Daikin Loop Water Manager Protocol Information

Size: px
Start display at page:

Download "Daikin Loop Water Manager Protocol Information"

Transcription

1 Engineering Data ED Group: Controls Part Number: ED Date: August 2012 Supersedes: New Daikin Loop Water Manager Protocol Information BACnet Networks 2012 Daikin

2 Table of Contents Table of Contents... 2 Revision History... 3 Software Revision... 3 Reference Documents... 3 Notice... 3 Limited Warranty... 3 Introduction... 4 Unit Controller Data Points... 4 Protocol Definitions... 4 Basic Protocol Information... 5 Setting Unit Controller Communications Parameters... 5 BACnet Networks... 5 MicroTech III Unit Controller Device Object... 6 Network Considerations... 8 Typical Application: Minimum Integration... 9 Alarms... 9 Unit Controller Sequence of Operation... 9 Comprehensive Data Point Tables BACnet Standard Objects Detailed Data Point Information Active Heat Addition Stages Active Heat Rejection Stages Application Mode Application Version Boiler Deadband Boiler Range Boiler Return Temperature Boiler Setpoint Boiler Supply Temperature Boiler Valve Position Clear Alarms Control Mode Control Temperature Current State Damper Interlock Geothermal Temperature Head Pressure Heat Addition Stage Differentials Heat Addition Stage Setpoints Heat Addition Status Heat Exchanger Return Temperature Heat Exchanger Supply Temperature Heat Rejection Stage Differentials Heat Rejection Stage Setpoints Heat Rejection Status Lead Pump Select Lead Secondary Pump Select Local Outdoor Air Temperature Loop Return Temperature Loop Return Temperature (Problem) Loop Supply Temperature Main Loop Capacity - Network Main Loop Control Select Max OA 30 Maximum Control Temp Range Minimum Control Temp Range Network Outdoor Air Temperature Outdoor Air Humidity Outdoor Air Reset Max Reset Amount Outdoor Air Reset Max Setpoint Outdoor Air Reset Max 32 Outdoor Air Reset Min Setpoint Outdoor Air Reset Min 32 Outdoor Air Temperature PreCool Differential PreCool Enable PreCool Outdoor Air Setpoint PreCool Setpoint PreCool Stages PreHeat Differential PreHeat Enable PreHeat Outdoor Air Setpoint PreHeat Setpoint PreHeat Stages Pump 1 Flow Pump 1 Hours Pump 2 Flow Pump 2 Hours Pump Fail Delay Recirc Timer Secondary Pump 1 Flow Secondary Pump 1 Hours Secondary Pump 2 Flow Secondary Pump 2 Hours Stage Time Storage Tank Temperature Sump Dump Day Sump Dump Month Sump Dump Deadband Sump Dump Select Sump Dump Setpoint Sump Fill Day Sump Fill Month Tower Deadband Tower Range Tower Fan Enable Tower Fan Speed Tower Return Temperature Tower Setpoint Tower Supply Temperature Unit State Unit Support Zero OA 43 Alarms Alarm LED Fault Alarms (Highest Priority) Problem Alarms (Medium Priority) Warning Alarms (Lowest Priority) Alarm Monitoring Alarm Notification Notification Class - Faults Notification Class - Problems Notification Class - Warnings Alarm Value Warning Alarm Problem Alarm Fault Alarm Boiler Pumps Fail Problem Emergency Stop Fault Main Loop Pump 1 Fail Main Loop Pump 2 Fail Main Loop Pump Shut Down Fault Main Loop Switch 1 Stuck Fail Main Loop Switch 2 Stuck Fail Pump 1 Manual Fail Pump 2 Manual Fail Secondary Loop Pump 1 Fail Secondary Loop Pump 2 Fail Secondary Loop Switch 1 Stick Fail Secondary Loop Switch 2 Stick Fail Secondary Pump 1 Manual Fail Secondary Pump 2 Manual Fail Tower Pumps Fail Problem UnoccLimProtect BACnet Device Management DeviceCommunicationControl - Disable DeviceCommunicationControl - Enable ReinitializeDevice (Reset) BACnet File Objects BACnet Client Config File ED 19015

3 BACnet COV Config File Error Log File History Log File BACnet Event Enrollment Config File EDE File EDE File State Text Appendix A: Protocol Implementation Conformance Statement (PICS) BACnet Protocol Implementation Conformance Statement Product Description BACnet Standardized Device Profile Standard Object Types Supported Data Link Layer Options Segmentation Capability Device Address Binding Networking Options Character Sets Supported Index Revision History ED March 2012 Preliminary release. Software Revision Keypad Menu Path Daikin LWM\Version Information\App Version= The software part number is encoded in the controller s memory and is available for display on the keypad/display. The part number is available via BACnet system integration tools. The software part number codification is as follows: Implied digits on all Daikin Loop Water Manager software Base part number (8090 indicates standard software) Version Revision This edition documents Network Protocols for version of the standard Loop Water Manager application and all subsequent versions until otherwise indicated. However, if your software is of a later version, some of the information in this document may not completely describe your application. You can determine the revision of the application software from the keypad/display. The path for this information from the main menu is Daikin LWM\Version Information\App Version=. Reference Documents Company Number Title Source Daikin IOM 1150 Daikin Loop Water Manager Installation & Operation Manual American Society of Heating, ANSI/ BACnet - A Data Communication Protocol for Building Refrigerating and Air- ASHRAE 135- Automation and Control Networks Conditioning Engineers 2008 Notice 2012 Daikin, Minneapolis MN. All rights reserved throughout the world DaikinApplied.com Daikin reserves the right to change any information contained herein without prior notice. The user is responsible for determining whether this product is appropriate for his or her application. The following are trademarks or registered trademarks of their respective companies: BACnet from American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.; Echelon, LONWORKS, LONMARK, and LonTalk from Echelon Corporation; Windows from Microsoft Corporation; and Daikin, Maverick II and MicroTech from Daikin. Limited Warranty Consult your local Daikin Representative for warranty details. Refer to Form Y. To find your local Daikin Representative, visit ED

4 Introduction This document contains the necessary information you need to incorporate a Loop Water Manager Unit from Daikin into a building automation system (BAS). It lists all BACnet properties, and corresponding Loop Water Manager data points. It also contains the BACnet Protocol Implementation Conformance Statement (PICS). BACnet terms are not defined. Refer to the respective specifications for definitions and details. Loop Water Manager Data Points The Loop Water Manager contains data points or unit variables that are accessible from three user interfaces: the unit keypad, a BACnet network (BACnet/IP or MS/TP). Not all points are accessible from each interface. This manual lists all important data points and the corresponding path for each applicable interface. Refer to IOM 1150 (available on for keypad details. This document contains the network details necessary to incorporate the MicroTech III Unit Controller into the network. Protocol Definitions The Loop Water Manager can be configured in an interoperable BACnet network. The controller must have a BACnet MS/TP communication module installed for network integration. BACnet Protocol BACnet is a standard communication protocol for Building Automation and Control Networks developed by the American National Standards Institute (ANSI) and American Society of Heating, Refrigeration and Air-conditioning Engineers (ASHRAE) specified in ANSI/ASHRAE standard It addresses all aspects of the various systems that are applied to building control systems. BACnet provides the communication infrastructure needed to integrate products manufactured by different vendors and to integrate building services that are now independent. 4 ED 19015

5 Basic Protocol Information Setting Loop Water Manager Communications Parameters There are seven communication parameters involved in setting up the unit controller for proper communication BACnet MS/TP. The table below lists possible sets of default parameter settings. The bold parameters can be changed using the keypad display located on the unit controller. Communication Setup Parameter Settings Parameter Name BACnet MS/TP MSTP MAC Address 1 18 MSTP Baud Rate Device Instance Number Max APDU Length Device Object Name Max Master Max Info Frames variable 480 POL904_AD45EC Notes: 1. The MSTP MAC Address is set via the keypad/display. You must cycle power after changing it for the changes to take effect. 2. The last 8 digits are computed from the production number and date code. BACnet Networks Compatibility The Loop Water Manager is tested according to the BACnet Testing Laboratory (BTL) Test Plan. It is designed to meet the requirements of the BACnet Standard (ANSI/ASHRAE ) as stated in the Protocol Implementation and Conformance Statement (PICS). However, it is not BTL listed. The PICS is located at the end of this manual. BACnet Objects Daikin Loop Water Managers incorporate standard BACnet object types (i.e., object types defined in the BACnet Standard) that conform to the BACnet Standard. Each object has properties that control unit variables or data points. Some object types occur more than once in the Loop Water Manager; each occurrence or instance has different properties and controls different unit variables or data points. Each instance is designated with a unique instance index. Some properties can be adjusted (read/write properties, e.g., setpoints) from the network and others can only be interrogated (read-only properties, e.g., status information). Each data point accessible from a BACnet network is described with a table that gives the, Identifier, Full BACnet Reference or path, and the Name enumeration of the property. Example of BACnet Data Point Keypad Menu Path MainOverivew\Unit Status\Blr Return Temp= Temperature F / C Real F C N/A BACnet Analog Input 0 4 Present_Value 85 <Device Name>.BoilerReturnTemp.Present_Value s are each designated with an Object type as defined in the BACnet specification. The first column of the data point definition gives the object type. This object happens to be Boiler Return Temperature (See page 16.) ED

