BAS Point Trend Data Guidance

Size: px
Start display at page:

Download "BAS Point Trend Data Guidance"

Transcription

1 BAS Point Trend Data Guidance Rev. 3, January 2018

2 Introduction The Building Automation System (BAS also, referred to as a DDC system, or a Direct Digital Control system) at your building has been set-up for Historical Trend Data collection and you are struggling to understand how to access the information that has been collected. You ve been left with the impression that the trending has been set-up as specified for your building, but amongst all the other pressing daily issues at your facility you really have not had the opportunity to fully explore and become familiar with all the BAS training modules. This is one of many common first impressions that the complexity of a BAS can have on a Building Engineer. A good practice to keep in mind when stepping up to the initial challenges of a BAS is to avoid the trap of becoming intimidated by the complexity of the overall system. You should instead focus your efforts towards working through any particular single problem, or exercise, one step at a time and then build upon as many small successes as possible until the bigger picture begins to show through. If you find any of those initial small steps to be not forthcoming, seek out support from a qualified BAS professional who is well acquainted with your particular system and can walk you through the initial hurdles so you can get the results out of the BAS you were looking for (one small step at a time). Another good practice is to build an archive of electronic documents that include screen captures and written descriptions of the various steps observed to be taken by BAS professionals for future reference of any particular BAS task. Trend data from various energy consuming mechanical and electrical systems connected to a BAS can provide building operators and commissioners with valuable feed-back on how efficiently and effectively these systems are operating in a building. Generally, the first use for BAS system historical trend data is to track and confirm specified equipment operations for BAS start-up and commissioning crews. After the building systems have been commissioned and passed onto the building operators, the trend data collection programming used for the start-up and commissioning of the building are commonly left enabled and in-use, but not necessarily setup to fully benefit the building operator s ongoing use. Further opportunities to identify additional building energy performance and comfort improvements, such as set-point and programming adjustments, can be revealed through strategic use and analysis of BAS historical trend data. In order for these opportunities to become apparent, the BAS trend data collection programming may require some adjustments to how system parameters being targeted for improvements are captured and displayed. Any modifications to the trend data collection programming should be approached with good planning, documentation and implementation practices to avoid any unnecessary system downtime or disruptions due to overextension of available system resources. If your operating staff do not have training or experience suitable for modifying your particular BAS, then support from qualified personnel familiar with the installed BAS for the building should be engaged to implement specific changes required for the trend data collection and any subsequent programing revisions designed to bring about the targeted improvements initially considered. The target audiences for this document are building operators relatively new to BAS s or experienced professionals interested in some best-practice tips for analysis and use of BAS Trended Data. This guide will offer assistance in identifying control points that would be good candidates for inclusion in historical trend data collections. A Trending Plan, as outlined in a companion document, is another recommended first step in this process and should be completed as part of a responsible planning process prior to making any changes to existing BAS trend definitions or programming. Where building operators lack adequate experience to plan or adjust BAS Point Trend parameters, it is strongly recommended that qualified individuals are to be engaged in this process as implementers, trainers or whatever combination will result in the best possible engagement of the building operator so that the desired operational results can be achieved. Page 2 of 15

3 Table of Contents Introduction... 2 Trend Data Guidelines and Recommendations... 4 Occupied/ Un-Occupied Zone Scheduling Control... 4 Occupied/ Un-Occupied Scheduling Trend Analysis... 5 Ventilation Unit Heating and Cooling Control... 6 Ventilation Unit Heating and Cooling Trend Analysis... 7 Ventilation Unit Mixed Air and Economizer Control... 8 Ventilation Unit Mixed Air and Economizer Trend Analysis... 8 Supply Air Temperature Control Supply Air Temperature Trend Analysis Supply Air Static Pressure Control Supply Air Static Pressure Trend Analysis Zone Terminal Unit Control Zone Terminal Unit Trend Analysis Page 3 of 15

4 Trend Data Guidelines and Recommendations The following are a collection of common building energy saving opportunities where strategic use of historical or archived trending results from a Building Automation System (or BAS system) can be useful in providing clues to uncover building performance energy robbing issues: Occupied/ Un-Occupied Zone Scheduling Control: a. Potential issues to look for: Are both night heating and cooling set-back schedules in place and enabled for all building zones during unoccupied time periods through the week and on weekends? Can equipment cycling during unoccupied time periods be reduced to save energy? Are unoccupied temperature, humidity and static pressure measured values providing the greatest energy saving results while maintaining reasonable control and expectations for the areas served? Can primary HVAC equipment (fans, etc.) stop or have air flow reduced while still maintaining reasonable control during unoccupied, and possibly occupied, time periods. Can secondary HVAC equipment (pumps, boilers, chillers, etc.) be stopped, cycled or can the flow through them be reduced during unoccupied, and possibly occupied, time periods while maintaining nominal building HVAC requirements? Do all digital VAV and other terminal equipment controllers have unoccupied modes enabled and are all set-back air flow and heat/cool set-points in use? Pneumatic controlled devices: i. for day-night thermostats, is the control supply air pressure resetting to initiate the night set-back and day occupied room temperature control setpoints? ii. are the pneumatic control devices, controllers, thermostats being calibrated regularly (annually or bi-annually) for the best possible operating efficiency? iii. are all the control valves and damper actuators fully closing when they are commanded to close? b. Recommended control points to be trended over time: Occupancy mode point or fan systems to reasonably demonstrate occupancy; Secondary equipment on/off control points, set-point or resulting fluid temperature, as indicative of equipment use, as available; For a reasonable sample of zones (the larger the sample size the better): i) room temperature, humidity and static pressure, as available; ii) VAV air flow, reheat control valve position, rad or convector control valve position, electric baseboard on/off control, as available Page 4 of 15

