1 CITY OF FARMINGTON 800 Municipal Drive Farmington, NM (505) Fax (505) IMMEDIATE ATTENTION Construction Services for Municipal Operations Center Expansion BID # ADDENDUM TWO April 15, 2016 Notice to Bidders: The above referenced bid is hereby amended as follows: The following are the questions received with the answers immediately following: 1. Site Grading Plan sheet C1.2, note 3 calls out 4 minimum new asphalt millings, while Site Improvements Plan sheet C1, note 8 calls out new 3 asphalt paving. It s not clear where new asphalt ends and asphalt millings starts. A1: For asphalt and millings location Sheet C1.2 is correct. 2. Demolition Keyed Note E on sheet C3.1 calls out saw cut and removal of existing asphalt, but the note points to the existing irrigation line. A2: Delete Note E. 3. Acoustical Ceiling tile Specification section , paragraph 2, part 2.3 A is calling for a 2X4 washable white vinyl tile Armstrong A769. However, the Armstrong Cortega A769 is a generic tile, not vinyl. Please clarify. A3: Delete reference to washable white vinyl. 4. Guard Rail at Interior Stairs: Please provide detail for guard rail at interior stairs. A4: Install 1½ ɸ pipe rail each side of stair. Extend past top and bottom tread Sheet S2.1, Wind Beam The roof framing plan for Building #2 shows wind beam WB-1 and WB-2. WB-1 is a W8x18 wide flange beam. Please provide size beam for WB-2. A5: Wind beam WB-2 W8x Are we to include a wall mounted steel ladder for access to the roof hatch in building #1? A6: No.

2 7. The civil drawings and structural drawings show a portion of Building #4 to be included in the base bid. Please advise if any of building #4 is to be included in the base bid or if all of Building #4 is part of Alternate #1. A7: Building #2 - Entire Building is an Alternate. 8. Please confirm the city will provide power up to and including the transformers, and we are only to include power from the transformers to buildings #1 and #3 (base bid) and building #4 (alternate #1). A8: Yes. FEUS will supply power up to and including the transformers. All service work from transformers should be included in proposal. 9. Please confirm the city will provide communications, including raceways and cabling to the buildings. A9: COF will provide an overhead fiber line for communications up to the utility pole located at the NW corner of the property. 10. Please advise if we are to provide the concrete pads for the transformers. A10: No. 11. Please confirm the contractor is to remove and relocate the light pole (note C on C1.1 and note 5 on C1.2) and the city will remove and relocate the overhead power line to the light pole. A11: FEUS will remove existing light pole and associated secondary line. 12. Please confirm CH2M will be providing and installing the site water line, new water meter, new fire hydrant and new 6 fire line as shown on sheet C1. A12: Contractor to install fire line, fire hydrant, domestic water line. CH2M will install water. Contractor to pay for meter. 13. Site Improvements Plan sheet C1, note 12, location for new fire hydrant what size water line to fire hydrant? Is this by CH2M? A13: 6 inches. 14. Please confirm our bid is to include the cost of CH2M s work described above. A14: No. 15. Sheet C1.2 note 3 install 4" min asphalt millings and C2.1 note 4 calls for 21/2 paving over 8" base course sheet C3.1 note 1 calls for same paving as note 4 on C2.1 what note is to be followed? A15: City is installing asphalt and providing millings.

3 16. In buildings 1 and 4 require a fire riser there is no location or detail provided. A16: Building #1 - Install between OHD and Door 102. Building #4 - Install in Southwest. 17. Who will be providing the millings? A17: City of Farmington. 18. If the irrigation line interferes with construction what is the plan to shut line down during irrigation season? A18: We will coordinate for shutdown to tie in. 19. Sheet A2.1 relay storage shows a 12x12 overhead door and sheet A2.2 shows a 12x14 the eave is not tall enough to accommodate the 12x14 door. A19: Door is 12x There is no water entry detail provided. A20: See Sheet P Is the CMU block to be a standard grey or colored? A21: South wall of Building #1 and East and North wall of Building #4 to be split face to match main Municipal Operations Center building. Rest is regular gray. 22. Who will be taking care of the communications for this project? A22: The City of Farmington will handle this internally. 23. Sheet E3.1 building #3 panel 3 shows 30 amp circuits feeding GFCI receptacles that are only 20 amp rated. A23: Sheet E3.1. Building #3. Panel 3 shows 30amp circuits feeding GFCI receptacles that are only 20amp rated. Response: The direction provided to us by the City of Farmington is that the block heaters require a 30amp, 120VAC branch circuit. The symbol used is for a 20amp, 120VAC duplex outlet. The contractor shall include in his bid for providing a 30amp, 120VAC receptacle, which shall be coordinated with the City of Farmington prior to ordering and installation. 24. Sheet E3.1 building 3 what controls the lighting? A24: Sheet E3.1. Building #3. What controls the lighting? Response: The light fixtures (type SL1 or SL2) in this area are specified with on-board occupancy sensors mounted integral to the fixtures. See light fixture schedule, Sheet E Sheet E1.2 (RT-2 shows that it's being fed from Panel 2 ckts 9, 11, 13. Also MA:1 shows that it is being fed from panel 2 ckts 8, 10, 12, and appears to be located at building 1. A25: Sheet E1.2. (RT-2 shows that it s being fed from Panel 2 ckts 9, 11, 13. Also MA.1

