OPERATION AND MAINTENANCE MANUAL COMPACT VENTILATION UNIT WITH HEAT PUMP MCKT-HPX SERVICE

Size: px
Start display at page:

Download "OPERATION AND MAINTENANCE MANUAL COMPACT VENTILATION UNIT WITH HEAT PUMP MCKT-HPX SERVICE"

Transcription

1 GDYNIA COMPACT AHU MCKT-HPX /14 COMPACT VENTILATION UNIT WITH HEAT PUMP MCKT-HPX SERVICE Tel.: (+48 58) /51 Fax: (+48 58) Mobile: (+48) GDYNIA, October 2016

2 GDYNIA COMPACT AHU MCKT-HPX /14 TABLE OF CONTENT GENERAL INFORMATION TECHNICAL SPECIFICATION AND APPLICATION AHU CONSTRUCTION OPERATION PRINCIPLE THERMAL BALANCE OPERATION OF CROSS-FLOW EXCHANGER OPERATION OF THE HEAT PUMP DESCRIPTION OF THE COOLING DEVICE OPERATION OF COOLING DEVICE OPERATION OF THE HEAT PUMP AT LOW EXTERNAL TEMPERATURES CONTROL SYSTEM DIAGRAM OF THE CONTROL SYSTEM CONTROL OF STANDARD EQUIPMENT TURNING ON THE AHU DELAYED COOLING SYSTEM PROTECTION COOLING SYSTEM PROTECTION AIR PARAMETER ADJUSTMENT FILTER PRESSURE GAUGES DEFROSTING THE CROSS-FLOW EXCHANGER FAN OPERATION ADJUSTMENT SIGNALS CONTROL OF OPTIONAL EQUIPMENT DAMPERS PRELIMINARY HEATER COMMISSIONING SCOPE OF THE DELIVERY TRANSPORT AND STORAGE AHU ASSEMBLY SUSPENDING THE AHU DRAINING CONDENSATE ELECTRICAL CONNECTION FEATURED OPTIONAL EQUIPMENT NGS PRELIMINARY ELECTRICAL HEATER FIRST START-UP OPERATION AND MAINTENANCE FAULTY AHU OPERATION H&S PRECAUTIONS SERVICE INFO COMMISSIONING PROTOCOL... 14

3 GDYNIA COMPACT AHU MCKT-HPX /14 1. GENERAL INFORMATION The purpose of this OMM manual is to made the installers and users aware of the construction as well as correct operation and maintenance of the MCKT-HPX Air Handling Unit. Before the device installation as well as before launching and operating the device you should carefully read this OMM and strictly follow all instructions herein. Failing to observe the guidelines and recommendations contained in the operation and maintenance manual exempts the manufacturer from any warranty-related obligations. KLIMOR reserves the rights to implement design and material changes without prior notice, in relation to modernization and improvement of the product. The device is not subject to qualification by Commission Regulation No. 1253/ TECHNICAL SPECIFICATION AND APPLICATION Compact MCKT-HPX AHU is an air supply-exhaust unit designed for ventilation with heat recovery in any rooms such as: shops, restaurants, offices, production halls, residential buildings, houses, etc. The AHU is located inside the building. It is powered with electric energy. The heat pump enables to cool down the air in summer and heat it up in winter. AHU's operating position suspended. The unit is not designed to operate in environments with air temperature exceeding 45 C and relative humidity over 60% as well as in environments endangered by explosion of flammable gases and vapors containing organic solvents or other aggressive substances. 3 L Rozdzielnica RZS 2 H 3 2 W+200 W 1 MCKT-HPX 4 A 1 4 B Uchwyt zawiesia Okno inspekcyjne Picture no. 1 Compact MCKT-HPX AHU (main picture, top view) Arrangement possibilities for inlets and outlets of air streams 1 Inlet of external air 2 Outlet of supply air 3 Inlet of exhaust air 4 Discharge of extracted air

4 GDYNIA COMPACT AHU MCKT-HPX /14 Table no. 1 Technical parameters, part 1 MCKT HPX 1 MCKT HPX 2 MCKT HPX 3 Length L [mm] Width W [mm] Hight H [mm] Ventilation port A x B [mm] Connector size A x B [mm] Weight kg Air filters Type FS x350 G4 FS x450 G4 FS x500 G4 *For the unit equipped with the control system the W dimension is enlarged by 250mm. Table no. 2 Technical parameters, part 2 MCKT HPX 1 MCKT HPX 2 MCKT HPX 3 Range of airflow rate m 3 /h Heating 1 kw 7,3 8,4 14,4 16,8 21,0 25,4 Cooling 2 kw 5,5 6,9 10,0 11,7 15,0 17,6 Fan power output kw 2 0,5 2 0,5 2 1,1 Fan voltage Ph/V/Hz 1 230V/ V/ /50 Fan current A 2 2,2 2 2,2 2 2,3 Compressor power 1,5 1,6 3,0 3,2 4,3 4,9 kw consumption (winter) Compressor power 1,8 1,9 3,3 3,4 4,7 5,6 kw consumption (summer) Compressor voltage Ph/V/Hz 1x230V/ / /50 Max compressor current 3 A 14,0 10,4 15,8 Cooling medium R407C R407C R407C Amount of cooling medium kg 2,0 3,0 4 Sound power level for suction/pressing duct db(a) 55/60 63/68 62/67 71/76 69/75 76/81 Level of acoustic pressure at 1m 2 from the casing for A=15m db(a) For parameters: external temperature -5 C; φ=80%, room temperature 20 C; φ=40% 2- For parameters: external temperature 30 C; φ=45%, room temperature 24 C; φ=40% 3- Max nominal compressor engine current. Table no. 3 Dedicated optional equipment MCKT HPX 1 MCKT HPX 2 MCKT HPX 3 Size Max output Size Max output Size Max output Electrical heater NGE NGE-1 4.5kW NGE-2 9kW NGE-3 13,5kW Multi-surface damper A.DPR A.DPR A.DPR 560x500 Flexible connection FC FC FC 560x500 Detailed data are listed in the chapter related to the optional equipment. Chart no. 1 MCKT-HPX available pressure

