1 MTA - NEW YORK CITY TRANSIT 2 BROADWAY NEW YORK, NY DIVISION OF MATERIEL web.mta.info/nyct/procure/nyctproc.htm Vreplies@nyct.com NOTICE -OF- ADDENDUM ADDENDUM # 5 BID OPENING/DUE DATE: 09/09/2016
2 2 Broadway vercnlque Hakim New York. NY President New York City Transit August 19,2016 ADDENDUM NO.5 Contract No. IFB Maintenance & Testing Services for Fire Retardant Cylinders in the Fire Suppression Systems on Buses TO ALL PROSPECTIVE BIDDERS: This addendum is to notify all prospective bidders that the Bid Opening Date has been changed to Friday, September 09, 2016 at 2:00pm. Attached is the revised Tech Spec. that reflect change in requirements. Reminder: Be sure to acknowledge this Addendum in your bid. Failure to do so may result in rejection of your bid. S~~~M'rr1J,'!j~ Thomas Spange Senior Director MTA New vork City Transit is an agency of the Metropolitan Transportation Authority, State of New vork
3 ~=:at... /?U=+±iJl. _. jm... MTA NEW YORK CITY TRANSIT DEPARTMENT OF BUSES TECHNICAL SERVICES Code: SPECIFICATION S Rev. F Subject: Date: Recharging of the Fire Retardant Agent Cylinder 6/09/16 for the Fire Suppression System Page: I of 10 I Supersedes: S Rev. E I Application: Kidde and Amerex Fire Retardant Agent Cylinders used in the fire suppression systems ofnyct DOB/ MTA Bus fleets. Purpose: To provide the contractor with the minimum requirements for the servicing and recharging of the Kidde and Amerex fire retardant agent cylinders listed below in Table I. Table # 1 Description 25 Ibs Amerex (ABC Drv Chemical) Cvlinder TA# Ibs Amerex (ABC Drv Chemical) Cvlinder Ibs Amerex (ABC Dry Chemical) Cvlinder Ibs Amerex (ABC Drv Chemical) Cvlinder Ibs Amerex (ABC Drv Chemical) Cvlinder Ibs Amerex (ABC Drv Chemical) Cvlinder Ibs Kidde/Dual (ABC Dry Chemical) Cylinder Ibs Kidde/Dual (PK Drv Chemical) Cvlinder Ibs KiddelDual (PK Drv Chemical) Cvlinder Ibs KiddelDual (PK Dry Chemical) Cvlinder Ibs Kidde/Dual (ABC Dry Chemical) Cvlinder Ibs KiddelDual (PK Drv Chemica\) Cvlinder Ibs KiddelDual (PK Drv Chemica\) Cvlinder OEM # Model # V25ABC VH25ABC V25ABC PRS SW V13ABC PRS SW V13ABC REVISION INDEX (Previous Revision Index on last oaze of this document) DATE REV. PAGES DESCRIPTION OF REVISION REVISED NO. AFFECTED 1) Revise application and added part numbers for Kidde and Amerex cylinders to the purpose. 2) Added cylinder OEM # & Model # identification. 3) Revise specific requirement as below a) Item # 3 for defective valve. b) Added item # 4 for pressure gauge. c) Item # 6 for visual inspection and tagging instructions for defective cylinders. 6/09116 F d) Item # 8 added standard # C-6 for visual inspection. c) Item # II for leak check using soap and water. All f) Item # 13 added table for hydrostatic pressure test. g) Added item # 14 for cylinder marking. h) Added item # 15 for tagging defective cylinders and returns for hydrostatic test. i) Added item # 18 & 19 for service tag and antitamper paint application. j) Added reference only figures of Kidde and Amcrcx cvlinders. APPROVED ~ I IUP\TSS Rev F Recharging FIre Relardenl Cyhnder
4 MTA NEW YORK CITY TRANSIT DEPARTMENT OF BUSES TECHNICAL SERVICES SPECIFICAnON Subject: Recharging of the Fire Retardant Agent Cylinder for the Fire Suppression System Identification ofoem # and Model # On Cylinders: (Reference Table # 1) Code: S Rev. F Date: Page: 6/09/16 2 of 10 Amerex Cylinder Kidde Cylinder liup\tss _04 Rev F Rechargmg Fire Rerardl'Jll C'ylillder
5 General Requirements: MTA NEW YORK CITY TRANSIT DEPARTMENT OF BUSES TECHNICAL SERVICES SPECIFICAnON Subject: Recharging of the Fire Retardant Agent Cylinder for the Fire Suppression System Code: S Rev. F Date: Page: 6/09/16 3 of 10 I. OEM or NYCT-DOB/ MTA Bus approved parts, materials and procedures shall be used in the servicing/recharging operation. Contractor shall be an authorized Amerex and/or Kidde Dual Spectrum rebuilder, and will provide authorization documentation from Amerex and/or Kidde Dual Spectrum. Fire Retardant Agent Cylinders shall comply with all applicable Federal, State, Local and OSHA laws/regulations. 2. Random samples of serviced/recharged cylinders will be inspected and tested to determine conformity with requirements set forth in the Contract Documents including this specification. Discrepancies in anyone (I) sample may result in rejection of the entire lot. 3. Each serviced/recharged cylinder must have the date of servicing/recharging, Contractor's identification code and the NYCTA symbol number permanently marked on a non-critical, external surface of the cylinder in large, bold figures. 4. All serviced/recharged cylinders shall be returned factory clean, individually packaged, with the NYCTA symbol number clearly visible, and ready for installation and service. Each delivered cylinder shall include quality control records and a certificate of conformance to this specification. 5. Individual components that are not serviceable/rechargeable shall be returned to the Salvage Department, Central Maintenance Facility, NYCT -DOB. Any component that is rejected must be replaced with an OEM component or a NYCT-DOB/MTA Bus approved equivalent. 6. NYCT shall have the option to request the apparent low bidder to furnish, at no cost to NYCT, three (3) finished samples to demonstrate the bidders' ability to successfully perform the Work. 7. Use the latest OEM Parts/Service Manuals and revisionslbulletins regarding replacement service parts, specifications, clearances, tolerances, dimensions, adjustments, settings and work standards during the process. All recharged cylinders mustmeet the specifications ofthe latest OEM Parts/Service Manuals/Service Information Letters. 8. Use all tolerances, settings, fasteners and sealant materials according to the latest OEM specifications. I IUP\TSS $.39_02_04Rev F RechargIngFue RellirdenlCyhnder