4 shows that it is being fed from Panel 2 ckts 8, 10, 12, and appears to be located at Building #1. Response: Panel P2 is located near the Building #1 addition and has more space available in it to serve two rooftop units. Sheet E0.1. Electrical General. 1. Fire alarm system shall be as manufactured by Honeywell, Vista-250FBP (no exception) to match the cities standard. The contractor shall disable the remote dial-in feature. 2. Provide all manual pull stations with covers as per the Farmington Fire Marshall requirements. 3. It is the design intent for all fire alarm cabling to be installed within conduit. Exposed cabling shall not be acceptable. 26. Specification section is for sheet metal roofing, yet we cannot locate where this material is in the drawings. Can you let me know if there is any sheet metal roofing in this project? If so, I would like to submit a prior approval for the material, and I need to do that in the next day or so. A26: Sheet A3.2. Building #3 has metal roof. Metals specified in Section gauge. 27. Can TPO be bid for all roofs instead of putting metal panels on such a low sloped roof? A27: Sheet A3.2. TPO can be substituted for metal panels. 28. Is there to be a ¼ substrate board on TPO assemble? A28: Yes. 29. Do we provide R-20 or R25 for the insulation? A29: R-20 CHANGE: Listed below are revisions to the technical specifications. The changes made are as follows: Specification Section In Section ¾ Insulated Translucent Fiberglass Sandwich Panel Wall System, 2.2 PANEL COMPONENTS, 4. Appearance:, a. Exterior face sheets: Smooth.070 thick and crystal in color.; and b. Interior face sheets: please revise to Interior face sheets: Smooth.045 thick and crystal in color. 2. In Section ¾ Insulated Translucent Fiberglass Sandwich Panel Wall System, 2.3 PANEL CONSTRUCTION, A.2 Light transmission: revise to 30%. 3. In Section ¾ Insulated Translucent Fiberglass Sandwich Panel Wall System, 2.4 BATTENS AND PERIMETER CLOSURE SYSTEM, D. Finish: revise Manufacturer s factory applied finish, which meets the performance requirements of AAMA Color to be selected from manufacturer s standards.

5 Specification Section Hardware Group #5: Add Door 500. Specification Section Delete existing hardware schedule. Insert schedule attached to this addendum. Sheet A2.1. Room 300. Relay Storage. Install 2 layers R-19 insulation using the basket system. Delete Detail A/S1.3. Earthwork shall follow Geotechnical Report by Geomat. Sheet M1.2. Building #2. Plumbing Plan should be Sheet P1.2. Sheet E0.1. Electrical General. 1. Fire alarm system shall be as manufactured by Honeywell, Vista-250FBP (no exception) to match the cities standard. The contractor shall disable the remote dial-in feature. 2. Provide all manual pull stations with covers as per the Farmington Fire Marshall requirements. 3. It is the design intent for all fire alarm cabling to be installed within conduit. Exposed cabling shall not be acceptable. Sheet E1.1. Building #1. Power Plans and Details. 1. Breakroom 201. Provide contactors for shutdown or the range outlet (P1-65, 67) and hood fan (P1-30) upon fire suppression system activation. Mount the contactors above the ceiling over the hood where they will be acceptable. Sheet E2.1. Building #2. Electrical Plans. 1. Storage 301 and 302. Remove ceiling mounted occupancy sensors. Revise fixtures to Type SL2. Sheet F1.1. Building #1. Fire Alarm Plans. 1. Work/Storage 102. Provide a second pull station at the exterior door on the west side of the building. 2. Delete duct mounted smoke detectors for RTU-2 and MAU-1. Sheet F5.1. Building #4. Fire Alarm Plan and Details. 1. Work/Storage 102. Provide a second pull station at the exterior door on the west side of the building.