5 Occupied/ Un-Occupied Scheduling Trend Analysis: a. Confirm that room/zone temperatures are allowed to drop to unoccupied heating setpoints or rise to unoccupied cooling set-points before any equipment is used in the unoccupied mode to either heat or cool the space (i.e. equipment used = open a heating/ cooling control valve, open a VAV box, start a fan, etc.). Reasonable set-back temperature ranges typically fall within a 3 to 6 C range of the occupied room/ zone temperature set-point 1 : i) reasonable winter months unoccupied set-back zone temperatures settings range between 19 C to 16 C and ii) reasonable summer months unoccupied set-back zone temperatures settings range between: 25 C to 28 C. b. Confirm that all humidification, cooling and gas-fired or electric heating systems in forced air ventilation systems are turned off when the fan systems are stopped (this should be obvious, but there is good value in confirming all these systems are actually not operating when the fans are stopped). c. For hydronic heating systems where the fans are stopped when the outdoor air temperature is less than 0 C, confirm that the fan s mixed air plenum temperature is no warmer than is reasonable to keep all components in the mixed air plenum from being damaged due to cold conditions (5 C is generally recommended). For glycol filled systems, and only if you have high confidence that adequate glycol concentration exists in the systems to protect the equipment from freezing, the glycol heating control valve can be fully closed or by-passed from the heat source. d. Confirm that duct and room static pressure sensors for all fan systems indicate nominally 0 Pa when the fans are off. Fan, duct or space static pressure measuring more than 0 Pa when the fan systems are commanded off should be investigated and either corrected to indicate an accurate value and/or confirmed that the fan is actually off. In the event that any duct static pressure sensors are indicating values more than +/- 20% from 0 Pa when the fan systems are confirmed to be off and there are no naturally occurring static pressure generating sources or other fan systems influencing the sensors, then the sensor should be recalibrated. If the pressure cannot be recalibrated with a reasonable level of confidence, then it should be replaced. 1..research from the Canadian Centre for Housing Technology shows that winter setbacks for houses tested would result in heating cost savings of five to fifteen percent. The highest savings came with a setback of 6 C (11 F) [ this roughly translates into 2.5% saving per degree Celsius & 0.7% per degree Fahrenheit ] Source: Canadian Mortgage and Housing Corporation Page 5 of 15

6 Ventilation Unit Heating and Cooling Control: a. Potential opportunities to look for: Is the amount of outdoor air that is being conditioned (i.e. heated, cooled and humidified) to provide good air quality in the building reasonable for the building population or could it be reduced while maintaining acceptable CO 2 levels 2 in the building? Are heating and cooling systems over-lapping each other, i.e. is simultaneous heating and cooling occurring (Do the heating and cooling systems have individually controlled thermostats - What are their settings - Do they overlap)? Can the supply air temperature be reset up or down to reduce mechanical cooling or heating load? Can the supply air temperature become so cold with mechanical cooling use that the zone reheats are needed to temper the supply air to maintain comfortable zone temperatures? Is the mixed air system being controlled to coincide with the supply air temperature control set-point to minimize mechanical heating and cooling loads? Is the mixed air system(s) reverting from free cooling to minimum damper position(s) when the comparison between the outdoor air and the return temperatures (or enthalpies) indicate that the outdoor air can no longer effectively mix with the return air to provide suitable cooling for the space being conditioned? b. Recommended control points to be trended over time with similar trend definitions when assessing a ventilation unit s heating and cooling control: Mixed air temperature; Mixed air temperature set-point; Outdoor air temperature; Outdoor air humidity (as available); Outdoor air CO 2 (as available); Outdoor air enthalpy (for enthalpy based economizer control); Return or Building air enthalpy (for enthalpy based economizer control); Outdoor air flow (as available); Differential pressure across the outdoor air damper as an indication of the amount of fresh air being drawn into the mixed air stream, as available; Reheat control valve positions; Heating & Cooling Lock-Out values and representative heating and cooling system operational values; Demand Control Ventilation (DCV) CO 2 control reference - where more than one CO 2 sensors are used to calculate the space reference value (the maximum measured CO 2 sensor value is the preferred value to be used for the space reference), all values should be trended; All control devices affecting the mixed air temperature control and supply air temperature control (i.e. mixed air dampers, minimum position outdoor air damper, fresh air injection fan, preheat control valve, heating control valve, cooling control valve, dehumidification control cycles, etc.); 2 1,000 PPM can be interpreted as a guideline for a limiting control set-point of space air quality control towards a surrogate level of odor causing components generated from human activity that may not be acceptable for human comfort of air quality: Summary of ASHRAE s position on Carbon Dioxide (CO 2 ) Levels in Spaces, by Stephen Petty, P.E., C.I.H. Page 6 of 15

