1 Fire Australia 2017 Fire Safety Engineering Stream - Quantification of Fire Safety AS/NZS :2015 IS IT GOOD ENOUGH FOR PERFORMANCE-BASED SMOKE EXHAUST SYSTEM DESIGN ABSTRACT M.C. HUI and M. KHEDHER BCA Logic Pty Ltd Level 6, 210 Clarence Street, Sydney 2000 This paper examines the shortcoming of the methodology to determine smoke exhaust rates as specified in section 9 Hot layer smoke control systems of AS/NZS by referring to the fundamental principles in various plume theories currently used by fire safety engineering practitioners locally and overseas, and by carrying out numerical experiments to investigate the performance of a mechanical smoke extraction system that operates at the exhaust rates determined by using the methodology in the joint Australian/New Zealand Standard for four design fires with a steady state heat release rate of 1.5, 5, 10 and 15MW respectively. 1 INTRODUCTION In Australia, smoke exhaust systems are commonly used to delay the onset of untenable conditions in performance based fire safety designs. There are two options to determine the smoke extraction rate of a smoke exhaust system, that is, either to follow the Deemed-to- Satisfy Provisions as stipulated in Specification E2.2b of the National Construction Code (Volume One Building Code of Australia Class 2 to Class 9 buildings) or to calculate the exhaust rate from first principles as a performance-based design. Calculations from first principles could be in the form of hand calculations based on empirical formulae in fire engineering literature, by using zone models, or by using field models. The recently published Australian Standard AS/NZS :2015 introduces a new section that sets out design requirements for hot layer smoke control systems. The performance criteria of the systems are that on initiation of fire mode, the hot layer smoke control systems shall operate to exhaust smoke from the hot smoke layer at a rate as determined in accordance with Clause of the Standard. Clause states that the required exhaust airflow rate shall be determined by: using Figure 9.2(a) for general cases, which is identical to Figure 2 in Specification E2.2b of the Building Code of Australia (BCA), or using Figure 9.2(b) for atrium which is similar to Figure 3.4 in Specification G3.8 of the BCA, but the smoke exhaust rate required in the Australian Standard is consistently lower than that in the BCA, or using the equation, EAC = Q FP SLH 1.5 (Equation 1) where EAC = exhaust air capacity (m³/s) Q = fire size (MW) FP = fire perimeter (m) SLH = height to underside of smoke layer (m) Page 1 of 24

2 The exhaust rate equation in AS/NZS :2015 with four decimal places suggest that the accuracy of the calculation results would be of the order of m³/s but there is no information on how the equation was derived nor reference to any engineering literature regarding the source of the equation. There is also no indication in the Standard on which type of fire plumes to which the equation is applicable. Currently the type of fire plumes can be categorised as follows: Point source axisymmetric plumes Finite area source axisymmetric plumes Wall plumes Corner plumes Line plumes Window plumes Balcony spill plumes Furthermore, the equation does not provide any information on or method to estimate the temperature of the hot smoke layer, thus the designer would not be able to determine the likely time of failure of the smoke exhaust fans as well as the likelihood of flashover in the enclosure of fire origin. In addition, Clause of the Standard prescribes the make-up airflow rates (in m³/s) which are the exhaust rates determined from Equation 1 minus 4, 13, 27 and 40m³/s for the associated design fires with steady state heat release rates of 1.5, 5, 10 and 15MW respectively, irrespective of the type of fire plumes and smoke layer temperatures. This paper provides a review of the fundamental principles in various plume theories currently used by fire safety engineering practitioners (locally and overseas), and reports the results of a number of numerical experiments. The experiments were carried out by using zone modelling and field modelling techniques to determine the performance of a smoke extraction system that operates at the smoke exhaust rates determined from Equation 1 for the four design fires mentioned above. 2 PLUME THEORIES Observations and studies on fluid flow could date back to ancient times because such subject was closely related to daily lives such as irrigation and sailing. Bahrami (2011) stated that Archimedes ( B.C.) postulated the parallelogram law for addition of vectors and the laws of buoyancy and applied them to floating and submerged objects. In regard to the studies of fire plumes which formed the foundation of a number of plume theories, attribution may be made to the work of Yih (1950), Rouse et al. (1952), Morton et al. (1956) and Yokoi (1960). The properties of fire plumes are important in the field of fire safety engineering as such properties relate to fire heating of building structures, smoke filling rates, fire venting and the design of fire detection and fire suppression systems. Of particular note is that the mass flow at a particular elevation in a fire plume is almost completely attributable to air entrained by the plume at lower elevations (Heskestad 2016). 2.1 Large fire plume (UK) As a result of a few large fires around the late 1950 s and early 1960 s in single-storey industrial buildings that could not be sub-divided into smaller fire compartments due to operational requirements, Thomas et al. (1963) investigated theoretically and experimentally the use of roof vents to exhaust the hot gases produced by a fire in a large single-storey Page 2 of 24

3 building. In particular, a large fire equation was derived from simple assumptions of entrainment, constant and upward velocity in the flame zone, based on the works of others such as Rouse et al. (1952) and Simms et al. (1960), and took the following form: M = 0.096P(H d) 3/2 o(g s/ o) ½ (Equation 2) where M P H d o s g is the mass rate of entrainment of air is the perimeter of the fire is the ceiling height measured above the fire source is the depth of the hot smoke layer under the ceiling is the density of ambient air is the mean density of the hot smoke layer is the gravitational constant Equation 1 was based on the assumption that A f > ½(H d) and h f > (H d) where A f is the area of the fire and h f is the height of flames above floor level. Assuming the smoke layer temperature is that of the flame as 1500 F (816 C) used in (Thomas et al. 1963), Equation 2 in SI units presented in modern fire engineering literature such as (CIBSE 2010) takes the following form: M = 0.188Pz 3/2 (kg/s) (Equation 3) where z is the distance between the bottom of the hot smoke layer and the top of the fire bed. 2.2 Large fire plume (US) The prediction of smoke mass flow rate in NFPA 92 (2012) for large fire similar to that described in section 2.1 above follows the following procedures. Firstly the limiting flame height needs to be estimated by the following equation: z l = 0.166Q c 2/5 where z l Qc is the limiting flame height (m) is the convective portion of the heat release rate (kw) Secondly if the distance between the base of the fire and the smoke layer interface (Note: this is an input parameter for smoke exhaust system designs) is less than or equal to the limiting flame height, i.e. z z l, then the mass flow rate in the plume at the height z can be determined by: M = 0.032Q c 3/5 z (kg/s) (Equation 4) The form of Equation 4 is significantly different from that reported by Heskestad (1982, 2016) where the mass flow rate in the plume at the height z, for fire source diameters of 0.3m and greater, is predicted by: M = Q c(z/z l) (Equation 5) However, investigation of the differences between the two equations is beyond the scope of this paper, and the NFPA 92 (2012) equation, i.e. equation 4, has been adopted for this study. Page 3 of 24

4 2.3 Point source axisymmetric plume (strong plume) For small fires that can be approximated to a point source, Thomas et al. (1963) developed the following equation based on the work of Yokoi (1960) and Yih (1952) for the mass rate of entrainment of air into the fire plume. M = c[q cg/( cc pt o)] ⅓ z 5/3 (Equation 6) where M c o Q c g C p T o z is the mass rate of entrainment of air is the mean density of the hot smoke layer is the density of ambient air is the convective heat release rate of the fire is the gravitational constant is the specific heat capacity of air is the ambient temperature is the distance between the effective point source and the bottom of the smoke layer, i.e. z = z o + h - d s where z o is the distance between the effective point source and the floor (in modern text this is referred to the point of virtual origin), h is the ceiling height, and d s is the depth of the smoke layer. The significance of equation 6 is that the mass entrainment rate is much more influenced by the vertical distance available for entrainment (power of 5/3) than the heat release rate (power of 1/3). The modern form of Equation 6 in SI units was developed by Heskastad (1982) and included in NFPA92B (1991) since its first edition as follows. M = 0.071Q c⅓ z 5/ Q c when z > z l (Equation 7) where z l = 0.166Q c 2/5 3 NUMERICAL EXPERIMENTS In order to compare the predictive capabilities of the equations in AS/NZS :2015 for smoke exhaust rate and make-up air rate with the equations for the plume theories discussed above, numerical simulations using zone and field modelling techniques have been carried out for a hypothetical building that has nominal dimensions of 30 m x 30 m x 9 m (1) and is served by a mechanical smoke extraction system. Such building could be seen as a representative of an atrium or sports halls and multifunction spaces for holding a variety of events. In the numerical experiments, the design fire sizes follow that in the BCA Specification E2.2b, i.e. having a steady state heat release rate (HRR) of 1.5, 5, 10 and 15 MW, assuming that the fire bed is located at the floor level and the convective heat release rate is 70% of the total heat release rate. The HRRs of the four design fires have been assumed to grow at fast t-squared growth rate for the unsteady state period until peak HRR is reached. A t-squared fast fire would reach 1055 kw within 150 s after it started. This assumption is in line with the recommended 1 The height of the building in the field model numerical analysis could be about 2.2% higher than 9 m due to mesh cell size configuration. However, such increase of building height does not affect the comparisons that are based on the conditions at the steady state of the design fire. Page 4 of 24

