SERVICE Manual SPLIT TYPE AIR CONDITIONER Indoor Unit AQ18A9(0)RCF AQ24A1(2)RC

Size: px
Start display at page:

Download "SERVICE Manual SPLIT TYPE AIR CONDITIONER Indoor Unit AQ18A9(0)RCF AQ24A1(2)RC"

Transcription

1 SERVICE Manual SPLIT TYPE AIR CONDITIONER Indoor Unit AQ8A9(0)RCF AQ4A()RC Outdoor Unit UQ8A9(0)RCF UQ4A()RC E DB985778A()

2 Safety Precautions The following safety precautions must be taken when using your air conditioner. WARNING Risk of electric shock. Can cause injury or death. Disconnect all remote electric power supplies before servicing, installing or cleaning. This must be done by the manufacturer or its service agent or a similar qualified person in order to avoid a hazard. INSTALLING THE UNIT The unit should not be installed by the user. Ask the dealer or authorized company to install the units except room air conditioners for the U.S.A and Canada area. If the unit is installed improperly, water leakage, electric shock or fire may result. The air conditioner must be installed in accordance with national wiring regulations and safety regulations wherever applicable. Mount with the lowest moving parts at least 8.ft(.5m) above the floor or grade level. (If applicable) The manufacturer does not assume responsibility for accidents or injury caused by an incorrectly installed air conditioner. If you are unsure about installation, contact an installation specialist. When installing the builtin type air conditioner, keep all electrical cables such as the power cable and the connection cord in pipe, ducts, cable channels e.t.c to protect them against liquids, outside impacts and so on. POWER SUPPLY LINE, FUSE OR CIRCUIT BREAKER If the power cord of this air conditioner is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard. The unit must be plugged into an independent circuit if applicable or connect the power cable to the auxiliary circuit breaker. An all pole disconnection from the power supply must be incorporated in the fixed wiring with a contact opening of >3mm. Do not use an extension cord with this product. If the unit is equipped with a power supply cord and a plug, the plug must be accessible after installation. This appliance must be installed accordance with the national wiring regulations.

3 Contents DISASSEMBLE AND REASSEMBLE. Indoor unit. Outdoor unit 4 8 Ι SET UP THE OPTION CODE ΙΙ TROUBLESHOOTING. Items to be checked first. Abnormal diagnosis by symptom 3. Replace PCB module 5 6 ΙΙΙ ASSEMBLY DRAWING AND PART S LIST. Indoor unit. Outdoor unit 3. PCB Box 4 8 ΙΛ REFRIGERATING CYCLE BLOCK DIAGRAM 9 Λ PERFORMANCE CURVE 30 ΛΙ ΛΙΙ PCB DIAGRAM 36 WIRING DIAGRAM. Indoor unit. Outdoor unit ΛΙΙΙ SCHEMATIC DIAGRAM. Indoor unit 4 ΙΧ SPLIT TYPE AIR CONDITIONER 3

4 Disassemble and reassemble Stop operation of the air conditioner and remove the power cable before repairing the Ι unit. Indoor unit If you disassemble the heat exchanger, you must pump down at first. No. Part Procedure Remark Front Panel ) Stop the operation of the air conditioner and block the main power. ) Separate the tape from the front panel. 3) Contract the second finger to the left, and right handle. And pull the inlet grille to open. 4) Take the left and right filter out. *Taking off the deodorizing and Electrostatic filter out. (Option) 5) Loosen one of the right screw and separate the terminal cover. 6) Loosen three screws of front grille. 4

5 No. Part Procedure Remark Front Panel 7) Pull the upper left and right of discharge softly so that the outside cover is pulled out. 8) Pull softly the lower part of discharge and push it up. Caution Assemble the front panel and fix the hooks of left and right. Assembly Tray ) Separate the drain hose from the Drain extension drain hose. ) Take the display PCB out. (Center of the indoor unit) 3) Pull tray drain out from the back body. 5

6 Ι Disassemble and reassemble (cont d) No. Part Procedure Remark 3 Electrical Parts (Main PCB) ) Take out all the connector of PCB on the upper part. ) Separate the outdoor unit connection wire from the terminal block. 3) If you pull out the main PCB up, it will be taken out. 4 Heat Exchanger ) Loosen two ground screws at the right side. ) Separate the connection pipe. 3) Separate the bush body at the upper side and holder at the rear side. 4) Loosen the two screws at the left side. 5) Lift the heat exchanger up a little to push the upper side to separate it from the indoor unit. 6

7 No. Part Procedure Remark 5 Fan Motor and ) Loosen two screws and separate the Cross Fan motor holder. ) Loosen the screw of fan motor. (By use of M3 wrench) 3) Separate the fan motor from the fan. 4) Separate the fan from the left holder bearing. 7

8 Ι Disassemble and reassemble (cont d) Outdoor unit UQ8A9(0)RCF No. Part Procedure Remark Common Work ) Loosen the fixing screws and separate the cover control. ) Separate the connection wire from the terminal block. 3) Loosen the fixing screws and separate the upper cabinet. 4) Loosen the fixing screws and separate the front cabinet. 5) Loosen two screws and pull up the control box. 6) Loosen the nut on the terminal cover and open it. 7)Separate the comp lead wire. 8

9 No. Part Procedure Remark Common Work 8) Loosen the fixing screws and separate the cabinet side. Fan and Motor ) Remove the nut flange (Turn to the clockwise). ) Separate the fan. 3) Loosen four screws to separate the motor. 3 Heat Exchanger and Compressor ) Release the refrigerant at first. ) Disassemble the inlet and outlet pipeby welding. 3) Loosen the fixing screws of the heat exchanger. 4) Separate the heat exchanger. 5) Loosen three bolts of the compressor. 6) Separate the compressor. 9

10 Ι Disassemble and reassemble (cont d) UQ4A()RC No. Part Procedure Remark Common Work ) Loosen the fixing screws and separate the cover control. ) Separate the connection wire from the terminal block. 3) Loosen the fixing screws and separate the upper cabinet. 4) Loosen the fixing screws and separate the front cabinet. 5) Loosen three screws and pull up the control box. 6) Separate the terminal cover and separate the comp lead wire. 0

11 No. Part Procedure Remark Common Work 7) Loosen the fixing screws and separate the cabinet side. Fan and Motor ) Loosen the fixing bolt and separate the fan. ) Loosen four fixing bolts to separate the motor. 3 Heat Exchanger and compressor ) Release the refrigerant at first. ) Disassemble the inlet and outlet pipe by welding. 3) Loosen the fixing screws of the heat exchanger. 4) Separate the heat exchanger. 5) Loosen four bolts of the compressor. 6) Separate the compressor.

12 ΙΙ Set up the option code The method for setting up the model option with the remote control It is necessary to set up option codes after replacing the main PCB with service parts. Make sure that you can set up option codes of the remote control after replacing the main PBA. Otherwise, the unit won t be working properly and all LED lamps on display will be flickering. Step Preparing for the remote control to the main PCB option set.. Remove the battery from the remote control.. Press the temperature button simultaneously and insert the battery again. 3. Make sure the remote control display shown as. Step Preparing for the remote control option set. Note In case that the wrong letter has been selected; continue to press the button until the correct letter appears.. If the number appears on the display, proceed to the second stage.. Every time you press the ) and 7) button, and continue to appear. 3. Every time you press the ), 3), 4), 5), 6), 8), 9), 0), ), ) button, the number increases from ~ (,,,,,,,,, ) and,,,,, in order. ) If the first number is, it is correct. Otherwise, press the button until appears. ) When pressing the button ~ on the display, select one of them. 3) When pressing the button ~ on the display, select one of them. 4) When pressing the button ~ on the display, select one of them. 5) When pressing the button ~ on the display, select one of them. 6) When pressing the button ~ on the display, select one of them.

