d-list Line Type Heat Detector Manual SCU SEC 15 Valid as of: Software version V1.24 LISTEC and LIST are registered trade marks

Size: px
Start display at page:

Download "d-list Line Type Heat Detector Manual SCU SEC 15 Valid as of: Software version V1.24 LISTEC and LIST are registered trade marks"

Transcription

1 d-list Line Type Heat Detector SCU SEC 5 Valid as of: Software version V.24 LISTEC and LIST are registered trade marks LISTEC GmbH Am Sandberg 34 D Isen Tel. +49 (0) Fax +49 (0) info@listec-gmbh.de

2 All rights reserved. Under copyright laws, no part of this manual may be duplicated, transferred to third parties, or used for other purposes than intended, without prior written consent of LISTEC GmbH. Subject to technical change without notice! Copyright LISTEC GmbH 203 Page 2/44 LISTEC GmbH 60T /

3 CONTENT CONVENTIONS...5. ABBREVIATIONS SAFETY AND GENERAL INFORMATION SAFETY WARRANTY STANDARDS AND CONFORMITY DOCUMENTATION STRUCTURE VALIDITY SYSTEM DESCRIPTION CABLE LENGTHS EXTERNAL SENSORS OPERATION MODES AUTO-CONFIGURED OPERATION CONFIGURED-MODE OPERATION THE SCU's METHOD OF OPERATION MEASUREMENT AND EVALUATION COMMUNICATION INTERFACES INSTALLATION SENSOR CABLE CONNECTION BOXES END CAP SCU SENSOR CABLE CONNECTIONS SECCON CONNECTIONS CONNECTION CABLE UNLOCK SECCON CONNECTIONS CRIMP CONNECTIONS CUTTING STRIPPING STRIPPING LS SENSOR CABLES CRIMPING SHIELD CONNECTOR CONNECTION MODULES UCM-SEC UCM-ESD CCM 50-A SCU 800 CONNECTIONS AND SETTINGS SENSOR CABLE RELAYS AND RESET ALARM RELAYS FAULT RELAY SINGLE RELAY-OUTPUT EXTERNAL RESET COMMUNICATION PROTOCOL SWITCH RS RS OTHER CONNECTIONS AND SETTINGS LED BOARD POWER SUPPLY EARTHING INSTALLATION IN STATIC ELECTRICAL FIELDS TEST CONNECTOR T / LISTEC GmbH Page 3/44

4 7 INDICATORS AND OPERATION INDICATORS OPERATION COMMISSIONING AUTO-SEEK TEST SAVING THE CONFIGURATION RESET INSPECTION AND MAINTENANCE INSPECTION MAINTENANCE...4 APPENDIX: PART NUMBERS...42 APPENDIX: DIMENSIONS...43 SCU CBO 5-SEC AND CBO 5-ESD-T...43 APPENDIX: OPENING SECCON...44 Page 4/44 LISTEC GmbH 60T /

5 CONVENTIONS Note / Important: All text, written in text boxes such as this, is of utmost importance to the correct and successful installation and operation of the system. These texts must be adhered to at all times. References to further information. Text written in this font indicates text on the screen of the connected PC. Commands called by pressing buttons or combinations of buttons are shown as follows: Command: CLEAR-TEXT COMMAND nn = Clear-text command from a PC keyboard = Numerical command from a PC Keyboard ( Commands and system messages ) BUTTONS AND CONTROL ELEMENTS IN SOFTWARE ARE SHOWN IN THIS FONT.. ABBREVIATIONS ESD Electrostatic Discharge KL Terminal LED Light-Emitting Diode NC Normally Closed (relays) NO Normally Open (relays) PLC Programmable Logic Controller SCADA Supervisory Control and Data Acquisition SCU Sensor Control (SCU 800) SEC Sensor cable (SEC 5) VK Cables between control unit and PC 60T / LISTEC GmbH Page 5/44

6 2 SAFETY AND GENERAL INFORMATION 2. SAFETY Read before installing the product. Retain and follow all product safety and operating instructions. Always refer to the documentation supplied with the equipment, whether printed or in electronic format. Observe all warnings in the operating manual. SCU 800: Important: To avoid damage to the control unit and to the sensor cable, disconnect the power cable before adding or removing cables or printed circuit boards. When working on an open unit provisions against ESD must be applied, such as an earthing mat with wrist strap. Connections may only be made while the unit is switched off. Appropriate shipping, handling, and storage, as well as professional installation, commissioning and operation are all required to assure safe functioning of the equipment. Never pour any liquid into the housing of the equipment. Short circuits and fire could result. Do not drop the equipment. The control unit's service temperature ranges from -0 C to +60 C. Avoid exposure to moisture. Get the equipment checked by service personnel, if: moisture has penetrated into the equipment. it does not work well, or it does not work according to the user's manual. it was dropped or damaged. it shows obvious signs of breakage. Sensor cable: Humidity: The sensor cable ends must always be protected from humidity, i.e. the cable ends must be sealed while storing or mounting the cable. Bending: The minimum bending radius of the sensor cable is 25 cm. This limit must be adhered to at all times. Installation temperature: Installation of the sensor cable may not take place at temperatures below +0 C (45 F). In case of doubt contact LISTEC GmbH! Phone: +49 (0) or service@listec-gmbh.de Page 6/44 LISTEC GmbH 60T /

7 2.2 WARRANTY All parts of the LISTEC sensor cable systems have been manufactured with greatest precision and the highest degree of care. Nevertheless, the possibility of a malfunction occurring during operation can not be ruled out entirely. In the event of a problem contact the authorised installer of your system or LISTEC service at: +49 (0) or service@listec-gmbh.de. The two year warranty period begins with the date of delivery. All parts, that become defective because of a demonstrable flaw in their manufacture or material, will be replaced or repaired free of charge during this period. Such cases will not extend the original warranty period, nor will a new warranty period be granted for the replaced or repaired parts. Beyond these regulations, the current General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry, issued by ZVEI, the Zentralverband Elektrotechnik- und Elektronikindustrie e.v., are applicable. 2.3 STANDARDS AND CONFORMITY The SCU 800 and SEC 5 sensor cable have been tested according to the DIN EN 54-5 (03/200) product standard and its references, as well as the VdS 2503 (2/996) guidelines and are marked with the CE sign. The products are designed to meet EN54-5, Class A. WEEE A product carrying this symbol may not be treated as household waste. By ensuring correct disposal, you will help to prevent potential negative consequences for the environment and human health. For more detailed information, please contact your waste disposal service. RoHS All Listec products and components follow the RoHS guidelines and requirements. 60T / LISTEC GmbH Page 7/44

8 2.4 DOCUMENTATION STRUCTURE The documentation for the installation, commissioning and maintenance of d-list Systems consists of three manuals.. d-list manual 60T023 This manual describes all the steps required to install and commission a d-list system in the auto-configured mode without using the LISTterm8 terminal programme on a PC to set further parameters ( 3.3 OPERATION MODES). SYSTEM DESCRIPTION: A description of the d-list system with its major components, SCU 800 operation modes and functionality INSTALLATION: Installation of the sensor cable, connection boxes and the SCU 800 SENSOR CABLE CONNECTIONS: Sensor cable connections SCU 800 CONNECTIONS AND SETTINGS: SCU 800 connections, as well as jumper and switch settings INDICATORS AND OPERATION: LED-display, commissioning and operation INSPECTION AND MAINTENANCE: Inspection and maintenance information 2. Extended commissioning manual for a d-list system 60T024 An extension of the d-list manual 60T023, describing the commissioning of zoned d-list systems and zonal alarm relay outputs using the REL 800/6 relay card. Prerequisites for this manual are the terminal programme LISTterm8 and a training course. The configured-mode commissioning ( 3.3 OPERATION MODES) and maintenance of a d-list system are described using an example. 3. Commands and system messages 60T025 Description of all SCU 800 commands and system messages. Further documentation:. SCU 800 data sheet 60V04 2. SEC5 data sheet 60V External sensor data sheet 60V Service case data sheet 60V Commissioning protocol 60T05 6. Inspection sheet 60T Maintenance report 60T LISTterm8 manual 60T VALIDITY This document is valid as of the following versions: Software V.24 SCU main board 06 LED card 02 The version number of the software is printed on the EPROM. Version numbers of circuit boards are printed in square brackets next to the serial number. Page 8/44 LISTEC GmbH 60T /

