2. Introduction of Committee Members and Guests. For a committee roster, see page 02.

Size: px
Start display at page:

Download "2. Introduction of Committee Members and Guests. For a committee roster, see page 02."

Transcription

1 NFPA Technical Committee on Educational and Day-Care Occupancies NFPA 101 and NFPA 5000 FIRST DRAFT MEETING AGENDA Tuesday, August 14, 2012 St. Louis Union Station Marriott St. Louis, Missouri 1. Call to Order. Call meeting to order by Chair Alex Szachnowicz at 8:00 a.m. on August 14, 2012 at the St. Louis Union Station Marriott, St. Louis, MO. 2. Introduction of Committee Members and Guests. For a committee roster, see page Approval of Prior Meeting Minutes. Approve the October 22, 2010 meeting minutes. See page The New Process Review. See page Fire Protection Research Foundation Code Fund Work. See page 20. Response to Fire Alarm Signals by Different Age Groups Child cognitive Ability to Follow Instructions Upon Being Awakened 6. Reevaluation of NFPA 5000 Sprinkler Threshold for Educational Occupancies. 7. Correlating Committee Wish List for 2015 Edition. See page Needed Changes for NFPA 5000/101 Correlation. See page Review of Core Chapters First Revisions. Drafts to be provided via separate distribution prior to meeting date. 10. NFPA 101 First Draft (formerly ROP) Preparation. For Public Input, see page NFPA 5000 First Draft (formerly ROP) Preparation. For Public Input, see page Other Business. 13. Future Meetings. 14. Adjournment. Page 1 of 58

2 Address List No Phone Educational and Day-Care Occupancies Building Code Aleksy L. Szachnowicz Chair Anne Arundel County Public Schools 2644 Riva Road Annapolis, MD U 7/24/1997 BLD-END Ron Coté Secretary (Staff-Nonvoting) National Fire Protection Association 1 Batterymarch Park Quincy, MA /28/2012 Ron Coté BLD-END 1/17/1997 BLD-END Steven D. Admire Principal Communication Concepts 101 Saint Louis Fort Worth, TX IM 10/4/2007 BLD-END Samuel S. Dannaway Principal S. S. Dannaway Associates, Inc. 720 Iwilei Road, Suite 412 Honolulu, HI SE 7/24/1997 BLD-END Victor L. Dubrowski Principal Code Consultants, Inc Woodland Parkway St. Louis, MO Alternate: Richard M. DiMisa SE 1/17/1997 BLD-END Keith S. Frangiamore Principal Fire Safety Consultants, Inc Alft Lane, Suite 100 Elgin, IL SE 10/4/2007 BLD-END Dominick G. Kasmauskas Principal National Fire Sprinkler Association, Inc Altamont Avenue, Suite 147 Rotterdam, NY Alternate: Terry L. Phillips M 10/3/2002 BLD-END Alfred J. Longhitano Principal Alfred J. Longhitano, P.E., LLC 26 Salem Road Chappaqua, NY SE 7/23/2008 BLD-END Maria B. Marks M 03/05/2012 Principal BLD-END Siemens Industry 8 Fernwood Road Florham Park, NJ National Electrical Manufacturers Association Alternate: Richard Jay Roberts Vern L. Martindale Principal Church of Jesus Christ of Latter-day Saints 50 East North Temple, 10th Floor Salt Lake City, UT U 1/17/1997 BLD-END Richard E. Merck Principal Montgomery County Fire & Rescue Service 255 Rockville Pike, 2nd Floor Rockville, MD E 1/10/2008 BLD-END Matthew J. Mertens Principal North Shore Fire Department 665 East Brown Deer Road Bayside, WI International Fire Marshals Association E 3/1/2011 BLD-END Kurt A. Roeper Principal ASSA ABLOY 110 Sargent Drive New Haven, CT Steel Door Institute M 7/26/2007 BLD-END Michael L. Savage, Sr. Principal Middle Department Inspection Agency, Inc Holly Road Ridgely, MD E 10/4/2007 BLD-END Page 2 of 58 1

3 Address List No Phone Educational and Day-Care Occupancies Building Code Michael L. Sinsigalli Principal West Hartford Fire Department 95 Raymond Road West Hartford, CT Alternate: Carmen A. Rao E 7/17/1998 BLD-END Catherine L. Stashak Principal Office of the Illinois State Fire Marshal Division of Technical Services James R. Thompson Center 100 West Randolph Street, #4-600 Chicago, IL Office of the Illinois State Fire Marshal Alternate: Kenneth Wood 06/28/2012 Ron Coté BLD-END E 1/17/1991 BLD-END Billy E. Upton Principal Ballou Justice Upton Architects 2402 North Parham Road Richmond, VA SE 7/26/2007 BLD-END Ann Marie A. Wolf Principal Sonora Environmental Research Institute, Inc East Grant Road Tucson, AZ C 03/05/2012 BLD-END Richard M. DiMisa Alternate Code Consultants, Inc Woodland Parkway, Suite 300 St. Louis, MO Principal: Victor L. Dubrowski SE 3/4/2009 BLD-END Terry L. Phillips Alternate National Fire Sprinkler Association, Inc Meadow Drive Cheyenne, WY Principal: Dominick G. Kasmauskas M 7/26/2007 BLD-END Carmen A. Rao Alternate Wallingford Fire Prevention Bureau 75 Masonic Avenue Wallingford, CT Principal: Michael L. Sinsigalli E 03/05/2012 BLD-END Richard Jay Roberts Alternate Honeywell Life Safety 3825 Ohio Avenue St. Charles, IL National Electrical Manufacturers Association Principal: Maria B. Marks M 3/1/2011 BLD-END Kenneth Wood Alternate Office of the Illinois State Fire Marshal 100 West Randolph St., Suite Chicago, IL Office of the Illinois State Fire Marshal Principal: Catherine L. Stashak E 10/10/1997 BLD-END Ron Coté Staff Liaison National Fire Protection Association 1 Batterymarch Park Quincy, MA /17/1997 BLD-END Page 3 of 58 2

4 ROC MEETING MINUTES Building Construction Life Safety Technical Committee on Educational and Day-Care Occupancies Friday, October 22, 2010 Teleconference Meeting 1. Call to Order. The teleconference meeting was called to order by Chair Aleksy Szachnowicz at 10:00 a.m. Eastern on Friday, October 22, Introduction of Committee Members. The following committee members were in attendance. TECHNICAL COMMITTEE MEMBERS PRESENT NAME Aleksy Szachnowicz, Chair Ron Coté, Nonvoting Secretary Thomas Beare, Principal Samuel Dannaway, Principal Keith Frangiamore, Principal Vern Martindale, Principal Richard Merck, Principal Kurt Roeper, Principal REPRESENTING Anne Arundel County, Public Schools NFPA Siemens Industry Rep. National Electrical Manufacturers Association S. S. Dannaway Associates, Inc. Fire Safety Consultants, Inc. Church of Jesus Christ of Latter-day Saints Montgomery County Fire Rescue Service Ingersoll-Rand Security Technologies Rep. Steel Door Institute BLD/SAF-END ROC Meeting Minutes / Page 1 Page 4 of 58

5 Michael Savage, Principal Cathy Stashak, Principal Middle Department Inspection Agency, Inc. Office of the Illinois State Fire Marshal TECHNICAL COMMITTEE MEMBERS NOT PRESENT NAME Steven Admire, Principal Victor Dubrowski, Principal Dominick Kass, Principal Alfred Longhitano, Principal Michael Sinsigalli, Principal Billy Upton, Principal REPRESENTING Communication Concepts Code Consultants, Inc. National Fire Sprinkler Association, Inc. Alfred J. Longitano, P.E., LLC Chappaqua Fire Department West Hartford, Fire Department Ballou Justice Upton Architects 3. Approval of Minutes. The minutes of the December 8, 2009 meeting were approved as written and distributed. 4. The Revision Process. Staff addressed the actions that the committee could take at the ROC meeting; described the letter ballot for recording the written vote on the committee actions on the comments; and highlighted significant changes made to the core chapters during the ROC meetings held two weeks earlier. 5. NFPA 101 ROC Preparation. All comments were addressed. See the ROC letter ballot. 6. NFPA 5000 ROP Preparation. All comments were addressed. See the ROC letter ballot. 7. Other Business. - Cathy Stashak and Alex Szachnowicz agreed to draft work statements for potential Research Foundation work on issues related to (1) response to fire BLD/SAF-END ROC Meeting Minutes / Page 2 Page 5 of 58