5 growth rate for retail occupancies and in stadia as specified in Table 7-2 of Engineers Australia practice note for design fires published in 2012 by the Society of Fire Safety. The fire safety design aims to maintain a smoke layer interface height of 6.5m so that the estimated smoke layer temperature will hopefully be below the temperatures (500 C to 600 C) that are typically considered as an indication that flashover is to occur, noting that there are criteria and have no physical content but are of considerable practical usefulness (Thomas 1995). This is because the zone and field models selected for the numerical experiments were not developed for fully developed fires. Using equation 1 and clause of AS/NZS :2015, the smoke exhaust rates and make-up air flow rates for the four design fires selected have been determined and shown in Table 1 below. Table 1: Smoke exhaust & make-up air flow rates determined in accordance with AS/NZS :2015 Heat release rate (HRR) (MW) Smoke exhaust rate (m³ s -1 ) Make-up air flow rate (m³ s- 1 ) The smoke exhaust rates outlined in Table 1 above have been adopted in the numerical experiments, with the exhaust being provided via four smoke exhaust outlets that are evenly distributed in the enclosure to avoid plugholing. In the simulations, it was assumed that the smoke exhaust fans would start after activation of a smoke detector in the building. The detector activation time was calculated by using the temperature equivalence approach (Heskestad 1981) which assumes the smoke detector to be a sensitive heat detector that would actuate at 13ºC above ambient temperature (IFEG 2005). It is recognised that there are more sophisticated methods to estimate the actuation time of smoke detectors by other means (e.g. Geiman and Gottuk 2006, Mowrer et al. 2008). However, as this study is on comparison of smoke exhaust rates after the design fires have reached their steady state, the actual time of smoke detector actuation is immaterial for the study. Once a fan has started on activation of the smoke detector, it was assumed that it would take 30 seconds to ramp up to its 100% capacity. The activation time of the smoke detector was estimated to be 120 seconds for the four design fires. Thus, the smoke exhaust fans have been specified in the simulations to have zero flow rate at 120 seconds and 100% flow rate at 150 seconds with a linear ramp-up function. Make-up air is provided via four openings with each one located at the centre of each external wall, instead of using a mechanically assisted make-up air system. The opening areas for make-up air for each of the four design fires were specified to be 2.4 m x 1.6 m, 5.2 m x 1.6 m, 4.2 m x 1.8 m, and 6 m x 6 m respectively, based on an exhaust area to make-up air area ratio of 2 for design fires 10 and 15 MW and a ratio of 3 for design fires 1.5 and 5 MW. Narayanan (1993) suggests that the make-up air openings must be located no higher than the lower edge of the smoke reservoir and the NFPA 92B (1991) also specifies that the make-up air opening should be located below the smoke layer interface height. In the field modelling study, the location of make-up air opening was specified to be one mesh cell size (0.6 m) above the floor level for design fires of 10 & 15 MW, and two mesh cell sizes (0.8 m) above the floor level for design fires of 1.5 & 5 MW. As a comparison, the smoke exhaust rates predicted by the three plume theories outlined above have been calculated by using equations 3, 4 and 7. As these equations provide estimates of the mass flow rates rather than volumetric flow rates, the temperature of the smoke layer is required to be estimated for determining the density of smoke. Such estimate is typically based on the conservation of energy principle and assuming adiabatic boundary conditions; the average temperature of the smoke layer can thus be given by: Page 5 of 24

6 T s T o = Q c/(mc p) (Equation 8) where T s is the temperature of the smoke layer ( C or K) T o is the ambient temperature ( C or K) The smoke exhaust rates required to maintain a smoke layer interface height of 6.5m as predicted by equations 3, 4 and 7 in conjunction with equation 8 are summarised in Table 2, and the predicted smoke layer temperatures are provided in Table 3. Table 2: Smoke exhaust rates and make-up air flow rates determined in accordance with equations 3, 4, 7 and 8 in this paper for smoke layer interface height of 6.5m Total HRR (MW) Smoke exhaust rate (m³ s -1 ) by equation 3 (UK large fire plume) Smoke exhaust rate (m³ s -1 ) by equation 4 (US large fire plume) Smoke exhaust rate (m³ s -1 ) by equation 7 (point source axisymmetric plume) Smoke exhaust rate (m³ s -1 ) by equation 1 (AS/NZS :2015) Table 3: Predicted smoke layer temperature for smoke layer interface height of 6.5m Total HRR (MW) Smoke layer temperature ( C) by equation 3 (UK large fire plume) Smoke layer temperature ( C) by equation 4 (US large fire plume) Smoke layer temperature ( C) by equation 7 (point source axisymmetric plume) 3.1 Zone Modelling The smoke layer interface heights in the hypothetical building for the four design fire sizes at the steady state condition have been estimated by using the zone model CFAST Version (Peacock et al. 2016b) developed by NIST. Whilst the initial release of the CFAST model in the HAZARD I package (Peacock et al. 1991) had a limitation in scope to one- and two- family residential structures, the model has been applied by various researchers to other types of buildings such as Duong (1990) and Chow (1994). Recently data from a number of experiments, including that in two large hangars with dimensions of 97.8m x 73.8m x 15m high and 45.7m x 73.8m x 22m high, were used to compare with CFAST predictions on smoke layer temperature and interface height for verification and validation (V&V) purposes (Peacock et al. 2016a). The conclusions drawn from the V&V exercise were that the use of the model is appropriate over a range of conditions for a variety of fire scenarios and although differences between the model and the experiments were evident in these studies, most differences can be explained by limitations of the model and the experiments. Moreover, a large fire in a building would create a two-zone environment, as evident in the FCRC Project 6 shopping centre fire tests (Bennetts et al. 1988) conducted in the Burn Hall Page 6 of 24

7 at the Scientific Services Laboratories in Port Melbourne which has a ceiling height of 9m and a volume of 12,500m³, and observed by one of the authors of this paper personally during one of the tests. The key assumptions in the input data include adiabatic boundary conditions, 30% radiative fraction for the design fire, and a limiting oxygen concentration of 15%. 3.2 Field Modelling Introduction Fire Dynamics Simulator (FDS), a computational fluid dynamics (CFD) model of fire-driven fluid flow, was used to estimate the smoke layer interface heights by using the smoke exhaust rates determined from the equations in AS/NZS :2015 for the four design fires. The FDS software is the product of a collaborative effort led by the National Institute of Standards and Technology (NIST) of the United States Department of Commerce and VTT Technical Research Centre of Finland. FDS solves numerically a form of Navier-Stokes equations appropriate for low-speed (Ma < 0.3) thermally-driven flow with an emphasis on smoke and heat transport from fire (McGrattan et al. 2016). In this study, the latest version of FDS, Version 6.5.3, available to the authors at the time of preparation of this paper has been used. Smokeview is a visualisation program that can be used to read and view graphically the output of FDS (Forney 2016). Typical output measurements of FDS for the gas phase include gas temperature, gas velocity, gas density, smoke concentration and visibility, pressure and heat flux per unit volume. For the solid phase FDS predicts surface and interior temperature, heat flux of both radiative and convective and burning rate. FDS requires the user to specify multiple parameters such as computational domain (building geometry, mesh and cell size), boundary conditions, initial conditions, and characteristics of the design fire (chemical composition of fuel, mass fraction of species, heat of combustion, and radiative fraction). An overview of the computational domain and key FDS user input parameters are provided below: Overview of simulation environment Front and top 3D views of the hypothetical building are shown in Figure 1. Figure 2 contains two 2D views of the building; (a) is a top view illustrating the location of fire and smoke exhaust outlets in the roof, and (b) is a side view showing make-up air opening in the external wall and location and of measuring devices within the building. Figure 3 shows 3D views of the building; (a) is a side view showing measuring devices, make-up air openings, exhaust outlets, smoke layer interface devices, and location of fire, and (b) is a side view showing the configuration of the multiple meshes. Page 7 of 24