6 Specific Reguirements: MTA NEW YORK CITY TRANSIT DEPARTMENT OF BUSES TECHNICAL SERVICES SPECIFICAnON Subject: Recharging of the Fire Retardant Agent Cylinder for the Fire Suppression System Code: S Rev. F Date: Page: 6/09/16 4 of Fire retardant agent cylinders will be picked up from designated NYCT-DOB/MTA Bus locations. 2. Remove anti-recoil plate and connect valve outlet to a "Closed" dry chemical recovery system. Discharge extinguisher into recovery system. Bleed agent cylinder of all residual pressure and fire suppression agent. 3. Remove the discharge valve assembly from the cylinder. Disassemble and repair the valve assembly, using new seals and o-rings. Reassemble and test the discharge valve assembly. If discharge valve assembly is found defective and not repairable, replace the discharge valve assembly with new valve. 4. Visually inspect the pressure gauge. Replace pressure gauge, if found bent, damaged, improper gauge or not having proper zero read ing. 5. Remove and dispose of any chemical remaining in the cylinder. Clean and check the condition of the cylinder to ensure serviceability. 6. During visual inspections, inspect the cylinders for corrosion, abrasion, dents, weld damage, weld cracks or holes. All cylinders exhibiting structural damage during a visual inspection shall be returned to the Salvage Department, Central Maintenance Facility, NYCT-DOB. When cylinder is found defective, the contractor shall stamp a series of 'X's over the DOT specification number and marked service pressure or stamp "CONDEMNED" on the shoulder, top head or neck using steel stamp. Tag the defective unit with brief description of defect. Return defective unit separately from good units. 7. Service the agent cylinder as required in accordance with the most recent National Fire Protection Association standard 17 (NFPA 17: Standard for Dry Chemical Extinguishing Systems). Clean the cylinder to factory standards. 8. Inspect the serviced and cleaned agent cylinders in accordance with the Compressed Gas Association (CGA, C-6) Visual Inspection Standard. 9. Replace the retardant agent as required by the most recent NFPA 17 standard with bicarbonate or phosphate based agents as specified in the manufacturer's specification. 10. Clean the agent cylinder collar O-ring seating surfaces and threads. Install the discharge valve assembly. 11. Pressurize the agent cylinder as per OEM specifications and check it for leaks at all valve components, including valve core and valve seat at cylinder using leak detector or OEM approved method. 12. All exterior surface areas ofthe cylinders shall be free of corrosion, and if required, corrosion resistant paint shall be applied per manufacturer specification. I \ljp\tss RevF Reo;harSln8Fife Re1ard~1 Cylinder
7 MTA NEW YORK CITY TRANSIT DEPARTMENT OF BUSES TECHNICAL SERVICES SPECIFICAnON Code: S Rev. F Subject: Date: Recharging of the Fire Retardant Agent Cylinder 6/09/16 for the Fire Suppression System Page: 5 of Cylinders that have reached 12 years since date ofmanufacture shall be hydro-statically tested at pressure values shown in table # 2 for 30 seconds in accordance with the Compressed Gas Association (CGA) standard C-l "Methods for Hydrostatic Testing of Compressed Gas Cylinders" and follow guide line mentioned in CFR Kidde Cylinders are made under specifications DOT-3AL and Amerex cylinders are made under specifications 4BW. Table # 2 OEM Cylinder Size Hydrostatic Pressure Test (PSI) Amerex 13 Ibs 700 Amerex 25 Ibs 700 Kidde 221bs Each cylinder passing hydrostatic pressure test must be marked on exterior surface with legible retester's identification number (RIN) set in square pattern between month and year ofthe retest date as shown in figure I. The marking would be marked plainly and permanently into the metal ofthe cylinder with the location requirements ofthe cylinder manufacturing specification ill: on a metal plate permanently secured to the cylinder ill: OEM approved equivalent. Letter characters not less than 1/8" high. 5 ~: 5...,". 08 a I Fig. 1 I Example of Hydrostatic Test Marking: Above cylinder tested in "May 2008" and approved by a person who has been issued Retester Identification Number "A123"