6 It is the intent of the design for the contractor to coordinate with the City of Farmington for the placement of the transformer, but the transformer will be installed by the City of Farmington. The contractor will extend service to the buildings from the new service transformers. The contractor will be required to provide conduit to Building #1 from the nearby utility pole. Phone service to Building #1 will be via the local phone utility. CHANGE: Attached is a list of approved substitutions. Receipt of this addendum shall be noted on Form AF-1 (a) in Tab I Bidding Requirements for the above referenced bid. If your bid has already been submitted to this office, and this addendum will affect your bid quote, please contact this office and we will return your bid. Any bids that have been received, and are not requested to be returned will remain in this office unopened until April 27 at 2:00 p.m. /s/ Emily Milne Emily Milne Buyer ll Phone: (505) Fax: (505) emilne@fmtn.org

7 APPROVED SUBSTITUTIONS: Sections Johns Manville and Carlisle Curries Major Industries Quadian Old Castle Arcadia Manko DL GL GLE SL SL1 SL2 Liton, Prescolite (2000 Lumen) Daybrite with 0-10 dimming, Columbia WL Daybrite with 4000 K, Columbia (4000 K) WL1 (4000 K) EM OWE P1 P1 Pole Evenlite, Compass LSI, Spaulding LSI, Spaulding LSI, Spaulding Lighting Controls Hubbell Control Solutions, Leviton

RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan

RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan ADDENDUM NO. 2 RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan TO: All Bidders Gentlemen: You are hereby directed to make the following changes in the Project Manual and/or

More information

NOTICE TO ALL FIRMS. Bid RFI Questions and Answers

NOTICE TO ALL FIRMS. Bid RFI Questions and Answers Purchasing Department 227 West 27 th Street New York, NY 10001 Purchasing Dept. Tel. 212-217-3630 Purchasing Dept. Fax 212-217-3631 Purchasing@fitnyc.edu NOTICE TO ALL FIRMS Date: March 8, 2018 To: From:

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

Springpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp.

Springpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp. Volume 1 Bidding Requirements, Contract Forms, Conditions of the Contract, Division 1, Architectural and Site Specifications 000107 Certification Page 000110 Table of Contents DIV00 PROCUREMENT AND CONTRACTING

More information

Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc.

Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc. Memphis Housing Authority High Rise Fire Alarm Upgrades Questions from Contractors (Through Addendum #2) Communications Systems, Inc.: Legend 1. DL - Dome light symbol should be on the tenant emergency

More information

HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California ADDENDUM NO. 3

HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California ADDENDUM NO. 3 HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California 95833 September 15, 2016 Woodland Joint Unified School District Spring Lake Area Elementary School HMC No. 3535003.000 DSA Appl.

More information

PROJECT NO. CWA SEPTEMBER 24, 2014 ADDENDUM NO. 6 BESSEMER RECREATION & WELLNESS CENTER

PROJECT NO. CWA SEPTEMBER 24, 2014 ADDENDUM NO. 6 BESSEMER RECREATION & WELLNESS CENTER PROJECT NO. CWA 2013-04 SEPTEMBER 24, 2014 ADDENDUM NO. 6 BESSEMER RECREATION & WELLNESS CENTER BIDS RECEIVED: CITY HALL, CITY OF BESSEMER TIME: 2:00pm DATE: October 2, 2014 City of Bessemer --------------------------------------------------------------------------------------------------------------------------------------------

More information

Additions & Alterations to Ascension Parish Library Galvez Prairieville, Louisiana Project No. 1401

Additions & Alterations to Ascension Parish Library Galvez Prairieville, Louisiana Project No. 1401 Henry L. Chauvin, Architect, LLC 9429 Highway 941 Gonzales, Louisiana 70737 (225) 612-0707 Fax: (224) 612-4565 Email: henry.chauvin@outlook.com Additions & Alterations to Ascension Parish Library Galvez

More information

Sidney, Ohio 1204 FORMAL ISSUANCE OF CERTIFICATE OF SUBSTANTIAL COMPLETION... ON OR BEFORE JULY 30, 2015.

Sidney, Ohio 1204 FORMAL ISSUANCE OF CERTIFICATE OF SUBSTANTIAL COMPLETION... ON OR BEFORE JULY 30, 2015. SECTION 000050 - INVITATION AND NOTICE TO BIDDERS PROJECT: OWNER: 3003 Cisco Road Sidney, Ohio 45365 Ohio Presbyterian Retirement Services 1001 Kingsmill Parkway Columbus, Ohio 43229 ARCHITECT: 4685 Larwell

More information

SANTA FE COUNTY IFB# PW/KE CONSTRUCTION FOR THE SANTA FE MOUNTAIN CENTER KITCHENETTE AND OFFICE SPACE ADDENDUM #2

SANTA FE COUNTY IFB# PW/KE CONSTRUCTION FOR THE SANTA FE MOUNTAIN CENTER KITCHENETTE AND OFFICE SPACE ADDENDUM #2 Henry P. Roybal Commissioner, District 1 Anna Hansen Commissioner, District 2 Robert A. Anaya Commissioner, District 3 2017-0262-PW/KE Anna T. Hamilton Commissioner, District 4 Ed Moreno Commissioner,

More information

9 E. Scarborough Park Concession Stand and Restroom And / Or Lake Kirby Park Softball Fields Restroom Addition

9 E. Scarborough Park Concession Stand and Restroom And / Or Lake Kirby Park Softball Fields Restroom Addition Addendum NO. 1 Issue Date: October 20, 2016 Project: City of Abilene 10 20 2016 Scarborough Park Concession Stand and Restroom And / Or Lake Kirby Park Softball Fields Restroom Addition I WILL STAT AMR.DUNCA