6 alarm signals by different age groups and (2) child cognitive abilities to follow instructions including upon being awakened. - Cathy Staskak advised that she and Ken Wood have identified needed changes in the day-care occupancy chapters and will provide recommendations for such changes for the next revision cycle. - The committee agreed to keep on the agenda a reevaluation of the NFPA 5000 sprinkler threshold for educational occupancies. 8. Future Meetings. The committee will need to meet in the Fall of 2012 to prepare the Reports on Proposals (ROPs) for the 2015 editions of NFPA 101 and NFPA Adjournment. The meeting was adjourned at 12:40 PM. Minutes prepared by Ron Coté and Linda MacKay BLD/SAF-END ROC Meeting Minutes / Page 3 Page 6 of 58

7 NFPA 101/5000 First Draft (Public Input) Meeting Educational - Day Care 1 NFPA 101 / 5000 First Draft (Public Input) Technical Committee Meeting Meeting General Guidelines Fire Safety If alarm sounds 2 Members, please make changes to your contact information on roster sheets accompanying the signin list Use of tape recorders or other means capable of reproducing verbatim transcriptions of this meeting is not permitted Guests Members representing another interest category Page 1 Page 7 of 58

8 NFPA 101/5000 First Draft (Public Input) Meeting NFPA First Draft Meeting General Procedures o Follow Robert s Rules of Order. o Discussion requires a motion. 3 NFPA First Draft Meeting 4 Motions for Ending Debate Previous Question or Call the Question o Not in order when another has the floor o Requires a second o This motion is not debatable and DOES NOT automatically stop debate o A 2/3 affirmative vote will immediately close debate and return to the original motion on the floor. Less then 2/3 will allow debate to continue. Page 2 Page 8 of 58

9 NFPA 101/5000 First Draft (Public Input) Meeting NFPA First Draft Meeting Committee member actions: o o o Member addresses the chair. Receives recognition from the chair. Introduces the motion. o Another member seconds the motion. 5 NFPA First Draft Meeting 6 Committee chair actions: o States the motion. o Calls for discussion. o Ensures all issues have been heard. o Takes the vote. o Announces the result of the vote. Page 3 Page 9 of 58

10 NFPA 101/5000 First Draft (Public Input) Meeting NFPA First Draft Meetings Technical Committee on Educational and Day-Care Occupancies (17) Enforcers, 5 Members: 29% Installer/Maintainer, 1 Member: 6% Manufacturers, 3 Members: 18% Special Experts, 6 Members: 35% Users, 2 Members: 12% 7 NFPA 101/NFPA 5000 New Process Timeline Public Input Stage (First Draft): PI Closing Date: May 4, 2012 First Draft Meeting: Core Chapters: May 21-25, 2012 Occupancy Chapters: August 12-16, 2012 Correlating Committees: November 5-7, 2012 Posting of First Draft for Balloting Date: Varies by TC Posting of First Draft for Public Comment: February 22, 2013 Comment Stage (Second Draft): Public Comment Closing Date: May 3, 2013 Second Draft Meeting: Core Chapters: May 20-23, 2013 Occupancy Chapters: June 24-27, 2013 Correlating Committees: October, 2013 Posting of Second Draft for Balloting Date: Varies by TC Posting of Final Second Draft for NITMAM: January 3, Page 4 Page 10 of 58

11 NFPA 101/5000 First Draft (Public Input) Meeting NFPA 101/NFPA 5000 New Process 9 Timeline Tech Session Preparation: NITMAM Closing Date: February 7, 2014 NITMAM /CAM Posting Date: April 4, 2014 NFPA Annual Meeting: June 9-12, 2014 Standards Council Issuance: Issuance of Documents with CAM: August 14, 2014 with 2015 edition date Changes in Terms: NFPA 101/NFPA 5000 New Process Terms 10 New Term Input Stage Public Input First Draft Meeting Committee Input Committee Statement (CS) First Revision (FR) First Draft Report First Draft Old Term ROP Stage Proposal ROP Meeting Committee Proposal that Failed Ballot or Trial Balloon Committee Statement Committee Proposal or Accepted Public Proposal ROP ROP Draft Page 5 Page 11 of 58

12 NFPA 101/5000 First Draft (Public Input) Meeting Changes in Terms: NFPA 101/NFPA 5000 New Process Terms 11 New Term Comment Stage Public Comment Second Draft Meeting Committee Comment Second Revision Second Draft Report Second Draft Old Term ROC Stage Public Comment ROC Meeting Committee Comment that Failed Ballot or Trial Balloon Committee Comment or Accepted Public Comment ROC ROC Draft NFPA 101/NFPA 5000 New Process Actions 12 NEW Committee Actions and Motions: o Resolve Public Input o Create a First Revision o Create a Committee Input (Trial Balloon) Page 6 Page 12 of 58

13 NFPA 101/5000 First Draft (Public Input) Meeting NFPA 101/NFPA 5000 New Process Actions 13 Resolve a Public Input (No Change to Text): o Committee does not want to incorporate the Public Input (PI) as a revision. o Committee develops a Committee Statement (CS) to respond to (resolve) a Public Input. o Committee must indicate, in CS, reasons for not accepting the recommendation (more on Slide 16). o CS does not get balloted. NFPA 101/NFPA 5000 New Process Actions Create a First Revision (FR) 14 o Committee details the change (in legislative text) it is making to current document. o Committee develops a Committee Statement (CS) substantiating the change. o If the revision is associated with one or more Public Input, the Committee develops a CS to respond to each PI. o Each FR gets balloted. Page 7 Page 13 of 58

14 NFPA 101/5000 First Draft (Public Input) Meeting NFPA 101/NFPA 5000 New Process Actions Create a Committee Input (Trial Balloon) 15 o Committee wants to receive Public Comment on a topic, but not ready to incorporate it into the draft. o Need to provide a Committee Statement. o Does not get balloted. NFPA 101/NFPA 5000 New Process Actions 16 Committee Response (CS) to Public Input: o All PI must receive a response (CS). o Advise submitter of flaws. o Provide reasons why committee disagreed. o Provide direction relative to refinement needed for securing committee s support. o Explain how the submitter s substantiation is inadequate. Page 8 Page 14 of 58

15 NFPA 101/5000 First Draft (Public Input) Meeting NFPA 101/NFPA 5000 New Process Actions Committee Response (CS) to Public Input: o Should reference the First Revision i if it addresses the intent of the Submitter s Public Input. 17 Formal voting NFPA 101/NFPA 5000 New Process Voting 18 o Voting during meeting is used to establish a sense of agreement (simple majority), and move First Revisions to letter ballot. o Secured by letter ballot (2/3 agreement). o Only the results of the formal ballot determine the official position of the committee on the First Draft. Page 9 Page 15 of 58

16 NFPA 101/5000 First Draft (Public Input) Meeting NFPA 101/NFPA 5000 New Process Voting Ballots are on the First Revisions (FR) ONLY Public Input and Committee Input not balloted Reference materials are available: First Draft, PI, CI, CS Ballot form allows you to vote: o o Affirmative on all FR Affirmative on all FR with exceptions specifically noted Ballot form provides a column for affirmative with comment o Note: This box only needs to be checked if there is an accompanying comment. Reject or abstain requires a reason. 19 NFPA 101/NFPA 5000 New Process Voting 20 Initial ballot. Circulation of negatives and comments. Members may change votes during circulation. First Revision that fails letter ballot becomes Committee Input (CI) just like the trial balloon version of CI so as to solicit Public Comment. Page 10 Page 16 of 58

