1 4790 Continuous Gamma Level System Installation Guide P/N Revision F Part of Thermo Fisher Scientific

2

3 4790 Continuous Gamma Level System Installation Guide P/N Revision F

4

5 2009 Thermo Fisher Scientific Inc. All rights reserved. Microsoft and Windows are either trademarks or registered trademarks of Microsoft Corporation in the United States and/or other countries. HART is a registered trademark of the HART Communication Foundation. All other trademarks are the property of Thermo Fisher Scientific Inc. and its subsidiaries. Thermo Fisher Scientific Inc. (Thermo Fisher) makes every effort to ensure the accuracy and completeness of this manual. However, we cannot be responsible for errors, omissions, or any loss of data as the result of errors or omissions. Thermo Fisher reserves the right to make changes to the manual or improvements to the product at any time without notice. The material in this manual is proprietary and cannot be reproduced in any form without expressed written consent from Thermo Fisher.

6 This page intentionally left blank.

7 Revision History Revision Level Date Comments B Initial release C Address change. D Revised per ECO E Revised per ECO F Revised per ECO Thermo Fisher Scientific 4790 Installation Guide v

8 This page intentionally left blank.

9 Contents Safety Information & Guidelines... ix Safety Considerations...ix Warnings, Cautions, & Notes...ix Chapter 1 Product Overview Associated Documentation Chapter 2 Handling & Storage ESD Procedures Unpacking, Inspection, & Storage Packing, Shipping, Transporting, & Receiving Chapter 3 Installation General Licensing Source-Detector Configurations Guidelines General Power Options The Transmitter Installing Transmitter Boards AC Power Supply The Detector Alignment Measurable Range Top of Range Bottom of Range The Source Fan Source Strip Source Multiple Detectors and / or Source Heads Chapter 4 Wiring Preparation The Transmitter EMC Requirement for ATEX Version of 1400S Transmitters Board Configurations General Wiring Procedure Thermo Fisher Scientific 4790 Installation Guide vii

10 Contents Detector Wiring Power Supply Wiring Vdc Input Power Vdc Input Power AC Power I/O Boards Current Output Wiring Relays Contact Closure (Switch) Inputs Serial Communications RS232 Wiring Using Serial Communications HART Communications Chapter 5 Service & Support Contact Information Appendix A Appendix B Appendix C Appendix D Ordering Information...A-1 Specifications...B-1 Drawings... C-1 Adding Ferrite Clamps to 1400S Transmitter...D-1 Procedure... D-1 Index...INDEX-1 viii 4790 Installation Guide Thermo Fisher Scientific

11 Safety Information & Guidelines This section contains information that must be read and understood by all persons installing, using, or maintaining this equipment. Safety Considerations Warnings, Cautions, & Notes Failure to follow appropriate safety procedures or inappropriate use of the equipment described in this manual can lead to equipment damage or injury to personnel. Any person working with or on the equipment described in this manual is required to evaluate all functions and operations for potential safety hazards before commencing work. Appropriate precautions must be taken as necessary to prevent potential damage to equipment or injury to personnel. The information in this manual is designed to aid personnel to correctly and safely install, operate, and/or maintain the system described; however, personnel are still responsible for considering all actions and procedures for potential hazards or conditions that may not have been anticipated in the written procedures. If a procedure cannot be performed safely, it must not be performed until appropriate actions can be taken to ensure the safety of the equipment and personnel. The procedures in this manual are not designed to replace or supersede required or common sense safety practices. All safety warnings listed in any documentation applicable to equipment and parts used in or with the system described in this manual must be read and understood prior to working on or with any part of the system. Failure to correctly perform the instructions and procedures in this manual or other documents pertaining to this system can result in equipment malfunction, equipment damage, and/or injury to personnel. Warnings, cautions, and notes are used throughout this manual to alert users to potential hazards or important information. Failure to heed the warnings and cautions in this manual can lead to injury or equipment damage. Warning Warnings notify users of procedures, practices, conditions, etc. which may result in injury or death if not carefully observed or followed. The triangular icon displayed with a warning depends on the type of hazard (general, electrical, radiation). Thermo Fisher Scientific 4790 Installation Guide ix

12 Safety Information & Guidelines Warnings, Cautions, & Notes Caution Cautions notify users of operating procedures, practices, conditions, etc. which may result in equipment damage if not carefully observed or followed. Note Notes emphasize important or essential information or a statement of company policy regarding an operating procedure, practice, condition, etc. Tip Tips may also be used in this manual. They are suggestions or things to consider that will help you use the instrument or this manual. x 4790 Installation Guide Thermo Fisher Scientific

13 Chapter 1 Product Overview Refer to the 4790 User Guide (P/N ) for a description of instrument functions and features, ordering information, and product specifications. Associated Documentation In addition to this guide, the following documents must be read and understood by all persons installing, using, or maintaining this equipment: 4790 User Guide (P/N ) Gamma Radiation Safety (P/N ) Thermo Fisher Scientific 4790 Installation Guide 1-1

14 This page intentionally left blank.

15 Chapter 2 Handling & Storage This chapter addresses procedures for handling electrostatic discharge (ESD) sensitive equipment, as well as procedures for unpacking, inspecting, and storing of the system. Caution This system is an ESD sensitive instrument. Use proper ESD protective equipment and procedures. Failure to comply with ESD procedures can result in circuit damage. ESD Procedures The instrument contains electronic components that can be damaged from discharges of static electricity. Ordinarily, handling the circuit boards by their edges will not damage the circuits. Caution Do not touch the circuit board components. Observe the following when installing, setting up, servicing, troubleshooting, or repairing the instrument: 1. Use an antistatic bag. Most instrument subassemblies are shipped in a special antistatic bag. When not installed, keep the assembly in the bag as often as possible. 2. Remove ESD sensitive subassemblies only under the following conditions: a. When at a designated static-free workstation or when the bag is grounded at a field site. b. After the conductive area of the container has been neutralized. c. After making firm contact with an antistatic mat and / or firmly gripping a grounded individual. 3. Personnel handling ESD sensitive devices should be neutralized to a static-free workstation by means of a grounding wrist strap that is connected to the station or to a good grounding point at the field site. Thermo Fisher Scientific 4790 Installation Guide 2-1

16 Handling & Storage Unpacking, Inspection, & Storage 4. Do not allow clothing to make contact with ESD sensitive devices. 5. Avoid touching edge connectors and components. 6. Avoid partially connecting ESD sensitive devices. These devices, especially the power supply connector, can be damaged by floating leads. 7. Ground test equipment. Unpacking, Inspection, & Storage 8. Avoid static charges during troubleshooting. Note Inspection, adjustment, installation, and maintenance of the instrument must be performed by experienced personnel only. 1. Upon receipt, inspect the instrument for damage that may have occurred while in transit. If there is evidence of rough handling or damage, file a damage claim with the transportation company immediately. Notify Thermo Fisher and / or your sales representative as soon as possible. 2. Carefully inspect the packing material prior to discarding it to ensure that all equipment and instruction paperwork has been removed. 3. Use the original packing material and container for storage if necessary. 4. If storing the instrument, the storage environment should be protected, free from extremes of temperatures and high humidity, and fall within the environmental constraints listed in the specifications (Appendix B). Packing, Shipping, Transporting, & Receiving All personnel involved in the packing, shipping, or receiving of hazardous material must be trained in accordance with the United States Department of Transportation (DOT) and OSHA hazardous materials regulations or in accordance with the Canadian Nuclear Safety Commission (CNSC) regulations Installation Guide Thermo Fisher Scientific

17 Chapter 3 Installation Read Gamma Radiation Safety (P/N ) prior to installing the equipment. Tip Copies of the drawings referenced in this manual are provided in Appendix C. General The Thermo Scientific 4790 consists of three components: A (non-metallic) or 1400S (stainless steel) transmitter Z ion chamber detector 3. Source head: Narrow beam (Models ), fan beam (Models , 5210), strip source (Models ) Note In this manual, the generic use of transmitter or transmitters implies the 1400A and 1400S. The specific model name will be used only when necessary. The combination of the detector and the source head is referred to as the gauge head. For transmitter to detector layout details, refer to drawing For mounting dimensions, refer to drawing Z0-01. The source head used with the detector depends on the requirements of the application. Refer to the appropriate drawing for your source. Thermo Fisher Scientific 4790 Installation Guide 3-1