6 The object identifier is a property of the object that you can read from the object. The name of the property is Object_Identifier and the property identifier is 75. Each object in the Loop Water Manager has a unique identifier. BACnet object identifiers are two-part numbers of BACnet data type. The first part identifies the object type (the first 10 bits of the 32-bit BACnet [See ANSI/ASHRAE BACnet A Data Communication Protocol for Building Automation and Control Networks]). The first column of the data point definition gives the object type. The second part identifies the instances of that particular object type (the last 22 bits of the 32-bit BACnet ). The object identifier is shown in the data points listing as two numbers. The first number is shown in the Type ID column and designates the Object type enumeration. The second number is shown in the Instance column and designates the instance of that particular object type. The object identifier is a property of the object that you can read from the object code. The name of the property is Object_Identifier and the property identifier is 75. The ASHRAE BACnet specification reserves the first 128 numbers for ASHRAE defined objects. Manufacturers may define additional object types and assign a number above 127 as long as they conform to the requirements of the ASHRAE BACnet specification. Each object also has a name. Object names are character strings. The object name is a property of the object that you can read from the object. The name of the property is Object_Name and the property identifier is 77. Objects are sometimes referred to as an object type and instance number as they are in the BACnet specification. The example object above would be: Analog Input, Instance 4. Identifier Each object has a number of properties or attributes. Each property has a unique identifier of BACnet Identifier data type. identifiers are an enumerated set; a number identifies each member. The Identifier enumeration number is shown in the ID column. In the example above the property identifier is 85. Name Each property also has a unique name. names are character strings and shown in the Name column. In the example above the property name is Present Value. The full reference is the path of the property within the network where the Loop Water Manager resides. It is a character string equivalent to the object identifier and the property identifier. In the example above the full reference is <Device Name>.BoilerReturnTemp.Present_Value. Enumerated Values Some properties are standard data types and some are enumerated sets. If the property value is an enumerated set, all enumerated values and corresponding meaning are given in the column of the data point listing. Loop Water Manager Device Object Each BACnet compatible device must have one and only one BACnet Device Object. Device The Loop Water Manager Device uniquely specifies the unit within the network. The device object type for all devices is fixed by ASHRAE at eight (8). Therefore the device object instance number must be unique. The initial Device Object identifier is set at manufacturing. The device object identifier can be read from the Loop Water Manager. The name of the property is Object_Identifier and the property identifier is 75. The initial device object instance number is 0. This number must be unique on the entire BACnet network. The object instance number can be changed via the keypad display. You must cycle power for the change to take effect.! CAUTION If another device in the network already has this object identifier (instance number), you must change the instance number of one device object, so that all devices in the network have a unique device identifier. 6 ED 19015

7 Device Object Name The Device Object Name uniquely specifies a device in the network. It must be unique in the network. The device name for the Loop Water Manager device is to be determined. The device name is the prefix of all object names in the Loop Water Manager. All objects include the device name and a period. preceding the object name. The Device Object name is also available to the network in the device. The property name is Object_Name and property identifier is 77. The default Object Name is POL904_######## where ######## is computed from the production number and date code. Device Object Properties The device object contains many other informative properties as shown in Table 1. Table 1. Daikin Loop Water Manager Device Object Properties Identifier Default Value Data Type 75 Device, variable BACnetObjectIdentifier Object Name 77 POL908_FF2BEE 1 Character String Object Type 79 8 BACnetObjectType System Status 112 BACnetDeviceStatus Vendor Name 121 Daikin Character String Vendor Identifier Unsigned 16 Model Name 70 MTIII_LWM Character String Firmware Version 44 variable Character String Application Software Revision 12 variable Character String Location 58 Character String Description 28 MTIII_LWM Character String Protocol Version 98 1 Unsigned Protocol Revision Unsigned Protocol Services Supported 97 BACnetServicesSupported Protocol Object Types Supported 2 96 AI, AO, AV, BI, BO, BV, Cal, BACnetObjectTypesSupported Device, MSI, MSO, NC, Sch, MSV Object List 76 Sequence of BACnetObjectIdentifer Max APDU Length Accepted Unsigned 16 Segmentation Supported 107 Segmentation-both (0) BACnetSegmentation Max Segments Accepted Unsigned Local Time 3 57 variable Time Local Date 3 56 variable Date UTC Offset (Range: ) Integer Daylight Savings Status 24 variable Boolean APDU Segment Timeout Unsigned APDU Timeout Unsigned Number of APDU Retries 73 3 Unsigned Device Address Binding 30 Sequence of BACnetAddressBinding Database Revision Unsigned Active COV Subscriptions 152 List of BACnetCOVSubsriptions 1. The last 8 digit are computed from the production number printed on the bar code label affixed to the side of the module. 2. While the Loop Water Manager supports the entire set of object types, not all object types are used. See the Object List for details. ED

8 3. The BACnet communication module and the Loop Water Manager both have their own time clocks. The date and time read via BACnet could differ from the date and time in the Loop Water Manager the date or time is changed via the keypad display. The two time clocks resynchronize approximately every minutes and after every power cycle of the Loop Water manager or BACnet communication module. Network Considerations Access to Properties Object properties are accessible from the network by specifying the device object identifier, object identifier, and the property identifier. To access a property, you must specify the object identifier including the device object identifier or the object name including the device object name and the property identifier. Configuring the Loop Water Manager The Loop Water Manager with attached BACnet communication module is ready to operate with the default values of the various parameters. Default values may be changed with the unit s keypad or via the network. See the Daikin Loop Water Manager Installation & Operation Manual (IOM 1150) available on BACnet MS/TP Network Addressing The BACnet MS/TP device address (Media Access Control [MAC] address) of the Daikin Loop Water Manager in a BACnet Master Slave/Token Passing (MS/TP) Local Area Network (LAN) is set using the keypad/display. Navigate to the Advanced Menus\MSTP Setup menu to change this value. You must cycle power (turn the Loop Water Manager off and then on again) in order for the new address to take effect. 8 ED 19015

9 Typical Application: Minimum Integration This section gives you the basic information and outlines a procedure to set up the unit for network control. Alarms Alarms in a Loop Water Manager are divided into three classes: Faults, Problems, and Warnings. Fault Alarms have the highest priority. Problem Alarms have medium priority. Warning Alarms have the lowest priority. Notification Daikin Loop Water Managers may have their alarms monitored by one of three methods: 1) Alarm value using one BACnet Analog Value, 2) Alarm class, or 3) Notification Classes. 1. To monitor alarms by alarm value, read the Present_Value property of the Alarm Value Analog Value object. The Present_Value displays a value that corresponds to the highest priority alarm that is active. It is possible to have multiple active alarms, but only the highest priority is displayed. For example, if there is a simultaneous Main Pump 1 Switch Stuck Warning (value of 56) and a Emergency Stop Fault (value of 250), then the Emergency Stop Fault value of 250 will display in the Present_Value because it is the higher priority alarm of the two. Once the Emergency Stop Fault condition is corrected and the fault is cleared, the next priority active alarm value (in this example, value of 56 for Main Pump 1 Switch Stuck Warning alarm) is displayed. The values for all alarms are described in the Alarms section tables. If the Present_Value displays a zero, there are no active alarms. 2. To monitor alarms by alarm class, read the Present_Value of the appropriate Analog Value object (Warnings, Problems and Faults). The Present_Value displays a value that corresponds to the highest priority alarm that is active for that particular alarm class. It is possible to have multiple active alarms, but only the highest priority is displayed. 3. To monitor alarms using the Notification Class objects, see the Alarm Notification section. Clearing Loop Water Managers have one Multi-State Value objects that can be used to clear alarms; ClearAlarms (See page 17). All alarms of a particular class may be cleared by writing the appropriate value to the Present Value property of ClearAlarms (2=ClearAllFaults, 3=ClearAllProblems, 4=ClearAllWarnings). All alarms of all three classes can be cleared by writing a 5 (ClearAllAlarms) to Present_Value. Once the alarms are cleared, the Present_Value of this object goes back to None (1). Loop Water Manager Sequence of Operation Refer to the Loop Water Manager Installation & Operation Manual (IOM 1150) for sequence of operation details, including keypad operation. ED