9 ! Li nea re Se ns o r Tec hn ik 3 SYSTEM DESCRIPTION d-list is a temperature measurement and heat detection system based on a sensor cable with integrated temperature sensors, which can be used in the harshest environmental conditions due to its sealed construction and high temperature resolution. A d-list system consists of a control and evaluation unit (SCU 800, Sensor Control ) with two sensor cable ports and SEC 5 sensor cable. The SEC 5 sensor cable has addressable temperature sensors mounted on a 2-core flexible flat cable. The digital temperature transmission allows maximum cable lengths of 250 m, respectively 99 sensors for each of the two sensor cable ports. Sensor spacing is application dependant and freely selectable. The sensor cable may also be branched, as long as certain limitations are respected ( 3. CABLE LENGTHS). The temperature sensor's fixed addresses allow an exact physical location of each sensor. Each sensor's position is indicated by a contiguous numerical imprint on the sensor cable jacket Imprints(4. SENSOR CABLE). Note: A d-list system requires at least 0 sensors for a correct differential evaluation. An aluminium shield screens the cable from EMI. The jacket-material is flame-retarding and halogenfree. The operating temperature range of the d-list sensor cable is specified from -40 C to +85 C. Cable jacket Ø = 5 mm Aluminium shield Sensor (hybrid circuit) 2-core flexible flat cable Filling material Strain relief threads Following sensor cable connection types are available: SECcon: Sensor cable prefabricated with connectors 5. SECCON CONNECTIONS SCU 800 G m bh Sensor Control SCU 800 CC 5 Connection cable (E30 / E60, shielded) SEC 5 (max. 99 sensors) SEC 5 (max. 99 sensors) END SECcon connection SECcon connection END (End cap) (End cap) Branching not possible. 250 m maximum total cable length per sensor cable port (SEC 5 + CC 5). 99 sensors maximum per sensor cable port. Sensor cable is delivered prefabricated. Quick connection on site - no special tools required. 60T / LISTEC GmbH Page 9/44

10 !! Lineare Sensor Technik Lineare Sensor Technik Lineare Sensor Technik Crimped connections: The sensor cable is fitted with crimp- and shield-connectors, which are connected to the SCU 800 either directly ( 6. SENSOR CABLE), or via connection cables and connection modules( CONNECTION MODULES). SCU 800 SEC 5 SEC 5 (max. 250 m / 99 sensors) (max. 250 m / 99 sensors) G m bh END (End cap) Sensor Control SCU 800 END (End cap) SEC 5 (max. 250 m / 99 sensors) SCU 800 G mb H END (End cap) Sensor Control SCU 800 Connection box (CBO) CC 5 connection cable (E30 / E60, shielded) total cable length max. 250 m SEC 5 (max. 99 sensors) END (End cap) Two possibilities are available for this connection type: Prefabricated sensor cable: Crimp contacts and shield connectors are already fitted to the sensor cable. Sensor cable branching is possible, if the length limitations listed below are met. 250 m maximum total cable length per sensor cable port (SEC 5 + CC 5). 99 sensors maximum per sensor cable port. Sensor cable is delivered prefabricated. Quick connection on site - no special tools required. Crimping on site: Stripping and crimping of the sensor cable takes place on site. Sensor cable branching is possible, if the length limitations listed below are met. 250 m maximum total cable length per sensor cable port (SEC 5 + CC 5). 99 sensors maximum per sensor cable port. Connections can be made as required, allowing for flexible installation. Special tools are required. The SCU 800 supplies the d-list sensor cable with power (5V), performs the cyclic addressing of the connected sensors, reads the measured temperature values and evaluates the data according to various criteria ( 3.4. MEASUREMENT AND EVALUATION). Page 0/44 LISTEC GmbH 60T /

11 Lineare Sensor Technik Lineare Sensor Technik Lineare Sensor Technik Lineare Sensor Technik Lin eare Sensor Technik Lin eare Sensor Techn ik Lineare Sensor Technik 3. CABLE LENGTHS Definition: Total cable length specifies the total length of all cables connected to one sensor cable port. Total cable length = SEC 5 Sensor cable + CC 5 connection cable The total cable length of 250 m and the maximum number of 99 sensors per sensor cable port applies for all system topologies without branching. to SCU 800 max. 250 m or 99 sensors / sensor cable port to SCU 800 to SCU 800 to SCU 800 to SCU 800 The sensor cable's bus-topology with addressable sensors allows branching within certain physical limitations. The following limitations should be taken into consideration. Other configurations may, but do not necessarily have to function. Note: Sub-branches are not allowed. Total cable length per sensor cable port for 2 branches = 200 m to SCU 800 to SCU T / LISTEC GmbH Page /44

12 Lineare Se nsor Tec hnik Lineare Se nsor Tec hnik Lineare Se nsor Tec hnik Lineare Se nsor Tec hnik Lineare Se nsor Tec hnik Lineare Se nsor Tec hnik Lineare Se nsor Tec hnik Lineare Se nsor Tec hnik Lineare Se nsor Tec hnik Lineare Se nsor Tec hnik Lineare Se nsor Tec hnik Total cable length per sensor cable port for 3 branches = 60 m to SCU 800 to SCU 800 Total cable length per sensor cable port for 4 branches = 20 m to SCU 800 to SCU 800 Important: The adaptor element should be activated for each branch 30 m and with 5 sensors CONNECTION MODULES. Page 2/44 LISTEC GmbH 60T /

13 L in ea re Se n s or Te c hn ik Lineare Sensor Technik 3.2 EXTERNAL SENSORS External sensors can be used to monitor temperature critical points in an installation. External sensors should only be used for technical alarms. The temperature sensor is fitted in a stainless steel casing. Rectangular sensor casings can be screwed onto an object, while sensors in cylindrical casings can be used as feelers. The sensor and cable are sealed into the casing with a special glue of low thermal resistance. ca. 5 cm ca. 5 cm ca. 25 cm Rectangular sensor ESD-A5-EL... ESD-A5-EL ESD-A5-RL Rounded sensor Type label Sensor imprint Sensor imprint ESD-A5-RL External sensors are connected to the d-list-bus using UCM-ESD connection modules UCM-ESD. Definition: Total cable length specifies the total length of all cables connected to one sensor cable port. Total cable length = SEC 5 Sensor cable + CC 5 connection cable + length of each external sensor's connection lead The combination of external sensors with a sensor cable reduces the total cable length to 200 m. In this case 99 sensors may be connected to one sensor cable port, with max. 4 external sensors connected to either end of the sensor cable. Max. 200 m total cable length / sensor cable port G m bh G m bh The following limitations to CC 5 connection cable lengths apply for installations operated exclusively with external sensors: Number of sensors Up to 50 sensors Total cable length 00 m 5 to 99 sensors 50 m Note: Adaptor elements should be activate for each external sensor CONNECTION MODULES. 60T / LISTEC GmbH Page 3/44

14 3.3 OPERATION MODES The SCU 800 can be used in auto-configured or in configured-mode operation AUTO-CONFIGURED OPERATION Auto-configured operation uses standard parameters and is initiated with the control elements inside the SCU 800. Sensors are allocated to the two sensor cable ports for signalisation ( AUTO-SEEK). This operation mode is only suitable for the SCU Note: These settings conform to a system response behaviour according to EN 54-5, class A CONFIGURED-MODE OPERATION Setting up the SCU 800 for configured-mode operation requires the terminal programme LISTterm8 (Windows XP Windows 7). Sensors can be sorted into the required order and grouped into 64 alarm sections. Thresholds can be defined for each alarm section and further project specific settings can be made. Note: This configuration mode requires SCU 800 software versions V.24 or higher and at least LISTterm8 version V Trained personnel may program the SCU 800, as described in the Extended Commissioning 60T024. In this mode of operation the SCU 800 may also be integrated into a networked system with either a LISTcontroller master, or with the connection to superordinate equipment (SCADA system, PLC, etc.), using a predefined protocol. ( 6.3 COMMUNICATION) Page 4/44 LISTEC GmbH 60T /

15 3.4 THE SCU'S METHOD OF OPERATION 3.4. MEASUREMENT AND EVALUATION The SCU 800 retrieves temperatures from the sensors in defined intervals (measuring cycles). During a measuring cycle all sensors are addressed, temperature values retrieved and evaluated. In autoconfigured mode a new measuring cycle is started every 0 seconds. The checksum of each retrieved data is tested and the value checked for plausibility. Discrepancies will re-initiate the measurement. If three consecutive measurements are invalid, a fault alarm is set. ( FAULT RELAY) All valid measurements are evaluated against two alarm criteria. Maximum temperature Default value [ C] 50 C 2,8 Alarm trigger The measured temperature is higher than the maximum value. Differential temperature The differential value is higher than the threshold. The differential temperature is calculated according to an algorithm, which compensates for natural temperature variations (e.g. day, night, seasons). Note: An alarm is only triggered if a pre-alarm was set in the previous measuring cycle. In case of an alarm the following LED and relay assignment applies for the SCU , irrespective of the operation mode ( AUTO-CONFIGURED OPERATION or CONFIGURED-MODE OPERATION ): Alarms on sensor cable port K set LED A and alarm relay REL Alarms on sensor cable port K2 set LED B and alarm relay REL2 Note: Alarms can only be reset once the values fall 0.5 C below the respective threshold COMMUNICATION INTERFACES The SCU 800 has one serial port, which is switchable between RS232 and RS485. Switching takes place on ST4 of the main board ( RS232). 60T / LISTEC GmbH Page 5/44