17 NFPA 101/5000 First Draft (Public Input) Meeting Balloting NFPA 101/NFPA 5000 New Process Voting 21 o Balloting will be web-based, based on-line format. o Alternates encouraged to return ballots. 22 TC Struggles with an Issue TC needs data on a new technology or emerging issue Two opposing views on an issue with no real data Data presented is not trusted by committee Code Fund Lends a Hand TC rep and/or staff liaison submits a Code Fund Request Requests are reviewed by a Panel and chosen based on need / feasibility Research Project Carried Out Funding for project is provided by the Code Fund and/or industry sponsors Project is completed and data is available to TC Page 11 Page 17 of 58

18 NFPA 101/5000 First Draft (Public Input) Meeting Legal 23 Antitrust: the single most important provision- Federal law prohibits contracts, combinations, or conspiracies which unreasonably restrain trade or commerce. Section 1 of the Sherman Act Patent: Disclosures of essential patent claims should be made by the patent holder, but others may also notify NFPA if they believe that a proposed or existing NFPA standard includes an essential patent claim. Legal Activities Disapproved by the Courts Packing meetings 24 Hiding commercial interest throwing the committees out of balance No decision-making authority to unbalanced Task Groups; include all interested parties. Hiding scientific or technical information from committees Page 12 Page 18 of 58

19 NFPA 101/5000 First Draft (Public Input) Meeting Doc Info Pages 25 Document Information Next Edition Technical Committee Document scope Current/Previous Edition information Issued TIAs, FIs and Errata Archived revision information Standard Council Decisions Articles and Reports Read only document Meetings and Ballots ROP/ROC or First Draft Report and Second Draft Report NITMAM and Standards Council Decisions Submission of Public Input/Comment Private TC info Ballot circulations, informational ballots and other committee info Committee name, responsibility and scope Staff liaison Committee list Private committee contact information Current committee documents in PDF format Committees seeking members and committee online application NFPA First Draft Meetings 26 Questions Page 13 Page 19 of 58

20 MEMORANDUM TO: FROM: NFPA Staff Liaisons Amanda Kimball, Research Project Manager, Fire Protection Research Foundation Amy Cronin, Secretary, NFPA Standards Council DATE: 17 April 2012 SUBJECT: Results of 2012 Research Projects in Support of NFPA Codes and Standards Process In 2011, you received two memorandums from us asking for ideas on possible research projects to help support the work of NFPA Technical Committees. In response we received 74 submittals representing a wide spectrum of NFPA activities, almost double the number from Thanks to those of you who submitted research statements for 2012 proposed projects. The full list of this latest round of submittals is attached for your information. All project submittals were subjected to a thorough review by a project review panel, with consideration of factors such as relevance to mission, likelihood of success, other available funding, required time frame, relation to strategic research agenda, etc. As a result, the following projects have been selected, with the assistance of the Foundation s review panel, to receive full or partial funding support: Determining the Appropriate Emergency First Responder PPE for Hybrid and Electric Vehicle Fires (NFPA 70E, 1851, 1855, 1951, 1971, 1975, 1999) Guide to Applying Reliability Based Decision Making to ITM Frequency for Fire Protection Systems and Equipment (all NFPA standards that have inspection, testing, and maintenance requirements) Development of Quantitative Risk Assessment Examples for Operating Rooms (NFPA 99) Defining Emergency and Non Emergency Use of Buildings by Occupants (NFPA 1, 101, and 5000) Assessment of Emergency Responder Performance Characteristics for All Hazards Response Environments (NFPA 450, 610, 1001, 1003, 1006, 1021, 1026, 1035, 1051, 1061, 1081, 1091, 1201, 1221, 1250, 1404, 1410, 1500, 1521, 1581, 1600, 1620, 1710, 1720, 1851, 1852, 1855, 1951, 1971, 1975, and 1999) Community Paramedicine and the Integration of Health Care (New Project) Assessment of Total Evacuation Systems of Tall Buildings (NFPA 101) Sprinkler Protection for Cloud Ceilings (NFPA 13) Combustible Metals Case Studies (NFPA 484) In addition, several more candidate projects are still being evaluated may still go forward with partial funding, as student projects, or using external funding means. Projects still being considered include: Improved SCBA Face Mask Design and Testing (NFPA 1404, 1852, and 1981) Development of a Quantitative Risk Assessment Methodology Protocol for LNG Facilities Siting (NFPA 59A) Development of a Quantitative Risk Assessment Methodology for Mass Notification Systems (NFPA 72) Hydrant Flow Testing Study (NFPA 13 and 24) Assessing the List of Typical Oxidizers (NFPA 400) Page 20 of 58

21 Fire Protection Piping C Factor Evaluation (NFPA 13) Sprinkler Protection Criteria for Automated Parking Structures (NFPA 13) Developing a Quantitative Method for Height and Area Limitations (NFPA 5000) Post Fire Electrical Equipment Evaluations (NFPA 70) Women s FF Glove Sizing (NFPA 1971) Determining Self Preservation Capability in Pre School Children (NFPA 101) Fuel Gas Hose Standards and Test Methods (NFPA 54 and 58) Impacts of Pressure Surges on Water Based Fire Protection Systems (NFPA 13, 20, and 24) Analysis of Recruit or Initial Fire Fighter Training Curricula (NFPA 472, 1001, and 1072) NFPA 1710 Turnout Time Motion Study (NFPA 1710) Continued Use of Electrical Equipment Exposed to Transient Voltage Surge (NFPA 70) Guidance for Use of Encapsulator Agents in Water Based Fixed Systems (NFPA 13, 15, 16, 18, 18A, 850, and 851) Assessment of Fire Safe Materials for Oxygen Enriched Atmospheres (NFPA 99) Recommendations for Land Based Fire Fighters that Respond to Marine Vessel Fires (NFPA 1005 and 1405) Hybrid Water Mist Fire Protection Systems (NFPA 750 and 2001) The Ultimate Fire Investigator s Tablet (NFPA 921) Code Fund information is available on a dedicated website: In addition to providing a status update on all prior and currently active projects, it also provides the submittal form so that new projects can be entered at any time throughout the year. These will be collected and reviewed on an annual basis. As you know the Research Foundation provides an important mechanism for facilitating research to support the work of NFPA Technical Committees, and we re fortunate to have this opportunity to address a limited number of projects. For those projects that are not going forward at this time, we will reassess and consider them for funding next year if they are still relevant to the Technical Committee(s) involved. Please contact us if you have any questions; thanks again for your help with this initiative. c: TC and TCC Chairs Page 21 of 58

22 2012 Code Fund Project Submittals ID# Title Document 1201 Regulatory and Adoption Assessment of Standardization for Emergency Management and Business Continuity Hybrid Water Mist Fire Protection Systems 750, Fuel Gas Hose Standards and Test Methods 54, Vent Line Manifold Size and Installation Requirements Internal Sprinkler Inspections/Obstruction Investigation Effectiveness Vapor Mitigation Design by Water Spray Systems Wildland Safety Clothing Heat Stress Testing Fire Service Reputation Management Preventing Cheating on Fire Service Professional Qualifications Tests 1500, ProQual documents 1209 Peer Review and Literature Review: Feasibility Study to Determine Sprinkler Performance and Performance of Automatic Smoke and Heat Vents Assessment of Fire Safe Materials for Oxygen Enriched Atmospheres Defining Emergency and Non Emergency Use of Buildings by Occupants 1, 101, Terminal Temperature of SE/SEU/SER Cable Run Through Thermal Insulation Developing a Quantitative Method for Height and Area Limitations Guidance for Use of Encapsulator Agents in Water Based Fixed Systems 13, 15, 16, 18, 18A, 850, Staffing Recommendations for NFPA 950/951 Compliance 950, Determining the Appropriate Emergency First Responder PPE for Hybrid and Electric Vehicle Fires 70E, 1851, 1855, 1951, 1971, 1975, Quantifying Heavy Snowfall in NFPA Hydrant Flow Testing Study 13, Sprinkler Protection Criteria for Automated Parking Structures Sprinkler Protection for Cloud Ceilings Post Fire Electrical Equipment Evaluations Continued Use of Electrical Equipment Exposed to Transient Voltage Surge Development of a Quantitative Risk Assessment Methodology Protocol for LNG Facilities Siting 59A 1224 Development of a Quantitative Risk Assessment Methodology for Mass Notification Systems Analysis of Recruit or Initial Fire Fighter Training Curricula 472, 1001, NFPA 1710 Turnout Time Motion Study Requirements for Deflagration Isolation in Small Diameter Ducts 61, 484, 654, 655, 664, Haz Mat Fundamentals TC 1228 Analysis of Engine Room Fire Detection and Fixed Fire Suppression Systems Aboard Watercraft 301, Women's FF Glove Sizing Development of Quantitative Risk Assessment Examples for Operating Rooms Converting New Friction Loss Coefficients to Metric 1002, Tall Building Safety Rating System (TBSRS) 101, Assessment of Total Evacuation Systems of Tall Buildings Large Grain Silo Explosion Venting 61 Page 22 of 58