10 Comprehensive Data Point Tables These comprehensive data point tables contain the significant parameters of specific data points. BACnet Standard Objects Network Control Page Read(R), Write(W), Commandable(C) Object Type Instance Description Device Object Application Version 16 R Device * Read the Application_Software_Version property. This is the version of the software loaded in the Loop Water Manager. Analog Inputs Loop Supply Temperature 29 R AI 1 Current reading of sensor Loop Return Temperature 28 R AI 2 Current reading of sensor Boiler Supply Temperature 17 R AI 3 Current reading of sensor Boiler Return Temperature 16 R AI 4 Current reading of sensor Local Outdoor Air Temperature 28 R AI 5 Current reading of sensor Tower Supply Temperature 42 R AI 6 Current reading of sensor Tower Return Temperature 42 R AI 7 Current reading of sensor Storage Tank Temperature 38 R AI 8 Current reading of sensor Head Pressure 19 R AI 9 psi Outdoor Air Humidity 31 R AI 10 % Loop Return Temperature (Problem) 29 R AI 11 Current reading of sensor. The Present Value of this object is the same as AI2. The only difference is that this object is used for intrinsic reporting of the return air temperature sensor, high and low problems when the control temperature is not set to return. Geothermal Temperature 19 R AI 13 Current reading of sensor Heat Exchanger Supply 23 R AI 14 Current reading of sensor Temperature Heat Exchanger Return Temperature 23 R AI 15 Current reading of sensor Analog Values Outdoor Air Reset Max Setpoint 32 W AV 1 F/ C Heat Addition Stage Setpoints Stage 1 Setpoint Stage 2 Setpoint Stage 3 Setpoint Stage 4 Setpoint Stage 5 Setpoint Stage 6 Setpoint Stage 7 Setpoint Stage 8 Setpoint Stage 9 Setpoint Stage 10 Setpoint Stage 11 Setpoint Stage 12 Setpoint Heat Addition Stage Differentials Stage 1 Differential Stage 2 Differential Stage 3 Differential Stage 4 Differential Stage 5 Differential Stage 6 Differential Stage 7 Differential Stage 8 Differential Stage 9 Differential 21 W Supply control temperature at which the LWM is to energize the corresponding heat stage output. (F/ C) AV 2 AV 3 AV 4 AV 5 AV 6 AV 7 AV 8 AV 9 AV 10 AV 11 AV 12 AV W Differential is added to the the corresponding Heat Addition Stage AV 14 Setpoint to determine the temperature at which the stage is turned off. AV 15 AV 16 AV 17 AV 18 AV 19 AV 20 AV 21 AV ED 19015

11 Network Control Page Read(R), Write(W), Commandable(C) Object Type Instance Description Stage 10 Differential Stage 11 Differential Stage 12 Differential Heat Rejection Stage Setpoints Stage 1 Setpoint Stage 2 Setpoint Stage 3 Setpoint Stage 4 Setpoint Stage 5 Setpoint Stage 6 Setpoint Stage 7 Setpoint Stage 8 Setpoint Stage 9 Setpoint Stage 10 Setpoint Stage 11 Setpoint Stage 12 Setpoint Heat Rejection Stage Differentials Stage 1 Differential Stage 2 Differential Stage 3 Differential Stage 4 Differential Stage 5 Differential Stage 6 Differential Stage 7 Differential Stage 8 Differential Stage 9 Differential Stage 10 Differential Stage 11 Differential Stage 12 Differential AV 23 AV 24 AV W Loop control temperature at which the LWM is to energize the AV 26 corresponding cool stage output. (F/ C) AV 27 AV 28 AV 29 AV 30 AV 31 AV 32 AV 33 AV 34 AV 35 AV 36 AV W Differential is subtracted from the the corresponding Cool Stage Setpoint AV 38 to determine the temperature at which the stage is turned off. AV 39 AV 40 AV 41 AV 42 AV 43 AV 44 AV 45 AV 46 AV 47 AV 48 AV 49 Pump 1 Hours 36 W AV 52 Pump 2 Hours 36 W AV 53 Secondary Pump 1 Hours 37 W AV 54 Secondary Pump 2 Hours 38 W AV 55 Tower Setpoint 42 W AV 56 F/ C Boiler Setpoint 16 W AV 57 F/ C PreHeat Setpoint 35 W AV 58 The temperature at which preheat will turn off. Also used to determine one of the conditions that will allow the preheat addition stages to turn on. PreHeat Differential 34 W AV 59 PreHeat Outdoor Air Setpoint 35 W AV 60 The Outdoor air temperature at which pre-cool will turn off. Also used to determine the conditions that will allow the precool heat rejections stages to turn on. PreCool Setpoint 33 W AV 61 The loop water temperature at which pre-cool will turn off. Also used to determine the conditions that will allow the precool heat rejections stages to turn on. PreCool Differential 33 W AV 62 PreCool Outdoor Air Setpoint 33 W AV 63 F/ C Tower Fan Speed 42 R AV 64 Indicates current percentage of tower fan speed. Boiler Valve Position 17 R AV 65 Indicates current percentage of boiler valve capacity. Alarm Value 49 R AV 66 24=UnoccLimProtect, 28=SecPump2Manual, 32=SecPump1Manual, 36=Pump2Manual, 40=Pump1Manual, 44=SecLpSw2Stick, 48=SecLpSw1Stick, 50=SecPump2Fail, 51=SecPump1Fail, 52=MainPmp2SwStuck, 56= MainPmp1SwStuck, 60=TowerReturnTempFail, 61=TowerSupplyTempFail, 65=StorageTankTempFail, 68=GeothermalTempFail, 70=BoilerSupplyTempFail, 71=BoilerReturnTempFail, 75=HeatXchrRATempFail, 76=HeatXchrSupplyTempFail, ED

12 Network Control Page Read(R), Write(W), Commandable(C) Object Type Instance Description 80=OAHumiditySensFail, 112=MainPump2Fail, 116=MainPump1Fail, 120=BoilerPumpsFail, 122=TowerPumpsFail, 124=LoRATProb, 128=HiRATProb, 132=RATSensorProb, 204=HiLoopSupplyTemp, 205=LoRATFlt, 206=HiRATFlt, 208=LoSupplyTmpFlt, 209=HeadPressSensFlt, 210=LoHeadPressure, 212=HiHeadPressure, 232=OutsideAirSensFault, 235=LpReturnSensFlt, 238=LpSupplySensFlt, 248=MainLpPumpFail, 250=EmergStop Warning Alarm 50 R AV 67 24=UnoccLimProtect, 28=SecPump2Manual, 32=SecPump1Manual, 36=Pump2Manual, 40=Pump1Manual, 44=SecLpSw2Stick, 48=SecLpSw1Stick, 50=SecPump2Fail, 51=SecPump1Fail, 52=MainPmp2SwStuck, 56=MainPmp1SwStuck, 60=TowerReturnTempFail, 61=TowerSupplyTempFail, 65=StorageTankTempFail, 68=GeothermalTempFail, 70=BoilerSupplyTempFail, 71=BoilerReturnTempFail, 75=HeatXchrRATempFail, 76=HeatXchrSupplyTempFail, 80=OAHumiditySensFail Fault Alarm 51 R AV = HiLoopSupplyTemp, 205=LoRATFlt, 206=HiRATFlt, 208=LoSupplyTmpFlt, 209=HeadPressSensFlt, 210=LoHeadPressure, 212=HiHeadPressure, 232=OutsideAirSensFault, 235=LpReturnSensFlt, 238=LpSupplySensFlt, 248=MainLpPumpFail, 250=EmergStop Stage Time 38 W AV 69 Boiler Deadband 16 W AV 70 Boiler Range 16 W AV 71 Used to calculate the gain used in the PI control function that modules that boiler valve. Tower Deadband 41 W AV 72 Tower Range 41 W AV 73 Used to calculate the gain used in the PI control function that modules that tower valve. Recirc Timer 37 W AV 74 Zero OA 43 W AV 75 Max OA 30 W AV 76 Pump Fail Delay 37 W AV 77 Control Temperature 18 R AV 78 This point reads the current supply or return temperature depending on which sensor is selected for control. Main Loop Capacity - Network 29 W AV 79 Default= A value greater than 160 indicates that this property is not being set by the network. (%) Problem Alarm 51 R AV =MainPump2Fail, 116=MainPump1Fail, 120=BoilerPumpsFail, 122=TowerPumpsFail, 124=LoRATProb, 128=HiRATProb, 132=RATSensorProb Active Heat Addition Stages 15 R AV Active Heat Rejection Stages 15 R AV Network Outdoor Air Temperature 31 W AV F / C indicates network is not writing this value. Outdoor Air Temperature 32 R AV 85 This point reads the current outdoor air temperature for control. If manual control is active, this will be the manual temperature. If a valid value is in Network Outdoor Air Temperature, this will be set to that value. Otherwise, this is set equal to the local Outdoor air temperature sensor. Sump Dump Setpoint 40 W AV 86 Sump Dump Deadband 39 W AV 87 Sump Dump Day 39 W AV 88 Day of the month the sump will dump, if feature is enabled. Sump Fill Day 40 W AV 89 Day of the month the sump will fill, if feature is enabled. Outdoor Air Reset Max Reset 31 W AV 90 Amount Outdoor Air Reset Min Setpoint 32 W AV 91 Outdoor Air Reset Min 32 W AV 92 Outdoor Air Reset Max 32 W AV 93 Minimum Control Temp Range 30 R AV 94 Maximum Control Temp Range 30 R AV 95 Binary Inputs Pump 1 Flow 35 R BI 2 0=Off, 1=On 12 ED 19015