16 4 INSTALLATION Important: To avoid damage to the SCU and to the sensor cable, disconnect the power cable before adding or removing cables or printed circuit boards. Connections may only be made while the unit is switched off. 4. SENSOR CABLE Humidity: The sensor cable must always be protected from humidity, i.e. the cable ends must be sealed while storing or mounting the cable. Bending: The minimum bending radius of the sensor cable is 25 cm. This limit must be adhered to at all times. Installation temperature: Installation of the sensor cable may not take place at temperatures below +0 C (45 F). Protection caps: Sensor cables are delivered with ESD-protection or protection caps ( 5 SENSOR CABLE CONNECTIONS), depending on the connection type. This protection may not be removed until the connection of the sensor cable takes place. ESD-protection: ESD-protection-cap Heatshrink Sensor cable Prefabricated sensor cables must be installed, so that the red ESD-protection-cap is situated at the SCU 800 or the connection box. The ESD-protection-cap also protects the crimp- and shield-connectors. Sensor cable delivered on cable spools always has the ESD-protection on the innermost sensor cable winding. A short-circuit connector is mounted under the ESD-protection-cap. Fixings: Various fixings, e.g. self-locking clamps, cable ties, pipe brackets, etc., may be used to install the sensor cable, so that project requirements are met. Overview 60V082 shows various possibilities, that can be supplied by LISTEC. Distance between fixings recommended: 0,75 m maximum:,0 m First fixing after connection box: ca. 30 cm Fixing next to end caps: ca. 0 cm Note: Local authorities may have special regulations regarding the mounting of equipment on ceilings. Page 6/44 LISTEC GmbH 60T /

17 Imprints: It is not of importance, whether the sensor cable is installed with ascending or descending imprints, since a logical order may be programmed later. It is recommended, that imprints at the ends of sensor cable sections be noted on a plan or drawing. Imprints at zone borders and other important points should also be noted. This information is needed for the system configuration. Sensors are marked by two imprints on opposing sides of the sensor cable to facilitate quick location. 80 Imprint Imprint Sensor imprint Sensor cable designation: yyy = Cable (batch) number zz = Sensor spacing * * * * xxx d- LIST-Sensorkabel Dyyyzz Listec GmbH Nexans VdS Nr. G * * * Imprints begin at the same level Cable jacket LIST Sensor Cable SEC5 LIST Sensor Cable SEC5 ********** ********** ********** Pre- and post-runs: The manufacturing process requires the sensor cable to be manufactured with pre- and post-runs. These can be up to 24m long and do not contain sensors. Pre- and post-runs are not part of the length(s) shown on the delivery notes. When installing the cable, proceed as follows:. Use the delivery note or spool label to determine the imprint of the first sensor. Sensors are alwayslocatedunder the sensor imprint. 2. Cut and seal the sensor cable at least 50 cm before the first sensor. The same applies for the end of the sensor cable. min. 50 cm Sensor spacing * xxx * d-list SENSORKABEL * Dyyyxx * LISTEC * xxx 60T / LISTEC GmbH Page 7/44

18 3. Sensor cable ends should extend at least 30 cm over connection points in a SCU 800 or connection boxes ca. 30 cm * xxx * d-list SENSORKABEL * Dyyyxx * LISTEC * xxx CBO Important: Open cable ends must be sealed immediately. Cut the cable at least 50 cm from sensor imprints. Use suitable cutters to cut the sensor cable. 4.2 CONNECTION BOXES Sensor cables can also be connected to a SCU 800 with CC5 connection cable. The change from a sensor cable to the connection cable may occur in a connection box (CBO). Note: To ensure ingress protection (IP), use the correct mounting holes. 5,00 mm 5,00 mm Important: Close all unused openings with plugs. Use the supplied O-rings on glands and plugs. Dimensions: APPENDIX: DIMENSIONS: CBO 5-SEC AND CBO 5-ESD-T Page 8/44 LISTEC GmbH 60T /

19 4.3 END CAP Unconnected cable ends must be sealed with END end caps Procedure:. Use suitable cutters to cut off the sensor cable end straight and clean. 2. Push the end cap completely over the sensor cable. 3. Use a heat-gun to shrink the cap (shrinking temperature is approximately 20 C) Thermoplastic glue END (Section) 60T / LISTEC GmbH Page 9/44

20 SCU 800 Important: To ensure ingress protection (IP), use the correct mounting holes. Provide enough space for the insertion of cables through the cable glands supplied with the SCU 800. The minimum bending radius of each cable must be adhered to at all times. Mounting:. Remove both screw-covers 2. Use the mounting holes Note: It is not necessary to remove the lid from the SCU 800 during installation 242 mm Lineare Sensor Technik 00 mm GmbH Sensor Control SCU 800 Cable glands: Important: All cable glands and plugs must be fitted with O-rings. Close all unused openings with plugs. Lineare Sensor Technik GmbH M20x,5 M20 2 M25x,5 M25 M25 M25x,5 Sensor Control SCU 800 M6x,5 M6x,5 M20x,5 M20x,5 Cable Ø. 3 8 mm mm mm M6 3 M6 3 M20 2 M20 2 Dimensions: APPENDIX: DIMENSIONS: SCU 800 Page 20/44 LISTEC GmbH 60T /

21 5 SENSOR CABLE CONNECTIONS Following connection types are possible: Prefabricated sensor cable with SECcon connectors: sensor cables are delivered with a pre-fitted connectors and only the connection with the CC 5 connection cable remains to be made on site ( 5. SECCON CONNECTIONS) Connections directly in the SCU 800 or in connection boxes can be delivered prefabricated or without connectors: Prefabricated: crimped sensor cable- and shield-connectors are pre-fitted on the sensor cable. After removal of the ESD-protection ( 4. SENSOR CABLE) the connections are made on a connection module ( CONNECTION MODULES) or directly in the SCU 800 ( 6. SENSOR CABLE) Without connectors: all crimping and connections are made on site ( 5.2 CRIMP CONNECTIONS) 5. SECCON CONNECTIONS SECcon connectors used to connect the sensor cable to a CC 5 connection cable, which leads to the SCU 800. The opposite side of the sensor cable is sealed with an end cap. The SECcon connector and the end cap are pre-fitted. 5.. CONNECTION CABLE Fit the supplied SECcon female connector to one end of the CC 5 connection cable:. Strip the connection cable and wires as shown. 2. Open the SECcon connector and place the housing over the the CC Insert the wires into the spring clamps: DQ red Terminal GND blue Terminal 2 Shield shield Terminal 4. Close SECcon housing as indicated in. 5. Lock the strain relief nut (Typical torque = 4+ Nm). 60T / LISTEC GmbH Page 2/44

22 6. Connect the opposite end of the connection cable to the SCU 800 ( 6. SENSOR CABLE). 7. Remove the SECcon protection cap from the connector on the sensor cable. Use the same procedure as shown in 5..2 UNLOCK SECCON CONNECTIONS. 8. The connection between sensor- and connection cable is established once the two connectors are plugged and locked. See APPENDIX: OPENING SECCON for instructions to open SECcon connectors UNLOCK SECCON CONNECTIONS Important: Do not open the connection while the SCU 800 is switched on. A SECcon connection can be opened as indicated below. Page 22/44 LISTEC GmbH 60T /

23 5.2 CRIMP CONNECTIONS 5.2. CUTTING Use a suitable cutter to cut the sensor cable at the required position STRIPPING Strip the sensor cable ends using the following procedure:. Score the sensor cable jacket with a suitable cable-knife approximately 20 cm from the end. ca. 20 cm 2. Check the orientation of the flexible flat cable. 3. Break the cable jacket by bending the sensor cable at the score, taking into account the orientation of the flat cable. 4. Pull off the jacket and shield carefully. 5. Cut off the strain-relief threads. 6. Cut off the end of the flexible cable perpendicularly to its length (90 cut) STRIPPING LS SENSOR CABLES Sensor cables with low smoke jacket material are marked with the additional imprint LS. * * * * The material used in this type of sensor cable sticks to the flexible flat cable, therefore requiring an intermediate step inbetween checking the orientation (2 nd step above) and breaking the cable jacket (3 rd step above). * xxx d- LIST-Sensorkabel LS Dyyyzz Listec GmbH Nexans VdS Nr. G Use adjustable joint pliers to apply light pressure to the sensor cable at the edges of the flat cable. Apply pressure repeatedly from the score to the end of the sensor cable to break away" the filling material from the flexible flat cable. The jacket and shield can now be pulled off as shown in step 4 above. * * * Score in cable jacket 60T / LISTEC GmbH Page 23/44

24 5.2.3 CRIMPING The sensor cable is connected to circuit boards using CLB2 female crimp connectors. The connectors are crimped with a LIST crimping tool (Refer to the crimping tool manual for further information) Crimping procedure:. LIST crimping tool: Deactivate both outer press plates by moving these to the top of the tool. 2. CLB2 female crimp connector: Open the lid of the CLB2 connector so that the contacts are exposed. Insert the CLB2 from the side of the tool. Both contacts must must be positioned over the two middle fingers of the anvil. 3. Insert sensor cable: Fully insert the flexible cable into the CLB2 contacts. 4. Crimping: Close the crimping tool completely by pressing the tool handle. The ratchet releases automatically, once the tool is fully closed. 5. Close the CLB2 lid Page 24/44 LISTEC GmbH 60T /