8 1(a) 1(b) Figure 1: Simulated building; (a) 3D front view: outline of building, fire location, and computational domain extension (blue lines), (b) 3D top view of building (solid) 2(a) 2(b) Figure 2: (a) 2D top view showing smoke exhaust outlets on the roof, make-up air inlets in external walls, fire at the centre of the building, and domain extension (outer white square) (b) 2D side view showing make-up air opening in the external wall, and measuring devices in the building 3(a) 3(b) Figure 3: 3D view of simulated building; (a) 3D side view showing measuring devices, roof vents and make-up air openings, and (b) 3D top view showing multiple meshes in the computational domain Page 8 of 24

9 3.2.3 FDS user input parameters Design fires The heat release rate (HRR) is an important parameter of the design fire and an FDS user input, which is usually specified as a function of time (Engineers Australia 2012). Table 4 lists the characteristics of the four design fires. In each simulation the fire was placed at the centre of the building and was specified to be located at one cell above the floor level. The simulation period for each run was specified to finish approximately 10 minutes after the design fire HRR has reached the peak heat release rate in order to allow for the smoke layer, temperature and other conditions within the building to stabilise. The chemical composition, heat of combustion and yield of species of the burning fuel was assumed to be 50% wood and 50% polyurethane (flexible) foam which is the average of the associated data for GM21, GM23, GM25 and GM27 outlined in Table and Table of the SFPE Handbook 4 th Edition. The user defined soot yield is one-third (0.034 g/g) of the estimated value of g/g because it has been reported that FDS over-predicts smoke concentration by a factor of 2 to 5 times the measured values, as the dynamic aerosol behaviours of soot, i.e. deposition, settling and agglomeration, have not yet been accounted for by the model (Gottuk et al. 2009). Design fires Total heat release rate (MW) Fire perimeter (AS/NZS :2015) (m) Table 4: Characteristics of selected design fires Fire bed area (m 2 ) Fire intensity (kw/m 2 ) Characteristic fire diameter D* (m) Time to reach peak HRR (s) FDS simulation duration (s) Computation domain, meshes and cell sizes Mesh resolution is another important parameter in field modelling that uses large eddy simulation techniques. FDS uses second-order accurate approximations of both the temporal and spatial derivatives of the Navier-Stokes equations, meaning that the discretization error is proportional to the square of the time step or cell size. In theory, reducing the grid cell size by a factor of two reduces the discretization error by a factor of four, however, it also increases the computing time by a factor of 16 (McGrattan et al. 2016). With any grid resolution study, a point of diminishing returns is reached when the improvement in the quality of the results outweighed by the cost of the computation. The US Nuclear Regulatory Commission (2007) study identified that refining the gird cell size beyond the ratio of characteristic fire diameter to computational cell size (D*/ x) of 4 to 16 did not make a noticeable difference in simulation results. For fire applications, the accuracy of the model depends on the characteristic fire diameter D*, which is defined as (Zhou et al. 2010): where: D* = characteristics fire diameter (m) Q = total heat release rate (kw) D* = [Q / ( o Cp T o g 0.5 )] 2/5 Page 9 of 24

10 o = density of air at ambient temperature (kg m -3 ) C p = specific heat (kj kg -1 K -1 ) T o = temperature of air (K) g = gravity acceleration (9.81 m s -2 ) Petterson (2002) cited in (Zhou et al. 2010) suggested that the cell size near the fire should be D*, and further away from the fire location the largest cell size in the computational domain should not exceed 0.5D*. The computational domain in this study was divided into five meshes in order to specify a finer grid for the fire mesh and a coarser grid for areas further away from the fire, and to allow for a reduced CPU time through utilisation of the multi-core processor (Intel i7-4770k, 3.50GHz) on the PC s. The boundary of the computational domain extends from -1.2 m to 37.2 m in the x-axis, -1.2 m to 37.2 m in the y-axis, and 0 m to 9.6 m in the z-axis. The building geometry extends from 2.4 m to 33.6 m in the x-axis, 2.4 m to 33.6 m in the y-axis and 0 m to 9.0 m in the z-axis. In the grid sensitivity study, all input parameters remained the same except the fire region mesh cell size. Table 5 details the mesh cell sizes that have been analysed. Note: for ease of reference to the simulation runs throughout this paper, the naming of simulation ID was based on the heat release rate and the fire region cell size modelled, e.g. for design fire of 1.5 MW and a fire mesh cell size of 200 mm the simulation ID is referred to as Table 5: Sensitivity analysis mesh sizes Fire total heat release rate (MW) Fire region grid cell size (cm) Bounding meshes grid size (cm) Simulation run scenario ID Total smoke exhaust outlet area (m 2 ) Total make-up air inlet area (m 2 ) Total number of cells CPU time (hours) x 0.1 x x 0.2 x x 0.4 x x 0.4 x (1.6 m x 0.8 m for each of 4 outlets) (2.4 m x 1.6 m for each of 4 inlets) 587, , x 0.1 x x 0.2 x x 0.4 x x 0.4 x (1.6 m x 1.6 m for each of 4 outlets) (5.2 m x 1.6 m for each of 4 inlets) 795, , x 0.15 x x 0.3 x x 0.6 x x 0.6 x (3 m x 1.2 m for each of 4 outlets) (4.2 m x 1.8 m for each of 4 inlets) 292, , x 0.15 x x 0.3 x x 0.6 x x 0.6 x (2.4 m x 2.4 m for each of 4 outlets) 43.2 (6 m x 1.8 m for each of 4 inlets) 356, , Apart from grid independence, there are other tricks of the trade items (Hui and Mendham 2015) such as computational domain extension that could significantly and adversely influence the simulation results. Zhang et al. (2010) studied the effects of computational Page 10 of 24

11 domain on numerical simulation of building fire results and identified the need to extend the domain boundary beyond the physical boundaries of vertical vents opening of the enclosure in order to take into account the interactions of inflow and outflow properly. The study compared experimental data with the numerical results of a domain with and without extended boundary and analysed domain extension in x, y and z directions under different heat release rates. It was reported in Zhang et al. (2010) that the difference in results diminishes as the domain is extended gradually. The extension in the perpendicular directions to the opening was identified to have the most effect on the results. The (Zhang et al. 2010) study also indicated the results of the extended computational domain yielded better agreement with experimental data. The computational domain for the FDS simulations presented in this paper was thus extended by 3.6 m, i.e. one hydraulic diameter of the make-up air inlet opening, according to the findings in Zhang et al. (2010), beyond the building physical geometry in the positive and negative x-axis and y-axis. The x-axis and y-axis boundary planes were specified to be open vents to eliminate the effect of physical / domain boundaries on the results FDS Output parameters Table 6 details the output parameters recorded and the location of the measuring devices. The output parameters write intervals were specified to be 10 s for devices, Plot3D and slice files. Knowledge of visibility and smoke layer interface is required so that the exhaust capacity modelled could be related to the smoke layer interface. Table 6: Output parameters collected Output parameters Velocity (m s -1 ) Temperature ( o C) Visibility (m) Smoke layer interface height above floor level (m) Volumetric flow rate (m 3 s -1 ) Locations of measuring devices Velocity measuring device positioned at the centreline of each exhaust outlet and make-up air opening Temperature measuring devices positioned at the centre of the fire and at the centre of each exhaust outlet. These devices are placed between the roof and 1.8 m above floor level. Slices positioned to cross through the centre of the fire, exhaust outlets and make-up air openings in the x-z plane and y-z plane. Slices positioned to cross through the centre of the fire, exhaust outlets and make-up air openings in x-z plane and y-z plane Four Layer Height devices for measuring the layer height positioned to measure the smoke layer interface between the floor and roof Volumetric flow measuring devices for measuring of the flow through each exhaust outlet and make-up air opening 4 SIMULATION RESULTS 4.1 Zone modelling The modelled heat release rates, predicted smoke layer interface heights and temperatures determined by CFAST are shown in Figures 4-6 respectively. Figure 4 indicates that the heat release rates in the simulations followed the prescribed design fire values. Figure 5 presents an anomaly that the smoke layer interface heights for design fires of 5, 10 and 15MW could be maintained at about 8.7m from floor level with the smoke exhaust rates determined from AS/NZS :2015, which is not what is expected. For the design fire of Page 11 of 24