5 GDYNIA COMPACT AHU MCKT-HPX /14 3. AHU CONSTRUCTION - The MCKT-HPX AHU's casing is made of framework casing made of anodized aluminum profiles and plastic corners, and galvanized steel sheet and non-flammable mineral wool which provides appropriate thermal and acoustic insulation. The casing panels are 50 mm thick. Inspection panels are equipped with handles and are mounted to the framework with oneand two-side clamps The AHU's framework is equipped with handles enabling suspension of the unit to ceiling with bars. Picture no. 2 Inspection panels AHU's side masking covers can be arranged in different ways, enabling 16 combinations of ventilation port arrangements. Picture no. 3 Side covers masking the ventilation ports - MCKT-HPX AHU internal equipment: two G4-class cartridge filters, plate cross-flow heat exchanger, two axialradial fans with direct drive and complete sets of heat pump: air-air with cooling system and two CuAl exchangers. The heat pump enables cooling of supply air in summer and heating it in winter. In the lower part of the inspection plate there are connections (hose connectors) for draining condensate water from the cross-flow heat exchanger and cooler outside the AHU. - The MCKT-HPX AHU is equipped with complete system of power supply and control system. The RZS box is attached to the AHU side wall. The AHU is directly controlled by the control panel. Information regarding operating the unit are attached. 4. OPERATION PRINCIPLE The MCKT-HPX AHU can operate only with the cross-flow exchanger or with the cross-flow exchanger and heat pump. The most beneficial external air temperate enabling the highest heat pump efficiency for cooling is above -5 C. In case of lower temperatures the control system switches off the cooling system and the unit operates in heat recovery mode only with the cross-flow exchanger. To ensure proper operation of the heat pump, in order to heat up air to required temperature, it is necessary to use preliminary NGE electrical heaters which heat up external air up to -5 C. 4.1 THERMAL BALANCE Compact MCKT-HPX AHU equipped with the cross-flow heat exchanger and heat pump forms a high-performance heat recovery system for a ventilated room. However ventilated rooms have to be source of heat in order to enable heat recovery. That is why at the stage of designing heating and ventilation system it is necessary to carry out the room's thermal balance a balance of profit and loss. Ventilated rooms should be equipped with independent heating provided by radiators, floor heating or other heating method, while the MCKT-HPX AHU should only take care of heating up the supply air.

6 GDYNIA COMPACT AHU MCKT-HPX / OPERATION OF CROSS-FLOW EXCHANGER Calculating heat amount to heat up the air is provided using the records below. Table no. 4 Sample operation spots at max air flow rate and min exchange efficiency while the heat pump is not operating. t1 [ o C] t2 [ o C] φ2 [%] η [%] Q [kw] Tlz [ o C] t12 [ o C] Designation t1 external air temperature t2 room air temperature φ2 - room air humidity η - t12 heat exchange efficiency air temperature after the exchange Q - thermal power recovered Tlz - freezing limit temperature t12 - air temperature after the exchange Temperature value downstream the cross-flow exchanger is determined using the diagram in picture no. 4 Przykład: temp. powietrza zewnętrznego t1 = -8 C temp. powietrza wewnętrznego t2 =+22 C przy zakładanej sprawności h=60%, temperatura powietrza po wymianie wynosi: t12 = h / 100 x (t2 - t1) + t1 t12 = +10 C Jak widać stosując HPX, powietrze po wymianie należy podgrzać o 12 C, podczas gdy bez wymiennika aż o 30 C. 20 C 10 C 0 C -10 C -20 C 30 C 20 C 10 C 0 C 30 C 20 C 10 C Dla sprawności wymiany η = 60%. Picture no. 4 Determining temperature at the cross-flow exchanger Characteristics of plate heat exchangers used in the MCKT-HPX AHU - The exchangers are characterized by high heat recovery efficiency at low investment costs. - The exchangers do not have any moving parts so they do not wear out and they are always ready to work. - Flowing air streams do not mix with each other and they do not carry over any contaminants. - The exchangers do not require electrical power supply. - The heat exchangers are lightweight, compact and are easy to assemble. - The exchangers are produced using the top level global standards. Problems with freezing condensate in the exchanger and countermeasures If warm air stream gets significantly cooled down, beside condensation freezing may also occur. In practice it does not happen so commonly several conditions must be met at the same time: - very low external air temperature - higher air flow of cool air than warm air - high efficiency of the exchanger - relatively low level of condensation - problems with draining out condensate - high humidity of extracted air If several of these conditions occur at the same time, the exchanger may start covering with frost, starting from the cold corner. Standard anti-freeze countermeasure for the exchanger in the MCKT-HPX AHU is temporary limiting flow of the air supply fan.

7 GDYNIA COMPACT AHU MCKT-HPX / OPERATION OF THE HEAT PUMP The heat pump, depending on needs, enables cooling down or heating up external air. Treated air has to be chemically inert, cannot contain caustic or explosive components as well as oily, viscous and fibrous slurries. The R407C Freon is used as the cooling medium. Correct operation of the cooling system requires sufficient amount and appropriate parameters of supplied air. The technical parameters table in the Air flow range line lists min air flow efficiency depending on the unit size. All data refer to summer period (cooling mode operation) and air extracted from a room at 24 C because these are the least favorable operating conditions. Setting lower air flow of the AHU will lead to turning off the cooling system by low or high pressure gauges Description of the cooling device The cooling sets are enclosed inside the AHU. The compressors are protected using high and low pressure gauges with automatic reset function. Triggering high pressure gauge requires reset to be carried out at the hand-held control unit. The cooling system is delivered together with the control system. It provides full protection during AHU operation, maintaining required air parameters and its maximizing output. In order to protect the compressor against flooding with the liquid medium, the system operates with removing by suction the medium vapor once turned off (the solenoid valve is closed before turning off the compressor). Removing the medium by suction is done at each system deactivation. Due to operation in heating and cooling modes at variable air parameters, the systems have got wide ranges of permissible operating pressure. Filling the system with Freon R407C should be carried out with the compressor operating, till the eyehole is filled with the medium Compressor 2. Low pressure gauges 3. High pressure gauges 4. Four-way valve 5. DX reservoir 6. DX fill-up valve 7. Filter dehydrator 8. Solenoid valve 9. Eyehole 10. Expansion valve 11. Check valve at the medium line 12. Solenoid valve to adjust performance 13. Valve to adjust performance Figure no. 5 Cooling system diagram Table no. 5 Range of manometric pressures for heat pump operation Min [MPa] Max [MPa] Pressure gauge setting Pabs [bar] Low pressure 0,2 0,65 4 High pressure 1,1 2, Operation of cooling device The cooling unit is an autonomous system fully controlled and supervised by control system. For that reason it does not require outside interference. All works should be done by personnel having appropriate certificated qualifications. However the personnel can reduce potential failures by following the unit s operation carefully. NOTE! The compressor requires appropriate operating parameters of the cooling oil. That is why before the first start and after each longer downtime of the whole AHU (when the switchboard is not energized) it is necessary to turn on the switchboard and do not enable to start the cooling system. It will initiate starting the compressor casing heater and heating up the oil. Appropriate time to ensure correct oil parameters is 8h. The basic parameter that should be taken into account is the amount and parameters of air flowing through the cooling system exchangers. The flow adjustment should ensure min air amount listed in the table no. 2 with MCKT-HPX AHU parameters. The condition of air filters should be monitored. Contamination of air filters causes considerable drops in airflow rate.

