Mechanical Systems Existing Conditions Evaluation. Instructor: Dr. Bahnfleth. November 12, Thesis Building Sponsor s: INOVA Fairfax Hospital

Size: px
Start display at page:

Download "Mechanical Systems Existing Conditions Evaluation. Instructor: Dr. Bahnfleth. November 12, Thesis Building Sponsor s: INOVA Fairfax Hospital"

Transcription

1 David J. Peterson Mechanical Option Mechanical Technical Report #3 The INOVA HEART INSTITUTE AT, Falls Church, VA. Mechanical Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth November 12, 2003 Thesis Building Sponsor s: and Turner Construction 3300 Gallows Road, Falls Church, VA

2 Table of Contents 1.0 Executive Summary 2.0 Background 3.0 Design Conditions 4.0 Major Equipment 5.0 Sequence of Operation 6.0 Systems Cost 7.0 Critique 8.0 References 9.0 Appendix 2

3 1.0 Executive Summary: The purpose of this report is to understand the mechanical systems and equipment selection for the INOVA Heart Institute. is an addition to the existing INOVA Fairfax Hospital. The mechanical systems for the new hospital addition include a combination of constant volume for the majority of the hospital and a variable volume for the entrance and atrium space. The building is served by 13 air handling units 3 of which are stand-by. From these 13 AHU s there are 4 separate systems. Each system supplies air into one common duct which branches out through the respective space that it serves. The hospital receives steam and chilled water from the remote central plant which also serves the existing hospital. Due to restrictions by the owner and hospital, information about the existing chiller and steam plants was unattainable all information on the mechanical systems is based off the design documents for the new addition. In section 2.0 of this report a discussion of the background data and information is included. The information that will be discussed includes the design objectives, design requirements, and site factors that effected the design. In section 3.0 of this report a discussion of the design conditions and information is included. The information that will be discussed includes the indoor and outdoor design conditions, utility rates, cost factors and design loads. In section 4.0 of this report a discussion of the major equipment and corresponding systems within the building are included. The information that will be discussed in this section includes the Air systems, steam systems and hydronic systems. In section 5.0 of this report the sequence of operation of the buildings mechanical air systems is included. The information that will be discussed includes operation the four types of air systems located In section 6.0 of this report a system s cost for the buildings mechanical systems are included. The information that will be discussed includes the total MEP cost break down for the building. In section 7.0 of this report an overall critique of the buildings mechanical systems is included. In section 8.0 of this report a ultimate references used to analyze the buildings mechanical systems are included. In section 9.0 of this report is the appendices that include major equipment schedules and systems schematics. final rendering is shown in the photo below courtesy of Turner Construction and is due to open in the Summer of INOVA Rendering 1: Final Rendering 3

4 2.0 Background: 2.1 Building Information is an addition to the existing Located in Falls Church, Virginia. As stated in its name the new addition will serve as a Cardio- Vascular Institute and provide Operating, Care, Rehabilitation and lab spaces for all issues dealing with the heart. The demand for such facilities is ever increasing with the explosion in population in the Northern Virginia Area. The overall size of the new hospital is approximated at 410,000 sq.ft. and 6 floors. The hospital is broken down into 3 wings and are divided into sections A, B and C. Sections A and B serve the majority of the hospital and serve as recovery, patient, lab, general hospital office, atrium and recreation spaces. The third wing or CVOR (Cardio-Vascular-Operating-Rooms) serves as the critical care and operation wing. The new addition will be located and attached to the rear of the existing facility on the west end of the property. INOVA Photo 1: Existing Hospital 2.2 Design Objectives The design objectives for the mechanical systems for the new INOVA Heart Institute include: 1. Provide round the clock sufficient conditions for patients, workers and visitors with the use of terminal duct reheats, steam humidification and critical sensors throughout. (CO2, Temperature, and Pressure) 2. A variable volume system for variable occupancy in the open areas and atrium space 3. A constant volume system for the typical hospital area 4. A system that ingrates with the existing facilities district chilled water, steam and condensate 5. Provide backup AHU s to each system in order to maintain sufficient conditions 2.3 Design Requirements As stated in section 2.2 the primary objective is to maintain sufficient condition for 24 hours of operation. This requires proper filtration for indoor air quality issues, sufficient temperature, pressure, and C02 levels. These requirements serve to protect the health and well being of the inhabitants of the facility. 2.4 Site Factors The major site factor that influenced the new addition is that the new addition needed to be located on the existing property of the original so that it could tap into the existing central plant located directly north of the existing hospital. The new addition 4

5 receives all its chilled water and high pressure steam from this remote central plant which is fed into the building s sub-basement via existing tunnels adjacent to the existing hospital. Parking Existing Central Plant Water Tower Existing Hospital Garage Relocation New Hospital Location North Parking INOVA Photo 2: Aerial shot of Existing Hospital The west end of the property was the only appropriate direction in which to expand. The north end contains overflow parking a water tower and the central plant. The south end contains limited space due to existing residential housing and is also dedicated to some patient and visitor parking. The existing hospital extends all the way to the property limits on the east end next to Gallows Road, a major thoroughfare. The ultimate choice for selecting location was made on the west end where an existing parking deck would be demolished and relocated further west. This dated photo show the beginning excavation of the new parking deck. The INOVA Heart Institute is currently being constructed between the new parking deck and the existing hospital. 3.0 Design Conditions: INOVA Photo 3: Existing Central Plant 5

6 3.1 Indoor Conditions The indoor air conditions are taken from the mechanical specifications and are represented below. Indoor Air Conditions Indoor design conditions for all areas excluding CVOR s Indoor design conditions for all areas including CVOR s (Cardio- Vascular Operating Rooms): Dry Bulb: 72 F Relative Humidity: 50% Wet Bulb: Relative Humidity: 50% INOVA Table 1: Indoor Air Conditions 3.2 Outdoor Conditions The outdoor air conditions for design match that of the design conditions given in ASHRAE s Fundamentals for Washington, DC (at 0.4%) and are listed in the table below. 65 F Outdoor Air Conditions Design Cooling Temperatures: Design Cooling Temperatures: Evaporating Temperatures: (Summer) Dry Bulb: Mean Wet Bulb (Winter) Dry Bulb: Wet Bulb: Mean Dry Bulb: 95 F 76 F 15 F 79 F 89 F INOVA Table 2: Outdoor Air Conditions 3.3 Utility Rates and cost factors The following utility charges apply to the INOVA Heart Institute. The energy sources for the new addition are electric power from Virginia Electric and Power Company and gas from the Washington Gas and Light Company. Virginia Electric and Power Company Schedule GS-3U Distribution Service Charges Basic monthly: $ or $ annual Distribution Demand on all KW: $2.12 per KW Competitive Trans. On Peak Demand: $2.897 per KW Competitive Trans. On Peak KWH: $ per KWH INOVA Table 3: Electric Rate Summary 6

7 Under this rate schedule there is always a distribution demand on all KW but there are no excess off-peak demand charges like there is for on-peak. Keeping this new facility on the premises of the existing facility takes advantage of the no off- peak demand charge. On-peak hours are as follows: 1. For the period of June 1 through September 30, 10 a.m. to 10 p.m., Mondays through Fridays. 2. For the period of October 1 through May 31, 7 a.m. to 10 p.m., Mondays through Fridays. Washington Gas Commercial and Industrial Service Rate Schedule NO. 2 $196.2 System Charge: /(annual) Distribution Charge: (Per Therm) First: 125 Therms /(mos.) Next: 875 Therms /(mos.) Over: 1,000 Therms /(mos.) INOVA Table 4: Gas Rates Summary Information for the gas boilers located in the central plant is not accessible. Savings is obtained by the use of a central plant which purchases this utility presumably in large quantities to support the needs of the existing as well as the new facilities on the property. 3.4 Design Loads The total design cooling load for the building is estimated at 1875 tons. Mechanical Load Data Total Cooling Load Ft 2 /ton Supply Air 1.06 cfm/ft 2 Ventilation Air cfm/ft 2 INOVA Table 5: Mechanical Load Data Mechanical Design loads Heating Loads Total Quantity Btu/hr Tons Constant Volume Terminal Reheat Coils: Variable Volume Terminal Reheat Coils: Secondary Reheat Coils for CVORs: Air Handling units preheat Coils: Fin tube radiation units Unit Heaters Hydronic Radiant Ceiling Panels: Fan coil units Totals:

