Preliminary investigations of smoke movement through HVAC systems and duct smoke detectors. Lougheed, G.D.; McCartney, C.; Carpenter, D.W.

Size: px
Start display at page:

Download "Preliminary investigations of smoke movement through HVAC systems and duct smoke detectors. Lougheed, G.D.; McCartney, C.; Carpenter, D.W."

Transcription

1 Preliminary investigations of smoke movement through HVAC systems and duct smoke detectors Lougheed, G.D.; McCartney, C.; Carpenter, D.W. NRCC A version of this document is published in / Une version de ce document se trouve dans : ASHRAE Transactions, v. 108, pt. 2, 2002, pp

2 HI (RP-1079) 2002, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( Reprinted by permission from ASHRAE Transactions 2002, Volume 108, Part 2. This paper may not be copied nor distributed in either paper or digital form without ASHRAE's permission. Preliminary Investigations of Smoke Movement Through HVAC Systems and Duct Smoke Detectors Gary D. Lougheed, Ph.D. Cameron McCartney Don W. Carpenter Member ASHRAE ABSTRACT A project was initiated to investigate concerns regarding the application of duct smoke detectors (ASHRAE RP-1079). The objective of the research was to investigate the effects of driving forces, dilution, aging, smoke stratification, filters, and sample tube efficacy on smoke detector response. As one part of this project, a series of full-scale fire tests were conducted in a ten-story facility. This paper describes the full-scale test facility and provides preliminary results regarding smoke movement through an HVAC system and the operation of duct smoke detectors. INTRODUCTION The fire hazards associated with air moving systems in buildings and the underlying approaches for fire safety of heating, ventilating, and air-conditioning (HVAC) systems were reviewed by Klote (1993). In principle, protection is needed from the spread of fire and smoke due to fires both inside and outside of the HVAC system. Various smoke management approaches to minimize fire spread through the HVAC system and to limit smoke production and smoke transport are provided in NFPA 90A (1999), NFPA 92A (2000a), and NFPA 92B (2000b). Detailed design considerations and engineering principles for smoke management systems are given in Klote and Milke (1992). The National Board of Fire Underwriters (NBFU 1939) recommended the shutdown of the HVAC system during a fire. For many years, this was the standard approach for preventing smoke transport by the HVAC system. In recent years, the operation of the HVAC system as a smoke control system has become a common alternative (Klote 1993). NFPA 90A (1999) requires that duct smoke detectors be installed in HVAC systems. The purpose of the duct smoke detector is to provide for the shutdown of the HVAC system in the event of a fire to avoid actively recirculating smoke through a building. Extensive research has been conducted in the area of fire detection (Grosshandler 1995, 1997; Mulholland 1995; Schifiliti et al. 1995). Nevertheless, little work has been conducted into the effectiveness of duct smoke detectors. In light of the lack of research, there has been only anecdotal evidence of their efficacy (Wolin et al. 2001). Recently, a project was initiated to investigate concerns regarding the application of duct smoke detectors (ASHRAE RP-1079). The objective of the research was to investigate the effects of driving forces, dilution, aging, smoke stratification, filters, and sample tube efficacy on smoke detector response. As part of this project, a literature review, small-scale fire tests, and modeling studies were conducted. Wolin et al. (2000) and Milke et al. (2002) provide results from these studies. Also, as part of the project, the National Research Council Canada (NRC) conducted a series of full-scale fire tests in its ten-story facility. This paper describes the full-scale test facility and provides preliminary results regarding smoke movement through the HVAC system and the operation of duct smoke detectors. TEST The full-scale fire tests utilized a ten-story tower facility that is part of the full-scale fire test facilities located near Almonte, Ontario. This facility was designed to represent conditions of a high-rise building. It has been used extensively for studies on smoke movement (Said and McDonald 1991; Hokugo et al. 1995; Lougheed and Carpenter 1997) and smoke control systems (Klote and Milke 1992; Tamura 1994). Gary Lougheed is a senior research officer, Cameron McCartney is a technical officer, and Don Carpenter is a senior technical officer in the Fire Risk Management Program, Institute of Research in Construction, National Research Council of Canada, Ottawa, Ontario. ASHRAE Transactions: Symposia 849

3 Figure 1 Typical floor plan for ten-story facility. Figure 2 Fire test floor. This ten-story facility includes an experimental tower and an attached observation tower. The typical floor height is 2.4 m except for the first and second floors, which are 3.4 m. Both towers are constructed of 200 mm thick monolithic reinforced concrete. A plan view of a typical floor is shown in Figure 1. The observation tower contains a freight elevator, stairway, and a workspace for instrumentation and data acquisition. It is protected from the experimental section by a firewall and fire doors with small fixed wired-glass windows. An independent air system maintains a comfortable temperature in winter and pressurizes the observation tower to prevent ingress of combustion products from the experimental tower. The experimental tower contains all the shafts and other features necessary to simulate air and smoke movement patterns in the center core of a typical multistory building, including the elevator, stair, smoke exhaust, service, and supply and return air shafts. The elevator and stair shafts are full-sized, but the elevator shaft has no car or hoisting apparatus. The stair shaft is equipped with a standard staircase. A surrounding corridor isolates the shafts from the exterior walls, creating a typical building center core (Figure 1). All joints in the concrete structure were sealed to minimize uncontrolled air leakage. The exterior walls and walls of vertical shafts were provided with variable openings that can be set to provide leakage areas of typical buildings. A separate structure, adjacent to the tower, houses the air moving and heating plant; the air ducts are connected underground to the main test facility through a short tunnel. Two separate HVAC systems are available. The first system handles the main air supply and heating load and includes all the elements of a building HVAC system, including return and supply fans, filters, etc. This system normally operates in the recirculation mode, but it can be operated with 100% outside air and used to pressurize the entire building. The second air-handling system supplies outside air either to the experimental stair and elevator shafts or to the vestibules located between the entrances to these shafts and the fire test area. This system was not used as part of this project. The airflow rates in the air ducts were measured with either multipoint self-averaging total pressure tubes and their associated static pressure taps or with an orifice plate. All were calibrated using the pitot traverse method. For this project, only the first air-handling system was used. This system includes a variable-speed return air fan with a maximum capacity of 17 m 3 /s, which was connected to the return airshaft in the test facility. A variable-speed supply air fan with a maximum capacity of 14 m 3 /s was connected to the supply airshaft in the building. These shafts are located on the north side of the center core (see Figure 1). TEST CONFIGURATION FIRE FLOOR The tower facility has been used predominantly for investigations related to smoke control systems. As such, the mechanical systems were primarily set up to supply or exhaust air from various parts of the building such as the stair shaft or the elevator shaft. These test arrangements were used to simulate operating smoke control systems. In the basic configuration for smoke control investigations, the supply and return airshafts were linked to each floor through simple openings in the shaft walls. For this project, supply and return air ducts were installed in the corridor on the first floor. (The first and second floors have nominal ceiling heights of 3.4 m compared with 2.4 m on all other floors. This provides room to install ductwork and a drop ceiling at the 2.6 m height simulating a corridor in an office building.) A fire room was set up at the south end of the east corridor (Figure 2) on the first floor of the test facility. The fire test room was approximately 4.1 m by 2.3 m by 2.6 m high, simulating a standard office. The fire room was connected to a corridor (Figure 2) through a 0.93 m by 2.13 m high doorway. The corridor extended around three sides of the center core of the test facility. It was approximately 1.2 m wide and had a total length of 25 m. A suspended ceiling was installed at the 2.6 m height. The floor area and the volume of the fire room and the corridor are given in Table ASHRAE Transactions: Symposia