8 MTA NEW YORK CITY TRANSIT DEPARTMENT OF BUSES TECHNICAL SERVICES SPECIFICAnON Subject: Recharging of the Fire Retardant Agent Cylinder for the Fire Suppression.System Code: S Rev. F Date: Page: 6/09/16 6 of If the unit failed during hydrostatic test, it shall be returned to the Salvage Department, Central Maintenance Facility, NYCT-DOB. When cylinder is found defective, the contractor shall stamp a series of 'X's over the DOT specification number and marked service pressure or stamp "CONDEMNED" on the shoulder, top head or neck using steel stamp. Tag the defective unit with brief description of defect. Return defective unit separately from good units. 16. Install a shipping plate to the top of the valve and anti-recoil plate to the valve outlet. 17. All serviced/recharged cylinders are to be completely assembled with new gaskets, seals, and O-rings. 18. Weigh the full extinguisher to 0.1 pound accuracy. Record empty weight, date and operator initials on the service tag and on the fill log sheet. 19. Apply anti-tamper paint to the fill valve cap, fill valve to body, dry chemical fill plug, gauge to body, squib to body, plug to body( If equipped) and valve to bottle joints see Figure 2. I Fig.2 I I Anti-temper Paint Marking 20. Deliver serviced/recharged cylinders back to designated NYCT-DOB/MTA Bus locations. Performance Requirements: I. All recharged/serviced cylinders shall maintain their operational and structural integrity for a guaranteed period of six (6) years. I \UP'ITSS _04 Rev F Recharging Fire Rellll'denl Cyllllder
9 MTA NEW YORK CITY TRANSIT DEPARTMENT OF BUSES TECHNICAL SERVICES SPECIFICAnON Subject: Recharging of the Fire Retardant Agent Cylinder for the Fire Suppression System Code: S Rev. F Date: Page: 6/09/16 7 of 10 SHER WARN BOTTLE ~ VALVE BODY c:n=1~ FILL VALVE ANTI-RECOIL PLUG PRESSURE GAUGE SHORTING PLU ~ SQUIB CONNECTOR ptq(j.uplube I Reference Only: Kidde Cylinder I \UPlTSS Rev F Re.;harpng FIre Retardem Cyllllder
10 MT A NEW YORK CITY TRANSIT DEPARTMENT OF BUSES TECHNICAL SERVICES SPECIFICATION Subject: Recharging of the Fire Retardant Agent Cylinder for the Fire Suppression System Code: S Rev. F Date: Page: 6/09/16 8 of 10 PRESSURE GAUGE SHIPPING PLATE AGENT CYLINDER VALVE RUPTURE DISC (UNDER CAP) ANTI-RECOIL PLATE AGENT CYLINDER DUST CAP I Reference Only: Amerex Cylinder I I \UI'\TSS S Rev F Recharging Fire Retardent Cylmder
11 MTA NEW YORK CITY TRANSIT DEPARTMENT OF BUSES TECHNICAL SERVICES Code: SPECIFICATION S Rev. F Subject: Date: ~3~ -l\l Recharging of the Fire Retardant Agent Cylinder 6/09116 for the Fire Suppression System Page: 9 of 10 REVISION INDEX e: DATE REV. PAGES DESCRIPTION OF REVISION REVISED NO. AFFECTED APPROVED 6/09/16 F 1) Revise application and added part numbers for Kidde and Arnerex cyjinders to the purpose. 2) Added cylinder OEM # & Model # identification. 3) Revise specific requirement as below a) Item # 3 for defective valve. b) Added Item # 4 for pressure gauge. c) Item # 6 for visual inspection and tagging instructions for defective cylinders. d) Item # 8 added standard # C-6 for Visual Inspection. c) Item # I I for leak check using soap and water. All f) Item # 13 added table for hydrostatic pressure test. g) Added item # 14 for cylinder marking. h) Added item # 15 for tagging defective cylinders and returns for hydrostatic test. i) Added item # 18 & 19 for service tag and anti- tamper paint application. j) Added reference only figures ofkidde and Amerex cylinders. 4122/1 6 General Requirements, item# 1 revised to include a Kidde E Dual Spectrum and/or Amerex certified contractor for recharging and servicina reouirernents. 1 ~ 11/19/15 General Requirements. item# 1 revised to include a Kidde D Qual Spectrum and Amerex certified-contractor for recharzinz and servicing requirements. 1 ~ e: Nomenclature changes to General Requirements ltems# I, 9110/14 C 2,3,4,5, and 6. Specific Requirements Items# 1,4,5,7, 1,2,3 10, and 13. Added items to General Requirements, Specific Requirements and replaced all items in Performance 1,2 Requirements with one item. 11/30/04 A Removed Item# 5 from General Requirements. I ~ 6120/07 B e. - Original issue. 11/7/03 - e: IIlJP\TSS S-~9-02_04 Rev F Re<.harg,ngfire Retardenl Cyllllder
12 MTA NEW YORK CITY TRANSIT DEPARTMENT OF BUSES TECHNICAL SERVICES SPECIFICAnON Subject: Recharging of the Fire Retardant Agent Cylinder for the Fire Suppression System Code: S Rev. F Date: Page: 6/09/16 10 of 10 Recommended for Approval: _.l...-~~;:::;:::=-!-~~;'-? ~~:::=:::-_ Daniel Cardoza Assistant Chief Maintenance Officer Technical Services and Engineering NYCT DOBI MTA Bus Approved by: --~'--J"----.,---,----""~---:------;fI---i'lI---- John Higgins Chief Maintenance <If'q~ Department ofbuses NYCT DOBI MTA Bus I.IUP1TSS RevF RechergmgFire Retardenl Cylinder
13 MTA - NEW YORK CITY TRANSIT 2 BROADWAY NEW YORK, NY DIVISION OF MATERIEL web.mta.info/nyct/procure/nyctproc.htm Vreplies@nyct.com NOTICE -OF ADDENDUM ADDENDUM #4 BID OPENING/DUE DATE: 08/23/2016
14 2 Broadway Veronique Hakim New York, NY President New York City Transit August 16, 2016 ADDENDUM NO.4 Contract No. IFB Maintenance & Testing Services for Fire Retardant Cylinders in the Fire Suppression Systems on Buses TO ALL PROSPECTIVE BIDDERS: This addendum is to notify all prospective bidders that the Bid Opening Date has been changed to Tuesday, August 23, 2016 at 2:00pm. Reminder: Be sure to acknowledge this Addendum in your bid. Failure to do so may result in rejection of your bid. '2;""11j:12 // GeO~R~ / Senior Dir tor MTA New York CityTransit is an agency of the Metropolitan Transportation Authority, State of New York
15 MTA - NEW YORK CITY TRANSIT 2 BROADWAY NEW YORK, NY DIVISION OF MATERIEL web.mta.info/nyct/procure/nyctproc.htm Vreplies@nyct.com NOTICE -OF ADDENDUM ADDENDUM #3 BID OPENING/DUE DATE: 8/17/2016
