... 4 2.0 Sequence of Operation...5 2.1 States of Operation...5 2.2 Modes

More information

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application 2025 Application Note 140-1054 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

N M AirControl AHU. Control manual

N M AirControl AHU. Control manual N 10.63 M 03-2016 AirControl AHU Control manual EN CONTENTS PAGE 1 - MONITORING AND CONTROL 2 1.1 The program 2 1.2 The HMI terminal 2 1.3 The controller 4 1.4 Description of the air handling units 4

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application 2023 Application Note 140-1052 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 6 Hardware Outputs...

More information

Installer Manual KNX Touchscreen Thermostat

Installer Manual KNX Touchscreen Thermostat Installer Manual 02952 KNX Touchscreen Thermostat Index GENERAL FEATURES AND FUNCTIONALITY from page 5 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 7 COMMUNICATION OBJECTS GENERAL FEATURES AND FUNCTIONALITY

More information

ETNC24-FC-BAC-PIR-01 Owner s manual & Technician Settings

ETNC24-FC-BAC-PIR-01 Owner s manual & Technician Settings ETNC-FC-BAC-PIR- Rev. Index Operating instructions....- Turning the thermostat and OFF Selecting temperature scale Adjusting the Set point temperature (for set point and set points configurations) Selecting

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

Climatix LON communication with POL SNVTs for eq zone application v1.x

Climatix LON communication with POL SNVTs for eq zone application v1.x Climatix SNVTs for eq zone application v1.x Table of contents 1 About this document...3 1.1 Revision history...3 1.2 Before you start...3 1.3 Reference documents...3 2 Application...4 2.1 General information...4

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

L SERIES UNITS 504,908M. 10/2004 Supersedes 9/2004

L SERIES UNITS 504,908M. 10/2004 Supersedes 9/2004 Litho U.S.A. 4 L SERIES UNITS 54,98M /4 Supersedes 9/4 M 7 VERSION 5.x INTEGRATED MODULAR CONTROL (IMC) GUIDE TO THE M 7 VERSION 5.x INTEGRATED MODULAR CONTROL USED IN L SERIES AND S CLASS 3 THROUGH 5

More information

L SERIES UNITS 505,191M. 4/2006 Supersedes 504,908M

L SERIES UNITS 505,191M. 4/2006 Supersedes 504,908M Litho U.S.A. 26 L SERIES UNITS 55,191M 4/26 Supersedes 54,98M M1 7 VERSION 5.2 INTEGRATED MODULAR CONTROL (IMC) GUIDE TO THE M1 7 VERSION 5.2 INTEGRATED MODULAR CONTROL USED IN L SERIES AND S CLASS 3 THROUGH

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

BACnet MODBUS N2 LON Description Type Point Description Name # Object Type Register Type ID SNVT # Name SNVT Read Only

BACnet MODBUS N2 LON Description Type Point Description Name # Object Type Register Type ID SNVT # Name SNVT Read Only Point Object Register SNVT SNVT Read Only 1 BAS CO 2 Sensor Value bas_co2_val_1 AV:49 float value 40001 data float 1 48 nvibasco2val SNVT_temp_p (105) BAS CO 2 Sensor Value in PPM 2 BAS Mixed Air Temperature

More information

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include: Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description

More information

G a

G a G2474 74 319 0081 0 a en Installation Instructions Heating controllers RVP3... Installation Place of installation In a dry room, e.g. in the boiler room Mounting choices: Control cabinet (in the front,

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

Natural Ventilation Controller with 24vDC drive NVC-1204

Natural Ventilation Controller with 24vDC drive NVC-1204 Natural Ventilation Controller with 24vDC drive NVC-1204 BACnet Enabled C-036 08/11 FEATURES > 24V DC supply > Native BACnet communications > Master/Slave grouping (shared information) > 3 x 0-10V outputs

More information

OWNER S MANUAL FreeWay. LiteConnector Lon FTT-10 LonWorks -gateway for Exvent AC-series

OWNER S MANUAL FreeWay. LiteConnector Lon FTT-10 LonWorks -gateway for Exvent AC-series OWNER S MANUAL FreeWay LiteConnector Lon FTT-10 LonWorks -gateway for Exvent AC-series Pajatie 8 06150 PORVOO Tel +358 19 529 700 Fax +358 19 529 7044 www.exvent.fi 2004_1 Table of contents TABLE OF CONTENTS...