8 GDYNIA COMPACT AHU MCKT-HPX /14 Monitoring the cooling system may be limited to checking pressure ranges when the system is in operation. The user has to carry out a visual inspection of the cooling system condition. Oily spots on the pipeline can indicate leakage of the medium from the system. They should be wiped dry. If oil appear in the same spots, there is a leakage. NOTE! Visual inspection of the cooling system should be carried out when the compressor and fans are turned off. Temperature of the pipeline directly downstream the compressor during operation can exceed 100 C. Pay particular attention while inspecting the cooling system Operation of the heat pump at low external temperatures At low temperatures of external air there is a drop of the heat pump efficiency. In order to prevent such situation it is recommended to use the preliminary heater with output dependent on the air flow and estimated temperature of external air. The preliminary heater ensures heating up the external air to the level enabling efficient operation of the heat pump. Depending on parameter relations between air supply and air exhaust streams, such as temperature, humidity, volume, the critical point temperature usually is about: -5 C. The heater output should be calculated for the most extreme operating conditions. For preliminary heating up the supply air you can use the NGE electrical heater. The heaters are optional equipment of the MCKT-HPX AHU. 5. CONTROL SYSTEM Detailed description of the MCKT-HPX AHU's control system is provided in a separate attachment to the OMM ( User s manual of the suspended MCKT-HPX AHU s automatic system controller ). 5.1 DIAGRAM OF THE CONTROL SYSTEM Picture no. 6 Diagram of the control system for the MCKT-HPX

9 GDYNIA COMPACT AHU MCKT-HPX / CONTROL OF STANDARD EQUIPMENT Turning on the AHU Turning on the system from the control panel. Common start of fans 20s after turning on the system. 30 seconds after starting the fans permit to start the cooling system. Once the system is turned off the fans keep operating for 30 seconds Delayed cooling system protection Once the compressor (3) is turned off, it can be turned on again only after 180 seconds Cooling system protection The cooling system is equipped with low pressure (4) and high pressure gauges with automatic reset function. If any of the pressure gauges is triggered, the cooling system is stopped. If the high pressure gauge (5) is activated 3 times within an hour, the cooling system is blocked and requires restarting from the control panel Air parameter adjustment Room temperature adjustment is carried out based on the air exhaust temperature sensor (11). The air supply sensor (10) enables reduction of min/max air supply temperature. Max air supply temperature at C. Min air supply temperature at 5 24 C. Min allowable difference between max and min air supply temperature is 16K Filter pressure gauges Filters of pressure gauges indicate filter contamination with a summary signal Defrosting the cross-flow exchanger If the sensor (12) detects temperature 0 C, the air supply fan reduces its output to 20% for 120 seconds Fan operation adjustment signals Fan operation adjustment signals are independent for air supply and air exhaust. Fans controlled with signal (13 and 8) 0-100% output. Fan start from the signal (9 and 14). The cooling system can operate for the control range of %. Below this setting at the air supply or exhaust operation of the heat pump is not allowed. 5.3 CONTROL OF OPTIONAL EQUIPMENT Dampers Both dampers (20 and 21) 24V AC/DC-powered open when the AHU is started. The air supply damper with a spring, the air exhaust damper without a spring Preliminary heater The preliminary heater (optionally, water or electrical one) ensures initial air heating to enable operation of the heat pump at external temperature below -5 C. The temperature measured at the temperature sensor (1) set from the panel in the 5 C 10 C range. Electrical heater Power supply and control with a separate module controlled by signal (18) from the main switchboard. The heater protection (19), once temperature exceeds 90 C, turning off the heater, while other AHU devices are operating.

10 GDYNIA COMPACT AHU MCKT-HPX /14 6. COMMISSIONING Compact MCKT-HPX AHU in fully assembled condition are subject to the manufacturer's quality control commissioning, which guarantees meeting quality requirements and parameters defined in the unit's data sheet. 7. SCOPE OF THE DELIVERY The delivery includes, standard equipment: - Compact MCKT-HPX AHU, fully assembled with enclosed control system. - The remote control panel and duct sensors supplied in a separate package (a shielded control cable, 4x0,5mm 2 is not provided) - Operation and Maintenance Manual (OMM) - The system control documentation ("User s manual of the suspended MCKT-HPX AHU s automatic system controller"). Additional equipment (on individual request): - Air damper and flexible connectors - NGE electrical heater 8. TRANSPORT AND STORAGE The MCKT-HPX AHU is delivered fully assembled to the final place of operation. Loading onto/unloading from a means of transport to a warehouse can be carried out manually or with a lift. The units should be stored in enclosed, roofed places. The AHU should be stored, transported and operated in horizontal position with the inspection panels facing downward. 9. AHU ASSEMBLY 9.1 SUSPENDING THE AHU The compact MCKT-HPX AHU should be installed in rooms which do not contain any airborne chemical contaminants reacting with non-ferrous metals. The AHU can be suspended using four side holder located at both sides of the casing. A M8 threaded bar is inserted into the lower part of the holder and a nut with a washer is screwed on. Next, the bar is inserted into the groove of the upper part of the holder, and at the same time they are joined together by pushing a lower element into an element at the bottom. Usage of M8 threaded bars enables easy and quick suspension and leveling of the unit. The M8 threaded bars are not supplied. The minimum retained distance of the upper surface of the unit to the partition should be min. 20mm. The AHU should be leveled and the final assembly should enable inclining the unit towards the air flow at 1 (about 1,5 2%). Picture no. 7 Optimal inclination of the AHU The unit should be assembled and connected using cables to ensure appropriate air flow. The air system should be connected using flexible connectors.

11 GDYNIA COMPACT AHU MCKT-HPX / DRAINING CONDENSATE The condensate should be drained from both trays using flexible hoses with drain traps, see picture no O króćca 13mm Picture no. 8 Drain traps NOTE! Estimated amount of condensate depending on air parameters: - up to 3 l/h for the MCKT-HPX1, - up to 6 l/h for the MCKT-HPX2, - up to 10 l/h for the MCKT-HPX3. Incorrect condensate drainage can lead to: - Flooding fan sections of the MCKT-HPX and damaging fan motors and electronic modules installed in these sections, - Flooding air ducts and in result rooms which are air-conditioned and the room where the AHU is installed. 9.3 ELECTRICAL CONNECTION Provide the power supply to the control system box of the MCKT-HPX AHU. If an additional electrical heater is used, make sure to provide a separate power supply to the heater control module and in case of the water heater connect an additional temperate sensor and power supply for the three-way valve and circulating pump. Connect the control panel to the control box with a shielded cable 4x0.5mm 2 (max cable length 25m). Other electrical elements should be installed in line with guidelines of the "User s manual of the suspended MCKT- HPX AHU s automatic system controller". While connecting electrical devices and components it is necessary to strictly follow the H&S requirements stated in appropriate standards and regulations related to the installation and operation of electrical devices. 10. FEATURED OPTIONAL EQUIPMENT Size 10.1 NGE PRELIMINARY ELECTRICAL HEATER Table no. 7 Family of the NGE preliminary electrical heaters for use with the MCKT-HPX AHU Max output MCKT HPX 1 MCKT HPX 2 MCKT HPX 3 No. of stages Current Power supply Size Max output No. of stages Current Power supply Size Max output No. of stages Current kw - A V/Hz kw - A V/Hz kw - A V/Hz Power supply NGE-1 4,5 1 19,6A 1 230/50 NGE-2 9, , /50 NGE-3 13,5 3 19, /50 NGE-1 NGE-2 NGE T T PE 1x230V T T PE T T PE 3x400V 3x400V Picture no. 9 NGE heater diagram