16 2 Broadway Veronique Hakim New York, NY President New York City Transit July 22, 2016 ADDENDUM NO.3 Contract No. IFB Maintenance & Testing Services for Fire Retardant Cylinders in the Fire Suppression Systems on Buses TO ALL PROSPECTIVE BIDDERS: You are hereby notified of the following change in this Solicitation: I. Please be advised that the Bid Opening Wednesday, August 17,2016 at 2:00 pm. Date has been changed to II. Schedule Q has longer applies. been removed from this solicitation, Bid Bonding no III. The following are questions received regarding the solicitation and the corresponding answers to those questions, which are made part of this Contract: (answers appear in Bold.) QI. We are approved vendors of Amerex and Kiddie, but we do not have a license in the city yet. Do we need to be licensed in NYC to recharge, 6 year or hydro? At. No. QI. When it comes to the inspections from the city who actually inspects the cylinders FDNY or DOT? A2. No city inspections are involved in this contract. Q3. In regards to the $10,000 bond, how soon after the bid is awarded to another vender would we receive our bond back? A3. The requirement for Bid Bonding has been removed. MTA New York City Transit is an agency of the Metropolitan Transportation Authority, State of New York
17 Solicitation No. IFB Addendum No.3 Please be advised that Addenda notification is sent via to the address each firm provided in e-bids. Bidders may obtain copies of all Addenda on the NYC Transit website. Reminder: Be sure to acknowledge this Addendum in your bid. Failure to do so may result in rejection of your bid. Sincerely, 9j~~1.IJI!I8 Thomas Spangen Senior Director Page 2 of2
18 MTA - NEW YORK CITY TRANSIT 2 BROADWAY NEW YORK, NY DIVISION OF MATERIEL web.mta.info/nyct/procure/nyctproc.htm Vreplies@nyct.com NOTICE -OF- ADDENDUM ADDENDUM # 2 BID OPENING/DUE DATE: POSTPONED
19
20
21 MTA - NEW YORK CITY TRANSIT 2 BROADWAY NEW YORK, NY DIVISION OF MATERIEL web.mta.lnfo/nyctjprocure/nyctproc.htm VreplleS@nyct.com NOTICE -OF ADDENDUM ADDENDUM #1 BID OPENING/DUE DATE: POSTPONED INDEFINITELY
22 2 Broadway Carmen Bianco New York, NY President II New York City Transit August 17,2015 ADDENDUM NO. I Contract No. IFB Maintenance & Testing Services for Fire Retardant Cylinders in the Fire Suppression Systems on Buses TO ALL PROSPECTIVE BIDDERS: Please be advised that the Bid Opening Date has currently been postponed indefinitely to allow additional time to answer questions from bidders. A subsequent addendum will be issued which will include the NEW Bid Opening Date. Please be advised that Addenda notification is sent via to the address each firm provided in e-bids. Bidders may obtain copies of all Addenda on the NYC Transit website. Reminder: Be sure to acknowledge this Addendum in your bid. Failure to do so may result in rejection ofyour bid. Sincerely, YiI. 1JtM1~~ Miriam Davidovich Contract Specialist, Procurement MTA New York City Transit is an agency of the Metropolitan Transportation Authority, State of New York
marta 2424 Piedmont Rd. N.E. Atlanta, GA
marta 2424 Piedmont Rd. N.E. Atlanta, GA 30324-3330 404-848-5000, February 20, 2013 TO ALL PLANHOLDERS SUBJECT: ADDENDUM NUMBER 1 PREVENTIVE MAINTENANCE AND REPAIR SERVICES FOR BUS FIRE SUPPRESSION AND
More informationCOUNTY OF ROCKLAND Department of General Services Purchasing Division
Department of General Services Purchasing Division Title: Contract Period: Fire Extinguishers and Suppression Systems-Inspection, Testing, Maintenance, Repair and Recharging 3/1/18 through 2/28/19 with
More informationPURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL
PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL NO. 05602 FOR AMEREX STORED PRESSURE, HAND PORTABLE DRY CHEMICAL FIRE EXTINGUISHERS. ABC (Ammonium Phosphate Base)
More informationMERAMEC VALLEY R-III SCHOOL DISTRICT 126 North Payne Street Pacific, MO
MERAMEC VALLEY R-III SCHOOL DISTRICT 126 North Payne Street Pacific, MO 63069 636-271-1400 REQUEST FOR PROPOSAL FIRE EXTINGUISHER/KITCHEN HOOD INSPECTIONS FOR ADDITIONAL INFORMATION CONTACT: Joel Cracchiolo,
More informationWHEELED STORED PRESSURE
OWNERS SERVICE MANUAL NO. 19795 INSTALLATION, OPERATING & SERVICING INSTRUCTIONS All fire extinguishers should be installed, inspected and maintained in accordance with the National Fire Protection Association
More informationOWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE
FOAM FIRE EXTINGUISHERS MODEL 254-6 LITER AFFF FOAM WITH SPRAY NOZZLE Model 250 2 ½ GAL.LON AFFF FOAM WITH ASPIRATED NOZZLE MODEL 252 2 ½ GAL.LON FFFP (ALCOHOL RESISTANT) FOAM WITH ASPIRATED NOZZLE OWNER'S
More informationF-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual
F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual 008094 All fire extinguishers should be installed, inspected and maintained in accordance with
More informationOWNERS SERVICE MANUAL NO INSTALLATION, OPERATING & SERVICING INSTRUCTIONS
STORED PRESSURE, WHEELED & STATIONARY 50 POUND DRY CHEMICAL FIRE EXTINGUISHERS ABC (AMMONIUM PHOSPHATE BASE), REGULAR (SODIUM BICARBONATE BASE), PURPLE K (POTASSIUM BICARBONATE BASE) OWNERS SERVICE MANUAL
More informationNOTE: THIS DOCUMENT IS FOR INFORMATIONAL PURPOSES ONLY. THIS IS NOT AN OFFICIAL BID DOCUMENT.