18 Installation Licensing Licensing Warning The instrument is a nuclear device regulated by federal and / or state authorities. You are responsible for knowing and following the pertinent safety and regulatory requirements. Refer to Gamma Radiation Safety (P/N ) for a summary of these requirements. Warning Moving or removing an installed source housing or any assembly that includes a source housing requires a person who is specifically licensed to install and commission Thermo Scientific source heads. In the United States, your general license permits you to own and install all of the instrument s components, including the source head. However, you may not commission the instrument (remove the lock and open the source housing shutter for the first time) without a specific license authorizing radiation commissioning of the instrument. In Canada, you are only allowed to remove the instrument from the shipping container if your CNSC license has a condition authorizing mounting / dismounting of devices. For assistance obtaining a license or commissioning / decommissioning the instrument, contact Thermo Fisher. Source-Detector Configurations The gauge consists of one or more source heads, one or more detectors, and a transmitter. Source heads are available with either a narrow or fan-shaped beam or with a strip source configuration. Strip sources emit radiation evenly along the length of the source. For most applications, ion chamber detectors are used, and for certain very narrow span applications (level measurement range of approximately two inches), a scintillation detector may be used. Some applications may require multiple sources and / or detectors. Three possible configurations are illustrated below. Figure Installation Guide Thermo Fisher Scientific

19 Installation Guidelines Guidelines Warning Do not install the system in any hazardous area other than those approved. Refer to the equipment tag for the specific approvals applicable to the configuration of your instrument. Warning Do not apply power to the instrument in any hazardous area unless the safety ground is properly wired inside the instrument and the cover is properly installed. General Review the following guidelines when planning gauge installation. 1. Correct power source is available. See Power Requirements later in this chapter. 2. Operating temperature range: a. Transmitter: -40 C to 60 C (-40 F to 140 F) b. 7002Z ion chamber detector: -25 C to 60 C (-13 F to 140 F) 3. The transmitter should be mounted so that the display is easily seen and the keypad on the transmitter is easily accessible. 4. The transmitter should not be mounted near high voltage, high current, corrosive vapors, corrosive liquids, or corrosive esters. 5. There should be enough clearance to install and service the gauge head. Refer to the appropriate drawings for your type of gauge and mount (Appendix C). 6. The source housing should be positioned so that the radioactive source identification tag is visible. The source housing tag should be upright. 7. The gauge should not be mounted where process overflow or other material can collect in the beam path. The source shutter mechanism must be kept free of debris. 8. The maximum cable length between the transmitter and the last detector should not exceed 2500 feet (763 m). Thermo Fisher Scientific 4790 Installation Guide 3-3

20 Installation The Transmitter Power Options 1. Transmitter a. 1400A 115/230 Vac input ( Vac), 50/60 Hz, 25 VA 24 Vdc input (20 28 Vdc), 12 W 12 Vdc input (9 15), 15 W max (requires optional PCB) b. 1400S 115/230 Vac input ( Vac), 50/60 Hz, 17.2 W 24 Vdc input (20 28 Vdc), 12 W Z ion chamber detector: Powered by transmitter. The Transmitter Warning Do not install the unit in any hazardous area other than those approved. Refer to the equipment tag for the specific approvals applicable to the configuration of your instrument. Follow all instructions on the installation drawings. Warning Do not apply power to the unit in any hazardous area unless the safety ground is properly wired inside the unit and the cover is properly installed. Warning Use proper lifting procedures during installation to avoid injury. 1. Refer to the proper dimensional drawing for the transmitter mounting dimensions ( for 1400A or for 1400S). 2. Mount the transmitter in one of the following two ways: - Four screws by placing one screw through each of the four holes in the transmitter enclosure s flange and tightening. - Four nuts, four bolts, and eight washers by placing one bolt through each of the four holes in the transmitter enclosure s flange, with one washer on each side. Screw on the nuts, and tighten the bolts Installation Guide Thermo Fisher Scientific

21 Installation The Transmitter Installing Transmitter Boards Warning Remove all power from the unit prior to opening the transmitter enclosure. Electrocution can result if power is present. The following procedure applies to all transmitter boards except for the AC power supply. Refer to Replacing the AC Power Supply later in this chapter. 1. Verify that power has been removed from the transmitter. 2. Remove the screws on the faceplate (cover) and open it. 3. If replacing a board, remove the board that is currently installed: a. Unplug any screw-in terminal connectors that have been wired from the board. b. Remove the board retaining screw in the upper card guide. c. Firmly but carefully push down on the top edge of the board to disengage the board connector from the transmitter. Pull up and out on the bottom edge of the board to remove it. 4. Align the board with the upper and lower card guide slots, and insert the board into the slots. 5. Line up the 3-pin by 16-pin male connector on the board with the corresponding connector on the back of the transmitter. 6. Firmly but carefully push on the board until the connector is fully seated. 7. Insert and tighten the board retaining screw in the upper card guide. 8. Connect the screw-terminal connector(s) to the corresponding replacement board connectors. 9. Refer to Chapter 4 for wiring procedures. 10. Close the transmitter and tighten the cover screws. Thermo Fisher Scientific 4790 Installation Guide 3-5

22 Installation The Transmitter AC Power Supply Warning If a power supply fails, the input capacitor might still be charged at a high voltage (up to 400 V). Caution Do not remove the 4 screws which are used to secure the power supply to the mounting bracket. The power supply and mounting bracket are placed as a single unit. Note The old power supply assembly is not field repairable. 1. Follow the procedure in step 3 above to remove all other transmitter boards (CPU, PCB 1, PCB 2, PCB 3, and PCB 4). 2. Remove the two hold-down screws from the base of the power supply mounting bracket. These screws secure the power supply mounting bracket to the main board. 3. Disconnect cables from the power supply (AC, DC, and Protective Safety Ground). If replacing the power supply, remove the existing power supply and mounting bracket assembly. Replace it with the new supply. 4. Connect the cables to the replacement power supply (see AC Power in Chapter 4 for wiring instructions). 5. Tighten the two hold-down screws to secure the power supply to the main board. (A screw-holding screwdriver facilitates installation.) 6. Reinstall the transmitter boards Installation Guide Thermo Fisher Scientific

23 Installation The Detector The Detector Warning Installation must be in accordance with local and national electric codes for the area classifications. Warning The source housing handle must be in the OFF position during installation. Warning Do not reach inside the source housing at any time during installation. Warning Use proper lifting procedures during installation to avoid injury. Alignment Refer to the appropriate installation and layout dimensional drawings for the detector supplied with your gauge (for the 7002Z ion chamber detector, refer to drawing ). The source housing and detector are normally installed across the diameter of the vessel. If mechanisms internal to the process vessel would interrupt the radiation beam, you can install the housing and detector slightly off center. Refer to Figure 3 2. If the angle between the source and detector relative to the center of the vessel is going to be less than 130º, contact Thermo Fisher. Figure 3 2. It is important to mount the gauge head securely, since any movement or change in alignment can affect the gauge s calibration. When mounting the source, be sure to include a means of aiming the beam several degrees left or right so the source beam can be aligned with the detector. The exact mounting method depends on the application. Align the center of the source beam as closely as possible with the centerline of the detector housing. The source beam is narrow horizontally, and the radiation is uniform only in the primary (center) part of the beam. The radiation in the secondary part of the beam is attenuated by the shielding in the source housing. Thermo Fisher Scientific 4790 Installation Guide 3-7

24 Installation The Detector Figure 3 3. To determine the primary beam width, you will need the included angle of the beam, which is typically approximately 12. For each degree, the beam will be 1 unit wide for every 5 units from the source. For example, if the included angle is 12, the primary beam width will be 12 inches wide 60 inches away from the source head. At 120 inches from the source head, the beam width will be 24 inches, and so on. This is illustrated in the figure below. Figure 3 4. Determining primary beam width Measurable Range Before beginning the installation, verify that the measurable range (the range over which the process level can be measured) of the proposed installation meets the requirements of your application. The top and bottom of the measurement range depend on the source type, the detector length, and the position of the source relative to the detector s sensitive length. Sensitive length refers to the part of the detector that senses radiation. Top of Range For a fan source with an ion chamber detector, the top of the range is at the top of the sensitive length of the detector or at the center of the source housing, whichever is lower. For a strip source with an ion chamber detector, the top of the range is at the top of the sensitive length of the detector or at the top of the active length of the source, whichever is lower Installation Guide Thermo Fisher Scientific

25 Installation The Source Bottom of Range For a fan source, the bottom of the range is the point where a line drawn from the fan source to the detector centerline at the bottom end of the detector s sensitive length intersects the inner vessel wall nearest the detector. Tip If the vertical beam width of the source does not fully illuminate the sensitive length of the detector, the bottom of the range is the point at which the lower limit of the source beam intersects the inner vessel wall. For a strip source, the bottom of the range is at the bottom of the detector s sensitive length or at the bottom of the active length of the source, whichever is higher. The Source Normally, the detector is mounted so that the top of the detector s sensitive length is even with the top of the fan beam or even with the top of the active length of the strip source. Refer to the appropriate drawing for your source for mounting dimensions and other details. Warning In the United States, you may uncrate and mount the source housing, but you may not remove the shipping bolt unless you are licensed to commission the gauge. In Canada, you must have a license condition permitting mounting / dismounting, and without this condition, users may not remove the source from the shipping crate. Warning Use proper lifting procedures to avoid injury. Fan Source Note the following if using a fan source. 1. The vertical angle of the fan source beam is typically 45. This means that the beam s vertical range is equal to the horizontal distance between the detector and the source. 2. Mount the source so that the top of the fan beam is aligned with the top of the sensitive length of the detector. 3. Install the source housing with its mounting face as close to the process vessel as practical, with no structural material (mounting tabs, brackets, etc.) between the beam area and the vessel. Thermo Fisher Scientific 4790 Installation Guide 3-9