12 GDYNIA COMPACT AHU MCKT-HPX / FIRST START-UP The AHU start-up can be carried out only by authorized personnel with sufficient knowledge and experience in this particular ventilation or air conditioning system. Once the installation process and all connections (electrical, ducts and controls) are complete: - Check if the electrical connections are correct - Check tightness of air duct connectors - Check if all other additional devices working with MCKT-HPX AHU are connected in a correct way. If no connection faults are found you can proceed with the AHU start-up procedure. The unit is started via the control panel. The description in provided in the attachment related to the control. - Turn on the AHU - Adjust and preset appropriate air flow of the fans - Adjust the temperatures. The first start-up of the unit requires filling in the commissioning protocol. Fill instalation of the R407C up to fill the viewport when the compressor is working Setting of pressure switch low pressure P = 2,5 bar g Setting of pressure switch high pressure P = 27 bar g 12. OPERATION AND MAINTENANCE Compact MCKT-HPX AHU is designed for continuous operation. In order to keep the AHU in continuous operation it is necessary to carry out the following inspections every 3 months: - Check the MCKT-HPX anticorrosive protection - Check condition of filters and exchangers - Check condition of cables - Check condition of fans (they should operate without excessive noise and vibration) - Check tightness of the cooling system. 13. FAULTY AHU OPERATION Table no. 8 Remedy actions in case of faulty AHU operation Symptoms Cause Remedy action Fans do not start No voltage in the system The protection is disconnected Check the electrical system Check the fuses Fans generate vibrations of AHU Contaminated fans' rotors Clean fans' rotors The compressor does not turn on Activated HP* pressure gauge Check condition of the filters Air flow is too small increase Reset the HP alarm high condensing pressure at the control system panel Incorrect temperature settings Change the temperature settings The compressor turns on and off Faulty compressors Activated LP** pressure gauge External air temperature is too low Not enough cooling medium Contact the service personnel Check condition of the filters Air flow is too small increase Change the Tz*** sensor setting Eliminate leakages, fill up the R407C The solenoid valve is faulty Check the valve's coil Cooling instead of heating The 4-way valve is faulty Check the valve's coil * Activation of HP pressure gauge is an alarm condition. The alarm has to be reset at the control panel. * Activation of LP pressure gauge is not an fault condition. It will be restarted automatically. In both cases the compressor will be activated at least 3 minutes after the stop. *** It is recommended to use the preliminary NGE electrical heater to heat up air at min -5 C.

13 GDYNIA COMPACT AHU MCKT-HPX / H&S PRECAUTIONS The compact MCKT-HPX AHU is not dangerous for personnel provided the basic operational Health & Safety precautions are observed. Specific requirements which must be obeyed: - Installation and first start-up of the units shall be done in conditions provided for in applicable regulations, and in particular in regulations concerning operation of electric appliances. - Connecting the unit to a protective installation shall be a condition for switching on the power supply. - Power supply shall be switched off prior to repair and maintenance operations. - Operation of the unit without any of the inspection panels is not allowed. - Servicing, repair and maintenance of the units may be done only by personnel having appropriate qualifications confirmed by a relevant certificate provided for by a competent ministry in a regulation concerning qualifications of personnel employed to maintain power appliances. - Protective equipment ensuring safe maintenance should be available at the maintenance post. 15. SERVICE INFO Please contact our Service department in order to learn more about operating the unit: Fax: (+48 58) Tel.: (+48 58) /51 Mobile: serwis@klimor.pl

14 GDYNIA COMPACT AHU MCKT-HPX / COMMISSIONING PROTOCOL Date Place Name and surname of the commissioner Device serial number Commissioning company (stamp) Installation actions (description) Remarks User approval of the provided actions Signature Date

HEATING AND COOLING DEVICE AGC

HEATING AND COOLING DEVICE AGC GDYNIA HEATING AND COOLING DEVICE - AGC 2013 1/8 HEATING AND COOLING DEVICE AGC SERVICE phone.: (+48 58) 783 99 50/51 Fax: (+48 58) 783 98 88 mobile: (+48) 510 098 081 E-mail: serwis@klimor.pl GDYNIA,

More information

Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans. Topvex SoftCooler TR. Specification data

Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans. Topvex SoftCooler TR. Specification data Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Topvex SoftCooler TR Specification data 2 Topvex SoftCooler TR Comfort cooling, ready from factory

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

VERSO Air Handling Units

VERSO Air Handling Units Energy efficient solutions for profitable indoor climate VERSO-S air supply units VERSO-R air handling units equipped with regeneration system VERSO-P air handling units equipped with recuperation system

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

VERSO Air Handling Units

VERSO Air Handling Units VERSO Air Handling Units Energy efficient solutions for profitable indoor climate VERSO Air Handling Units VERSO-S air supply units VERSO-R air handling units equipped with regeneration system VERSO-P

More information

recooler HP EQKR HEAT PUMP

recooler HP EQKR HEAT PUMP AIR COMFORT AIR TREATMENT 9566 GB 2016.03.17 recooler HP EQKR HEAT PUMP» TECHNICAL CATALOGUE 2 ReCooler HP EQKR Technical Catalogue Content ReCOOLER HP EQKR HEAT PUMP 3 product presentation. 3 applications.

More information

AHU Plus. DX Air Handling Units

AHU Plus. DX Air Handling Units AHU Plus DX Air Handling Units AHU Plus DX DX Air Handling Units AHUPlusDX-TH: DX Air Hadling Unit with 100% Fresh Air AHUPlusDX -IGK: DX Air Hadling Unit with 100% Fresh Air and Heat Recovery AHUPlusDX-KH:

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Air curtain SMART

INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Air curtain SMART INSTALLATION, OPERATION AND MAINTENANCE MANUAL Air curtain SMART Read instructions carefully before attempting installation. Deliver this manual to end user. SECURITY ADVISE SYMBOLS Attention, Danger,

More information

Mobile Air-Con Service Solution. AC7000 Operation Manual

Mobile Air-Con Service Solution. AC7000 Operation Manual Mobile Air-Con Service Solution AC7000 Operation Manual Cool-It Mobile HVAC Group Contents 1 About this operation manual.......................................... 2 1.1 Cool-It Hotline......................................................