7 Ventilation Unit Heating and Cooling Trend Analysis: a. ASHRAE Standard 62.1 defines the minimum amount of fresh required to be introduced into a building for air quality management based on building occupant population. This code defines a DCV requirement and CO 2 sensor use as a means of managing this process through matching reasonable amounts of fresh air delivery to the quantity of people and activities of this population through the various zones in a building. With changes in building population and different modes of operation that a building can go through in a day, the amount of outdoor air introduced to the HVAC system requiring conditioning (i.e. heating, cooling, filtration, humidification, etc.) tends to be a significant factor in the operating costs of a building. The use of trended values for all parameters related to outdoor air volume measurement and CO 2, where DCV control strategies are in place, are important and should be compared to ASHRAE 62 requirements to confirm the volume of outdoor air being introduced to the HVAC system in real-time is not considerably more than is required to maintain reasonably good overall air quality in the building. Annual calibration of temperature and CO2 sensors should also be completed for optimal energy performance and control, in consideration of the important role played by these devices in building HVAC systems. b. Assessing trended results for heating and cooling control devices during periods of cooling mode use will provide an opportunity to identify any inadvertent simultaneous use of both these systems. Where reheat coils are part of down-stream HVAC systems that are used to temper the supply air distribution systems during the cooling season, a better choice for tempering the cooling supply air stream might be to simply allow the temperature of the mixed air and resulting supply air to increase a little instead - by reducing the use of mechanical cooling. An energy-conservation guideline to consider for this type of system is to use a supply air temperature reset strategy that will adjust up the supply air temperature adequately so that minimal reheat is applied to mitigate the cost of simultaneous heating and cooling. Minimal use of boiler hot water should also be considered when building heating hot water is required during the cooling season. Most facility operators generally turn-off the hot water boiler systems when in the cooling mode, or generally in the summer, to prevent this scenario from occurring. c. Over-lapping heating and cooling lock-outs can occur through simple confusion or byway of inadvertent post commissioning control programming adjustments. This occurrence is best flushed-out through review of trended results for the lock-out values and compares them to specified or known expectations to confirm that the heating and cooling systems have a well-defined intermediate range where neither is in use. d. Cooling through the use of the economizer is considerably more cost effective than by using mechanical cooling equipment. The use of the economizer is typically limited by the temperature and humidity of the ambient outdoor air. Based on the specific control strategy that has been selected for the building, the more outdoor air that is introduced through the mixed air dampers before the mechanical cooling systems are enabled, the more utility energy savings can generally be realized. In drier climates, ambient dry-bulb temperatures are generally adequate for this purpose, while in climates having higher levels of humidity enthalpy content in the air is generally used. Trended values for the mixed air damper, mechanical cooling systems, outdoor air temperature and humidity to confirm economizer mode transition and mechanical system use will generally identify how efficiently these systems are interacting with each other. Page 7 of 15

8 Ventilation Unit Mixed Air and Economizer Control: a. Potential opportunities to look for: Are the motorized dampers inoperative - stuck in open or closed positions? Are motorized damper linkages or actuators disconnected or malfunctioning? Are the motorized dampers not fully closing/ faulty edge seals resulting in unwanted conditioned air leakage from the building? Is the mixed air temperature acceptably tracking the mixed air temperature setpoint? Is the mixed air temperature control erratic or unstable, over time? b. Recommended control points to be trended over time with similar trend definitions when assessing mixed air temperature control: Mixed air temperature; Mixed air temperature set-point; Outdoor air temperature; The controlled devices affecting the supply air temperature control (i.e. heating and cooling control valves, gas-fired heating reset, mixed air dampers, etc.). Ventilation Unit Mixed Air and Economizer Trend Analysis: a. Damper maintenance is important for reliable operation of mechanical systems. Annual lubrication and adjustment for full freedom of movement will pay significant dividends in energy dollar savings. Since the mixed air system handles a considerable volume of air and is essentially the first line of conditioning in most ventilation systems, it is a very influential component and warrants an appreciable level of attention. b. The importance of mixed air damper systems can easily be unappreciated and can commonly result in varying degrees of neglect and poor states of repair. Actuators, linkages, jack-shafts, damper blades etc. are all part of the mixed air system and require regular lubrication, adjustment and repair to maintain optimum control and energy efficiency of the overall system. c. Effective damper closure when the ventilation unit is stopped can be a significant factor in building energy management and is important for the protection from damage of hydronic equipment contained within the ventilation unit in extreme cold climates. Adjustment of the damper actuator to preload the outdoor air damper for good closure will result in reasonable management of energy losses through the damper assembly when closed. Damper edge seal maintenance and repair are equally important for the management of energy losses through building damper sections to prevent unnecessary energy losses when the fans systems are not in use. d. When the following guideline conditions are observed to be true, the mixed air damper control is probably operating correctly: the position of the mixed air dampers is beyond the minimum ventilation damper position and tracking in free-cooling range of control; trend data results or multiple screen print-outs indicate that the mixed air temperature and the set-point values are consistently within +/- 4% of each other; trend data results or multiple screen print-outs indicate that the mixed air damper control is not hunting or un-responsive. When mixed air dampers are either limited by a minimum ventilation position in winter conditions or reverted to a minimum position in the summer to minimize mechanical Page 8 of 15

9 cooling load, well managed mixed air temperature control cannot be expected. Since there could be situations where both heating and cooling control devices are not in use, the mixed air temperature control set-point could be the same or somehow related to the supply air temperature control. This should be taken into consideration when assessing trend results of mixed air temperature control for energy saving opportunities during free cooling modes. e. When the position of the mixed air dampers is beyond the minimum ventilation damper position and trend data displays for the mixed air temperature value and the set-point values are not within +/- 4%, this is a probable indication that loop tuning for the controlled devices or the controlled devices are in need of attention. Flat line trend data patterns from the mixed air temperature that is considerably off of the mixed air temperature set-point could suggest control device failure. Page 9 of 15

10 Supply Air Temperature Control: a. Potential opportunities to look for: Is the supply air temperature value acceptably tracking the supply air temperature set-point? Is the supply air temperature value erratic or unstable, over time? Is a supply air temperature reset schedule set up correctly and in use ( i.e. is the supply air temperature set-point fixed and manually adjusted from building occupant complaints)? Is the supply air temperature value tracking too high or too low from the supply air temperature set-point? Has the indicated supply air temperature value failed or is it indicating unrealistic values? b. Recommended control points to be trended over time with similar trend definitions when assessing supply air temperature control: Supply air temperature; Supply air temperature set-point; Mixed air temperature; Mixed air temperature set-point; The controlled devices affecting the supply air temperature control (i.e. heating and cooling control valves, gas-fired heating reset, mixed air dampers, etc.) Supply Air Temperature Trend Analysis: a. If trend data shows that the supply air temperature is consistently being maintained within +/- 4% of the set-point control values, recorded in regular time segments daily over the duration of no less than a week, then this is generally a reasonable indication that the supply air temperature control is operating acceptably, for that particular season. Similar supply air temperature control trend result assessments for each season (winter, summer, spring and fall) can be used to demonstrate that the supply air temperature control is operating acceptably overall. b. If the supply air temperature sensor values are questionable or reporting an unreasonable value, sensor calibration or replacement may be necessary. c. Where trend data for the supply air temperature and the set-point values are not within +/- 4%, this could be an indication that the BAS control loop tuning parameters or the controlled devices are in need of attention. Supply air temperature flat line trend data patterns can suggest potential control device failure while erratic trend data patterns suggest possible loop tuning control issues. d. Where the supply air temperature trended values show noticeable reduction or increase in temperature control coincident with the starting of a chiller or boiler, this could be an indication that the control valve is encountering some close-off issues and might be in need of adjustment or replacement. Page 10 of 15