26 Installation The Source 4. The mounting should ensure accurate beam alignment with the detector and provide for easy left-right angular adjustment. The top of the beam should be even with the top of the measurable range. Strip Source Note the following if using a strip source. 1. Refer to the source housing drawings to determine the position of the active length of the strip source and other mounting dimensions. 2. Secure the housing with the 1/2-inch (12 mm) bolts and lock washers (six places). The housing mounting face allows clearance for bolts or studs extending up to 2-1/4 inches (57 mm) from the mounting surface. 3. For best results, the measurable range should be less than the active length of the strip source(s). Position the strip source so that the bottom of the active length of the source is even with the minimum level to be measured. If the measurable range must be greater than the active length of the strip source, position the top of the active length of the source so that it is even with the maximum level to be measured. 4. The mounting surface should be vertical, and the mounting should ensure accurate beam alignment with the detector and provide for easy left-right angular adjustment. 5. Install the source housing with its mounting face as close to the vessel as practical, with no structural material (mounting tabs, brackets, etc.) between the beam area and the vessel Installation Guide Thermo Fisher Scientific

27 Installation Multiple Detectors and / or Source Heads Multiple Detectors and / or Source Heads Certain applications may require the use of multiple detectors and/or source heads to span the desired measurable range. If multiple detectors are used, mount the uppermost unit so that the top of its sensitive length is even with the top of the measurable range. Mount the remaining units so that the top of each detector s sensitive length is aligned with, or slightly overlaps, the bottom of the sensitive length of the detector mounted just above it. If more than one source head is required, install the top source housing with the top of its beam even with the top of the desired measurable range. Space the other source housings evenly along the vertical dimension of the vessel. For example, if the range of interest is 12 feet and three fan beam sources are used, space the source housings four feet apart. When mounting two or more pairs of strip sources and detectors on a small diameter tank, adjacent pairs of sources and detectors may be rotated by 90 if necessary. The source and detector for each source-detector pair at the same height must still be mounted on opposite sides of the tank (180 ). After mounting the uppermost source-detector pair, the position of the next lower pair may be rotated by 90. Thermo Fisher Scientific 4790 Installation Guide 3-11

28 This page intentionally left blank.

29 Chapter 4 Wiring Wiring should be performed in the following order: 1. Power to the transmitter 2. The detector to the transmitter 3. Optional wiring: a. Relay contacts b ma current output(s) c. Contact closure inputs d. Serial communications e. Wiring to connect multiple detectors Preparation Review the following warnings and cautions carefully prior to connecting any wiring. Warning Remove all power from the unit before making any connections. Electrocution can result if power is present. Warning All wiring must be done by qualified individuals in accordance with applicable codes such as the NEC (National Electric Code) ANSI/NFPA 70 specifications or the Canadian Electrical Code Part 1. Only approved conduit, boxes, and fittings may be used. Warning Do not apply power to the unit in any hazardous area unless the safety ground is properly wired inside the unit and the cover is properly installed. Warning For hazardous location installations, the cable entries must be sealed per drawing Thermo Fisher Scientific 4790 Installation Guide 4-1

30 Wiring The Transmitter Warning For non-hazardous location installations, the cable entries into the enclosure must be sealed with a compound to protect against the passage of gas or vapors. The sealing compound should not be affected by the surrounding atmosphere or liquids. The sealing compound must have a thickness of at least 5/8 inch (16 mm). Warning If metal conduit is used, the conduit must be grounded. Warning Connect the AC wiring earth ground to the internal safety ground terminal, as shown in the wiring diagram. Refer to AC Power later in this chapter to change the AC supply voltage. The Transmitter EMC Requirement for ATEX Version of 1400S Transmitters Drawing provides general guidance for routing the cables to the instrument. Drawing describes the function and wiring requirements for each connector on the boards. This drawing also shows cable requirements, power requirements, and grounding locations. The wiring label on the top of the instrument s detector-transmitter chassis also provides connector wiring information for the CPU, power, and temperature compensation boards. In order for the 1400S transmitter to meet electromagnetic emission requirements for CE-EMC approvals, ferrite clamps must be installed within the transmitter enclosure on all power and signal wiring going into and out of the transmitter housing. One ferrite clamp is installed on the wires of the AC power supply input. Five additional ferrite clamps are provided with the EMC ferrite clamps kit (P/N ). The installation procedure accompanies the kit. It is also provided in Appendix D. Note The ferrite clamps are only used in the ATEX version of the 1400S transmitter. They are not required for the CSA version or the plastic 1400A transmitter Installation Guide Thermo Fisher Scientific

31 Wiring The Transmitter Board Configurations The transmitter has slots for the following boards: AC power supply CPU board with 7002Z interface PCB 1: Standard current I/O / DC power board in one of the following configurations: 24 Vdc input power and current I/O #1, 2 contact inputs, 2 relays (optional) 12 Vdc input power and current I/O #1, 2 contact inputs (optional) PCB 2: Optional current I/O board, 2 contact inputs, 2 relays PCB 3: Optional current I/O board, 2 contact inputs, 2 relays General Wiring Procedure Follow this general procedure to wire boards installed in the transmitter. Warning Remove all power from the unit before making any connections. Electrocution can result if power is present. Warning All wiring must be done by qualified individuals in accordance with applicable codes such as the NEC (National Electric Code) ANSI/NFPA 70 specifications or the Canadian Electrical Code Part 1. Only approved conduit, boxes, and fittings may be used. Note CSA certified fittings must be used to maintain CSA rating for the enclosure. 1. Ensure power to the gauge is removed, and open the enclosure cover. 2. Remove the plugs only from the cable conduit holes you will use. The holes are labeled on the transmitter enclosure. 3. Pull the cable through the fitting on the end of the enclosure. Leave approximately 6 inches (150 mm) of stress relief. Secure the conduit, ensuring it is completely sealed. 4. For ATEX versions of the 1400S: Install a ferrite clamp on all wiring. You will need kit Refer to Appendix D. Thermo Fisher Scientific 4790 Installation Guide 4-3

32 Wiring Detector Wiring 5. Connect a cable to a PCB as follows: a. Remove the plug-in screw terminal connector from the board connector. If the connector is tight, brace the board with your hand to remove the screw terminal connector, but be careful to not touch any circuit components. b. Loosen the terminal screws on the connector. Insert the wires into the connector and make connections as shown in the appropriate installation wiring drawing. c. Tighten the terminal screws to secure the wires. d. Plug the screw-terminal connector back into the corresponding onboard connector. 6. When all connections are complete, close and secure the transmitter cover. Detector Wiring Power Supply Wiring The detector is completely powered from the transmitter. The threeconductor cable provides +24 Vdc input to the detector and a 24 V bidirectional log signal, which use a common ground. The only other electrical connection to the detector is the Safety. Refer to drawing Note To meet the requirements of CSA , an external switch or circuit breaker must be installed to allow the power source to be disconnected from the gauge. In addition, protective bonding (grounding) must always be provided even if a DC power source is used. 24 Vdc Input Power With 24 Vdc input power, the system is designed to operate on Vdc. The maximum input power requirement is 12 W when all options are present. Refer to drawing for wiring requirements. Note To meet the requirements of CSA , the input DC terminals must be supplied from an SELV (Safety Extra Low Voltage) source. 1. Connect +24 Vdc to pin 8 of the J5 connector on the current I/O #1 (PCB 1) board. 2. Connect the return for the +24 Vdc supply to ground, pin 9 of the J5 connector Installation Guide Thermo Fisher Scientific

33 Wiring I/O Boards 12 Vdc Input Power With 12 Vdc input power, the system is designed to operate on 9 15 Vdc. The maximum input power requirement is 15 W when all options are present. Refer to drawing for wiring requirements. To connect 12 Vdc: 1. Connect +12 Vdc to pin 2 of the J6 connector on the current I/O #1 (PCB 1) board. 2. Connect the return for the +12 Vdc supply to ground, pin 1 or pin 3 of the J6 connector. Note The J6 connector is only present if the 12 Vdc option is installed. AC Power With AC power, the system is designed to operate on Vac at an input frequency of 50/60 Hz. This configuration can be directly wired to either 115 or 230 Vac. The maximum input power requirement is 25 VA when all options are present. Refer to drawing for wiring requirements. To connect AC power: 1. Connect AC power input (L and N) to the J1 terminal block. I/O Boards Current Output Wiring 2. Connect electrical safety ground to a dedicated safety ground terminal. One current output (I/O) board is supplied as standard with the instrument. It is installed in the PCB 1 slot. Up to two optional I/O boards can be installed in the PCB 2 and PCB 3 slots. The current output is programmable between 0 and 20 ma. The minimum output is approximately 3 ma, and the maximum load is 750 ohms. The current output is normally shipped with an isolated, self-powered output configuration. You can reconfigure it with an isolated, looppowered configuration by removing the jumper from pins 3 and 4 on the J5 connector on the I/O board. In the loop-powered configuration, you must supply +24 Vdc loop power to pin 3 of J5; pin 2 of J5 is Iout+. Relays Two or four relays are available as options on the I/O board in the PCB 1 slot. Refer to drawing and the label inside the transmitter cover for wiring details. Relay contacts are Form C SPDT, isolated 8 A, 220 Vac. Thermo Fisher Scientific 4790 Installation Guide 4-5

