OVERVIEW. Increasing Awareness of Occupant Evacuation in Tall Buildings. Traditional Focus has been on Evacuation From Fire
|
|
- Eileen White
- 5 years ago
- Views:
Transcription
1
2 OVERVIEW Increasing Awareness of Occupant Evacuation in Tall Buildings Traditional Focus has been on Evacuation From Fire Current Practice - Facilitate Broad Variety of Evacuation Scenarios Design to Facilitate Full Building Evacuation Considerations for Adjacent Building Evacuations Impact of Mass Disasters in High Density Urban Centers
3 High Rise Fire Safety Approach Active & Passive Fire Safety Features to Control Fire and it s Effects Fire Resistant Structure & Fire Barriers Fire Suppression Systems Fire Detection, Alarm & Communication Systems Smoke Management Systems Means of Egress to Facilitate Occupant Evacuation and Defend in Place Exit Stairs Refuge Floors Evacuation Elevators Features that Support Fire Fighting Operations Internally in The Building Fire Command Center Fire Fighter s Elevators & Vestibules Fire Fighting Water Supply
4 Jin Mao Tower M Shanghai World Financial Center M Shanghai Tower M Shanghai A Tale of Three Towers
5 Early Mixed-Use Design Office & Hotel Atrium Design Local Code & International Best Practices Defend in Place Active Fire Systems Means of Egress Jin Mao Tower
6 Refuge Floors Jin Mao Tower Fire Safety Features Level 15 & 30 in Office Every Floor in Hotel
7 Jin Mao Tower Fire Safety Features Stairs Interrupt at Refuge Floors Egress to Refuge Floor Reduces Stack Effect Allows Transfer to Other Stairs Refuge Floors 2 hour Enclosure Mechanical Pressurization 2 Hour Shaft Separation Area of Refuge
8 Mixed-Use Design Office & Hotel Atrium Design at Top Shanghai World Financial Center Local Code & International Best Practices Defend in Place Active Fire Systems Means of Egress
9 SWFC Fire Safety Features Fire Safety Features Protected inside Concrete Core Walls Critical Life Safety Functions located inside Concrete Core Shear Walls Exit Stairs Fire fighters Elevators Evacuation Elevators Sprinkler/Standpipe Risers Fire Detection, Alarm & Communication Risers Emergency Power Risers
10 High Occupancy at Top of Tower SWFC Fire Safety Features
11 Elevator Assisted Evacuation SWFC Fire Safety Features
12 Elevator Assisted Evacuation Number of occupants in Tower SWFC Fire Safety Features Total number of occupants in tower against time Time (minutes) Evacute using Stairway Only Lift-assisted Evacuation
13 Shanghai Tower Mixed-Use Design Office & Hotel Atrium Design in Each Section High Occupancy Use at Top Local Code & International Best Practices
14 Shanghai Tower Fire Safety Features Evacuation Elevators Fire Fighters Elevators Evacuation Elevators
15 Shanghai Tower Fire Safety Features Lifeboat Evacuation Elevators Attendant Controlled Emergency Power Protected From Water Effects Operating Characteristics of Evacuation Elevators
16 Refuge Floor Shanghai Tower Fire Safety Features Level 117 Refuge Floor Fire Fighters Elevators Evacuation Elevator Exit Stairs Refuge Area
17 Observation Floor Shanghai Tower Fire Safety Features Level 118 Observation Floor Fire Fighters Elevators Primary Exit Stairs Supplemental Exit Stairs
18 Shanghai Tower Fire Safety Features Evacuation Modeling Benchmarking for 2 Hour Evacuation Using Stairs & Evacuation Elevators
19 Emergency Planning & Response Considerations Emergency management in Dense Urban Areas Siting Buildings to Reduce Impacts on Adjacent Structures Emergency Vehicle Access within Adjacent Properties Flexible Command & Control Locations Assembly Points for Building Occupants inside and outside building Shelter, Sustenance & Transportation
20 Contact Information Fang Li, FSFPE; Executive Vice President, RJA China James Antell, AIA, PE; Executive Vice President, RJA International Martin Reiss, PE, FSFPE; President, RJA International
Fire Protection Coffee Break Training May 2016
Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers
More informationFire Safety in Tall Building: Performance-Based Solutions. Chris Jelenewicz, P.E., FSFPE
Fire Safety in Tall Building: Performance-Based Solutions Chris Jelenewicz, P.E., FSFPE Kingdom Tower -- Jeddah Central Park Tower Philadelphia, PA One Meridian Plaza February 23, 1991 SFPE/ICC Guide
More informationBOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015