8 Cooling Loads Total Secondary Cooling Coil: Air Handling Cooling Coils: AC Units Cooling Coils: Fan coil units Totals: INOVA Table 6: Mechanical Design Loads Broken Down The systems mechanical equipment supplying heating and cooling loads are represented in the table above. The values represent design conditions at peak capacity and are not an accurate representation of performance in non-peaking conditions. 4.0 Major Equipment: 4.1 Air Systems Schematics of each air system are located in the appendices section 9.2. Sketch 1: 3-D Sketch of the AHU s Serving Area (Not to Scale) Air Handling Units Section A: Units 1,2,3,4: Serve patient rooms and general hospital Area (Constant Volume System). They are located on the 5 th floor of the building in the upper Penthouse. The contents include min/max OA dampers, re-circulated air with variable frequency drive, pre-filter (30% efficiency), post-filter (60% efficiency), pre-heat, steam humidification, cooling coil, a variable frequency drive supply fan (operated by a static pressure controller down stream), sound attenuators, a post filter (95% efficiency). For clean work spaces and labs further upstream there are constant volume re-heats, humidification, and final filter (99.95% efficiency). Each AHU is 8

9 designed to serve section A (see sketch 1, above and constant volume schematic for units 1,2,3,4 located in the Appendices) and are balanced at: 33,567 CFM, SA and 10,610 CFM, OA. The spaces in section A are served by this constant volume system which is equipped with terminal reheat units used to maintain supply temperature at 55 F to each space. For design conditions three air handlers are used to supply air into a common duct, which then splits into two major shafts that run down the entire length of the building. The fourth unit (AHU-4) is connect to the same system and is for back up purposes only. Each air handling unit is typical with a maximum supply CFM of approximately 40,000 and balanced with 30% outdoor air. The back-up unit provides and extra level of safety in this section of the building insuring appropriate supply air conditions to each space Air Handling Units Section A (Atrium): Units 5,6: Serve the atrium and lobby areas (Variable Volume System). The contents include min/max OA dampers, re-circulated air with variable frequency drive, pre-filter (30% efficiency), post-filter (60% efficiency), pre-heat, steam humidification, cooling coil, a variable frequency drive supply fan (operated by a static pressure controller downstream), and sound attenuators. Each AHU serve the section in front of A (see sketch 1, above and constant volume schematic for units 5,6 located in the Appendices section 9.2) and are balanced at: 35,310 CFM, SA and 10,593 CFM, OA. The space in front of section A called the atrium is served by this variable volume system which is equipped with terminal reheat units used to maintain supply temperature at 55 F to each space. For design conditions the two air handlers are used to supply air into a common duct and supply air to the front entrance atrium. Each air handling unit is typical with a maximum supply CFM of approximately 40,000 and balanced with 30% outdoor air Air Handling Units Section B: Units 7,8,9,10: Serve patient rooms and general hospital Area (Constant Volume System). They are located on the 5 th floor of the building in the upper Penthouse. The contents include min/max OA dampers, re-circulated air with variable frequency drive, pre-filter (30% efficiency), post-filter (60% efficiency), pre-heat, steam humidification, cooling coil, a variable frequency drive supply fan (operated by a static pressure controller down stream), sound attenuators, a post filter (95% efficiency). Each AHU is designed to serve section B (see sketch 1, above and constant volume schematic for units 7,8,9,10 located in the Appendices section 9.2) and are balanced at: 32,295 CFM, SA and 9,689 CFM, OA. The spaces in section B are served by this constant volume system, which is equipped with terminal reheat units used to maintain supply temperature at 55 F to each space. For design conditions three air handlers are used to supply air into a common duct, which then splits into two major shafts that run down the entire length of the building. The fourth unit (AHU-10) is connect to the same system and is used for back up purposes only. Each air handling unit is typical with a maximum supply CFM of approximately 40,000 and balanced with 30% outdoor air. The back-up units provides and extra level of safety in this section of the building insuring appropriate supply air conditions to each space. 9

10 Air Handling Units Section C: Units 11,12,13: Serve Cardio Vascular Operating Room (CVORs) spaces and areas directly above (Constant Volume System with Isolation Dampers). They are located on the 4 th floor of the building in the lower Penthouse. The contents include min/max OA dampers, re-circulated air with variable frequency drive, pre-filter (30% efficiency), post-filter (60% efficiency), preheat, steam humidification, cooling coil, a variable frequency drive supply fan (operated by a static pressure controller down stream), sound attenuators, a post filter (95% efficiency). For the CVOR spaces, a secondary chilled water loop is incorporated along with balancing isolation dampers (operated by pressure controller down stream), re-heat, humidification, and final filter (99.95% efficiency). Each serve in section C (see sketch 1, above and constant volume schematic for units 11,12,13 located in the Appendices section 9.2) and are balanced at: 30,973 CFM, SA and 9,292 CFM, OA. The spaces in section C are served by this constant volume system, which is also equipped with terminal reheat units used to maintain supply temperature to the non operating spaces at 55 F. For design conditions two air handlers are used to supply air into a common duct which only drops down two floors. The third unit (AHU-13) is connect to the same system and is for back up purposes only. Each air handling unit is typical with a maximum supply CFM of approximately 40,000 and balanced with 30% outdoor air. The back-up unit provides and extra level of safety in this section of the building insuring appropriate supply air conditions to each space. 4.2 Steam Systems Schematics of the steam system are located in the appendices section 9.2. Note that information regarding the central plant is unattainable so steam boilers that provide High Pressure Steam will not be discussed Basement Steam This system brings in High Pressure Steam (HPS) from the central plant through the existing mechanical tunnel to the new addition. This system converts HPS into Medium pressure steam (MPS) and Low Pressure Steam (LPS) through a network of Pressure Reducing Valves (PRV). The conversion to LPS is used to serve duct mounted humidifiers around the building and kitchen dish washers. The MPS is used to serve domestic water heaters and steam/heating-water-converters or heat exchangers. The basement houses a condensate pump return which is used to return condensate back to the central plant via the same mechanical tunnel The Fifth Floor Steam System This system like the basement brings in HPS supplied by the central plant from the tap off of the existing 14 pipe located in the mechanical tunnel entering the basement. This system is identical in the manner of converting the HPS to MPS and LPS. The purpose of the steam system on the fifth floor is to provide a future tap for equipment requiring MPS and to supply the AHU s located in the penthouse (fifth floor) with LPS to the humidifiers in the supply air systems. Like the basement system the fifth floor system returns condensate to the same duplex condensate pump return which the returns it back to the central plant via an existing pump condensate return pipe in the mechanical tunnel The Fourth Floor Steam System

11 This system is again similar to the previous two when converting HPS by the central plant to MPS and LPS in the building. This system receives HPS from the same tap as the previous two and converts it for use in steam/heating-water-converters for the CVOR wing, which require MPS. It also converts it to LPS for supplying the AHU s located on that floor with humidification. Like the basement system the fourth floor system has its own duplex condensate pump return and returns pump condensate bask to the existing 14 pump condensate pipe located in the basement, which will then return it back to the central plant. 4.3 Hydronic systems Schematics of the respective hot and cold water systems are located in the appendices. Note that the chillers for the major chilled water loop are also located in the central plant and will not be discussed. However there are two 50 Ton chillers in the building that serve the purpose of sub-cooling air to six operating (CVOR) spaces on floor two of section C Hot water Hot water is provided to the building through a self-contained loop, which uses steam/heating-water-converters or heat exchangers to produce hot water to re-circulate through the building. The heat exchangers are supplied with MPS as stated in the previous section and are located both in the basement as well as on the fourth floor and serve all three sections of the building. The purpose of the hot water loop is to provide reheat water to the constant and variable volume terminal reheat units and unit heaters located throughout the facility. Also this hot water is used to serve preheat water to all the air handlers and radiant panels throughout the building. There are seven hot water pumps, which performed the task of delivering the hot water throughout the building Chilled Water As stated in the beginning of this section chilled water is provided by the remote central plant through the subterranean mechanical tunnels to the new addition. Through analysis of the design documents it is assumed that primary secondary pumping occurs at the plant, as there are no major chilled water pumps in the new building (there are chilled water coil recirculation pumps at the air handlers). The purpose of the chilled water is to provide cooling for coils located within the air handlers and fan coil units. The secondary chilled water loop in section C of the building is supplied by two secondary air-cooled chillers located in section C. The evaporators are located on the fourth floor and two remote air cooled condensers located on the roof of the directly above the fourth floor of section C. A mixture of 20% propylene glycol is used as the refrigerant to the condenser. The chillers have a total capacity of approximately 50 tons each and are in parallel to each other with in line pumping. The cooling coils here are used to supply a dry bulb temp of 42.3 F at an entering water temperature of 38 F to the operating spaces. 5.0 Sequence of Operation: 5.0 Systems Operation The systems in this facility use direct digital control with a combination of electronic and pneumatic actuation that control the variable frequency drive supply fans, dampers, and return air fans. There are 4 total air systems in the INOVA Heart Institute. 11