13 Network Control Page Read(R), Write(W), Commandable(C) Object Type Instance Description Pump 2 Flow 36 R BI 3 0=Off, 1=On Secondary Pump 1 Flow 37 R BI 4 0=Off, 1=On Secondary Pump 2 Flow 38 R BI 5 0=Off, 1=On Damper Interlock 18 R BI 6 0=Off, 1=On Binary Outputs Alarm LED 44 C BO 1 0=Off, 1=On Tower Fan Enable 41 C BO 2 0=Off, 1=On Binary Values Emergency Stop Fault 52 C BV 1 0=Normal, 1=Alarm UnoccLimProtect 57 C BV 2 0=Normal, 1=Alarm Second Pump 2 Manual Fail 56 C BV 3 0=Normal, 1=Alarm Second Pump 1 Manual Fail 56 C BV 4 0=Normal, 1=Alarm Pump 2 Manual Fail 54 C BV 5 0=Normal, 1=Alarm Pump 1 Manual Fail 54 C BV 6 0=Normal, 1=Alarm Secondary Loop Switch 2 Stick Fail 55 C BV 7 0=Normal, 1=Alarm Secondary Loop Switch 1 Stick Fail 56 C BV 8 0=Normal, 1=Alarm Main Loop Switch 2 Stuck Fail 54 C BV 9 0=Normal, 1=Alarm Main Loop Switch 1 Stuck Fail 53 C BV 10 0=Normal, 1=Alarm Secondary Loop Pump 2 Fail 55 C BV 15 0=Normal, 1=Alarm Secondary Loop Pump 1 Fail 55 C BV 16 0=Normal, 1=Alarm Main Loop Pump 2 Fail 53 C BV 17 0=Normal, 1=Alarm Main Loop Pump 1 Fail 52 C BV 18 0=Normal, 1=Alarm Boiler Pumps Fail Problem 52 C BV 20 0=Normal, 1=Alarm Main Loop Pump Shut Down Fault 53 C BV 21 0=Normal, 1=Alarm Tower Pumps Fail Problem 56 C BV 22 0=Normal, 1=Alarm Multistate Values Unit State 43 R MSV 1 1=Unocc, 2=UnoccLim, 3=Recirc, 4=Preheat, 5=PreCool, 6=ExtFlowReq, 7=Occ, 8=Alarm, 9=Manual, 10=Off Lead Pump Select 28 W MSV 3 1=None, 2=Pump1, 3=Pump2, 4=Auto (default) Lead Secondary Pump Select 28 W MSV 4 1=None, 2=Pump1, 3=Pump2, 4=Auto (default) PreHeat Stages 35 W MSV 5 1=None (default), 2=1, 3=2, 4=3, 5=4 PreCool Stages 34 W MSV 6 1=None (default), 2=1, 3=2, 4=3, 5=4, 6=5, 7=6 PreCool Enable 33 W MSV 7 1=Disabled (default), 2=Enabled PreHeat Enable 34 W MSV 8 1=Disabled (default), 2=Enabled Unit Support 43 W MSV 9 1=SI, 2=US (default) Application Mode 15 W MSV 10 1=Off, 2=Recirc, 3=HeatAddOnly, 4=HeatRejOnly, 5=HeatAddRej(default) Current State 18 W MSV 11 1=Occ, 2=Unocc, 3=Auto(default) Sump Dump Select 40 W MSV 13 1=Disable, 2=Enabled (default) Main Loop Control Select 29 W MSV 14 1=Supply (default), 2=Return Control Mode 17 R MSV 15 1=Off, 2=Recirc, 3=HeatAddOnly, 4=HeatRejOnly, 5=HeatAddRej 6=Auto/Net (default) Clear Alarms 17 W MSV 16 1=No, 2=ClrFlts, 3=ClrPrblms, 4=ClrWrngs, 5=ClearAllAlms. Heat Addition Status 23 R MSV 17 1=None, 2=OffLoc, 3=OffNet, 4=Enabled, 5=Alarm. Heat Rejection Status 27 R MSV 18 1=None, 2=OffLoc, 3=OffNet, 4=Enabled, 5=Alarm Sump Dump Month 39 W MSV 19 1=Disable, 2=Jan, 3=Feb, 4=March, 5=April, 6=May, 7=June, 8=July, 9=Aug, 10=Sept, 11=Oct, 12=Nov, 13=Dec. Sump Fill Month 40 W MSV 20 1=Disable, 2=Jan, 3=Feb, 4=March, 5=April, 6=May, 7=June, 8=July, 9=Aug, 10=Sept, 11=Oct, 12=Nov, 13=Dec. Notification Class Notification Class - Faults 47 W NC 1 Generates notifications for fault alarms. Notification Class Problems 48 W NC 2 Generates notifications for problem alarms. Notification Class - Warnings 48 W NC 3 Generates notifications for warning alarms. File Objects BACnet Client Config File 59 N/A File 1 This file contains the BACnet client configuration. For this application, the ED

14 Network Control Page Read(R), Write(W), Commandable(C) Object Type Instance Description Loop Water manager acts as a server, so this file does not apply. BACnet COV Config File 59 N/A File 2 This file contains the BACnet COV configuration. Error Log File 59 N/A File 3 This is the error log file for the BACnet module. History Log File 59 N/A File 4 This is the history log file for the BACnet module. BACnet Event Enrollment Config 60 N/A File 5 This is the BACnet Event Enrollment Configuration file. File EDE File 60 N/A File 6 This is the engineering data exchange file of this controller. This file details the BACnet interface of the controller. It tells you what points are available and information about each point. EDE File State Text 60 N/A File 7 This is the engineering data exchange file of this controller with state text. 14 ED 19015

15 Detailed Data Point Information The data points or properties (attributes) defined in this section reference data that is generated in the Loop Water Manager. Active Heat Addition Stages This read only object indicates the current number of active heat addition stages. If the unit is not configured for any heat addition stages, this object will not be available. Stages No Units Real 0-12 N/A Analog Value 2 82 Present_Value 85 <Device Name>.ActiveHeatAddStage.Present_Value Active Heat Rejection Stages This read only object indicates the current number of active heat rejection stages. If the unit is not configured for any heat rejection stages, this object will not be available. Stages No Units Real 0-12 N/A Analog Value 2 83 Present_Value 85 <Device Name>.ActiveHeatRejStage.Present_Value Application Mode Keypad Menu Path Main Menu\App Mode= This read/write attribute sets the unit in an application mode (auto, recirc, heat addition only, heat rejection only, or heat addition and rejection). This attribute has no affect unless Control Mode is set to Auto. Control Mode is only set at the keypad/display. Method N/A Unsigned Enumerated 5=HeatAddRej Multistate Value Present_Value 85 <Device Name>.AppMode.Present_Value 1=Off 2=Recirc 3=HeatAddOnly 4=HeatRejOnly 5=HeatAddRej ED

16 Application Version Keypad Menu Path Main Menu\About This LWM\App Version= This read-only property identifies the version of application software loaded into the Loop Water Manager. N/A N/A CharacterString N/A N/A Device 8 Variable Application_Software_Version 12 <Device Name>.Application_Software_Version Boiler Deadband Keypad Menu Path Main Menu\View/Set Unit\Boiler Setpoints\Boiler DB= This read/write property indicates the current boiler deadband. Differential Temperature d F / d C Real d F d F Analog Value 2 70 Present_Value 85 <Device Name>.BoilerDB.Present_Value Boiler Range Keypad Menu Path Main Menu\View/Set Unit\Boiler Setpoints\Boiler Ctrl Zn= This read/write property is used to calculate the gain used in the PI control function that modules that boiler valve. If the boiler valve is hunting, lower this value. If it is sluggish, raise this value. Make small adjustments to avoid overcorrecting. Differential Temperature d F /d C Real d F d F Analog Value 2 71 Present_Value 85 <Device Name>.BoilerRange.Present_Value Boiler Return Temperature Keypad Menu Path Main Menu\Quick Menu\Blr Return Tmp= This read-only property indicates the current reading of the unit Boiler Return temperature sensor. Temperature F / C Real F ( C ) N/A Analog Input 0 4 Present_Value 85 <Device Name>.BoilerReturnTemp.Present_Value Boiler Setpoint Keypad Menu Path Main Menu\View/Set Unit\Boiler Setpoints\Boiler Spt= This read/write property sets the Boiler Setpoint via the network. 16 ED 19015