Exam ID Examination Code Part BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 BC3-7 Level III Exam 7 BCBC Part 3 (Part 3 Buildings Classification & Construction) BC3-8 Level III Exam 8 BCBC
More informationCase Study of Underground Car Park. Team Japan
11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not
More informationRichard B. Alpert, P.E. Senior FPE, Clark Nexsen
Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of
More informationModule 7. Control of Smoke & Highlights of Code Requirements
Module 7 Control of Smoke & Highlights of Code Requirements 1 Module 7 Overview This module will cover: 1. The requirements of smoke control in the Ohio Building Code Section 909 2. The differences between
More informationLife Safety - Means of Egress/Exits NFPA 101
Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all
More informationBall State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Smoke, Not Flame
SMOKE CONTROL Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Smoke, Not Flame The most significant cause of death in building fires is smoke, which accounted for 73% of fire-related deaths
More informationFIRE PROTECTION SYSTEMS IN BURJ KHALIFA. By NAFFCO Fire Protection
FIRE PROTECTION SYSTEMS IN BURJ KHALIFA By NAFFCO Fire Protection 8 September 2015 Company Introduction NAFFCO ( National Fire Fighting Manufacturing FZCO ) an ISO 9001:2008 certified company with its
More informationPractice Advisory 18: Fire safety design for tall buildings
Practice Advisory 18: Fire safety design for tall buildings It s important that reliable and resilient fire design features are used in the design of tall buildings. This advisory highlights the specific
More informationSelecting appropriate egress strategies
Selecting appropriate egress strategies The selection of an appropriate egress strategy requires a good understing of the building its occupants, the protection measures in place, the expected emergency
More informationThe Residences at Christina Landing Wilmington, DE
5.0 FIRE PROTECTION EXISTING CONDITIONS 5.1 Project Specific Fire Protection Data Codes, Regulations, and Standards Building Officials and Code administrators (BOCA) National Building Code [1996] with
More informationActive & Passive Fire Protection System. Page 1 Kalidasan S BT IN SSP-OP
Active & Passive Fire Protection System Page 1 Kalidasan S BT IN SSP-OP Fire Protection - Introduction Introduction: The definition of fire protection of a building refers to the building ability to detect,
More informationFIRE PREVENTION MANUAL CHAPTER 12, FPIB 44 May 14, 2008 EMERGENCY ACTION PLAN (EAP) NON-FIRE EMERGENCIES IN CLASS E OFFICE BUILDINGS 1.
EMERGENCY ACTION PLAN (EAP) NON-FIRE EMERGENCIES IN CLASS E OFFICE BUILDINGS FIRE PREVENTION MANUAL CHAPTER 12, FPIB 44 May 14, 2008 1. INTRODUCTION 1.1 Local Law 26 of 2004 required that the Fire Commissioner
More informationSCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY
SCHEDULE Essential s taken from Schedule 9 of the Building Regulations 2006 43 PART 1 BUILDING FIRE INTEGRITY 1 Building elements required to satisfy prescribed fire-resistance levels 2 Materials and assemblies
More informationBy: Russell Bainbridge March 18th, 2016 FPE 596
By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse
More information9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement
Second Revision No. 5501-NFPA 5000-2016 [ New Section after 29.2.1.2 ] 29.2.1.3 Bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars in accordance with the provisions
More informationBUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007
BUILDING CODE OF THE CITY OF NEW YORK New York City Department of Buildings 4 June 2007 Fatma Amer, PE, Deputy Commissioner, Technical Affairs James Colgate, RA, Executive Architect John Lee, RA Keith
More informationSPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,
More informationWelcome to the AccessibilityOnline Webinar Series. Listening to the Webinar. Listening to the Webinar, continued
Welcome to the Webinar Series A collaborative program between the ADA National Network and the U.S. Access Board The Session is Scheduled to begin at 2:30pm Eastern Time We will be testing sound quality
More informationIBC Committee Responsibility Matrix January 2017
IBC Committee Responsibility Matrix January 2017 Chapter 1 ADMIN same Chapter 3 High-Hazard Group H 307.1 same IFC same Uses Other Than Group H 307.1.1 same IFC same Hazardoss Materials 307.1.2 307.2 IFC