13 7) If the first number is, it is correct. Otherwise, press the button until appears. 8) When pressing the button ~ on the display, select one of them. 9) When pressing the button ~ on the display, select one of them. 0) When pressing the button ~ on the display, select one of them. ) When pressing the button ~ on the display, select one of them. ) When pressing the button ~ on the display, select one of them. Step 3 Reconfirming the option set after completing Example : 04A5700b7 Press the button for the mode and the display will be shown as. Press the button for the mode and the display will be shown as. Step 4 Pressing the (On/Off) button When pressing the (On/Off)button in the direction of the remote control for unit, it sounds beep or ringing and the first LED (STANDARD)lamp on the left side is flickering at the same time, then the input option is completed. If it doesn t sound ringing, try again by pressing the (On/Off)button. Step 5 Testing the unit Remove the battery from the remote control.. Insert the battery into the remote control. 3. Press the (On/Off)button in the direction of the remote control for set. Note Error mode. If all lamps of the indoor units are flickering, plug out and in again and press the (On/Off)button again.. If the unit doesn t work properly or all lamps are continuously flickering after setting the option code, check that the option code is set properly for its own model. 3

14 ΙΙ Set up the option code(cont d) Table of the option code Model AQ8A9RCF AQ8A0RCF AQ4ARC AQ4ARC Option code 09545A0d 08545A0d 09767A03F 08767A03F 4

15 ΙΙΙ Troubleshooting Items to be checked first ) The input voltage should be rating voltage within ±0% range. The air conditioner may not operate properly if the voltage is out of this range. ) Is the connection cable linking the indoor unit and the outdoor unit properly? The indoor unit and the outdoor unit shall be linked by seven cables. Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables. Otherwise the air conditioner may not operate properly. 3) When a problem occurs due to the contents illustrated in the table below, it is a symptom not related to the malfunction of the air conditioner. No Operation of air conditioner The STD operation indicator, LED blinks when a power plug of the indoor unit is plugged in at first. In the Cool mode, the compressor does not operate at a room temperature higher than the setting temperature while the indoor fan operates. In the Heat mode, the compressor does not operate at a room temperature lower than the setting temperature that indoor fan should operate. The Fan speed operating is not allowed in the Auto or Dry mode. Compressor stops operating intermittently in the Dry mode. Compressor of the outdoor unit is operating although it is turned off in the Heat mode. Only timer LED of the indoor unit lights up and the air conditioner does not operate. The compressor and indoor fan stop intermittently in the Heat mode. Indoor fan and outdoor fan stop operating intermittently in the Heat mode. The compressor stops intermittently in the Cool mode or Dry mode and the fan speed of the indoor unit decreases. Explanation It indicates power is on. The LED stops blinking if the operation On/Off button on the remote control is pushed. It happens after three minutes when the compressor is reoperated. The same phenomenon occurs when a power is on. As a phenomenon that the compressor is reoperated after three minutes, the indoor fan is adjusted automatically with reference to a temperature of the air. The speed of the indoor fan is set to LL in the Dry mode. Fan speed is five steps are selected automatically in the Auto mode. Compressor operation is controlled automatically in the Dry mode depending on the room temperature and humidity. When the unit is turned off while deice is activated, the compressor continues operating for up to 9 minutes (maximum) until the deice is completed. The Timer is being activated and the unit is in the ready mode. The unit operates normally if the timer operation is cancelled. The compressor and indoor fan stop intermittently if room temperature exceeds a setting temperature in order to protect the compressor from overheated air in a Heat mode. The compressor operates in a reverse cycle to remove exterior ice in the Heat mode, and indoor fan and outdoor fan do not operate intermittently for within 0% of the total heater operation The compressor stops intermittently or the fan speed of the indoor unit decreases to prevent inside/outside air from freezing depending on the inside/outside air temperature. 4) Indoor unit observes operation condition of the air conditioner, and displays self diagnosis details on the display panel. No Display STD LED blinking (Hz) TIMER LED blinking (Hz) STD and TIMER LED blinking (Hz) BIO LED blinking (Hz) STD, BIO and TIMER LED blinking(hz) All LED blinking(hz) Self Diagnosis Restore from power failure (input initial power) Indoor unit Room sensor Error (open or short) Indoor unit heat exchanger temperature sensor Error (open or short) Indoor fan malfunctioning (for spead is Below 450rpm) EEPROM Error Option Error (option wasn t setup or option data error) 5

16 ΙΙΙ Troubleshooting (cont d) Abnormal diagnosis by symptom. No Power Initial diagnosis ) Checklist : () Is input voltage normal? (voltage rating within ±0% range) () Is AC power linked correctly? (3) Are connections between primary side, secondary side of the power transformer and PCB good? (4) Is input voltage of DC regulator IC KA7805 (IC0) normal? (VDC.5VDC) (5) Is output voltage of DC regulator IC KA7805 (IC0) normal? (4.5VDC5.5VDC) ) Troubleshooting procedure Remove the power cord and plug it in again in approx. 5 seconds 6 Replace PCB display Is DC voltage of PCB display normal? Is the rating Voltage ±0% range applied to the between # and #3 of CN78 Check linkage between a power cord and a terminal tap Check fuse Does ~.5VDC appear in the input side of the DC regulator IC KA7805(IC0)? Replace PCB module Refer to page Replace resonator (X50) Is operation normal? OK Does the lamp blink? Does it start operating when you push the On/Off button of the remote control? Is transmission display of the remote control unit blinking? Does the beep sound from the main unit? Is DC voltage of the PCB module normal? Are voltages of #8(IC04 : compressor), #7(IC04 : 4way valve) and #6(IC04 : outdoor fan) of Micom normal? 5VDC is voltage of #60((IC04 : indoor fan) of Micom normal? DC5V 0ms Is voltage of #33 terminal of Micom (IC04)normal? 0VDC Is voltage of #8 terminal of Micom (IC04)normal? 5VDC Is voltage of #5 terminal of Micom (IC04)normal? 0ms Are voltage of #48 and #49 of Micom (IC04)normal? Replace Micom 00ns Normal Refer to remote control unit abnormal diagnosis Replace PCB module Refer to page Are voltages at RY7(Compressor) and RY7 (Outdoor fan) normal? ; DCV Is voltage at SS7(indoor fan)? Check PCB pattern Replace PCB module Refer to page OK Check connections compressor, outdoor fan and indoor fan Replace RY7, RY73, RY7 and SS7 Is output voltage of ICO normal?(dc5v) Is voltage output terminal of D0~D05(IN4007) normal? Replace IC0 Replace IN4007

17 . When the Indoor Unit Fan Does Not Operate Initial Diagnosis ) Checklist : () Is the indoor unit fan motor properly connected with the connector (CN73)? () Is the AC voltage correct? (3) Is HALL IC in the indoor fan motor properly connected with the connector (CN43)? (4) Is the running capacitor properly connected with PCB board? ) Troubleshooting procedure After unplugging out, the power cord should be reconnected within five seconds. Does the STD lamp(orange) blink? Check as the procedure No power Refer to page 6 Does the Solid State Relay(SS7) work properly? Test rod location + Normal Voltage Micom is abnormal. SS7 SS7 V Is the supply voltage of the fan motor sufficient? PCB is abnormal. Replace the PCB module Refer to page Test rod location PCB CN73 Condition Normal voltage pin #3 and #5 Fan operate about AC 80V MFC is abnormal. Replace MFC Fan motor is abnormal. Replace Fan motor 7

18 ΙΙΙ Troubleshooting (cont d) 3. When the Outdoor Unit Does Not Operate Initial Diagnosis ) Checklist : () Is input voltage normal? (voltage rating within ±0% range) () Is the set temperature of the remote control higher than room temperature in the Cool mode? (3) Is the POWER IN connector (CN78) linked correctly? (4) Is the outdoor unit properly connected with the terminal block connector(6p)? ) Troubleshooting procedure After unplugging out, the power cord should be reconnected within five seconds. Does the STD lamp blink? Does the timer lamp blink during operation? Check PCB and room temperature sensor Check as the procedure No power Refer to page 6 Room temperature sensor is abnormal. Is the power relay RY7 operated by adjusting the room temperature? 3 PCB is abnormal. Test rod location + Condition IC06 Pin #6 GND RY7 ON Normal Voltage DC 4.8V Replace the PCB module Refer to page Is voltage rating within ±0% range applied relay between CN 78 and 3? Power relay is abnormal. Replace the Power relay Outdoor unit is abnormal. Is the room sensor registered normal? 50 F(0 C) 68 F(0 C) 86 F(30 C) 7.96k Ω.09k Ω 8.3k Ω 3 8

19 4. When the UP/DOWN Louver Motor Does Not Operate Initial Diagnosis ) Checklist : () Is input voltage normal?(voltage rating within ±0% range) () Is the UP/DOWN louver motor properly connected with the connector (CN6)? ) Troubleshooting procedure Remove the power cord and plug it in again in approx. five seconds. Does the STD lamp blink? Does it start operating when you push the swing button of the remote control? Check as the procedure No Power. Refer to page 6. Normal Is voltage of #~#4 of Micom (ICO4) change?(squarewave) Micom (IC04) is abnormal. Is voltage of pin #0, #5 and #6 of IC06 (KID65003) change?(squarewave) Driver IC06(KID65003) or IC06 is abnormal. UP/DOWN louver motor is abnormal. 5. When there is no warm air in the current mode ) Checklist : () Is the set temperature of Remote Control lower than room temperature in the Heat mode? () Is the Indoor PCB properly connected with the CN78 connector? ) Troubleshooting procedure After training on, the Heating starts in five minutes. Normal Is the number #7 of Micom (IC04) DC 4.8 V? Micom is abnormal. Is the number # of IC06 (KID65003) LOW? IC07 is abnormal Is voltage rating between CN7 #5 and CN78 # within ±0% range? 4 way valve of the outdoor unit or connection cable is abnormal. Replace 4 way valve Check connection cable RY73 is abnormal Replace PCB module Refer to page 9