23 ID# Title Document 1236 Evaluation of Existing Inspection, Testing, and Maintenance (ITM) Intervals for Suppression Systems in "Protected" Sites Analysis of Wildland / Urban Interface (WUI) Exposure to Buildings 1143, NFPA79 and IEC Comparison Guide Community Paramedicine and the Integration of Health Care New Project 1240 Assessing the List of Typical Oxidizers Combustible Metals Case Studies Assessment of Emergency Responder Performance Characteristics for All Hazards Response Environments 450, 610, 1001, 1003, 1006, 1021, 1026, 1035, 1051, 1061, 1081, 1091, 1201, 1221, 1250, 1404, 1410, 1500, 1521, 1581, 1600, 1620, 1710, 1720, 1851, 1852, 1855, 1951, 1971, 1975, and Review of Occupational Injuries from Electrical Shock and Arc Flash Accidents 70E 1244 Use of Contact Lenses During Arc Flash/Blast Event 70E 1245 Residential Fire Sprinkler Water Quality Investigation 13D 1246 Steam Fire Extinguishing System Design and Application Response Times for On Airport ARFF Fire Departments Assess the Value of Combining the Life Safety and Critical Branches within a Hospital Assess the Feasibility of Alternate Means of Communication Between Patients and Nurses Cost and Feasibility of Automatic Sprinkler Systems for all Animal Housing Facilities Quantitative Research on Fires in Animal Housing Facilities Recommendations for Land Based Fire Fighters that Respond to Marine Vessel Fires 1005, Equipment Grounding Conductor Sizing in Standard Multiconductor Cables The Ultimate Fire Investigator's Tablet Evaluation of Arc Mapping Risk Assessment Methodology to Determine Test Frequencies and Performance of Integrated Fire Protection and Life Safety Systems Evaluation of "Alternate Equipotential Bonding Means" to Reduce Voltage Gradients in Pool Areas, Phase II Characterization of Harmonic Producing Loads and Load Composition in Distribution Systems Fire Protection Piping C Factor Evaluation Hazards of Cryogenic CO2 Carbonated Beverage Sprinkler Obstruction in Small Rooms Antifreeze Solutions in Non Residential Occupancies Impacts of Pressure Surges on Water Based Fire Protection Systems 13, 20, Improved SCBA Face Mask Design and Testing 1852, 1981, Substantiation for Surge Protection Devices NFPA 79 NFPA 70 Comparison 70, 79 Page 23 of 58

24 ID# Title Document 1267 Research and Analysis of the Adoption of New Functional Safety Requirements by Domestic and International Standards for Machine Guarding Voltage Drop in Long Cable Runs Evaluation of Corrugated Stainless Steel Tubing (CSST) Response to a Direct Strike to a Structure The Effects on the Human Body with Circuits of Under 50 Volts 70, 70E 1271 Response to Evacuation Signals and Instructions by Children and Teenagers Determining Self Preservation Capability in Pre School Children Fire Protection for the Marine Environment 302, 301, Effectiveness of Oven and Furnace Explosion Relief Requirements 68, 86 Page 24 of 58

25 9. Increasing Attendance at Technical Committee Meetings. Robert Solomon reported on the NFPA goal of increasing attendance at technical committee meetings. Efforts are being made to attract participants from the geographic area where the committee meeting is being held via communication with professional groups. Use of social media is being considered. Participation via telephone and Microsoft Live Meeting is being considered for committees with few Public Input items and for which short duration meetings are expected. 10. New Codes and Standards Revision Process. Robert Solomon used a PowerPoint presentation, for which handouts of the slides were distributed by on March 12, to explain terminology and the workings of the new revision process. Approximately 1.5 hours into the review, it was agreed to leave this agenda item and move to the agenda item addressing the identification of subject areas for technical committee focus during the upcoming revision cycle. 11. Subject Areas for TC Focus During 2015 Edition Revision Cycle. The correlating committees reviewed the list of 36 subject areas as prepared by staff mainly from committee meeting minutes distributed with the agenda. Item 36 referenced the subjects detailed in the SAF-AAC meeting minutes of January 6, 2011, also included in the agenda packet. Members introduced additional items for consideration, including those received via from Jim Lathrop, chair of BLD/SAF-MEA who was unable to participate in the meeting. The following is a list of subject areas that the technical committees are already scheduled to address or are asked by the correlating committees to address for preparation of NFPA and NFPA No. Subject Notes 1 Glossary of Terms (GOT) TCs are asked to remove requirements from documents. Place requirements in code provisions. Document or Committee Impacted NFPA 101 NFPA 5000 All TCs All TCs Up-to-date GOT, with designation of assigned TC and preferred definition, does not exist. TCs are asked to respond to PIs relative to definitions and to do their best relative to moving toward standardization. Efforts needed to implement new revision process might preclude much effort from being expended on GOT issues. 2 Update requirements Correlation needed Not AXM, BCF, BLD AAC and SAF AAC pre First Draft planning meeting March 13, 2012 Page 7 Page 25 of 58

26 No. Subject Notes in NFPA 5000 to include changes made in recent editions of NFPA 101 to the provisions for new construction, but missed for NFPA Non Emergency Movement and Non- Fire Emergency situations in/outside of buildings 4 Multi-hazards (other than fire) 5 Atrium as occupancy separation 6 Study use of FRTW in plenum spaces regulated by NFPA 90A Examples: Baseball park patron reaches for ball and falls over guard; outside shooter protect in place; weather events; gas leak Document or Committee Impacted NFPA 101 NFPA 5000 Applicable BSF, DET, END, FIR, FUN, FUR, HEA, IND, MEA, MER, RES AXM, FUN, MEA, MER Task group of FUN assigned FUN FUN Subject rejected during last revision cycle Topic of appeal to NFPA Standards Council. BLD- AAC asked SCM and BLC to look at issue again for 2015 editions. Receive input from AIC-AAA as well. 7 Photovoltaic Systems Topic of Held comment in NFPA Cuts across multiple TCs and projects. Consider formation of a Task Group comprised of members from BLC, BSY, SCM as well as NEC-AAC, FCC-AAA and a representative of the NFPA Fire Service Section to look at the issue and develop a recommendation. 8 Revise or remove Height and Area tables in NFPA 5000 Area limitations in Table were questioned during last cycle. FPRF fund request submitted but not yet acted on. FUN May impact Chapter 8 Not applicable Not Applicable AXM, FUN, MEA, MER FUN BLC, SCM BLC, BSY, SCM BLD AAC and SAF AAC pre First Draft planning meeting March 13, 2012 Page 8 BLC 9 Defining exit access, Task group of MEA assigned MEA MEA exit, exit discharge 10 Atrium egress Task group of MEA assigned MEA MEA 11 Stair descent devices relative to RESNA product standard Task group of MEA assigned. MEA annex material might be deleted MEA MEA, BSY Page 26 of 58