12 Temperature ( C) Height (m) HRR (kw) 1.5MW, the simulation indicates that the smoke exhaust rate determined from the joint Standard is not adequate to maintain the smoke layer interface height at 6.5m. Figure 6 depicts the predicted smoke layer temperatures which at steady states are higher than the temperatures predicted by all three plume theories presented in section HRR-1.5 HRR-10 HRR-5 HRR Time (s) Figure 4: Modelled Design Fire Heat Release Rates HGT-1.5 HGT HGT-10 HGT-15 Design Time (s) Figure 5: Predicted Smoke Layer Interface Heights TEMP-1.5 TEMP-10 TEMP-5 TEMP Time (s) Figure 6: Predicted Smoke Layer Temperatures Page 12 of 24

13 4.2 Field modelling Grid independence study A grid independence study aimed to determine a mesh cell size that will produce accurate results without inefficient use of resources and unnecessary increase of computational time was performed. Figure 7 shows the FDS predicted smoke layer interface heights and upper layer temperatures as a result of varying the fire region mesh cell size for each design fire. The deviations between the output data are tabulated in Table 7. It should be noted that the computation of percentage deviations was based on the output data after the fire has reached steady state. (a) 1.5 MW & 5 MW temperature (b) 10 MW & 15 MW temperature (c) 1.5 MW & 5 MW layer interface height (d) 5 MW & 15 MW layer interface height Figure 7: Grid independence study results The results presented in Table 7 show that a coarser mesh for the fire region for design fires of 5, 10 and 15 MW predicted a higher upper layer temperature and a lower smoke layer interface height than that with a finer mesh. For the 1.5MW design fire, the difference in the results between the coarser grid and the finer grid is minimal with respect to upper layer temperature and smoke layer interface height. The CPU time with a coarser mesh for the fire region was approximately 6.5, 4.3, 1.2 and 13.7 times shorter than the CPU time with a finer mesh for the 1.5, 5, 10 and 15 MW design fires respectively (Table 5). As the FDS results with a coarser mesh in the fire region were found to be more conservative, the results of simulations with a coarser mesh in the fire region have been adopted for the following analyses. Page 13 of 24

14 Table 7: FDS output parameters percentage deviation Fire total heat release rate (MW) Fire region mesh cell sizes HRR Average make-up air velocity Percentage deviation Smoke layer interface height Upper layer temperature mm vs 200 mm (minimal difference) 0.22 (minimal difference) mm vs 200 mm (coarser mesh shows lower layer height) 3.74 (coarser mesh shows higher temperature) mm vs 300 mm (coarser mesh shows lower layer height) 0.32 (minimal difference) mm vs 300 mm (coarser mesh shows lower layer height) 4.74 (coarser mesh shows higher temperature) Simulation results Selected relevant results predicted by FDS for the four design fires are discussed within this section Heat release rate (HRR) Figure 8 shows that steady state HRRs were reached as specified and maintained for the specified remaining duration of the simulations which means the fires were well ventilated. Figure 8: FDS simulated HRRs of the four design fires Velocity profile through exhaust outlets and make-up air openings Velocity-measuring devices were placed at the centre of each exhaust outlet and make-up air opening. The FDS predicated velocities at each exhaust outlet were averaged to calculate the exhaust velocity. The same method was used to calculate the averaged makeup air velocity. Figure 9 and 10 show the averaged smoke exhaust velocities and make-up air velocities for the four design fires respectively, and steady state conditions were achieved after the heat release rates of the design fires reached their respective peak value. Page 14 of 24

15 (a) 1.5 MW (b) 5 MW (c) 10 MW (d) 15 MW Figure 9: Averaged velocity at the smoke exhaust outlets for simulated design fires; (a) 1.5 MW, (b) 5 MW, (c) 10 MW, and (d) 15 MW Volumetric flow rate Figure 10: Averaged make-up air velocity for simulated design fires Figure 11 shows the predicted smoke exhaust and make-up air volumetric flow rates for the four design fires. The data shows the make-up air volumetric flow rate predicted by FDS is approximately 5 to 10% more than that determined from the AS/NZS :2015 equation. This means the Australian Standard equation underestimates the quantity of make-up air required. However, this underestimate is not considered to be detrimental in this study as natural make-up air is provided. Page 15 of 24

16 However, the velocity of make-up air at the perimeter of large open space needs to be limited to sufficient low value so as to not deflect the fire plume significantly, increase the fire plume entrainment rate, and disturb the smoke layer interface (NFPA ). The NFPA 92 (2012) recommends a velocity of approximately 1 m/s based on the flame deflection data (Mudan and Croce 1988). (a) 1.5MW (b) 5.0MW (c) 10MW (d) 15MW Figure 11: Simulated smoke exhaust and make-up air volumetric flow rates for design fires of 1.5, 5, 10 and 15MW by FDS Smoke layer interface height and visibility Four Layer Height devices positioned at 5.1m from the centre of the fire along the positive and negative x-axis as well as y-axis were specified to measure the smoke layer interface. Figure 12 shows the height of the smoke layer interface for each design fire which is the mean value of the layer heights predicted by FDS from the four Layer height devices. Figure 12 illustrates that the smoke layer interface stabilised at 4.57 m, 4.31 m, 3.77 m and 3.31 m during the steady state period of the 1.5, 5, 10 and 15 MW design fires respectively. The formation of a constant smoke layer interface suggests that the mass of smoke exhausted equalled the mass of air entrained into the plume. The results in Figure 12 show the smoke exhaust rates determined in accordance with AS/NZS :2015 are not sufficient to maintain the design smoke layer interface height of 6.5m. Page 16 of 24

17 Figure 12: Smoke layer interface height predicted by FDS Figure 13 and Figure 14 show the y-z plane images of visibility after steady state conditions were reached. These images show that the depth of the smoke layer decreases with an increase in HRR. The visibility within the lower section of the building for the duration of the simulation remained above 10 m which is considered a suitable tenability limit for large enclosures to assist occupants escape (Engineers Australia 2014). (a) 1.5 MW at 700 s (b) 5 MW at 850 s Figure 13: Smoke layer interface heights for 1.5 & 5 MW design fires (a) 10 MW at 1000 s (b) 15 MW at 1100 s Figure 14: Smoke layer interface heights for 10 & 15 MW design fires Page 17 of 24

18 Temperature profile Five thermocouple trees were included in the simulations to measure the air temperatures; one each at the centreline of each exhaust outlet and one at the centreline of the fire. Each tree has seven thermocouples that were positioned between 1.6 m above the floor level and the roof for design fires 1.5 MW and 5 MW, and between 1.8 m above the floor level and the roof for design fires 10 MW and 15 MW. The vertical distance between each thermocouple was set to be 1.2 m. The four temperatures measured (excluding the thermocouples at the centreline of the fire) at each of the seven elevations were averaged to calculate the mean air temperature at that corresponding elevation. Figure 15 shows the averaged air temperature at each elevation for the modelled scenarios. The results at 9 m for design fires 10 MW and 15 MW being 20ºC were discarded because the devices snapped to the obstruction which is the roof and recorded the temperature of the object rather than the temperature of the gas. (a) 1.5 MW (b) 5.0 MW (c) 10 MW (d) 15 MW Figure 15: Averaged temperature measurements at multiple elevations within the building for design fires: (a) 1.5 MW, (b) 5 MW (c) 10 MW and (d) 15 MW 5 DISCUSSIONS The zone modelling results as shown in Figure 5 indicate that the smoke exhaust rate determined by using the AS/NZS :2015 equation for 1.5MW design fire (19.1m³/s) is not sufficient to maintain a smoke layer interface height of 6.5m; instead, it would require 20.4m³/s from CFAST (trial and error) simulation. Other results in Figure 5 indicate that the opposite observation applies to design fires of 5, 10 and 15MW steady state heat release rate, where smoke exhaust rates determined by the Page 18 of 24