More information

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort Application guide FLATAIR - FLCK/FLHK Providing indoor climate comfort MSL60E-0701 12-2006 Congratulations you have made a wise choice and we feel sure that it will meet your expectation INDEX CONTENTS

More information

USER MANUAL. Frigate HRV 120 SR Frigate ERV 120 SR. Heat (energy) recovery ventilation unit

USER MANUAL. Frigate HRV 120 SR Frigate ERV 120 SR. Heat (energy) recovery ventilation unit USER MANUAL Frigate HRV 120 SR Frigate ERV 120 SR Heat (energy) recovery ventilation unit 2 CONTENTS Safety requirements... 3 Introduction... 5 Use... 5 Included in the box... 5 Designation key... 5 Technical

More information

panel filters with filtering class G4. Supply filter F7 can be supplied with the few models.

panel filters with filtering class G4. Supply filter F7 can be supplied with the few models. AIR HANDLING UNITS WITH HEAT RECOVERY Series Series VUT 350 PE EC VUT 600 PE EC VUT 1000 PE EC VUT 2000 PE EC VUT 3000 PE EC VUT 600 PW EC VUT 1000 PW EC VUT 2000 PW EC VUT 3000 PW EC Ceiling mounted air

More information

Technical documentation: S1 S2 S3 S4

Technical documentation: S1 S2 S3 S4 Technical documentation: S1 S2 S3 S4 1 Table of contents: 2 1. Introduction 3 1.1 Precautions 3 1.2 Transport 3 1.3 Package content 4 1.4 Use and principle of operation 4 2. Schematic diagram 4 2.1 Construction

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

Air Comfort. Installation instructions (English) A

Air Comfort. Installation instructions (English) A Air Comfort Installation instructions (English) WWW.BRINKAIRFORLIFE.NL 614788-A This appliance may be used by children as of 8 years of age, persons of reduced mental or physical capacities and those of

More information

Operating Instructions

Operating Instructions Operating Instructions TEKA Cartmaster Type PF-W 1, PF-W 2 TEKA Absaug- und Entsorgungstechnologie GmbH Industriestraße 13 D-46342 Velen Postfach 1137 D-46334 Velen Tel.: +49 (0) 2863 9282-0 Fax: +49 (0)

More information

Refrigerant R407C CW-AR. 2.4 to 3.1kW. Water Source Heat Pumps - Vertical Mounting Version Models 07 to to 2.7kW

Refrigerant R407C CW-AR. 2.4 to 3.1kW. Water Source Heat Pumps - Vertical Mounting Version Models 07 to to 2.7kW Refrigerant R407C CW-AR Water Source Heat Pumps - Vertical Mounting Version Models 07 to 12 2.4 to 3.1kW 1.9 to 2.7kW Some advantages... RAL 9010 painted cabinet 3-fan speeds G2 filter is supplied as

More information

Contour TM Screw Compressors

Contour TM Screw Compressors Contour TM Screw Compressors Semi-Hermetic Compact Operating Instruction SCH1 High Temp Compressors Form No. 99-77 1. Introduction This series of semi-hermetic compact screw compressors is designed for

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION VALLOX-product code: HVAC code: 358500 L 35850 R 79076 L 79077 R SOUND ATTENUATOR (OPTIONAL) IVALLOX 252 WATER OPERATED POST- HEATING UNIT (OPTIONAL) ELECTRICAL POST-HEATING UNIT (OPTIONAL) ELECTRICAL

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

ELECTRIC BOILERS FOR CENTRAL HEATING

ELECTRIC BOILERS FOR CENTRAL HEATING ELECTRIC BOILERS FOR CENTRAL HEATING TermoMax INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS FOR INSTALLATION We reserve the right of alternations WE ARE NOT LIABLE FOR DAMAGES RESULTING FROM NON- OBSERVING

More information

MECHANICAL INTEGRITY INSPECTIONS OF AIR COOLERS

MECHANICAL INTEGRITY INSPECTIONS OF AIR COOLERS By Joe Fazzari, P.E, Vice President of Colmac Coil Manufacturing, Inc. MECHANICAL INTEGRITY INSPECTIONS OF AIR COOLERS Owners should perform periodic mechanical integrity inspections on air coolers to

More information

Decentralised ventilation units

Decentralised ventilation units Notes on installation Decentralised ventilation units FSL / SCHOOLAIR GB/en TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany Phone: +49 (0) 2845 2020 Fax: +49 (0) 2845 202265 E-mail: trox@trox.de

More information

Service Manual & Installation Manual

Service Manual & Installation Manual GE Consumer & Industrial Appliances Service Manual & Installation Manual Split System Air Conditioner Model numbers: GE AIR C18 GE AIR C24 GE AIR C34 GE AIR C41 1 Introduction and Features Model Remarks

More information

Vacuum System Troubleshooting Author: Keith Webb, P.E. Application Engineering Manager

Vacuum System Troubleshooting Author: Keith Webb, P.E. Application Engineering Manager INTRODUCTION The science of creating vacuum is often misunderstood and when the desired vacuum condition is not being achieved in a manufacturing setting this usually means production comes to a halt and

More information

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S USER S MANUAL Heat (Energy) Recovery Ventilator Vents Frigate HRV 120 S Vents Frigate ERV 120 S 2 Frigate HRV(ERV) 120 S CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key...

More information

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points Epsilon Echos+ 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Configuration /LN: Low noise unit /HP: Reversible heat pump /LE /HP: Reversible condensing unit Unique

More information

CPF PRODUCT DESCRIPTION

CPF PRODUCT DESCRIPTION CPF 175 340 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPF 175-340 compressor is a quiet, complete and ready-for-use unit for the production of compressed air in industrial applications. OVERVIEW The CHICAGO

More information

panel filters with filtering class G4. Supply filter F7 can be supplied with the few models.

panel filters with filtering class G4. Supply filter F7 can be supplied with the few models. AIR HANDLING UNITS WITH HEAT RECOVERY Series Series VUT 350 PE EC VUT 600 PE EC VUT 1000 PE EC VUT 2000 PE EC VUT 3000 PE EC VUT 600 PW EC VUT 1000 PW EC VUT 2000 PW EC VUT 3000 PW EC Ceiling mounted air

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

CPC PRODUCT DESCRIPTION

CPC PRODUCT DESCRIPTION CPC 40 60 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPC 40-60 compressor is a quiet, complete and readyfor-use unit for the production of compressed air in industrial applications. OVERVIEW The CHICAGO

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 1402 C O K AIR R-407C Series RAE... C K Cooling capacity from 81 to 250 kw - 2 circuits The air cooled chillers of RAE C K series, with centrifugal fans, are designed for indoor installation and are

More information

SUSPENDED AIR HANDLING UNIT WITH ROTARY HEAT EXCHANGER

SUSPENDED AIR HANDLING UNIT WITH ROTARY HEAT EXCHANGER SUSPENDED AIR HANDLING UNIT WITH ROTARY HEAT EXCHANGER Energy Recovery Ventilation Specialist Beijing Holtop Artificial Environment Technology Co., Ltd ISO 9001: 2000 Approved Company COMPANY BRIEF INTRODUCTION

More information

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300 USER S MANUAL Heat Recovery Ventilator Vents Brig HRV 200 Vents Brig HRV 300 2 Brig HRV 200 (300) CONTENT Introduction... 3 Application... 3 Delivery set... 3 Unit designation key... 4 Basic unit dimensions...