More information

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...

More information

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems Series 9 Commissioning Checklist S9-CL2017.doc ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 S9-CL2017.doc Commissioning

More information

Technical manual MARK WTW AIRSTREAM _R01

Technical manual MARK WTW AIRSTREAM _R01 Technical manual EN MARK WTW AIRSTREAM 0661130_R01 Read this document before installing the appliance Warning An incorrectly performed installation, adjustment, alteration, repair or maintenance activity

More information

Your Home. Jacco & Assoc.

Your Home. Jacco & Assoc. Your Home Fan on with call for heating or cooling Heating on with call from space thermostat Stage as required to maintain The 75F Basics adj. - First stage of heating shall be heat pump Cooling on with

More information

Natural Ventilation Controller with 24vDC drive NVC-1204

Natural Ventilation Controller with 24vDC drive NVC-1204 Natural Ventilation Controller with 24vDC drive NVC-1204 BACnet Enabled C-038 08/16 FEATURES SPECIFICATION > 24V DC supply > Native BACnet communications > Master/Slave grouping (shared information) >

More information

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application 2070 Application Note 140-1040 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware

More information

SAUTER flexotron800 V2 Ventilation V3.3. manual P P

SAUTER flexotron800 V2 Ventilation V3.3. manual P P SAUTER flexotron800 V2 Ventilation V3.3 manual 2/175 Content Content 1 Generell notes 9 1.1 Disclaimer 9 1.2 Trademarks 9 1.3 Safety information 9 1.3.1 Mandatory note 9 1.3.2 General note 10 1.4 Notes

More information

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence

More information

TC-9102 Applications

TC-9102 Applications Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...

More information

EXcon zone control. Control for up to 4 individual zones _ fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov

EXcon zone control. Control for up to 4 individual zones _ fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov 3005925_2018-02-05.fm EXcon zone control Control for up to 4 individual zones EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov Tel. +45 65 66 12 34 Fax +45 65 66 11 10 exhausto@exhausto.dk www.exhausto.dk OJ-Air2

More information

Manual Supplement. Product/System Title: Static Pressure Controller. Contents of this manual supplement include:

Manual Supplement. Product/System Title: Static Pressure Controller. Contents of this manual supplement include: Model Number: Product/System Title: 8635-ST Static Pressure Controller Contents of this manual supplement include: 1) Sequence of operation 2) Description of new software items 3) Deleted software menu

More information

Installation Guide. Bacharach HGM300 to LonWorks FT-10 Communications Adapter

Installation Guide. Bacharach HGM300 to LonWorks FT-10 Communications Adapter 3015-4568 Revision 0 9/11/03 Installation Guide Bacharach HGM300 to LonWorks FT-10 Communications Adapter Introduction The Bacharach HGM300 to LonWorks Communications Adapter enables an HGM300 Refrigerant

More information

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application 2050 Application Note 140-1136 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware Outputs...

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application 2273 Application Note 140-1045 Building Technologies Table of Contents Overview... 4 Hardware Inputs...

More information

VCB-X Modular Service Tool Technical Guide. VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2.