4 Supply and return air ducts were installed above the suspended ceiling in the corridor. These two duct systems were connected to the building supply and return shafts. Air was supplied to the fire room from the supply duct through an outlet at the center of the ceiling. No return air inlet was provided in the test room. This simulates a typical arrangement for an HVAC system in buildings with separate offices. That is, a system in which air is supplied to the office space and the inlets for the return air system are in the common corridor connecting the offices. Secondary ducts were connected to the supply duct in each section of the corridor. These ducts extended through the ceiling and had outlets located approximately 550 mm above the floor. These ducts were used to simulate airflow reaching the corridor through vents in office doors. Return air inlets were located in the corridor ceiling in each section of the corridor and connected to the return air duct. The return air inlets and the supply air outlets were equispaced in each corridor. However, their locations were offset to ensure mixing of the air in the corridor. TEST CONFIGURATION NONFIRE FLOORS The test facility consists of ten floors. However, two floors (Floors 2 and 7) were fire-hardened for previous test programs. As a result, it was difficult to access the HVAC shafts on these floors and they were not included in the final test setup. These floors also contained significant amounts of particulate matter from previous testing that may affect the duct smoke detectors. Floors 3 through 6 and 8 through 10 were used as the nonfire floors. The floor area and volume for each floor are given in Table 1. The total floor area and volume for the test arrangement, including the two HVAC shafts, are also shown. Ductwork was not installed on the nonfire floors. The openings in the shaft walls were used to provide airflow to and from each floor. The door in the north corridor (Figure 1) was closed for all the tests ensuring the airflow mixed throughout each floor. Dampers on the fire floor supply ducts were used to balance the supply airflow evenly throughout the floor area. The openings to the shafts on each floor were then adjusted to provide a balanced airflow to each nonfire floor. DETECTOR LOCATIONS Seven models of commercially available duct smoke detectors were used in the project. They included two ionization, two photoelectric, one photoelectric/thermal, one integrated (ionization, photoelectric, and thermal), and one sampling. Duct smoke detectors were located at three primary locations in the HVAC system ductwork: 1. Measuring Station 1. Measuring Station 1 (MS1) was located in the return air duct on the fire floor at the connection to the return shaft. This location was used to provide information on the ability of the detectors to detect smoke on the fire floor. An ionization and a photoelectric detector were mounted at this location. 2. Measuring Station 2. Measuring Station 2 (MS2) was located in a section of the return air duct in the mechanical room. A sample of each detector model and type used in the project was mounted at this location. 3. Measuring Station 3. Measuring Station 3 (MS3) was located in a section of the supply air duct. A sample of each detector model and type was used at this location. 4. In addition to the detectors located at the three primary measuring stations, ten detectors (identical model and type) were located in a straight section of the return air duct in the mechanical room. These detectors were at five locations along the length of the duct starting upstream of an elbow. The sampling tubes for the two detectors at each location were on the vertical and horizontal centerline of the duct, respectively. These detectors were used to investigate the effect of smoke stratification. INSTRUMENTATION The following instrumentation was used in the full-scale fire tests: 1. Temperature in fire room. Two thermocouple trees were located in the fire room to measure the temperature profiles during the test. The thermocouples were located 450, 770, 1050, 1650, 1940, 2240, and 2550 mm above the floor. In addition, four thermocouples were mounted 150 mm below the ceiling at the room quarter points, and one thermocouple was at the center top of the doorway 40 mm below the top of the opening. 2. Temperature in the corridor. Three thermocouple trees were located at the midpoint of each section of the corridor. The thermocouple heights were the same as those used in the fire room. 3. Pressure differences. Pressure differences were measured at the following locations: (a) south wall of the fire room 150 mm below the ceiling (average of three equispaced taps), (b) first floor corridor 150 mm below ceiling, (c) first floor corridor at 1.2 m height, (d) supply duct leading to the fire room, (e) return duct at the shaft connection, (f) supply duct at the shaft connection, (g) exterior of the building in TABLE 1 Floor Area and Volumes in Test Arrangement Location Floor Area (m 2 ) Volume (m 3 ) Fire room Corridor fire floor Total fire floor Nonfire floor HVAC shafts Total test arrangement ASHRAE Transactions: Symposia 851