19 joint Standard were found to be more than sufficient to maintain a 6.5m interface height. Additional (trial and error) CFAST simulations indicate that the minimum smoke exhaust rates to maintain 6.5m interface height are 37.8, 60.0 and 80.4m³/s only for design fires of 5, 10 and 15MW respectively, as opposed to 43.5, 67.0 and 90.4m³/s respectively determined by the joint Standard. Overprediction of the smoke layer interface height by CFAST may be due to the mass flow rate across the smoke layer interface not being accounted for in the zone model. Chow et al. (2006) suggested that such mass flow rate could be up to 30% of the smoke mass exhaust rate based on their experimental data from full-scale burning tests on a mechanical smoke exhaust system in a big hall. The field modelling results on predicted smoke layer interface heights presented in Figure 12 show that all four smoke exhaust rates determined by the joint Standard could not maintain an interface height of 6.5m for the four design fires, but at 3.2m to 4.2m only. It should be noted that the smoke layer interface heights in Figure 12 were not determined by visually analysing the slice files at different elevations by the modeller nor by the N- percentage rule (Cooper et al. 1982) which are both considered to be subjective, but by the FDS code internally (see page 225 in McGrattan et al. 2016) using the integral ratio method (He et al. 1998). Coyle and Novozhilov (2007) compared the predictions by FDS Version with the results of full-scale experiments carried out by Yamana and Tanaka (1985) with respect to mechanical extraction of smoke (exhaust rate of 6.0 m³ s -1 with natural make-up air) in the BRI test facility of 30m x 24m x 26.3m high with a 1,300kW steady state fire. Their FDS simulation run (1A) with 500 x 500 x 500mm grid cell size produced rather scattered results at the initial stage and predicted strong downward propagation of smoke contradicting with common sense expectations and experimental results, whereas simulation run (1B) with 400 x 400 x 400mm grid cell size overpredicted smoke descent rate initially and slightly underpredicted at later stages (Figure 16). Coyle and Novozhilov (2007) reported that the overprediction error is approximately 12% at 50s whereas the underprediction error is approximately 35% at 400s. Figure 16: Comparison of FDS predicted smoke layer interface height with experimental data. Smoke extraction of 6.0 m³ s -1 in BRI test facility (adopted from Fig. 7 in Coyle and Novozhilov (2007)) Page 19 of 24

20 Coyle and Novozhilov (2007) also compared the predictions by FDS Version with other experiments with lower exhaust rates of 4.5 and 3.2 m³ s -1 where the make-up air inlet was deliberately closed in the experiments to investigate how well the mechanical extraction system would perform without replacement air. Coyle and Novozhilov (2007) reported that in the 4.5 m³ s -1 exhaust rate scenario, FDS overpredicted the smoke filling rate from a height of 26.3m to a height of 16m by approximately 8% and thereafter it underpredicted the smoke filling rate by approximately 34%. In the 3.2 m³ s -1 exhaust rate scenario, FDS overpredicted the smoke filling rate by approximately 40% for the initial 130s and thereafter underpredicted the filling rate which resulted in a final layer height error (the predicted height was higher than the actual height measured in the experiment) of 42% at 400s. It can be deduced from the discussions above that whilst simulations by using field modelling techniques could provide much more detailed information on parameters such as temperatures, velocities, radiant heat flux and the like of the smoke plume and smoke layer spatially than by using zone modelling techniques, the accuracy of prediction of smoke layer interface height from field modelling is not necessarily higher than that from zone modelling per se. A comparison (Table 8) of the smoke layer temperatures predicted by zone modelling (Figure 6) and field modelling (Figure 15) with that by the three plume theories (Table 3) indicates that there is a general over-prediction of smoke layer temperature by the plume theories and CFAST. This may be due to the conservative assumption in Equation 8 of this paper that there is no heat loss from the smoke layer but in reality a significant amount of heat has been lost through the smoke exhaust outlets. Additional cooling of the fire plume by the make-up air is considered to be unlikely because the make-up air velocities recorded in FDS simulations range from 1.5 to 2.5ms -1 only (Figure 10). It is well known that CFAST overpredicts the upper layer temperature (Peacock et al. 2016a) and in some experiments the deviations could be between 10 to 50% (Luo et al. 1996/1997). Peacock et al. (2016a) states that the most common cause of over prediction of upper layer temperature by CFAST can be attributed to not knowing the species production (soot) and relative absorption of radiation by the gas layers which highlights the importance of scenario specification. A brief literature review indicates that FDS also overpredicts the upper layer temperature. The study of Coyle and Novozhilov (2007) with respect to the 6.0 m³ s -1 exhaust rate scenario reports that the maximum temperature error is approximately 21% at 100s. In the work of Beji et al. (2014) that has the objective to evaluate the capabilities of FDS version with a multi-compartment experimental set-up, general overprediction of the upper layer and lower layer temperatures were observed in the rooms adjacent and connected to the burn room as well as the corridor that connected to the burn room. Table 8: Comparison of predicted smoke layer temperatures between plume theories and CFAST & FDS simulations for smoke layer interface height of 6.5m Smoke layer temperature ( C) \ Total HRR (MW) UK large fire plume prediction US large fire plume prediction Point source axisymmetric plume prediction Maximum smoke layer temperature predicted in CFAST simulations Maximum temperature of smoke layer near the roof recorded in the FDS simulations ~108 ~158 ~230 ~278 ~51 ~78 ~108 ~122 Page 20 of 24

21 As the smoke exhaust rates determined by the joint Standard are higher than the predictions from the three selected plume theories (see Table 2), it implies that using the plume theories would also overestimate the smoke layer interface height if the field modelling simulation results are to be used as the benchmark. Since these plume theories have been widely used in overseas and documented in national engineering standards or fire engineering literature over at least the last three decades without causing significant and adverse consequences or receiving criticism from the fire engineering fraternity or the approval authorities, further research is required to examine whether there are other input parameters and assumptions in the FDS simulations which could influence the output as well as to compare with available experimental data such as that used in the study by Coyle and Novozhilov (2007). 6 CONCLUSION The methodology to determine smoke exhaust rates specified in section 9 Hot layer smoke control systems of AS/NZS has been examined. It was found that the joint Standard has not indicated which types of fire plume are intended to be covered by the methodology, has not provided guidance on how the temperature of the upper smoke layer can be estimated, and has not disclosed the technical basis of the methodology. A significant revision of section 9 of the joint Standard would be required for it to be useful as a tool for performance-based smoke exhaust system design. Numerical experiments were conducted in the study by using zone modelling and field modelling techniques. Based on the assumption that the smoke exhaust rates predicted by the joint Standard and plume theories in Table 2 are reasonably accurate, it was found that the CFAST zone model (V7.2.1) underpredicts the smoke filling rates by 11 to 13%, whereas the FDS field model (V6.5.3) overpredicts the smoke filling rates by about 60% according to the results presented in Figure 12. These observations demonstrate that whilst field modelling has the capability to yield more detailed information about the smoke properties spatially and temporally, it does not infer the predictions by using field modelling techniques must be more accurate than by simpler methods such as zone modelling and empirical equations. Additional research is required to examine the predictive capabilities of FDS V6.5.3 by comparing with available experimental data and to identify which user inputs have significant influence on the simulation results. REFERENCES Australian Building Codes Board, International Fire Engineering Guidelines (IFEG), Edition Bahrami, M. (2011). Introduction, Notes for ENSC 283 Introduction to Fluid Mechanics. Simon Fraser University [Accessed 23 February 2017]. Beji, T., Bonte, F. and Merci, B. (2014). Numerical Simulations of a Mechanically-Ventilated Multi-Compartment Fire. In: Fire Safety Science Proceedings of the Eleventh International Symposium. International Association for fire Safety Science. Bennetts, I.D., Poh, K.W., Poon, S.L., Thomas, I.R., Lee, A.C., Beever, P.F., Ramsay, G.C. and Timms, G.R. (1988). Fire Safety in Shopping Centres. Final Research Report Project 6, Fire Code Reform Research Program. Chow, W.K. (1994). A Short Note on the Simulation of the Atrium Smoke Filling Process Using Fire Zone Models. J. of Fire Sciences, 12: Page 21 of 24