17 Temperature F / C Real F ( C ) N/A Analog Value 2 57 Present_Value 85 <Device Name>.BoilerSpt.Present_Value Boiler Supply Temperature Keypad Menu Path Main Menu\Quick Menu\Blr Supply Tmp= This read-only property indicates the current reading of the unit Boiler Supply temperature sensor. Temperature F / C Real F ( C ) N/A Analog Input 0 3 Present_Value 85 <Device Name>.BoilerSupplyTemp.Present_Value Boiler Valve Position This read-only property indicates the current percentage of the Boiler Valve capacity. Percent % Real 0-100% N/A Analog Value 2 65 Present_Value 85 <Device Name>.BoilerValvePos.Present_Value Clear Alarms This read/write property allows alarms to be cleared through the network. After a clear command is sent, the Present Value will be automatically switched back to No (1). Method N/A Unsigned Enumerated 1=No Multistate Value Present_Value 85 <Device Name>.ClearAlarms.Present_Value 1=No 2=ClrFlts 3=ClrPrblms 4=ClrWrngs 5=ClrAllAlms Control Mode Keypad Menu Path Main Menu\Ctrl Mode= ED

18 This read only property indicates the current control mode in the Loop Water Manager. If the Present Value is equal to Auto/Net (6), then the controller will use the Application Mode. The control mode does not set the unit into a particular state, it just tells the controller which states are possible. Method N/A Unsigned Enumerated 6=Auto/Net Multistate Value Present_Value 85 <Device Name>.ControlMode.Present_Value 1=Off 2=Recirc 3=HeatAddOnly 4=HeatRejOnly 5=HeatAddRej 6=Auto/Net (default) Control Temperature Keypad Menu Path Main Menu\Quick Menu\Lp Ctrl Temp= This read-only property indicates the current temperature used for control. It is either the supply or return temp depending on the configuration. Temperature F / C Real F ( C ) N/A Analog Value 2 78 Present_Value 85 <Device Name>.ControlTemp.Present_Value Current State This read/write property is used to command occupancy for the Loop Water Manager (LWM). If this parameter is set to Occ(1), the LWM will be occupied regardless of the internal schedule. If the Present Value is set to Unocc(2), then the LWM will be unoccupied, unless it is being scheduled by the internal schedule. If the Present Value is set to Auto(3), then the internal schedule only is used to determine occupancy. Method N/A Unsigned Enumerated 3=Auto Multistate Value Present_Value 85 <Device Name>.CurrentState.Present_Value 1=Occ 2=Unocc 3=Auto(Null) Damper Interlock Keypad Menu Path MainOverview\Unit Configuration\Component Setup\Damper I lock= When this read/write BACnet object indicates On, a tower fan discharge damper proving switch is wired to the LWM as heat rejection stage 1 and you want to wait for this input to be closed before progressing to Heat Rejection Stage 2. When Off, the controller will not pause between Heat Rejection Stages 1 and 2 any more than the stage timer requires. 18 ED 19015

19 Method N/A Unsigned Enumerated 1=On Binary Input 3 6 Present_Value 85 <Device Name>.DamperInterlock.Present_Value 0 = Off 1 = On Geothermal Temperature Keypad Menu Path Main Menu\View/Set Unit\Temperatures\Geothermal Tmp= This read-only attribute indicates the current value of the geothermal temperature sensor. Temperature F / C Real F ( C) N/A Analog Input 0 13 Present_Value 85 <Device Name>.GeothermalTemp.Present_Value Head Pressure Keypad Menu Path Main Menu\Quick Menu\Head Pressure= This read-only property displays the unit s head pressure. Pound per square inch psi Real psi N/A Analog Input 0 9 Present_Value 85 <Device Name>.HeadPressure.Present_Value Heat Addition Stage Differentials Keypad Menu Path Main Menu\View/Set Unit\Heat Stage Spts\Stage 1 Diff= Main Menu\View/Set Unit\Heat Stage Spts\Stage 2 Diff= Main Menu\View/Set Unit\Heat Stage Spts\Stage 3 Diff= Main Menu\View/Set Unit\Heat Stage Spts\Stage 4 Diff= Main Menu\View/Set Unit\Heat Stage Spts\Stage 5 Diff= Main Menu\View/Set Unit\Heat Stage Spts\Stage 6 Diff= Main Menu\View/Set Unit\Heat Stage Spts\Stage 7 Diff= Main Menu\View/Set Unit\Heat Stage Spts\Stage 8 Diff= Main Menu\View/Set Unit\Heat Stage Spts\Stage 9 Diff= Main Menu\View/Set Unit\Heat Stage Spts\Stage 10 Diff= Main Menu\View/Set Unit\Heat Stage Spts\Stage 11 Diff= Main Menu\View/Set Unit\Heat Stage Spts\Stage 12 Diff= These read/write properties set the Heat Addition Stage Differentials via the network. Differential d F / d C Real 0-9d F d F ED

20 Stage 1 Differential Analog Value 2 14 Present_Value 85 <Device Name>.HeatAddStage1Diff.Present_Value Stage 2 Differential Analog Value 2 15 Present_Value 85 <Device Name>.HeatAddStage2Diff.Present_Value Stage 3 Differential Analog Value 2 16 Present_Value 85 <Device Name>.HeatAddStage3Diff.Present_Value Stage 4 Differential Analog Value 2 17 Present_Value 85 <Device Name>.HeatAddStage4Diff.Present_Value Stage 5 Differential Analog Value 2 18 Present_Value 85 <Device Name>.HeatAddStage5Diff.Present_Value Stage 6 Differential Analog Value 2 19 Present_Value 85 <Device Name>.HeatAddStage6Diff.Present_Value Stage 7 Differential Analog Value 2 20 Present_Value 85 <Device Name>.HeatAddStage7Diff.Present_Value Stage 8 Differential Analog Value 2 21 Present_Value 85 <Device Name>.HeatAddStage8Diff.Present_Value 20 ED 19015

21 Stage 9 Differential Analog Value 2 22 Present_Value 85 <Device Name>.HeatAddStage9Diff.Present_Value Stage 10 Differential Analog Value 2 23 Present_Value 85 <Device Name>.HeatAddStage10Diff.Present_Value Stage 11 Differential Analog Value 2 24 Present_Value 85 <Device Name>.HeatAddStage11Diff.Present_Value Stage 12 Differential Analog Value 2 25 Present_Value 85 <Device Name>.HeatAddStage12Diff.Present_Value Heat Addition Stage Setpoints Keypad Menu Path Main Menu\View/Set Unit\Heat Stage Spts\Stage 1 Spt= Main Menu\View/Set Unit\Heat Stage Spts\Stage 2 Spt= Main Menu\View/Set Unit\Heat Stage Spts\Stage 3 Spt= Main Menu\View/Set Unit\Heat Stage Spts\Stage 4 Spt= Main Menu\View/Set Unit\Heat Stage Spts\Stage 5 Spt= Main Menu\View/Set Unit\Heat Stage Spts\Stage 6 Spt= Main Menu\View/Set Unit\Heat Stage Spts\Stage 7 Spt= Main Menu\View/Set Unit\Heat Stage Spts\Stage 8 Spt= Main Menu\View/Set Unit\Heat Stage Spts\Stage 9 Spt= Main Menu\View/Set Unit\Heat Stage Spts\Stage 10 Spt= Main Menu\View/Set Unit\Heat Stage Spts\Stage 11 Spt= Main Menu\View/Set Unit\Heat Stage Spts\Stage 12 Spt= These read/write properties set the Heat Addition Stage Setpoints via the network. This set point will adjust upward in response to the Outdoor air temperature if the OAResetType is set to OAT. Temperature F / C Real F ( C ) 64.9 F Stage 1 Setpoint Analog Value 2 2 Present_Value 85 <Device Name>.HeatAddStage1Spt.Present_Value Stage 2 Setpoint Analog Value 2 3 Present_Value 85 <Device Name>.HeatAddStage2Spt.Present_Value ED

22 Stage 3 Setpoint Analog Value 2 4 Present_Value 85 <Device Name>.HeatAddStage3Spt.Present_Value Stage 4 Setpoint Analog Value 2 5 Present_Value 85 <Device Name>.HeatAddStage4Spt.Present_Value Stage 5 Setpoint Analog Value 2 6 Present_Value 85 <Device Name>.HeatAddStage5Spt.Present_Value Stage 6 Setpoint Analog Value 2 7 Present_Value 85 <Device Name>.HeatAddStage6Spt.Present_Value Stage 7 Setpoint Analog Value 2 8 Present_Value 85 <Device Name>.HeatAddStage7Spt.Present_Value Stage 8 Setpoint Analog Value 2 9 Present_Value 85 <Device Name>.HeatAddStage8Spt.Present_Value Stage 9 Setpoint Analog Value 2 10 Present_Value 85 <Device Name>.HeatAddStage9Spt.Present_Value Stage 10 Setpoint Analog Value 2 11 Present_Value 85 <Device Name>.HeatAddStage10Spt.Present_Value 22 ED 19015