5 Test TABLE 2 Fuel Sources for Tests Fuel 7-9, 12, 16, 19, 23 Propane 13, 17, 21 Clothing 14, 18, 20, 22 Polyurethane foam 15 Heptane TABLE 3 HVAC Flow Rates for Tests Test Fire Floor Nonfire Floor Total (m 3 /s) (m 3 /s) (m 3 /s) the west wall, (h) return shaft at second floor level, and (i) return shaft at the tenth floor. These measurements will be used to investigate the relative effect of the pressures produced by the fire on smoke movement compared with smoke movement due to the HVAC system. 4. Air velocities and temperatures in ducts. Bidirectional probes were used to measure the velocities in the return duct on the fire floor and the return duct in the mechanical room and in the main supply duct). Bidirectional probes were also installed in the supply duct to the test room and the supply duct at the connection to the main supply shaft. These probes were oriented to measure the velocity in the opposite direction to the normal airflow (i.e., they measure smoke flow produced in the duct by the fire). The temperature was also measured at all locations at which pitot static probes were installed. 5. Smoke obscuration. Smoke density meters were used to measure the smoke optical density in the ductwork at Measuring Stations 1 and Carbon dioxide concentration. Gas analyzers were used to measure the concentration of carbon dioxide in the fire room doorway and at Measuring Stations 1 and 2. In addition, an oxygen analyzer was used to measure the concentration of oxygen at Measuring Station 1. This measurement was used to estimate the heat release rate for the test fires. A data acquisition system was used to record the data from the instrumentation noted above. In addition, the analog outputs of the duct smoke detectors were recorded using data acquisition systems and software provided by the detector manufacturers. FIRE SOURCES The test arrangement discussed in this paper was developed specifically to investigate smoke movement in the HVAC system and issues related to the effectiveness of duct smoke detectors. In order to provide baseline data on smoke movement in the test arrangement and in the HVAC system, a set of propane burners was used for a series of initial tests. The propane burner system was selected since it could provide steady well-controlled heat release rates over an extended time period. These tests also provided data for use in investigating the relative magnitude of pressures that affect smoke movement in the test facility. Based on the results from the propane burner tests, it was determined that steady fires with a heat output of approximately 100 to 200 kw would produce fire conditions appropriate for this study. Initial tests were conducted using a calorimeter facility to investigate potential fuels, including paper, clothing, polyurethane foam, and heptane pan fires that could be used for the full-scale tests. Based on these tests, it was determined that relatively steady fires with a duration of 10 to 20 min and with heat release rates of 100 to 200 kw could be obtained using clothing or polyurethane foam as a fuel. These fuels were used for the tests in the tower facility discussed in this paper. The fuel sources for the tests are shown in Table 2. PROPANE BURNER FIRE TESTS Five tests were conducted using propane burners as the fire source. The test arrangement for the HVAC system for these tests is summarized in Table 3. For Tests 8 and 9 with the propane burner and Tests 12 to 15 with other fuel sources, the openings in the return and supply shafts on the nonfire floors were adjusted to provide a balanced airflow to these floors. It was also intended that the same airflow be provided to the fire floor. However, a preliminary analysis of the test data indicated that the airflow on the fire floor was lower than expected. This was confirmed with measurements using a hot-wire anemometer. The airflow shown in Table 3 for Tests 8 and 9 are the measured capacities. For subsequent tests with the propane burner and other fuels (Tests 16-23), the airflow to all floors, including the fire floor, were measured using a hot-wire anemometer to provide a balanced airflow to all floors. In both Tests 8 and 9, the propane burner was used to provide a steady heat release rate of 100 kw for extended test durations. In Test 8, the HVAC system was operated in full recirculation mode. In Test 9, the system was operated with 100% exhaust of the return air and 100% fresh air for the supply system. The CO 2 concentrations measured in the doorway of the fire room and at Measuring Stations 1 and 2 are shown in Figure 3. The background CO 2 concentration was subtracted from the measured results. The plots shown in Figure 3 are the increase in CO 2 concentrations due to the propane fire. 852 ASHRAE Transactions: Symposia

6 This is equivalent to the relative rate of air provided by the HVAC system to the seven nonfire floors to that provided to the fire floor. That is, the difference in CO 2 levels measured at the two locations is the result of dilution with fresh air in the return airshaft, resulting in a 92.4% reduction in the CO 2 levels. The CO C = A(1-e -Bt 2 concentrations measured in Test 8 are also )(1) shown in Figure 3. There was a continual increase at all three For Test 9, there was an initial increase in the gas concentrations at the three locations. Subsequently, the CO 2 concentrations reached steady state. Figure 4 shows a regression fit to the CO 2 concentrations measured in the return system in Test 9 using a two-parameter exponential rise to a maximum (Equation 1). where C = CO 2 concentration, %; A = maximum CO 2 concentration, %; B = time constant, s -1 ; t = time, s. The calculated parameters for the two regression fits shown in Figure 4 are given in Table 4. The ratio of the maximum concentrations measured at Measuring Stations 1 and 2 (A MS1 /A MS2 ) is approximately 13. Figure 3 Increase in carbon dioxide concentrations for Tests 8 and 9. locations until the propane burner was shut off. However, the most noticeable effect was in the CO 2 levels measured in the main HVAC return duct in the mechanical room. The relative impact of the recirculated fire gases is also demonstrated by the calculated parameters given in Table 4 for fits using Equation 1. For the concentrations at Measuring Station 1, the fit parameters for Test 8 are comparable to those for Test 9. The small differences in the calculated parameters are consistent with the recirculation of relatively dilute fire gases back to the fire floor. The fit parameters calculated for the concentrations measured in the main mechanical system indicate a slow increase in CO 2 levels throughout the test. At the end of the test, the concentration in the main return system has reached approximately 32% of that measured in the return duct on the fire floor compared with 7.6% in the initial stages of the test. Tests 16, 19, and 23 were also conducted with the propane burner. In these tests, the fire size was varied during the test to produce three steady-state heat release rates of 100, 250, and 500 kw. In addition, the total airflow provided by the HVAC system was varied. In Test 16, the airflow was the same as that used in Tests 8 and 9. However, in this test, the same airflow was provided to all floors (Table 3). For Tests 19 and 23, the total HVAC airflow was decreased and increased by 27% and 35%, respectively, compared with Test 16. The increase in CO 2 measured at Measuring Stations 1 and 2 are shown in Figures 5 and 6, respectively. In addition, the calculated parameters A MS1 and B MS1 for exponential increase to a maximum are given in Table 5. These parameters were calculated using the data for the initial 500 s of the test. Some general trends are as follows: 1. With increased airflow to the fire floor, the CO 2 levels at Measuring Station 1 decreased (a similar decrease was also noted in the levels measured in the doorway). These results suggest that, with lower ventilation rates for the fire floor, both fresh and contaminated air was drawn into the fire TABLE 4 Parameters for Exponential Increase of CO 2 Concentration at Measuring Stations 1 and 2 for Tests 8 and 9 Figure 4 Regression fits to CO 2 concentrations for Test 9. Test A MS1 B MS1 A MS2 B MS2 (%) (s -1 ) (%) (s -1 ) ASHRAE Transactions: Symposia 853