27 No. Subject Notes upon completion of RESNA standard 12 Anthropometric Data Consider currency of the data (as shown in 101: A ); secure new data; revise code requirements where needed 13 Exiting within super- Consider provisions for secure buildings 14 Evaluate current requirements for existing buildings 15 Accessibility criteria of NFPA NFPA 5000 Accessibility 17 Energy Conservation Provisions Document or Committee Impacted NFPA 101 NFPA 5000 MEA MEA MEA MEA shelter-in-place Reality check? MEA MEA Topic of appeal to NFPA Standards Council involving jurisdiction of BSY and RES on visitability issue. Do Occupancy TCs have the ability to modify BSY actions on this subject? Do 2010 DOJ Standards create need for revisions? Level of stringency, impact on fire and life safety and availability of ASHRAE 90.1 and Mechanical Code Include reference to IAPMO Mechanical Code? 19 Plumbing Code Include reference to IAPMO Plumbing Code? 20 Isolated Hazardous Clarification of intent of Area/Special Hazard application of not more than sprinkler protection 6 sprinklers supplied by 21 Occupant notification via public address/entertainment system in assembly occupancies 22 Assembly seating aisle termination 23 Evaluation of smokeprotected assemblyseating capacity factors 24 Assembly occupancies life domestic water Task group of AXM assigned Task group of AXM assigned Task group of AXM assigned Task group of AXM assigned Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable BSF FIR AXM AXM AXM AXM BSY and occupancy TCs, mainly RES BLD AAC and SAF AAC pre First Draft planning meeting March 13, 2012 Page 9 BSY BSY BSY BSY BSF FIR AXM AXM AXM AXM Page 27 of 58

28 No. Subject Notes safety evaluation (LSE) operational requirements 25 Assembly crowd managers and their training 26 Evaluation of existing exemptions for places of religious worship 27 Introduction of riskbased provisions into health care chapters 28 Person-directed / person-centered health care Task group of AXM assigned Task group of AXM assigned Document or Committee Impacted NFPA 101 NFPA 5000 AXM AXM AXM AXM Task group of HEA assigned HEA HEA Task group of HEA assigned HEA HEA 29 Home health care Task group of HEA assigned HEA HEA 30 Increasing allowable risk to achieve better quality of life in health care occupancies Task group of HEA assigned HEA HEA 31 Ambulatory Health Care (AHC) Occupancies 32 Dormitory requirements 33 Fireplaces and CO detection 34 CO detection for board and care facilities 35 Occupant Load Factor for business uses 36 Correlation of HAZMAT requirements among NFPA 1/400/5000 Consider making AHC chapters self-standing (without need to consult Business Occupancy chapters) Evaluate whether dormitory requirements justify their own chapters, independent of those for hotels Clarification on need for CO detection with fireplaces (solid fuel, gas, electric?). FI did not pass ballot of RES. HEA HEA BLD AAC and SAF AAC pre First Draft planning meeting March 13, 2012 Page 10 RES RES BCF RES RES BCF Task group of BCF assigned BCF BCF Review project by Fire Protection Research Foundation. Consider call centers vs. less-populated business uses. Staff to draft committee-pis for review by TG-3. MER Not Applicable MER FIR Page 28 of 58

29 No. Subject Notes 37 Leakage at smoke barriers and fire barriers 38 Active fire protection systems and fire ratings 39 Terms/phrases: - Smoke barrier - Smoke partition - Partition that resists passage of smoke - Partition that limits passage of smoke 40 Accuracy of annex material Document or Committee Impacted NFPA 101 NFPA 5000 Quantification of leakage? FIR FIR Revisit issue of crediting active fire protection systems, like sprinklers, with providing fire resistance rating to an assembly so protected If FIR finds the time, work toward correlation throughout code by suggesting changes to other TCs. Other TCs to review their use of these terms. Review annex material for accuracy FIR FIR, and other TCs All TCs FIR FIR, and other TCs All TCs 12. Other Business. None. 13. Next Meeting. The correlating committees will meet in November 2012 in a face-to-face meeting to address the Public Input process conducted by the technical committees earlier in the year. The BLD-AAC and SAF-AAC committees will individually hold a one-day meeting. The two meetings will be on consecutive days and be held during the week of November 5-9. No meeting location had been determined. 14. Adjournment. The meeting was adjourned 2:00 p.m. Eastern. BLD AAC and SAF AAC pre First Draft planning meeting March 13, 2012 Page 11 Page 29 of 58

30 BLD/SAF-END: NFPA 5000/101 Correlation Changes NFPA through Application The requirements of this chapter shall apply to new buildings or portions thereof used as an educational occupancy Administration. The provisions of Chapter 1, Administration, shall apply General. The provisions of Chapter 4, General, shall apply Repairs, renovations, modifications, additions, and reconstruction of an educational occupancy, and changes of use, including change of occupancy classification to an educational occupancy, or correction of a damaged or unsafe portion of the building containing the educational occupancy, shall comply with one of the following: (1) Provisions of this chapter (2) Provisions of Chapter Educational facilities that do not meet the definition of an educational occupancy shall not be required to comply with this chapter but shall comply with the following requirements: (1) Instructional building business occupancy (see Chapter 28) (2) Classrooms under 50 persons business occupancy (see Chapter 28) (3) Classrooms 50 persons and over assembly occupancy (see Chapter 16) (4) Laboratories, instructional business occupancy (see Chapter 28) (5) Laboratories, noninstructional industrial (see Chapter 29) Classification of Occupancy. Classification of occupancy shall be in accordance with Educational occupancies shall include all buildings used for educational purposes through the twelfth grade by six or more persons for 4 or more hours per day or more than 12 hours per week Educational occupancies include part-day preschools, kindergartens, and other schools whose purpose is primarily educational, even though the children are of preschool age In cases where instruction is incidental to some other occupancy, the section of this Code governing such other occupancy shall apply. 1 Page 30 of 58

31 Other occupancies associated with educational institutions shall be in accordance with the appropriate parts of this Code Multiple Occupancies General. Multiple occupancies shall be in accordance with Section 6.2 and Where there are differences in the specific requirements in this chapter and provisions for mixed occupancies or separated occupancies, as specified in and 6.2.4, the requirements of this chapter shall apply. (See ) Assembly and Educational Spaces subject to assembly occupancy shall comply with Chapter 16, including , which provides that, where auditorium and gymnasium egress leads through corridors or stairways also serving as egress for other parts of the building, the egress capacity shall be sufficient to allow simultaneous egress from auditorium and classroom sections In the case of an assembly occupancy of a type suitable only for use by the school occupant load (and, therefore, not subject to simultaneous occupancy), the same egress capacity shall be permitted to serve both auditorium and classroom sections Dormitory and Classrooms. Any building used for both classroom and dormitory purposes shall comply with the applicable provisions of Chapter 24 in addition to complying with this chapter. Where classroom and dormitory sections are not subject to simultaneous occupancy, the same egress capacity shall be permitted to serve both sections Classification of Occupancy. Classification of occupancy shall be in accordance with Educational occupancies shall include all buildings used for educational purposes through the twelfth grade by six or more persons for 4 or more hours per day or more than 12 hours per week Educational occupancies include part-day preschools, kindergartens, and other schools whose purpose is primarily educational, even though the children are of preschool age In cases where instruction is incidental to some other occupancy, the section of this Code governing such other occupancy shall apply Other occupancies associated with educational institutions shall be in accordance with the appropriate parts of this Code Definitions General. For definitions, see Chapter 3, Definitions Special Definitions. A list of special terms used in this chapter follows: 2 Page 31 of 58