20 ΙΙΙ Troubleshooting (cont d) 6. When the remote control does not operate ) Troubleshooting procedure Remove the power cord and plug it in again approx. five Seconds Does the STD lamp blink? The melody sounds from the indoor unit when you push the On/Off button on the remote control. Is voltage of battery less than.5v (Remote Control Unit)? Is LCD display status of the remote control normal? Check as the procedure No Power Refer to page 6 Normal Replace the battery LCD is abnormal. Does the transmission display lamp blink when you push the On/Off button on the remote control? Is voltage of #30 of remote control of Micom (IC04) changed? Is voltage at collector of Q60 or Q60 changed? Replace button Micom is abnormal. Q60(C4375Y) or Q60(C63Y) is abnormal. IR LED(CLL5EU) is abnormal. Is voltage of #6 of Micom (IC04) changed (Indoor unit)? Receiver module is abnormal. Micom (IC04) is abnormal. 0

21 3 Replace PCB module Remove the power cord Replace the PCB module Check the connection and plug in Does the display lamp blink or STD lamp blink? Refer to set up the option code Replace another PCB module

22 ΙΛ Assembly drawing and part s list Indoor unit

23 Part s List No. Code No. Description Specification DB64007A DB633050C DB950087N DB6064B DB D DB D DB630009A DB640030A DB93003C DB63005A DB B DB3053B DB660004A DB9605A DB9605G DB A DB A DB Y DB60060A DB G DB305D DB J DB A DB A DB930984A DB30007B DB6063A DB940007A DB A DB700663A DB63007A DB70005A DB930086B GRILLE AIR INLET GUARD AIR FILTER CLEANER FILTER ASS Y CASECLEANER FILTER CARBON FILTER CLEANER FILTER COVER TERMINAL FRONT PANEL ASS Y PCB DISPLAY COVER DISPLAY UP ASS Y TRAY DRAIN STEPPING MOTOR BLADEH ASS Y EVAP ASS Y EVAP SPACEREVAP ASS Y HOLDER MOTOR(4K) ASS Y HOLDER MOTOR(8K) HOLDER MOTOR TERMINAL BLOCK ASS Y MOTOR FAN IN ASS YCROSS FAN RUBBER BEARING BEARING MOTOR ASS Y PCB MAIN ASS YTHERMISTOR CASE CONTROL ASS Y BACK BODY ASS Y HOLDER PIPE PLATE HANGER COVERTERMINAL BLOCK PLATEKCKOUT ASS YREMOCON HIPS PP ASS Y PP POLTER/CARBON POLTER/COTTON ABS(V0) HIPS ASS Y ABS(BLK) ASS Y MP4S HIPS PLATE.(5/8 ) SLIT.5(/ ) PVC ASS Y ASS Y PP(Vo) 6P, 5A IIC9430SKC7B ø95 x L CR(BLK) ASS Y PDSH30ZC00 03AT/DSK03FW ABS(VO) ASS Y ASS Y SGCCM ABS SGCCM ASS Y Q TY AQ8A9(0)RCF AQ4A()RC 3

24 ΙΛ Assembly drawing and part s list (cont d) Outdoor unit UQ8A9(0)RCF

25 Part s List No. Code No. Description Specification Q TY DB K DB90060H DB A DB603000A DB300056D DB60008C DB940065A DB96054B DB904076B DB90067L DB90063D 48D90IUEH DB730008A DB603008A DB603008A DB63065D DB9500C DB990046A DB600898B DB990075C DB K DB B DB959006B DB300007A DB750537A DB6700A DB603000A DB603000C ASS YCABI FRONT ASS YBASE OUT FANPROPELLER NUT FLANGE MOTOR FAN OUT BASEMOTOR ASS YPARTITION ASS YCOND UNIT ASS YCOVERCONTROL ASS YCABI BACK ASS YCABI UPPER COMPRESSOR GROMMET ISOLATOR NUT WASHER NUT FLANGE COVERTERMINAL ASS YHEATER ASS Y4WAY V/V PACKED V/V /" ASS YCHECK V/V ASS YCONTROL OUT POWERRELAY CAPACITOR TERMINAL BLOCK ASS Y SPARK KILLER FUSE MOTOR CAPACITOR THERMOSTAT CLOTH SOUND DRAIN PLUG OUT NUT FLARE /4" NUT FLARE /" ASS Y ASS Y AS+G/F0% M6LF ASS030ZTEC SGCCM ASS Y ASS Y ASS Y ASS Y ASS Y PH, 08/30V, 60Hz NR, BLK M8 M5 PBT, BLK 40V, 45W ASS Y PTYPE ASS Y ASS Y UZ A BB0 5A 40uF/450VAC 8P/35A ASS Y A, 50V.5uF/450VAC PW N PP C377BD C377BD 3 3 5

26 ΙΛ Assembly drawing and part s list (cont d) UQ4A()RC

27 Part s List No. Code No. Description Specification Q TY DB900065P ASS YCABI FRONT ASS Y DB9000A ASS YBASE OUT ASS Y 3 DB A FANPROPELLER AS+G/F0% 4 DB60000A BOLT SPECIAL M8 L5 5 DB30007F MOTOR FAN OUT OSM906SRC 6 DB95047A ASS YMOTOR B/K ASS Y 7 DB C ASS YPARTITION ASS Y 8 DB96096B ASS YCONDENSER ASS Y 9 DB904076B ASS Y COVERCONTROL ASS Y 0 DB646060B CABI SIDE OUT SC90073T DB90066D ASS YCABI UPPER ASS Y DB950339G COMPRESSOR H9B6UABCA DB730008A GROMMET MOUNT CR 4 DB603008A NUT WASHER M8 4 3 DB99049E ASS Y4WAY V/V ASS Y 3 DB640055F PACKED V/V 5/8" PTYPE 3 DB60056C 4WAY V/V RANCO(V6905) 4 DB99038H ASS YCHECK V/V ASS Y 5 DB G ASS Y CONTROL OUT ASS Y 5 DB B SWITCH MAGNET 4NBAG CAPACITOR 35µFx450VAC 53 DB B TERMINAL BLOCK 8P, 35A 54 DB959006B SPARK KILLER FUSE A,50V MOTOR CAPACITOR 4µF/450VAC 6 DB75065A CLOTH SOUND COMP 7 DB6700A DRAIN PLUG OUT PP 7 DB603000A NUT FLANGE /4" C377BD 73 DB603000D NUT FLANGE 5/8" C377BD 7

28 ΙΛ Assembly drawing and part s list (cont d) 3 PCB Box Part s List No. Description Specification AQ8A9(0)RCF / AQ4A()RC Q TY Remark ASS Y MAIN PCB DB930984A ASS Y THERMISTOR 03AT / DKS03FW 3 ASS Y PCB DISPLAY ASS Y 4 CASE CONTROL ABS 5 COVER DISPLAY ABS 8

29 Λ Refrigerating cycle block diagram T Liquid side way valve Capillary tube Check valve Capillary tube Heat exchanger (Evaporator) Cross fan Heat exchanger (Condenser) Propeller fan T Gas side 3way valve Compressor 4way valve Cooling Heating Gas leak check point Refrigerating cycle temperature and pressure Model Operating Condition STD Pressure (psi) 3Way Valve Piping Temp.[ F ( C)] T T Use Temp. Condition[ F ( C)] Indoor Outdoor DB WB DB WB Cooling Standard Max over load 64~78 46~54(8~) 46~54(8~) 80(7) 80(7) 67(9) 67(9) 95(35) 95(35) 75(4) 75(4) AQ8A9(0)RCF Heating Low temp Standard Max over load 70~37 90~97(3~36) 40~58(60~70) 67(9) 70() 80(7) 57(4) 59(5) 67(9) 47(8) 75(4) 57(4) 43(6) 65(8) Low temp 70() 59(5) 35() 33() Standard 57~7 46~54(8~) 46~54(8~) 80(7) 67(9) 95(35) 75(4) Cooling Max over load 80(7) 67(9) 5(46) 75(4) AQ4A()RC Heating Low temp Standard Max over load 70~37 90~97(3~36) 40~58(60~70) 67(9) 70() 80(7) 57(4) 59(5) 67(9) 47(8) 75(4) 57(4) 43(6) 65(8) Low temp 70() 59(5) 35() 33() 9

30 ΛΙ Performance curve Note Data is based on condition of indoor humidity 50% and cooling mode. Air flow should be set at HI. AQ8A9(0)RCF Total power consumption (x0 3 kw) Total power consumption Indoor intake air WB temperature( F) Outdoor intake air DB temperature( F) Total capacity (x0 3 Btu/h) Total capacity Indoor intake air WB temperature( F) Outdoor intake air DB temperature( F)

31 Condensing pressure (psi.g) High pressure Indoor DB temperature( F) Outdoor ambient DB temperature( F) Suction pressure (psi.g) Indoor DB temperature( F) Low pressure Outdoor ambient DB temperature( F)