More information

SELF-PRIMING JET PUMPS

SELF-PRIMING JET PUMPS SS Anti-Rust SS Shaft Copper & Cold-rolled SELF-PRIMING JET PUMPS CONTENTS 1. Applications.... Model Description.... Technical Data... 4. Implementation Standards... 5. Safety Precautions... 6. Product

More information

Installation instruction

Installation instruction Installation instruction CTS 600 by Nilan VP 18 10P Version: 5.03, 15-04-2011 Contents Contents... 2 List of figures... 2 Before starting... 3 Electrical connection... 4 VP 18-10P installation... 5 Condensation

More information

DX AIR CURTAIN. SensAir

DX AIR CURTAIN. SensAir DX AIR CURTAIN SensAir Biddle and Daikin Complete climate system Since 2006 Biddle and Daikin have joined forces to provide a complete climate system for shops and public buildings. By combining Biddle

More information

Installer manual AG-WL10

Installer manual AG-WL10 LEK LED CLEAN TIMER OPERATION Installer manual Indoor unit air/air heat pump IHB GB 1637-1 331827 Table of Contents 1 Important information Safety information Read before starting the installation Electrical

More information

Instructions manual DEHUMID HP50

Instructions manual DEHUMID HP50 Instructions manual DEHUMID HP50 Table of contents 1. Unpacking 3 2. Intended use 3 3. Disposal 3 4. Safety instructions 3 5. Functional principle 4 6. Automatic defrosting system 4 7. Set up and transportation

More information

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01 b cool manufacturers of air-conditioning equipment ltd BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION Ver. 1.01 Ver. 3.02 01_18 BCool# 1 brt c/h r407c / r410a

More information

HEAT RECOVERY AND HEAT AND HUMIDITY RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AND HEAT AND HUMIDITY RECOVERY AIR HANDLING UNIT HEAT RECOVERY AND HEAT AND HUMIDITY RECOVERY AIR HANDLING UNIT S S11 Series SB S11 Series SB -E S11 Series SB -E S11 Series EN OPERATION MANUAL CONTENTS Safety requirements... 2 Purpose... 4 Delivery set...

More information

All alerts are still logged as alarms and also show up in the current alarm list.

All alerts are still logged as alarms and also show up in the current alarm list. Alarm Descriptions This document describes all possible alarm types as listed in the alarm log for software version 5.5.0 and later. x indicates compressor circuit for compressor related alarms. Alarms

More information

Series VENTS MPA...W. Supply units with the air capacity up to 6500 m 3 /h in the compact sound- and heat-insulated casing with water heater

Series VENTS MPA...W. Supply units with the air capacity up to 6500 m 3 /h in the compact sound- and heat-insulated casing with water heater SUPPLY UNITS Series Series LCD control panel SAS908 control panel Supply units with the air capacity up to 3500 m 3 /h in the compact sound- and heat-insulated casing with electric heater Supply units

More information

Air handling unit. BlauAir RH USER S MANUAL

Air handling unit. BlauAir RH USER S MANUAL Air handling unit EN USER S MANUAL CONTENTS Safety requirements... 2 Purpose... 4 Delivery set... 4 Designation key... 4 Technical data... 5 Unit design and operation logic... 7 Installation and set-up...

More information

VACUUM EXTRACTOR MODEL NO: CWVE1 OPERATING & MAINTENANCE INSTRUCTIONS PART NO: GC0916

VACUUM EXTRACTOR MODEL NO: CWVE1 OPERATING & MAINTENANCE INSTRUCTIONS PART NO: GC0916 VACUUM EXTRACTOR MODEL NO: CWVE1 PART NO: 6471168 OPERATING & MAINTENANCE INSTRUCTIONS GC0916 INTRODUCTION Thank you for purchasing this CLARKE Workshop Vacuum Extractor. Before attempting to use this

More information

Hi-Pres. Self Contained A/C Unit HI-PRES MARINE & OFFSHORE

Hi-Pres. Self Contained A/C Unit HI-PRES MARINE & OFFSHORE Hi-Pres Self Contained A/C Unit TYPE SCU-C & SCU-W Product specifications HI-PRES MARINE & OFFSHORE Contents Introduction..................... 2 Type SCU-W.......................... 2 Type SCU-C...........................

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 201 C K RAE 482 C K AIR R-407C Series RAE... C K from 19 to 83 kw - 1 and 2 circuits The air cooled chillers of RAE... C K series, with centrifugal fans, are designed for indoor installation and are

More information

DUNHAM-BUSH. Request for start-up and commissioning of Dunham-Bush chillers (Water Cooled or Air Cooled) and Condensing Units.

DUNHAM-BUSH. Request for start-up and commissioning of Dunham-Bush chillers (Water Cooled or Air Cooled) and Condensing Units. DUNHAM-BUSH Request for start-up and commissioning of Dunham-Bush chillers (Water Cooled or Air Cooled) and Condensing Units. Job Name Unit Model Address & Location Unit Serial Number of Units Kindly complete,

More information

Series VUT PW EC. wool internal heat and sound-insulating layer for VUT PE/PW 350, 600, 1000 units and 50 mm for VUT PE/PW 200, 3000 units.

Series VUT PW EC. wool internal heat and sound-insulating layer for VUT PE/PW 350, 600, 1000 units and 50 mm for VUT PE/PW 200, 3000 units. AIR HANDLING UNITS WITH HEAT RECOVERY Series VUT PE EC Series SAS908 control panel SAS908 control panel Ceiling mounted energy saving Air Handling Units (AHU) with the air capacity up to 4000 m 3 /h and

More information

AIR HANDLING UNITS MANDÍK

AIR HANDLING UNITS MANDÍK AIR HANDLING UNITS MANDÍK 2 CONTENTS MANDÍK, a. s. The Company... 3 Photo Gallery... 4 Unit Description... 6 Air handling unit parameters according to Eurovent... 7 Product Range of the Air Handling Units...