34 Wiring Serial Communications Contact Closure (Switch) Inputs Two user-provided contact closure inputs are included on each I/O board. The contact closure inputs are dry contact inputs between ground and Switch 1 and ground and Switch 2. The gauge can be configured via software settings to execute a command or other function upon a userprovided contact opening or closing. Refer to the 4790 User Guide (P/N ) for instructions on assigning commands to the contact closure inputs. Serial Communications RS232 Wiring The gauge provides an RS232 single-drop serial interface. Screw terminal connectors for the ports are located on the CPU board. Refer to drawing for details. The serial port on a PC (COM1 or COM2) can be connected directly to the RS232 port on the gauge. This connection requires five wires: ground, transmit (TX), receive (RX), RTS, and CTS. The connections between the gauge RS232 port connector (located on the CPU board in the transmitter) and the PC serial port are summarized in the following table for standard DB9 and DB25 PC serial port connectors. Table 4 1. CPU Board (J8) RS232 Connector PC Serial Port DB9 Connector PC Serial Port DB25 Connector Pin 1, J8 (RTS) Pin 8 Pin 5 Pin 2, J8 (TX) Pin 2 Pin 3 Pin 3, J8 (CTS) Pin 7 Pin 4 Pin 4, J8 (RX) Pin 3 Pin 2 Pin 5, J8 (GND) Pin 5 Pin 7 Using Serial Communications To communicate with the gauge from a PC requires that the PC be running TMTComm, a Windows -based communications software, or another terminal emulation software. The default communication settings: 7 data bits Even parity 1 stop bit 9600 baud data rate Refer to the 4790 User Guide (P/N ) for additional details about setting up and using serial communications Installation Guide Thermo Fisher Scientific

35 Wiring HART Communications HART Communications The HART communication protocol is supported over the 4 20 ma current output with an optional daughter board. You can communicate with the gauge using the 375 Field Communicator from Emerson Electric Co. Refer to manual for instructions. Thermo Fisher Scientific 4790 Installation Guide 4-7

36 This page intentionally left blank.

37 Chapter 5 Service & Support Contact Information The local representative is your first contact for support and is well equipped to answer questions. You can also contact Thermo Fisher directly for application assistance. In the United States Thermo Fisher Scientific 1410 Gillingham Lane Sugar Land, TX Phone: Fax: In Europe Thermo Fisher Scientific Ion Path Road Three Winsford Cheshire CW7 3GA United Kingdom Phone: +44 (0) In Canada Thermo Fisher Scientific 14 Gormley Industrial Avenue Gormley, Ontario L0H 1G0 Phone: Fax: On the Web Thermo Fisher Scientific 4790 Installation Guide 5-1

38 This page intentionally left blank.

39 Appendix A Ordering Information Table A 1. System ordering information Code Model continuous nuclear/gamma level Code Approval 7002ZC Factory Mutual approvals 7002ZB CSA approvals Code First Detector Length 01 1 ft detector (305 mm) 02 2 ft detector (610 mm) 03 3 ft detector (915 mm); consult Thermo Fisher 04 4 ft detector (1220 mm) 05 5 ft detector (1525 mm) ; consult Thermo Fisher 06 6 ft detector (1830 mm) 08 8 ft detector (2440 mm) ft detector (3660 mm) Code Second Detector Length (optional) XX XX ft detector (same lengths available as first detector) Code Third Detector Length (optional) XX XX ft detector (same lengths available as first detector) Code Fourth Detector Length (optional) XX XX ft detector (same lengths available as first detector) Thermo Fisher Scientific 4790 Installation Guide A-1

40 Ordering Information Table A 2. Detector P/N Description Assembly, controller, and pre-amp PCB set Assembly, PCB insulating cover Clamp, detector mounting End cap, detector O-ring, detector end cap Table A 3. Transmitter P/N Description HLT-MTXR 1400A transmitter HLT-MTXR-SS 1400S transmitter, stainless steel Kit, KRIL/4790 CPU with EPROM for level KIB for KRIL/ line display AC power supply OTO545B HART interface module Current output module 1, no relays Current output module 1, with 2 Form C relays Current output module 2, no relays Current output module 2, with 2 Form C relays Kit, EMC ferrite clamps for 1400S transmitter (for ATEX units only) A Installation Guide Thermo Fisher Scientific

41 Appendix B Specifications Results may vary under different operating conditions. Table B 1. System specifications Operating principle Accuracy Stability Gamma radiation from the source passes through the process pipe and material. The amount of radiation reaching the detector decreases as the process level increases. ± 1% of span Drift less than 1.0% absolute radiation change per 6 months Table B 2. Ion chamber detector specifications Detectors per installation Supply voltage / consumption Operating temperature range Humidity Minimum operational radiation field Enclosure Connections Output Interconnecting cable Up to 4 detectors may be used per installation Power supplied from transmitter -25 C to +60 C (-13 F to +140 F) 10% to 95% RH non-condensing 0.2 mr/hr ANSI 300 Series stainless steel Two 3/4-inch NPT conduit entries Single 3-wire instrument cable for digital communication to transmitter; in multi-detector installations, each detector is wired in parallel Maximum length 2500 ft (763 m) between detector and transmitter Standard 3-conductor, shielded (Belden 9365) Thermo Fisher Scientific 4790 Installation Guide B-1

42 Specifications Table B A transmitter specifications Power supply NEMA 4X FM/CSA approvals Dimensions Weight Operating temperature Circuit protection Serial interface Current output Contact closure inputs Power input is transient surge protected. AC power: 115/230 Vac ( V), 50/60 Hz, 25 VA DC power: 24 Vdc (20 28 V), 12 W; or 12 Vdc (9 15 V), 15 W Class I, Div. 2, Groups A, B, C, D Class II, Div. 2, Groups F, G Class III NEMA 4X, Type 4X 12 x 8.5 x 8.25 in. (305 x 216 x 210 mm) 7.5 lb (3.4 kg) -40 C to +60 C (-40 F to +140 F) Meets IEC 801-1, -2, and -3. Current outputs and relay outputs are isolated RS232, full duplex communication with remote terminal, printer, PC, or host computer One standard; maximum of two additional Standard Configuration: Isolated, self-powered, 700-ohm maximum load Alternate Configuration: Isolated, loop-powered, 24 Vdc nominal supply voltage, 700-ohm maximum load Two per I/O board Relays Two optional per I/O board; six maximum. Form C SPDT, isolated, 8 A, 220 Vac B Installation Guide Thermo Fisher Scientific

43 Specifications Table B S transmitter System architecture Display Current output Serial outputs Multiprocessor-based electronics for uninterrupted output during data entry and system interrogation. All user data doubly stored in non-volatile memory with no battery backup required. Four-line backlit display; up to eight readouts displayed simultaneously One standard. Maximum of three current outputs available, with each representing independent span channels Standard configuration: Isolated, self-powered, 800-ohm max. load Alternate configuration: Isolated, loop-powered, 24 Vdc nominal supply voltage, 800-ohm max. load RS485 half-duplex. RS232 full duplex. Contact closure outputs Up to 16 available. 115 Vac / 28 Vdc 10 amps (230 Vac 8 amps) Inputs Programming options Power supply Up to three additional I/O available; dry contact closure. Menu driven, direct keypad entry AC power: 115/230 Vac ( V), 50/60 Hz, 17.2 W DC power: 24 Vdc (20 28 V), 12 W Dimensions See drawing Approvals NEMA 4X / IP65 ATEX: II 3 G Ex na IIC T6 (-40 C Ta 60 C) DC version, EPSILON 08 ATEX 2387: II 3 G Ex na nc IIC T4 (-20 C Ta 50 C) AC version, EPSILON 08 ATEX 2387 CSA: Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III Enclosure type 4X, Temperature code T3C / T4 Power = Vdc, 12 W, Vac, 50/60 Hz, 2 A, 25 VA maximum Ambient temperature variation: -40 C to +60 C (-40 F to +140 F) CE compliant Low Voltage Directive compliant EMC Directive compliant Thermo Fisher Scientific 4790 Installation Guide B-3