7 TABLE 5 Parameters for Exponential Increase of CO 2 Concentration at Measuring Station 1 for Tests 16, 19, and 23 Test A MS1 B MS1 (%) (s -1 ) Figure 5 Increase in CO 2 concentrations in return duct on fire floor for Tests 16, 19, and 23. Figure 6 Increase in CO 2 concentrations in main HVAC return duct for Tests 16, 19, and 23. Figure 7 Response of detectors at Measuring Stations 1, 2, and 3 for Test 14 with polyurethane foam. room to produce increased CO 2 concentrations. This effect is also shown in the higher heat release portions of Test 19, resulting in more rapid increases in CO 2 levels (Figure 5). 2. Also, with increased airflow to the fire floor, steady conditions were reached earlier, as indicated by the higher values for B MS1. 3. The increase in CO 2 levels at Measuring Station 2 followed the changes in heat release rate and the increase in CO 2 levels measured in the floor duct. Initially, the amount of CO 2 at Measuring Station 2 was approximately 14% of the levels at Measuring Station 1. This is consistent with the level of dilution in the main return shaft for these tests. Although the total airflow was varied, the ratio of airflow to the nonfire floors versus the airflow to the fire floor was approximately 7:1 in all tests. 4. Subsequent to the initial increase in CO 2 levels with changes in the fire size, there was a continuous increase in the concentrations at Measuring Station 2 as the contaminated air was recirculated throughout the test facility. During the steady heat release rate periods, the increase in CO 2 levels was comparable in the three tests (Figure 6). FIRE TESTS WITH CLOTHING AND POLYURETHANE FOAM Fire tests were conducted using clothing and polyurethane foam as fuel sources (Table 2). The setup of the HVAC system for the tests is shown in Table 3. All tests were conducted with the HVAC system operating in the full recirculation mode. By using thick fuel beds, these fuel sources provided extended fire duration with relatively steady heat release rates and smoke production. The heat release rates were approximately 100 and 200 kw for polyurethane foam and clothing fires, respectively. Identical ionization and photoelectric detectors were located at the three measuring stations in the HVAC system. The detector responses measured at these three locations for tests with polyurethane foam and clothing are shown in Figures 7 and 8. (Each detector model has a different output. To facilitate data analysis, the detector responses were normalized. First, the baseline output was subtracted from the detector data. Subsequently, the data were divided by the difference between the maximum and baseline outputs to determine the detector response as a percent of the maximum output.) 854 ASHRAE Transactions: Symposia

8 Figure 8 Response of detectors at Measuring Stations 1, 2, and 3 for Test 13 with clothing. Figure 9 Response of photodetectors at Measuring Station 1 for tests with polyurethance foam. For the polyurethane foam fire (Test 14), the peak outputs for both detectors were at or near 100% in the return duct on the fire floor (MS1). With the dilution in the main return shaft, the outputs were reduced to 20% to 30% (MS2). There was a further reduction in the output to 12% to 20% for the detectors in the supply duct (MS3). (The tests were conducted with commercial fiberglass filters installed in the HVAC system between the MS2 and MS3.) For Test 14, slightly higher initial responses were measured with the ionization detectors. Also, these detectors were slower in decreasing to minimal response after the fire. For the clothing tests, the initial response of the ionization detector was significantly higher than that for the photoelectric detector in the return duct on the fire floor (MS1). However, the initial outputs at the other two locations were comparable. In fact, the output of the photoelectric detector was higher than that for the ionization detector in the main return duct (MS2). After 400 s, the outputs for the detectors in the main HVAC system showed a steady increase. This can be attributed in part to the recirculation of smoke through the HVAC system. However, in the later stages of the test, the output of the photoelectric detector increased more rapidly than the ionization detectors with the detector at MS1 eventually reaching the 100% level at approximately 1700 s. Since a similar change in response occurred for all of the photoelectric detectors, it can be assumed it was due to changes in the test dynamics. As noted above, there were some differences in the responses of the two types of detectors. However, in general, the responses of the ionization and photoelectric detectors were comparable, particularly for the diluted smoke in the main HVAC system. Figure 10 Response of photodetectors at Measuring Station 2 for tests with polyurethane foam. Figures 9 and 10 show the photoelectric detector responses in the return duct on the fire floor (MS1) and in the main return duct (MS2) for tests with polyurethane foam. The CO 2 concentrations measured at these two locations for Tests 18, 20, and 22 are shown in Figure 11. Also, the smoke optical density measured in the main return duct is shown in Figure 12. The CO 2 levels in the main return duct were approximately 15% to 20% of that measured in the return duct on the fire floor (Figure 11). This is consistent with the expected change due to the approximately 7:1 dilution factor (86% decrease). ASHRAE Transactions: Symposia 855

9 The detector responses shown in Figures 9 and 10 were consistent with the test-to-test variations in the fire and HVAC system: 1. The highest change in detector response at the two measuring locations was for Test 14 in which the smoke dilution in the main return shaft was approximately 13:1. 2. The fire development in Test 22 was affected by the air supply through the inlet in the ceiling of the fire room. With the higher supply airflow used in this test, there was direct airflow onto the fuel surface. This resulted in a slower development of the fire and a delay in smoke production that was reflected in the detector responses. 3. Less fuel was used in Test 14, resulting in shorter test duration. This resulted in more rapid decrease in the output of the detector on the fire floor. The continued output for the detector in the main return duct can be attributed to the recirculation of the smoke through the test facility. Figure 11 CO 2 concentrations in return duct fire floor (MS1) and in main return duct (MS2) for tests with polyurethane foam. Figure 12 Smoke optical density in main return duct (MS2) for tests with polyurethane foam. The responses of the detectors located in the main return duct were also consistent with the smoke optical density results shown in Figure 12. Specifically, the maximum detector response depended on the test-to-test variation in optical density. Also, the general dynamics of the smoke detector response was similar to the optical density results. For the tests with polyurethane foam, the maximum detector responses ranged between approximately 20% and 60%. For these same tests, the measured optical density ranged between approximately 0.02 and 0.08 m -1. Using the relationship between visibility and optical density given by Tamura (1994) for front illuminated signs, Visibility (m) = 1/optical density (m -1 ), (2) the visibility in the smoke in the main HVAC system in these tests ranges from 12.5 m to 50 m. CONCLUSIONS For the tests discussed in this paper, a ten-story test facility was set up to simulate smoke movement through a building HVAC system. In order to minimize parameters, the test arrangement was reduced to four primary components: 1. the fire room 2. the corridor on the fire floor 3. the HVAC system 4. compartments on seven nonfire floors The only path for smoke and airflow between the fire floor and the other floors was through the HVAC system. Steady heat release tests were conducted with a propane burner to investigate smoke movement in the test arrangement. These tests indicated that the fire size and the airflow rate provided by the HVAC system affected the smoke dynamics on the fire floor. With low HVAC airflow, there was increased contamination of the air in the corridor, resulting in higher CO 2 levels in the return duct on the fire floor. With higher airflow, the contaminated air was mixed more rapidly into the return duct on the fire floor. However, the maximum concentrations were lower as a result of higher dilution in the corridor. The CO 2 concentrations measured in the main return duct initially increased at the same rate as in the return duct on the fire floor. However, the air from the seven nonfire floors diluted the contaminated air, reducing the concentrations. With the HVAC system operated in full recirculation mode, the concentrations in the main HVAC system continued to increase as the contaminated air mixed throughout the facility. The results of tests with polyurethane foam and clothing indicate that there were some differences in the responses produced by photoelectric and ionization detectors. However, for the diluted smoke in the main HVAC system, the outputs of the two detectors were comparable. For the tests with polyurethane foam, the outputs of the detectors varied with the changes in fire dynamics and the HVAC setup. In particular, the detector responses were consistent with the variations in the smoke optical density. The 856 ASHRAE Transactions: Symposia