12 5.1 Air Systems Section A (Constant Volume): AHU Units 1,2,3,4 and Return Fans 1,2,3: The total maximum airflow for the system is 120,000 CFM and the leaving air dry bulb temperature is 50.5 F. Normal Mode: Three interconnected AHU s shall operate, while the fourth remains on standby. Two interconnected return fans shall operate, while the third remains on standby. Smoke Detection: Smoke detectors located in the supply air discharge, when detecting smoke, shall shut down the supply fan and close supply, return, and outside air dampers. Smoke Purge Mode: One of the three operating AHU s shall be deenergized, such that only two interconnected AHU s remain operational. Two interconnected return fans shall operate, while the third remains assigned as the standby fan Start/Stop: When AHU is commanded to run through the central control monitoring system or CCMS using a direct digital controller DDC logic controller, the supply fan will run continuously, it will not run until the limit switch indicates smoke damper is open. The CCMS will not turn on the AHU supply fan until such safeties requirements as the freeze stat (set at 38 F), high discharge pressure safety switch (set at 6 wg), supply duct smoke detector regardless of the variable frequency drive VFD mode requirements are met. The CCMS will control the speed of the VFD (all fans in unison) to maintain the supply duct static pressure setpoint, which is used to meet the minimum pressure required at the static sensing station down stream. On start and stop the VFD will ramp to speed and slow down within adjustable acceleration and deceleration limits. The speed of each supply fan will be limited if necessary to maintain a maximum discharge pressure. The CCMS will control the output of both operating return fans in unison to maintain a return flow setpoint equal to the supply flow design minimum CFM. When supply fan is deenergized the return damper will stay open and outside air dampers will stay closed. When the supply fan is energized the min OA damper opens. The economizer mode will be active while the AHU supply fan is energized and when the OA temperature falls below the return air temp. The economizer mode will be activated before the chilled water cooling in the coils. In general supply and return fans will run continuously. The system static pressure sensing station located down stream through the DDC system will control the variable frequency drive on the supply fan to maintain its setting. When cooling mode is activated the discharge sensor through the DDC system will modulate chilled water valves associated with the respective AHU to maintain a discharge air temp of 65. The preheat coil pump and steam humidifier will be deenergized and the preheat coil valve and humidifier isolation valve will be shut. When the unit is operating in heating mode the discharge temp sensor through the DDC system will modulate the preheat coil valve to maintain a discharge temp of 45 and the humidifier isolation valve will be open and the cooling coil valve will be closed. 5.2 Air Systems Section B: Units 7,8,9,10 and Return Fans 6,7,8: This constant volume system operates in the same manner as the previous. 5.3 Air Systems Section A (Atrium): Units 5,6 and Return Fans 4,5: The total maximum airflow for the system is 80,000 CFM and the leaving air dry bulb temperature is 51.0 F. 12

13 Normal Mode: One AHU and one return fan will be commanded to run at all times. The second AHU will be commanded to run based on load of the space. The AHU and return fan with the most runtime will be selected for lead operation. On a rise in supply fan speed signal (based on a 10 minute running average) to 100% the lag AHU will be turned on. On a fall in total system supply air flow to 30,000cfm the AHU with the most runtime will be turned off. On a rise in return fan speed signal (based again on 10 minute running average) to 100% the lag return fan will be turned on. On a fall in total system return air flow to 26,000 CFM the return fan with the most runtime will be turned off. Smoke Detection: Smoke detectors located in the supply air discharge, when detecting smoke, shall shut down the supply fan and close supply, return, and outside air dampers. Atrium Smoke Evacuation Mode: If two AHU s are running, one of the two operating AHU s will be deenergized, such that only one AHU remains operational. If only one return fan is running, the second return fan will be turned on, such that both will be running. Start/Stop: When AHU is commanded to run through the central control monitoring system or CCMS using a direct digital controller DDC logic controller, the supply fan will run continuously, it will not run until the limit switch indicates smoke damper is open. The CCMS will not turn on the AHU supply fan until such safeties requirements as the freeze stat (set at 38 F), high discharge pressure safety switch (set at 6 wg), supply duct smoke detector regardless of the variable frequency drive VFD mode requirements are met. The CCMS will control the speed of the VFD (all fans in unison) to maintain the supply duct static pressure setpoint, which is used to meet the minimum pressure required at the static sensing station down stream. On start and stop the VFD will ramp to speed and slow down within adjustable acceleration and deceleration limits. The speed of both supply fan will be limited if necessary to maintain a maximum discharge pressure. The CCMS will control the output of the return fan to maintain a return flow setpoint equal to supply flow minus the limits of system exhaust make-up air CFM and the design minimum CFM to maintain an return air CO2 setpoint of 700 ppm. In smoke evacuation mode CCMS will control the output of the return fan to maintain a return flow setpoint of 56,000 CFM. When supply fan is deenergized the return damper shall stay open and outside air dampers will stay closed. When the supply fan is energized the min OA damper opens. The economizer mode shall be active while the AHU supply fan is energized and when the OA temperature falls below the return air temp. The economizer mode will be activated before the chilled water cooling in the coils. In general supply and return fans will run continuously. The system static pressure sensing station located down stream through the DDC system will control the variable frequency drive on the supply fan to maintain its setting. When cooling mode is activated the discharge sensor through the DDC system will modulate chilled water valves associated with the respective AHU to maintain a discharge air temp of 65. The preheat coil pump and steam humidifier will be deenergized and the preheat coil valve and humidifier isolation valve will be shut. When the unit is operating in heating mode the discharge temp sensor through the DDC system will modulate the preheat coil valve to maintain a discharge temp of 45 and the humidifier isolation valve will be open and the cooling coil valve will be closed. 5.4 Air Systems Section C (CVOR): Units 11,12,13 and Return Fans 11,12,13: The total maximum airflow for the system is 80,000 CFM and the leaving air dry bulb temperature is 50.5 F. 13

14 Normal Mode: Three interconnected AHU s shall operate, while the third remains on standby. Two interconnected return fans shall operate, while the third remains on standby. Smoke Detection: Smoke detectors located in the supply air discharge shall, on the detection of the products of combustion, shut down supply fan and close supply, return and outside air dampers Smoke Purge Mode: One of the two operating AHU s shall be deenergized, such that only two interconnected AHU s remain operational. Two Interconnected return fans shall operate, while the third remains assigned as the standby fan Start/Stop: When AHU is commanded to run through the central control monitoring system or CCMS using a direct digital controller DDC logic controller, the supply fan will run continuously, it will not run until the limit switch indicates smoke damper is open. The CCMS will not turn on the AHU supply fan until such safeties requirements as the freeze stat (set at 38 F), high discharge pressure safety switch (set at 6 wg), supply duct smoke detector regardless of the variable frequency drive VFD mode requirements are met. The CCMS will control the speed of the VFD (all fans in unison) to maintain the supply duct static pressure setpoint, which is used to meet the minimum pressure required at the static sensing station down stream. On start and stop the VFD will ramp to speed and slow down within adjustable acceleration and deceleration limits. The speed of each supply fan will be limited if necessary to maintain a maximum discharge pressure. The CCMS will control the output of both operating return fans in unison to maintain a return flow setpoint equal to the supply flow design minimum CFM. When supply fan is deenergized the return damper will stay open and outside air dampers will stay closed. When the supply fan is energized the min OA damper opens. The economizer mode will be active while the AHU supply fan is energized and when the OA temperature falls below the return air temp. The economizer mode will be activated before the chilled water cooling in the coils. In general supply and return fans will run continuously. The system static pressure sensing station located down stream through the DDC system will control the variable frequency drive on the supply fan to maintain its setting. When cooling mode is activated the discharge sensor through the DDC system will modulate chilled water valves associated with the respective AHU to maintain a discharge air temp of 65. The preheat coil pump and steam humidifier will be deenergized and the preheat coil valve and humidifier isolation valve will be shut. When the unit is operating in heating mode the discharge temp sensor through the DDC system will modulate the preheat coil valve to maintain a discharge temp of 45 and the humidifier isolation valve will be open and the cooling coil valve will be closed. Once entering the secondary cooling loop before entering the operating spaces the air will pass through a manual balancing isolation damper which is controlled by CCMS through a down stream air monitoring device. Seconaday cooling will be modulated by a 3 way valve and will be reheated if needed (reheat coils are the next component down stream). When cooling mode is activated the preheat coil pump and steam humidifier will be deenergized and the preheat coil valve and humidifier isolation valve will be shut. When the unit is operating in heating mode the humidifier isolation valve will be open and the cooling coil valve will be closed. 6.0 Systems Costs: The building is a new facility, hence has no operating history. The following mechanical system costs, supply actual values for the all three wings of the hospital combined and they are 14