More information

GENERAL ASSIGNMENT CLASSROOM DESIGN STANDARDS

GENERAL ASSIGNMENT CLASSROOM DESIGN STANDARDS University of Iowa FSG - Design & Construction Services Design Reference Manual 2 Design Standards 2.02 Classroom Design Standards Classroom Design Standards GENERAL ASSIGNMENT CLASSROOM DESIGN STANDARDS

More information

2 Main Office Building BLDG-955A Building Purpose Building Area Administration offices. Training room 7,610 SF Inspection Date August 16, 2016 Inspect

2 Main Office Building BLDG-955A Building Purpose Building Area Administration offices. Training room 7,610 SF Inspection Date August 16, 2016 Inspect 1 Site Summary Address 7200 Bluff Springs Road Austin, TX 78744 Number of Permanent Campus Facilities 2 Original Year of Construction 2014 Total Campus Building Area (combined) 25,314 SF Introduction The

More information

BID INFORMATION LIST Crossroads East N. Scottsdale Road, #105 Scottsdale, AZ Rev

BID INFORMATION LIST Crossroads East N. Scottsdale Road, #105 Scottsdale, AZ Rev BID INFORMATION LIST Crossroads East 18511 N. Scottsdale Road, #105 Scottsdale, AZ 85255 Rev.1 12-20-17 SITE CONTACTS: LANDLORD CONSTRUCTION CONTACT Diversified Partners Kevin Gantner Office - (480) 947-8800

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT ELECTRICAL POWER AND TRANSMISSION INSTALLERS. Test Code: 5922 Version: 01

CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT ELECTRICAL POWER AND TRANSMISSION INSTALLERS. Test Code: 5922 Version: 01 CUSTOMIZED TEACHER ASSESSMENT BLUEPRINT ELECTRICAL POWER AND TRANSMISSION INSTALLERS Test Code: 5922 Version: 01 Specific competencies and skills tested in this assessment: Basic Safety Identify career

More information

FIRE AND SAFETY PROJECT REVIEW REPORT

FIRE AND SAFETY PROJECT REVIEW REPORT 1. A001 2. A001 3. A001 4. D102/103 5. A102/103 *VA enforces/applies the National Fire Protection Association (NFPA) 101 (current edition is 2015) and not the International Building Code (IBC). Ideally

More information

ARCHITECT S PRE-BID ADDENDUM

ARCHITECT S PRE-BID ADDENDUM ARCHITECT S PRE-BID ADDENDUM 14203 487 Main Street Suite 500 Buffalo, New York Addendum No: 001 Date Issued: Feb. 8, 2019 Project: The West End (CWM Project No. 18.122) Location: 240-260 Lakefront Blvd.

More information

ELECTRICAL SYMBOLS AND ABBREVIATIONS NOT ALL SYMBOLS, DEVICES OR ABBREVIATIONS MAY BE USED

ELECTRICAL SYMBOLS AND ABBREVIATIONS NOT ALL SYMBOLS, DEVICES OR ABBREVIATIONS MAY BE USED SYMBOLS AND ABBREVIATIONS ABBREVIATIONS GENERAL NOTES LINE TYPE LEGEND CIRCUITS TELECOMMUNICATION SYSTEM ING EQUIPMENT POWER DEVICES FIRE ALARM SYSTEM NOT ALL SYMBOLS, DEVICES OR ABBREVIATIONS MAY BE USED

More information

ADDENDUM NO. 1. for. MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140. Marquette, Michigan.

ADDENDUM NO. 1. for. MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140. Marquette, Michigan. ADDENDUM NO. 1 for MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140 Marquette, Michigan December 12, 2016 TO: ALL BIDDERS OF RECORD This addendum forms a part of

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

PLATTEVILLE MIDDLE SCHOOL

PLATTEVILLE MIDDLE SCHOOL Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle

More information

Procurement Department ADDENDUM # 1

Procurement Department ADDENDUM # 1 To: 1012-909-62-3408 RFP for: Unit Make Ready Services Procurement Department ADDENDUM # 1 Change the closing date as follows: Responses are due 11:00a.m. Tuesday, March 15, 2011. Please note the following

More information

Addendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017

Addendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017 Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD 21801 Ph. 410-548-4805 Fax 410-334-3130 Email: purchasing@wicomicocounty.org Addendum # 2 Wicomico County Circuit Court Second Floor

More information

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Facility Condition Assessment Summary Report British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Submitted by: VFA Canada Corp. Burnaby Centre 4211 Kingsway Burnaby, BC V5H 1Z6

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

Commercial Application/Plan Review Submittal Checklist

Commercial Application/Plan Review Submittal Checklist Commercial Application/Plan Review Submittal Checklist The following checklist has been compiled to assist in expediting the commercial plan review and permit issuance process. Please take a moment to