32 ΛΙ Performance curve (cont d) Suction temperature ( F) Suction temperature Indoor DB temperature( F) Outdoor ambient DB temperature ( F) Discharge temperature ( F) Discharge temperature Indoor DB temperature( F) Outdoor ambient DB temperature ( F)

33 AQ4A()RC Total power consumption (x0 3 kw) Total power consumption Indoor intake air WB temperature( F) Outdoor intake air DB temperature( F) Total capacity (x0 3 Btu/h) Total capacity Indoor intake air WB temperature( F) Outdoor intake air DB temperature( F)

34 ΛΙ Performance curve (cont d) Condensing pressure (psi.g) High pressure Indoor DB temperature( F) Outdoor ambient DB temperature( F) Suction pressure (psi.g) Indoor DB temperature( F) Low pressure Outdoor ambient DB temperature( F)

35 Suction temperature Suction temperature ( F) Indoor DB temperature( F) Outdoor ambient DB temperature ( F) Discharge temperature Discharge temperature ( F) Indoor DB temperature( F) Outdoor ambient DB temperature ( F)

36 ΛΙΙ PCB diagram Main PCB 36

37 Part s List Location No. Description Specification C03 CCERAMIC,DISC.nF,0%,400V,Y5U,TP,. C70 CFILM,MPPF 00nF,0%,75V,BK,8x6x,5 CR7 CFILM,MPPF 000nF,+05%,450V,BK,38x8x C70 CFILM,MPEF 0NF,0%,75V,BK,6.5X8.5X RY7,7,73, 74 RELAYMINIATURE VDC,00MW,3000MA,FORM 4 SS7 SSR Vdc,,A,mS,mS IC04 IC MICOM S3C8469(SDIP) IC0 ICVOLT REGU KA7805A,TO0AB,A,0/5C, TN TRANS UEW0.30/UEW0.45,.5KV,KHz,,7Pi FT7 CHOKECOIL LSA0530P,AC50V,A,30.5xx3 BZ6 BUZZER CBE0BA,STICK,,,,,,, F70 FUSE FST,50V,3.5A,0MM,VDE,50T03 F70 HOLDERFUSE FH5H,7.5A,,,,, D0,0,03,04 DIODERECTIFIER N4007,000V,A,DO4,TP 4 D05 DIODERECTIFIER UGB,00V,A,DO04AC,TP ZD DIODEZENER DIODEZENER;MTZ3.6A,3.6V, V,50 ZD3 DIODEZENER DIODEZENER;MTZJB,V,0.5.05V,500m ZD DIODETVS DIODETVS;ST0D00,85/00/5V,00W,DO Q603 TRSMALL SIGNAL TRSMALL SIGNAL;KSA708Y,PNP,800mW,TO9 Q40,60,60 TRSMALL SIGNAL TRSMALL SIGNAL;KSC945,NPN,50mW,TO9,T 3 Q90,90 TRDIGITAL TRDIGITAL;KSR00,PNP,300MW,0K/0K,TO Q0 TRDIGITAL TRDIGITAL;KSR00,NPN,300MW,0K/0K,TO PC PHOTOCOUPLER PHOTOCOUPLER;TR,50600%,00mW,DIP4,ST PC PHOTOCOUPLER PHOTOCOUPLER;TR,0300%,00mW,DIP4,ST IC0 ICPWM CONTROLLER ICPWM CONTROLLER;55,DIP,8P,300MIL,PLAS VA7,7 VARISTOR 560V,500A,7.5x7.5mm,TP R405,406 RCARBON 330ohm,5%,/8W,AA,TP,.8x3.mm R04,05 RCARBON 0OHM,5%,/4W,AA,TP,.4X6.4MM R0 RCARBON 470OHM,5%,/4W,AA,TP,.4X6.4MM R06,50,50,60,604,606,90 RCARBON 0KOHM,5%,/8W,AA,TP,.8X3.MM 7 R0,07,08,40,403,408,603, RCARBON KOHM,5%,/8W,AA,TP,.8X3.MM 9 R605,608 R90,9,9,93 RCARBON 3.3KOHM,5%,/8W,AA,TP,.8X3.MM 4 R0,03 RCARBON 330KOHM,5%,/4W,AA,TP,.4X6.4MM R06,90 RCARBON 4.7KOHM,5%,/8W,AA,TP,.8X3.MM R607 RCARBON 560OHM,5%,/4W,AA,TP,.4X6.4MM R40 RCARBON 6.8KOHM,5%,/8W,AA,TP,.8X3.MM R60 RCARBON(S) KOHM,5%,/W,AA,TP,.4X6.4M R0,03 RMETAL OXIDE(S) 5Kohm,5%,W,AA,TP,4x R404,407 RMETAL 6.8Kohm,%,/8W,AA,TP,.8x3.m C03,04,40 CCERAMIC,MLCAXIAL 0nF,+800%,5V,Y5V 3 C404,903 CCERAMIC,MLCAXIAL nf,0%,50v,y5p,tp, C0,04,07,09,4,6,7, CCERAMIC,MLCAXIAL 00nF,+800%,50V,Y5 4 C8,0,0,40,403,50,90 C05 CAL 000uF,0%,5V,GP,TP,0x0,5 C60 CAL 47uF,0%,50V,GP,TP,6.3x,.5 C08 CAL 470uF,0%,5V,GP,TP,0x6,5 C0,0 CAL 6.8uF,0%,450V,GP,TP,0x6mm,5 X50 RESONATORCERAMIC 4MHz,0.5%,TP,0.0x5.0x F70 FUSERADIAL LEAD 50V,A,TIMELAG,,8.5x CN78 CONNECTORHEADER WALL,3P/5P,R,3.96mm,S CN7 CONNECTORHEADER WALL,3P/5P,R,3.96mm,S CN73 CONNECTORHEADER WALL,3P/5P,R,3.96mm,S CN9 CONNECTORHEADER BOX,0P,R,.5mm,STRAIG CN43 CONNECTORHEADER BOX,3P,R,.5mm,STRAIGH CN4 CONNECTORHEADER BOX,4P,R,.5mm,STRAIGH CN6 CONNECTORHEADER BOX,6P,R,.5mm,STRAIGH IC07 ICMASK ROM 93LC56B,8BIT,,DIP,8P,,, IC03 ICRESET KA7533,DIP,,,,, IC06 ICDRIVE KID65003AP,DIP,6P,STICK,TRAR L0 COIL CHOKE 5.0mH,,8.0*.0,,,PEM0 WIRESO COPPER PI0.6,SN,T,5MM,TAPING_WI 35 PCBMAIN PDSH30ZC00,FR,,,T.6,W97 Q TY 37

38 ΛΙΙΙ Wiring diagram Indoor unit AQ8A9(0)RCF/AQ4A()RC This document can not be used without Samsung s authorization. 38

39 Outdoor unit UQ8A9(0)RCF MARK NAME MARK NAME PR POWER RELAY TB, TERMINAL BLOCK 0S SOLEID COIL FM FAN MOTOR F FUSE(A, 50V~) S SPARK KILLER This document can not be used without Samsung s authorization. 39

40 ΛΙΙΙ Wiring diagram (cont d) UQ4A()RC MARK NAME MARK NAME 5C MAGNETIC CONTACTOR TB, TERMINAL BLOCK 0C SOLEID COIL CH CRANK CASE HEATER C CAPACITOR FM FAN MOTOR F FUSE(A,50V~) S SPARK KILLER This document can not be used without Samsung s authorization. 40

41 ΙΧ Schematic diagram Indoor unit AQ8A9(0)RCF/AQ4A()RC This document can not be used without Samsung s authorization. 4

42 ELECTRONICS This Service Manual is a property of Samsung Electronics Co.,Ltd. Any unauthorized use of Manual can be punished under applicable lnternational and/or domestic law.