More information

Installation and Operating Manual

Installation and Operating Manual Installation and Operating Manual SR868C6 System Regulator for Solar Thermal Systems Display Panel Illustration Pos. Button on display panel Button description 1 Green lamp Power indication lamp 2 On/Off

More information

INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS

INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS INSTALLATION OPERATION & MAINTENANCE INSTRUCTION HEAT RECOVERY UNITS VHR MODELS TSEK VENCO Havalandırma ve Makina San.ve Tic. A.Ş. 2004. Cad. No:5 45400 OSB Turgutlu MANISA / TURKİYE Tel: +90 (236) 332

More information

TTV 1500 / TTV 3000 OPERATING MANUAL CONVEYING FAN TRT-BA-TTV TC EN

TTV 1500 / TTV 3000 OPERATING MANUAL CONVEYING FAN TRT-BA-TTV TC EN TTV 1500 / TTV 3000 EN OPERATING MANUAL CONVEYING FAN TRT-BA-TTV1500-3000-TC2016-26-004-EN Table of contents Notes regarding the operating manual... 2 You can download the current version of the operating

More information

Local Air Conditioner

Local Air Conditioner Local Air Conditioner Thank you for selecting this air-conditioner. Please keep this User s Manual for future reference. Read the User s Manual carefully before operating this unit. IMPORTANT SAFEGUARDS

More information

VEX100 series Air handling units with cross-flow heat exchanger

VEX100 series Air handling units with cross-flow heat exchanger Product information - Version 6 VEX100 series Air handling units with cross-flow heat exchanger VEX140: 400-2200 m 3 /h VEX150: 700-3600 m 3 /h VEX160: 1100-5000 m 3 /h VEX170: 1400-8400 m 3 /h Contents

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC AQB8J6WC_IM_E_25864 2006.4.4 3:29 PM Page 7 INSTALLATION MANUAL Indoor Unit AQB8J6WC AQB24J2WC Outdoor Unit UQB8J6WC UQB24J2WC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

ErP OPERATIONS MANUAL FOR СOMMERCIAL CURTAINS PROTON HEAT DOOR C2. Safety precautions Construction and dimensions Technical parameters Installation

ErP OPERATIONS MANUAL FOR СOMMERCIAL CURTAINS PROTON HEAT DOOR C2. Safety precautions Construction and dimensions Technical parameters Installation OPERATIONS MANUAL FOR СOMMERCIAL CURTAINS PROTON HEAT DOOR C 0506 ErP 05 Water heating Electric heating Without heating Safety precautions Construction and dimensions Technical parameters Installation

More information

Series. Suspended air supply units with the air capacity up to 4100 m 3 /h in the sound- and heat-insulated casing with the water heater

Series. Suspended air supply units with the air capacity up to 4100 m 3 /h in the sound- and heat-insulated casing with the water heater SUPPLY UNITS Series VENTS PA E Series VENTS PA W A13 control panel A13 control panel Suspended air supply units with the air capacity up to 3350 m 3 /h in the sound- and heat-insulated casing with the

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

FUTURE AIR SOLUTIONS OIL FREE SCROLL COMPRESSORS

FUTURE AIR SOLUTIONS OIL FREE SCROLL COMPRESSORS FUTURE AIR SOLUTIONS OIL FREE SCROLL COMPRESSORS The Most Advanced Technologies for High-Quality air High-precision processing technology is required to produce the components that make up a Scroll Compressor.

More information

The ultimate in air handling units: directly and indirectly fired

The ultimate in air handling units: directly and indirectly fired AHU The ultimate in air handling units: directly and indirectly fired Mark has developed a range of air handling units with several options for a wide variety of applications. From a simple air intake

More information

ECO85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

ECO85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL ECO85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www.eipl.co.uk Page 1 of 12 INTRODUCTION Designed for a wide range of applications, the ECO85 dehumidifier is a rugged, industrial unit which utilizes an energy-efficient

More information

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100 HTD High Temperature Non-Cycling Refrigerated Compressed Air Dryers Operation & Maintenance Manual MODELS HTD 21 thru HTD 100 - TABLE OF CONTENTS - 1.0 GENERAL 2 1.1 How to use this manual 1.2 Symbols

More information

VUT 350 H VUT 500 H VUT 530 H VUT 600 H VUT 1000 H VUT 2000 H HEAT RECOVERY AIR HANDLING UNIT

VUT 350 H VUT 500 H VUT 530 H VUT 600 H VUT 1000 H VUT 2000 H HEAT RECOVERY AIR HANDLING UNIT РУКОВОДСТВО USER S MANUAL ПОльзователя VUT 350 H VUT 500 H VUT 530 H VUT 600 H VUT 1000 H VUT 2000 H HEAT RECOVERY AIR HANDLING UNIT 2 CONTENTS Safety requirements 3 Introduction 5 Use 5 Delivery set 5

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL INSTALLATION, OPERATION AND MAINTENANCE MANUAL Air curtains ROTOWIND, INVISAIR Please, read these instructions carefully before attempting installation SECURITY ADVISE SYMBOLS Attention, Danger, Safety

More information

Refrigerator KE T

Refrigerator KE T Refrigerator KE 680-1-3T Service Manual: H8-74-07 Responsible: U. Laarmann KÜPPERSBUSCH HAUSGERÄTE AG E-mail: uwe.laarmann@kueppersbusch.de Tel.: (0209) 401-732 Customer Service Fax: (0209) 401-743 Postfach

More information

Heat pump & cooling unit in one

Heat pump & cooling unit in one + + Heat pump & cooling unit in one The reversible ThermoCooler HP heat pump can be integrated in our Envistar Flex units. All parts of the cooling/heating pump are incorporated in a module section, which

More information

HRV-IP. Ceiling Type Heat Pump Heat Recovery Unit

HRV-IP. Ceiling Type Heat Pump Heat Recovery Unit HRV-IP Ceiling Type Heat Pump Heat Recovery Unit HRV-IP Ceiling Type Heat Pump Heat Recovery Unit Ceiling type heat pump heat recovery units are energy saving devices thanks to plate type heat exchanger

More information

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL WM150 OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the WM150 is a rugged, industrial unit, which utilizes an

More information

KOMFORT EC DB Suspended heat recovery air handling units

KOMFORT EC DB Suspended heat recovery air handling units 2018 AIR HANDLING UNITS KOMFORT EC DB Suspended heat recovery air handling units Features Air handling units for efficient supply and exhaust ventilation in flats, houses, cottages and other buildings.

More information

Portable Air Conditioner, Dehumidifier,Heater and Fan utilizing Heat Pump Technology

Portable Air Conditioner, Dehumidifier,Heater and Fan utilizing Heat Pump Technology Portable Air Conditioner, Dehumidifier,Heater and Fan utilizing Heat Pump Technology OWNER'S MANUAL Model # KY-34 3046364 Please read owner s manual carefully before operating unit. TABLE OF CONTENTS INTRODUCTION...3

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

Supply air unit VEKA Installation & Maintenance

Supply air unit VEKA Installation & Maintenance November 2008 Safety instructions Operating the air treatment unit and accessory components WARNING Before the air treatment unit is taken into service, any free connections must be provided with protective

More information

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A... 70 80 99-00-O Residential Gas Condensing Boiler ZBR//8/35/4-3A... ZWB8/35/4-3A... 70 80 993 (03/03) CA/US Operating Instructions Contents Contents Key to symbols and safety instructions............................