More informationEngineering Systems an Incremental Response to Terrorist Threat
ctbuh.org/papers Title: Authors: Subject: Keywords: Engineering Systems an Incremental Response to Terrorist Threat Norman D. Kurtz, Principal, WSP Flack + Kurtz Andrew Hlushko, Director, WSP Flack + Kurtz
More informationNEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS
Mandatory Fire Safety Instruction NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS Reference A: Reference B: Approved Document B
More informationWelcome to the AccessibilityOnline Webinar Series. Listening to the Webinar
Welcome to the Webinar Series A collaborative program between the ADA National Network and the U.S. Access Board The Session is Scheduled to begin at 2:30pm Eastern Time We will be testing sound quality
More informationStatue of Liberty: A Risk Analysis
Statue of Liberty: A Risk Analysis Bruce Campbell, FSFPE VP DOE Services National Park Service Agenda Overview of Project Scope Evaluation Steps Task 1 Code Analysis Task 2 Fire Modeling Task 3 Egress
More informationFirst Aspen Federal Regulation Set: K LSC 2000 Health Existing
First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall
More informationSPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,
More informationBUILDING CODE COMMISSION
Ruling No. 03-30-928 Application No. 2003-34 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.1.8.12.(1)
More information2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)
[F]TABLE 903.2.11.6 ADDITIONAL REQUIRED SUPPRESSION SYSTEMS SECTION SUBJECT 402.10 402.5 Covered and open mall buildings (Portions of table not show remain unchanged) 2012 International Building Code SEVENTH
More informationSMOKE CONTROL: ISSUES / APPROACHES. Smoke, Not Flame
SMOKE CONTROL: ISSUES / APPROACHES Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Smoke, Not Flame The most significant cause of death in building fires is smoke, which accounted for 73% of
More informationPreview of the MA Building Code (780 CMR) 9 th edition
Preview of the MA Building Code (780 CMR) 9 th edition Presented by: Ron Melucci, P.E. Engineering Planning and Management, Inc rbm@epm inc.com www.epm inc.com 508 875 2121 Engineering Planning and Management,
More informationKensington Aldridge Academy, London W10
Kensington Aldridge Academy, London W10 Fire Safety Review Job Number: 1103 June 2018 FIRE SAFETY REVIEW CONTENTS EXECUTIVE SUMMARY 1.0 INTRODUCTION 2.0 FIRE SAFETY REQUIREMENTS 3.0 EXTERNAL WALL SPECIFICATION
More information22 BISHOPSGATE Lift Evacuation Strategy
June 28, 2018 22 BISHOPSGATE Lift Evacuation Strategy Romain Hourqueig, Head of UK Fire Engineering Neil Allardice, Senior Fire Engineer AGENDA The project Fire Safety Strategy Why lift evacuation? The
More informationUnit 2 Fire Safety (Zone 2)
IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 2) Examiner Report March 2017 Introduction 21% of the candidates that sat the examination attained a pass. Candidates did not
More informationCode Technologies Committee Report Elevator Lobby Group A changes: Elevator Lobby
Code Technologies Committee Report Elevator Lobby Group A changes: There are 11 areas of study currently listed under CTC. 1. Balanced Fire Protection 1.1. Vertical Opening 1.2. Roof Vents 2. Carbon Monoxide
More informationDutchess Community College. Emergency Action Plan. Conklin Hall College Residence
Dutchess Community College Emergency Action Plan Conklin Hall College Residence June 2014 1 TABLE OF CONTENTS Purpose Page 3 Introduction Page 3 Evacuation Page 4 Fire Emergencies Page 5 Evacuating Individuals
More informationThe Physical Environment Portal: Module 5, LS Leadership
The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings
More informationCalifornia Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19
PART 3 Building and Equipment Design Features Chapters 5 through 19 Chapter 5 Fire Service Features No changes addressed Chapter 6 Building Services and Systems Chapter 7 Fire-Resistance-Rated Construction
More information2012 B.C. Building Code Compliance Review (Division B Part 3)
Planning and Building Department 2012 B.C. Building Code Compliance Review PROJECT NAME:.. CIVIC ADDRESS:...... PERMIT APPLICATION NO.:. DATE:... I,, have: 1. reviewed the design, plans and supporting
More informationProject 4: Active Fire Protection Systems Issues. Project 4: Investigation Team