VCB-X Modular Service Tool Technical Guide. VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2. VCB-X Modular Service Tool Technical Guide VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2.0 and up Table of Contents INTRODUCTION... 3 Modular Service Tool...3 SYSTEM

More information

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control Critical Environments Model 8682KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control Manual Supplement Contents of this manual supplement

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE

More information

Operation and Maintenance Manual OM MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps

Operation and Maintenance Manual OM MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps Operation and Maintenance Manual OM 239 Group: WSHP Document PN: 906530 Date: July 205 MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps Large Capacity

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

Fan Coil Unit (FCU) Application Guide

Fan Coil Unit (FCU) Application Guide Fan Coil Unit (FCU) Series Room Controllers TABLE OF CONTENTS and SCs Fan coil terminal equipment controllers 2 A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves

More information

VEX100 series Air handling units with cross-flow heat exchanger

VEX100 series Air handling units with cross-flow heat exchanger Product information - Version 6 VEX100 series Air handling units with cross-flow heat exchanger VEX140: 400-2200 m 3 /h VEX150: 700-3600 m 3 /h VEX160: 1100-5000 m 3 /h VEX170: 1400-8400 m 3 /h Contents

More information

VMB1TSW Temperature sensor module for the Velbus system

VMB1TSW Temperature sensor module for the Velbus system VMB1TSW Temperature sensor module for the Velbus system CONTENTS DESCRIPTION... 3 CHARACTERISTICS... 3 VELBUS CHARACTERISTICS... 5 OVERVIEW SENSOR MODULE... 7 EMBEDDING THE TEMPERATURE SENSOR... 8 EMBEDDING

More information

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

District heating controller for two heating circuits and d.h.w. according to Siemens specifications: 4 319 2984 0 G2384en en Installation Instructions District heating controller for two heating circuits and d.h.w. RVD240 Installation Place of installation In a dry room, e.g. in the heat exchanger room

More information

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH,

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH, SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS Options AG3 Unit-Mounted Ductstat Options AG15, AG16 A = Ductstat Temperature Module P/N 115848 B = Stage Adder Module, P/N 115849 (quantity varies

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

Table of Contents. WSHP Open v3

Table of Contents. WSHP Open v3 WSHP Open v3 Integration Guide CARRIER CORPORATION 2012 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-500-01 11/29/2012 Table of Contents Introduction... 1

More information

Model: RT510RF. Installation Manual

Model: RT510RF. Installation Manual Model: RT50RF Installation Manual Contents Product compliance... 3 Safety Information... 3 Box content... 3 Introduction... 3 Features... Installation... 5. RXRT50 Receiver... 5 Button Description for

More information

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 Application Note 140-1042 Building Technologies Table of Contents Overview... 4 Hardware

More information

Rev UltraSite User s Guide BCU Supplement

Rev UltraSite User s Guide BCU Supplement 026-1004 Rev 1 09-04-97 UltraSite User s Guide BCU Supplement Computer Process Controls, Inc. 1640 Airport Road Suite #104 Kennesaw, GA 31044 Phone (770) 425-2724 Fax (770) 425-9319 ALL RIGHTS RESERVED

More information

MicroTech III Applied Air Handling Unit Controller Protocol Information

MicroTech III Applied Air Handling Unit Controller Protocol Information Engineering Data ED 15112-2 Group: Controls Part Number: ED 15112-2 Date: January 2009 Supersedes: ED 15112-1 MicroTech III Applied Air Handling Unit Controller Protocol Information Networks Networks 2009

More information

Standard Instructions For MC-2000/3000/4000 Controllers

Standard Instructions For MC-2000/3000/4000 Controllers Standard Instructions For MC-2000/3000/4000 Controllers Manual Update: 09/12/11 Version: 3.10 1 1 QUICK REFERENCE GUIDE 1.1 NAVIGATING THE DISPLAY Interacting with the AboveAir Technologies unit is accomplished

More information

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB Summary 1 CONNECTIONS... 3 1.1 TEMPERATURE PROBES...3 1.2 LOW VOLTAGE DIGITAL INPUTS...3 1.3 LIVE DIGITAL INPUTS...4 1.4 RELAY OUTPUTS...5 2 POWER SUPPLY... 6 3 SERIAL CONNECTIONS... 6 4 SOFTWARE... 7