15 further broken down into three main costs Mechanical/ Plumbing/Med.Gas (combined), Sprinklers and Electrical. The system cost represented show that the Mechanical overall cost is the most expensive per square foot of the building. This makes sense due to all the specialty equipment needed to maintain safety with in the critical care environment. System's Cost Type Cost ($) Cost/sq.ft. ($) Sprinkler 836, *Mechanical 17,200, Electrical 9,200, Total: 27,236, *(Includes all Mech., Plumbing, and Med. Gas ) INOVA Table 7: System s Cost The excluding ducting and piping the majority of the mechanical equipment is mainly located in the basement and penthouse floors. The Chiller and Steam Boilers are not located within the building but are on the property and are located in an existing central plant The mechanical systems for the INOVA Heart Institute can be characterized as non-typical and specialized and have higher amount of safety associated with them. The Overall cost for the building was $80 million per square foot the mechanical systems make up approximately 21% of the overall cost of the entire building. 7.0 Critique: I believe the system is very well organized and serves its purpose for maintaining sufficient and safe conditions in a hospital environment. Indoor air quality issues, which are of most importance in this type of facility, are satisfied with high filtration and pressurization in each system. The use of a common duct system for each air systems allows for constant supply air to all spaces this insures that every space will get served. This is critical for maintaining safe and healthy conditions within a hospital. This common duct system also allows for extra AHU s to be added and used as back-ups in the event of failure of one of the on-line AHU s. Back up AHU s were used in all 3 constant volume systems which serves the majority of the hospital. The variable volume system is meant for the front entrance and is dependent and varies with load. Occupancy would be the major source of load in this system. I do think that conditioning air to such extremes is somewhat redundant and wasteful. An example of this is when looking at total heating load, depending on OA conditions air is brought into the system preheated humidified and then cooled to a LAT of about 51 F dry bulb then it is sent down the shaft and before entering each space is terminally reheated to a room supply temperature of 55 F dry bulb. I believe this is done to always maintain a constant entering room air temp. The hospital runs reheat water to over 600 terminal (constant and variable volume) units. This does not include the various unit heaters and radiant panels. This method uses a lot of energy as was shown in the heating load estimate and might want to be reconsidered. The benefit of using a centralized plant that provides steam and chilled water to multiple facilities reduces operating cost significantly for the INOVA Health System (owners of the new INOVA Heart Institute). 15

16 8.0 References: 9.0 Appendix: 1. ASHRAE Standard , Energy Standards for Buildings. 2. Penn State Architectural Engineering Department, Thesis Advisors Mechanical Option. 3. Turner Construction, Construction Drawings, Shop Drawings and Specifications. 4. Virginia Power, Schedule GS-3U /customer/pdf/va/vags3u.pdf 5. Washington Gas Light Company, Commercial and Industrial Service Schedule No. 2 16

17 9.1 Appendix: Equipment Schedules Appendix

18 Equipment Schedules Fan Schedule Filter Schedule Design Service Cfm Sp in Approx BHP HP motor Wheel Nom Approx Ban No. Cartridge Face Media Area Maximum Efficiency H20 RPM Size Dia in Desig Type CFM Dimesion Cartridges Size Vel. Per Initial RF-1 RA AHU-1 32, LxHxD LxHxD FPM Cartridge PD In Wg % RF-2 RA AHU-2 32, F-1-1 A 40, "x120"x 25 24"24"2" % RF-3 RA AHU-3 32, F-1-2 B 40, "x120"x 25 24"24"12" % RF-4 RA AHU-4 32, F-1-3 C 40, "x120"x 25 24"24"12" % *RF-5 RA AHU-5 28, F-1-4 D 3,000 48"x24"x "24"12" % *RF-6 RA AHU-5 28, F-1-5 D 3,000 48"x24"x "24"12" % RF-7 RA AHU-7 32, F-2-1 A 40, "x120"x 25 24"24"2" % RF-8 RA AHU-8 32, F-2-2 B 40, "x120"x 25 24"24"12" % RF-9 RA AHU-9 32, F-2-3 C 40, "x120"x 25 24"24"12" % RF-10 RA AHU-10 32, F-3-1 A 40, "x120"x 25 24"24"2" % EF-1 TB EXH 9, F-3--2 B 40, "x120"x 25 24"24"12" % EF-2 TB EXH 9, F-3-3 C 40, "x120"x 25 24"24"12" % EF-3 TB EXH 8, F-4-1 A 40, "x120"x 25 24"24"2" % EF-4 TB EXH 8, F-4-2 B 40, "x120"x 25 24"24"12" % EF-5 TOILET EXH 5, F-4-3 C 40, "x120"x 25 24"24"12" % EF-6 TOILET EXH 5, F-5-1 A 32, "x120"x 20 24"24"2" % EF-7 TOILET EXH 10, F-5-2 B 32, "x120"x 20 24"24"12" % EF-8 TOILET EXH 4, F-5-3 C 32, "x120"x 20 24"24"12" % EF-9 TOILET EXH 7, F-6-1 A 32, "x120"x 20 24"24"2" % EF-10 GEN EXH 1, F-6-2 B 32, "x120"x 20 24"24"12" % EF-11 GEN EXH 1, F-6-3 C 32, "x120"x 20 24"24"12" % ***EF-12 KITCHEN EXH 1, F-7-1 A 40, "x120"x 25 24"24"2" % EF-13 DISH EXH F-7-2 B 40, "x120"x 25 24"24"12" % VF-1 BASEMENT MECH 12, F-7-3 C 40, "x120"x 25 24"24"12" % VF-2 ELEC ROOM 7, F-8-1 A 40, "x120"x 25 24"24"2" % VF-3 PENTHOUSE 25, F-8-2 B 40, "x120"x 25 24"24"12" % GF-1 GARAGE 30, F-8-3 C 40, "x120"x 25 24"24"12" % SPF-1 STAIR PRESS'ZN SO 13, F-9-1 A 40, "x120"x 25 24"24"2" % SPF-2 STAIR PRESS'ZN NO 11, F-9-2 B 40, "x120"x 25 24"24"12" % VF-4 F-9-3 C 40, "x120"x 25 24"24"12" % VF-5 TUNNEL VENT 6, F-10-1 A 40, "x120"x 25 24"24"2" % VF-6 FAN RM VENT /25 10 F-10-2 B 40, "x120"x 25 24"24"12" % RF-11 RA AHU-11,12,13 32, F-10-3 C 40, "x120"x 25 24"24"12" % RF-12 RA AHU-11,12,13 32, F-11-1 A 7,000 72"x48"x "24"2" % RF-13 RA AHU-11,12,13 32, F-11-2 B 7,300 72"x48"x "24"2" % EF-14 GENERAL EXH 4, F-11-3 C "x12"x "24"2" % VF-7 CVOR MECH RM 20, F-12-1 A 40, "x120"x 25 24"24"2" % F-12-2 B 40, "x120"x 25 24"24"12" % F-12-3 C 40, "x120"x 25 24"24"12" % F-13-1 A 40, "x120"x 25 24"24"2" % F-13-2 B 40, "x120"x 25 24"24"12" % F-13-3 C 40, "x120"x 25 24"24"12" % F-14-1 A 40, "x120"x 25 24"24"2" % F-14-2 B 40, "x120"x 25 24"24"12" % F-14-3 C 40, "x120"x 25 24"24"12" % F-OR-1 D 3,440 48"x24"x "24"12" % F-OR-2 D 3,440 48"x24"x "24"12" % F-OR-3 D 3,440 48"x24"x "24"12" % F-OR-4 D 3,420 48"x24"x "24"12" % F-OR-5 D 3,420 48"x24"x "24"12" % F-OR-6 D 3,420 48"x24"x "24"12" % page 1