11 e. Where trend data for the supply air temperature and the set-point values are not within +/- 4% and all controlled devices that impact the supply air temperature control are closed or off, investigation of any upstream controlled devices that could be affecting the supply air temperature control should be considered. These upstream controlled devices could include pre-heat control valves or the mixed air damper actuators. Where upstream devices are not the cause of this situation, control sequence programming for the supply air temperature control should be reviewed for any possible contributing issues. f. Where applicable, the addition of, or modification to, a supply air temperature reset control strategy to include programing that will provide the minimum amount of cooling required to satisfy the warmest significant zone, or zones, of a building can be an effective way of saving utility energy costs in a multi-zone building. The actual supply air temperature reset range for both cooling and heating modes can be expected to be relatively unique for each building. Ideally for cooling, the optimum supply air temperature will occur when the VAV box serving the zone having the most extreme cooling demands operates at 100% capacity while resulting in the room cooling demands being met and the room temperature being maintained at set-point. Depending on the specific VAV heating mode control strategy, a similar optimum reset supply air temperature control strategy can be determined using a similar approach to find the lowest tolerable supply air temperature that will keep the building occupants comfortable while not adding unnecessary heating load on auxiliary heating equipment. Where VAV zone systems can be trended, airflow control patterns can be monitored and compared to the supply air temperature and outdoor air temperature trends can be analyzed to work-out at a reset supply air temperature control strategy. g. A control sequence programming upgrade that uses time-steps to adjust the supply air temperature set-point up and down from VAV zone feed-back could also be considered as another option for optimizing the supply air temperature reset control strategy. Trending of the VAV zone operation and space temperatures could be used to fine tune the ratcheting rate for optimum results. Where zone feed-back control strategies are being considered, refer to the Zone Terminal Unit Control for recommended trending and observations in addition to those identified in this section. h. Sequencing of auxiliary heating and cooling equipment within each building zone with the primary cool/heat source can also present opportunities for energy utility cost saving if overlapping heating and cooling operation has been identified and can be corrected. Refer to the Zone Terminal Unit Control for recommended trending and observations in addition to those identified in this section. Page 11 of 15

12 Supply Air Static Pressure Control: a. Potential opportunities to look for: Is the supply air static pressure value acceptably tracking the supply air static pressure set-point? Is the supply air static pressure value erratic or unstable, over time? Is the supply air static pressure value tracking too high or too low from the supply air static pressure set-point? Has the indicated supply air static pressure value failed or is it indicating unrealistic values? Is the speed drive at minimum, or fan inlet vanes nearly closed, while the supply air static pressure value is higher than the supply air static pressure set-point? Is the speed drive at maximum, or fan inlet vanes fully open, while the supply air static pressure value is less than the supply air static pressure set-point? b. Recommended control points to be trended over time with similar trend definitions when assessing supply air static pressure control: Supply air static pressure; Supply air static pressure set-point; Supply air static pressure high limit (if available); Supply air static pressure high limit set-point (if available); The controlled devices affecting the supply air static pressure control (i.e. speed drive (or VFD), fan inlet vanes or dampers, modulating control dampers, by-pass VAV control box, etc.); Down-Stream terminal equipment controlled devices (i.e. VAV damper positions). Supply Air Static Pressure Trend Analysis: a. If trend data shows that the supply air static pressure is being maintained within +/- 7% of the set-point control values, recorded in regular time segments daily over the duration of no less than a week, then this is generally a reasonable indication that the supply air static pressure control is operating acceptably, for that particular season. Similar supply air static pressure control trend assessments for each season (winter, summer, spring and fall) can be used to demonstrate that the supply air static pressure control is operating acceptably overall. b. If the supply air static pressure sensor value is questionable or reporting an unreasonable value, sensor calibration or replacement may be required? c. Where trend data for the supply air static pressure value and the set-point values are not within +/- 7%, this could be an indication that the BAS control tuning parameters or the controlled devices are in need of attention. Supply air static pressure flat line trend data patterns can suggest potential control device failure while erratic trend data patterns suggest loop tuning control issues. d. Where trend data for the supply air static pressure value and the set-point values are not within 10% and the controlled device that impacts the supply air pressure is trending at its minimum value, this may be an indication that the down-stream systems are also operating at minimal values or that the ductwork is blocked by an obstruction (i.e. a closed fire damper). Where the down-stream terminal equipment systems are operating at minimum values, this could be an indication that the supply air temperature being distributed to the building from this AHU system is actually too cold for the needs of the building and that most of the zone terminal units are operating at their minimum air flow capacities to avoid overcooling the various zones spaces throughout the building. This Page 12 of 15