44 This page intentionally left blank.

45 Appendix C Drawings Note Information presented in this chapter has been regenerated from original drawings. Every effort is made to maintain document accuracy. However, in order to enhance legibility, the documents may have been restructured, and some information may have been intentionally excluded. Therefore, the drawings within this guide may not be an exact duplicate of the original drawings. Note Drawings in this manual are included for reference only and may not be the current version. Contact the factory if you need a copy of the latest revision. Table C 1. Wiring: Ion Chamber Detectors Drawing # Rev. Description Page B Installation layout, 1400A / 1400S transmitter to 7002Z ion chamber detectors (1 sheet) C B Wiring diagram (3 sheets) C 4 Table C 2. Mechanical Drawing # Rev. Description Page F 1400A transmitter dimensional diagram (1 sheet) C A 1400S transmitter dimensional diagram (1 sheet) C Z Z ion chamber detector installation dimensions (1 sheet) C 9 D Typical source / detector installation drawing (2 sheets) C B Mounting dimensions Model 5200 source housing, 100 mci or less (1 sheet) C Mounting dimensions Model 5201 source housing, 100 mci or less (1 sheet) D Mounting dimensions Model 5202 source housing, 500 mci or less (1 sheet) C 12 C 13 C 14 Thermo Fisher Scientific 4790 Installation Guide C-1

46 Drawings Drawing # Rev. Description Page C Mounting dimensions Model 5203 source housing, 2000 mci or less (2 sheets) C Mounting dimensions Model 5204 source housing, 8000 mci or less (2 sheets) C Mounting dimensions Model 5205 source housing, 100 mci or less (1 sheet) C Mounting dimensions Model 5206 source housing, 500 mci or less (1 sheet) C Mounting dimensions Model 5207 source housing, 2000 mci or less (1 sheet) D Mounting dimensions Model 5208 source housing, 8000 mci or less (1 sheet) A Mounting dimensions Model 5210 source housing, 10 Ci CS-137 or 3 Ci Co-60 (1 sheet) B Mounting dimensions Model 5194 strip source, 1 ft, 500 mci (1 sheet) C Mounting dimensions Model 5195 strip source, 2 ft, 1000 mci (1 sheet) C Mounting dimensions Model 5196 strip source, 3 ft, 1000 mci (1 sheet) C 15 C 17 C 19 C 20 C 21 C 22 C 23 C 24 C 25 C 26 Table C 3. Source Housing Options Drawing # Rev. Description Page Interlock option for Models source heads (1 sheet) B Pneumatic actuator and position switch for Model (1 sheet) B Mounting instructions Remote manual actuator for Models (2 sheets) C 27 C 28 C 29 C Installation Guide Thermo Fisher Scientific

47 Drawings Figure C : Installation layout, 1400A / 1400S transmitter to 7002Z ion chamber detectors (sheet 1 of 1) Thermo Fisher Scientific 4790 Installation Guide C-3

48 Drawings Figure C : Wiring diagram, 1400A / 1400s transmitter to 7002Z ion chamber detectors (sheet 1 of 3) C Installation Guide Thermo Fisher Scientific

49 Drawings Figure C : Wiring diagram, 1400A / 1400S transmitter to 7002Z ion chamber detectors (sheet 2 of 3) Thermo Fisher Scientific 4790 Installation Guide C-5

50 Drawings Figure C : Wiring diagram, 1400A / 1400S transmitter to 7002Z ion chamber detectors (sheet 3 of 3) C Installation Guide Thermo Fisher Scientific

51 Drawings Figure C : 1400A transmitter installation dimensions (sheet 1 of 1) Thermo Fisher Scientific 4790 Installation Guide C-7

52 Drawings Figure C : 1400S transmitter dimension diagram (sheet 1 of 1) C Installation Guide Thermo Fisher Scientific

53 Drawings Figure C Z0-01: 7002Z ion chamber detector installation dimensions (sheet 1 of 1) Thermo Fisher Scientific 4790 Installation Guide C-9

54 Drawings Figure C 8. D : Typical source / detector installation drawing (sheet 1 of 2) C Installation Guide Thermo Fisher Scientific

55 Drawings Figure C 9. D : Typical source / detector installation drawing (sheet 2 of 2) Thermo Fisher Scientific 4790 Installation Guide C-11

56 Drawings Figure C : Mounting dimensions Model 5200 source housing, 100 mci or less (sheet 1 of 1) C Installation Guide Thermo Fisher Scientific

57 Drawings Figure C : Mounting dimensions Model 5201 source housing, 100 mci or less (sheet 1 of 1) Thermo Fisher Scientific 4790 Installation Guide C-13

58 Drawings Figure C : Mounting dimensions Model 5202 source housing, 500 mci or less (sheet 1 of 1) C Installation Guide Thermo Fisher Scientific

59 Drawings Figure C : Mounting dimensions Model 5203 source housing, 2000 mci or less (sheet 1 of 2) Thermo Fisher Scientific 4790 Installation Guide C-15

60 Drawings Figure C : Mounting dimensions Model 5203 source housing, 2000 mci or less (sheet 2 of 2) C Installation Guide Thermo Fisher Scientific

61 Drawings Figure C : Mounting dimensions Model 5204 source housing, 8000 mci or less (sheet 1 of 2) Thermo Fisher Scientific 4790 Installation Guide C-17

62 Drawings Figure C : Mounting dimensions Model 5204 source housing, 8000 mci or less (sheet 2 of 2) C Installation Guide Thermo Fisher Scientific

63 Drawings Figure C : Mounting dimensions Model 5205 source housing, 100 mci or less (sheet 1 of 1) Thermo Fisher Scientific 4790 Installation Guide C-19

64 Drawings Figure C : Mounting dimensions Model 5206 source housing, 500 mci (sheet 1 of 1) C Installation Guide Thermo Fisher Scientific

65 Drawings Figure C : Mounting dimensions Model 5207 source housing, 2000 mci or less (sheet 1 of 1) Thermo Fisher Scientific 4790 Installation Guide C-21

66 Drawings Figure C : Mounting dimensions Model 5208 source housing, 8000 mci or less (sheet 1 of 1) C Installation Guide Thermo Fisher Scientific

67 Drawings Figure C : Mounting dimensions Model 5210 source housing, 10 Ci Cs-137 or 3 Ci Co-60 (sheet 1 of 1) Thermo Fisher Scientific 4790 Installation Guide C-23

68 Drawings Figure C : Mounting dimensions Model 5194 strip source, 1 ft, 500 mci (sheet 1 of 1) C Installation Guide Thermo Fisher Scientific

69 Drawings Figure C : Mounting dimensions Model 5195 strip source, 2 ft, 1000 mci (sheet 1 of 1) Thermo Fisher Scientific 4790 Installation Guide C-25

70 Drawings Figure C : Mounting dimensions Model 5196 strip source, 3 ft, 1000 mci (sheet 1 of 1) C Installation Guide Thermo Fisher Scientific

71 Drawings Figure C : Interlock option for Models source heads (sheet 1 of 1) Thermo Fisher Scientific 4790 Installation Guide C-27

72 Drawings Figure C : Pneumatic actuator and position switch for Models (sheet 1 of 1) C Installation Guide Thermo Fisher Scientific

73 Drawings Figure C : Mounting instructions Remote manual actuator for Models (sheet 1 of 2) Thermo Fisher Scientific 4790 Installation Guide C-29

74 Drawings Figure C : Mounting instructions Remote manual actuator for Models (sheet 2 of 2) C Installation Guide Thermo Fisher Scientific

75 Appendix D Adding Ferrite Clamps to 1400S Transmitter Note The ferrite clamps are only used in the ATEX version of the 1400S transmitter. They are not required for the CSA version or the plastic 1400A transmitter. If needed, the ferrite clamps kit may be ordered separately. In order for the 1400S transmitter to meet electromagnetic emission requirements for CE-EMC approvals, ferrite clamps must be installed within the transmitter enclosure on all power and signal wiring going into and out of the transmitter housing. Procedure The ferrite clamp is part of the EMC ferrite clamps kit (P/N ). The kit consists of the following: Five ferrite clamps (P/N ) At least one clamp key The procedure The clamp key is used to remove the ferrite clamp from the wire during wiring changes. Figure D 1. Ferrite clamps A ferrite clamp will need to be installed on all wiring that enters or exits the transmitter enclosure. This may be a shielded twisted pair or a bundle of individual wires. The limitation is that the wires through one clamp cannot exceed 5 mm in diameter. Also, all of the clamps MUST be installed within the enclosure. Thermo Fisher Scientific 4790 Installation Guide D-1

76 Adding Ferrite Clamps to 1400S Transmitter Procedure Figure D 2. Ferrite clamps installed within enclosure As shown in Figure D 2 the ferrite clamp can be placed around a shielded twisted pair cable or a bundle of individual cables, as long as the diameter of the bundle does not exceed 5 mm (a little over 3/16 ). The ferrite clamp kit (P/N ) contains five clamps. Depending on your wiring scheme, you may need additional clamps. They can be ordered using part number For example, in a Thermo Scientific DensityPRO+ system with a scintillation detector, flow input, and three outputs, there will be eight shielded twisted pair cables and one power cable. This system would require a total of nine ferrite clamps. So you would need either two kits or one kit and four additional clamps to be EMC compliant. Note All ATEX version 1400S transmitters shipped after August 2009 will contain one ferrite clamp kit and will have one ferrite clamp installed on the AC voltage input wiring. Note If the locking mechanism of the clamp should fail, a plastic wire tie can be used to secure the clamp around the wire. D Installation Guide Thermo Fisher Scientific

DensityPRO+ Gamma Density System with Remote Transmitter Installation Guide P/N Part of Thermo Fisher Scientific.