NIST World Trade Center Investigation Project 4: Active Fire Protection Systems Issues William Grosshandler Presenting Project 4: Investigation Team David D. Evans, Project 4 Leader W. Stuart Dols, M.E.,
More informationOpen to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP
Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com
More informationFIRE SAFETY PLAN FIRST & JASPER JASPER AVENUE
FIRE SAFETY PLAN FIRST & JASPER 10065 JASPER AVENUE March 2014 Fire/Emergency Evacuation Procedures Introduction GWL Realty Advisors is the property management company responsible for the building located
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT YOUNG INTERNATIONAL PLOT NO. 32-36, SECTOR 5-CEPZ, CHITTAGONG OTHER FACTORIES: NONE July 20, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/20/2014 by Hughes Associates,
More informationFire evacuation drill
European guideline (handbook) Fire evacuation drill (draft document) Ver: 2010-06-02 Prepared by Aleš Jug, Slovenia Related guideline: CFPA E: 19_2009 Fire safety engineering concerning evacuation from
More informationSupplemental Evacuation Products
Supplemental Evacuation Products PT ELJE PERDANA sells experience and solution that goes with the Supplemental Evacuation www.elje4escape.com When Should You Evacuate? It is recommended: when the alarm
More informationEmergency Evacuation Procedures
Emergency Evacuation Procedures Vaughn College of Aeronautics and Technology Residence Hall 22-40 90 th street When an alarm sounds, follow these fire alarm evacuation procedures: 1. Leave the building
More informationElement C3.5 Means of Escape
.5 Means of Escape RRFSO Article 14 Legal Factors Responsible person must ensure routes to emergency exits and exits themselves are kept clear at all times Exits must directly lead to place of safety Safe
More informationTechnical Analysis of the Need for Enclosed Elevator Lobbies
Technical Analysis of the Need for Enclosed Elevator Lobbies EXECUTIVE SUMMARY Prepared for the ICC CTC by the Elevator Lobby Study Group The ICC Executive Board directed the Code Technology Committee
More informationTHE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6
THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6 WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio 1 QUESTIONS How To Ask a Question: POLLING There will be occasional
More informationPROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:.
2012 B.C. Building Code Checklist (Division B Part 3) This checklist is provided as a reference only. The submission of this checklist with a Building Permit application should not be considered as a substitute
More informationTake your keys, coat, and any important information with you.
7. Responsibilities Building Emergency Team Building Emergency Teams are present in most buildings on campus. It is the function of the Building Emergency Team to assist and coordinate a prompt and organized
More informationDEALING WITH FIRE SAFETY
DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the
More informationThe project scope work is 90% new construction and 10% remodel in Esslinger Hall.
CREIGHTON ENGINEERING INC. FIRE PROTECTION CONSULTING ENGINEERS 210 N. University Road, Suite 100 Spokane Valley, WA 99206 TEL: 509.921.9755 FAX: 509.921.9806 WEB: www.creightoneng.com SCOTT R. CREIGHTON,
More informationNFPA 45 NFPA 211 NFPA 1600
NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT MAHID APPAREL LTD ACCORD ID: 11956 NOWPARA, MADHABDI, NARSINGDI, DHAKA-1604 OTHER FACTORIES: NONE February 20, 2015 Page 2 SUMMARY was surveyed for fire safety on 2/20/2015
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationAre there any policies regarding outlets that contain USB ports?
Answers to the Questions Mark J. Blackburn, P.E., CFPS February, 2016 Question 1 Are there any policies regarding outlets that contain USB ports? There is no direct reference in code about these types
More informationAcademic and Administrative Buildings
Academic and Administrative Buildings Fire Prevention Inspections The Tufts Fire Marshal s staff conducts fire prevention inspections in the academic and administrative buildings on a regular schedule
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Assessor: 28 S.S. Tower, Vogra, Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Uttaron The Alliance for Worker Safety Page 1/17 12 Apr 2015 Introduction to the Report The following
More informationSAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.