13 can generally be resolved by resetting the supply air temperature up in small increments until the airflow begins to recover to more reasonable values. A time-stepped adjustment program can be implemented that will increase the supply air temperature 0.5 C every 15 minutes (or some other combination of values appropriate for the size of the ventilation system) until the supply air static pressure moves to within a reasonable range. Similarly when the supply air flow is greater than reasonable values, a similar time-stepped programmed control sequence can reduce the supply air temperature until resulting air flow and/ or static pressure move to within a reasonable range. e. If trend data displays supply air static pressure values that are tracking at 10% or less than the set-point while the controlled device is trending at, or near, its maximum value, then this may be an indication that the: i) down-stream terminal equipment systems are demanding more air flow than the ventilation system is capable of delivering. This could be addressed by increasing the cooling capacity of the ventilation system by reducing the supply air temperature 0.5 C every 15 minutes (or some other combination of values appropriate for the size of the ventilation system) until the supply air static pressure rises to within a reasonable range of set-point, through a time-stepped control strategy or, ii) high-limit static control strategy could be in effect and may be over-riding the controlling duct static pressure sensor. In the event that adjustment is being considered to the high-limit set-point, careful analysis of trend data and ventilation system parameters is recommended before making any changes are made to establish whether the system can handle any additional static pressure without resulting in damage. Page 13 of 15

14 Zone Terminal Unit Control: a. Potential opportunities to look for: Is a zone terminal unit located in an interior (or exterior) zone delivering more heated or cooled ventilation air than other similar units in the same zone? Is the space temperature in any terminal unit zones more than 5% higher or lower than the temperature set-point? Are there any building zones that have unique heating or cooling demand requirements that can be significantly influencing the source/ primary AHU heating or cooling systems adversely? Are any zones out of control and oscillating between heating and cooling modes? b. Minimum recommended representative zones to consider for trending in a building: Floors with less than 8 zones per floor = trend all zones per floor; Floors with more than 8 zones per floor = trend a minimum of 8 zones per floor (where practical: select 4 exterior zones representative of each building face direction (i.e. N., E., S. & W.) and 4 interior zones). c. Minimum recommended representative floor counts to consider for trending in a building: Less than 4 floors = trend all floors; 4 floors, or more = trend every other floor; 20 floors, or more = trend every third floor; d. Generally, when analyzing trend data for energy saving opportunities, give special consideration to the following: i. comfort complaint zones; ii. focus on any Interior zones with low heating and cooling demand that may be unnecessarily skewing any feed-back control from primary building requirements (i.e. unoccupied, reduced occupancy, janitor & storage rooms) where no feed-back control is in use to influence the primary building heating and cooling systems these areas can be disregarded from any programming and trending; e. Recommended control points to be trended over time with similar trend definitions when assessing zone control (trend as many as possible from the following): Occupancy and Temporary Occupancy (as available) Room temperature Room temperature set-point; Cooling and/ or Heating Loop or control Device; Air flow and air flow set-point (as available); Fan status and command (as available). Page 14 of 15

15 Zone Terminal Unit Trend Analysis: a. Review results for the heating and cooling control devices in all trended zones for general comparison and identify those zone having noticeably greater heating and/or cooling demand. Investigate and take corrective action for any set-point adjustment or other factors that may cause increased demand for these zones. b. Review results of all building space temperatures in all trended zones and identify any values observed to be in excess of +/- 2.5 C from set-point. Confirm the heating and cooling control demand values are being correctly applied to the control device. Confirm the control device is fully operational and that when commanded to close or be off that it actually does fully close or stop. c. Review temperature results for all electrical service rooms, and other similar conditioned building spaces, in the building and adjust temperature set-points to appropriate values for the intended purpose of the room. Many buildings have storage or electrical rooms that have different purposes than most other rooms and frequently these rooms tend to be handled similar to other rooms unnecessarily and in some cases dictate heating or cooling demands of primary AHU systems. An example of this is an electrical room that has a sizable concentration of heat generating equipment with higher tolerances for warmer temperatures than most other spaces in a building being maintained at nominal comfort levels unnecessarily in this scenario where a control feed-back strategy is in use the supply air temperature reset control set-point could be unnecessarily driven down to its coldest possible value to cool the electrical room. Most electrical rooms can generally operate up to 27 C (80 F) without any adverse effects to the equipment contained in the room while typical building occupant comfort is obtained in a temperature range of 21.5 C to 23.5 C (70.7 F to 74.3 F) 3. d. Review all trended temperature results for erratic swings in values. Room temperatures in controlled conditioned spaces do not typically vary more than 1 C in 15 minute time spans in stable nominal operating conditions. Where erratic temperature swings are observed, temperature sensors, control devices, controllers and possibly external programming are all potential sources that should be considered and investigated. Temperature sensor placement should also be reviewed to confirm that the room temperature control is not being adversely affected by direct sunlight or other potential heat sources (i.e. office photo copiers) that could contribute to false, potentially erratic, temperature indication for the space. 3..research from the Canadian Centre for Housing Technology shows that winter setbacks for houses tested would result in heating cost savings of five to fifteen percent. The highest savings came with a setback of 6 C (11 F) [ this roughly translates into 2.5% saving per degree Celsius & 0.7% per degree Fahrenheit ] Source: Canadian Mortgage and Housing Corporation Page 15 of 15

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS 1 AIR HANDLING UNIT TRENDS 2 1. The trending charts provided on the following pages prepared as part of a retro-commissioning investigation. The

More information

OSU Alumni Center Phase I Implementation Review. Oregon State University 130 Oak Creek Bldg. Corvallis, Oregon

OSU Alumni Center Phase I Implementation Review. Oregon State University 130 Oak Creek Bldg. Corvallis, Oregon OSU Alumni Center Phase I Implementation Review Prepared for Oregon State University 130 Oak Creek Bldg. Corvallis, Oregon 97331 October 31, 2011 Job No. 02.11.00113 Introduction: Glumac was engaged by

More information

IAQ: Re-tuning Commercial Buildings

IAQ: Re-tuning Commercial Buildings IAQ: Re-tuning Commercial Buildings A low-cost path to improved air quality and energy efficiency. B y S c o t t G o r d o n, C M All images courtesy of Johnson Controls Service. 10 RSES Journal FEBRUARY

More information

Improving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks

Improving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks Improving Performance with a Building Tune-Up Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks How much is too much? Most buildings can cut total energy use by 5-30% while