25 5.2.4 SHIELD CONNECTOR The shield connector fits over the cable jacket and under the aluminium shield. Note: The shield connector must be pushed completely up to the cable jacket. Take care not to damage the flexible flat cable, when fitting the shield connector. Shield connector types: SCON 5/: Terminated with a ferrule for connection to UCM- and CCM-modules ( CONNECTION MODULES). SCON 5/0: Terminated with a ring lug for connection in the SCU 800 ( 6. SENSOR CABLE). 60T / LISTEC GmbH Page 25/44

26 5.2.5 CONNECTION MODULES Following connection modules are used in connection boxes: UCM-SEC are built into CBO 5-SEC connection boxes. UCM-ESD are built into CBO 5-ESD-T connection boxes. CCM 50-A is housed in a DIN rail housing and may be used in various connection boxes which are fitted with DIN rails. Important: Note the flexible flat conductor orientation, when connecting sensor cable to connection modules. Ensure correct seating of the connectors in the strain relief (latching level)( 6. SENSOR CABLE). Note: Sensor cable branches with activated adaptor elements may not be longer than 30 m, or contain more than 20 sensors. Sub-branches are not allowed. Remove the jumper(s) to activate the adaptors Note: All signals on connection modules are connected in parallel UCM-SEC Connection module for two sensor cables in a CBO 5-SEC connection box. SCON 5/ shield connector SEC 5 sensor cable DQ marking Connector X2 for CC 5 connection cable (E30 / E60, shielded) X2 X4 X6 X8 X ST2 3 2 ST4 3 2 ST6 3 2 ST8 SHIELD GND DQ LISTEC GmbH DQ ST2 ST ST9 SHIELD ST0 BU DQ DQ GND SHIELD ST 2 3 ST3 2 3 ST5 2 3 ST X X X3 X5 X7 Connector X for CC 5 connection cable (E30 / E60, shielded) SCON 5/ shield connector DQ marking SEC 5 sensor cable Cable Connector Signal colour [terminal] DQ GND SHIELD Adaptor element SEC 5 ST Marking Shield connector [BU] ST9 SEC 5 ST2 Marking Shield connector [BU] ST0 CC 5 X red [] blue [2] Shield [3] CC 5 X2 red [] blue [2] Shiled [3] Page 26/44 LISTEC GmbH 60T /

27 UCM-ESD This connection module is installed in a CBO 5-ESD-T connection box, and may be used for one of three connection possibilities: For max. 8 ESD external sensors. For 4 ESD external sensors + x SEC 5 sensor cable. For 2 SEC 5 sensor cables. SCON 5/ shield connector SEC 5 sensor cable DQ marking Connector X2 for CC 5 connection cable (E30 / E60, shielded) X2 X ST2 3 2 ST4 ST 2 3 X2, X4, X6, X8: connections for 3 2 ST6 SHIELD 4 ESD external sensors ST3 2 3 X, X3, X5, X7: connections for 3 2 ST8 4 ESD external sensors X6 X8 X2 SHIELD GND DQ LISTEC GmbH DQ BU ST0 ST2 ST ST9 DQ DQ GND SHIELD ST5 2 3 ST X X X3 X5 X7 Connector X for CC 5 connection cable (E30 / E60, shielded) SCON 5/ shield connector DQ marking SEC 5 sensor cable Cable Connector Signal colour [terminal] DQ GND SHIELD Adaptor element SEC 5 ST Marking Shield connector [BU] ST9 SEC 5 ST2 Marking Shield connector [BU] ST0 ESD external sensors X white [] brown [2] Shield [3] ST X2 white [] brown [2] Shield [3] ST2 X3 white [] brown [2] Shield [3] ST3 X4 white [] brown [2] Shield [3] ST4 X5 white [] brown [2] Shield [3] ST5 X6 white [] brown [2] Shield [3] ST6 X7 white [] brown [2] Shield [3] ST7 X8 white [] brown [2] Shield [3] ST8 CC 5 X red [] blue [2] Shield [3] CC 5 X2 red [] blue [2] Shield [3] Note: Removing the jumper actives the respective adaptor element. 60T / LISTEC GmbH Page 27/44

28 CCM 50-A This connection module is used in boxes with DIN rails. SCON 5/ shield connector SEC 5 sensor cable DQ marking Adaptor element for sensor cable Connection cable CC 5 (E30 / E60, shielded) GND DQ Shield DQ DQ Shield DQ GND Listec GmbH CCM50 Connection cable CC 5 (E30 / E60, shielded) Adaptor element for sensor cable DQ marking SEC 5 sensor cable SCON 5/ shield connector Cable Signal Colour DQ GND Shield SEC 5 Marking Shield connector CC 5 red blue Shield Note: Removing the jumper actives the respective adaptor element. Page 28/44 LISTEC GmbH 60T /

29 7 8 6 SCU 800 CONNECTIONS AND SETTINGS 6. SENSOR CABLE K K2 Sensor cable port ST ST2 Sensor cable direct connection Sensor cable over CC 5 connection cable KL 7 (DQ) KL 8 (GND) KL 9 (DQ) KL 20 (GND) Earthing PCB mounting holes KL or ST3 / ST7 Pin 2 Important: Note the flexible flat conductor orientation when connecting the sensor cable (see label next to ST2) EARTHING with SECON 5/0 shield connector ST2 ST KL20 KL9 KL8 KL7 KL6 KL5 KL4 GND DQ GND DQ GND - + K2 K COM DQ marking Strain relief: Important: Ensure correct seating of the connector in the strain relief (latching level). Latching level 60T / LISTEC GmbH Page 29/44

30 6.2 RELAYS AND RESET Designation Terminals/ IC-socket / component Section (page) Alarm relays KL5 KL8 / LG 6.2. (30) Fault relay KL2 KL4 / LG (3) External reset KL9 KL 0 / BR (32) Note: Observe maximum relay output switching voltage and current 48 V DC / 32 V AC max., 250 ma max., resistive load 6.2. ALARM RELAYS Signal alarms on exceeding maximum or differential thresholds. Relay output coding with IC-socket LG: Normally open Normally closed Monitored outputs (NO) (NC) with resistors AL AL KL6 4 8 LG LG LG Ra Rn LG Ra Rn Rn AL AL2 AL AL2 AL AL2 Ra KL5 KL 7 KL 8 7 Relay Terminal designation Terminal Relay Terminal designation Terminal A KL5 B KL7 REL AL REL2 AL2 C KL6 C KL8 Page 30/44 LISTEC GmbH 60T /

31 6.2.2 FAULT RELAY Signals unit and / or sensor cable faults. All three relay contacts are available on terminals. Fail safe (relay contact closes when the unit is powered down). Relay output coding with IC-socket LG2: KL 2 KL 3 KL LG2 4 Relay Terminal designation Terminal NC KL2 REL3 FAULT NO KL3 C KL SINGLE RELAY-OUTPUT The SLMB piggyback module combines alarm A/B and fault relay-outputs to a single alarm- and faultsignal, using monitoring resistors. This allows the SCU800 to be connected to a single fire-panel input. The SLMB (part no. M0028) and monitoring resistors are not within the scope of delivery of the SCU 800 and must therefore be ordered separately. Resistor values must meet the fire panel's specifications. KL2 Fault Alarm A/B REL3 REL REL2 R s R f R a KL4 R s = Resulting monitoring resistance R a = Alarm resistor R f = Fault resistor Depending on the SCU800's alarm and fault status, the resulting monitoring resistance R s can have the following values: Normal operation (no fault, no alarms): R s =R f Fault (no alarms): R s = Alarm (relay A and / or B)(no fault): R s = R a R f R a R f Fault and alarm (relay A and / or B): R s =R a Installation:. Remove all power from the SCU Remove all resistors from the SCU 800 main board's sockets LG and LG2. 3. Place the SLMB on the IC-sockets LG and LG2. Ensure that all pins are correctly seated. 60T / LISTEC GmbH Page 3/44

32 Populate the IC-socket on the SLMB with the required alarm- (R a ) and fault- (R f ) resistors. 5. KL2 and KL4 are now used as a common alarm- and fault-output (terminals 3 and 5 to 8 may not be used). 6. Power up the SCU800. R a 3 R f KL8 KL7 KL6 KL5 KL4 KL3 KL2 KL ST5 ST LG IC LG2 4 SLMB 6 KL20 KL9 KL8 KL7 KL6 KL5 KL4 KL3 KL2 KL KL0 KL9 KL8 KL7 KL6 KL5 KL4 KL3 KL2 KL GND DQ GND DQ GND - + GND C B C A C NO NC K2 K COM COM EXR AL2 AL FAULT ST7 + ST3 C B AL2 C A AL C NO NC FAULT R s EXTERNAL RESET External reset input from superordinate equipment. Input type is selected with BR2: Contact with external voltage 0-30 V DC (default setting) Contact using internal voltage EXR+ KL9 EXR+ KL V DC 0 V BR2 2 3 BR EXR KL0 EXR KL0 Terminal designation Terminal + KL9 EXR KL0 Warning: Do not use an external power supply, if internal power is selected. Page 32/44 LISTEC GmbH 60T /