32 (1) Common Atmosphere. See (2) Flexible Plan and Open Plan Educational or Day-Care Building. See (3) Separate Atmosphere. See Classification of Hazard of Contents Hazard of contents shall be classified in accordance with Buildings or areas in which high hazard contents are stored, used, or handled shall comply with Chapter Minimum Construction Requirements Construction shall be in accordance with all of the following, except as modified by and and : (1) Chapter 7, Construction Types and Height and Area Requirements (2) Chapter 8, Fire-Resistive Materials and Construction (3) Chapter 13, Encroachments into the Public Right-of-Way (4) Chapter 14, Safeguards During Construction (5) Chapter 31, Occupancies in Special Structures (6) Chapter 35, Structural Design (7) Chapter 36, Soils, Foundations, and Retaining Walls (8) Chapter 37, Exterior Wall Construction (9) Chapter 38, Roof Assemblies and Roof Structures (10) Chapter 39, Flood-Resistant Design and Construction (11) Chapter 40, Quality Assurance During Construction * * Educational occupancies shall not be located more than one level below the level of exit discharge In buildings of Type V(000) construction, educational occupancies shall not be located below the level of exit discharge Occupant Load The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater. 3 Page 32 of 58

33 The occupant load of an educational occupancy, or a portion thereof, shall be permitted to be modified from that specified in if the necessary aisles and exits are provided. An approved aisle or seating diagram shall be required by the authority having jurisdiction to substantiate such a modification Accessibility. Accessibility shall be in accordance with Chapter 12. Substantiation: Correlation with the formatting and pointer references used in NFPA 101. Note that the text of , shown in underscore format, is not new but represents moved text. Similarly, the text of that is shown in strikethrough format, is not being deleted, just moved. The text of Definitions is new and was copied from NFPA 101 where it has served as helpful text to the document user. NFPA and Rooms normally occupied by preschool, kindergarten, or first-grade students shall be located on a level of exit discharge Rooms normally occupied by second-grade students shall not be located more than one story above a level of exit discharge Rooms or areas located on floor levels other than as specified in and shall be permitted to be used where provided with independent means of egress dedicated for use by the preschool, kindergarten, first-grade, or second-grade students. Substantiation: Correlation with the formatting used in NFPA 101. NFPA and Any exit door that is designed to normally be kept closed shall conform with Only one locking or latching device shall be permitted on a door or on one leaf of a pair of doors. 4 Page 33 of 58

34 Substantiation: Correlation with NFPA 101. The criteria specified are in Chapter 11 as egress provisions that need not be duplicated in the occupancy chapter. NFPA Drinking fountains or other equipment, fixed or movable, shall not be placed so as to obstruct the required minimum 6 ft (1830 mm) corridor width. Substantiation: Correlation with NFPA 101. The text shown as being deleted was dropped from NFPA 101 beginning in It is not needed. NFPA Protection of Vertical Openings Any vertical opening, other than unprotected vertical openings in accordance with , shall be enclosed or protected in accordance with Section Where the provisions of are used, the requirements of shall be met. Substantiation: Correlation with formatting used in NFPA 101. NFPA Occupant Notification * Occupant notification shall be accomplished automatically in accordance with Positive alarm sequence shall be permitted in accordance with Page 34 of 58

35 Where installed and operated in accordance with NFPA 72, the fire alarm system shall be permitted to be used for other emergency signaling or for class changes In order to prevent students from being returned to a building that is burning, the recall signal shall be separate and distinct from, and incapable of being mistaken for, any other signals. Such signal shall be permitted to be a distinctively colored flag or banner If the recall signal required by is electrical, the push buttons or other controls shall be kept under lock, the key for which shall be in the possession of the principal or some other designated person to prevent a recall at a time when there is an actual fire Regardless of the method of recall, the controls for the signal shall be kept under a lock. Substantiation: Correlation with formatting used in NFPA 101. NFPA Educational occupancy buildings exceeding 12,000 ft 2 (1120 m 2 ) 20,000 ft 2 (1860 m 2 ) shall be protected throughout by an approved, electrically supervised automatic sprinkler system in accordance with Section Substantiation: Correlation with threshold used in NFPA 101. For life safety protection, 20,000 ft 2 is too large an area to go unprotected. NFPA through Each room occupied by more than 300 persons shall have two or more means of egress entering into separate atmospheres Where three or more means of egress are required, not more than two such means of egress shall enter into the same common atmosphere. 6 Page 35 of 58

36 Flexible plan buildings shall be permitted to have walls and partitions rearranged periodically only if revised plans or diagrams have been approved by the authority having jurisdiction Flexible plan buildings shall be evaluated while all folding walls are extended and in use, as well as when they are in the retracted position. Substantiation: Correlation with formatting used in NFPA 101. NFPA 5000 A A A See for the requirement that portions of an educational occupancy building below the level of exit discharge are to be protected by automatic sprinklers. Substantiation: Editorial renumbering for correlation with change made in Chapter 17. NFPA through Application The requirements of this chapter shall apply to new buildings or portions thereof used as a day-care occupancy Administration. The provisions of Chapter 1, Administration, shall apply General. The provisions of Chapter 4, General, shall apply Repairs, renovations, modifications, additions, and reconstruction of a day-care occupancy, and changes of use, including change of occupancy classification to a day-care occupancy, or correction of a damaged or unsafe portion of the building containing the day-care occupancy, shall comply with one of the following: (1) Provisions of this chapter (2) Provisions of Chapter Sections 18.1 through 18.5 shall apply to life safety requirements for day-care occupancies in which more than 12 clients receive care, maintenance, and 7 Page 36 of 58

37 supervision by other than their relative(s) or legal guardian(s) for less than 24 hours per day Section 18.1, other than , and Section 18.6 shall apply to life safety requirements for day-care homes Where a facility houses more than one age group of selfpreservation capability, the strictest requirements applicable to any group present shall apply throughout the day-care occupancy or building, as applicable, unless the area housing that group is maintained as a separate fire area Places of religious worship shall not be required to meet the provisions of this chapter when providing day care while services are being held in the building Classification of Occupancy. Classification of occupancy shall be in accordance with Occupancies that include part-day preschools, kindergartens, and other schools whose purpose is primarily educational, even though the children are of preschool age, shall comply with the provisions of Chapter Adult day care shall include any building, or portion thereof, used for less than 24 hours per day to house more than three adults requiring care, maintenance, and supervision by other than their relative(s). Clients shall be ambulatory or semiambulatory and shall not be bedridden. They shall not exhibit behavior that is harmful to themselves or others Multiple Occupancies General. Multiple occupancies shall be in accordance with Section 6.2 and Where there are differences in the specific requirements in this chapter and provisions for mixed occupancies or separated occupancies, as specified in and 6.2.4, the requirements of this chapter shall apply. (See ) Day-Care Occupancies in Apartment Buildings. If the two required exit accesses from a day-care occupancy enter the same corridor as an apartment occupancy, the exit accesses shall be separated in the corridor by a smoke barrier having not less than a 1-hour fire resistance rating and constructed in accordance with Section The smoke barrier shall be located so that it has an exit on each side Classification of Occupancy. Classification of occupancy shall be in accordance with Occupancies that include part-day preschools, kindergartens, and other schools whose purpose is primarily educational, even though the children are of preschool age, shall comply with the provisions of Chapter Adult day care shall include any building, or portion thereof, used for less than 24 hours per day to house more than three adults requiring care, maintenance, 8 Page 37 of 58

MEETING MINUTES NFPA Technical Correlating Committee on Safety to Life January 6, 2011 ROC Meeting The Wyndham Phoenix, Phoenix, AZ

MEETING MINUTES NFPA Technical Correlating Committee on Safety to Life January 6, 2011 ROC Meeting The Wyndham Phoenix, Phoenix, AZ MEETING MINUTES NFPA Technical Correlating Committee on Safety to Life January 6, 2011 ROC Meeting The Wyndham Phoenix, Phoenix, AZ 1. Call to Order. The meeting was called to order by Chair William Koffel

More information

TECHNICAL COMMITTEE MEMBERS WHO PARTICIPATED

TECHNICAL COMMITTEE MEMBERS WHO PARTICIPATED MEETING MINUTES NFPA Correlating Committee on Safety to Life (SAF-AAC) November 7, 2013 Second Draft Meeting Embassy Suites Atlanta Hartsfield Airport Hotel Atlanta, GA 1. Call to Order. The meeting was

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 43 10/20/2015 4:02 PM First Revision No. 2035-NFPA 101-2015 [ Global Input ] To 14.3.4.4.1, add an item (4) to read: (4) Carbon monoxide detectors shall be installed centrally located within occupiable

More information

NFPA s Standards Development Process

NFPA s Standards Development Process NFPA s Standards Development Process Revision Cycle 104 weeks or 141 weeks Guiding Principles Due process Openness Lack of dominance Seek society s balance between: Acceptable risk Commitment of resources

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

2. Introduction of committee members and guests. For a current committee roster, see page 2.

2. Introduction of committee members and guests. For a current committee roster, see page 2. AGENDA NFPA Technical Committee on Educational and Day-Care Occupancies NFPA 101 and NFPA 5000 Second Draft Meeting Tuesday, July 19, 2016 Hilton Fort Lauderdale Marina Fort Lauderdale, FL 1. Call to order.