19 Equipment Schedules Steam Humidifier Desig Service CFM Face Vel Steam Capacity Duct Casing Number of FPM Pressure LBS/HRs Size Size Manifolds Steam WxH SH-1 AHU-1 40, PSI "x120" 6 SH-2 AHU-2 40, PSI "x120" 6 SH-3 AHU-3 40, PSI "x120" 6 SH-4 AHU-4 40, PSI "x120" 6 SH-5 AHU-5 32, PSI "x96" 6 SH-6 AHU-6 32, PSI "x96" 6 SH-7 AHU-7 40, PSI "x120" 6 SH-8 AHU-8 40, PSI "x120" 6 SH-9 AHU-9 40, PSI "x120" 6 SH-10 AHU-10 40, PSI "x120" 6 SH-11 EP LAB Ass 3, PSI "x24" - 2 SH-12 AHU-11 40, PSI "x120" 6 SH-13 AHU-12 40, PSI "x120" 6 SH-14 AHU-13 40, PSI "x120" 6 SH-15 CVOR-1 3, PSI 58 54"x30" 120"x120" 6 SH-16 CVOR-2 3, PSI 58 54"x30" - 2 SH-17 CVOR-3 3, PSI 58 54"x30" - 2 SH-18 CVOR-4 3, PSI 57 54"x30" - 2 SH-19 CVOR-5 3, PSI 57 54"x30" - 2 SH-20 CVOR-6 3, PSI 57 54"x30" - 2 Air Handling Unit Schedule Fan Section Cooling Section Heating Section Desig Duty cfm min OA TSP in. Motor RPM Wheel EAT (F) LAT ( Total Sens GPM: Max MIN TOT MAX Min EAT LAT Max MIN TOT MAX cfm H20 BHP HP Dia. in. DB WB DB WB MBH MBH 42 F E H20 PD Face Face Vel Rows F F 190 F 30 F H20 PD Face Face Vel 57 F LWT FT H2O (SQFT) (FPM) EWT Delta T FT H2O (SQFT) (FPM) AHU-1 Patient FL 40,000 12, AHU-2 Patient FL 40,000 12, AHU-3 Patient FL 40,000 12, AHU-4 Patient FL 40,000 12, AHU-5 Atrium 32,000 8, AHU-6 Atrium 32,000 8, AHU-7 Patient FL 40,000 12, AHU-8 Patient FL 40,000 12, AHU-9 Patient FL 40,000 12, AHU-10 Patient FL 40,000 12, MAHU-1 Kitchen AHU-11 CVOR 40,000 12, AHU-12 CVOR 40,000 12, AHU-13 CVOR 40,000 12, Air Conditioning Unit Schedule Design ACUService Fan Data DX cooling coil data Humidifer Electrical Air Cooled Condenser Unit Data CFm Esp in. Motor EAT F Total Sense Min Tot Max famin LBS/HR KW V/PH/HFLA Design OutDoor Fan Outdoor Coil H20 Hp DB WB MBH MBH Face AreVel FPRows CFM Motor OutdooTotal Face (ft^2) size Temp FArea ACU-1 OOPA /3p 8.4 ACCU ACU-2 OOPA /3p 8.4 ACCU ACU-3 OOPA /3p 7.2 ACCU ACU-4 OOPA /3p 8.4 ACCU ACU-5 OOPA /3p 4.8 ACCU ACU-6 OOPA /3p 8.4 ACCU EL-ACU-1 O5PC / /1p 1.6 CU EL-ACU-2 O5PC @ 1/ /1p 2.6 CU EL-ACU-3 O5PC @ 1/ /1p 2.6 CU page 2

20 Equipment Schedules Secondary Heating Water Coil Schedule Desig Duty CFM Heating Max Air Min EAT F LAT F Sensible Max H20 Max Face PD in H20 Rows Expansion Tank Schedule DB DB MBH 190 F EWTFT-H2O Vel FPM Fin/ in Desig Duty Tank type Dimesion Dry Remarks HWC-1 CVOR Volume Dia Height Weight HWC-2 CVOR Gal HWC-3 CVOR ET-1 Re-Heat H Diaphragm 48"ph Vertical HWC-4 CVOR ET-2 Pre-Heat H2 528 Diaphragm 48"ph Vertical HWC-5 CVOR ET-3 Pre/Re-Hea 119 Diaphragm 24"ph Vertical HWC-6 CVOR ET-4 ndary chilled 37 Diaphragm 20"ph Vertical Duplex Condensate Return Unit Schedule Desig Service Capacity GPM Head ft Reciever Pump Motor Sqft EDR Water Size Discharge SHP CRU-1 Base Mech GAL 4"ph 7 1/2 CRU-2 Kitchen Dis GAL 1 1/4"ph 1/2 CRU-3 CVOR Mec GAL 1 1/4"ph 3/4 Unit Heater Desig Nominal Cap F Maximum Motor HP Rpm Electrical CFM 190 F EWT Delta T H20 H20 PD FT H20 UH / /3ph/60 Constant Volume RA Terminal Unit Schedule UH / /3ph/60 Desig CFM Outlet Inlet Stat PressMax Noise Service UH / /3ph/60 Size in. Size in. Drop in W1.5 in H20 UH / /1ph/60 inlet SP "x18" 24"x16" CVOR 1 Fin Tube Radiation Schedule "x18" 24"x16" CVOR 2 Desig heating element Average Nominal "x18" 24"x16" CVOR 3 Tube Dia Fin Size Fin Spacing Element water Capcity "x18" 24"x16" CVOR 4 fin/ft Length temp F BTU/HR "x18" 24"x16" CVOR 5 1 1" 2 3/4 "x3" 48 6'-0" "x18" 24"x16" CVOR 6 2 1" 2 3/4 "x3" 48 8'-0" " 2 3/4 "x3" 48 3'-0" Hydronic Radiant Ceiling Panel Schedule Desig CAP Mean H20 GPM Delta P Dimesion Type MBH Temp F (ft) LxW in. RP x16 Linear RP x24 Modular Roof Ventilator Schedule Design Duty CFM Max Air Pd Throat Throat AreApprox in H20 Vel FPM Sqft Weight RV-1 RF-11, RF RV-2 Exst AHU page 3

21 Equipment Schedules Sound Attenuator Schedule Design Duty No Size Capcity Max PD Face Vel Minimum DB Reduction by Octave Band Pump Schedule Atten LxHxW in CFM In. H20 FPM Desig Duty Type GPM Head Suction x HP RPM Efficiency SA-1-1 AHU x48x Feet H2O Discharge SA-1-2 RF-1,2,3 4 36x48x HWP-1 Re-Heat H20 A x % SA-1-3 RF-1,2,3 4 36x48x HWP-2 Re-Heat H20 A x % SA-2-1 AHU x48x HWP-3 PRe-Heat H20 A x % SA-3-1 AHU x48x HWP-4 PRe-Heat H20 A x % SA-4-1 AHU x48x HWP-5 PRe-Heat H20 A x % SA-5-1 AHU x48x FP-1 Fire Pump B x % SA-5-2 RF-4,5 4 36x48x CRP-1 Recirc Pump AH C x % SA-6-1 AHU x48x CRP-2 Recirc Pump AH C x % SA-7-1 AHU x48x CRP-3 Recirc Pump AH C x % SA-7-2 RF-6,7,8 4 36x48x CRP-4 Recirc Pump AH C x % SA-7-3 RF-6,7,8 4 36x48x CRP-5 Recirc Pump AH C x % SA-7-4 RF-6,7,8 4 36x48x CRP-6 Recirc Pump AH C x % SA-8-1 AHU x48x CRP-7 Recirc Pump AH C x % SA-9-1 AHU x48x CRP-8 Recirc Pump AH C x % SA-10-1 AHU x48x CRP-9 Recirc Pump AH C x % SA-11-1 AHU x48x CRP-10 Recirc Pump AH C x % SA-12-1 AHU x48x CRP-11 Recirc Pump AH C x % SA-13-1 AHU x48x CRP-12 Recirc Pump AH C x % SA-14-1 CVOR RF 2 120x48x CRP-13 Recirc Pump AH C x % SA-14-2 CVOR RF 2 60x42x HRP-1 Water Recircula C x % HRP-2 Water Recircula C x % HRP-3 Water Recircula C x % HRP-4 Water Recircula C x % BP-1 mestic Water Boo x % BP-2 mestic Water Boo x % Steam/Heating Water Converter Schedule BP-3 mestic Water Boo x % Desig Approx Capacity HWP-6 CVOR Re- Heat A x % GPM EWT FLWT F Tube Vel Max Press No Heati Fouling Steam Sat SteaCond Size BTUH HWP-7 CVOR Re- Heat A x % Drop in H2 Pass Surfa Factor Pressu Temp Load SCHP-1 econd Chilled H2 A x % HE PSI 298 F 6650 L16"x48" SCHP-2 econd Chilled H2 A x % HE PSI 298 F 6650 L16"x48" HE PSI 298 F 6680 L18"x36" HE PSI 298 F 6680 L18"x36" HE PSI 298 F 6680 L18"x36" HE S PSI 298 F 2244 L12"x36" HE S PSI 298 F 2244 L12"x36" HE S PSI 298 F 2244 L12"x36" Fan Coil Unit Schedule Design Service Fan Data Cooling Coil Data Heating Coil Data CFM Motor Esp in EAT LAT Total Sens H20No EAT MBH Max H20 Min HP H20 DB WB MBH MBH 42 F EWPD FT Rows F 190 F EWTPD FT Rows F F 57 F LWH F LWTH20 FCU-1 Stairwell FCU-2 Stairwell FCU-3 Stairwell FCU-4 Stairwell FCU-5 Stairwell FCU-6 Stairwell FCU-7 Stairwell FCU-8 Stairwell FCU-9 Stairwell FCU-10 Stairwell page 4