10 results indicate that the detectors are responding to smoke with visibility in the range of 10 to 50 m. This visibility range overlaps with the visibility levels suggested for smoke control and smoke management applications (Tamura 1994). ACKNOWLEDGMENTS This work was funded by the Fire Detection Institute (FDI). The suggestions, comments, and contributions of John Cholin and the FDI members are greatly appreciated. As part of the FDI project, the University of Maryland conducted a literature review, small-scale fire tests, and modeling studies that provided invaluable information for the full-scale fire tests undertaken in this project. The authors would also like to acknowledge the support of Mickey Ryan, Michael Wright, Vic Fortington, and Bruce Taber in setting up the test arrangement and conducting the tests. REFERENCES Grosshandler, W.L Proceedings of the 1995 Workshop on Fire Detector Research, NISTIR Gaithersburg, Md.: National Institute of Standards and Technology. Grosshandler, W.L Progress report on fire detection research in the United States, U.S./Japan Government Cooperative Program on Natural Resources (UJNR), 13th Joint Panel Meeting, March 13 20, 1996, Gaithersburg, Md., Vol. 2, Beall, K.A., ed., pp Hokugo, A., D. Yung, and G.V. Hadjisophocleous Experiments to evaluate the NRCC smoke movement model for risk-assessment. Proceedings of the Fourth International Symposium, International Association for Fire Safety Science, Ottawa, pp Klote, J.H Air moving systems and fire protection, NISTIR 5227, Gaithersburg, Md.: National Institute of Standards and Technology. Klote, J.K., and J.A. Milke Design of Smoke Management Systems. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Lougheed, G.D., and D.W. Carpenter Full-scale fire tests for sprinklered offices in a high rise building. Proceedings Second International Conference on Fire Research and Engineering, Gaithersburg, Md., pp Milke, J.A., J.L. Torero, and F.W. Mowrer Use of optical density-based measurements as metrics for smoke detectors. ASHRAE Transactions, Volume 108. Mulholland, G.W Smoke production and properties. SFPE Handbook of Fire Protection Engineering, 2d ed., Quincy, Mass.: National Fire Protection Association. NFPA NFPA 90A, Standard for the installation of air conditioning and ventilating systems. Quincy, Mass.: National Fire Protection Association. NFPA. 2000a. NFPA 92A, Recommended practice for smoke-control systems. Quincy, Mass.: National Fire Protection Association. NFPA. 2000b. NFPA 92B, Guide for smoke management systems in malls, atria, and large areas. Quincy, Mass.: National Fire Protection Association. NBFU Smoke hazards of air-conditioning systems. NFPA Quarterly 33: Said, M.N.A, and R.A. MacDonald An evaluation of a network smoke control model. ASHRAE Transactions 97: Schifiliti, R.P., B.J. Meacham, and R.L.P. Custer Design of detection systems. SFPE Handbook of Fire Protection Engineering, 2d ed. Quincy, Mass.: National Fire Protection Association. Tamura, G.T Smoke movement & control in high-rise office buildings. Quincy, Mass.: National Fire Protection Association. Wolin, S.D., N.L. Ryder, F. Leprince, J.A. Milke, F.W. Mowrer, and J.L. Torero Measurements of smoke characteristics in HVAC ducts. Fire Technology 37: DISCUSSION Sam Gillie, Senior Tech. Engineer, Hawaiian Electric Company, Honolulu, HI: (1) What type of smoke density meter was used? (2) Was the density across the duct measured in a grid so that cross section of the duct could be measured for density? Gary Lougheed: (1) Since smoke detectors are sensitive to relatively low smoke optical densities (<0.1 OD/m) compared to the levels normally measured in fire tests, a smoke meter system was developed specifically for this project. The system used an LED source that produces light in the visible portion of the spectrum. This source simulates the light sensitivity of the human eye. The system was calibrated using neutral density filters. The output of the system was linear with optical density over the range of OD/m (2) Because of the size of the HVAC system ducts, it was not possible to set up a grid system to measure the smoke optical density over the duct cross-section. For the smoke optical density measurements, a smoke sample was taken from the centre of the duct. ASHRAE Transactions: Symposia 857

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS Prepared for Smoke Safety Council 6775 SW 111 th Avenue, Suite 10 Beaverton, OR 97008 Prepared by Jesse J. Beitel Alison J. Wakelin Craig L.

More information

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment AKIHIKO HOKUGO Building Research Institute Ministry of Construction Tatehara I, Tsukuba-City 305, Japan DAVID YUNG and

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

Smoke movement for sprinklered fires. Lougheed, G.D.; McCartney, C.; Taber, B.C.