More information

TECHNICAL COMMITTEE ON FIRE CODE

TECHNICAL COMMITTEE ON FIRE CODE TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

1. The meeting was called to order by Chair James Lathrop at 8:00 AM (CDT) on Wednesday, August 26, 2015.

1. The meeting was called to order by Chair James Lathrop at 8:00 AM (CDT) on Wednesday, August 26, 2015. MINUTES NFPA Technical Committee on Residential Occupancies NFPA 101 and NFPA 5000 First Draft Meeting Wednesday, August 26, 2015 InterContinental Milwaukee Milwaukee, WI 1. The meeting was called to order

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

Iowa (2) Delete section and insert in lieu thereof the following new section:

Iowa (2) Delete section and insert in lieu thereof the following new section: Iowa Iowa Admin. Code 661-301.3(103A) Iowa Administrative Code Agency 661 Public Safety Department Chapter 301 State Building Code-General Provisions 661-301.3(103A) General provisions. The provisions

More information

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fire Code (FCC-AAA) Gregory

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Residential Occupancies Kelly

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

home smoke candles alarms electrical burns smoking medical oxygen cooking FIREFIGHTING MATCHES & LIGHTERS SPRINKLERS

home smoke candles alarms electrical burns smoking medical oxygen cooking FIREFIGHTING MATCHES & LIGHTERS SPRINKLERS FIREFIGHTING home smoke alarms REGULATIONS GOVERNING THE NFPA EDUCATIONAL MESSAGES DESK REFERENCE FOR THE FIRE SERVICE AND FIRE AND LIFE SAFETY EDUCATORS MATCHES & LIGHTERS medical oxygen cooking FIRE

More information

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts Guy R. Colonna, PE Division Manager, NFPA Combustible Dust Symposium Detroit, MI September 20, 2011 1 Objectives

More information

SC # /16/17/18/19/23/24 D#03-24

SC # /16/17/18/19/23/24 D#03-24 SC #03-7-15/16/17/18/19/23/24 D#03-24 Casey C. Grant, P.E. Secretary, Standards Council 26 July 2003 To: Interested Parties Subject: Standards Council Decision (Final): D#03-24 Standards Council Agenda

More information

At its meeting of August 7-9, 2012, the Standards Council considered the above referenced matter.

At its meeting of August 7-9, 2012, the Standards Council considered the above referenced matter. SC #12-8-56 D#12-15 Amy Beasley Cronin Secretary, Standards Council 30 August 2012 To: Interested Parties Subject: Standards Council Decision (Final): D#12-15 Standards Council Agenda Item: SC#12-8-56

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical on Fluidized Bed Boilers AGENDA Web/Teleconference 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of Members and Guests 3. Approval of Minutes from

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Building Service and

More information

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time, changes

More information

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels

More information

MEMORANDUM. NFPA Technical Correlating Committee on Building Code. NFPA 5000 TCC Report on Proposals Letter Ballot (A2011)

MEMORANDUM. NFPA Technical Correlating Committee on Building Code. NFPA 5000 TCC Report on Proposals Letter Ballot (A2011) MEMORANDUM TO: FROM: NFPA Technical Correlating Committee on Building Code Robert Solomon DATE: April 1, 2010 SUBJ: NFPA 5000 TCC Report on Proposals Letter Ballot (A2011) In accordance with the NFPA Regulations

More information

MEETING AGENDA High Rise Building Safety Advisory Committee

MEETING AGENDA High Rise Building Safety Advisory Committee MEETING AGENDA High Rise Building Safety Advisory Committee Renaissance Blackstone Chicago 636 South Michigan Avenue, Chicago, IL 60605 May 13-14, 2014 Chicago, IL 1. Call to Order. Call the meeting to

More information

January 1, 2014 Mandatory Effective Date

January 1, 2014 Mandatory Effective Date 2013 Kentucky Building Code Highlights Winnie Blythe, Technical Advisor Dept. of Housing, Buildings, and Construction winnie.blythe@ky.gov www.dhbc.ky.gov 502-573-0373 January 1, 2014 Mandatory Effective

More information

ROP MEETING MINUTES. 2. Introduction of Attendees. The following committee members and guests were in attendance. TECHNICAL COMMITTEE MEMBERS PRESENT

ROP MEETING MINUTES. 2. Introduction of Attendees. The following committee members and guests were in attendance. TECHNICAL COMMITTEE MEMBERS PRESENT BLD/SAF-FIR 24-25 September 2009 ROP Meeting Minutes ROP MEETING MINUTES Building Code Life Safety Technical Committee on Fire Protection Features Thursday-Friday, September 24-25, 2009 Meeting Embassy

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical self-closing device

More information

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, 2014 9:00 AM - 5:00 PM EST Web/Teleconference Meeting 1. Welcome. George Seuss, Chair 2. Introductions and Update

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

2014 NFPA Conference & Expo

2014 NFPA Conference & Expo 2014 NFPA Conference & Expo NFPA Wildland Standards Development: Where We ve Been and Where We re Going Presented by: Ryan Depew NFPA Emergency Services Spc. OVERVIEW NFPA Technical Committees NFPA Wildland

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

First Revision No NFPA [ Section No ]

First Revision No NFPA [ Section No ] of 45 10/21/2015 8:54 AM First Revision No. 3501-NFPA 101-2015 [ Section No. 3.3.190.1 ] 3.3.196.1* Ambulatory Health Care Occupancy. An occupancy used to provide services or treatment simultaneously to

More information

Standards and Safety Update

Standards and Safety Update Standards and Safety Update Presented By: Michael J. Johnston Executive Director Standards and Safety, NECA Update Objectives Update on NFPA 70E and NECA Safety products Update on NECA S National Electrical

More information

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H

More information

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010) CHAPTER 1 SCOPE AND ADMINISTRATION 102.7 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 45 47 and such codes and standards shall

More information

Narrative Reports As Regulated by 780 CMR, Section 903.0

Narrative Reports As Regulated by 780 CMR, Section 903.0 EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for

More information

ICC CODE CORNER 2015 International Fire Code

ICC CODE CORNER 2015 International Fire Code PART II GENERAL SAFETY PROVISIONS CHAPTER 4 EMERGENCY PLANNING AND PREPAREDNESS SECTION 401 GENERAL 401.1 Scope. Reporting of emergencies, coordination with emergency response forces, emergency plans and

More information

International Code Council

International Code Council Page 1 of 7 International Code Council ICC 300-2012 edition Committee Actions Report for Committee Actions taken at the March 9th, 2011 meeting The ICC Standard Development Committee for Bleacher Safety

More information

NFPA Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems

NFPA Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems San Antonio, TX October 12-14, 2016 The following are the meeting minutes from the third meeting of the Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems held in San Antonio,

More information

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5 AGENDA: Ambulatory Health Care & Business Occupancies Definitions / Examples Mixed & Contiguous Occupancies Ambulatory Health Care &

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES

FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES West Metro Fire Rescue Life Safety Division 433 South Allison Parkway Lakewood, Colorado 80226 (303) 989-4307 Fax (303)