Technical Assignment 3 11/15/04. Executive Summary

Technical Assignment 3 11/15/04. Executive Summary Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria

More information

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3 Existing System Evaluation Executive Summary The MBNA Career Services Center is a 44,000 square foot, 4-story office type building at Penn State University, University Park Campus. The building is located

More information

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Technical Report #3 Mechanical Systems Existing Conditions Evaluation Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents

More information

4. OVERVIEW OF MECHANICAL SYSTEM

4. OVERVIEW OF MECHANICAL SYSTEM 4. OVERVIEW OF MECHANICAL SYSTEM The 87,000 SF SLCC is served by six (6) Trane M-Series Climate Changer Air Handing Units (AHUs). Each unit serves a distinct zone within the facility that is unique in

More information

TECHNICAL REPORT 3: Mechanical Systems and Existing Conditions. Michael Morder Mechanical Option Advisor: Dr. William Bahnfleth

TECHNICAL REPORT 3: Mechanical Systems and Existing Conditions. Michael Morder Mechanical Option Advisor: Dr. William Bahnfleth TECHNICAL REPORT 3: Mechanical Systems and Existing Conditions Michael Morder Mechanical Option Advisor: Dr. William Bahnfleth INOVA South Patient Tower Falls Church, VA November 16, 2011 Table of Contents

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Technical Assignment 3. Mechanical Systems Existing Conditions Evaluation

Technical Assignment 3. Mechanical Systems Existing Conditions Evaluation Technical Assignment 3 Mechanical Systems Existing Conditions Evaluation The Milton Hershey School New Supply Center Prepared for: William P. Bahnfleth, Ph.D., P.E., Professor Department of Architectural

More information

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

EADQUARTERS. Technical Report One. Stephanie Kunkel   Mechanical Option EADQUARTERS 707 N. Calvert St. Technical Report One ASHRAE Standard 62.1 Ventilation ASHRAE Standard 90.1 Energy Design Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1 Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9

More information

I. Introduction and Arrangement

I. Introduction and Arrangement Joseph Firrantello - Mechanical Option Primary Faculty Consultant: Freihaut Laboratory Facility, Eastern Pennsylvania Mechanical Assignment 3 Existing Conditions Report 11.14.03 Executive Summary The purpose

More information

Redesign of Bennett Hall HVAC System

Redesign of Bennett Hall HVAC System MEE 488 April 18, 2006 Redesign of Bennett Hall HVAC System Greg Andreasen Michael Chicoine Florent Hohxa Jason Jacobe Mechanical Engineering, University of Maine, Orono ME 04473, USA ABSTRACT Our task

More information

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS AND APPLICATIONS Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS Earliest air conditioning system used only for heating (winter) Provided heated air for comfort

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

Mechanical Technical Report 3. Mechanical Systems Existing Conditions Evaluation

Mechanical Technical Report 3. Mechanical Systems Existing Conditions Evaluation Mechanical Technical Report 3 Lutheran Theological Seminary at Philadelphia The New Learning Center Prepared For: William P. Bahnfleth, Ph.D., P.E. Department of Architectural Engineering Pennsylvania

More information

Terminal. Las Vegas, NV. Technical

Terminal. Las Vegas, NV. Technical McCarran International port Terminal 3 Technical Assignment 3 Mechanical System Existing Conditions Evaluation December 3, 2007 Prepared By: Faculty Advisor: Dr. William Bahnfleth, Ph.D., P..E. Table of

More information

11/2 ORT THREEE. Virtua Repla. acement Hospi. ital. Voorhees NJ. Justin Prior. Mechanical

11/2 ORT THREEE. Virtua Repla. acement Hospi. ital. Voorhees NJ. Justin Prior. Mechanical 11/2 29 Virtua West Jersey Repla acement Hospi ital Voorhees NJ TECHNICAL REPO ORT THREEE System Overview Justin Prior Mechanical Table of Contents Executive Summary 3 System Overview 4 Design Factors

More information

Technical Assignment 3

Technical Assignment 3 0 David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option Technical Assignment 3 Mechanical Systems and Existing Conditions Report David H. Koch Institute for Integrative

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size...

More information

Appendices. Included in this section are

Appendices. Included in this section are Appendices Included in this section are Appendix A Building Overview Appendix B Alternative Mechanical Designs Appendix C Integration of Structural System and Constructability 68 Appendix A Building Overview

More information

Computing Services Center

Computing Services Center Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Continuous Commissioning: A Valuable Partner to Retrofit Projects Continuous Commissioning: A Valuable Partner to Retrofit Projects Yeqiao Zhu Aamer Athar Kenneth Banks Ph.D. PE, CEM PE, CEM Energy Systems Laboratory Sempra Energy Solutions Sempra Energy Solutions Charles

More information

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae APPENDIX C Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 12:56PM Air System Information Air System Name Equipment Class Air System Type Lobby System CW AHU SZCAV Number

More information

Existing Mechanical System Operation

Existing Mechanical System Operation majority of the air handlers. There are louvers along the north side of the building that allow for outdoor air to come in and feed the air handlers. On levels 4-8 the research laboratories are variable

More information

Description of All Alternatives Considered-

Description of All Alternatives Considered- Description of All Alternatives Considered- Energy efficiency is an area where the Tubman design can be improved. The design heating load is 1807.8 MBH and the design cooling load is 1702.2 MBH or 142

More information

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee ASHRAE WILL GIVE YOU THE WORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique CTTC

More information

The Temperature and Relative Humidity Control in Cushing Library

The Temperature and Relative Humidity Control in Cushing Library The Temperature and Relative Humidity Control in Cushing Library Chenggang Liu Research Associate Song Deng Assistant Director Homer L. Bruner, Jr., CEM Mechanical Systems Specialist Utilities Office of

More information

Christopher Kelly Technical Report Three

Christopher Kelly Technical Report Three Christopher Kelly Technical Report Three Mechanical Systems and Existing Conditions Evaluation SALK HALL ADDITION The University of Pittsburgh, Pittsburgh Christopher Kelly, Mechanical Option Professor

More information

MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY

MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY 2018 57 MECHANICAL ASSESSMENT MECHANICAL ASSESSMENT This report section includes an overview of the existing

More information

Architectural Alliance Incorporated MDP CONSULTING ENGINEERS, INC N 11th Street Beaumont, TX 77702

Architectural Alliance Incorporated MDP CONSULTING ENGINEERS, INC N 11th Street Beaumont, TX 77702 04/08/2013 last saved: TRENT plotted: DRAWN BY: TLH CHECKED BY: DWD 04/08/2013 last saved: DMCPHERSON plotted: DRAWN BY: TLH CHECKED BY: DWD 04/08/2013 last saved: DMCPHERSON plotted: DRAWN BY: TLH CHECKED

More information

Technical Development Program

Technical Development Program Technical Development Program PRESENTED BY: James Parker Insert your logo here AIR HANDLERS Coils: Direct Expansion Chilled Water and Heating Menu Section 1 Introduction Section 2 Typical Coil Applications

More information

Technical Report Three

Technical Report Three Technical Report Three Existing Conditions for Mechanical Systems Contents Executive Summary...2 Building Overview...2 Mechanical Systems Overview...2 Mechanical System...3 Outdoor & Indoor Design Conditions...3

More information

MT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS

MT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS CARROLL COUNTY PUBLIC SCHOOLS LIFE CYCLE COST ANALYSIS SUMMARY DGS PROCEDURES FOR THE IMPLEMENTATION OF LIFE CYCLE COST ANALYSIS AND ENERGY CONSERVATION OCTOBER, 2010 G.A.I.#09090 GIPE ASSOCIATES, INC.