Smoke movement for sprinklered fires. Lougheed, G.D.; McCartney, C.; Taber, B.C. Smoke movement for sprinklered fires Lougheed, G.D.; McCartney, C.; Taber, B.C. NRCC-43138 Posting courtesy American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. www.ashrae.org

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS

COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS , Volume 1, Number 3, p.123-128, 1999 COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS D. Yung and G.V. Hadjisophocleous Fire Risk Management Program, Institute for Research

More information

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 Response-Time Comparisons of Ionization and Photoelectric/Heat Detectors 1. Introduction Despite

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates Zhou Y., Fei Y.*, Hu S. Q. Nanjing Tech University, College of Fire Safety Science and Engineering &

More information

PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR

PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR VIJAY T. D SOUZA, JASON A. SUTULA, STEPHEN M. OLENICK*, WEI ZHANG and RICHARD J. ROBY Combustion Science & Engineering, Inc. Columbia,

More information

Smoke Transport and FDS Validation

Smoke Transport and FDS Validation Smoke Transport and FDS Validation DANIEL GOTTUK, CHRISTOPHER MEALY and JASON FLOYD Hughes Associates, Inc. 361 Commerce Drive, Suite 817 Baltimore, Maryland 21227 ABSTRACT A 26 Fire Protection Research

More information

How design fires can be used in fire hazard analysis

How design fires can be used in fire hazard analysis How design fires can be used in fire hazard analysis Yung, D.T.; Bénichou, N. NRCC-44511 A version of this document is published in / Une version de ce document se trouve dans : Fire Technology, v. 38,

More information

Smoke Layer Height and Heat Flow through a Door

Smoke Layer Height and Heat Flow through a Door Smoke Layer Height and Heat Flow through a Door 2018 Smoke Layer Height and Heat Flow through a Door In this tutorial you will simulate a growing fire in the corner of a 5m x 5m room. The room has a 1m

More information

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Jason Huczek a, Marc Janssens a, Kentaro Onaka b, Stephen Turner c a SwRI, 6220 Culebra Road, San

More information

Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings

Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings Stephen M. Olenick 1, Richard J. Roby, Douglas J. Carpenter, and Adam Goodman Combustion Science & Engineering, Inc. 8940 Old Annapolis

More information

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE 1 RU ZHOU, 2 WEI ZHANG 1 School of Urban Construction and Safety Engineering, Nanjing University of Technology, Nanjing

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

Edward K. Budnick Hughes Associates, Inc. Wheaton, Maryland, U.S.A SUMMARY. that is entrained or otherwise mixed into the mass.

Edward K. Budnick Hughes Associates, Inc. Wheaton, Maryland, U.S.A SUMMARY. that is entrained or otherwise mixed into the mass. THE CAPABILITIES OF SMOKE CONTROL: FUNDAMENTALS AND ZONE SMOKE CONTROL John H. Klote Center for Fire Research National Institute of Standards and Technology Gaithersburg, Maryland, U.S.A. 20899 Edward

More information

Measurements of Smoke Characteristics

Measurements of Smoke Characteristics Fire Technology, 37, 363 395, 2001 2001 Kluwer Academic Publishers. Manufactured in The United States. Measurements of Smoke Characteristics in HVAC Ducts Steven D. Wolin, Noah L. Ryder, Frederic Leprince,

More information

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

ZONE MODEL VERIFICATION BY ELECTRIC HEATER , Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting

More information

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM , Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,

More information

A DESCRIPTION OF THE PROBABILISTIC AND DETERMINISTIC MODELLING USED IN FIRECAM

A DESCRIPTION OF THE PROBABILISTIC AND DETERMINISTIC MODELLING USED IN FIRECAM , Volume 1, Number 1, p.18-26, 1999 A DESCRIPTION OF THE PROBABILISTIC AND DETERMINISTIC MODELLING USED IN FIRECAM D. Yung, G.V. Hadjisophocleous and G. Proulx Fire Risk Management Program, National Research

More information

Aspirating Gas Detection CFD Modelling Predicts Application Performance

Aspirating Gas Detection CFD Modelling Predicts Application Performance Aspirating Gas Detection CFD Modelling Predicts Application Performance Yun Jiang Xtralis, Bentleigh East, Australia Claudio Groppetti Xtralis, Avon, MA, USA Abstract Historically gas detection has utilized

More information

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING H. Kotani, R. Satoh, T. Yamanaka Dept. of Architectural Engineering, School of Engineering, Osaka University, Osaka, Japan ABSTRACT The purpose

More information

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Mingsheng Liu, Ph.D., P.E. Energy Systems Laboratory Texas A&M University College Station, Texas

More information

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME Elizabeth L. Milarcik, Stephen M. Olenick*, and Richard J. Roby Combustion Science & Engineering,

More information

The Current (2017) State of the Art for Air Leakage in Ductwork

The Current (2017) State of the Art for Air Leakage in Ductwork The Current (2017) State of the Art for Air Leakage in Ductwork Over the last ten years there has been a major shift in the way ASHRAE has approached air leakage in ductwork. This is reflected in the latest

More information

Sprinklers in Combustible Concealed Spaces

Sprinklers in Combustible Concealed Spaces Sprinklers in Combustible Concealed Spaces G.D. Lougheed and J.K. Richardson Fire Research Section Institute for Research in Construction National Research Council Canada Ottawa, Ontario SUMMARY NFPA 13

More information

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER , Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

Analysis of the influence of open door size on fire smoke diffusion law in protective engineering

Analysis of the influence of open door size on fire smoke diffusion law in protective engineering Analysis of the influence of open door size on fire smoke diffusion law in protective engineering Abstract Zheli Xing a, Jinfeng Mao b, Chaofeng Li c and Jin Zhou d PLA University of Science and Technology,

More information

Using Smoke Obscuration to Warn of Pre-Ignition Conditions of Unattended Cooking Fires

Using Smoke Obscuration to Warn of Pre-Ignition Conditions of Unattended Cooking Fires Using Smoke Obscuration to Warn of Pre-Ignition Conditions of Unattended Cooking Fires Erik Johnsson, Mariusz Zarzecki National Institute of Standards and Technology, Gaithersburg, MD, USA Abstract A series

More information

Smoke Management in High-Rise Structures

Smoke Management in High-Rise Structures Smoke Management in High-Rise Structures Most modern building codes define a high-rise structure as a building greater than 75 feet in height from the lowest level of fire department vehicle access to

More information

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION DL Bohac * Center for Energy and Environment, Minneapolis, MN USA ABSTRACT Extensive

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team Jeremiah Crocker and Dr. Bin Xiao New Technology Team Copyright 2010 Tyco Fire Suppression & Building Products. All rights reserved. The products and specifications published herein are for general evaluation