22 Chow, W.K., Yi, L., Shi, C.L., Li, Y.Z. and Huo, R. (2006). Mass flow rates across layer interface in a two-layer zone model in an atrium with mechanical exhaust system. Building and Environment, 41: CIBSE Guide E (2010). Fire Safety Engineering. 3 rd ed. The Chartered Institution of Building Services Engineers, London. Cooper, L.Y., Harkleroad, M., Quintiere, J. and Rinkinen, W. (1982). An Experimental Study of Upper Hot Layer Stratification in Full-Scale Multiroom Fire Scenarios. Journal of Heat Transfer, 104: Coyle, P. and Novozhilov, V. (2007). Further Validation of Fire Dynamics Simulator Using Smoke Management Studies. International Journal on Engineering Performance-Based Fire Codes, 9(1):7-30. Duong, D.Q. (1990). The Accuracy of Computer Fire Models: Some Comparisons with Experimental Data from Australia. Fire Safety Journal, 16: Engineers Australia, 2012, Practice note for design fires, Version 1.2. Society of Fire Safety, New South Wales, Australia. Engineers Australia, 2014, Practice note for tenability criteria in building fires, Version 2, Society of Fire Safety, New South Wales, Australia. Fire Dynamic Simulator, 2016, Version 6.5, National Institute of Standards and Technology (NIST). Forney, G.P. (2016). Smokeview, A Tool for Visualizing Fire Dynamics Simulation Data Volume II: Technical Reference Guide, NIST Special Publication , Sixth Edition. National Institute of Standards and Technology, US Department of Commerce, USA. Geiman, J.P. and Gottuk, D.T. (2006). Evaluation of Smoke Detector Response Estimation Methods: Part I Optical Density, Temperature Rise and Velocity at Alarm. Journal of Fire Protection Engineering, 16(4): Gottuk, D., Mealy, C. and Floyd, J. (2009). Smoke Transport and FDS Validation. Fire Safety Science Proceedings of the Ninth International Symposium, pp He, Y.P., Fernando, A. and Luo, M.C. (1998). Determination of interface height from measured parameter profile in enclosure fire experiment. Fire Safety Journal, 31: Heskestad, G. (1982). Engineering relations for fire plumes. SFPE TR 82-8, Society of Fire Protection Engineers. Heskestad, G. (2016). Fire Plumes, Flame Height, and Air Entrainment. In: Hurley, M.J., ed. SFPE Handbook of Fire Protection Engineering, 5 th ed. Chapter 13, pp , Society of Fire Protection Engineers, Springers New York. Hinkley, P.L. (1986). Rates of production of hot gases in roof venting experiments. Fire Safety Journal, Vol. 10, pp Hui, M.C. and Mendham, F. (2015). Is the use of CFD in developing Alternative Solutions regarded as a professional engineering service and how could its quality be assured? Presentation at the IFE Australia Conference, Fire Safety So much more than compliance with the NCC-BCA, Canberra, 8 th and 9 th October Luo, M., He, Y. and Beck, V. (1996/1997). Comparison of Existing Fire Model Predictions With Experimental Results From Real Fire Scenarios. Journal of Applied Fire Science, 6(4):357. McGrattan, K., Hostikka, S., McDermott, R., Floyd, J., Weinschenk, C. and Overholt, K. (2016). Fire Dynamics Simulator User s Guide, FDS Version 6.5.0, NIST Special Publication 1019 Sixth Edition, National Institute of Standards and Technology, US Department of Commerce, USA. Page 22 of 24

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM , Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,

More information

CFD Model of a Specific Fire Scenario

CFD Model of a Specific Fire Scenario 16 th Australasian Fluid Mechanics Conference Crown Plaza, Gold Coast, Australia 2-7 December 27 CFD Model of a Specific Fire Scenario D. Mackay, T. Barber and E. Leonardi School of Mechanical and Manufacturing

More information

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL , Volume 9, Number 4, p.154-162, 7 NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL D. Mackay and T. Barber School of Mechanical and Manufacturing

More information

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research

More information

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

ZONE MODEL VERIFICATION BY ELECTRIC HEATER , Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting

More information

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand Mohammed Mutafi 1, Mohammad Nasif 1*, William Pao 1 and

More information

Fire Scenario Influence of Material of Boundary Condition on Results

Fire Scenario Influence of Material of Boundary Condition on Results Fire Scenario Influence of Material of Boundary Condition on Results HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE & ENGINEERING Luciano Nigro Andrea Ferrari Elisabetta Filippo Hughes Associates Europe srl

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

Smoke Layer Height and Heat Flow through a Door

Smoke Layer Height and Heat Flow through a Door Smoke Layer Height and Heat Flow through a Door 2018 Smoke Layer Height and Heat Flow through a Door In this tutorial you will simulate a growing fire in the corner of a 5m x 5m room. The room has a 1m

More information

Recent BRANZFIRE enhancements and validation

Recent BRANZFIRE enhancements and validation Recent BRANZFIRE enhancements and validation Michael Spearpoint University of Canterbury Summary BRANZFIRE is a multi-compartment fire zone model that has been under development since 1996 predominately

More information

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea PRACTICAL APPLICATIONS OF FIRE MODELING IN INDUSTRIAL APPLICATIONS By James M. Dewey, Advisor Risk Management

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Jason Huczek a, Marc Janssens a, Kentaro Onaka b, Stephen Turner c a SwRI, 6220 Culebra Road, San

More information

Case Study 2 (Production and Storage Buildings) - Spain

Case Study 2 (Production and Storage Buildings) - Spain Case Study 2 (Production and Storage Buildings) - Spain OBJECTIVE Developed by the SFPE Spanish Chapter Editor: Jimmy Jönsson, JVVA Fire & Risk The objective of this case study is to show how a project

More information

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability Proceedings of the International Conference in Dubrovnik, 15-16 October 2015 FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability Johan Anderson a, Lars Boström a, Robert Jansson

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER , Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology PO Box 310 North

More information

PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR

PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR VIJAY T. D SOUZA, JASON A. SUTULA, STEPHEN M. OLENICK*, WEI ZHANG and RICHARD J. ROBY Combustion Science & Engineering, Inc. Columbia,

More information

Case Study 1 Underground Car Park

Case Study 1 Underground Car Park Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building

More information

Test One: The Uncontrolled Compartment Fire

Test One: The Uncontrolled Compartment Fire The University of Edinburgh BRE Centre for Fire Safety Engineering One Day Symposium on The Dalmarnock Fire Tests: Experiments & Modelling Test One: The Uncontrolled Compartment Fire Cecilia Abecassis

More information

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS Yunlong Liu*, Xijuan Liu and Bradley Paroz Fire Science and Technology Laboratory CSIRO Manufacturing and Infrastructure Technology

More information

Computer Models For Fire and Smoke

Computer Models For Fire and Smoke Computer Models For Fire and Smoke Model Name: JASMINE Version: 3.1 Classification: Very Short Description: CFD or Field A CFD or field model for predicting consequences of fire to evaluate design issues

More information

IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015

IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015 IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015 SCALE MODEL EXPERIMENTS ON SMOKE MOVEMENT IN A TILTED TUNNEL photo Author 1 30 mm 40 mm photo Author 2 30 mm 40 mm

More information

Sprinklers Modeling for Tunnel Road Fire Fighting

Sprinklers Modeling for Tunnel Road Fire Fighting Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and

More information

Smoke Layer Height and Heat Flow through a Door

Smoke Layer Height and Heat Flow through a Door Smoke Layer Height and Heat Flow through a Door 2017 Smoke Layer Height and Heat Flow through a Door In this tutorial you will simulate a growing fire in the corner of a 5m x 5m room. The room has a 1m

More information

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Fire and smoke management in a uni-directional road tunnel for a congested traffic condition Y Liu, J Munro Parsons Brinckerhoff Australia B Dandie Thiess Pty Ltd., Australia ABSTRACT Emergency smoke ventilation

More information

ctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title:

ctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title: ctbuh.org/papers Title: Authors: Subjects: Keywords: Fire Engineering the Tallest Building in the Historic City of Manchester, UK Dean McGrail, Associate Director, WSP Group Simon Lay, Technical Director,

More information

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL

SIMULATION OF A COMPARTMENT FLASHOVER FIRE USING HAND CALCULATIONS, ZONE MODELS AND A FIELD MODEL Reference : Spearpoint M J, Mowrer F W, McGrattan K. Simulation of a single compartment flashover fire using hand calculations, zone models and a field model. Proc. 3 rd International Conference on Fire

More information

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE , Volume, Number 4, p.138-14, 23 EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE Yuanzhou Li, Ran Huo, Liang Yi and Guodong Wang State Key Laboratory of Fire