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop Energy-Savings Strategies for Rooftop VAV Systems Occupied set-point temperature Unoccupied set-point temperature Rooftop variable-air-volume (VAV) s are used to provide comfort in a wide range of building

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012 HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

ASHRAE JOURNAL ON REHEAT

ASHRAE JOURNAL ON REHEAT Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide

More information

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE

More information

CHAPTER 4. HVAC DELIVERY SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer

More information

Modeling projects that require very tight space temperature control

Modeling projects that require very tight space temperature control Modeling projects that require very tight space temperature control Whereas space temperature controls for maintaining human thermal comfort typically have a deadband of several degrees between heating

More information

Job Name Control Systems Description Date

Job Name Control Systems Description Date Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

Dehumidifying with Dedicated Outdoor Air

Dehumidifying with Dedicated Outdoor Air Dehumidifying with Dedicated Outdoor Air System Configurations Figure 71. Configurations for dedicated outdoor-air systems A dedicated outdoor-air handler separately filters, cools, dehumidifies, heats,

More information

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate COMcheck Software Version 4.0.8.1 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2013) Standard Buda, Texas 2a New Construction Construction

More information

Analyzing Air Handling Unit Efficiency. Michael Rosenberg, PE, CEM

Analyzing Air Handling Unit Efficiency. Michael Rosenberg, PE, CEM Analyzing Air Handling Unit Efficiency Michael Rosenberg, PE, CEM Analyzing Air Handling Unit Efficiency Introduction...1 Air Handlers and Energy...2 Air Handler Case Study...7 Optimizing Economization

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates Prescriptions for Critical Healthcare Cx John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. Medical Industry Changes and how they impact Design, Construction,

More information

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Continuous Commissioning: A Valuable Partner to Retrofit Projects Continuous Commissioning: A Valuable Partner to Retrofit Projects Yeqiao Zhu Aamer Athar Kenneth Banks Ph.D. PE, CEM PE, CEM Energy Systems Laboratory Sempra Energy Solutions Sempra Energy Solutions Charles

More information

An HVAC Audit of the Canberra Institute of Technology

An HVAC Audit of the Canberra Institute of Technology An HVAC Audit of the Canberra Institute of Technology 30 th November 2016 Amnon Holland amnon.holland@esbsconsult.com.au www.esbsconsult.com.au Agenda Overview CIT and various other sites The sites Type

More information

Civil Engineering Building

Civil Engineering Building Continuous Commissioning Report For the Civil Engineering Building Building 492 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

HVAC Mandatory Provisions Part II, Page 1

HVAC Mandatory Provisions Part II, Page 1 HVAC Mandatory Provisions Part II, Page 1 Mandatory Equipment Efficiency Worksheet (6.4.1.1) System Equipment Type Size Category (Tables 6.8.1A through K) Sub-Category or Rating Condition Units of Efficiency

More information

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS AND APPLICATIONS Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS Earliest air conditioning system used only for heating (winter) Provided heated air for comfort

More information

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas

More information

2009 IECC Commercial Mechanical Requirements

2009 IECC Commercial Mechanical Requirements BUILDING ENERGY CODES UNIVERSITY 2009 IECC Commercial Mechanical Requirements Ken Baker PNNL-SA-66171 Learning(Objec-ves(( ( 1. Find(minimum(equipment(efficiency(requirements( and(recite(at(least(3(common(terms(for(measuring(

More information

Mechanical Compliance Certificate

Mechanical Compliance Certificate COMcheck Software Version 4.0.7.0 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2013) Standard Austin, Texas 2a (weather data: TBD) New

More information

Paul McCown, PE, CEM, LEED AP, CxA Sr. Mechanical Engineer SSRCx, LLC Nashville, TN USA

Paul McCown, PE, CEM, LEED AP, CxA Sr. Mechanical Engineer SSRCx, LLC Nashville, TN USA Continuous Commissioning of a LEED-EB Gold Certified Office Building Paul McCown, PE, CEM, LEED AP, CxA Sr. Mechanical Engineer SSRCx, LLC Nashville, TN USA KEYWORDS Continuous Commissioning, Retro-Commissioning,

More information

control sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals

control sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals control sequences Table 47: QST / EST Analog Electronic Control Strategies Control Package Number QST EST FS-A-5000 FSE-A-5000 FS-A-5001 FSE-A-5001 FS-A-5002 FSE-A-5002 FS-A-5003 FSE-A-5003 FS-A-5004 FSE-A-5004

More information

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

terminal units only provide sensible cooling, a separate dehumidification system is usually needed. providing insights for today s hvac system designer Engineers Newsletter volume 44 3 Dual-Temperature Chiller Plants This Engineers Newsletter describes several dual-temperature configurations that can

More information

DIGI-VAV APPLICATIONS

DIGI-VAV APPLICATIONS DIGI-VAV DIGI-VAV APPLICATIONS Digi-VAV: An optimization kit for Variable Air Volume Air Handling Units (VAV AHU) that ensures individual zone indoor air quality (IAQ), and minimizes system energy consumption.

More information

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-05 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Galveston (TAMU-G) Galveston, Texas Submitted to Texas A&M University

More information

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1: 4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XRT INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

10+ HVAC Troubleshooting Tips for Healthcare Facilities Jerry Hirsch JCI Facility O&M Performance Development Manager.