More information

Experimental Study on Response Sensitivity of Smoke Detectors in High Flow Velocity

Experimental Study on Response Sensitivity of Smoke Detectors in High Flow Velocity Experimental Study on Response Sensitivity of Smoke Detectors in High Flow Velocity QIYUAN XIE 1, GUOFENG SU 2, HONGYONG YUAN 2, and YONGMING ZHANG 1 1 State Key Laboratory of Fire Science University of

More information

Experimental Study on the Characteristics of Temperature Field of Fire Room

Experimental Study on the Characteristics of Temperature Field of Fire Room Experimental Study on the Characteristics of Temperature Field of under Stack Effect in a Scaled High-rise Building Model WENXI SHI 1,2, JIE JI 1*, JINHUA SUN 1, SIUMING LO 2, LINJIE LI 1 and XIANGYONG

More information

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,

More information

Recent BRANZFIRE enhancements and validation

Recent BRANZFIRE enhancements and validation Recent BRANZFIRE enhancements and validation Michael Spearpoint University of Canterbury Summary BRANZFIRE is a multi-compartment fire zone model that has been under development since 1996 predominately

More information

Keywords: VEWFD; Smoke detection; Smoke production; In-situ testing.

Keywords: VEWFD; Smoke detection; Smoke production; In-situ testing. In-Situ Smoke Generation for Testing Very Early Warning Fire Detection (VEWFD) Joshua Dinaburg, Benjamin Gaudet Jensen Hughes, Baltimore, MD, USA Abstract In-situ smoke sensitivity testing in an operational

More information

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN , Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen

More information

Overview of the PRISME project Technical Description and Main Outcomes

Overview of the PRISME project Technical Description and Main Outcomes OECD PRISME Project on Fire Propagation Final Seminar Overview of the PRISME project Technical Description and Main Outcomes Audouin L., Rigollet L., Pretrel H., Le Saux W. IRSN / ETIC Summary (1) Context

More information

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist Andrew Kim and George Crampton Fire Research Program, National Research Council of Canada 1200 Montreal Road, Ottawa, Ontario,

More information

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 SAE Alternate Refrigerant Cooperative Research Program Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 To: Alternate Refrigerant Task Force Members From: Ward Atkinson

More information

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions Smoke Characterization Study October 29, 2008 Paul E. Patty, P.E. Senior Research Engineer Northbrook, IL 847-664-2752

More information

Air Moving Systems. Fire Safety Inspection and Testing of. NBSIR jan «1933. Washington, DC General Services Administration

Air Moving Systems. Fire Safety Inspection and Testing of. NBSIR jan «1933. Washington, DC General Services Administration National Bureau of Standards Gaithersburg, Maryland 2.0899 NBSIR 87-3660 jan «1933 Fire Safety Inspection and Testing of Air Moving Systems John H. Klote U.S. DEPARTMENT OF COMMERCE National Bureau of

More information

Test One: The Uncontrolled Compartment Fire

Test One: The Uncontrolled Compartment Fire The University of Edinburgh BRE Centre for Fire Safety Engineering One Day Symposium on The Dalmarnock Fire Tests: Experiments & Modelling Test One: The Uncontrolled Compartment Fire Cecilia Abecassis

More information

Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building

Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building Modelling Concepts for the Risk-cost Assessment Model FIRECAMTM and its Application to a Canadian Government Office Building D. YUNG, G.V. HADJISOPHOCLEOUS and G. PROULX National Fire Laboratory Institute

More information

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance Jong Min Choi, W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building

More information

A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS

A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS , Volume 3, Number 4, p.151-157, 2001 A NETWORK MODEL OF SIMULATING SMOKE MOVEMENT IN BUILDINGS F. Liu and X.Z. Fu Faculty of Urban Construction and Environmental Engineering Chongqing University, Chongqing

More information

EPSRC Research Project: Real Fires for the Safe Design of Tall Buildings

EPSRC Research Project: Real Fires for the Safe Design of Tall Buildings EPSRC Research Project: Real Fires for the Safe Design of Tall Buildings Prof Luke Bisby, Acting Director BRE Centre for Fire Safety Engineering Arup Chair of Fire and Structures BRE Centre for Fire Safety

More information

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c 1.0 INTRODUCTION This report presents the results of a fire performance evaluation in accordance with the 2011 Edition of National Fire Protection Association (NFPA) Standard 265, Standard Methods of Fire

More information

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me!

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me! 97.501B Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415) 451-24800 Monitored In-Situ Performance of Residential Air-Co onditioning Systems Sponsored By: Arizona Public Service Company

More information

Examination of Performance of Water Mist Fire Suppression Systems under Ventilation Conditions

Examination of Performance of Water Mist Fire Suppression Systems under Ventilation Conditions Examination of Performance of Water Mist Fire Suppression Systems under Ventilation Conditions ZHIGANG LIU,* ANDREW K. KIM AND JOSEPH Z. SU Fire Risk Management, Institute for Research in Construction,

More information

Don t Turn Active Beams Into Expensive Diffusers

Don t Turn Active Beams Into Expensive Diffusers This article was published in ASHRAE Journal, April 2012. Copyright 2012 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be

More information

Chapter 17, Initiating Devices

Chapter 17, Initiating Devices Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.

More information

Smoke Control Design and Activation. CFAA NCA Technical Seminar 2015

Smoke Control Design and Activation. CFAA NCA Technical Seminar 2015 Smoke Control Design and Activation CFAA NCA Technical Seminar 2015 2 Overview Principles of smoke control Codes CACF controls Programming Commissioning Testing Goals To provide an introduction to smoke

More information

Fire Protection as the Underpinning of Good Process Safety Programs

Fire Protection as the Underpinning of Good Process Safety Programs Fire Protection as the Underpinning of Good Process Safety Programs Key Words: fires; protection, fire; building Background James Milke, Ph.D., P.E., Professor and Chair Department of Fire Protection Engineering

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter except as otherwise

More information

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2012 Energy Transfer Based Test Method Development and Evaluation of Horizontal Air

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research

More information

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION Liu Jing 1, Yoshihiro Aizawa 2, Hiroshi Yoshino 3 1 School of Municipal

More information

Characterising the smoke produced from modern materials and evaluating smoke detectors