More information

DESIGN & CONSTRUCTION GUIDELINES

DESIGN & CONSTRUCTION GUIDELINES ADMINISTRATIVE SERVICES 4202 E. FOWLER AVENUE, FPC110 PHONE: (813) 974-2625 FACILITIES PLANNING & CONSTRUCTION TAMPA, FLORIDA 33620-7550 WEBSITE: USF.EDU/FPC DESIGN & CONSTRUCTION GUIDELINES DIVISION 21

More information

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR 5/9/18 Procurement Towson University 8000 York Road Towson, MD 21252-0001 t. 410 704-2171 f. 410 704-8233 Ladies and Gentlemen:

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT

More information

Yes, any other system must be clean agent, and the Fire Alarm Control Panel must be a single addressable Fire Alarm Control Panel.

Yes, any other system must be clean agent, and the Fire Alarm Control Panel must be a single addressable Fire Alarm Control Panel. Please respond to: SB-8 Mayo Building Tallahassee, Florida 32399 TO: FROM: RE: Vendors Christie Hutchinson, Purchasing Director INVITATION TO BID NUMBER ITB/PI-12/13-53 INSTALLATION OF A FIRE SUPPRESSION

More information

PLAN REVIEW SUBMITTAL GUIDE

PLAN REVIEW SUBMITTAL GUIDE PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,

More information

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963) INFORMATION BULLETIN / PUBLIC - MECHANICAL CODE REFERENCE NO.: LAMC 91.8604 Effective: 6-20-84 DOCUMENT NO. P/MC 2002-005 Revised: 6-15-00 Previously Issued As: MGD #74 FIRE SAFETY REQUIREMENTS FOR PRE-

More information

Maintence/Renewal Report

Maintence/Renewal Report Maintence/Renewal Report Property Address: C4U Inspections Lloyd Kenzle CPBC # 47652 3518 Webber Rd. West Kelowna, BC V4T 1H9 866 765-4434 Table of Contents Cover Page... 1 Table of Contents...2 I SUMMARY...

More information

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors 1. SUMMARY AND BACKGROUND: Princeton Joint Unified School District located in Princeton

More information

ADDENDUM NO. 1. PREPARED BY: Justin Scott DATE PREPARED: 05/25/2018. PROJECT: Centerville-Washington Park District Park Operations Facility

ADDENDUM NO. 1. PREPARED BY: Justin Scott DATE PREPARED: 05/25/2018. PROJECT: Centerville-Washington Park District Park Operations Facility ADDENDUM NO. 1 PREPARED BY: Justin Scott DATE PREPARED: 05/25/2018 PROJECT: Centerville-Washington Park District Park Operations Facility PROJECT NO.: 2017-051 OWNERS REPS: Ken Carter Nick Meyer COPIES

More information

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing

More information

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO Prepared For: Public Schools Facilities Authority State of New Mexico 2019 Galisteo, Suite

More information

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler

More information

This addendum responds to initial questions submitted by vendors. A1. Batteries are to be invoiced separately under the cost plus.

This addendum responds to initial questions submitted by vendors. A1. Batteries are to be invoiced separately under the cost plus. 5761 Keyo Building Orono, ME 04469-5761 Main:207-581-2712 ldd/tdy:207-973-3262 www.maine.edu REQUEST FOR PROPOSALS #030-17 University of Southern Maine Scheduled Testing, Inspection & Cleaning of Life

More information

Community Development Department Commercial Permit Application

Community Development Department Commercial Permit Application Commercial Permit Application Permit # Property Project Information Address Suite # Business Name Parcel # Fire Department County Type of Improvement (check all that apply) New Addition Alteration Repair

More information

6. ENGINEERING SYSTEMS REQUIREMENTS H50 WATERFRONT UTILITIES

6. ENGINEERING SYSTEMS REQUIREMENTS H50 WATERFRONT UTILITIES 6. ENGINEERING SYSTEMS REQUIREMENTS H50 WATERFRONT UTILITIES SYSTEMS REQUIREMENTS WATERFRONT UTILITIES TEMPLATE 02/18 Instructions for using this template: There are template files for each UNIFORMAT Level

More information

An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010

An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010 An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010 Putnam County Planning & Development Services Building & Zoning Division Compliance Section PO Box 1486 Palatka, FL 32178 1486 Office

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

Florida Department of Transportation 1000 NW 111 th Avenue, Room 6203 Miami, Florida

Florida Department of Transportation 1000 NW 111 th Avenue, Room 6203 Miami, Florida RICK SCOTT GOVERNOR Florida Department of Transportation 1000 NW 111 th Avenue, Room 6203 Miami, Florida 33172-5800 ANANTH PRASAD, P.E. SECRETARY ADDENDUM No. 02 ISSUED ON OCTOBER 14, 2014 TO THE PROJECT