More information

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose

More information

Advantages and Disadvantages of Fire Modelling

Advantages and Disadvantages of Fire Modelling Advantages and Disadvantages of Fire Modelling Dr Guillermo Rein School of Engineering University of Edinburgh & Imperial College London Dr Guillermo Rein 9 May 2012 Chief Fire Officers Association Annual

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

Simulation of Full-scale Smoke Control in Atrium

Simulation of Full-scale Smoke Control in Atrium Available online at www.sciencedirect.com Procedia Engineering 11 (2011) 608 613 The 5 th Conference on Performance-based Fire and Fire Protection Engineering Simulation of Full-scale Smoke Control in

More information

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space Available online at www.sciencedirect.com Procedia Engineering 31 (2012) 734 738 International Conference on Advances in Computational Modeling and Simulation A Numerical study of the Fire-extinguishing

More information

VIRTUAL FIRES via COMPUTERS

VIRTUAL FIRES via COMPUTERS VIRTUAL FIRES via COMPUTERS Robert N. Meroney Wind Engineering Software Wind Engineering and Fluids Laboratory Civil and Environmental Engineering Colorado State University, Fort Collins, CO Paper prepared

More information

Heat Transfer in Evacuated Tubular Solar Collectors

Heat Transfer in Evacuated Tubular Solar Collectors Heat Transfer in Evacuated Tubular Solar Collectors Graham L. Morrison, Indra Budihardjo and Masud Behnia School of Mechanical and Manufacturing Engineering University of New South Wales Sydney 2052 Australia

More information

Hot Issues in Fire Engineering 28 February 2012

Hot Issues in Fire Engineering 28 February 2012 Hot Issues in Fire Engineering 28 February 2012 A Note on Cabin Fire Design for Protecting Large Halls W.K. Chow Research Centre for Fire Engineering, Department of Building Services Engineering The Hong

More information

Travelling Fires for CFD

Travelling Fires for CFD Travelling Fires for CFD JOAKIM SANDSTRÖM 1,2, XUDONG CHENG 1, MILAN VELJKOVIC 1, ULF WICKSTRÖM 1,3, and TIM HEISTERMANN 1 1 Department of Civil, Mining and Environmental Engineering Luleå University of

More information

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN , Volume 6, Number 4, p.248-254, 04 RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN C.L. Choi Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Water

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Y. Momoi 1, K. Sagara 1, T. Yamanaka 1 and H. Kotani 1 1 Osaka University, Graduate School of Eng., Dept.

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

Figure 1. Structure Used For the Simulations.

Figure 1. Structure Used For the Simulations. OVERVIEW: Vent, Enter, Search (VES) is one of the most talked about tactics in the fire service today. When used correctly, its positive impact can be measured by the lives it saves. The VES method is

More information

Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings

Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings Stephen M. Olenick 1, Richard J. Roby, Douglas J. Carpenter, and Adam Goodman Combustion Science & Engineering, Inc. 8940 Old Annapolis

More information

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Liu Jing 1, Yoshihiro Aizawa 2, Hiroshi Yoshino 3 1 School of Municipal

More information

CFD Analysis of Fire Characteristics on Subway Junction Station

CFD Analysis of Fire Characteristics on Subway Junction Station ISGSR27 First International Symposium on Geotechnical Safety & Risk Oct. 18~19, 27 Shanghai Tongji University, China CFD Analysis of Fire Characteristics on Subway Junction Station G. H. Wu, X. Han, Q.Q.

More information

and vent height on mechanical smoke exhaust efficiency

and vent height on mechanical smoke exhaust efficiency Experimental investigation on influence of smoke venting velocity and vent height on mechanical smoke exhaust efficiency Ji Jie a, Li Kaiyuan b, Zhong Wei c, *, Huo Ran a a State Key Laboratory of Fire

More information

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL / SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 504/220-7475 A CRITIQUE OF HUGHES ASSOCIATES, INC. PAPER TITLED: Analysis of the Performance of Ganged

More information

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS? Corresponding author: Jasmin Geppert University of Bonn Household and Appliance Technology Section Nussallee 5 D-53115 Bonn E-Mail: haushaltstechnik@uni-bonn.de

More information

Aspirating Gas Detection CFD Modelling Predicts Application Performance

Aspirating Gas Detection CFD Modelling Predicts Application Performance Aspirating Gas Detection CFD Modelling Predicts Application Performance Yun Jiang Xtralis, Bentleigh East, Australia Claudio Groppetti Xtralis, Avon, MA, USA Abstract Historically gas detection has utilized

More information

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length HEIMO WALTER Institute for Thermodynamics and Energy Conversion Vienna University

More information

Computer Simulation Investigation on the Effect of Channelled and Unchannelled Screens on Smoke Contamination in Atriums Upper Balconies

Computer Simulation Investigation on the Effect of Channelled and Unchannelled Screens on Smoke Contamination in Atriums Upper Balconies MATEC Web of Conferences 13, 27 (214) DOI: 1.151/ matecconf/ 21413 27 C Owned by the authors, published by EDP Sciences, 214 Computer Simulation Investigation on the Effect of Channelled and Unchannelled

More information

Smoke Transport and FDS Validation

Smoke Transport and FDS Validation Smoke Transport and FDS Validation DANIEL GOTTUK, CHRISTOPHER MEALY and JASON FLOYD Hughes Associates, Inc. 361 Commerce Drive, Suite 817 Baltimore, Maryland 21227 ABSTRACT A 26 Fire Protection Research

More information

STUDY REPORT SR 292 (2013) B-RISK 2013 Software Benchmarking Examples. C.A. Wade

STUDY REPORT SR 292 (2013) B-RISK 2013 Software Benchmarking Examples. C.A. Wade STUDY REPORT SR 292 (213) B-RISK 213 Software Benchmarking Examples C.A. Wade The work reported here was funded by BRANZ from the Building Research Levy. BRANZ 213 ISSN: 1179-6197 Preface This report presents

More information

Experimental Room Fire Studies with Perforated Suspended Ceiling

Experimental Room Fire Studies with Perforated Suspended Ceiling Experimental Room Fire Studies with Perforated Suspended Ceiling FIONA S.C. TSUI 1, W.K. CHOW 1, N.K. FONG 1, Y. GAO 2, H. DONG 2, and G.W. ZOU 2 1 Research Centre for Fire Engineering Department of Building

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings Justin A. Geiman, Noah L. Ryder Fire & Risk Alliance, Rockville, MD, USA André W. Marshall Custom Spray Solutions, Silver Spring,

More information

Shalaby Institute of Fire Protection Heyrothsberge, Germany.

Shalaby Institute of Fire Protection Heyrothsberge, Germany. International Water Mist Conference November 3-4, 2010, Prague, Czech Republic The Influence of Droplet Size of Water Mist on Extinguishment Fire Plume Dr.Hemdan Shalaby Institute of Fire Protection Heyrothsberge,

More information

A study for a fire spread mechanism of residential buildings with numerical modeling

A study for a fire spread mechanism of residential buildings with numerical modeling Safety and Security Engineering IV 185 A study for a fire spread mechanism of residential buildings with numerical modeling C.-S. Ahn & J.-Y. Kim Fire Safety Research Division, Korea Institute of Construction

More information

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE 1 RU ZHOU, 2 WEI ZHANG 1 School of Urban Construction and Safety Engineering, Nanjing University of Technology, Nanjing

More information

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates Zhou Y., Fei Y.*, Hu S. Q. Nanjing Tech University, College of Fire Safety Science and Engineering &

More information

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team Jeremiah Crocker and Dr. Bin Xiao New Technology Team Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved. The products and specifications published herein are for general evaluation

More information

Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications

Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications Pianet Grégoire Studies and modelling section manager Fire and Environmental Department, CNPP

More information

Fire Protection as the Underpinning of Good Process Safety Programs

Fire Protection as the Underpinning of Good Process Safety Programs Fire Protection as the Underpinning of Good Process Safety Programs Key Words: fires; protection, fire; building Background James Milke, Ph.D., P.E., Professor and Chair Department of Fire Protection Engineering

More information

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels Jack R. Mawhinney, P. Eng., FSFPE Javier J. Trelles, Ph.D. Authors & acknowledgement J. R. Mawhinney

More information

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro

NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT Z. Stevanovic 1, T. Valentina 1, N. Kadic 1, Z. Markovic 1,