10+ HVAC Troubleshooting Tips for Healthcare Facilities Jerry Hirsch JCI Facility O&M Performance Development Manager. 10+ HVAC Troubleshooting Tips for Healthcare Facilities Jerry Hirsch JCI Facility O&M Performance Development Manager 2019 WHEA Webinar Johnson Controls Institute Overview Operation & Maintenance (O&M)

More information

Hello, my name is Audra Benzschawel and I m a marketing engineer in the C.D.S. Slide 1 TRACE 700

Hello, my name is Audra Benzschawel and I m a marketing engineer in the C.D.S. Slide 1 TRACE 700 Slide 1 TRACE 700 Unmet Load Hours Hello, my name is Audra Benzschawel and I m a marketing engineer in the C.D.S. group at TRANE. Today I will be talking about unmet hours. What are they, common causes,

More information

Appendix 13. Categories of Cooling and Heating systems

Appendix 13. Categories of Cooling and Heating systems EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

- Data Brochure Universal Reset Module 422

- Data Brochure Universal Reset Module 422 - Data Brochure Universal Reset Module 422 D 422 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

Physical Plant Complex

Physical Plant Complex Continuous Commissioning Report For the Physical Plant Complex Building #1156 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Technical Report Three

Technical Report Three Technical Report Three Existing Conditions for Mechanical Systems Contents Executive Summary...2 Building Overview...2 Mechanical Systems Overview...2 Mechanical System...3 Outdoor & Indoor Design Conditions...3

More information

DACC Health Sciences Building Air Handler Assessment/Study

DACC Health Sciences Building Air Handler Assessment/Study DACC Health Sciences Building Air Handler Assessment/Study NMSU Facilities and Services Department P.O. Box 30001 Las Cruces, NM 88003-8001 June 14, 2016 Final Submittal 1065 S. Main St., Bldg. D, Ste.

More information

b.) Technical Information:

b.) Technical Information: Section VI- Strategies a.) Summary: It is important for new construction designers to consider the heating, ventilation, and air conditioning needs within a building. There are many different systems,

More information

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC VOLUME ONE NUMBER THREE SYNOPSIS A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S In this issue... Part-Load Strategies Why they re important.......... 1 What Things

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

Hydronic & HVAC Control Systems

Hydronic & HVAC Control Systems tekmar 218 Full Line Catalog Hydronic & HVAC Control Systems HVAC Multi-Staging Alternative Energy Zoning Snow Melting Setpoint tekmarcontrols.com tekmarcontrols.com Better Design, Better Control, Better

More information

- Data Brochure Universal Reset Module 423

- Data Brochure Universal Reset Module 423 - Data Brochure Universal Reset Module 423 D 423 08/07 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough-in Wiring Rough-in

More information

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1: 4510 Helgesen Drive, Madison, WI, 53718 608.221.4499, 800.627.4499, Fax: 608.221.2824 support@renewaire.com www.renewaire.com RD2XIN INSTALLATION AND OPERATION MANUAL BOOK 1 OVERVIEW ABOUT BOOK 1: This

More information

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner ESL-TR-99/12-09 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Commerce (TAMU-Commerce) Commerce, Texas Submitted to Texas

More information

Improving Control of Dual-Duct Single-Fan Variable Air Volume Systems

Improving Control of Dual-Duct Single-Fan Variable Air Volume Systems Improving Control of Dual-Duct Single-Fan Variable Air Volume Systems Guanghua Wei, P.E. Joe Martinez Tom Minihan Assistant Research Engineer Research Engineering Associate Graduate Student Tim Brundidge

More information

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available. PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

User s Manual

User s Manual 997-060180-4e User s Manual 8403-060 Menu Driven Display 1120-445 I. CONTROLLER OPERATION ADJUSTING TEMPERATURE (Temporary Override when in Programmable mode) 1. Before you can adjust the temperature,

More information

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application 2236 Application Note 140-1228 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 10 Hardware Outputs... 10

More information

Computing Services Center

Computing Services Center Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Better Design, Better Control, Better Systems.

Better Design, Better Control, Better Systems. Product Catalog Better Design, Better Control, Better Systems. At tekmar Control Systems, we believe the indoor comfort of a building depends on the performance of its heating, ventilating & air conditioning

More information

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION BES-TECH TECHNOLOGY & SYSTEM INTEGRATION BES-TECH TECHNOLOGY & SYSTEM INTEGRATION DIGI-ACC Digi-ACC is a control kit for air cooled chiller systems, optimizing both chiller and pumps thereby reducing consumption

More information

TESTING, ADJUSTING AND BALANCING

TESTING, ADJUSTING AND BALANCING PART 1 GENERAL 1.01 DESCRIPTION A. Work Included: After completion of the work of installation, owner is responsible for procuring an air balancing and testing agency to test and regulate all components

More information

VLT 6000 HVAC Application Booklet

VLT 6000 HVAC Application Booklet Variable Air Volume Ventilation Systems... 3 Application...3 Traditional Design... 3 Adjustable frequency drives...4 Specific energy consumption...5 Annual operation load profile...5 Energy savings calculation

More information

Urbana Free Library HVAC Analysis. Prepared for the Urbana Free Library. Prepared by Paul Boland, P.E., and Nathan Alderman, E.I.T.

Urbana Free Library HVAC Analysis. Prepared for the Urbana Free Library. Prepared by Paul Boland, P.E., and Nathan Alderman, E.I.T. Urbana Free Library HVAC Analysis Prepared for the Urbana Free Library Prepared by Paul Boland, P.E., and Nathan Alderman, E.I.T. Report Dated August 8, 2016 1. Introduction The Urbana Free Library is

More information

Application of Direct Digital Temperature Control Systems for Maximum System Efficiency on VAV Systems

Application of Direct Digital Temperature Control Systems for Maximum System Efficiency on VAV Systems Application of Direct Digital Temperature Control Systems for Maximum System Efficiency on VAV Systems Frank W. Mayhew, EC/TC Consulting The acceptance of direct digital temperature control technology

More information

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Technical Report #3 Mechanical Systems Existing Conditions Evaluation Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents

More information

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)

More information

General HVAC Recommendations

General HVAC Recommendations General HVAC Recommendations DESIGN GUIDELINES FOR ENERGY EFFICIENT HVAC SYSTEMS Thank you for your interest in energy efficiency! Energy efficient heating, ventilation, and air conditioning (HVAC) equipment

More information

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee ASHRAE WILL GIVE YOU THE WORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique CTTC

More information

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size...