More information

Florida Department of Transportation

Florida Department of Transportation Page 1 of 7 RICK SCOTT GOVERNOR Florida Department of Transportation 1109 S. Marion Avenue Lake City, Florida 32025 ANANTH PRASAD SECRETARY September 27, 2011 To: Proposal Holders Addendum No: 1, E2Q23,

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

Inspection Report. 1 Inspection Way Orlando, FL Prepared for: Wanda Figueroa Prepared by: ACF Home Inspections Inc

Inspection Report. 1 Inspection Way Orlando, FL Prepared for: Wanda Figueroa Prepared by: ACF Home Inspections Inc Inspection Report 1 Inspection Way Orlando, FL 32825 Prepared for: Wanda Figueroa Prepared by: Page 1 of 25 Needs Service Summary This summary is not the entire report. The complete report may include

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

Welcome to Voice Permits

Welcome to Voice Permits Welcome to Voice Permits In an ongoing commitment to improve customer service, your building department has installed an Interactive Voice Response System (IVR) for inspections, 24-hours a day, 7 days

More information

Inspecta-Homes 2469 University Avenue West St. Paul MN Ph#: (651)

Inspecta-Homes 2469 University Avenue West St. Paul MN Ph#: (651) Page 1 Doc #: Inspector: Date: Dwelling Address: Client Name: Client's Agent: Real Estate Company: Please refer to the General Home Inspection Contract. Thank you for using Minnesota and Western Wisconsin's

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT February 29, 2012 RFP NO: 17 PROJECT: Josephine County Justice Center HVAC Upgrades BID CLOSING DATE: NO CHANGE: March 8, 2012 / NOT LATER

More information

Asurity 1. Property Inspection Report S Gurd Rd., Hastings, MI Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski -

Asurity 1. Property Inspection Report S Gurd Rd., Hastings, MI Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski - Cover Page Property Inspection Report Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski - Date of Inspection: 3/28/2017 Time: 2:00 Age of Home: Built 1999 Size: 2015 Weather: 50 Overcast.

More information

Photovoltaic (Solar) Array Installation Guide

Photovoltaic (Solar) Array Installation Guide Building & Safety Division Community Development Department 7351 Rosanna Street, Gilroy, CA 95020 Phone: 408 846-0451 Fax: 408 846-0429 Visit us: www.cityofgilroy.org Photovoltaic (Solar) Array Installation

More information

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. DIVISION 26 ELECTRICAL SECTION 26 27 26 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. B. Specialty switches and outlets

More information

Product Guide Specification

Product Guide Specification December 2012 3948 Townsfair Way, Suite 200 Columbus, Ohio 43219 Toll Free 800-746-6686 Website www.simonton.com E-Mail archdetails@simonton.com Product Guide Specification Specifier Notes: This product

More information

Fire Permit Application

Fire Permit Application Fire Permit Application FOR STAFF USE ONLY Case Permit Number: Plan Number: Related permits: Project #: Responsibility for information Although designated Department staff members will help you with general

More information

CITY OF MEXICO BEACH REQUEST FOR QUOTES: LIFT STATION PANELS REPLACEMENT

CITY OF MEXICO BEACH REQUEST FOR QUOTES: LIFT STATION PANELS REPLACEMENT CITY OF MEXICO BEACH REQUEST FOR QUOTES: LIFT STATION PANELS REPLACEMENT The City of Mexico Beach is requesting quotes for replacement of 18 lift station control panels. The lift stations range from 2

More information

OPERATIONS AND STORAGE BUILDING

OPERATIONS AND STORAGE BUILDING OPERATIONS AND STORAGE BUILDING Standard and Large OPERATIONS AND STORAGE Purpose The Operations and Storage Building provides office space for range personnel and a storage area for range maintenance

More information

Tualatin Valley Fire & Rescue Finance Department SW 70 th Ave., Tigard, OR Phone: , Fax:

Tualatin Valley Fire & Rescue Finance Department SW 70 th Ave., Tigard, OR Phone: , Fax: Tualatin Valley Fire & Rescue Finance Department 11945 SW 70 th Ave., Tigard, OR 97223 Phone: 503-259-1157, Fax: 503-649-5347 SOLICITATION NO: ITB 13-0002 AMENDMENT NO. 2 General Contractor Construction

More information

FAQ. (Frequently Asked Questions) What is required to convert my unfinished basement to finished space?

FAQ. (Frequently Asked Questions) What is required to convert my unfinished basement to finished space? NEW CASTLE COUNTY DEPARTMENT OF LAND USE FAQ (Frequently Asked Questions) What is required to convert my unfinished basement to finished space? 1. To convert an unfinished basement to finished space, at

More information

Element D Services Electrical

Element D Services Electrical PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as a Specification.