SERVICE Manual SPLIT TYPE AIR CONDITIONER Indoor Unit AQ18A9(0)RCF AQ18A9(0)RCFD AQ24A1(2)RC AQ24A1(2)RCD

SERVICE Manual SPLIT TYPE AIR CONDITIONER Indoor Unit AQ18A9(0)RCF AQ18A9(0)RCFD AQ24A1(2)RC AQ24A1(2)RCD SERVICE Manual SPLIT TYPE AIR CONDITIONER Indoor Unit AQ8A9(0)RCF AQ8A9(0)RCFD AQ24A(2)RC AQ24A(2)RCD Outdoor Unit UQ8A9(0)RCF UQ8A9(0)RCFD UQ24A(2)RC UQ24A(2)RCD E DB985778A(4) Safety Precautions The

More information

SERVICE Manual SPLIT TYPE AIR CONDITIONER Indoor Unit AS18A9(0)RCF AS18A9(0)RCFD AS24A1(2)RC AS24A1(2)RCD

SERVICE Manual SPLIT TYPE AIR CONDITIONER Indoor Unit AS18A9(0)RCF AS18A9(0)RCFD AS24A1(2)RC AS24A1(2)RCD AS8A9(0)RCF SM_E_5775 3/0/05 7:6 PM Page 43 SERVICE Manual SPLIT TYPE AIR CONDITIONER Indoor Unit AS8A9(0)RCF AS8A9(0)RCFD AS24A(2)RC AS24A(2)RCD Outdoor Unit US8A9(0)RCF US8A9(0)RCFD US24A(2)RC US24A(2)RCD

More information

ROOM AIR CONDITIONER INDOOR UNIT OUTDOOR UNIT AQ09A5(6)MA UQ09A5(6)MA AQ12A5(6)MC UQ12A5(6)MC SERVICE

ROOM AIR CONDITIONER INDOOR UNIT OUTDOOR UNIT AQ09A5(6)MA UQ09A5(6)MA AQ12A5(6)MC UQ12A5(6)MC SERVICE ROOM AIR CONDITIONER INDOOR UNIT AQ09A5(6)MA AQ2A5(6)MC OUTDOOR UNIT UQ09A5(6)MA UQ2A5(6)MC SERVICE Manual AIR CONDITIONER CONTENTS. Installation 2. Disassembly and Reassembly. Troubleshooting 4. Exploded

More information

SERVICE Manual FREE JOINT MULTI AIR CONDITIONER

SERVICE Manual FREE JOINT MULTI AIR CONDITIONER FREE JOINT MULTI AIR CONDITIONER INDOOR UNIT MH020FPEA MH023FPEA MH026FPEA MH035FPEA MH052FPEA MH8VP2-09 MH9VP2-07 MH9VP2-2 MH026FKEA MH035FKEA MH052FDEA OUTDOOR UNIT MH8VP2X MH9VP2X MH052FXEA2 MH068FXEA4

More information

SERVICE Manual SYSTEM AIR CONDITIONER INDOOR UNIT GH052EAM GH070EAM OUTDOOR UNIT UH052EAMT UH070EAMT. 1. Product Specifications

SERVICE Manual SYSTEM AIR CONDITIONER INDOOR UNIT GH052EAM GH070EAM OUTDOOR UNIT UH052EAMT UH070EAMT. 1. Product Specifications SYSTEM AIR CONDITIONER INDOOR UNIT GH052EAM GH070EAM OUTDOOR UNIT UH052EAMT UH070EAMT SERVICE Manual SYSTEM AIR CONDITIONER CONTENTS 1. Product Specifications 2. Disassembly and Reassembly 3. Set Up the

More information

SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz)

SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz) SPLIT TYPE ROOM AIR CONDITIONER CEILING TYPE (60Hz) Indoor unit MS6YF Outdoor unit MR6YF CONTENTS SPECIFICATIONS... OUTLINE AND DIMENSIONS... REFRIGERANT SYSTEM DIAGRAM.... CIRCUIT DIAGRAM... INDOOR PCB

More information

SERVICE Manual CASSETTE TYPE AIR CONDITIONER INDOOR UNIT KH026EAM KH035EAM OUTDOOR UNIT UH026EAM UH035EAM. 1. Product Specifications

SERVICE Manual CASSETTE TYPE AIR CONDITIONER INDOOR UNIT KH026EAM KH035EAM OUTDOOR UNIT UH026EAM UH035EAM. 1. Product Specifications CASSETTE TYPE AIR CONDITIONER INDOOR UNIT KH026EAM KH035EAM OUTDOOR UNIT UH026EAM UH035EAM SERVICE Manual AIR CONDITIONER CONTENTS 1. Product Specifications 2. Disassembly and Reassembly 3. Block Diagrams

More information

RC-54CA RO-50CA RC-54HA RO-50HA. SPLIT TYPE AIR CONDITIONER CASSETTE TYPE (50Hz) Indoor unit Outdoor unit

RC-54CA RO-50CA RC-54HA RO-50HA. SPLIT TYPE AIR CONDITIONER CASSETTE TYPE (50Hz) Indoor unit Outdoor unit SPLIT TYPE AIR CONDITIONER CASSETTE TYPE (50Hz) Indoor unit Outdoor unit RCW-54CB RO-50CA RC-54CA RO-50CA RC-54HA RO-50HA CONTENTS SPECIFICATIONS OUTLINE AND DIMENTIONS CIRCUIT DIAGRAM REFRIGERANT SYSTEM

More information

CEILING type (60Hz) SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models

CEILING type (60Hz) SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models SPLIT TYPE ROOM AIR CONDITIONER CEILING type (60Hz) Models Indoor unit ABU6RSLX Outdoor unit AOU6RLX CONTENTS SPECIFICATIONS....................... OUTLINE AND DIMENSIONS............. REFRIGERANT SYSTEM

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASY9USCCW ASY9USCCW ASY12USCCW Outdoor unit AOY9USCC AOY9UFCC AOY12USCC CONTENTS SPECIFICATIONS................................... 1

More information

SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS

SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS SPECIFICATION... 1 FUNCTIONS... 5 SERVICE FUNCTION EXPLANATION... 7 OPERATION DETAILS... 8 TROUBLESHOOTING GUIDE... 13 PERFORMANCE

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models CONTENTS

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models CONTENTS SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASY9USCCW ASY9USCCW ASY12USCCW Outdoor unit AOY9USCC AOY9UFCC AOY12USCC CONTENTS SPECIFICATIONS.................. 1 OUTLINE AND DIMENSIONS.........

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER CONTENTS. Models SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASY9USCCW ASY9USCCW ASY12USCCW Outdoor unit AOY9USCC AOY9UFCC AOY12USCC CONTENTS SPECIFICATIONS.................. 1 OUTLINE AND DIMENSIONS.........

More information

CASSETTE type INVERTER MULTI AIR CONDITIONER. Models AUY12LBAB AUY14LBAB AOY18LMAK2

CASSETTE type INVERTER MULTI AIR CONDITIONER. Models AUY12LBAB AUY14LBAB AOY18LMAK2 INVERTER MULTI AIR CONDITIONER CASSETTE type Models Indoor unit AUY12LBAB AUY14LBAB Outdoor unit AOY18LMAK2 CONTENTS SPECIFICATIONS..................... 1 OUTLINE AND DIMENSIONS........... 2 REFRIGERANT

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH530 Models MU-GE50VB- E1 - E1 Indoor unit service manual MS/MSH-GE VB Series (OBH529) CONTENTS 1. TECHNICAL CHANGES 2 2. PART

More information

TECHNICAL & SERVICE MANUAL. Ceiling Concealed

TECHNICAL & SERVICE MANUAL. Ceiling Concealed STAND BY DEFROST CHECK CLOCK ON OFF NOT AVAILABLE FILTER CHECK MODE TEST RUN FUNCTION SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL Series SEZ Ceiling Concealed R40A.OC0 REVISED EDITION-A

More information

FLOOR CONSOLE / UNDER CEILING DUAL type (60Hz)

FLOOR CONSOLE / UNDER CEILING DUAL type (60Hz) SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL type (60Hz) Models Indoor unit MSYF Outdoor unit MRUYF CONTENTS SPECIFICATIONS... OUTLINE AND DIMENSIONS... REFRIGERANT SYSTEM DIAGRAM...

More information

FLOOR CONSOLE / UNDER CEILING DUAL type

FLOOR CONSOLE / UNDER CEILING DUAL type SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL type Models Indoor unit ABU8RULX ABURULX Outdoor unit AOU8RLX AOURLX CONTENTS SPECIFICATIONS... OUTLINE AND DIMENSIONS... REFRIGERANT

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

4. Disassembly and Reassembly

4. Disassembly and Reassembly 4. Disassembly and Reassembly Stop operation of the air conditioner and remove the power cord before repairing the unit. 4-1 Indoor Unit 4-1-1 MH FPEA /MH VP2-1 Front Panel 1) Stop the air conditioner

More information

DUCT type. Большая библиотека технической документации каталоги, инструкции, сервисные мануалы, схемы.

DUCT type. Большая библиотека технической документации   каталоги, инструкции, сервисные мануалы, схемы. SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type Models Indoor unit Outdoor unit RD-25CA RD-25HA RD-30CA RD-30HA RO-25CA RO-25HA RO-30CA RO-30HA C O N T E N T S SPECIFICATIONS.............................................