SAFETY GENERAL Buildings must be designed according to building and fire safety codes and other regulatory standards at the time of construction. However, such codes and standards are continuously changing.
More informationFirefighting operations on fire alarm panels F5-04 GD
DESIGNER S GUIDE Firefighting operations on fire alarm panels F5-04 GD Introduction Alarm system devices Alarm system types A fire alarm system consists of one or more devices and/or control mechanisms
More informationAvailable online at ScienceDirect. Procedia Engineering 135 (2016 )
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 135 (2016 ) 170 174 Evacuation Strategy of Ultra-tall Towers among Stairs and Elevators Juan-juan Chen a,b, *, Xiao-gang Wang
More informationCHAPTER 7 ALTERATIONS LEVEL
CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration
More informationHow to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs
How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada
More informationSome Important Aspects of Fire Safety Regulations about High Rise Buildings
Some Important Aspects of Fire Safety Regulations about High Rise Buildings Tokyo University of Science Prof. Kyoichi Kobayashi (Dr. of Engineering) Many high rise buildings are being built with awful
More informationFIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015
FIRE ALARM SYSTEMS & 780 CMR Dave LeBlanc, PE, FSFPE March 17, 2015 BIOGRAPHY David J. LeBlanc, PE, FSFPE BS EE & MS FPE - WPI 23 Years PE Technical Committee Member NFPA72 - National Fire Alarm Code NFPA3
More informationDesign of Fire safety in Multi Occupancy Residential Accommodation
Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability
More informationBuilding & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!
Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?
More informationEMERGENCY PREPAREDNESS: EVACUATIONS
GUIDELINE I. EMERGENCY PREPAREDNESS: EVACUATIONS 1.0 PURPOSE 1.1 To provide guidance for the safe and orderly evacuation of faculty, staff, students and visitors to the University of Pennsylvania campus
More informationShort Term Accommodations Fire Code Requirements
Short Term Accommodations Fire Code Requirements 1 Foreward The following is a comprehensive reference to Retrofit 9.3 of Division B of the Ontario Fire Code (OFC). Retrofit provisions were developed to
More informationINITIAL FIRE SAFETY ASSESSMENT
INITIAL FIRE SAFETY ASSESSMENT Factory 214 Baiozid Bostami Road Nasirabad Industrial Area Chittagong 04 Sep 2016 The Alliance for Bangladesh Worker Safety Page 1/11 Factory 04 Sep 2016 Introduction to
More informationMODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces
MODULE 8 Tying the Systems Together: Emergency Control Functions and Interfaces 1 OVERVIEW OF MODULE 8 In this module we will: Describe all components, their arrangements and how the systems work Describe
More informationHealth, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service
Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in
More informationThe Application of Performance- Based Design Concepts for Fire and Life Safety
SUPPLEMENT 7 The Application of Performance- Based Design Concepts for Fire and Life Safety Milosh Puchovsky, P.E. James Quiter, P.E. Editor s Note: This supplement provides a brief overview regarding
More informationEmergency Response Floor Leader Training
https://www.lsuhsc.edu/admin/pfm/ehs/docs/erflt.pdf Emergency Response Floor Leader Training May 10, 2017 1 Outline Emergency Response Plan Organization and Communication Floor Leader Responsibilities
More informationExtreme Fires!
Extreme Fires! Is History Repeating Itself? 1971 - Airlie House Conference International Conference On Fire Safety In High-rise Buildings Evacuation impractical protect in place Limit fuel load prohibit
More informationLIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN
Title/Description: Life Safety & Fire Prevention Management Department: Facilities Management Personnel: All Effective Date: 5/97 Revised: 7/00, 7/01, 7/02, 7/03, 7/04, 7/05, 7/08 LIFE SAFETY & FIRE PREVENTION
More informationFire safety challenges and performance based fire engineering design of high-rise buildings
Tall Buildings: Tall Architectural Buildings: Architectural and Structural and Advances Structural Advances Fire safety challenges and performance based fire engineering design of high-rise buildings Kelvin
More informationBCAC Egress Work Group
2015 Group A Code Change Cycle Copyright 2014 International Code Council, Inc. BCAC item E-17.1 E?? 15 1006.2.1, 1006.3 1006.2.1 Egress based on occupant load and common path of egress travel distance.