More information

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR SECTION 08734 COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead

More information

Garfield Elementary School Feasibility Study for New Library Building Project Number A C

Garfield Elementary School Feasibility Study for New Library Building Project Number A C Larry Teixeira Selma Unified School District 3036 Thompson Avenue Selma, CA 93662 Subject: Feasibility Study for New Library Building Project Number A 12-8581.00 C Dear Mr. Teixeira: At your request, we

More information

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

I. INTRODUCTION Codes, Rules, Laws, & Requirements

I. INTRODUCTION Codes, Rules, Laws, & Requirements I. INTRODUCTION 1.03 Codes, Rules, Laws, & Requirements A. Buildings and sites are to be designed in conformance to the applicable requirements of the following: 1. The Texas Engineering Practice Act and

More information

This Report Was Prepared For: Property Address Inspected:

This Report Was Prepared For: Property Address Inspected: This Report Was Prepared For: Jane Do (to protect the identity and privacy of our clients) Property Address Inspected: 321 Sample Dr Example Report, FL 32828 Date: August 11, 2115 File # H50855255 The

More information

Ph: (907) Quality Homes

Ph: (907) Quality Homes Standard Specifications BUILDING your dream home www.destinyhomesak.com Ph: (907) 232-9751 Email: destiny4paul@aol.com Quality Homes 2016 1 HOME PRICE Prices of the homes are based on the $40,000 lot allowance.

More information

ADDENDUM NO. 1 BID-CONTRACT DOCUMENTS FOR. RFP No Professional Design Services for CCC Le-Jao Student Resource Center

ADDENDUM NO. 1 BID-CONTRACT DOCUMENTS FOR. RFP No Professional Design Services for CCC Le-Jao Student Resource Center ADDENDUM NO. 1 BID-CONTRACT DOCUMENTS FOR RFP No. 2030 Professional Design Services for CCC Le-Jao Student Resource Center COAST COMMUNITY COLLEGE DISTRICT COSTA MESA, CALIFORNIA COUNTY OF ORANGE COAST

More information

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Ohio Administrative Code Rule Number OPC Section IPC origin Reason for proposed 4101:3-2-01 Alternate on-site 2015 Added definition

More information

CHAPTER SIX Automatic Gates

CHAPTER SIX Automatic Gates CHAPTER SIX Automatic Gates Contents: Steps to Obtain Permits Installation Requirements Electrical Requirements Gate Construction Knox Key Switch Placement and Installation Preemption Automatic Gate Signage

More information

Electric Floor Warming Systems Installation and Operation Instructions. Mat Heating Systems and Cable Heating Systems. UL Listed for USA and Canada

Electric Floor Warming Systems Installation and Operation Instructions. Mat Heating Systems and Cable Heating Systems. UL Listed for USA and Canada Electric Floor Warming Systems Installation and Operation Instructions Mat Heating Systems and Cable Heating Systems UL Listed for USA and Canada Thank you for your purchase of a Warming Systems electric

More information

Arlington Public Schools Purchasing Office

Arlington Public Schools Purchasing Office Arlington Public Schools Purchasing Office NOTICE OF ADDENDUM NO. 1 Issued on March 30, 2018 TITLE: ITB NO.: YORKTOWN HIGH SCHOOL INTERIOR MODIFICATIONS PROJECT 57FY18 ITB CLOSING DATE PRIOR TO 2:00 P.

More information

ADDENDUM 1. Southeast High School Auditorium & Gymnasium HVAC Improvements

ADDENDUM 1. Southeast High School Auditorium & Gymnasium HVAC Improvements ADDENDUM 1 CLIENT: PROJECT: TO: FROM: Guilford County Schools (GCS) Southeast High School Auditorium & Gymnasium HVAC Improvements All Prospective Bidders Derrick Giles, SAMR, PLLC. DATE: 6/6/2018 The

More information

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means

More information

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1 Page 1 TABLE OF CONTENTS 1 ELECTRICAL 2 Summary Sustainability Electrical Distribution Lighting Detection and Alarm Communication Systems Lightning Protection Clock Systems Access Control Housekeeping

More information

Fire & Life Safety Supplemental Rules & Regulations for New Construction & Significant Remodels

Fire & Life Safety Supplemental Rules & Regulations for New Construction & Significant Remodels DEPARTMENT OF PUBLIC SAFETY FIRE MARSHAL S OFFICE 9611 SE 36 TH ST Mercer Island, WA 98040 (206) 236-3515 direct; (206) 236-3622 FAX Rod Mandery, Fire Marshal Updated version: 03-19-2002 Fire & Life Safety

More information

LIGHT LEVEL REQUIREMENTS MINIMUM ACCEPTABLE FOOT CANDLES

LIGHT LEVEL REQUIREMENTS MINIMUM ACCEPTABLE FOOT CANDLES LIGHT LEVEL REQUIREMENTS LOCATION Classrooms and instrumental areas- Study Halls, Lecture Rooms, Art Rooms, Offices, Libraries, Conference Rooms, Work Rooms, Shops, Laboratories and Secondary School Cafeterias.