More information

SERVICE Manual AIR CONDITIONER AW0719 AW Precautions. 2. Product Specifications. 3. Operating Instructions and Installation

SERVICE Manual AIR CONDITIONER AW0719 AW Precautions. 2. Product Specifications. 3. Operating Instructions and Installation ROOM AIR CONDITIONER AW079 AW089 SERVICE Manual AIR CONDITIONER CONTENTS. Precautions 2. Product Specifications 3. Operating Instructions and Installation 4. Disassembly and Reassembly 5. Troubleshooting

More information

CASSETTE type INVERTER MULTI AIR CONDITIONER

CASSETTE type INVERTER MULTI AIR CONDITIONER INVERTER MULTI AIR CONDITIONER CASSETTE type Models Indoor unit AUY12LBAB AUY14LBAB Outdoor unit AOY18LMAK2 CONTENTS SPECIFICATIONS..................... 1 OUTLINE AND DIMENSIONS........... 2 REFRIGERANT

More information

SERVICE Manual CEILING TYPE AIR CONDITIONER INDOOR UNIT FH052EZA FH070EZA OUTDOOR UNIT FH052EZX FH070EZX. 1. Product Specifications

SERVICE Manual CEILING TYPE AIR CONDITIONER INDOOR UNIT FH052EZA FH070EZA OUTDOOR UNIT FH052EZX FH070EZX. 1. Product Specifications CEILING TYPE AIR CONDITIONER INDOOR UNIT FH052EZA FH070EZA OUTDOOR UNIT FH052EZX FH070EZX SERVICE Manual AIR CONDITIONER CONTENTS 1. Product Specifications 2. Trouble Shooting 3. Block Diagrams 4. Disassembly

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A TECHNICAL & SERVICE MANUAL SA 183A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. SA-183A 1 851 006 96 Destination Australia SA 183A REFERENCE NO. SM700514 IMPORTANT! Please Read Before

More information

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit SPLIT TYPE AIR CONDITIONER CASSETTE type (50Hz) Models Indoor unit Outdoor unit RCW-12HA RO-12HB C O N T E N T S SPECIFICATIONS........................................ 1 OUTLINE AND DIMENSIONS..............................

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG18KLCA ASYG24KLCA OUTDOOR AOYG18KLTA AOYG24KLTA DR_AS069EF_01 2018.03.16 Notices: Product specifications and design are subject to

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: ASR609CL ASR612CL ASR609CL ASR612CL

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: ASR609CL ASR612CL ASR609CL ASR612CL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: ASR609CL ASR612CL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. ASR609CL 387006970 ASR612CL 387006971 0.8180.250.0 05/2002 IMPORTANT! Please read

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CLM97 CLM7 CLM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No.

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA OUTDOOR AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA DR_AS049EF_02 2017.10.11 Notices: Product

More information

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. Please void OBH733 REVISED EDITION-A. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH733 REVISED EDITION-B Models MUZ-GL09NA

More information

AIR CONDITIONER. Model : 1. Precautions. 2. Product Specifications. 3. Disassembly and Reassembly. 4. Troubleshooting. 5.

AIR CONDITIONER. Model : 1. Precautions. 2. Product Specifications. 3. Disassembly and Reassembly. 4. Troubleshooting. 5. SYSTEM AIR CONDITIONER Model : INDOOR UNIT AC012MNADCH/AA AC018MNADCH/AA AC024MNADCH/AA AC030MNTDCH/AA AC036MNTDCH/AA OUTDOOR UNIT AC012KXADCH/AA AC018JXADCH/AA AC024JXADCH/AA AC030JXADCH/AA AC036JXADCH/AA

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513 TECHNICAL & SERVICE MANUAL SA 123A FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-123A 1 851 006 95 Australia SA 123A REFERENCE NO. SM700513 IMPORTANT! Please Read Before

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 19,100 BTU/h,200 BTU/h 30,600 BTU/h Outdoor Model No. CU-3KE19NBU CU-4KE24NBU

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH Revision D: Capacity corrections have been corrected [7-1. 2), 3)]. OBH684 REVISED EDITION-C is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH684 REVISED EDITION-D Models MUZ-FH06NA MUZ-FH09NA

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338 TECHNICAL & SERVICE MANUAL SA 128S5 FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-128S5-A 1 851 004 09 General (50Hz) & Europe SA 128S5 REFERENCE NO. SM700338 IMPORTANT!

More information

TAC-09CS/K TAC-12CS/K TAC-18CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-12CHS/K TAC-18CHS/K TAC-24CHS/K

TAC-09CS/K TAC-12CS/K TAC-18CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-12CHS/K TAC-18CHS/K TAC-24CHS/K TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE040427 Models TAC-07CS/K TAC-09CS/K TAC-2CS/K TAC-8CS/K TAC-24CS/K TAC-07CHS/K TAC-09CHS/K TAC-2CHS/K TAC-8CHS/K TAC-24CHS/K CONTENTS. IMPORTANT

More information

INSTALLATION MANUAL Duct Type Series MH FECA

INSTALLATION MANUAL Duct Type Series MH FECA INSTALLATION MANUAL Duct Type Series MH FECA ENGLISH FRANÇAIS ESPAÑOL Free Joint Multi Air Conditioner (Cooling and Heating) E S F DB98-960A() Safety Precautions The following safety precautions must be

More information

SERVICE Manual AIR CONDITIONER INDOOR UNIT SH09AWH SH09ZWH AQ09WHWE KFR-25G/SWA SH12AWH SH12ZWH AQ12WHWE KFR-35G/SWA

SERVICE Manual AIR CONDITIONER INDOOR UNIT SH09AWH SH09ZWH AQ09WHWE KFR-25G/SWA SH12AWH SH12ZWH AQ12WHWE KFR-35G/SWA ROOM AIR CONDITIONER INDOOR UNIT SH09AWH SH09ZWH AQ09WHWE KFR5G/SWA SHAWH SHZWH AQWHWE KFR5G/SWA OUTDOOR UNIT SH09AWHX SH09ZWHX UQ09WHWE KFR5W/SWA SHAWHX SHZWHX UQWHWE KFR5W/SWA SERVICE Manual AIR CONDITIONER

More information

CASSETTE type SPLIT TYPE AIR CONDITIONER. (60Hz) AUU18RCLX AUU24RCLX AUU36RCLX AUU42RCLX AOU18RLX AOU24RLX AOU36RLX AOU42RLX CONTENTS.

CASSETTE type SPLIT TYPE AIR CONDITIONER. (60Hz) AUU18RCLX AUU24RCLX AUU36RCLX AUU42RCLX AOU18RLX AOU24RLX AOU36RLX AOU42RLX CONTENTS. SPLIT TYPE AIR CONDITIONER CASSETTE type (60Hz) Models Indoor unit AUU8RCLX AUURCLX AUU6RCLX AUURCLX Outdoor unit AOU8RLX AOURLX AOU6RLX AOURLX CONTENTS SPECIFICATIONS... DIMENSIONS... REFRIGERANT SYSTEM

More information

Part 3 Troubleshooting

Part 3 Troubleshooting Part Troubleshooting What is in this part? This part contains the following chapters: Chapter See page Troubleshooting 2 Error Codes: Hydro-box 7 Error Codes: Outdoor Units Error Codes: System Malfunctions

More information

Room Air Conditioner Service and Parts Manual

Room Air Conditioner Service and Parts Manual Cool Dry Temp Mode Room Air Conditioner Service and Parts Manual F Fan Speed hr Timer 0n 0ff Money Saver Fan Only Auto Swing Power CP06 CP08 93011401_01 CONTENTS 1. PREFACE 1.1 SAFETY PRECAUTIONS...2 1.2

More information

Room Air Conditioner CP06 & CP08. Chill 115 Volts. Service & Parts Manual THE EXPERTS IN ROOM AIR CONDITIONING _02

Room Air Conditioner CP06 & CP08. Chill 115 Volts. Service & Parts Manual THE EXPERTS IN ROOM AIR CONDITIONING _02 Room Air Conditioner Service & Parts Manual 2014-2015 CP06 & CP08 Chill 115 Volts THE EXPERTS IN ROOM AIR CONDITIONING 93011401_02 CONTENTS 1. PREFACE 1.1 SAFETY PRECAUTIONS...2 1.2 INSULATION RESISTANCE

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL For Extra Cold Climate Area INDOOR ASU18RLF ASU24RLF OUTDOOR AOU18RLXFWH AOU24RLXFWH DR_AS014EF_04 2017.03.10 Notices: Product specifications

More information

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 Indoor unit service manual MSZ-DM VA Series (OBH750) CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES

More information

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO.

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO. wiring diagrams AIR-COOLED CONDENSING UNIT 566D Sizes 120-240 Cancels: New WD 566D.120.1 11/15/96 UNITS PRODUCED AFTER JANUARY, 1996 INDEX UNIT 566D 120-240 ELECTRICAL CHARACTERISTICS (V-Ph-Hz) SCHEMATIC

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL KS1872 + C1872 + CL1872 KS2472 + C2472 + CL2472 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KS1872 KS2472 Product

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE OUTDOOR AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE DR_AS037EF_01 2016.12.05 Notices: Product

More information

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC Revision A: MUZ-HM09/12NA- U8, MUZ-HM09/12NA2- U8, MUZ-HM15/18NA- U1, MUZ-HM15/18NA2- U1 and MUZ-HM24NA2- U1 have been added. Please void OBH747. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A.