ANNUAL MAINTENANCE CONTRACT TO COVER FIRE EXTINGUISHER SERVICE FROM JULY, 208 THROUGH JUNE 30, 209 Supply labor and materials to perform annual maintenance service, inspection and certification for campus
More informationFIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES
FIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES FLS has organized the following information to act as a guideline/checklist for any inspection, maintenance, recharging and testing that
More informationFIre Extinguishers. K-GUARD Wet Chemical Fire Extinguishers Manual INSTALLATION 2014-DEC-29 REV. 03 PAGE 1 EXTINGUISHERS
K-GUARD Wet Chemical K-GUARD K-Guard WET CHEMICAL Wet Chemical EXTINGUISHERS FIre Extinguishers INSTALLATION 2014-DEC-29 REV. 03 PAGE 1 Installation, OPERATION, Recharge, and Maintenance Manual 004327
More informationREQUEST FOR QUOTES (RFQ) # Issue Date: September 21, 2017
Procurement Division Public Services Building 2051 Kaen Road Oregon City, OR 97045 (503) 742-5444 (Office) REQUEST FOR QUOTES (RFQ) #2017-66 Issue Date: September 21, 2017 Project Name: Quote Due Date/Time:
More informationSERVICE MANUAL (v1) UL / ULC. WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK
STRIKE FIRST CORPORATION AKC SERVICE MANUAL (v1) UL / ULC WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK All fire extinguishers should be installed, inspected
More informationAldine Independent School District Aldine Westfield Road Houston, Texas Phone (281)
Aldine Independent School District 14910 Aldine Westfield Road Houston, Texas 77032 Phone (281) 985-6265 Created on August 2007 ALDINE INDEPENDENT SCHOOL DISTRICT BUILDINGS AND PROPERTIES 14910 Aldine-Westfield
More informationCOMDTPUB P NVIC JUNE 1995
COMDTPUB P16700.4 NVIC 3-95 19 JUNE 1995 NAVIGATION AND VESSEL INSPECTION CIRCULAR NO. 3-95 Electronic Version for Distribution on the World Wide Web Subj: PERIODIC INSPECTION AND TESTING OF FIXED HALON
More informationHIGH PERFORMANCE HEAVY DUTY INDUSTRIAL STORED PRESSURE
HIGH PERFORMANCE HEAVY DUTY INDUSTRIAL STORED PRESSURE ABC (AMMONIUM PHOSPHATE BASE),Regular (SODIUM BICARBONATE BASE), PURPKE K (POTASSIUM BICARBONATE BASE) OWNERS SERVICE MANUAL NO. 0566 INSTALLATION,
More informationFIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT
SANTA MONICA FIRE DEPARTMENT Fire Prevention Division 333 Olympic Drive 2 nd Floor Santa Monica, CA 90401 310-458-8915 / Fax 310-395-3395 FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT
More informationTHIS ADDENDUM MUST BE ACKNOWLEDGED.
Denver Public Schools Purchasing Department 1350 East 33 rd Avenue Denver, Colorado 80205 INVITATION TO BID 13-MC-Fire Extinguisher ADDENDUM NUMBER ONE December 14, 2012 THIS ADDENDUM MUST BE ACKNOWLEDGED.
More informationOWNERS SERVICE MANUAL NO
OWNERS SERVICE MANUAL NO. 05608 INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS for AMEREX STORED PRESSURE WHEELED & STATIONARY 125/150 POUND DRY CHEMICAL FIRE EXTINGUISHERS WHEELED STATIONARY Model
More informationCOMPONENT MAINTENANCE MANUAL WITH ILLUSTRATED PARTS LIST
98 Columbus Street, Pointe Claire, QC, Canada H9R 4K4 info@caspaerospace.com www.caspaerospace.com T: 514-630-7777 F: 514-630-9999 HAND PORTABLE AIRCRAFT FIRE EXTINGUISHERS 3.0 lb. Halon 1211 Part No.
More informationOxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)
Oxnard Fire Department 360 W. Second Street Oxnard, CA 93030 (805) 385-7722 Fax (805) 385-8009 FIVE YEAR CERTIFICATION REPORT Service and maintenance report for automatic fire extinguishing systems, including
More informationTEXAS DEPARTMENT OF TRANSPORTATION PORTABLE FIRE EXTINGUISHER SERVICES ANNUAL INSPECTION MAINTENANCE, REPAIR, AND RECHARGING
TEXAS DEPARTMENT OF TRANSPORTATION SPECIFICATION NO. * PORTABLE FIRE EXTINGUISHER SERVICES ANNUAL INSPECTION MAINTENANCE, REPAIR, AND RECHARGING PUBLICATION This specification is a product of the Texas
More informationCOMPONENT MAINTENANCE MANUAL
MAINTENANCE INSTRUCTIONS WITH ILLUSTRATED PARTS LIST HALON 1/ 1.2/ 2.5 AIR TOTAL List of Portable Fire Extinguishers Part No. Type: 74-00 HAL 1.0 74-20 HAL 1.2 74-21 HAL 1.2 (LH) 74-22 HAL 1.2 (AF) 76-00
More informationAddendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017
Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD 21801 Ph. 410-548-4805 Fax 410-334-3130 Email: purchasing@wicomicocounty.org Addendum # 2 Wicomico County Circuit Court Second Floor
More informationBasic Vehicle Fire Protection Manual
Basic Vehicle Fire Protection Manual Basic Vehicle Fire Protection Manual TABLE OF CONTENTS Introduction... 3 System Operation...... 5 Component Overview.... 7 Operator Controls Control Panel.........
More informationOWNER'S OPERATION AND MAINTENANCE MANUAL
OWNER'S OPERATION AND MAINTENANCE MANUAL P/N 15064 Amerex Industrial Dry Chemical Fire Suppression System MODELS IS18ABC (18 lb. ABC) / IS35ABC (35 lb. ABC) / IS45ABC (45 lb. ABC) / Manufactured by: AMEREX
More informationSECTION WET-PIPE SPRINKLER SYSTEMS
SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition
More informationOWNERS SERVICE MANUAL
OWNERS SERVICE MANUAL NO. 08220 INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS for AMEREX MODEL 570 30 POUND (13.6 KG) CLASS D SODIUM CHLORIDE, STORED PRESSURE FIRE EXTINGUISHER FOR COMBUSTIBLE METAL
More informationJune 2018 Safety Meeting Fire Extinguishers Part I
June 2018 Safety Meeting Fire Extinguishers Part I The portable fire extinguisher, one of the most common fire protection appliances in use today, is found in fixed facilities and on propane vehicles.