33 6.3 COMMUNICATION Description Switch / Terminal / Component Section (page) Protocol switch S (33) RS232 ST (34) RS485 S / KL KL 6 / BR (34) The SCU 800 has one serial port, which can be switched between RS232 and RS485 on ST4 ( RS232). The data transfer format selection between ASCII and protocol takes place with switch S PROTOCOL SWITCH Switches the serial interface between ASCII- (configuration / maintenance with LISTterm8) and protocol format (visualisation / SCADA connection): ASCII: move switch S2 towards crystal Q (default setting) Protocol: move switch S2 towards EPROM Note: The position of S2 determines the data transfer format on powering up the SCU T / LISTEC GmbH Page 33/44

34 6.3.2 RS232 May be used for data transfer in ASCII or protocol format. The RS232 interface is activated by a bridge in the RS232 connection cable. Connector: ST4 9 pin Sub-D male Connection cable: 9 pin 9 pin female sub-d female sub-d SCU TX RX GND RX TX PC Interface configuration: 9600 Baud, 8 Bit, No Parity, Stop Bit Note: Pins and 9 must be bridged on the SCU 800 end of the connection cable to activate the RS232 interface RS485 Data transfer only in protocol format. The RS485 interface is always active if the RS232 cable is not connected. Connectors: The terminals are doubled up so that the signals can be looped through. Terminal designation Terminal + KL KL2 COM + KL3 KL4 Interface configuration: Depends on the protocol in use( protocol manual). Baud rate S- S ON ON 2400 OFF ON 4800 ON OFF OFF OFF 2 Default setting The following rules apply for the baud rate setting: Power up SCU: Move S: Baud rate is read from the EEPROM Changing the baud rate with S is only possible while the SCU 800 is switched on. Changes are saved in the EEPROM. Changing the position of S while the SCU 800 is switched off has no effect on the baud rate setting. Page 34/44 LISTEC GmbH 60T /

35 ! Sensor Control SCU 800 Lineare S ensor Techn ik! Sensor Control SCU 800 Line are S en s or T ech ni k! Sensor Control SCU 800 Lin ea re S e ns or Tec hn i k! Sensor Control SCU 800 L in ea re Se ns or Tec h ni k RS485 bus: Maximum length:.00 m without repeaters. Cabling: Twisted-pair cable with 20 Ω impedance. Star-type wiring topologies are NOT allowed. Termination: Active Always at the communication master (i.e. at the i.e. LISTcontroller, PLC or PC) Passive Jumper BR enables the resistor for passive termination. Must always be set in the SCU 800 at the end of the RS485 bus. None Jumper BR open. Termination: active none none none passive BR open BR open BR open BR closed Communication Master max..00 m 60T / LISTEC GmbH Page 35/44

36 6.4 OTHER CONNECTIONS AND SETTINGS Description Switch / Terminal / Component Section (page) LED board ST (36) Power supply ST3 / ST7 / F (37) Earthing KL ST3 & ST7: Pin 2 4 PCB mounting holes (37) Use in electrical fields BR (37) 6.4. LED BOARD The LED board must be connected, else a fault alarm is set. BR on the LED board activates (closed) or deactivates (open = default) the front panel reset button ( ). Note: In most cases, resetting may only take place from the fire panel and by authorised persons. Page 36/44 LISTEC GmbH 60T /

37 6.4.2 POWER SUPPLY Connector ST7 can be used to supply further SCUs. Fuse F: 35 ma (fast-acting). Connector Pin Signal V DC ST3 / ST7 2 Earth 3 0 V Note: Connect the power supply on completion of all other connections EARTHING Earting point Earthing for ST3 / ST7: Pin 2 Power supply; CC 5 connection cable KL CC 5 connection cable 4 PCB mounting holes Sensor cable: SCON 5/0 shield connector INSTALLATION IN STATIC ELECTRICAL FIELDS When using the system in static electrical fields (direct current greater than 5kV) BR3 should be closed. This prevents the electronics from getting charged up, which may lead to the destruction of the control unit. Under normal conditions BR3 should remain open TEST CONNECTOR ST5 is used for factory tests only. 60T / LISTEC GmbH Page 37/44

38 7 INDICATORS AND OPERATION 7. INDICATORS ALARM A: Fire alarm on sensor cable port K. ALARM B: Fire alarm on sensor cable port K2.! FAULT: or sensor cable POWER MEASUREMENT: Temperature retrieval from sensor cable. DATA TRANSFER: Data transfer on the serial interface. RESET: Resets the unit after alarm or fault. 7.2 OPERATION 7.2. COMMISSIONING The SCU 800 can automatically recognise all connected sensors and register these for monitoring (= auto-configured operation: 3.3 OPERATION MODES). Note: All settings conform to a system response behaviour according to EN 54-5, class A. The unit is commissioned with the buttons TA and TA2,using the following procedure: AUTO-SEEK: Automatic recognition of all active sensors TEST: Compare expected and recognised number of sensors SAVING THE CONFIGURATION Important: The final configuration must be saved to prevent configuration loss and resultant faults. 4. It is recommended, that the first and last sensor on each physical cable branch be tested, so that correct signalling to superordinate equipment is ensured. Page 38/44 LISTEC GmbH 60T /

39 7.2.2 AUTO-SEEK Press TA and TA2 simultaneously. TA TA2 All LEDs other than the alarm LEDs light up Automatic recognition and registration of all active sensors. Sensors, connected to cable port K, are allocated to Zone (AL). Sensors, connected to cable port K2, are allocated to Zone 2 (AL2). Automatic transition to monitoring mode. Warning: Selecting this function will delete the current cable configuration, zones and all messages, as well as reset all parameters to the default values TEST This function is used to compare the expected number of sensors with the number of active sensors during commissioning and inspection. During commissioning: Compare the number of active (recognised) sensors to the number of sensors noted on plans, while installing the sensor cable ( 4. SENSOR CABLE: Imprints). It is recommended to connect and test sensor cable branches individually, so that possible faults can be isolated. Connect all sensor cables, once individual cables have been tested and found to be correct. Press TA. TA TA2 The number of active sensors are indicated by the data transfer LED: Tens: slow blinking s: quick blinking Example: 5 x slow, 3 x quick blinks = total of 53 active sensors 60T / LISTEC GmbH Page 39/44

40 7.2.4 SAVING THE CONFIGURATION The SCU s configuration is stored in a volatile memory (RAM) after an auto-seek. Should the power supply be interrupted, the last known configuration from the non-volatile memory (EEPROM) will be used when the SCU is powered up again. If the configuration does not correspond to the connected sensors, a fault alarm will be set. The configuration should therefore always be saved to the EEPROM. Pauses in the sequence may not be longer than one second: Press TA 3x and then Press TA2 x. The data transfer LED will blink very quickly for one second to confirm the procedure RESET Alarms and faults can be reset. This button has the same function as the front panel reset button and the external reset input ( EXTERNAL RESET). Press TA2 TA TA2 Page 40/44 LISTEC GmbH 60T /

41 8 INSPECTION AND MAINTENANCE The inspection of a d-list system is a quick functional test, which can be performed by briefed personnel. Maintenance of a d-list system can be performed by trained personnel only. 8. INSPECTION Form 60T028 outlines the procedure and may also be used to document the inspection. Note: Deviations should be reported to the responsible maintenance service. This form can be adapted to project specific conditions. The project name, position, unit name/number, the number of configured measuring points and the SCADA-connection can be pre-specified. The following points are checked during an inspection: The state of all LEDs. The number of active sensors. Sensor cable fixings. SCU 800 and connection box cable glands. 8.2 MAINTENANCE Note: Maintenance can only be performed by trained personnel utilising the terminal programme LISTterm8. Maintenance is described in the Extended Commissioning for d-list systems 60T024 and in the LISTterm8 manual 60T87. 60T / LISTEC GmbH Page 4/44