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

CHANGES TO THE TEXT OF THE 2010 CODE BOOKS

CHANGES TO THE TEXT OF THE 2010 CODE BOOKS The State Uniform Fire Prevention and Building Code (the Uniform Code) includes the publications that are incorporated by reference in Parts 1220 to 1227 of Title 19 of the New York Codes, Rules and Regulations

More information

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS I. Introduction. This is the Motions Committee Report on Standards in the Fall 2013 Revision Cycle. The report identifies Certified

More information

Amend Base Code. Amend Base Code. Amend Base Code. Disposition. (Statute, Rule, FBC, Industry) Y/N

Amend Base Code. Amend Base Code. Amend Base Code. Disposition. (Statute, Rule, FBC, Industry) Y/N Code Reference NFPA 101 1.1.1.2 (2009 1.1.1.1 (2012 1.1.7 (New) 1.3.1.1 Florida Specific Amendment Anytime a reference is made to NFPA 1 or NFPA 101 within this Code, it shall be the Florida specific version

More information

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016 TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES NFPA 610 First Draft Meeting October 17-18, 2016 Westin Kansas City at Crown Center 1 East Pershing Road Kansas City, MO, 64108 Conference Call Access:

More information

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY. STATE OF LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BOULEVARD, BATON ROUGE, LA 70806 800-256-5452 225-925-4920

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Furnishings

More information

The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101):

The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101): The following are the Proposed Amendments to 2015 edition of the Life Safety Code (NFPA 101): 1.1.1 Title. NFPA 101, Life Safety Code, shall be known as the Life Safety Code, is cited as such, and shall

More information

NFPA 101 Life Safety Code Culture change 2012

NFPA 101 Life Safety Code Culture change 2012 NFPA 101 Life Safety Code Culture change 2012 Produced by Kansas Fire Marshal April, 2012 On March 9, 2012 Centers for Medicare & Medicaid Services implements a policy where they have formally adopted

More information

Retain. Retain. Retain. Board Advisory. Board Advisory. Retain. Disposition. (Statute, Rule, FBC, Industry)

Retain. Retain. Retain. Board Advisory. Board Advisory. Retain. Disposition. (Statute, Rule, FBC, Industry) Florida Specific Amendment Code Reference NFPA 101 Anytime a reference is made to NFPA 1 or NFPA 101 within this Code, it shall be 1.1.1.1 the Florida specific version of NFPA 1 and NFPA 101. The Florida

More information

FHCA 2014 Annual Conference & Trade Show

FHCA 2014 Annual Conference & Trade Show FHCA 2014 Annual Conference & Trade Show CE Session #5 Preparing for the Upcoming Code Changes Don t Look Back Tuesday, July 8 8:15 to 9:15 a.m. Canary 3 Operations/Quality Improvement Upon completion

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

Technical Committee on Liquefied Natural Gas

Technical Committee on Liquefied Natural Gas Technical Committee on Liquefied Natural Gas MEMORANDUM TO: FROM: Technical Committee on Liquefied Natural Gas Denise Beach, Senior Engineer/Staff Liaison DATE: March 16, 2011 RE: NFPA 59A LNG-AAA ROP

More information

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 34 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Statute or Rule Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0001 - OTHER

More information

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.14 Control Number: A.0 Effective Date: 9/14/11 TITLE:

More information

NFPA 550 ROP Meeting Minutes

NFPA 550 ROP Meeting Minutes NFPA 550 ROP Meeting Minutes NFPA Technical Committee on Fire Risk Assessment Methods (FIR-AAA) June 24, 2010 Microsoft Live Meeting 1. Call to order. The meeting was called to order at 1:00 PM on Monday,

More information

M E M O R A N D U M. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action.

M E M O R A N D U M. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action. M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Marshal Professional Qualifications Stacey Van Zandt DATE: July 13, 2010 SUBJECT: NFPA 1037 ROP TC Letter Ballot (F2011) The ROP letter ballot

More information

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN Mr. Merton Bunker, Committee Chair, called the meeting to order at 8:05 on Wednesday September

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical Committee on Fluidized Bed Boilers AGENDA NFPA Headquarters 1 Batterymarch Park Quincy, MA 02169 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

E25 (D) Automatic controls for general means of egress lighting

E25 (D) Automatic controls for general means of egress lighting Adhoc Health Care MOE Study Group Study Group Report of Adhoc Meeting July 12&13, 2012 Possible Public Comments E25, E69, E74, G71, G77/G80 Study Group E25 (D) Automatic controls for general means of egress

More information

GIS Data Exchange Committee. and the NFPA Standards Making System

GIS Data Exchange Committee. and the NFPA Standards Making System GIS Data Exchange Committee and the NFPA Standards Making System This briefing... NFPA Technical Committees New GIS Data Exchange Committee Background of the NFPA Standards Making Process Status of the

More information

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Guideline Title: Residentially Based Care Facilities Group

More information

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES 1.

More information

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter

More information

NFPA Fire Inspector I Study Guide

NFPA Fire Inspector I Study Guide NFPA 1031-2003 Fire Inspector I Study Guide National Certification Program October 2004 This document is provided This document at no cost is provided to the user at no by cost Kansas to the user Fire

More information

BUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007

BUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007 BUILDING CODE OF THE CITY OF NEW YORK New York City Department of Buildings 4 June 2007 Fatma Amer, PE, Deputy Commissioner, Technical Affairs James Colgate, RA, Executive Architect John Lee, RA Keith

More information

Residential Based Care Facility Guidelines

Residential Based Care Facility Guidelines Moreno Valley Fire Department Fire Prevention Bureau Residential Based Care Facility Guidelines Approved and Authorized By: Randall Metz, Fire Marshal Issued: January 1, 2011 Residential Based Care Facilities

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Correlating Committee on

More information

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Item No. Subject 13-6-1 Call to Order (8:00 A.M) 13-6-2 Roll Call 13-6-3 Approval

More information

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 HCFMO Harris County Fire Marshal M.S. Montgomery Fire Marshal FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011 EFFECTIVE JANUARY 1, 2007 These guidelines

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

NFPA Technical Committee on Fire Tests

NFPA Technical Committee on Fire Tests National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Tracy

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Means of Egress

More information

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 Kenneth Kretchman, CIH, CSP Mgr, Industrial Hygiene NC State University Ken_Kretchman@ncsu.edu International Building

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007

More information

Fire Test Requirements for Upholstered Furniture Used in Public Buildings

Fire Test Requirements for Upholstered Furniture Used in Public Buildings INTRODUCTION In the U.S., there are two major fire safety codes: NFPA 101 Life Safety Code and the International Building/Fire Code. Both sets of codes specify fire tests for upholstered furniture. The

More information

Residential-based Care Facility R-4 Guideline

Residential-based Care Facility R-4 Guideline Moreno Valley Fire Department Fire Prevention Bureau Residential-based Care Facility R-4 Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 7, 2017 Residential-based Care

More information

AGENDA. NFPA Correlating Committee on Safety to Life (SAF-AAC) NFPA 101 Second Draft Meeting. November 17, NFPA Headquarters, Quincy, MA

AGENDA. NFPA Correlating Committee on Safety to Life (SAF-AAC) NFPA 101 Second Draft Meeting. November 17, NFPA Headquarters, Quincy, MA AGENDA NFPA Correlating Committee on Safety to Life (SAF-AAC) NFPA 101 Second Draft Meeting November 17, 2016 NFPA Headquarters, Quincy, MA 1. Call to order. Call meeting to order by Chair Bill Koffel

More information

NFPA 45 NFPA 211 NFPA 1600

NFPA 45 NFPA 211 NFPA 1600 NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA

More information

1. Welcome. Robert Smith, Chair. 2. Introductions and Update of Committee Roster. (attached)

1. Welcome. Robert Smith, Chair. 2. Introductions and Update of Committee Roster. (attached) TECHNICAL COMMITTEE ON WATER-COOLING TOWERS NFPA 214 (F2015) Second Draft Meeting Agenda February 17, 2014 10:00 AM - 1:00 PM EST Web/Teleconference Meeting 1. Welcome. Robert Smith, Chair 2. Introductions

More information