More information

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks Ventilation Heat Recovery PoolPak International Maintaining Your Climate for Indoor Pools and Waterparks Complete Ventilation, Heat Recovery and Dehumidification Packaged System by PoolPak International

More information

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0993 SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS A. This section defines the manner and method by which controls function. Requirements for each type of

More information

Design Standard. Thermal Systems (Chilled Water and Hot Water Systems) Detailed specifications follow. CHW AND HHW SUPPLY TEMPERATURE RESET

Design Standard. Thermal Systems (Chilled Water and Hot Water Systems) Detailed specifications follow. CHW AND HHW SUPPLY TEMPERATURE RESET Design Standard Detailed specifications follow. PART 1 CHW AND HHW SUPPLY TEMPERATURE RESET 1.1 The Utilities & Energy Services Department (UES) at Texas A&M University is actively identifying and implementing

More information

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. SECTION 239950 MECHANICAL COMMISSIONING SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process. B. Commissioning

More information

Best Practices for Condensing Boilers

Best Practices for Condensing Boilers ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal at www.cleaverbrooks.com. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For

More information

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate COMcheck Software Version 4.0.6.2 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2007) Standard HALCYON Bldg. 400 Alpharetta, Georgia 3a

More information

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.

More information

Zoned Rooftop Systems. Light commercial packaged rooftop systems from Trane

Zoned Rooftop Systems. Light commercial packaged rooftop systems from Trane Zoned Rooftop Systems Light commercial packaged rooftop systems from Trane Trane Zoned Rooftop Systems Components of Trane Zoned Rooftop Systems p. 3 Zoned Rooftop System Configurations p. 4 Systems comparison

More information

A full list of energy conservation opportunities (ECO) for air-conditioned buildings

A full list of energy conservation opportunities (ECO) for air-conditioned buildings A full list of energy conservation opportunities (ECO) for air-conditioned buildings Team France (Project coordinator) Armines - Mines de Paris Austria Austrian Energy Agency Belgium Université de Liège

More information

High-Performance VAV Systems

High-Performance VAV Systems This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not

More information

The M & V Guided Recommissioning Process. Energy & Water Conservation Program. September 2015 MOO

The M & V Guided Recommissioning Process. Energy & Water Conservation Program. September 2015 MOO The M & V Guided Recommissioning Process MOO Energy & Water Conservation Program September 2015 EWC Agenda MOO EWC Overview Our approach Progress Fault Detection Zone & customer feedback Variance reporting

More information

Product Data. Features/Benefits. 33CS Carrier Comfort System Variable Volume and Temperature (VVT )

Product Data. Features/Benefits. 33CS Carrier Comfort System Variable Volume and Temperature (VVT ) Product Data 33CS Carrier Comfort System Variable Volume and Temperature (VVT ) The VVT Comfort System provides the following features and benefits: 365-day scheduling, daylight savings compensation, and

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic VAV Systems One of the Systems Series July 2012 TRG-TRC014-EN VAV Systems One of the Systems Series A publication of Trane Preface VAV Systems A Trane Air Conditioning Clinic Figure

More information

- Data Brochure Boiler Control 274

- Data Brochure Boiler Control 274 - Data Brochure Boiler Control 274 274_D 03/17 The Boiler Control 274 operates up to four on/off boilers to provide outdoor reset operation, domestic hot water and setpoint operation with priority. When

More information

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Related Sections..1 The contractor is to ensure that all related work is co ordinated among all specification sections, as well as between Division 11,

More information

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for: Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT

More information

Evolution Control. Zone Control Homeowner s Guide

Evolution Control. Zone Control Homeowner s Guide Evolution Control Zone Control Homeowner s Guide CONGRATULATIONS! Your decision to choose the Bryant Evolution Control puts you in a select group of homeowners who understand the value of precise comfort

More information

Your Home. Jacco & Assoc.

Your Home. Jacco & Assoc. Your Home Fan on with call for heating or cooling Heating on with call from space thermostat Stage as required to maintain The 75F Basics adj. - First stage of heating shall be heat pump Cooling on with

More information

AirTrak. Digital Control System. User Manual. Touchscreen Systems

AirTrak. Digital Control System. User Manual. Touchscreen Systems AirTrak Digital Control System User Manual Touchscreen Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 9 AIRTRAK DEFAULT SETTINGS... 9 Unit Operating Modes... 10 MRT Controls...

More information

HVAC Design Overview of Variable Air Volume Systems

HVAC Design Overview of Variable Air Volume Systems PDHonline Course M252 (4 PDH) HVAC Design Overview of Variable Air Volume Systems Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

Heat Pumps M2 SERIES. Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features:

Heat Pumps M2 SERIES. Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features: Heat Pumps M2 SERIES Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features: Water-source and geothermal heat pump self-contained units with capacities from 3-70 tons 10%-100% variable

More information

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012) Madeira City Schools Madeira, Ohio HVAC Assessment December 2011 (Revised February 2012) Prepared by: CMTA Engineering Consultants, Inc. 10411 Meeting Street Prospect, KY 40059 www.cmtaegrs.com (502) 326-3085

More information

Harrington Tower Building

Harrington Tower Building Continuous Commissioning Report For the Harrington Tower Building Building #435 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

1 - This title will copy onto other forms Date

1 - This title will copy onto other forms Date 2015 Washington State Energy Code Compliance Forms for Commercial, R2 and R3 over 3 stories and all R1 Mechanical Summary MECH-SUM Project Title: 1 - This title will copy onto other forms Date 1/1/2015

More information

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series.

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series. RN/RQ Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS RQ Series Features: Air-cooled or water-cooled condenser, with unit capacities

More information

NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING

NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING Danny Hall, National Sales Manager, Desert Aire Corp., Milwaukee, WI USA Traditionally, a heat pump has relied on a reversing valve system

More information