42 APPENDIX: PART NUMBERS Part number Designation Remark G0023 SCU control unit Control unit with 2 alarm- and fault-relay, LIST-protocol. G00233 SCU 800/6 control unit Control unit with 6 zonal alarm- and fault-relay, LIST-protocol. G00300 CBO 5-SEC connection box For two SEC 5 sensor cables; incl. UCM-SEC connection module. G00530 CBO 5-ESD-T connection box For max. 8 ESD external sensors; incl. UCM-ESD connection module. SPARES SCU 800 M00402 SCU 800 housing Incl. hinges, front panel foil, plugs, lid-screws & -covers. M0089 SCI 800 main board Main PCB for SCU / SCU 800/6. M0092 LED-IB 800 indicator board Indicator board with LEDs for SCU M00225 REL 800/6 relay card Relay card with 6 relays, for SCU 800/6. M0045 Cable-gland accessory bag All cable glands for SCU 800: M25, M20, M6 (with O-Ring). M0046 Connector accessory bag Incl. jumper s, SCON 5/0 shield-, CLB2 crimp- and power connectors. M00439 Cable-gland plug accessory bag Incl. cable-gland plugs: 2x M25, 3x M20, 2x M6 (with O-Rings). SENSOR CABLE M0035 SCON 5/0 Sensor cable shield connector in a SCU 800. M0036 SCON 5/ Sensor cable shield connector to UCM or CCM 50-A. Z0035 CLB 2 crimp connector Female 2-way crimp connector for flexible flat cables; 00 pcs.. Z00503 END end cap Heat-shrinkable cap to seal the ends of SEC 5 and SEC 20 sensor cables. G00396 N5 repair set Heat-shrinkable cable sleeve with flexible flat cable, shield connector, connectors, sealing material for the connection of two SEC 5 sensor cables. CONNECTION BOXES M00409 CBO 5-SEC accessory bag Cable glands; CLB 2 crimp connectors; fixing material. M00422 CBO 5-ESD-T accessory bag Cable glands, seals; plugs; fixing material. M00258 UCM-ESD connection module For max. 8 ESD external sensors. M00259 UCM-SEC connection module For 2 SEC 5 sensor cables. Z00320 Clincher PCB latch To latch CLB crimp connectors to PCBs; 00 pcs.. TOOLS M0072 VK232-S8-PC-03 connection cable RS232 connection cable; PC to SCU 800. Z00347 CLCT crimping tool LIST crimping tool for flexible flat cable crimp connectors. A00427 LIST cable cutter for SEC 5 and SEC 20 sensor cables. G00432 SC 5/20 service case SEC 5 and SEC 20: for commissioning and repairs LIST crimping-, standard tools and consumables in a service case. Page 42/44 LISTEC GmbH 60T /

43 M25x,5 454 M6x,5 APPENDIX: DIMENSIONS SCU mm M25x,5 46,0 mm 90,0 mm 260,0 mm Lineare Sensor Technik GmbH 50,0 mm M20x,5 79 mm M25x,5 M25x,5 Sensor Control SCU 800 M20x,5 M6x,5 M6x,5 M20x,5 M20x,5 CBO 5-SEC AND CBO 5-ESD-T M20x,5 M25x,5 75,0 mm 30,0 mm 4,5 mm 3,0 mm Lineare Sensor Technik GmbH M25x,5 M25x,5 30,0 mm 4,0 mm M20x,5 M20x,5 28,0 mm 60T / LISTEC GmbH Page 43/44

44 APPENDIX: OPENING SECCON Opening SECcon connectors: Unlocking spring clamps: Use a 3,5 mm de-burred DIN 5264 A screwdriver to unlock wires from spring clamps: LISTEC GmbH Am Sandberg 34 D Isen Germany Tel.: +49 (0) Fax.: +49 (0) info@listec-gmbh.de A company of the Swiss Securitas Group Service: Tel.: +49 (0) service@listec-gmbh.de Subject to change without prior notice! Page 44/44 LISTEC GmbH 60T /

Extended commissioning manual

Extended commissioning manual Line Type Heat Detector Extended commissioning manual SCU 800-03 SCU 800/16 SEC15 Valid as of: Software version V1.24 LISTEC and LIST are registered trade marks LISTEC GmbH Am Sandberg 34 D-84424 Isen

More information

SecuriSens d-list Product Catalogue 2015

SecuriSens d-list Product Catalogue 2015 SecuriSens d-list Product Catalogue 2015 Content 1. Processor Units... 5 2. Cable d-list... 7 3. Single Sensor d-list... 8 4. Accessories d-list... 9 5. ATEX components d-list... 13 6. Spare Parts d-list...

More information

SecuriSens LIST Product Catalogue 2015

SecuriSens LIST Product Catalogue 2015 SecuriSens LIST Product Catalogue 2015 Content 1. Processor Units... 5 2. Cable... 7 3. Accessories List... 8 4. Spare Parts... 13 5. Services... 15 6. Product Type Index... 16 2 Securiton Product Catalogue

More information

SCR100 User Manual. Version:1.1 Date:Dec 2009

SCR100 User Manual. Version:1.1 Date:Dec 2009 SCR100 User Manual Version:1.1 Date:Dec 2009 Introduction: This document mainly introduces the installations and connections of SCR100 products, and the brief operations about attendance software. Important

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

RS485 MODBUS Module 8AI

RS485 MODBUS Module 8AI Version 1.4 15/04/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000 SERVICE INSTRUCTIONS FOR Fire Alarm System MINI-2000 Version 1.3 02.04.1998 Jari Ollila Tom Brunberg Oy Esmi Ab Copyright Oy ESMI Ab, 1991... 1998 The copyright to the documentation herein is the property

More information

CTT8 TEMPERATURE MONITOR DEVICE

CTT8 TEMPERATURE MONITOR DEVICE INSTRUCTION MANUAL IM302-U v2.3 CTT8 TEMPERATURE MONITOR DEVICE GENERALITY The device of control temperatures CTT8 is used in the control of electric machine, transformer, motor, etc. where it s possible

More information

M-Sens 2. Online-Moisture Meter for Solids. Operating Instructions. SWR engineering Messtechnik GmbH

M-Sens 2. Online-Moisture Meter for Solids. Operating Instructions. SWR engineering Messtechnik GmbH EN M-Sens 2 Operating Instructions Online-Moisture Meter for Solids SWR engineering Messtechnik GmbH CONTENTS Page 1. System Overview......................................................................

More information

MO n : 12JMC rév A

MO n : 12JMC rév A CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES

More information

MBZ300. Emergency power control unit. GB Installation instructions MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 PME PME. Reset.

MBZ300. Emergency power control unit. GB Installation instructions MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 PME PME. Reset. 24V 24V PME PME CM DM SM DM WM Reset Reset Emergency power control unit GB Installation instructions 1 Table of contents 1 Symbols and illustrations...3 2 Product liability...3 3 Safety instructions...3

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The nvent RAYCHEM NGC-40 is a multipoint

More information

and Channel indicator and monitoring unit B Operating Instructions 2.00/

and Channel indicator and monitoring unit B Operating Instructions 2.00/ and Channel indicator and monitoring unit B 70.0202 Operating Instructions 2.00/00375947 Contents 1 Instrument functions... 3 1.1 Ordering details... 3 1.2 Functions of the LMD-96... 4 1.3 Functions of

More information

M-Sens 2. Online moisture measurement for solids. Operating Instructions. SWR engineering Messtechnik GmbH PART OF THE ENVEA GROUP

M-Sens 2. Online moisture measurement for solids. Operating Instructions. SWR engineering Messtechnik GmbH PART OF THE ENVEA GROUP EN M-Sens 2 Operating Instructions Online moisture measurement for solids SWR engineering Messtechnik GmbH PART OF THE ENVEA GROUP CONTENTS Page 1. System overview.............................................

More information

Original operating instructions Safety switch with guard locking AC901S AC902S

Original operating instructions Safety switch with guard locking AC901S AC902S Original operating instructions Safety switch with guard locking AC901S AC902S 7390914/03 01/2017 Contents 1 Preliminary note...4 1.1 Explanation of symbols...4 2 Safety instructions...4 3 Items supplied...5

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The Raychem NGC-40 is a multipoint electronic

More information

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems) ISOSCAN EDS460/490 EDS461/491 Insulation fault locators with control and display function for EDS systems (insulation fault location systems) EDS460-490_D00085_01_D_XXEN/01.2017 ISOSCAN EDS460/490 EDS461/491

More information

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 35305 Grünberg Phone: 040 807-0 Fax: 040 807-259 Alarm indicator and test combination MK2430 Remote alarm indicator and test combination with LC display

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS The SensorNet I/O Module provides attachment for up to 32 alarms and up to 16 switched devices. An RS-232 or RS-422 communications port is also provided for receiving serial alarms.

More information

ME 3011C / Alarm Indication / Quick Reference Guide

ME 3011C / Alarm Indication / Quick Reference Guide Tables of Contents Page Application 1 Features 1 Important Safety Information! 2 Note to this Guide 2 Further Information 2 Device Variants 2 General Functions 3 Annunciator Sequences - ISA 18.1 3 Plan

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances _D00108_00_D_XXEN/05.2015 ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances

More information

On the job around the clock 24/7: Fire detection systems

On the job around the clock 24/7: Fire detection systems On the job around the clock 24/7: Fire detection systems Version 02.2010 Version: 02.2010 Product catalogue Fire detection systems This product catalogue is intended for sales purposes only. For planning,

More information

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment

More information

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev. TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL Microener- Copyright 2010 FW 2.1 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

FIRERAY 5000 range USER GUIDE

FIRERAY 5000 range USER GUIDE FIRERAY 5000 range USER GUIDE 0044-003-04 IMPORTANT PLEASE NOTE: The beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the Detector initiating a Fire or Fault signal.