DensityPRO+ Gamma Density System with Remote Transmitter Installation Guide P/N Part of Thermo Fisher Scientific. DensityPRO+ Gamma Density System with Remote Transmitter Installation Guide P/N 717818 Revision F Part of Thermo Fisher Scientific DensityPRO+ Gamma Density System with Remote Transmitter Installation

More information

LevelPRO Measurement Systems. Continuous Gamma Level System Installation Guide PN

LevelPRO Measurement Systems. Continuous Gamma Level System Installation Guide PN LevelPRO Measurement Systems Continuous Gamma Level System Installation Guide PN 1-0702-040 LevelPRO Measurement Systems Continuous Gamma Level System Installation Guide PN 1-0702-040 2014 Thermo Fisher

More information

DensityPRO+ Gamma Density System with Remote Transmitter Installation Guide P/N Part of Thermo Fisher Scientific.

DensityPRO+ Gamma Density System with Remote Transmitter Installation Guide P/N Part of Thermo Fisher Scientific. DensityPRO+ Gamma Density System with Remote Transmitter Installation Guide P/N 717818 Revision D Part of Thermo Fisher Scientific DensityPRO+ Gamma Density System with Remote Transmitter Installation

More information

Nuclear Density Gauges

Nuclear Density Gauges Nuclear Density Gauges DensityPRO DensityPRO+ DensityPRO-C ConsistencyPRO CutPRO 3680 Authorised Distributor www.transmin.com.au Thermo Scientific Nuclear Density Gauges Energy Attenuation Gauges The expandable

More information

DensityPRO+ Gamma Density System with Remote Transmitter User Guide P/N Part of Thermo Fisher Scientific. Revision C

DensityPRO+ Gamma Density System with Remote Transmitter User Guide P/N Part of Thermo Fisher Scientific. Revision C DensityPRO+ Gamma Density System with Remote Transmitter User Guide P/N 717819 Revision C Part of Thermo Fisher Scientific DensityPRO+ Gamma Density System with Remote Transmitter User Guide P/N 717819

More information

Sapphire. Ultrasonic Point Level System User Guide P/N Part of Thermo Fisher Scientific. Revision C

Sapphire. Ultrasonic Point Level System User Guide P/N Part of Thermo Fisher Scientific. Revision C Sapphire Ultrasonic Point Level System User Guide P/N 900-000068 Revision C Part of Thermo Fisher Scientific Sapphire Ultrasonic Point Level System User Guide P/N 900-000068 Revision C 1992 Thermo Fisher

More information

Troubleshooting Thermo Scientific LevelPRO Gauges

Troubleshooting Thermo Scientific LevelPRO Gauges Troubleshooting Thermo Scientific LevelPRO Gauges Key Words Scintillation detector Current board Relay output Communications Level indication Purpose A chapter in the user guide for the Thermo Scientific

More information

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16 TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and

More information

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required. TTSIM-1A TraceTek Sensor Interface Module with Relay Installation Items (not supplied) General Information Installation/Operation Instructions Please read these instructions and keep them in a safe place.

More information

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS GENERAL INFORMATION Please read these instructions and keep them in a safe place. These instructions must

More information

FLT93 Installation, Operation and Troubleshooting Guide

FLT93 Installation, Operation and Troubleshooting Guide FLT93 Installation, Operation and Troubleshooting Guide Pre-Installation A. To get the best results from the instrument, the instrument should be mounted 20 pipe diameters downstream from any valve, pipe

More information

Beacon 800 Gas Monitor Operator s Manual

Beacon 800 Gas Monitor Operator s Manual Beacon 800 Gas Monitor Operator s Manual Part Number: 71-0037RK Revision: F Released: 4/18/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be

More information

Model 144H. Product Data Sheet , Rev DB February Content

Model 144H. Product Data Sheet , Rev DB February Content Rosemount 144 PC-Programmable Temperature Transmitter Provides an installation-ready solution for temperature monitoring applications using Complete Point Solutions (CPS) Increases measurement accuracy

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE

DSGH. Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE DSGH Radiation-Based Detector with GEN2000 Electronics for Density Measurement QUICK REFERENCE GUIDE Revision History Revision History Version of manual Description Date 1.0 Initial release 051025 1.1

More information

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm

More information

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

Installing the Cisco ONS FAP-4 Fuse Alarm Panel Installing the Cisco ONS 15454-FAP-4 Fuse Alarm Panel Product Number: 15454-FAP-4= This document explains how to install, test, operate, and maintain the Cisco ONS 15454-FAP-4 fuse alarm panel. This document

More information

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001 SLATE Base Module R8001A1001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform can

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TT-1343 5/06b INSTALLATION INSTRUCTIONS Original Issue Date: 8/03 Model: Automatic Transfer Switches Equipped with Series 1000 Programmable Controller Market: ATS Subject: Remote Annunciator Kits GM28938-KP1,

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

standards: standards:

standards: standards: INSTRUCTION MANUAL D2xB1LD2 LED Beacons For use in Hazardous Locations 1) Warnings DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT DO NOT OPEN WHEN ENERGISED POTENTIAL ELECTROSTATIC CHARGING HAZARD

More information

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION

DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION DET-TRONICS SPECIFICATION DATA Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION The EQ2200UVHT UV Flame Detector is used with the Eagle Quantum

More information

Greentrol Automation, Inc.

Greentrol Automation, Inc. Model GA-100 Technical Manual GreenAlert 100 Series Greentrol Automation, Inc. Installation, Operation and Maintenance Technical Manual GA-100 Document Name: TM_GA-100_R1C TM_GA-100_R1C Part Number: 960--0000

More information

Series 155. Mass Flow Computers TECHNICAL SPECIFICATIONS

Series 155. Mass Flow Computers TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS Mass Flow Computers Series 155 The Kurz 155 Mass Flow Computer is a versatile system transmitter that integrates the functions of flow and temperature measurement, flow totalization,

More information

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards.

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards. 4100S The operation and functions described in this manual are available from Software Version 4100S-023-013 onwards. Specifications: Item Specification Details Enclosure Steel IP30 Dimensions H x W x

More information

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions Description The NGC-UIT-ORD is a panel mounted display used in conjunction with other approved Raychem control and

More information

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg.

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg. WARD OXYGEN Installation, Operation, and Maintenance Instructions MEGA medical electronic gas alarm MEGA WARD MEGA medical electronic gas alarm WARD POWER SUPPLY Medical Electronic Gas Alarm OXYGEN SYSTEM

More information

Sensor Interface Module Installation/Operation Instructions

Sensor Interface Module Installation/Operation Instructions TraceTek TTSIM-1 Sensor Interface Module Installation/Operation Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and VDE Certified. For

More information

Colibri. Automatic Tank Gauge CL6 Series Installation Guide

Colibri. Automatic Tank Gauge CL6 Series Installation Guide Colibri Automatic Tank Gauge CL6 Series Installation Guide Manual # Revision Date Changes from Previous Revision 000-2153 C Jan. 2013 Pipe compound brand change, Updated Control drawing. Franklin Fueling

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

Sapphire ULTRASONIC POINT LEVEL SYSTEM

Sapphire ULTRASONIC POINT LEVEL SYSTEM ULTRASONIC POINT LEVEL SYSTEM Introduction Compliance with growing government regulations mandates tighter level controls with advanced diagnostics to avoid releases, overspills and costly environmental

More information

Beacon 410A Gas Monitor Operator s Manual

Beacon 410A Gas Monitor Operator s Manual Beacon 410A Gas Monitor Operator s Manual Part Number: 71-0397 Revision: F Released: 12/5/17 www.rkiinstruments.com Product Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be

More information

Installation and Operating Instructions

Installation and Operating Instructions The Leader of RF and Sonic Level For Assistance Call 1-800-527-6297 Outside North America 1-215-674-1234 Installation and Operating Instructions Series 504-1200 Ultrasonic VeriGAP Switch using 404-1200

More information

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features. CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse

More information

OPTISENS TUR 2000 Technical Datasheet

OPTISENS TUR 2000 Technical Datasheet OPTISENS TUR 2000 Technical Datasheet Sensor for turbidity measurement in water and wastewater Rugged design for harsh applications Integrated transmitter with direct 4...20 ma output Near infrared light