More informationAnnual Fire Systems and Backflow Preventers Testing
Facilities Management Request for Qualifications Annual Fire Systems and Backflow Preventers Testing At Various Facilities Proposals Due: 2:30 PM, Tuesday May 15, 2018 Deliver to: Attn: Sara Winger, Purchasing
More informationTwin-Agent Fire Fighting/Securing Systems Specifications
Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50, 450/100, 900/100 & 1350/200 INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,
More informationSPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM
1. GENERAL SPECIFICATION 1.1 An Engineered Carbon Dioxide Fire Suppression System shall be installed to meet a minimum design concentration of %, by volume in all designated spaces/areas to be protected.
More informationThird Year Renewal of Three-Year Contract Bid # LR, Fire Extinguisher Service Maintenance Department Florida Fire Services, Inc.
Department of Purchasing 813/ 794-2222 Fax: 813/ 794-2111 727/ 774-2222 TDD: 813/ 794-2484 352/ 524-2222 e-mail: kgoodman@pasco.k12.fl.us December 12, 2007 MEMORANDUM TO: FROM: RE: Honorable School Board
More informationSUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING.
SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING Table of Contents Section Title Page 1 Introduction 2 2 Proposed Schedule 2 3 Instructions
More informationNOTICE INVITING TENDER
NOTICE INVITING TENDER Ref No.: SCOPEMINAR/MMO/18-19/183 Dated :- 06.12.2018 1. Online e-tenders are invited by Dy.General Manager, SCOPE on behalf of Constituents of SCOPE MINAR, Laxmi Nagar Delhi- 110092
More informationADDENDUM #1: MODIFICATIONS AND ADDITIONS TO CONTRACT DOCUMENTS
Annex Laundry and Shower Alterations ADDENDUM #1 March 7, 2019 ADDENDUM #1: MODIFICATIONS AND ADDITIONS TO CONTRACT DOCUMENTS A. Invitation to Bid - Call for Bids has been modified as follows: 1. Notice
More informationTABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5
DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING
More informationSubject: Addendum #3 IFB No CNG Gas Detection Repair and Maintenance
October 12, 2012 Subject: Addendum #3 IFB No. 112-12 CNG Gas Detection Repair and Maintenance Please be advised of the following questions and responses: 1. Question #1: If the MBTA Everett and Arborway
More informationCOMPONENT MAINTENANCE MANUAL
WITH ILLUSTRATED PARTS LIST HALON 1/ 1,2/ 2,5 AIR TOTAL List of Portable Fire Extinguishers Part No. Type: 74-00 HAL 1,0 74-20 HAL 1,2 74-21 HAL 1,2 (LH) 76-00 HAL 2,5 COMPONENT MAINTENANCE MANUAL TOTAL
More informationANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS
ANSUL Twin-Agent Fire Fighting/Securing Systems Specifications Models 450/50-B, 450/100-B, 900/100-B INDEX 1.0 GENERAL 1.1 References 1.2 Submittals 1.3 System Capabilities 1.4 Quality Control 1.5 Warranty,
More informationCITY OF PASADENA FIRE DEPARTMENT
Page 1 of 8 CITY OF PASADENA FIRE DEPARTMENT INSTALLATION OF COMMERCIAL SPRINKLERS (Revised 12/10/2014) SCOPE: This standard applies to the design and installation of automatic fire sprinkler systems in
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.13 Control Number: A.0 Effective Date: 11/15/11 TITLE:
More informationNORTH HILLS SCHOOL DISTRICT INVITATION TO BID GENERAL/SPECIAL CONDITIONS. Fire Extinguisher Inspection and Maintenance
NORTH HILLS SCHOOL DISTRICT INVITATION TO BID GENERAL/SPECIAL CONDITIONS Fire Extinguisher Inspection and Maintenance Due April 3, 2018 2:00 p.m. NORTH HILLS SCHOOL DISTRICT 135 SIXTH AVENUE PITTSBURGH,
More informationC. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.
SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this
More informationREVISION NO. 1 DATED SEPT 20/10 HIGHLIGHTS
COMPONENT MAINTENANCE MANUAL TO: HOLDERS OF THE FIRE EXTINGUISHER, DUAL OUTLET DUAL BYPASS SYSTEM 70 CUBIC INCH COMPONENT MAINTENANCE MANUAL,, DATED. REVISION NO. 1 DATED SEPT 20/10 HIGHLIGHTS THIS PUBLICATION
More informationNEW YORK CITY FIRE DEPARTMENT. Notice of Public Hearing and Opportunity to Comment on Proposed Rule
NEW YORK CITY FIRE DEPARTMENT Notice of Public Hearing and Opportunity to Comment on Proposed Rule What are we proposing? The Fire Department is proposing to comprehensively update Section 3004-01 of Title
More informationHydrostatic Retest Requirements for ANSUL Pressure Vessels
TECHNICAL BULLETIN Hydrostatic Retest Requirements for ANSUL Pressure Vessels Portables, Wheeled Units, and Pre-engineered Pressure Vessels One Stanton Street Marinette, WI 54143-2542, USA +1-715-735-7411
More informationPIP PCTPA001 Testing of Process Analyzer Systems
January 2016 Process Control PIP PCTPA001 Testing of Process Analyzer Systems PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice
More informationTEXAS DEPARTMENT OF TRANSPORTATION GENERAL SERVICES DIVISION LIGHT, WARNING, 360 DEGREE LED BEACON PUBLICATION
TEXAS DEPARTMENT OF TRANSPORTATION GENERAL SERVICES DIVISION DHT NO.: 165308 LIGHT, WARNING, 360 DEGREE LED BEACON PUBLICATION This specification is a product of the Texas Department of Transportation
More information*** Inspection *** Please identify yourself as a Cintas representative when arriving onsite.