More information

Product Specifications Dialog Room Controller* (*patent pending)

Product Specifications Dialog Room Controller* (*patent pending) 1 Product Specifications Dialog Room Controller* (*patent pending) 1. GENERAL 1.1. OVERVIEW 1.1.1. Provide a complete stand-alone, decentralized, low voltage, digital lighting control system for classrooms,

More information

FOUNTAINS UGA DESIGN & CONSTRUCTION SUPPLEMENTAL GENERAL REQUIREMENTS & STANDARDS APRIL 30,

FOUNTAINS UGA DESIGN & CONSTRUCTION SUPPLEMENTAL GENERAL REQUIREMENTS & STANDARDS APRIL 30, 13 12 00 FOUNTAINS A. Due to water conservation efforts and the high maintenance requirements of fountains, new interior and / or exterior fountains are not allowed. B. If a variance is granted for a fountain,

More information

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District HOLUM EDUCATION CENTER Architectural The existing building has approximately 41,823 square feet and sets on a lot about 4.14 acres in size. Parking lots are located along the east and west sides of the

More information

LED Bollard Collection

LED Bollard Collection LED Bollard Collection LED Bollards As distance to architecture decreases, luminaire height and scale should also decrease. Kim Lighting s Theory of Relativity Blending light fixtures into the cohesive

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

Appendix B. Facilities Assessment Report

Appendix B. Facilities Assessment Report Mile Lane Army Reserve Center Redevelopment Plan September 2008 Appendix B Facilities Assessment Report RKG Associates, Inc. Mile Lane Army Reserve Base Middletown, CT MEP System Evaluation For RKG Associates

More information

Canadian Property Inspections

Canadian Property Inspections Cover Page Canadian Property Inspections Home Inspection Report L9Z-1K4 Inspection prepared for: K.C. Pitman Date of Inspection: 3/6/2017 Time: 3pm Age of Home: 42 Size: 500-1000 Weather: Cloudy, cool.

More information

Page 1 of General

Page 1 of General Page 1 of 8 16.1 General 1. This section covers items common to sections of CSI s Master Format - Division 16. 2. Dalhousie University is certified by IBEW for new construction and all electrical contractors

More information

Home Inspection Report

Home Inspection Report Pfeifer Home Inpsection, LLC 8332 Crystal Pointe Lane Indianapolis, Indiana 46236 317-340-1734 Lic #HI01700103 Home Inspection Report Columbus, IN 47201 Page 1 of 20 Table of Contents Definitions 2 General

More information

Hearth and Homes Inspections, llc

Hearth and Homes Inspections, llc Cover Page Property Inspection Report 44092 Inspection prepared for: Ember Griffith Real Estate Agent: Samantha Elly - Keller Williams Date of Inspection: 3/4/2017 Time: 10:00 AM Age of Home: 63 Years

More information

1921 River Birch Dr., Shawnee, OK Inspection prepared for: Vicki Jager Date of Inspection: 7/27/2015 Time: 8am Weather: Sunny

1921 River Birch Dr., Shawnee, OK Inspection prepared for: Vicki Jager Date of Inspection: 7/27/2015 Time: 8am Weather: Sunny Cover Page 74804 Inspection prepared for: Vicki Jager Date of Inspection: 7/27/2015 Time: 8am Weather: Sunny Inspector: John Crouch License #70001257 Newalla, OK 74857 Phone: 4054815032 Email: john@goodlivinghomes.com

More information

COMMERCIAL PERMIT APPLICATION AND CHECKLIST. Depending on the scope of your project, the following submittal requirements will apply:

COMMERCIAL PERMIT APPLICATION AND CHECKLIST. Depending on the scope of your project, the following submittal requirements will apply: Planning/Building Department 115 Ramsdell Street Fircrest WA 98466 (253) 564-8902 COMMERCIAL PERMIT APPLICATION AND CHECKLIST Depending on the scope of your project, the following submittal requirements

More information

National Property Inspections

National Property Inspections Sunday, February 7, 2016 Inspector Eldon Holliday 901-497-0943 npi@centurytel.net Page 1 of 9 GENERAL INFORMATION GENERAL CONDITIONS AT TIME OF INSPECTION : Yes Property Occupied : Property Faces : þ North

More information

Brighton Area Fire Authority

Brighton Area Fire Authority 615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following

More information

Commercial Rules and Regulations

Commercial Rules and Regulations Commercial Rules and Regulations Public Works and Community Development Department City of Shenandoah 29955 I 45 North Shenandoah, Texas 77381 281 298 5522 www.shenandoahtx.us Construction Documents Submit

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

SECTION (16140) - WIRING DEVICES

SECTION (16140) - WIRING DEVICES SECTION 26 27 26 (16140) - WIRING DEVICES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Receptacles, Connectors, Switches, and Finish Plates. B. Related Sections: 1. Section 00 31 13.43 (00370) -

More information