More information

GETTING STARTED GUIDE. NI 9212 and TB TC, ±78 mv, 24 Bit, 95 S/s/ch Simultaneous, Isothermal Terminal Block

GETTING STARTED GUIDE. NI 9212 and TB TC, ±78 mv, 24 Bit, 95 S/s/ch Simultaneous, Isothermal Terminal Block GETTING STARTED GUIDE NI 9212 and TB-9212 8 TC, ±78 mv, 24 Bit, 95 S/s/ch Simultaneous, Isothermal Terminal Block This document explains how to connect to the NI 9212 using the TB-9212. In this document,

More information

CONTROL BE MADE CHANGES MAY NOT. Page 1

CONTROL BE MADE CHANGES MAY NOT. Page 1 HI 6020IT and HI 6020JB US & Canada Hazardous Locations User Guide (Class I, II, III, Division 1, Class I, Zone 0 and Zone 20) Hardy Process Solutions Document Number: : 0596-0352-01 REV A CONTROL LLED

More information

/9308 External Battery Chargers Installation Instructions

/9308 External Battery Chargers Installation Instructions 4081-9306/9308 External Battery Chargers Installation Instructions Introduction This publication describes the installation procedure for an External Battery Charger used with the 4100U or 4100ES System.

More information

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08 GasScanner 8C Eight Channel Monitor Operator s Manual MINT-0281-XX Rev. A 01/29/08 Product Warranty Matheson Tri-Gas, Inc., warrants gas alarm equipment sold by us to be free from defects in materials,

More information

Victoreen Primalert 35 Area Radiation Monitor

Victoreen Primalert 35 Area Radiation Monitor Victoreen 05-437 Primalert 35 Area Radiation Monitor Operators Manual March 2005 Manual No. 126011 Rev. 3 2003, 2005 Fluke Corporation, All rights reserved. Printed in U.S.A. All product names are trademarks

More information

DL424/425 DirectLine Sensor Module for Dissolved Oxygen Probes Series DL5000 Specifications

DL424/425 DirectLine Sensor Module for Dissolved Oxygen Probes Series DL5000 Specifications DL424/425 DirectLine Sensor Module for Dissolved Oxygen Probes Series DL5000 Specifications 70-82-03-48 January 2003 Overview The DirectLine DL424/425 Sensor Modules are part of a family of products developed

More information

ACTIVE INFRARED BARRIER

ACTIVE INFRARED BARRIER Although PROTECH provides high security indoor intrusion sensors for the military and government markets, our specialty is outdoor protection. Since we first introduced our PIRAMID outdoor dual technology

More information

Rosemount 4500 Hygienic Pressure Transmitter. Start

Rosemount 4500 Hygienic Pressure Transmitter. Start Quick Installation Guide June 2007 Rosemount 4500 Rosemount 4500 Hygienic Pressure Transmitter ProductDiscontinued Start Step 1: Mount the Transmitter Step 2: Set the Switches Step 3: Connect Wiring and

More information

Instruction Manual Model Backup Switch, 1 for 8

Instruction Manual Model Backup Switch, 1 for 8 Instruction Manual Model 2582-282 Backup Switch, 1 for 8 December 2011, Rev. 0 MODEL 2582 SWITCH CROSS TECHNOLOGIES INC. SWITCH ALARM PSA PSB ALARM OFFLINE ONLINE UNIT STATUS 1 2 3 4 5 6 7 8 BU PROT MODE

More information

MODEL 8144-RD CLOCK SELECTOR/DISTRIBUTION AMPLIFIER INSTRUCTION MANUAL. SPECTRACOM CORPORATION 95 Methodist Hill Drive, Suite 500 Rochester, NY 14623

MODEL 8144-RD CLOCK SELECTOR/DISTRIBUTION AMPLIFIER INSTRUCTION MANUAL. SPECTRACOM CORPORATION 95 Methodist Hill Drive, Suite 500 Rochester, NY 14623 MODEL 8144-RD CLOCK SELECTOR/DISTRIBUTION AMPLIFIER INSTRUCTION MANUAL SPECTRACOM CORPORATION 95 Methodist Hill Drive, Suite 500 Rochester, NY 14623 PHONE 585-321-5800 FAX 585-321-5218 REVISIONS, IF ANY,

More information

MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL

MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL TABLE OF CONTENTS Product Overview... 2 Operation... 3 Installation... 5 Troubleshooting... 9 Ordering Information, Warranty and Service...10

More information

Snifter ATEX22 VERSION. User Manual. Distributor

Snifter ATEX22 VERSION. User Manual. Distributor Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5

More information

Fisher LCP100 Local Control Panel

Fisher LCP100 Local Control Panel Instruction Manual LCP100 Local Control Panel Fisher LCP100 Local Control Panel Contents Introduction... 1 Scope of Manual... 1 Description... 2 Specifications... 2 Installation... 3 Hazardous Area Classifications

More information

Model 144H. Product Data Sheet , Rev DB February Content

Model 144H. Product Data Sheet , Rev DB February Content Rosemount 144 PC-Programmable Temperature Transmitter Provides an installation-ready solution for temperature monitoring applications using Complete Point Solutions (CPS) Increases measurement accuracy

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116279 (LR 025993_0_000) Issued to: General Monitors, Incorporated 26776 Simpatica Circle Lake Forest, California 92630 USA Attention: Larry Vlagea The

More information

RAEGuard 2 PID. User Guide

RAEGuard 2 PID. User Guide RAEGuard 2 PID User Guide P/N: H-D03-4001-000 Rev M February 2018 Contents Section 1: RAEGuard 2 PID User s Guide 1 General Information... 6 2 General Specifications... 8 2.1 RAEGuard 2 PID Specifications...

More information

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS... SECTION Table of Contents SECTION 1 INTRODUCTION...................... 1.1 Description............................... 1.2 Features................................. 1.3 Models..................................

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

4100U City and Relay Cards Installation Instructions

4100U City and Relay Cards Installation Instructions 4100U City and Relay Cards Installation Instructions Introduction This publication describes the installation procedure for the following: 4100-6031/6032 City Circuit Cards 4100-6033 Alarm Relay Card Inspecting

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

MBUV-100D, MBUVS-100D MBIR-100D, MBFR-100D DIN RAIL MOUNT FLAMEWORX MODULES

MBUV-100D, MBUVS-100D MBIR-100D, MBFR-100D DIN RAIL MOUNT FLAMEWORX MODULES MBD-00 FEBRUARY 00 MBUV-00D, MBUVS-00D MBIR-00D, MBFR-00D DIN RAIL MOUNT FLAMEWORX MODULES APPROVED Year 000 Compliant in accordance with BSI document DISC PD000-I:998 DESCRIPTION Fireye offers a complete

More information

KT-100 Door Controller

KT-100 Door Controller WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully

More information

INSTRUCTIONS FOR THE LCR10 TEN INCH CIRCULAR CHART RECORDER

INSTRUCTIONS FOR THE LCR10 TEN INCH CIRCULAR CHART RECORDER INSTRUCTIONS FOR THE LCR10 TEN INCH CIRCULAR CHART RECORDER LOVE LOVE CONTROLS a Division of Dwyer Instruments, Incorporated PO Box 338 Michigan City, IN 46361-0338 (800) 828-4588 (219) 879-8000 FAX (219)

More information

YP7999A1000 ControLinks Fuel Air Ratio Control Panel

YP7999A1000 ControLinks Fuel Air Ratio Control Panel YP7999A1000 ControLinks Fuel Air Ratio Control Panel FEATURES INSTALLATION INSTRUCTIONS Pre-wired and ready to install Includes the R7999A control, wiring subbase and S7999D1048 touchscreen display Commission,

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The nvent RAYCHEM NGC-40 is a multipoint

More information

DETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS

DETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS TEST LOG Detector Identification Information Manufacturer and Serial Date Detector Model: Number: Installed: Description of Detector Location: Test Results and Maintenance Data Date Test Test Maintenance

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS The SensorNet I/O Module provides attachment for up to 32 alarms and up to 16 switched devices. An RS-232 or RS-422 communications port is also provided for receiving serial alarms.

More information

Duct and Rough Service Carbon Monoxide Sensor

Duct and Rough Service Carbon Monoxide Sensor Product Identification and Overview Duct and Rough Service Carbon Monoxide Sensor BAPI s Carbon Monoxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations.

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The Raychem NGC-40 is a multipoint electronic

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...