23 Stage 11 Setpoint Analog Value 2 12 Present_Value 85 <Device Name>.HeatAddStage11Spt.Present_Value Stage 12 Setpoint Analog Value 2 13 Present_Value 85 <Device Name>.HeatAddStage12Spt.Present_Value Heat Addition Status Keypad Menu Path Main Menu\Quick Menu\HeatAdd Status= This read only property displays the current heat addition status. If the unit is not configured for any heat stages, this will show None(1). If the Control Mode is locking out heat addition, the Present Value will read OffLoc(2). If the network is locking out heat addition using the Application Mode, the Present Value will read OffNet(3). If the Secondary Loop Pump Fail Problem is active, the Present value will read Alarm(5). Otherwise heat addition will be enabled(4). Method N/A Unsigned Enumerated Multistate Value Present_Value 85 <Device Name>.HeatAddStatus.Present_Value 1=None 2=OffLoc 3=OffNet 4=Enabled 5=Alarm Heat Exchanger Return Temperature Keypad Menu Path Main Menu\View/Set Unit\Temperatures\HeatXchr RetTmp= This read-only attribute indicates the current value of the heat exchanger return temperature sensor. Temperature F / C Real F ( C) N/A Analog Input 0 15 Present_Value 85 <Device Name>.HeatXchrReturnTemp.Present_Value Heat Exchanger Supply Temperature Keypad Menu Path Main Menu\View/Set Unit\Temperatures\HeatXchr SupTmp= This read-only attribute indicates the current value of the heat exchanger supply temperature sensor. Temperature F / C Real F ( C) N/A ED

24 Analog Input 0 14 Present_Value 85 <Device Name>.HeatXchrSupplyTemp.Present_Value Heat Rejection Stage Differentials Keypad Menu Path Main Menu\View/Set Unit\Cool Stage Spts\Stage 1 Diff= Main Menu\View/Set Unit\Cool Stage Spts\Stage 2 Diff= Main Menu\View/Set Unit\Cool Stage Spts\Stage 3 Diff= Main Menu\View/Set Unit\Cool Stage Spts\Stage 4 Diff= Main Menu\View/Set Unit\Cool Stage Spts\Stage 5 Diff= Main Menu\View/Set Unit\Cool Stage Spts\Stage 6 Diff= Main Menu\View/Set Unit\Cool Stage Spts\Stage 7 Diff= Main Menu\View/Set Unit\Cool Stage Spts\Stage 8 Diff= Main Menu\View/Set Unit\Cool Stage Spts\Stage 9 Diff= Main Menu\View/Set Unit\Cool Stage Spts\Stage 10 Diff= Main Menu\View/Set Unit\Cool Stage Spts\Stage 11 Diff= Main Menu\View/Set Unit\Cool Stage Spts\Stage 12 Diff= This read/write property sets the Heat Rejection Stage Differentials via the network. Differential d F / d C Real 0-9d F d F Stage 1 Differential Analog Value 2 38 Present_Value 85 <Device Name>.HeatRejStage1Diff.Present_Value Stage 2 Differential Analog Value 2 39 Present_Value 85 <Device Name>.HeatRejStage2Diff.Present_Value Stage 3 Differential Analog Value 2 40 Present_Value 85 <Device Name>.HeatRejStage3Diff.Present_Value Stage 4 Differential Analog Value 2 41 Present_Value 85 <Device Name>.HeatRejStage4Diff.Present_Value Stage 5 Differential Analog Value 2 42 Present_Value 85 <Device Name>.HeatRejStage5Diff.Present_Value 24 ED 19015

25 Stage 6 Differential Analog Value 2 43 Present_Value 85 <Device Name>.HeatRejStage6Diff.Present_Value Stage 7 Differential Analog Value 2 44 Present_Value 85 <Device Name>.HeatRejStage7Diff.Present_Value Stage 8 Differential Analog Value 2 45 Present_Value 85 <Device Name>.HeatRejStage8Diff.Present_Value Stage 9 Differential Analog Value 2 46 Present_Value 85 <Device Name>.HeatRejStage9Diff.Present_Value Stage 10 Differential Analog Value 2 47 Present_Value 85 <Device Name>.HeatRejStage10Diff.Present_Value Stage 11 Differential Analog Value 2 48 Present_Value 85 <Device Name>.HeatRejStage11Diff.Present_Value Stage 12 Differential Analog Value 2 49 Present_Value 85 <Device Name>.HeatRejStage12Diff.Present_Value Heat Rejection Stage Setpoints Keypad Menu Path Main Menu\View/Set Unit\Cool Stage Spts\Stage 1 Spt= Main Menu\View/Set Unit\Cool Stage Spts\Stage 2 Spt= Main Menu\View/Set Unit\Cool Stage Spts\Stage 3 Spt= Main Menu\View/Set Unit\Cool Stage Spts\Stage 4 Spt= Main Menu\View/Set Unit\Cool Stage Spts\Stage 5 Spt= Main Menu\View/Set Unit\Cool Stage Spts\Stage 6 Spt= Main Menu\View/Set Unit\Cool Stage Spts\Stage 7 Spt= Main Menu\View/Set Unit\Cool Stage Spts\Stage 8 Spt= Main Menu\View/Set Unit\Cool Stage Spts\Stage 9 Spt= Main Menu\View/Set Unit\Cool Stage Spts\Stage 10 Spt= ED

26 Main Menu\View/Set Unit\Cool Stage Spts\Stage 11 Spt= Main Menu\View/Set Unit\Cool Stage Spts\Stage 12 Spt= These read/write properties set the Heat Rejection Stage Setpoints via the network. This set point will adjust upward in response to the Outdoor air temperature. Temperature F / C Real F ( C ) 81.0 F Stage 1 Setpoint Analog Value 2 26 Present_Value 85 <Device Name>.HeatRejStage1Spt.Present_Value Stage 2 Setpoint Analog Value 2 27 Present_Value 85 <Device Name>.HeatRejStage2Spt.Present_Value Stage 3 Setpoint Analog Value 2 28 Present_Value 85 <Device Name>.HeatRejStage3Spt.Present_Value Stage 4 Setpoint Analog Value 2 29 Present_Value 85 <Device Name>.HeatRejStage4Spt.Present_Value Stage 5 Setpoint Analog Value 2 30 Present_Value 85 <Device Name>.HeatRejStage5Spt.Present_Value Stage 6 Setpoint Analog Value 2 31 Present_Value 85 <Device Name>.HeatRejStage6Spt.Present_Value Stage 7 Setpoint Analog Value 2 32 Present_Value 85 <Device Name>.HeatRejStage7Spt.Present_Value 26 ED 19015

27 Stage 8 Setpoint Analog Value 2 33 Present_Value 85 <Device Name>.HeatRejStage8Spt.Present_Value Stage 9 Setpoint Analog Value 2 34 Present_Value 85 <Device Name>.HeatRejStage9Spt.Present_Value Stage 10 Setpoint Analog Value 2 35 Present_Value 85 <Device Name>.HeatRejStage10Spt.Present_Value Stage 11 Setpoint Analog Value 2 36 Present_Value 85 <Device Name>.HeatRejStage11Spt.Present_Value Stage 12 Setpoint Analog Value 2 37 Present_Value 85 <Device Name>.HeatRejStage12Spt.Present_Value Heat Rejection Status Keypad Menu Path Main Menu\Quick Menu\HeatAdd Status= This read only property displays the current heat rejection status. If the unit is not configured for any cool stages, this will show None(1). If the Control Mode is locking out heat rejection, the Present Value will read OffLoc(2). If the network is locking out heat rejection using the Application Mode, the Present Value will read OffNet(3). If the Secondary Loop Pump Fail Problem is active, the Present value will read Alarm(5). Otherwise heat rejection will be enabled(4). Method N/A Unsigned Enumerated Multistate Value Present_Value 85 <Device Name>.HeatRejStatus.Present_Value 1=None 2=OffLoc 3=OffNet 4=Enabled 5=Alarm ED

MicroTech III Applied Air Handling Unit Controller Protocol Information

MicroTech III Applied Air Handling Unit Controller Protocol Information Engineering Data ED 15112-2 Group: Controls Part Number: ED 15112-2 Date: January 2009 Supersedes: ED 15112-1 MicroTech III Applied Air Handling Unit Controller Protocol Information Networks Networks 2009

More information

MicroTech III Rooftop and Self Contained Unit Controller Protocol Information

MicroTech III Rooftop and Self Contained Unit Controller Protocol Information Engineering Data ED 15112-8 Group: Controls Part Number: ED 15112 Date: February 2011 Supersedes: ED 15112-7 MicroTech III Rooftop and Self Contained Unit Controller Protocol Information Networks Networks

More information

PIR Ready VT76xx Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications. BACnet Integration Manual September 1, 2010