More information

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16 TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Bender Incorporated 700 Fox Chase, Coatesville PA 1930 Tel.: (800) 356-466 Fax: (610) 383-7100 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control function

More information

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

LINEAR HEAT DETECTION CABLE DURÁN-SAFE LINEAR HEAT DETECTION CABLE DURÁN-SAFE Installation & User Manual 2018 DURAN ELECTRONICA S.L. - All rights reserved www.duranelectronica.com I-manSAFECABLE-v05 TABLE OF CONTENTS Pages 1. INTRODUCTION...

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 06401 807-0 Fax: 06401 807-59 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control

More information

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1- DPR-45 User Manual V-2.0 (2..206) DPR-45 TEMPERATURE PROTECTION RELAY PT00 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT 9-50VDC SUPPLY DESCRIPTION DPR-45 is a precision unit designed for the temperature

More information

Eclipse Nursecall Systems Ltd. Clipper Plus & Clipper ID. Document V.2.1b (Basic) ENS. Freedom Through Technology

Eclipse Nursecall Systems Ltd. Clipper Plus & Clipper ID. Document V.2.1b (Basic) ENS. Freedom Through Technology Ltd. Clipper Plus & Clipper ID Document V..b (Basic) ENS Freedom Through Technology Contents Terms of the document... 3 Introduction... 3 Network and wiring... Global Wiring architecture... Power... 5

More information

ECO N DATE DESCRIPTION OF CHANGE CHG

ECO N DATE DESCRIPTION OF CHANGE CHG Model Number: M21E-24-DIN Description: The product is a loop powered device which controls an unsupervised dual pole output channel suitable to manage 24VAC loads. The M21E-24-DIN is micro-controller operated,

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Insulation fault evaluator EDS460-DG

Insulation fault evaluator EDS460-DG Insulation fault evaluator for localising insulation faults in DC IT systems with a number of branch circuits where high system leakage capacitances are involved Preliminary data sheet TDB108021en/09.2008

More information

Ethernet General Purpose

Ethernet General Purpose Ethernet General Purpose Technical Manual Revision 1.03 8 November 2013 Pakton Technologies IO PAE224 Ethernet GPIO Manual.docx Page 1 of 22 Revision 1.03 Last updated 8/11/2013 Table of Contents INTRODUCTION...3

More information

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual Revision 1.03 8 November 2013 JVA Technologies Ethernet General Purpose IO Technical Manual www.jva-fence.com.au Table of Contents INTRODUCTION...3 Scope and Purpose...3 Glossary...3 SPECIFICATIONS...4

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

General Purpose IO Technical Manual

General Purpose IO Technical Manual General Purpose IO Technical Manual Revision 1.06 8 November 2013 Pakton Technologies PAE222 GPIO Manual.docx Page 1 of 21 Revision 1.06 Last updated 8/11/2013 Table of Contents INTRODUCTION...3 Scope

More information

Remote alarm indicator and test combination MK2430

Remote alarm indicator and test combination MK2430 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 5 35305 Grünberg Tel.: 040 807-0 Fax: 040 807-259 Remote alarm indicator and test combination MK2430 Remote alarm indicator and test combination with LC

More information

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1 Operation Manual Fighter ProVision Software Version: 0.0 Revision: 1 TABLE OF CONTENTS 1. Introduction 5 2. Software Installation 5 3. PC Users 6 3.1 Introduction 6 3.2 Default Code 6 3.3 Edit PC User

More information

HTC-915-CONT. Heat-Trace Control system

HTC-915-CONT. Heat-Trace Control system Heat-Trace Control system Product overview The Raychem HTC-915 system is a compact, full-featured microprocessor-based single-point heat-trace controller. The HTC-915-CONT provides control and monitoring

More information

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required. TTSIM-1A TraceTek Sensor Interface Module with Relay Installation Items (not supplied) General Information Installation/Operation Instructions Please read these instructions and keep them in a safe place.

More information

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS GENERAL INFORMATION Please read these instructions and keep them in a safe place. These instructions must

More information

Installation Manual Tracker 221

Installation Manual Tracker 221 Installation Manual Tracker 221 KSR KUEBLER AG Im Kohlstatterfeld 17 D-69439 Zwingenberg / Germany www.ksr-kuebler.com Contents About this Installation Manual...4 Description Tracker 220-series...4 Installing

More information

KNX module for smoke alarm devices Dual/VdS and Q-Label (Order no )

KNX module for smoke alarm devices Dual/VdS and Q-Label (Order no ) Product definition KNX module for smoke alarm devices Dual/VdS and Q-Label (Order no 2343 00) Art. no 2343 00 Page 1 of 22 Product definition Table of contents 1 Product definition... 3 1.1 Product catalogue...

More information

User manual. ABB i-bus EIB. Zone Terminal MT/S Intelligent Installation System ABB STOTZ-KONTAKT

User manual. ABB i-bus EIB. Zone Terminal MT/S Intelligent Installation System ABB STOTZ-KONTAKT User manual ABB i-bus EIB Zone Terminal MT/S 4.12.1 Intelligent Installation System ABB STOTZ-KONTAKT 2 Contents Page 1 Device configuration..................................... 4 1.1 Introduction..........................................

More information

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm.

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm. E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0E FL0E FL0E mm mm 0 mm DESCRIPTION The LT FL0 Series is part of the Fire Alarm Aspiration

More information

Advance Optima Module Magnos 17

Advance Optima Module Magnos 17 Advance Optima Module Magnos 17 Service Manual 43/24-1002-0 EN Table of Contents Page Chapter 1: Description of functions 1-1 Chapter 2: Module variants and components 2-1 Chapter 3: Analyzer variants

More information

Universal fault annunciator for panel mounting

Universal fault annunciator for panel mounting Universal fault annunciator for panel mounting Communication over Ethernet USM - Universal-fault annunciator for panel mounting Low depth housing for panel mounting Versions with 8, 16, 32 or 48 inputs

More information

FDCL221 Line separator

FDCL221 Line separator FDCL221 Line separator Technical manual Fire Safety & Security Products Technical specifications and availability subject to change without notice. 2004-2009 Copyright Siemens, Inc. We reserve all rights

More information

SIMATRIX NEO Modular Video Matrix

SIMATRIX NEO Modular Video Matrix SIMATRIX NEO Modular Video Matrix SIMNEO-168 Modular Design Expandable up to 224 Video-Inputs, 32 Video-Outputs Up to 8 keyboards can be connected for control Multiple protocol driver for the direct control

More information

ASD 535 Aspirating Smoke Detector

ASD 535 Aspirating Smoke Detector ASD 535 Aspirating Smoke Detector Application guidelines for refrigerated warehouses Beginning with SW version 01.02.01 Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland T 131 390 en Imprint Imprint

More information

Parameterisable compact fault annunciator with permanent display

Parameterisable compact fault annunciator with permanent display Parameterisable compact fault annunciator with permanent display FSM 10 Drop-flap fault annunciator 31.08.2010 Permanent display even on power failure Compact module for 10 alarms Supply and alarm signal

More information

Fire and Gas Monitoring Panel ST7-HV

Fire and Gas Monitoring Panel ST7-HV Fire and Gas Monitoring Panel ST7-HV INTRODUCTION TO THE ST7-HV SYSTEM The ST7-HV system is a programmable PLC suitable for safety and security installations with a high technological and economic content

More information

Intelligent addressable fire alarm control panel

Intelligent addressable fire alarm control panel Intelligent addressable fire alarm control panel Input current consumption: Panel rating: Batteries: Networking and Interfaces Panel to panel communication: Number of panels: Interface port: System capacity

More information

M1000 Alarm Annunciator

M1000 Alarm Annunciator Data Sheet Alarm Annunciator Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions

More information

Heat Sensor Cable Alarm Units DT650L / DT950L

Heat Sensor Cable Alarm Units DT650L / DT950L Heat Sensor Cable Alarm Units DT650L / DT950L For conventional and 950 series analogue addressable systems Installation and Commissioning Manual Version 2.1 / May 2004 http://www.geindustrial.com/ge-interlogix/emea

More information

Danfoss gas detection unit Type GD Heavy Duty

Danfoss gas detection unit Type GD Heavy Duty Data sheet Danfoss gas detection unit Type GD Heavy Duty The Heavy Duty gas detection units are used for monitoring and warning of hazardous Ammonia gas concentrations. They are intended for ATEX/ IECEx

More information

SCHMIDT LED Measured Value Display MD Instructions for Use

SCHMIDT LED Measured Value Display MD Instructions for Use SCHMIDT LED Measured Value Display MD 10.010 Instructions for Use Table of Contents 1 Important Information... 3 2 Application range... 4 3 Mounting instructions... 4 4 Electrical connection... 6 5 Signalizations...