More information

PDU Power Distribution Unit for IP-NINJAR. User s Guide Ver

PDU Power Distribution Unit for IP-NINJAR. User s Guide Ver Power Distribution Unit for IP-NINJAR PDU-1209 User s Guide Ver. 1.0.0 Thank you for choosing this IDK product. To ensure the best performance of this product, please read this User s Guide fully and carefully

More information

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-3 ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS Features: For use with doors or groups of doors that must interlock with each other to regulate control of accessing one area from another,

More information

E340 BOILER CONTROL INSTALLATION MANUAL

E340 BOILER CONTROL INSTALLATION MANUAL E-3451 JUNE 1999 E340 BOILER CONTROL INSTALLATION MANUAL DESCRIPTION The E340 Boiler Room Control is a microprocessor-based Boiler Management System designed to interface with existing Fireye D Series

More information

Global Water Instrumentation, Inc.

Global Water Instrumentation, Inc. Instrumentation, Inc. 11390 Amalgam Way Gold River, CA 95670 T: 800-876-1172 Int l: (916) 638-3429, F: (916) 638-3270 High Water Alarm WA400-DC WA400-AC WA400-BU WA400-FS WA400-AL 10/23/06 P/N: 01-527

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

DensityPRO C. Gamma Density System User Guide P/N Part of Thermo Fisher Scientific. Revision D

DensityPRO C. Gamma Density System User Guide P/N Part of Thermo Fisher Scientific. Revision D DensityPRO C Gamma Density System User Guide P/N 900-748300 Revision D Part of Thermo Fisher Scientific DensityPRO C Gamma Density System User Guide P/N 900-748300 Revision D 2007 Thermo Fisher Scientific

More information

MBCE-110/230UV Flame Sensor Module

MBCE-110/230UV Flame Sensor Module MBCE-1002 FEBRUARY 3, 2017 MBCE-110/230UV Flame Sensor Module DESCRIPTION The MBCE-110/230UV modules provide visual indication and electrical outputs that signal the user regarding flame presence in a

More information

Mark 25 Ultrapure Water Conductivity Analyzer

Mark 25 Ultrapure Water Conductivity Analyzer Martek Instruments, Inc. Mark 25 Ultrapure Water Conductivity Analyzer Instruction Manual WARRANTY POLICY Unless otherwise stated, MARTEK INSTRUMENTS, INC. warrants this equipment to be free from defects

More information

GETTING STARTED GUIDE NI RTD, 0 Ω to 400 Ω, 24 Bit, 400 S/s Aggregate, PT100

GETTING STARTED GUIDE NI RTD, 0 Ω to 400 Ω, 24 Bit, 400 S/s Aggregate, PT100 GETTING STARTED GUIDE NI 9217 4 RTD, 0 Ω to 400 Ω, 24 Bit, 400 S/s Aggregate, PT100 This document explains how to connect to the NI 9217. Note Before you begin, complete the software and hardware installation

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

Aerosol Inlet Dryer. User s manual. Part Number: AE33-AEDN. User's manual Version 1.5 December /30

Aerosol Inlet Dryer. User s manual. Part Number: AE33-AEDN. User's manual Version 1.5 December /30 Aerosol Inlet Dryer User s manual Part Number: AE33-AEDN User's manual Version 1.5 December 2015 1/30 Aerosol Inlet Dryer User s manual Version 1.5, December 2015 Copyright 2015 Aerosol d.o.o. Magee Scientific,

More information

Certificate of Compliance

Certificate of Compliance FF0 001 Certificate of Compliance Certificate: 70116284 (LR 064969_0_00) Issued to: Mine Safety Appliances Company North American Division 1000 Cranberry Woods Dr Cranberry Township, Pennsylvania 16066-5296

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

Power Supply Display Module PSDM. Installation and Operation Manual

Power Supply Display Module PSDM. Installation and Operation Manual Power Supply Display Module PSDM Installation and Operation Manual Read this manual before using this product. Failure to follow the instructions and safety precautions in this manual can result in serious

More information

T3/E3 Fiber Optic Line Drivers

T3/E3 Fiber Optic Line Drivers MT618A-ST-R3 January 2004 MT619A-ST-R2 MT620AE-R2 T3/E3 Fiber Optic Line Drivers CUSTOMER SUPPORT INFORMATION Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500) FREE technical

More information

Rosemount 3490 Series

Rosemount 3490 Series Product Data Sheet July 2014 00813-0100-4841, Rev DA Rosemount 3490 Series 4 20 ma + HART Compatible Controller Field mounted controller with integral multi-function LCD and keypad Tough weatherproof wall

More information

Dräger Polytron 5100 EC Detection of toxic gases and vapors

Dräger Polytron 5100 EC Detection of toxic gases and vapors Dräger Polytron 5100 EC Detection of toxic gases and vapors The Dräger Polytron 5100 EC is a cost-effective explosion proof transmitter for the detection of toxic gases or oxygen. It uses a high performance

More information

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors. Fire Sentry Corporation (FSC) 593 Apollo Street Tel.: 714-671-1100 Brea, California 92821 Fax: 714-671-5821 Multi-Spectral, Digital, Infrared Electro-Optical FSC Model No. s FS10-R and FS10-A Unitized,

More information

Remote NAC Power Supply D7038

Remote NAC Power Supply D7038 Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus

More information

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08 Beacon 200 Gas Monitor Operator s Manual Part Number: 71-2102RK Released: 6/6/08 Table of Contents Chapter 1: Introduction.................................................3 Overview.............................................................3

More information

TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions

TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions Approvals / Certifications Hazardous Locations Class I, Division 2 Groups A, B, C, D Touch 1500-HAZ-CPU and Touch 1500-HAZ-TS

More information

4-Channel Contact Closure Fiber Link Card System

4-Channel Contact Closure Fiber Link Card System USER GUIDE RLH Industries, Inc. The leader in rugged fiber optic technology. U-020 2017A-0330 4-Channel Contact Closure Fiber Link Card System SYSTEM INSTALLATION INFORMATION Description The 4 Channel

More information

Dräger Polytron 8000 Stationary gas detector (EC)

Dräger Polytron 8000 Stationary gas detector (EC) Dräger Polytron 8000 Stationary gas detector (EC) The microprocessor-based transmitter can be equipped with various electrochemical DrägerSensors. This way, you can easily detect oxygen and various toxic

More information

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08 GasScanner 4C Four Channel Monitor Operator s Manual MINT-0280-XX Rev. A 02/25/08 Product Warranty Matheson Tri-Gas., warrants gas alarm equipment sold by us to be free from defects in materials, workmanship,

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

AC/DC Power Supply and Battery Charger Installation and Maintenance

AC/DC Power Supply and Battery Charger Installation and Maintenance AC/DC Power Supply and Battery Charger Installation and Maintenance 61175043L3-5A Issue 1, January 2004 CLEI Code: SIMPAADA_ CLEI Code: SIMPAAGA_ CONTENTS 1. GENERAL... 1 2. DESCRIPTION... 1 3. INSTALLATION...

More information

GPS Evaluation Kit EVA1037/1080

GPS Evaluation Kit EVA1037/1080 GPS Evaluation Kit An evaluation system for Tyco Electronics GPS modules A1037-A & A1080-A User s Manual Version 2.0 Hardware Revision 01 This page was intentionally left blank. Revision History Revision

More information

/8 DIN Level Indicator

/8 DIN Level Indicator Data Sheet SS/_6 High visibility 5-digit LED display clear and accurate indication Analog and relay outputs as standard high, low, latch and rate alarms, plus isolated retransmission Maths functions included

More information

GETTING STARTED GUIDE NI TC, ±78 mv, 24 Bit, 75 S/s Aggregate

GETTING STARTED GUIDE NI TC, ±78 mv, 24 Bit, 75 S/s Aggregate GETTING STARTED GUIDE NI 9213 16 TC, ±78 mv, 24 Bit, 75 S/s Aggregate This document explains how to connect to the NI 9213. Note Before you begin, complete the software and hardware installation procedures

More information

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM Card Rack Modules CABLE DUCT MAIN SWITCH 800 mm USER INTERFACE TERMINAL PRODUCT OVERVIEW The nvent

More information

POINTEK CLS 100 OINTEK CLS 100 CAPACITANCE LIQUIDS/SOLIDS. Instruction Manual March 2001

POINTEK CLS 100 OINTEK CLS 100 CAPACITANCE LIQUIDS/SOLIDS. Instruction Manual March 2001 POINTEK CLS 100 CAPACITANCE LIQUIDS/SOLIDS Instruction Manual March 2001 OINTEK CLS 100 Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect

More information

Instruction Manual April sitrans AS 100

Instruction Manual April sitrans AS 100 Instruction Manual April 2005 sitrans AS 100 Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment.

More information

TraceNet ECM Series Control System

TraceNet ECM Series Control System TraceNet ECM Series Control System ECM Operating Guide Thermon Manufacturing Company TraceNet is a registered trademark of Thermon Manufacturing Company. ECM Operating Guide 2014, 2015 Thermon Manufacturing

More information

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM

TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM TRACENET TM TCM18 CONTROL AND MONITORING SYSTEM APPLICATION OVERVIEW Control and monitoring systems play an essential role in heat tracing applications which range from freeze protecting water lines to

More information