PIR Ready VT76xx Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications. BACnet Integration Manual September 1, 2010 PIR Ready VT76xx Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications BACnet Integration Manual September 1, 2010 1 Product Overview The VT76xx PI thermostat family is specifically

More information

BACnet Integration Manual ITG-VH72xx-BAC-E00 ( _R0 Issue Date: October 21, 2008)

BACnet Integration Manual ITG-VH72xx-BAC-E00 ( _R0 Issue Date: October 21, 2008) VH7200 Humidistat Series For Humidification & Dehumidification Control For Commercial HVAC Applications BACnet Integration Manual ITG-VH72xx-BAC-E00 (028-6017_R0 Issue Date: October 21, 2008) 1 Product

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-7 Group: Controls Part Number: ED 15121 Date: July 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHRAE 135-2004, BACnet

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a fieldselectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

MicroTech Water-Cooled Screw Chiller Controller

MicroTech Water-Cooled Screw Chiller Controller BACnet Data Information Packet BD 02-8 Group: Controls Date: January 2003 MicroTech Water-Cooled Screw Chiller Controller Point mapping data for the MicroTech BACdrop Gateway with PMF version 1.10 software

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet DataSheet ev 1.2.008/4.1 July 30, 2013 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

Table of Contents. WSHP Open v3

Table of Contents. WSHP Open v3 WSHP Open v3 Integration Guide CARRIER CORPORATION 2012 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-500-01 11/29/2012 Table of Contents Introduction... 1

More information

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47 WSHP Open v3 CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-539-01 2/8/2017 Verify that you have the most current version of this document

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

Table of Contents. W2W Open

Table of Contents. W2W Open W2W Open Points and Properties CARRIER CORPORATION 2013 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-457-01 3/27/2013 Table of Contents Introduction... 1

More information

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C DataSheet ev 1.10.403/4.02 November 6, 2012 Operating Sequence Standard Occupied During

More information

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical

IMC BACnet Module. Service Literature. Table of Contents. General. Field Connections. Physical Service Literature Corp. 0808 L6 06/08 IMC BACnet Module General The IMC BACnet Module (BP1) allows communication between the Lennox IMC M1 8 controller and a BACnet MS/TP network. This module is mounted

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-6 Group: Controls Part Number: ED 15121 Date: March 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHAE 135-2004, BACnet

More information

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY A C-TRAC3 COMMUNICATION MANUAL FOR BACnet NOVEMBER 2010 TO JANUARY 2014 UNIT MODEL NO. UNIT SERIAL NO. SERVICED BY: TEL. NO: CANADIAN HEAD OFFICE AND FACTORY 1401 HASTINGS CRES. SE CALGARY, ALBERTA T2G

More information

MicroTech Series-200 Flooded Screw Chiller

MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D

More information

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller All volatile (Output) type points will revert to the uncommanded values after a power interruption.

More information

MicroTech Unit Ventilator

MicroTech Unit Ventilator Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This

More information

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include: Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2018 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-537-01 1/9/2018 Verify that you have the most current version of this document

More information

Open Protocol Data Communications

Open Protocol Data Communications MicroTech Series-100 Centrifugal Chiller Open Protocol Data Communications Information Packet Version 3.2 April, 1996 - C O N F I D E N T I A L - This Document may not be copied or reproduced in any way

More information

Platform Services BACnet Alarm Management

Platform Services BACnet Alarm Management Description: Guide to understanding and setting up BACnet Alarms, visualizing real-time and historical BACnet alarms using AlarmWorX64 Viewer and logging them to SQL database using AlarmWorX64 Logger OS

More information

McQuay Microtech III BACnet MS/TP Application 4181 Point Map

McQuay Microtech III BACnet MS/TP Application 4181 Point Map Point Map June 2009 Systems Integration McQuay Microtech III BACnet MS/TP Application 4181 Point Map APOGEE Open Processor with McQuay Microtech III BACnet MS/TP Driver: Microtech III Applied Rooftop Unit

More information

Manual for the integration in BMS/GTC

Manual for the integration in BMS/GTC Manual for the integration in BMS/GTC Communication parameters MODBUS RTU and BACNET COMMUNICATION UTBS PRO-REG Software Version 3.6 EN ÍNDEX 1. GENERALITIES...2 1.1. Introduction...2 1.2. signals types...2

More information

Introduction. What is the RTU Open controller?

Introduction. What is the RTU Open controller? TU Open v3 CAIE COPOATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-521-01 8/22/2017 Verify that you have the most current version of this document

More information

BACnet Points List for Single Compressor Water to Water PROSSWWE-01

BACnet Points List for Single Compressor Water to Water PROSSWWE-01 The network variables will be listed by point type instance convention. 2:1 would mean point type 2, point instance 1. All volatile (Output) type points will revert to the uncommanded values after a power

More information

Delta ORCAview 3.40 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT

Delta ORCAview 3.40 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT Date: December 12, 2012 Vendor Name: Delta Controls Inc. Product Name: ORCAview Product Model Number: DOW-340 Product Version: 3.40 BACnet Protocol Revision: 6 Product Description: ORCAview is an industry

More information

Installation and Maintenance Manual IM

Installation and Maintenance Manual IM Installation and Maintenance Manual IM 1234-1 BACnet Thermostat Group: Applied Air Systems Part Number: IM 1234 Date: December 2014 Use with Daikin MicroTech Integrated Systems or as standalone Table of

More information

ESAC ebacgw Siemens. Date: Oct 15,2008. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description:

ESAC ebacgw Siemens. Date: Oct 15,2008. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description: Date: Oct 15,2008 Vendor Name: ESAC srl Product Name: ebacgw-siemens Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3 Product Description: ebacgw is a BACnet gateway to Siemens WSM

More information

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed

More information

Multistate Alarm. Introduction

Multistate Alarm. Introduction Object Dictionary 1 Multistate Alarm Introduction The Multistate Alarm object adds the alarming capability for a Boolean or multistate attribute for any object, such as the Present Value of a Binary Input

More information

Reciprocating Chiller

Reciprocating Chiller HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence

More information

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Technical Bulletin Code No. LIT-12011956 Issued November 23, 2015 Refer to the QuickLIT website for the most up-to-date

More information

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA HART Field Device Specification Meridian wiredhart 4320 Goldmine Rd. Monroe, NC 28110 USA HART is a registered trademark of the HART Communication Foundation TABLE OF CONTENTS 1. Introduction...5 1.1 Scope...5

More information

MRMS Multi-Room Monitoring Station

MRMS Multi-Room Monitoring Station Technical Specification Sheet Document. 149-213 October 2, 2014 MRMS Multi-Room Monitoring Station High Definition Color (TFT) Touchscreen Display Meets CE Conformance Standards Immediate feedback on room

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide Aurora Touch UPC Kit Instruction Guide For use in single compressor water-to-air equipment utilizing fi rmware UPCSWASTD01-01 Aurora Touch UPC Kit Instruction Guide *IG1583EW* IG1583EW 08/14 Aurora Touch

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

ICC INDUSTRIAL CONTROL COMMUNICATIONS, INC.

ICC INDUSTRIAL CONTROL COMMUNICATIONS, INC. ETH-1000 Chillgard LC Quick Start Guide for BACnet MS/TP This document provides a brief overview of the connections and settings that must be used to connect a preconfigured ETH-1000 gateway to a MSA Chillgard

More information

ESAC ebacgw Meteo. Date: Nov 25,2008. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description:

ESAC ebacgw Meteo. Date: Nov 25,2008. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description: Date: Nov 25,2008 Vendor Name: ESAC srl Product Name: ebacgw-meteo Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3 Product Description: ebacgw is a BACnet gateway to the weather

More information

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer Installation and interface must be performed by a qualified controls technician. IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND CONFIGURATION OF THIS EQUIPMENT. READ

More information

IntesisBox BACnet/IP Server - Notifier ID3000 series

IntesisBox BACnet/IP Server - Notifier ID3000 series IntesisBox Server - Notifier ID3000 series Gateway for integration of Notifier ID3000, ID3002, ID50 and ID60 fire panels into enabled control systems. Integrate your Notifier fire panels into your BACnet

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

ESAC ebacgw Tecnoalarm

ESAC ebacgw Tecnoalarm Date: Feb 28,2011 Vendor Name: ESAC srl Product Name: ebacgw-tecnoalarm Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3 Product Description: ebacgw is a BACnet gateway for Tecnoalarm

More information

RPM1600 Series Room Pressure Monitors

RPM1600 Series Room Pressure Monitors RPM1600 Series Room Pressure Monitors Technical Bulletin LB-RPM1611-0, LB--0 Code No. LIT-12012228 Issued October 2017 Refer to the QuickLIT website for the most up-to-date version of this document. How

More information

Document # R00

Document # R00 Viconics VT7200 Series PIR Ready Zoning Thermostats General The VT7200 series PIR Ready low-voltage microprocessor-based zoning thermostats have been specifically designed to control either 0-10Vdc, staged,