More information

HVAC Mandatory Provisions Part II, Page 1

HVAC Mandatory Provisions Part II, Page 1 HVAC Mandatory Provisions Part II, Page 1 Mandatory Equipment Efficiency Worksheet (6.4.1.1) System Equipment Type Size Category (Tables 6.8.1A through K) Sub-Category or Rating Condition Units of Efficiency

More information

ASHRAE Illinois Chapter 2015 Excellence in Engineering Awards

ASHRAE Illinois Chapter 2015 Excellence in Engineering Awards ASHRAE Illinois Chapter 2015 Excellence in Engineering Awards PROJECT Chicago Vocational Career Academy Chicago, Illinois OWNER Chicago Public Schools PREPARED FOR American Society of Heating Refrigerating

More information

S H R E V E P O R T, L O U I S I A N A File: ARCHIVE MAIN STORAGE 102 09 / 18 / 2018 REVISIONS BY SCHEMATIC DESIGN SET DESIGN DEVELOPMENT SET CONSTRUCTION DOCUMENT SET CLIENT REVIEW SET AS-BUILT DOCUMENT

More information

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story

More information

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,

More information

The Ed Roberts Campus

The Ed Roberts Campus The Ed Roberts Campus Technical Report 3 Anderson Clemenceau Mechanical Option Advisor: Donghyun Rim November 11, 2014 2 Contents Technical Report 3... 1 Executive Summary... 3 Building Overview... 4 Design

More information

TECHNICAL REPORT III Mechanical Systems Existing Conditions

TECHNICAL REPORT III Mechanical Systems Existing Conditions TECHNICAL REPORT III Mechanical Systems Existing Conditions TEMPLE UNIVERSITY TYLER SCHOOL OF ART Pennsylvania State University Architectural Engineering Mechanical Option Faculty Adviser: Dr. Jim Freihaut

More information

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK ENERGY CONSERVATION MEASURE 1 Partial Steam System Decentralization SIEMENS will Furnish and Install condensing hot water boilers with associated

More information

COMcheck Software Version Interior Lighting Compliance Certificate

COMcheck Software Version Interior Lighting Compliance Certificate Section 1: Project Information Energy Code: 2009 IECC Project Title: Berry Farms Animal Hospital Project Type: New Construction COMcheck Software Version 4.0.3.0 Interior Lighting Compliance Certificate

More information

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

Chiller Plant Design. Julian R. de Bullet President debullet Consulting Chiller Plant Design Julian R. de Bullet President debullet Consulting 703-483-0179 julian@debullet.com This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer ASHRAE

More information

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory Overview of Chilled Beam Technology Purpose Chilled beam technology is new to the United States but has been used in Europe since the 1950 s. Chilled beams can reduce energy costs, improve indoor air quality,

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 can be

More information

TECHNICAL REPORT 3 Mechanical Systems and Existing Conditions Northfield Mental Healthcare Center Northfield, Ohio

TECHNICAL REPORT 3 Mechanical Systems and Existing Conditions Northfield Mental Healthcare Center Northfield, Ohio Technical Report 3 Northfield Mental Healthcare Center Dr. Stephen Treado Ji Won Park Mechanical Option Fall 2012 TECHNICAL REPORT 3 Mechanical Systems and Existing Conditions Northfield Mental Healthcare

More information

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled FORM 145.05-EG1 (1004) VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU 10 105 Ton Water-Cooled Table of Contents FORM 145.05-EG1 (0804) Features and Benefits.....................................................

More information

SECTION I: EXISITNG SYSTEM AND PROPOSED SYSTEMS

SECTION I: EXISITNG SYSTEM AND PROPOSED SYSTEMS SECTION I: EXISITNG SYSTEM AND PROPOSED SYSTEMS Original Design: Traditional Central Heating and Cooling Heating and Cooling System Schematic Original Design Ventilation Schematic: Existing system summary:

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

2009 IECC Commercial Mechanical Requirements

2009 IECC Commercial Mechanical Requirements BUILDING ENERGY CODES UNIVERSITY 2009 IECC Commercial Mechanical Requirements Ken Baker PNNL-SA-66171 Learning(Objec-ves(( ( 1. Find(minimum(equipment(efficiency(requirements( and(recite(at(least(3(common(terms(for(measuring(

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

AIR HANDLER DESIGN WORK SHEET

AIR HANDLER DESIGN WORK SHEET AIR HANDLER DESIGN WORK SHEET JOB Project: Date Representative Unit Model No. of Units Unit Tag(s) UNIT CONSTRUCTION UNIT ARRANGEMENT: [ HORIZ VERT] [ INDOOR OUTDOOR] [ BASE MTD CEILING HUNG CURB MTD]

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS 550.23-TG5Y (893) CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L2EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility.

More information

DACC Health Sciences Building Air Handler Assessment/Study

DACC Health Sciences Building Air Handler Assessment/Study DACC Health Sciences Building Air Handler Assessment/Study NMSU Facilities and Services Department P.O. Box 30001 Las Cruces, NM 88003-8001 June 14, 2016 Final Submittal 1065 S. Main St., Bldg. D, Ste.

More information

Vertical Air Handler Unit

Vertical Air Handler Unit Bulletin 20-019 (September 2016) Vertical Air Handler Unit For cooling, the unit is designed for R-410A refrigerant (both A/C and Heat Pump) or a chilled water coil. For heating, the unit offers an optional

More information

Appendix 13. Categories of Cooling and Heating systems

Appendix 13. Categories of Cooling and Heating systems EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01

More information

MBNA Career Services Center The Pennsylvania State University University Park Campus

MBNA Career Services Center The Pennsylvania State University University Park Campus University Park Campus Variable Air Volume System and Dedicated Outdoor Air System with Fan Coil Units Comparison AE Senior Thesis Primary Consultant Spring 2003 Dr. Bahnfleth Table of Contents Executive

More information

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-05 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Galveston (TAMU-G) Galveston, Texas Submitted to Texas A&M University

More information

VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN

VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN 20-019 TABLE OF CONTENTS DESIGN & SPECIFICATIONS...3 APPLICATIONS... 3 CABINET CONSTRUCTION... 3 FEATURES AND CONTROLS... 3 DIMENSIONAL DATA... 5 SPECIFICATIONS...

More information

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN September 30, 2015 PBA Project No. 2015.0140.00 PETER BASSO ASSOCIATES INC. CONSULTING ENGINEERS 5145 LIVERNOIS ROAD,

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

DIVISION 23 - HVAC HVAC

DIVISION 23 - HVAC HVAC DIVISION 23-23 00 00 PART 1 - GENERAL 1.01 GENERAL CRITERIA A. The heating system typical set point shall be 70 F inside. 1. The winter outdoor design temperature for most systems shall be -6 F. 2. The

More information

CHAPTER 4. HVAC DELIVERY SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer

More information

Architectural Engineering Senior Thesis Mechanical System Redesign

Architectural Engineering Senior Thesis Mechanical System Redesign Saint Joseph Medical Center Architectural Engineering Senior Thesis Mechanical System Redesign Chris Nicolais Building Description Existing Mechanical System Proposed Redesign Alternative Option Emergency

More information

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

terminal units only provide sensible cooling, a separate dehumidification system is usually needed. providing insights for today s hvac system designer Engineers Newsletter volume 44 3 Dual-Temperature Chiller Plants This Engineers Newsletter describes several dual-temperature configurations that can

More information

ASHRAE Standard 62 Ventilation Report Technical Assignment #1. Calvert Memorial Hospital Prince Frederick, MD

ASHRAE Standard 62 Ventilation Report Technical Assignment #1. Calvert Memorial Hospital Prince Frederick, MD ASHRAE Standard 62 Ventilation Report Technical Assignment #1 Prepared By: Holly Mawritz October 6, 2004 Table Of Contents: Executive Summary 2 Assumptions 3 Procedure 4 Sample Calculations 5 System and

More information

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas

More information

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner ESL-TR-99/12-09 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Commerce (TAMU-Commerce) Commerce, Texas Submitted to Texas

More information

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc.