More information

Snifter ATEX22 VERSION. User Manual. Distributor

Snifter ATEX22 VERSION. User Manual. Distributor Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

P2267 NETWORK INTERFACE

P2267 NETWORK INTERFACE P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61

More information

Interface and EOL Modules 8

Interface and EOL Modules 8 Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface

More information

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2 DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2 Interactive fire detection systems Product Datasheet Features Interactive For interfacing and controlling external units to Autronica s interactive fire detection

More information

HANDBUCH / MANUAL / MANUEL / MANUALE TopScan-S

HANDBUCH / MANUAL / MANUEL / MANUALE TopScan-S FACTORY AUTOMATION HANDBUCH / MANUAL / MANUEL / MANUALE TopScan-S Certification Type Tested Inhalt / Content / Sommaire / Indice Deutsch......................................................... 3 English.........................................................

More information

Fire Control Panel FS5100

Fire Control Panel FS5100 Fire Control Panel FS5100 INSTRUCTION MANUAL Revision 6/02.11 Contents 1. Introduction... 5 2. Terminology... 5 3. Function... 7 4. Technical data... 7 4.1. Modules... 7 4.1.1. Type of modules... 7 4.1.2.

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

Data Sheet. Self regulating heating tapes. RS stock numbers

Data Sheet. Self regulating heating tapes. RS stock numbers Data Pack K Issued September 2001 232-3125 Data Sheet Self regulating heating tapes RS stock numbers 379-312 The information contained within this sheet regarding applications and installation of RS WinterGard

More information

Consignes d installation

Consignes d installation PBS-200-A Single entry power junction box Installation Instructions PBS-200-A Single entry power junction box with cold applied connection technology for use with BARTEC PSB / HSB trace heaters Consignes

More information

Branching and Connection Box AAB. Operating manual AAB EN11. GTE Industrieelektronik GmbH

Branching and Connection Box AAB. Operating manual AAB EN11. GTE Industrieelektronik GmbH AAB 430-2410-001 EN11 EN Operating manual Branching and Connection Box AAB GTE Industrieelektronik GmbH Helmholtzstr. 21, 38-40 D-41747 Viersen, GERMANY info@gte.de +49(0)2162 / 3703-0 www.gte.de Branching

More information

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Revision 4/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Operating Instructions

Operating Instructions Operating Instructions System 57 Module Kit (05701-A-0309) Alarm Update Panel (05701-A-0339) Helping to make a safer world Ensure that you read and understand these instructions BEFORE operating the equipment.

More information

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number Worldwide Supplier of Safety Solutions GfG Instrumentation 1194 Oak Valley Drive #20 Phone: 734-769-0573 Fax: 734-769-1888 E-Mail: info@gfg-inc.com Internet: www.gfg-inc.com GMA 301 Operation Manual Part

More information

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI E N G L I S H FIRE ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL0EI, MI-FL0EI AND MI-FL0EI mm mm 0 mm DESCRIPTION The LT MI-FL0 Series is part of the Fire Alarm

More information

ASD 535 Aspirating smoke detector

ASD 535 Aspirating smoke detector ASD 535 Aspirating smoke detector From production number 3072 and FW version 0.06.00 The ASD 535 aspirating smoke detector performs the task of taking continuous air samples via one or two sampling pipe

More information

600 Range Dialer Installation Manual. Version 1.0

600 Range Dialer Installation Manual. Version 1.0 600 Range Dialer Installation Manual Version 1.0 The information contained is supplied without liability for any errors or omissions. No part may be reproduced or used except as authorised by contract

More information

GMA200-MT. Operation Manual. Gas detection controller for mounting rail assembly

GMA200-MT. Operation Manual. Gas detection controller for mounting rail assembly Operation Manual GMA200-MT Gas detection controller for mounting rail assembly GfG GESELLSCHAFT FÜR GERÄTEBAU MBH KLÖNNESTRASSE 99 44143 DORTMUND, Germany TEL. +49 / (0)231 / 564 00 0 FAX +49 / (0)231

More information

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02 7 783 ISO 9001 DETACTOGYR Flame Safeguard Series 02 The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil

More information

PRELIMINARY EDITION

PRELIMINARY EDITION 3 131 PRELIMINARY EDITION 14.01.2003 Synco 700 Heating Controllers Heating controller for medium-size and large buildings. The is used as a heating circuit or primary controller. The controller is supplied

More information

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series Panel Mounted Fault Annunciator Series BSM / USM Panel-mounted fault annunciator Annunciators for panel mounting with,,,, 0 and signal inputs Storage of the last state of inputs and sequence in the case

More information

RC802/ B 8E1 Modular Fiber-Optic Multiplexer (Rev. M) User Manual

RC802/ B 8E1 Modular Fiber-Optic Multiplexer (Rev. M) User Manual RC802/804-240B 8E1 Modular Fiber-Optic Multiplexer (Rev. M) User Manual Raisecom Technology Co., Ltd. (04/2005) 1. Cautions Please read the following notices carefully before installing and using the device,

More information

Combi B Alarm box. Mounting instructions

Combi B Alarm box. Mounting instructions Combi B Alarm box Mounting instructions EN Mounting instructions Alarm box Combi B VdS, G113064, G113065, G113066 Table of Contents 1 Description... 3 2 System overview... 3 3 Structure... 3 3.1 Power

More information

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER Heating Circuit ZONE Controller RVA 46.531/109 Zonal temperature controller for control of a lowtemperature heating system, for use with condensing gas boilers Instructions for the INSTALLER INDEX Page

More information

ADW 535 Line type heat detector

ADW 535 Line type heat detector ADW 535 Line type heat detector Beginning with production version 140214 and FW version 01.00.19 The ADW 535 is an integrating line type heat detector that consists of the cable terminal processor and

More information

RC801/803/ B 16E1 Fiber-Optic Multiplexer (Rev. M) User Manual. Raisecom Technology Co., Ltd. (04/2005)

RC801/803/ B 16E1 Fiber-Optic Multiplexer (Rev. M) User Manual. Raisecom Technology Co., Ltd. (04/2005) RC801/803/805-480B 16E1 Fiber-Optic Multiplexer (Rev. M) User Manual Raisecom Technology Co., Ltd. (04/2005) 1. Cautions Please read the following notices carefully before installing and using the device,

More information

Series Digital Controller Instruction Sheet

Series Digital Controller Instruction Sheet 216/3/11 Series Digital Controller Instruction Sheet Thank you very much for purchasing DELTA DTC Series Temperature Controller. Please read this instruction sheet before using your DTC series to ensure

More information

Data Sheet. Self regulating process heating tapes RS stock numbers ,

Data Sheet. Self regulating process heating tapes RS stock numbers , Data Pack K Issued March 1997 232-3333 Data Sheet Self regulating process heating tapes RS stock numbers 379-889, 379-974 The information contained within this sheet regarding applications and installation

More information

NurseCall Main Unit F.01U V User Manual

NurseCall Main Unit F.01U V User Manual NurseCall Main Unit F.01U.252.699 V1.1 2012.01 en User Manual NurseCall Main Unit Table of Contents en 3 Table of Contents 1 Safety instructions 6 1.1 Importance of safety instructions 6 1.2 Disregarding

More information

AFMS Audible Flow Monitoring System TECHNICAL SPECIFICATION

AFMS Audible Flow Monitoring System TECHNICAL SPECIFICATION 968 AFMS AFMS TECHNICAL SPECIFICATION 08/07 Ref B ATV-ELEKTRONIK GMBH WIENER STRASSE 228 A-4030 LINZ +43 732 301600 FAX. +43 732 301600 21 Page 2 Table of contents General Introduction...3 Overview...3

More information

Operating Manual MS220DA

Operating Manual MS220DA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panel Meters MINIPAN

More information

5, SE GÅNGHESTER,

5, SE GÅNGHESTER, KSUB Control and monitoring unit Valid from week of manufacture 48/2005 Description The KSUB is a control and monitoring unit designed to control various types of fire/smoke dampers and fans in a flexible

More information

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel Synova TM Commissioning in no time thanks to automatic address allocation Auto-addressing makes setting dip switches unnecessary Automatic

More information

RMS/RPX Reader. User Manual

RMS/RPX Reader. User Manual RMS/RPX Reader User Manual Copyright Disclaimer Trademarks and patents Intended use FCC compliance Copyright 2005, GE Security Inc. All rights reserved. This document may not be copied or otherwise reproduced,

More information

Gas Detection System TOX ALARM DG2000-Garage

Gas Detection System TOX ALARM DG2000-Garage Gas Detection System TOX ALARM DG2000-Garage Gas Detection System 32 independent programmable channels 2 programmable alarm levels for each gas = up to 6 for each channel LCD alphanumeric display of gas

More information

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 505 Grünberg Tel.: 060 807-0 Fax: 060 807-59 A-ISOMETER IRDH575 Insulation monitoring device for unearthed AC, DC and AC/DC systems (IT systems) with

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information