More information

MicroTech III Unit Controller for Applied Rooftop and Self-Contained Systems

MicroTech III Unit Controller for Applied Rooftop and Self-Contained Systems Operation and Maintenance Manual OM 920-1 MicroTech III Unit Controller for Applied Rooftop and Self-Contained Systems Group: Applied Systems Part Number: OM 920-1 Date: October 2009 RAH, RCS, RDS, RDT,

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

200i/KN2, KN4 Firmware Revision Sheet

200i/KN2, KN4 Firmware Revision Sheet 200i/KN2, KN4 Firmware Revision Sheet Revision 2.9 Special Release 1- November 2013 1. Added an external boiler Failsafe feature. The J6 Analog Output can be used to enable a SSR which can be used to enable

More information

FlameGard 5 UV/IR HART

FlameGard 5 UV/IR HART FlameGard 5 UV/IR HART HART Communication Manual The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

Enterprise Buildings Integrator R500 Protocol Implementation

Enterprise Buildings Integrator R500 Protocol Implementation June 2017 Enterprise Buildings Integrator R500 Protocol Implementation Conformance Statement (PICS) Topic: BACnet Protocol Implementation Conformance Statement (PICS) Date: June 2017 Version 1 Applicable

More information

Pathfinder Air-Cooled Chillers

Pathfinder Air-Cooled Chillers Operating & Maintenance Manual OMM 1168 Group: Chiller Part Number: OMM 1168 Date: September 2012 Rev 00 Supercedes: OMM 1123, July 2012 Pathfinder Air-Cooled Chillers AWS 170A/B through AWS 550A/B (Includes

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 482641 Microprocessor Controller for Make-Up Air Products Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

Metasys Integrator TITUS Application

Metasys Integrator TITUS Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application

More information

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN April 2005 CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP

PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP PoolPak SWHP with CommandPak Control System CPCS BACnet IP User s Guide DOCUMENT #: SVW05-BACNETIP-20180529 UPDATED: MAY 2018 INTRODUCTION PoolPak dehumidifiers equipped with the CommandPak Control System

More information

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

FCD-wire Contents. List of Figures

FCD-wire Contents. List of Figures FCD-wire Contents FCD-X21 Configuration 1 Introduction... 1 2 Opening the FCD Application... 1 3 FCD Window... 2 4 FCD LEDs... 3 5 Configuration Operations... 4 FCD Info...4 FCD System Info...5 FCD Interface

More information

Pathfinder Air-Cooled Chillers

Pathfinder Air-Cooled Chillers Operating & Maintenance Manual OMM 1123 Group: Chiller Part Number: OMM 1123 Date: January 2012 Supercedes: December 2011 Rev 00 Pathfinder Air-Cooled Chillers AWS 170A/B through AWS 550A/B (Includes Models

More information

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

FieldServer Driver - Serial FS McQuay Microtech Open Protocol Description FieldServer Driver - Serial FS-8700-80 McQuay Microtech Open Protocol This is an active client protocol. The driver is capable of acting as a master or slave. As a master, the Fieldserver polls

More information

PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30

PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30 PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30 OPERATION AND SERVICE MANUAL P/N 6006643, REVISION C AUGUST 2015 PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30 OPERATION AND SERVICE MANUAL P/N 6006643, REVISION

More information

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System Technical Bulletin AD-1272 Code No. LIT-12012477 Issued December 2017 Refer to the QuickLIT website for the most up-to-date version of

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Yokogawa DX Ethernet Driver Help Kepware Technologies

Yokogawa DX Ethernet Driver Help Kepware Technologies Yokogawa DX Ethernet Driver Help 2012 Kepware Technologies 2 Table of Contents Table of Contents 2 4 Overview 4 Device Setup 5 Communications Parameters 7 Optimizing Your Ethernet Communications 9 Data

More information

MicroTech II Vertical Self-Contained Unit Controller

MicroTech II Vertical Self-Contained Unit Controller Operation Manual OM 712 Group: Applied Systems Part Number: OM712 Date: February 2002 MicroTech II Vertical Self-Contained Unit Controller Space Comfort Control (SCC) Used with McQuay models: SWP, SWT

More information

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV CyCLO User Guide Version 2.00 19 th December 2017 REV 2.00 1 Contents 1. Hardware... 3 1.1. Introduction... 3 1.2. Electrical Specification... 3 1.3. Board Overview... 4 1.4. Electrical Installation...

More information

GeneSys Air-Cooled Screw Compressor Chiller

GeneSys Air-Cooled Screw Compressor Chiller Operation Manual OM AGSB-5 Group: Chiller Part Number: 331373201 Date: June 2005 Supersedes: OM AGSB-4 GeneSys Air-Cooled Screw Compressor Chiller AGS 230A/B through AGS 475A/B, 60 Hertz AGS 206A/B through

More information

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20 PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND OPERATION AND SERVICE MANUAL P/N 6006644, REVISION J JULY 018 PRESSURA ROOM PRESSURE CONTROLLER MODEL RPM10 AND OPERATION AND SERVICE MANUAL P/N 6006644,

More information

C5 controller Bacnet

C5 controller Bacnet Date: September 02, 2013 Vendor Name: Amalva UAB Product Name: C5 Firmware Revision: 1.000 BACnet Protocol Revision: 12 C5 controller Bacnet BACnet Protocol Implementation Conformance Statement Communication:

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

ComfortSense 7500 Commercial Thermostat. User Guide

ComfortSense 7500 Commercial Thermostat. User Guide ComfortSense 7500 Commercial Thermostat User Guide 507505-02 6/2018 Supersedes 5/2017 Table of Contents Features...2 Home Screen Temperature Indicator...2 Home Screen Information...3 Operating Mode Selection...5

More information

Control manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions

Control manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions KNCT2-808 KN Series Gas-fired direct vent Cast iron boilers Models KN-6, -10, -20 only (HeatNet control firmware edition 45 ) Control manual Control adjustment and Operation instructions Also read and

More information

Document Introduction Annex A - Protocol Implementation Conformance Statement (Normative) Product Description... 4

Document Introduction Annex A - Protocol Implementation Conformance Statement (Normative) Product Description... 4 NS Series Temperature and Humidity Network Zone and Discharge Air Sensors and NS Series Network Sensors with Fault Code Capability Protocol Implementation Conformance Statement Technical Bulletin Code

More information

Version 1.03 January-2002 USER S MANUAL

Version 1.03 January-2002 USER S MANUAL Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units... Application Note Issue Date 04/17/08 Supersedes 01/11/01 APPLICATION NOTE Using...3 Introduction... 3 Key Concepts... 4 UNT Controller Applications... 4 Fan Coil Units... 8 Unit Ventilators... 11 Rooftop

More information

Service Manual Models: 1.0, 1.3, and 1.5

Service Manual Models: 1.0, 1.3, and 1.5 AWX2-SER_100160837_2000000360_Rev F Service Manual Models: 1.0, 1.3, and 1.5 LOW LEAD CONTENT WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions,

More information

RBI H-NET V3 Control Firmware Revision Sheet

RBI H-NET V3 Control Firmware Revision Sheet RBI H-NET V3 Control Firmware Revision Sheet 9 Nov - 2018 Release Control Firmware Revision 3.13 1. Off Boiler Blower Running feature corrected for Ametek blowers 2. Added flow sensor temperature protection

More information

RBI H-NET V3 Control Firmware Revision Sheet

RBI H-NET V3 Control Firmware Revision Sheet RBI H-NET V3 Control Firmware Revision Sheet 19 - Oct - 2018 Release LCD Touch Display Firmware Revision 1.3-R5-1.3-R6 1. Added local flow rate (GPM) data to HeatNet Online messages. 2. Added support for

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20 PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND OPERATION AND SERVICE MANUAL P/N 6006644, REVISION A JULY 01 PRESSURA ROOM PRESSURE CONTROLLER MODEL RPM10 AND OPERATION AND SERVICE MANUAL P/N 6006644,

More information

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 140-1158 Building Technologies Table of Contents Overview... 5 BACnet 14 Hardware Inputs... 14 Room Unit Identification...

More information

V1.21: (Required for All Dryers with Static Sampler or Incoming MST Sensor, Good for All Dryers)

V1.21: (Required for All Dryers with Static Sampler or Incoming MST Sensor, Good for All Dryers) QuadraTouch Pro Software Update Change Log Official Release vs. Beta Release (How to tell): Tools -> System Tools -> System Information and look for Official Release or Beta Release in the bottom right

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER Table of Contents - 2 - INTRODUCTION... 3 OPERATING LIMITS:... 4 CONTROLLER FEATURES... 4 GENERAL DESCRIPTION... 5 CONTROL

More information

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/ Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/09 Table Of Contents Interconnecting the HART Communicator with the Detector.... 1 HART Device Description Language.... 3 Detector Wiring.......................................

More information