More information

Automation System TROVIS 5400 Ventilation Controller TROVIS Mounting and Operating Instructions EB 5477 EN. Electronics from SAMSON

Automation System TROVIS 5400 Ventilation Controller TROVIS Mounting and Operating Instructions EB 5477 EN. Electronics from SAMSON Automation System TROVIS 5400 Ventilation Controller TROVIS 5477 ounting and Operating Instructions Electronics from SASON EB 5477 EN Firmware version 2.0x Edition April 2004 Disclaimer of liability Disclaimer

More information

TELLUS. Complete HVAC substation for air handling, cooling, heating and hot tap water. Main benefits. General

TELLUS. Complete HVAC substation for air handling, cooling, heating and hot tap water. Main benefits. General Complete HVAC substation for air handling, cooling, heating and hot tap water General TELLUS is a complete, modular substation that can be installed both indoors and outdoors. TELLUS produces and distributes

More information

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602* User's Guide VI.7C.E6.02 2005.09 C37 *VI7CE602* *087R8070* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8070* *VI7CE602* Mixing controller with ON / OFF controlled

More information

ECL Comfort 110, application 116

ECL Comfort 110, application 116 Operating Guide ECL Comfort 110, application 116 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

REMOTE CONTROL FOR CHILLER MYCHILLER

REMOTE CONTROL FOR CHILLER MYCHILLER REMOTE CONTROL FOR CHILLER MYCHILLER GENERAL FEATURES... 3 MAIN FUNCTIONS AND EQUIPMENT:... 3 LCD DISPLAY... 4 KEYBOARD... 5 BOARD CONFIGURATION... 7 LIST OF MAIN PARAMETERS... 7 CONFIGURATION OF MAIN

More information

CONTENTS. Installation Guide. VT7200 Series

CONTENTS. Installation Guide. VT7200 Series VT7200 Series Installation Guide For mercial HVAC Applications November 2015 CONTENTS Installation 2 Location 2 Installation 2 Configurable BI/UI inputs overview 4 Network ready 6 Terminal, Identification

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 482641 Microprocessor Controller for Make-Up Air Products Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

Climatix Basic reference addresses for eq Fläkt application v1.x

Climatix Basic reference addresses for eq Fläkt application v1.x Climatix Basic reference addresses for eq Fläkt application v1.x Modbus communication, slave mode Table of contents 1 About this document...3 1.1 Revision history...3 1.2 Before you start...3 1.3 Reference

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

Room thermostats with LCD for wall mounting

Room thermostats with LCD for wall mounting s 3 181 RDG100 / RDG110 RDG140 / RDG100 RDG100/H Room thermostats with LCD for wall mounting for fan coil unit applications for universal applications for use with compressors in dx type equipment RDG1

More information

Installation and Maintenance Manual OM

Installation and Maintenance Manual OM Installation and Maintenance Manual OM 1149-3 Group: WSHP Document PN: 910208203 Date: April 2017 MicroTech III SmartSource Unit Controller with I/O Expansion Module for Single and Two Stage Water Source

More information

ROOM THERMOSTATS KNX BASIC DOCUMENTATION

ROOM THERMOSTATS KNX BASIC DOCUMENTATION ROOM THERMOSTATS KNX BASIC DOCUMENTATION Contents 2 2 2 2 ABOUT THIS DOCUMENT Document use / request to the reader Target audience, prerequisites Glossary 59 59 60 62 63 HANDLING Mounting and installation

More information

- Data Brochure D 260. Boiler Control /09

- Data Brochure D 260. Boiler Control /09 - Data Brochure Boiler Control 260 D 260 03/09 The Boiler Control 260 is designed to control a single stage heat source in order to provide outdoor reset or Domestic Hot Water () operation. The control

More information