Tech Clock-In/Out IVR: 1-877-349-2906 Job #: Tech ID #: 2902 FP Service Instructions Job #: *** Inspection *** You must clock in and out of this job through Cintas's IVR phone system! Call 1-877-349-2906
More informationREQUEST FOR PROPOSALS CLEANING SERVICES
REQUEST FOR PROPOSALS CLEANING SERVICES Jeffrey Gray City Manager City of Jonesville 265 E. Chicago Street Jonesville, MI 49250 manager@jonesville.org (517) 849-2104 Overview The City of Jonesville is
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.1 Control Number: I.0 Effective Date: 12/15/11 TITLE:
More informationDOCUMENT ADVERTISEMENT FOR BIDS
IFB 15-014 - 2015 Fire Alarm Upgrades for 4-15078 DOCUMENT 00 11 13 ADVERTISEMENT FOR BIDS 1.1 PROJECT INFORMATION A. Notice to Bidders: Qualified bidders may submit bids for project as described in this
More informationDEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS
DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS (By authority conferred on the director of the department of licensing and regulatory affairs by sections
More informationCOMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.
4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No. 2016-316 Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE
More informationGENERAL AREAS OF INSPECTION
This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that
More information5.07 Air Replenishment Systems
5.07 Air Replenishment Systems Reference: 2010 SFFC, Section 511.2 Definitions: CERTIFIED COMPRESSOR. A compressor used by a contractor for maintenance and testing of air replenishment systems that is
More informationAustin Independent School District Police Department Policy and Procedure Manual
Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for
More informationAMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER
AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER The 2016 Denver Building and Fire Code includes the following codes except as amendment herein. 2015 IBC (Building) 2015 IFC (Fire)
More informationDesign & Construction Standards, Revised January
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.
More informationADDENDUM NO. 3 March 19, 2018
ADDENDUM NO. 3 March 19, 2018 PROJECT: MT. VIEW ELEMENTARY CASSIA SCHOOL DISTRICT NO 151 BURLEY, IDAHO The following addenda apply to the Project Manual and / or Drawings for this project and shall be
More informationSECTION ELECTRIC-DRIVEN, FIRE PUMPS
SECTION 21 30 13 ELECTRIC-DRIVEN, FIRE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between // --- // if not applicable to the project. Also delete any other item or paragraph including
More informationENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS
ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered
More informationFIRE SUPPRESSION SPRINKLER SYSTEM
PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 3 Page 1 of 6 I. PURPOSE This policy establishes the steps required for performing the monthly fixed systems inspections and the semi-annual systems testing. Fixed systems include; wet chemical
More informationTechnical Data Sheet No. JS-SM-40 DOCUMENT TITLE 2.0 LITRE STORED PRESSURE WET CHEMICAL FIRE EXTINGUISHER
PAGE: ISSUE: DATE: of A 00 07285 DOCUMENT TITLE 2.0 LITRE STORED PRESSURE WET CHEMICAL FIRE EXTINGUISHER MODELS: R2WC 0 07285 ISSUE A FIRST RELEASE NEW DOCUMENT WJJ LRL LHG REV DATE REVISION DESCRIPTION
More informationRevised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*
1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system
More informationAUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)
AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with
More informationNew Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationUNIVERSITY. Facilities Management
EAST TENNESSEE STATE UNIVERSITY Facilities Management Policy Number: 700.10 Title: Fire Protection Impairment Program Implementation Date: April, 2008 Last Revised: August 4th, 2014 Introduction The probability
More informationInternational Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures
International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project
More informationHYDROSTATIC TEST INSTRUCTIONS
HYDROSTATIC TEST INSTRUCTIONS STORED PRESSURE PORTABLE FIRE EXTINGUISHERS One Stanton Street / Marinette, WI 54143-2542, USA / +1-715-735-7411 Copyright 2017 Tyco Fire Products LP. All rights reserved.
More informationWELDING, CUTTING, AND BRAZING SAFETY PROGRAM
WELDING, CUTTING, AND BRAZING SAFETY PROGRAM HOT WORK TABLE OF CONTENTS 1.0 Introduction 1.1 Purpose 1.2 Scope 2.0 Responsibilities 2.1 Building Office 2.2 Building Personnel 2.3 Individuals Performing
More information1. Delete BID FORM in its entirety and replace with the BID FORM attached to this Addendum.
ADDENDUM NO. 2 TO THE BIDDING DOCUMENTS Solicitation Number 2016-13 Fire Alarm, Sprinkler & BFP Inspections and Repairs Saint Clair County MidAmerica Saint Louis Airport DATE: November 30, 2016 BIDS CLOSE:
More information11 CONTRACT AWARD FOR SECURITY SERVICES
11 CONTRACT AWARD FOR SECURITY SERVICES The Finance and Administration Committee recommends the adoption of the recommendations contained in the following report dated November 3, 2011, from the Commissioner
More informationFire Sprinkler Submittal Requirements and Acceptance Testing
Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 fireprevention@mylubbock.us Fire Sprinkler Submittal Requirements and Acceptance Testing To all Registered
More informationSECTION WET-PIPE SPRINKLER SYSTEMS
SECTION 21 13 13 PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The design and installation of a hydraulically
More informationRequest for Bid Proposal For Repair of Sprinkler Systems Iowa Veterans Home Marshalltown, Iowa
The is seeking a service provider to correct the deficiencies of the fire sprinkler system as identified during a standard inspection. Deficiencies will be corrected per NFPA 25 in the buildings located
More informationPROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS
SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationROSWELL INDEPENDENT SCHOOL DISTRICT P.O. Box 1437 Roswell, New Mexico General Bid Conditions
ROSWELL INDEPENDENT SCHOOL DISTRICT P.O. Box 1437 Roswell, New Mexico 88202-1437 General Bid Conditions BID # 19-06 Fire Sprinkler Systems Inspections, Testing and Maintenance SEALED BIDS will be opened
More informationSPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM
1. GENERAL SPECIFICATION 1.1. A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated
More information2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7
WET SPRINKLER Monthly Wet Sprinkler 2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 VISUALS [per NFPA 25-1998 ed] 1. Gauge (Ck for Condition, Normal Pressure) [per 2-2.4.1] 2. Valves
More informationSECTION FIRE-SUPPRESSION STANDPIPES
PART 1 - GENERAL 1.1 DESCRIPTION Fire-suppression wet and manual dry standpipes. 1.2 SCOPE OF WORK SECTION 21 12 00 A. Design, installation and testing shall be in accordance with NFPA 14 except for specified
More informationADDEDUM NOTICE Addendum #1 has been issued
Raymore-Peculiar School District Fire Alarm Monitoring/Inspection Date: 06-01-2017 Project: Fire Alarm/Intrusion Monitoring and Inspection/Maintenance Services Bid Date and Time: June 8, 2017 10:00am ADDEDUM
More informationItem No. Description 1. BID PROPOSAL FORM Make the following revisions: a. Replace the BID PROPOSAL FORM with the attached BID PROPOSAL FORM.