More information

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE FILE. SVM-04004-3 SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-13UKHP-E3 / RAS-13UAH-E3 RAS-10UKHP-E3 / RAS-10UAH-E3 RAS-07UKHP-E3 / RAS-07UAH-E3 RAS-13UKP-E3 / RAS-13UA-E3 RAS-10UKP-E3 / RAS-10UA-E3

More information

YC ON-OFF SERIES. Service Manual

YC ON-OFF SERIES. Service Manual YC ON-OFF SERIES Service Manual CONTENTS 1. Precaution... 3 1.1 Safety Precaution... 3 1.2 Warning... 3 2. Model Lists... 6 3. Dimension... 7 3.1 Indoor Unit... 7 3.2 Outdoor Unit... 11 4. Refrigerant

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF94R5 CAF124R5 SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. CAF94R5 387106979 CAF124R5 387106980 0.8180.361.0 07/2005 IMPORTANT! Please read before

More information

SERVICE MANUAL 42QHF009DS* 42QHF012DS* 42QHF018DS* 42QHF022DS* 38QUS009DS* 38QUS012DS* 38QUS018DS* 38QUS022DS* Indoor unit.

SERVICE MANUAL 42QHF009DS* 42QHF012DS* 42QHF018DS* 42QHF022DS* 38QUS009DS* 38QUS012DS* 38QUS018DS* 38QUS022DS* Indoor unit. SERVICE MANUAL Indoor unit Outdoor unit 42QHF009DS* 42QHF012DS* 42QHF018DS* 42QHF022DS* 38QUS009DS* 38QUS012DS* 38QUS018DS* 38QUS022DS* INDEX PART1 GENERAL INFORMATION PART2 ELECTRICAL DIAGRAM PART3 TROUBLE

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF97R5IAA CAF98MR5IAA CAF127R5IAA CAF128MR5IAA CAF187R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. CAF97R5IAA CAF127R5IAA CAF187R5IAA CAF98MR5IAA CAF128MR5IAA

More information

DUCT type. SPLIT TYPE AIR CONDITIONER (50Hz)

DUCT type. SPLIT TYPE AIR CONDITIONER (50Hz) SPLIT TYPE AIR CONDITIONER (50Hz) DUCT type Models Indoor unit Outdoor unit ARY0ELA AOY0EPBL CONTENTS SPECIFICATIONS.............................. OUTLINE AND DIMENSIONS...................... CIRCUIT DIAGRAM............................

More information

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467. SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-HC35VA- E2 and MUZ-HC35VAB- E2 have been added. Please void OBH467 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH467 REVISED EDITION-B

More information

CONTENTS 1. Specifications... 2. Features and Technical Explanation... 2-1. Featurs... 2-2. Neuro fuzzy Washing time optimization... 2-3. Water level Contorl... 2-4. Door Contorl... 2-5. The door can cont

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC Revision E: MUZ-FH25VE- E4, ER4, ET3, MUZ- FH35VE- E3, ER3, ET3 and MUZ- FH50VE- E2, ER2, ET2 have been added. Please void OBH624 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624

More information

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE -(1) SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-24UKHP-E3 / RAS-24UAH-E3 RAS-18UKHP-E3 / RAS-18UAH-E3 RAS-24UKP-E3 / RAS-24UA-E3 RAS-18UKP-E3 / RAS-18UA-E3 RAS-24UKP-AR3 / RAS-24UA-AR3 RAS-18UKP-AR3

More information

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2 Revision F: "How to check miswiring and serial signal error" has been corrected (11-5. M ). OBH648 REVISED EDITION-E is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH648 REVISED EDITION-F Models

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC AQB8J6WC_IM_E_25864 2006.4.4 3:29 PM Page 7 INSTALLATION MANUAL Indoor Unit AQB8J6WC AQB24J2WC Outdoor Unit UQB8J6WC UQB24J2WC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

Service Manual & Installation Manual

Service Manual & Installation Manual GE Consumer & Industrial Appliances Service Manual & Installation Manual Split System Air Conditioner Model numbers: GE AIR F24 GE AIR F34 GE AIR F41 1 2 3 Introduction and Features Model Remarks GE AIR

More information

SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE

SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE Indoor unit ABYF8LAT ABYF8LAT ABYF8LAT ABYF8LAT ABYF8LBT ABYF8LBT ABYFLAT ABYFLAT ABYFLAT ABYFLAT ABYFLBT ABYFLBT Outdoor unit AOYA8LACL

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 93AH FILE NO. SA 93AH REFERENCE NO. SM700510

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 93AH FILE NO. SA 93AH REFERENCE NO. SM700510 TECHNICAL & SERVICE MANUAL SA 93AH FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-93AH 1 851 006 97 Australia SA 93AH REFERENCE NO. SM700510 IMPORTANT! Please Read Before

More information

SERVICE MANUAL K LIGHT COMMERCIAL

SERVICE MANUAL K LIGHT COMMERCIAL SERVICE MANUAL 36 48 60K LIGHT COMMERCIAL Cassette indoor unit Under-ceiling indoor unit Ducted indoor unit 42QTD036DS* 42QTD048DS* 42QTD060DS* 42QZL036DS* 42QZL048DS* 42QZL060DS* 42QSM036DS* 42QSM048DS*

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE9NB4U & CZ-18BT1U CS-MKE12NB4U & CZ-18BT1U CS-KE18NB4UW & CZ-18BT1U DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 9,000BTU / h 11,900BTU / h 17,500BTU

More information

TABLE OF CONTENTS REFRIGERATOR-FREEZER. Model No. NR-BN34FX1 Model No. NR-BN34FW1

TABLE OF CONTENTS REFRIGERATOR-FREEZER. Model No. NR-BN34FX1 Model No. NR-BN34FW1 Order Number GORR1405001CE REFRIGERATOR-FREEZER Model No. NR-BN34FX1 Model No. NR-BN34FW1 Product-Color X:Stainless W:White Destination E(Europe Continental) B(U.K.) TABLE OF CONTENTS PAGE 1 Safety Precautions-----------------------------------------------

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL AW22AL AW28AL AW38AL

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL AW22AL AW28AL AW38AL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW22AL 387030005 AW28AL 387030006 AW38AL 387030007 AW42AL 387030094 0.8180.467.0

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AE22AH 387031006 AE28AH 387031007 AE38AH 387031008

More information

SPLIT-TYPE AIR CONDITIONER

SPLIT-TYPE AIR CONDITIONER SPLIT-TYPE AIR CONDITIONER INDOOR UNIT Basic : AQB09JJWC AQB12JJWC Model : AQV09JA AQV12JA Model Code : AQV09JA AQV12JA OUTDOOR UNIT AQV09JAX AQV12JAX AIR CONDITIONER THE FEATURE OF PRODUCT High Energy

More information

SERVICE MANUAL OFFICE PRO 36 SERIAL NUMBER FROM APRIL 2007 (0407) TO PRESENT. DocID: 00G00010EA

SERVICE MANUAL OFFICE PRO 36 SERIAL NUMBER FROM APRIL 2007 (0407) TO PRESENT. DocID: 00G00010EA SERVICE MANUAL OFFICE PRO 36 SERIAL NUMBER FROM APRIL 2007 (0407) TO PRESENT DocID: 00G00010EA 2008 DENSO SALES CALIFORNIA, INC. All rights reserved. This book may not be reproduced or copied, in whole

More information

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table)

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table) 1 2 Warning: - Do not place your hand or any other objects into the air outlet and fan. It could damage the heat pump and cause injuries; - In case of any abnormality with the heat pump, cut off the power

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

Fast Track Troubleshooting

Fast Track Troubleshooting Fast Track Troubleshooting Models Covered: RF266AD**/XAA French Door Refrigeration IMPORTANT SAFETY NOTICE For Technicians Only This service data sheet is intended for use by persons having electrical,

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL RESET SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. OC0 TECHNICAL & SERVICE MANUAL Series SLZ Ceiling Cassettes R0A Indoor unit [Model names] SLZ-A09AR SLZ-AAR SLZ-A8AR [Service Ref.] SLZ-A09AR.TH SLZ-AAR.TH

More information

Model name: AJ009JNNDCH AJ012JNNDCH AJ018JNNDCH AJ007JNADCH AJ009JNADCH AJ012JNADCH

Model name: AJ009JNNDCH AJ012JNNDCH AJ018JNNDCH AJ007JNADCH AJ009JNADCH AJ012JNADCH Model name: AJ009JNNDCH AJ012JNNDCH AJ018JNNDCH AJ007JNADCH AJ009JNADCH AJ012JNADCH MULTI AIR CONDITIONER INDOOR UNIT AJ018JNADCH AJ024JNADCH AJ009JNLDCH AJ012JNLDCH AJ018JNLDCH OUTDOOR UNIT AJ020JCJ2CH

More information

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E SPLIT-TYPE AIR CONDITIONERS Revision E: MFZ-KA5VA- E5, MFZ-KA35VA- E5 and MFZ-KA50VA- E5 have been added. Please void OB409 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OB409 REVISED EDITION-E Models

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: GRF188R5TAA GRF228R5TAA GRF228R7TAA SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. GRF188R5TAA 38.7107.083 GRF228R5TAA 38.7107.084 GRF228R7TAA 38.7107.085