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc. FAARM-Underground Facility Conceptual Design Review Mechanical Systems Prepared by: Dunham Associates, Inc. April 17, 2012 Dunham Project Number: 0412145-000-00 Dunham Associates Inc. Page 1 of 8 Mechanical

More information

Liebert PDX and PCW Thermal Management Systems

Liebert PDX and PCW Thermal Management Systems Liebert PDX and PCW Thermal Management Systems 3 to 8 Ton (11 to 29 kw) Nominal Capacity, Upflow and Downflow, 60 Hz, Air-, Water-, Glycoland Chilled-water-cooled Models System Design Catalog Technical

More information

Mechanical Redesign, Proposal Elizabeth C. Krauss Mechanical Option September 18, 2013

Mechanical Redesign, Proposal Elizabeth C. Krauss Mechanical Option September 18, 2013 Mechanical Redesign, Proposal Elizabeth C. Mechanical Option September 18, 2013 State Institute of Rehabilitation T e c h n i c a l R e p o r t I 1 Mechanical Redesign, Proposal... 0 Executive Summary...

More information

VertiCool Aurora Engineering Guide

VertiCool Aurora Engineering Guide Engineering Guide Effective August 2016 Air-Cooled, Water-Cooled and Water Source Heat Pump Contents Product Features... 3 Options... 4 Physical Data...5-6 Air-Cooled Performance Data (a) (b) (c)...7-8

More information

C13-Series Engineering Guide

C13-Series Engineering Guide Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................

More information

ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS

ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN 20-131.001 Page 1 Copyright 2017 Unico Inc. TABLE OF CONTENTS APPLICATIONS... 3 CABINET CONSTRUCTION... 3 FEATURES AND CONTROLS... 3 DIMENSIONAL

More information

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN Introduction to HVAC Agenda Psychrometrics Human Comfort Heat Transfer Refrigeration Cycle HVAC Terminology HVAC Systems Introduction to HVAC Psychrometrics 2000 TRG-TRC002-EN Properties of Air Dry-bulb

More information

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307 DESCRIPTION Technical Guide CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) This 20 ton evaporator blower is designed with two distinct modules to provide maximum application

More information

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS 036-21096-001 (0101) SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240 20 NOMINAL TONS DESCRIPTION This 20 ton evaporator blower is designed with two distinct modules to provide maximum application flexibility. The

More information

Technical Investigation, Part Three Elizabeth C. Krauss Mechanical Option September 18, 2013

Technical Investigation, Part Three Elizabeth C. Krauss Mechanical Option September 18, 2013 Technical Investigation, Part Three Elizabeth C. Mechanical Option September 18, 2013 State Institute of Rehabilitation T e c h n i c a l R e p o r t I 1 Technical Investigation, Part Three... 0 Executive

More information

General Catalogue. FORM SSI - G.C (94)

General Catalogue. FORM SSI - G.C (94) FORM SSI - G.C (94) www.ssi.co.ir General Catalogue INDEX 09CDF 16DNS 16DES 16JBP 16JBP Air Cooled Condenser Air Cooled Condenser Absorption Chiller Double Effect Direct Fired Absorption Chiller Double

More information

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps Product Data OMNIZONE 50BV020-064 Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps 18 to 60 Nominal Tons omnizonebwlogo 50BVC,E,J,K,Q020-034 SINGLE PIECE OMNIZONE

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

LV Installation Manual

LV Installation Manual LV Installation Manual Includes: LV-50 LV-70 LV-120 LV-140 Manufactured By Energy Saving Products Ltd. ESP 202.02b INSTALLATION, OPERATING, AND MAINTENANCE MANUAL LO-V UNIT INSTALLATION INSTRUCTIONS Lo-V

More information

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS* TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS K*ES120 10 NOMINAL TONS EER 8.5 DESCRIPTION These completely assembled dual circuit evaporator blower units include a well-insulated cabinet, a DX cooling

More information

The Premium Quality Fan Coil Units for Vertical, Horizontal (Left or Right) Application with Direct Expansion, Hydronic or Electric Heat

The Premium Quality Fan Coil Units for Vertical, Horizontal (Left or Right) Application with Direct Expansion, Hydronic or Electric Heat Producing Quality Heating & Cooling Equipment For Over 50 Years DUW/DUX SERIES 1.5 THROUGH 5 TON VERTICAL OR HORIZONTAL FAN COIL UNITS The Premium Quality Fan Coil Units for Vertical, Horizontal (Left

More information

2006 Washington State Nonresidential Energy Code Compliance Form Washington State Nonresidential Energy Code Compliance Forms Revised July 2007

2006 Washington State Nonresidential Energy Code Compliance Form Washington State Nonresidential Energy Code Compliance Forms Revised July 2007 Mechanical Summary 2006 Washington State nresidential Energy Code Compliance Form MECH-SUM 2006 Washington State nresidential Energy Code Compliance Forms Revised July 2007 Project Info Project Address

More information

COMMON WATERSIDE ECONOMIZER APPLICATIONS:

COMMON WATERSIDE ECONOMIZER APPLICATIONS: APPLICATION MANUAL WATERSIDE ECONOMIZER TABLE OF CONTENTS Safety Approvals...1 Common Waterside Economizer Applications...1 Sequence of Operation (Single)...1 Cooling Mode...2 Heating Mode...2 Sequence

More information

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Temperature. In the HVAC area, we talk about two kinds of temperatures. HEATING and COOLING HEATING and COOLING PSYCHROMETRIC CHART Temperature In the HVAC area, we talk about two kinds of temperatures. One is called dry bulb (DB) temperature, a fancy name for the reading

More information

Product Data. 40RUA/40RUS 6to15TonDirectExpansion 7.5to15TonChilledWater Packaged Air---Handling Units FEATURES/BENEFITS. Indoor air quality features

Product Data. 40RUA/40RUS 6to15TonDirectExpansion 7.5to15TonChilledWater Packaged Air---Handling Units FEATURES/BENEFITS. Indoor air quality features A/S 6to15TonDirectExpansion 7.5to15TonChilledWater Packaged Air---Handling Units Product Data Carrier s versatile packaged air-handling units satisfy design requirements with: ---, the environmentally

More information

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate COMcheck Software Version 3.8.2 Mechanical Compliance Certificate 90.1 (2007) Standard Section 1: Project Information Project Type: New Construction Project Title : Rudy's Star Motors Construction Site:

More information

JH Series Installation

JH Series Installation JH Series Installation Space Heating / Fresh Air Make-Up From the Manufacturers of Hi-Velocity Systems TM Includes: JH-15 JH-30 Module-JH-Series-Installation-Manual-010118 Installation JH fan coils by

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

Pharmaceutical Facility Design

Pharmaceutical Facility Design PhEn-602 Pharmaceutical Facility Design J. Manfredi Notes 9A PhEn-602 J. Manfredi 1 Primary & Secondary HVAC units Primary Primary air handling unit arrangement: One unit is responsible for all of the

More information

THERMAL ICE STORAGE: Application & Design Guide

THERMAL ICE STORAGE: Application & Design Guide THERMAL ICE STORAGE: Application & Design Guide Table of Contents: 1. Introduction A. History of Thermal Energy Storage B. Operating and Cost Benefits 2. Applications A Fundamental System B. HVAC Cooling

More information

Technical Assignment 3 Mechanical Systems Existing Conditions Evaluation

Technical Assignment 3 Mechanical Systems Existing Conditions Evaluation Technical Assignment 3 Mechanical Systems Existing Conditions Evaluation City of Hope: Amini Medical Center Duarte, CA Christopher Bratz Pennsylvania State University Architectural Engineering Mechanical

More information

ELECTRICAL QUANTITY WEIGHT (LB)

ELECTRICAL QUANTITY WEIGHT (LB) VRF SYSTEM INDOOR UNIT ENTERING AIR TEMPERATURES ( F) CAPACITIES (kbtuh) Max SOUND ELECTRICAL WEIGHT TOSHIBA-CARRIER COOLING HEATING Airflow PRESSURE, MARK NO. TYPE ROOM TOTAL SENSIBLE HEATING V / Ø /

More information

CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS

CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS 7 Rosemex Products 97 VENTILATION CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS 2 INTRODUCTION Rosemex "Penthouse" units are essentially outdoor mechanical rooms. They group in one compact weather proof outdoor

More information