More information

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4 Installation Operation Maintenance Ductable water unit FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RFEC/U/2017-1 (EN) (valid since 18.08.2017) ROOF FANS RF/EC...-... / RFV/EC...-... Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the

More information

Fresh air unit ALB. ALB it s simple and so easy! Air supplied through a heater and filter in a single unit.

Fresh air unit ALB. ALB it s simple and so easy! Air supplied through a heater and filter in a single unit. Fresh air unit ALB ALB it s simple and so easy! Air supplied through a heater and filter in a single unit. The ALB fresh air units from Helios provide comfortable room temperatures. Fresh outside air is

More information

TopMaster Air Handling unit. Technical data

TopMaster Air Handling unit. Technical data Technical data Contents Page Description of the unit... 3 Design... 4 Technical data Size 030... 5 Size 0... 6 Accessories... 7 Controls... 9 Control functions... 10 Order codes... 11 Fläkt Woods 8180

More information

Operation Manual R205BV, R209BV

Operation Manual R205BV, R209BV Operation Manual R205BV, R209BV 1 Safety Instruction The rotary evaporator is manufactured according to current methods and accepted safety regulations. However, risks still exist during the installation,

More information

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL

Indholdsfortegnelse. Danvent Air Handling Units SERVICE MANUAL Indholdsfortegnelse Danvent Air Handling Units SERVICE MANUAL Service Servicing of the Air Handling Unit Your ventilation system is equipped with a Danvent Air Handling Unit (AHU) which will contribute

More information

Safety. Connect the product properly to the ground. (Malfunctioning or power leaks can cause electrical shock.)

Safety. Connect the product properly to the ground. (Malfunctioning or power leaks can cause electrical shock.) User s Manual TEVHR Contents Safety...1 Control List...2 Components...3 Dimensions...3 Installation...4 Technical Specification...5 Electrical Connection...6 Electrical Scheme...7 Maintenance...10 Control...11

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL INSTALLATION, OPERATION AND MAINTENANCE MANUAL Air Curtains RUND Please, read these instructions carefully before attempting installation SECURITY ADVISE SYMBOLS Attention, Danger, Safety Advice! Danger

More information

DRI-AIR INDUSTRIES, INC. ARID-X10C FLOOR MOUNT DRYER OPERATING MANUAL

DRI-AIR INDUSTRIES, INC. ARID-X10C FLOOR MOUNT DRYER OPERATING MANUAL ARID-X10C FLOOR MOUNT DRYER OPERATING MANUAL Page 1 DRI-AIR INDUSTRIES, INC. 16 THOMPSON ROAD P.O. BOX 1020 EAST WINDSOR, CT 06088-1020 Tel. (860) 627-5110 FAX (860) 623-4477 Internet http://www.dri-air.com

More information

RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www.eipl.co.uk Page 1 of 12 INTRODUCTION Designed for a wide range of applications, the RM85 is a rugged, industrial unit, which utilizes an energy-efficient

More information

CPVS PRODUCT DESCRIPTION

CPVS PRODUCT DESCRIPTION CPVS 20 30 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPVS 20-30 compressor is a quiet, complete and ready-for-use unit for the production of compressed air for light and medium industrial applications.

More information

WINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G

WINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G WINDOW TECHNICAL GUIDE Single package Cooling only and Heat pump Models YO-YM 09-24 R407C YM 09 V6 G YM 09 V7 G YO 12-19-24 V6 G YO 12-19-24 V7 G YORK List of Contents Page 1 - Safety...2 2 - Unit packaging...2

More information

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models:

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models: INSTALLATION, OPERATION AND MAINTENANCE MANUAL BHW MEDIUM STATIC PRESSURE DUCTABLE TYPE Models: 174 205 358 410 515 720 724 Cooling capacities from 3,1 to 25 KW Heating capacities from 4,5 to 55,5 KW Thank

More information

AIR HANDLING UNITS RIS P EKO 3.0. New range - 5 sizes, 20 models! Efficient EC. E f f i c i e n c y up to 94%! E x t r e m e l y low height! fans!

AIR HANDLING UNITS RIS P EKO 3.0. New range - 5 sizes, 20 models! Efficient EC. E f f i c i e n c y up to 94%! E x t r e m e l y low height! fans! AIR HANDLING UNITS RIS P EKO 3.0 1 2 3 4 fans! Efficient EC E f f i c i e n c y up to 94%! E x t r e m e l y low height! New range - 5 sizes, 20 models! Contents Basic features 4 RIS P EKO 3.0 full range

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL INSTALLATION, OPERATION AND MAINTENANCE MANUAL Air Curtains: RECESSED WINDBOX (M, ECM, G, ECG), RECESSED COMPACT (M, ECM, G, ECG), RECESSED DAM (M, ECM, G, ECG) Please, read these instructions carefully

More information

Residential Gas Condensing Boiler Greenstar combi 100 p / 151 p ZWB28-3A... ZWB42-3A...

Residential Gas Condensing Boiler Greenstar combi 100 p / 151 p ZWB28-3A... ZWB42-3A... Residential Gas Condensing Boiler Greenstar combi 00 p / 5 p ZWB8-3A... ZWB4-3A... Operating Instructions 708733 (07/04) US/CA Contents Contents Explanation of symbols and safety instructions.......................

More information

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001829 OPERATIONS AND MAINTENANCE MANUAL Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1.0 SCOPE: This Operations and Maintenance

More information

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001927 Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579 1 1.0 SCOPE: This

More information

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw Air cooled chillers with brushless oil-free compressors R-134a RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw External installation with very low sound level Cooling circuit with

More information

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News VA 23606 Telephone (757) 873-6800 FAX (757) 873-3632 Website: www.ebacusa.com INTRODUCTION

More information

GLOBAL LP. Ceiling-mounted ventilation unit with plate heat exchanger

GLOBAL LP. Ceiling-mounted ventilation unit with plate heat exchanger Ceiling-mounted ventilation unit with plate heat exchanger Ventilation unit with plate heat exchanger for commercial applications. Well-suited for both newly constructed buildings and renovation projects

More information

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw TECHNICAL INSTRUCTIONS CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw CHG 1 CHG 1 8. kw. kw.7 kw 1. kw April 7 19 - GB - 2 MARKING This product marked conforms to the essential

More information

User manual for reversible heat pump

User manual for reversible heat pump User manual for reversible heat pump Heat pump system integrated in Geniox, DV or TIME air handling unit Manual version 1.01.14 Part number of this manual 90925374 Contents DECLARATION OF CONFORMITY EXAMPLE...2

More information

Instruction manual. Submersible sump pump. Safety instructions Application Electrical connection Installation Maintenance Technical data

Instruction manual. Submersible sump pump. Safety instructions Application Electrical connection Installation Maintenance Technical data Instruction manual Submersible sump pump Safety instructions Application Electrical connection Installation Maintenance Technical data U 3 K /2 U 3 KS /2 U 3 K spezial /2 U 3 KS spezial /2 U 5 K /0 U 5

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information