More information

CASSETTE TYP FANCOIL UNIT SERVICE MANUAL

CASSETTE TYP FANCOIL UNIT SERVICE MANUAL CASSETTE TYP FANCOIL UNIT SERVICE MANUAL (GC201109-I) Contents PRODUCT...2 1. MODELS LIST...2 2. NOMENCLATURE OF THE UNIT...3 3. FUNCTION...3 4. PRODUCT DATA...4 CONTROL...10 1. WIRELESS REMOTE CONTROLLER...10

More information

Кондиционеры Mitsubishi Heavy

Кондиционеры Mitsubishi Heavy Кондиционеры Mitsubishi Heavy Техническое руководство Кондиционеры настенного типа SRK28HD, SRK40HD INDOOR UNIT Models SRK28HD, SRK40HD OUTDOOR UNIT Model SRC28HD REMOTE CONTROLLER Model SRC40HD GENERAL

More information

SERVICE MANUAL KFR-7002GW

SERVICE MANUAL KFR-7002GW SPLIT TYPE AIR CONDITIONER SERVICE MANUAL KFR-7002GW CONTENTS 1.PART NAMES AND FUNCTIONS... 2.SPECIFICATION... 3.OUTLINES AND DIMENSIONS... 4.WIRING DIAGRAM... 5.REFRIGERANT SYSTEM DIAGRAM... 6.PERFORMANCE

More information

INSTALLATION MANUAL RHF025EE Series RHF035EE Series RHF050EE Series RHF080EE Series RHF100EE Series

INSTALLATION MANUAL RHF025EE Series RHF035EE Series RHF050EE Series RHF080EE Series RHF100EE Series INSTALLATION MANUAL RHF025EE Series RHF035EE Series RHF050EE Series RHF080EE Series RHF100EE Series PORTUGUÊS ENGLISH ITALIANO ESPAÑOL FRANÇAIS ERV (Energy Recovery Ventilator) DEUTSCH E S F I P D DB98-27512A(3)

More information

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD.

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD. Technical Support Division 2017-4-25 New CMV System - Floor ceiling Indoor Unit 1 1. External appearance 2. Nomenclature 3. Specifications 4. Dimensions 5. Service space 6. Piping diagram 7. Wiring diagram

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT: AE726SCL AE752SCL AE71SCL3 AE735SCL AE752SCL3 AE100SCL3 AE764SCL3 AE125SCL3 SPLIT SYSTEM AIR CONDITIONER Model No. AE726SCL AE735SCL AE752SCL AE752SCL3 AE764SCL3

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K303A + SAP C303A FILE NO. REFERENCE NO. SM Destination: Australia

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K303A + SAP C303A FILE NO. REFERENCE NO. SM Destination: Australia AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP K303A + SAP C303A FILE NO. Destination: Australia SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No. SAP K303A A 1 852 098 83 Outdoor Model No.

More information

SERVICE MANUAL AIR CONDITIONER SPLIT TYPE

SERVICE MANUAL AIR CONDITIONER SPLIT TYPE FILE No. A90-961 SERVICE MANUAL AIR CONDITIONER SPLIT TYPE WAY CASSETTE TYPE RAV-133TU-PE/RAV-13A-PE RAV-163TU-PE/RAV-18A-PE Printed in UK Dec 1996 s CONTENTS 1. SPECIFICATION...3. CONSTRUCTION VIEWS...5

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629.

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-A Models MUZ-SF25VE - E1 MUZ-SF42VE

More information

RAS-10JKVP-E RAS-10JAVP-E RAS-13JKVP-E RAS-13JAVP-E

RAS-10JKVP-E RAS-10JAVP-E RAS-13JKVP-E RAS-13JAVP-E FILE NO. A0-05 SPLIT TYPE RAS-0JKVP-E RAS-0JAVP-E RAS-3JKVP-E RAS-3JAVP-E PRINTED IN JAPAN, Jun.,003 ToMo . EXPLODED VIEWS AND PARTS LIST -. Indoor Unit () 0 0 6 35 5 4 0 5 33 7 08 6 07 9 3 0 3 8 30 39

More information

REFRIGERATOR SIDE BY SIDE TYPE CONTENTS REFRIGERATOR MODEL NAME : RH22H9010SR RH29H9000SR MODEL CODE : RH22H9010SR/AA RH29H9000SR/AA

REFRIGERATOR SIDE BY SIDE TYPE CONTENTS REFRIGERATOR MODEL NAME : RH22H9010SR RH29H9000SR MODEL CODE : RH22H9010SR/AA RH29H9000SR/AA REFRIGERATOR SIDE BY SIDE TYPE MODEL NAME : RH22H9010SR RH29H9000SR MODEL CODE : RH22H9010SR/AA RH29H9000SR/AA REFRIGERATOR CONTENTS 1. PRECAUTIONS(SAFETY WARNINGS) 5 2. PRODUCT SPECIFICATIONS 8 3. DISASSEMBLY

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A09LEC AS A12LEC OUTDOOR AO R09LECN AO R12LECN 1.INDOOR UNIT : AS A09LEC AS A12LEC DTR_AS047E_01 2010.10.05 1. INDOOR UNIT CONTENTS

More information

Service Manual. Room Air Conditioner Split Wall-Mounted Type. Applies to: HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1

Service Manual. Room Air Conditioner Split Wall-Mounted Type. Applies to: HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1 Service Manual Room Air Conditioner Split Wall-Mounted Type Applies to: HSG-09CRN1 HSG-12CRN1 HSG-18CRN1 HSG-24CRN1 HSG-09HRN1 HSG-12HRN1 HSG-18HRN1 HSG-24HRN1 NOTE: Please read this first before servicing

More information

SERVICE MANUAL CLASSIC PLUS 14 SERIAL NUMBER FROM JANUARY 2008 (0108) TO PRESENT. DocID: 00G00019E

SERVICE MANUAL CLASSIC PLUS 14 SERIAL NUMBER FROM JANUARY 2008 (0108) TO PRESENT. DocID: 00G00019E SERVICE MANUAL CLASSIC PLUS 14 SERIAL NUMBER FROM JANUARY 2008 (0108) TO PRESENT DocID: 00G00019E 2008 DENSO SALES CALIFORNIA, INC. All rights reserved. This book may not be reproduced or copied, in whole

More information

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E Revision E: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH629 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-E Models

More information

ASU18RLF ASU24RLF AOU18RLXFWH AOU24RLXFWH CONTENTS WALL MOUNTED TYPE ROOM AIR CONDITIONER FOR EXTRA LOW TEMP. DISTRICT

ASU18RLF ASU24RLF AOU18RLXFWH AOU24RLXFWH CONTENTS WALL MOUNTED TYPE ROOM AIR CONDITIONER FOR EXTRA LOW TEMP. DISTRICT WALL MOUNTED TYPE ROOM AIR CONDITIONER FOR EXTRA LOW TEMP. DISTRICT Indoor unit ASU8RLF ASURLF Outdoor unit AOU8RLXFWH AOURLXFWH CONTENTS SPECIFICATIONS.................... DIMENSIONS........................

More information

Multi Type Room Air Conditioner

Multi Type Room Air Conditioner Multi Type Room Air Conditioner SERVICE MANUAL INDOOR UNIT: AMNN076L/M/NQA0 AMNN096L/M/NQA0 AMNN6L/M/NRA0 AMNN86L/M/NTA0 AMNN46L/M/NTA0 AMNN096APA0 AMNN6APA0 AMNN6TEA0 AMNN86TEA0 AMNN86VBA0 OUTDOOR UNIT:

More information

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit

CASSETTE type (50Hz) SPLIT TYPE AIR CONDITIONER. Models Indoor unit Outdoor unit SPLIT TYPE AIR CONDITIONER CASSETTE type (50Hz) Models Indoor unit Outdoor unit RCW-8CA RCW-8HA RO-8CB RO-8HB C O N T E N T S SPECIFICATIONS........................................ OUTLINE AND DIMENSIONS..............................

More information

AIR CONDITIONER 4 WAY CASSETTE SERIES. 1. Precautions. 2. Product Specifications. 3. Disassembly and Reassembly. 4. Troubleshooting. 5.

AIR CONDITIONER 4 WAY CASSETTE SERIES. 1. Precautions. 2. Product Specifications. 3. Disassembly and Reassembly. 4. Troubleshooting. 5. SYSTEM AIR CONDITIONER 4 WAY CASSETTE SERIES Model : INDOOR UNIT AC018JN4DCH/AA AC024JN4DCH/AA AC030JN4DCH/AA AC036JN4DCH/AA AC042JN4DCH/AA AC048JN4DCH/AA OUTDOOR UNIT AC018JXADCH/AA AC024JXADCH/AA AC030JXADCH/AA

More information

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC Revision F: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH590 REVISED EDITION-E. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED EDITION-F

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL OUTDOOR UNIT:. TRIAL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. 38.7107.102. 0.8180.611.02 09/2012 IMPORTANT! Please read before installation This air conditioning

More information