City of Raleigh, Fire Station No. 11 Renovation September 28, 2018 274-CM2018-15A Page 1 HUFFMAN ARCHITECTS, PA 632 PERSHING ROAD RALEIGH, NORTH CAROLINA 27608 PHONE (919) 740-5669 TO: ALL PRIME BIDDERS
More informationModel Policy On Portable Fire Extinguishers (Ontario Version)
Model Policy On Portable Fire Extinguishers (Ontario Version) Every workplace needs a policy ensuring the appropriate selection, use, storage and maintenance of fire extinguishers. OHS managers in any
More informationEX-TECH SIGNALLING SAS SD100-1 WEATHERPROOF SOUNDER/HORN TECHNICAL MANUAL
PRODUCT NAME: SD-100-1- WEATHER-PROOF SOUNDER/HORN DOC NO.: EX-TECH SIGNALLING SAS-12-SD100-1-TM REV03 WEATHERPROOF SOUNDER/HORN IP66 SD-100 SERIES EX-TECH SIGNALLING SAS SD100-1 WEATHERPROOF SOUNDER/HORN
More informationGUILFORD COUNTY SCHOOLS
GUILFORD COUNTY SCHOOLS Fire Extinguisher Plan Policy In accordance with the regulations established by the United States Department of Labor pursuant to the Occupational Safety and Health Act and the
More informationNASSAU COUNTY FIRE PROTECTION PERMIT APPLICATION
BUILDING PERMIT# Revised 6/30/15 AP# PERMIT # Cost $ Check# Receipt# NASSAU COUNTY FIRE PROTECTION PERMIT APPLICATION 5 TH EDITION (2014) OF THE FLORIDA BUILDING CODE IS IN EFFECT THE 2012 FLORIDA FIRE
More informationBrunswick-Glynn County Joint Water & Sewer Commission
Brunswick-Glynn County Joint Water & Sewer Commission INVITATION FOR BIDS DATE: 18 August 2015 PROJECT: Academy Creek Sludge Dryer Repairs 1.0 PROJECT DESCRIPTION The Brunswick-Glynn Joint Water & Sewer
More informationBUREAU OF INDIAN STANDARDS ( CENTRAL MARKS DEPARTMENT-III ) Our Ref: CMD-III/16:
BUREAU OF INDIAN STANDARDS ( CENTRAL MARKS DEPARTMENT-III ) Our Ref: CMD-III/16:2878 03-12-2007 Subject: Implementation of Amendment No 4 August 2007 to IS 2878:2004 For Fire Extinguishers, Carbon Dioxide
More informationA. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.
1. GENERAL SPECIFICATION 1.1 A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated
More informationDRY CHEMICAL AND CLEAN AGENT HAND PORTABLE FIRE EXTINGUISHERS
DRY CHEMICAL AND CLEAN AGENT HAND PORTABLE FIRE EXTINGUISHERS OPERATION, RECHARGE, INSPECTION, AND MAINTENANCE MANUAL 000769 One Stanton Street / Marinette, WI 54143-2542, USA / +1-715-735-7411 Copyright
More informationBusiness License Pre-inspection Checklist
Business License Pre-inspection Checklist August, 2016 Alberta Fire Code business license pre-inspection and annual checklist This checklist provides business owners with Alberta Fire Code requirements
More informationSPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection
1. GENERAL SPECIFICATION 1.1 A total flooding, Novec 1230 fluid, fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in
More informationFIRE EXTINGUISHER SERVICING & MAINTENANCE INSTRUCTIONS
BRITANNIA RANGE FIRE EXTINGUISHER SERVICING & MAINTENANCE INSTRUCTIONS Cartridge Operated Water Based Models Page 1 of 5 SPINTRO REV 6 October 2017 PROCEDURES FOR SERVICING THE BRITANNIA RANGE OF HAND
More informationAMENDMENT NO.: III INVITATION FOR BID NO.: GPA FOR
January 26, 2018 AMENDMENT NO.: III TO INVITATION FOR BID NO.: GPA-022-18 FOR PHYSICAL SECURITY AND ACCESS CONTROL SYSTEM (ACS) REPAIR AND UPGRADE AT VARIOUS GPA LOCATIONS Prospective Bidders are hereby
More informationD. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe
More informationSCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF PORTABLE FIRE EXTINGUISHER- PERFORMANCE AND CONSTRUCTION AS PER IS 15683: 2006
SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF PORTABLE FIRE EXTINGUISHER- PERFORMANCE AND CONSTRUCTION AS PER IS 15683: 2006 1. LABORATORY 1.1 A Laboratory shall be maintained which shall be suitably
More informationTRAINING BULLETIN TOOLS 1 May 27, 2011 PRESSURIZED WATER EXTINGUISHER
TRAINING BULLETIN TOOLS 1 May 27, 2011 1. DESCRIPTION Weight is approximately 30 lbs. Water 2½ gallons. Operating Pressure: 100 psi @ 70 degrees F. Note: Water expelled in 55 seconds. Stainless Steel Cylinder
More information