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT ALAUDDIN GARMENTS LTD. 88, KAZI NAZRUL ISLAM AVENUE, TAJGAON, DHAKA- 1215 OTHER FACTORIES: CAMBRIDGE GARMENTS, PRIMODIAL April 27, 2014 Page 2 SUMMARY was surveyed for fire
More informationFIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT COMFORT APPAREL, ( PVT ) LTD. 96, DARUS SALAM, MIRPUR, DHAKA OTHER FACTORIES: SALMA FASHION WEARS LTD, COMFORT KNIT FASHION LTD March 27, 2014 Page 2 SUMMARY was surveyed
More informationUnit 2 Fire Safety (Zone 1)
IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 1) Examiner Report March 2018 Introduction 42% of candidates attained a Pass. Half of the candidates that attained a Pass secured
More informationctbuh.org/papers Risk-Based Approach of Achieving Code Compliance in Tall Buildings: Case Study Title:
ctbuh.org/papers Title: Author: Subjects: Keywords: Risk-Based Approach of Achieving Code Compliance in Tall Buildings: Case Study John Devlin, Senior Vice President, Aon Fire Protection Engineering Building
More information3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials
AMCA International Design Tips For Fire and Smoke Barriers William E. Koffel, P.E., FSFPE President, Koffel Associates, Inc. www.koffel.com Air System Engineering & Technology (ASET) Conference US San
More informationWORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS
1 WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS TABLE 4.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF ASSEMBLIES Construction
More informationJanuary 1, 2014 Mandatory Effective Date
2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective
More informationNEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS
Mandatory Fire Safety Instruction Reference A: Reference B: NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS Approved Document B Fire Safety
More informationFIRE SERVICE FEATURES
CHAPTER 5 FIRE SERVICE FEATURES SECTION 501 GENERAL 501.1 Scope. Fire service features for buildings, structures and premises shall comply with this chapter. 501.2 Permits. A permit shall be required as
More informationFIRE/SMOKE BARRIER FUNDAMENTALS
FIRE/SMOKE BARRIER FUNDAMENTALS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire OBJECTIVE Identify the different
More informationUCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES
Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments
More informationAgency for Health Care Administration
Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title
More informationWHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS
WHITE PLAINS SMOKE CONTROL CODE a. Application of Code. PART 1. GENERAL REQUIREMENTS The following uniform standards and procedures shall apply to the design, installation and testing of new smoke purge
More informationEmergency Evacuation Team Training James Zour Life Safety Specialist Transwestern
Emergency Evacuation Team Training James Zour Life Safety Specialist Transwestern Emergency Evacuation Plan Designed Specifically for the Building Provides an Organization Chart Outlines the Role and Responsibility
More informationLauzon Life Safety Consulting
Welcome to This Presentation By The WHEA Education & Professional Development Committee WHEA Lunch & Learn April 13, 2017 Lauzon Life Safety Consulting FIRE PLANS & DRILLS 1 Agenda Lauzon Life Safety Consulting
More informationAerial Urban Fire Suppression. Information proprietary to Simplex Aerospace and shall not be copied without express permission from Simplex
Aerial Urban Fire Suppression Aerial Urban Fire Surpression 7 Most city ladders can only reach 30m (7 floors) November 2013, firefighters in Sharjah, north of Dubai, struggled to battle a blaze in a 25-storey
More informationElement Z General Design Requirements Existing Facilities Information
PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and Element Z for technical
More informationBC Building Code Checklist Part 3 Planning and Development Department
BC Building Code Checklist Part 3 Planning and Development Department Project: Civic address: Permit No.: CRP: Certified Professional: Date: 1 Value of Construction: $ Developed Site Area: m2 2 BUILDING
More informationEmergency Planning and Preparedness
Emergency Planning and Preparedness Writing an Emergency Evacuation Plan A thorough emergency plan will include the following components: The procedure for reporting emergencies The procedure for relocating
More informationMechanical Smoke Extract Shaft Systems
Mechanical Smoke Extract Shaft Systems Presented by Mechanical Smoke Extract Shaft Systems Why Choose Crossflow? Crossflow is a family run company with over 45 years technical expertise. We are a solutions
More information