More information

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS , Volume 11, Number 2, p.21-26, 212 SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS C.Y. Tso and W.K. Chow Research Centre for Fire Engineering,

More information

Practicalities and Limitations of Coupling FDS with Evacuation Software

Practicalities and Limitations of Coupling FDS with Evacuation Software ABSTRACT Practicalities and Limitations of Coupling FDS with Evacuation Software Daniel Rådemar, WSP, Sweden Daniel Blixt, WSP, Sweden Brecht Debrouwere, WSP, Sweden Björn Grybäck Melin, WSP, Sweden Andrew

More information

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS Modeling water-mist based suppression of 34 GJ car-deck fires using FDS S. Li, R. Acharya, M. Colket, V. Sankaran, G. Poncia United Technologies Research Center L. Torpo Marioff Corporation March 1 st,

More information

PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES

PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES R. Huo a, Y. Li a, W. Fan a and W. Chow b a. State Key Laboratory of Fire Science, CHINA b. The Hong Kong Polytechnic University

More information

Tenability criteria for design of smoke hazard management systems

Tenability criteria for design of smoke hazard management systems Tenability criteria for design of smoke hazard management systems By Dr Weng Poh M.AIRAH Associate director, principal fire engineer, Umow Lai Pty Ltd ABSTRACT In the design of smoke hazard management

More information

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario

Water Mist-Based Fire Suppression Modelling of an Office Space Scenario Water Mist-Based Fire Suppression Modelling of an Office Space Scenario Hai Jiang, Vaidya Sankaran, Med Colket, May Corn United Technologies Research Center Kati Laakkonen Marioff Corporation 14th International

More information

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon

More information

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES UDC 614.84 : 628.854 : 52-17 DOI: 10.7562/SE2011.1.01.03 Original article www.safety.ni.ac.rs DARKO ZIGAR 1 DESIMIR JOVANOVIĆ 2 MARTINA ZDRAVKOVIĆ 3 1-4 University of Niš, Faculty of Occupational Safety

More information

Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development

Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development Fire and Evacuation Modeling Technical Conference (FEMTC) 2018 Gaithersburg, Maryland, October 1-3, 2018 Fire Investigation in Italian Waste Treatment Plant: lessons learned and future development Ing.

More information

A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS

A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS , Volume 3, Number 4, p.151-157, 2001 A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS F. Liu and X.Z. Fu Faculty of Urban Construction and Environmental Engineering Chongqing University, Chongqing

More information

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM Mingjie Zheng Research Laboratory, SANKO AIR CONDITIONING CO., LTD. Nagoya, 450-0003, JAPAN ABSTRACT In large

More information

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS Staņislavs GENDELIS, Andris JAKOVIČS Laboratory for mathematical modelling of environmental

More information

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen * Journal of Environmental Protection, 2013, 4, 638-646 http://dx.doi.org/10.4236/jep.2013.46073 Published Online June 2013 (http://www.scirp.org/journal/jep) The Research of Performance Comparison of Displacement

More information

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger International Journal of ChemTech Research CODEN( USA) IJCRGG ISSN 0974-4290 Vol.5, No.2, pp 925-934, April-June 2013 ICGSEE-2013[14th 16th March 2013] International Conference on Global Scenario in Environment

More information

The Prediction of Smoke Detector. Activation Times in a Two-Storey House. Fire through CFD Modelling

The Prediction of Smoke Detector. Activation Times in a Two-Storey House. Fire through CFD Modelling The Prediction of Smoke Detector Activation Times in a Two-Storey House Fire through CFD Modelling Fire Engineering Thesis, 2010 Submitted by Julie Saunders Supervised by Michael Spearpoint, University

More information

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology IJIRST International Journal for Innovative Research in Science & Technology Volume 1 Issue 11 April 2015 ISSN (online): 2349-6010 CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

More information

A Monte Carlo Approach for the Design of Thermal Fire Detection System

A Monte Carlo Approach for the Design of Thermal Fire Detection System A Monte Carlo Approach for the Design of Thermal Fire Detection System Walter W. Yuen Department of Mechanical & Environmental Engineering University of California at Santa Barbara California, USA and

More information

LONGITUDINAL VENTILATION FOR SMOKE CONTROL IN A TILTED TUNNEL BY SCALE MODELING

LONGITUDINAL VENTILATION FOR SMOKE CONTROL IN A TILTED TUNNEL BY SCALE MODELING LONGITUDINAL VENTILATION FOR SMOKE CONTROL IN A TILTED TUNNEL BY SCALE MODELING W.K. Chow, and W.Y. Chung Research Centre for Fire Engineering, Department of Building Services Engineering Area of Strength:

More information

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan Open Journal of Fluid Dynamics, 2017, 7, 205-218 http://www.scirp.org/journal/ojfd ISSN Online: 2165-3860 ISSN Print: 2165-3852 Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke

More information

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment AKIHIKO HOKUGO Building Research Institute Ministry of Construction Tatehara I, Tsukuba-City 305, Japan DAVID YUNG and

More information

COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire Tests in a Residential Unit

COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire Tests in a Residential Unit Application of Structural Fire Engineering, 19-20 April 2013, Prague, Czech Republic COMPARISON OF CFD MODELLING WITH FIRE TESTS Comparison of CFD Modelling with Results of Full Scale Compartment Fire

More information

OIL AND GAS INDUSTRY

OIL AND GAS INDUSTRY FIRED HEATER DESIGN This case study demonstrates the implementation of an API 560 fired heater compound component in Flownex. It also shows how Flownex has been used during the process design and preliminary

More information

Developing a fire model for offshore QRA

Developing a fire model for offshore QRA Developing a fire model for offshore QRA Yongfu Xu & David Worthington DNV Software Palace House 3 Cathedral Street London SE1 9DE yongfu.xu@dnv.com david.worthington@dnv.com Prepared for Presentation

More information

FREQUENCY ENHANCEMENT OF DUAL-JUNCTION THERMOCOUPLE PROBES

FREQUENCY ENHANCEMENT OF DUAL-JUNCTION THERMOCOUPLE PROBES XXIII Biannual Symposium on Measuring Techniques in Turbomachinery Transonic and Supersonic Flow in FREQUENCY ENHANCEMENT OF DUAL-JUNCTION THERMOCOUPLE PROBES James Braun Purdue University Indiana, United

More information

Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters with Ventilation Factors in Balcony

Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters with Ventilation Factors in Balcony Journal of Civil Engineering and Architecture 9 (215) 1341-1353 doi: 1.17265/1934-7359/215.11.9 D DAVID PUBLISHING Full-Scale Measurement and Numerical Analysis of Liquefied Petroleum Gas Water Heaters

More information

Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces

Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces Comparative Evaluation Method for Fire Safety Design of Large Storage Spaces ZHENKUN WU 1,2, HAIHANG LI 1, YAPING HE 3, DECHUANG ZHOU 1, JIAN WANG 1 1 State Key Laboratory of Fire Science, University of

More information

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 6B-2 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea CONDUCTING A FULL-SCALE EXPERIMENT ON A RAIL PASSENGER CAR ABSTRACT N. White and V.P. Dowling CSIRO Fire

More information

A comparison between emergency ventilation systems semi-transvers ventilation and natural ventilation in Road Tunnel A

A comparison between emergency ventilation systems semi-transvers ventilation and natural ventilation in Road Tunnel A A comparison between emergency ventilation systems semi-transvers ventilation and natural ventilation in Road Tunnel A Ludwig Jerräng Carlstedt Fire Protection Engineer, bachelor's level 2017 Luleå University

More information

Compression of Fins pipe and simple Heat pipe Using CFD

Compression of Fins pipe and simple Heat pipe Using CFD Compression of Fins pipe and simple Heat pipe Using CFD 1. Prof.Bhoodev Mudgal 2. Prof. Gaurav Bhadoriya (e-mail-devmudgal.mudgal@gmail.com) ABSTRACT The aim of this paper is to identify the advantages

More information

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? Plumis White Paper April 2017 How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? As with the introduction of every new formal product category through

More information

Chapter 17, Initiating Devices

Chapter 17, Initiating Devices Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.

More information

Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2

Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2 A CFD Analysis of Smoke Movement in Steel Industry Sheds Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2 Mechanical Dept. Dr.Babasaheb Ambedkar College of Engineering and Research,

More information