Characterising the smoke produced from modern materials and evaluating smoke detectors www.bre.co.uk Briefing Paper Characterising the smoke produced from modern materials and evaluating smoke detectors Raman Chagger 01 Contents Abstract 02 Introduction 02 Background 03 The current test

More information

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN , Volume 6, Number 4, p.248-254, 04 RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN C.L. Choi Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Water

More information

Smoke Layer Height and Heat Flow through a Door

Smoke Layer Height and Heat Flow through a Door Smoke Layer Height and Heat Flow through a Door 2017 Smoke Layer Height and Heat Flow through a Door In this tutorial you will simulate a growing fire in the corner of a 5m x 5m room. The room has a 1m

More information

PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES

PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES R. Huo a, Y. Li a, W. Fan a and W. Chow b a. State Key Laboratory of Fire Science, CHINA b. The Hong Kong Polytechnic University

More information

A Monte Carlo Approach for the Design of Thermal Fire Detection System

A Monte Carlo Approach for the Design of Thermal Fire Detection System A Monte Carlo Approach for the Design of Thermal Fire Detection System Walter W. Yuen Department of Mechanical & Environmental Engineering University of California at Santa Barbara California, USA and

More information

An Overview to Designing Smoke-Control Systems

An Overview to Designing Smoke-Control Systems The following article was published in ASHRAE Journal, June, 2002. Copyright 2002 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator 18 R. Saidur et al./journal of Energy & Environment, Vol. 6, May 2007 Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator R. Saidur, M. A. Sattar, M.

More information

CERBERUS: A NEW MODEL TO ESTIMATE SIZE AND SPREAD FOR FIRES IN TUNNELS WITH LONGITUDINAL VENTILATION

CERBERUS: A NEW MODEL TO ESTIMATE SIZE AND SPREAD FOR FIRES IN TUNNELS WITH LONGITUDINAL VENTILATION - 69 - CERBERUS: A NEW MODEL TO ESTIMATE SIZE AND SPREAD FOR FIRES IN TUNNELS WITH LONGITUDINAL VENTILATION R.O. Carvel, A.N. Beard & P.W. Jowitt Department of Civil and Offshore Engineering, Heriot-Watt

More information

Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2

Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2 A CFD Analysis of Smoke Movement in Steel Industry Sheds Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2 Mechanical Dept. Dr.Babasaheb Ambedkar College of Engineering and Research,

More information

Experimental Room Fire Studies with Perforated Suspended Ceiling

Experimental Room Fire Studies with Perforated Suspended Ceiling Experimental Room Fire Studies with Perforated Suspended Ceiling FIONA S.C. TSUI 1, W.K. CHOW 1, N.K. FONG 1, Y. GAO 2, H. DONG 2, and G.W. ZOU 2 1 Research Centre for Fire Engineering Department of Building

More information

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE This article was published in ASHRAE Journal, March 20145 Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

Ventilation Trainer B500

Ventilation Trainer B500 Ventilation Trainer B500 Safe and Suitable For Unsupervised Student Operation. Responds Rapidly to Control Changes. Negligible Operating and Maintenance Costs. Two year Warranty. Page 1 of 5 Introduction

More information

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS Nikola TANASIĆ, Tomislav SIMONOVIĆ, Miloš IVOŠEVIĆ, Branislav

More information

Demand-Controlled Ventilation For Commercial Kitchens

Demand-Controlled Ventilation For Commercial Kitchens Demand-Controlled Ventilation For Commercial Kitchens Tetra Images/Corbis By Derek Schrock, Member ASHRAE; Jimmy Sandusky, Associate Member ASHRAE; Andrey Livchak, Ph.D., Member ASHRAE Food service facilities

More information

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel

Virtual Compartment: An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Virtual : An Alternative Approach to Means of Egress Design in Airport Pedestrian Tunnel Xiaolei Chen, PhD California State University, Los Angeles, United States Ning (Frank) Wang, P.E. Jensen Hughes,

More information

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0593 TESTING, ADJUSTING, AND A. Testing, adjustment, and balancing of air systems. B. Testing, adjustment, and balancing of hydronic, steam, and refrigerating

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

Case Study : Evaluation Smoke & Evacuation Performance of a College Auditorium

Case Study : Evaluation Smoke & Evacuation Performance of a College Auditorium Case Study : Evaluation Smoke & Evacuation Performance of a College Auditorium Ramisetti Sairam Department of Building Technologies &Services, School of Planning and Architecture, JNA&FAU Hyd E-mail :

More information

Effects of Smoke on Evacuation Martin Lopušniak 1, a

Effects of Smoke on Evacuation Martin Lopušniak 1, a Advanced Materials Research Online: 2014-02-27 ISSN: 1662-8985, Vol. 899, pp 539-542 doi:10.4028/www.scientific.net/amr.899.539 2014 Trans Tech Publications, Switzerland Effects of Smoke on Evacuation

More information

A Comparison of Aspirated Smoke Detectors

A Comparison of Aspirated Smoke Detectors A Comparison of Aspirated Smoke Detectors Honeywell FAAST Detectors and Xtralis VESDA VLF (Laserfocus) Conducted by Packer Engineering, Inc And The Fire Testing and Evaluation Center at The University

More information

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION - 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT

More information

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room Y. Momoi 1, K. Sagara 1, T. Yamanaka 1 and H. Kotani 1 1 Osaka University, Graduate School of Eng., Dept.

More information

EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS

EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS PROCEEDINGS, Fire and Evacuation Modeling Technical Conference 211 Baltimore, Maryland, August 15-16, 211 EVACUATION MODELING DEPENDENCE ON INPUT PARAMETERS Brian Salyers, Bevan Jones Holmes Fire 13 Sutter

More information

Brine Generation Study

Brine Generation Study DOE/WIPP 00-2000 Brine Generation Study April 2000 Waste Isolation Pilot Plant Carlsbad, New Mexico Processing and final preparation of this report was performed by the Waste Isolation Pilot Plant Management

More information

Summary of International Road Tunnel Fire Detection Research Project Phase II

Summary of International Road Tunnel Fire Detection Research Project Phase II Summary of International Road Tunnel Fire Detection Research Project Phase II Prepared by: Z. G. Liu, A. Kashef, G. Lougheed, G. Crampton National Research Council of Canada Daniel T. Gottuck Hughes Associates,

More information

Heat pump supplemental heating system for motor vehicles

Heat pump supplemental heating system for motor vehicles 1 Heat pump supplemental heating system for motor vehicles D Antonijevic and R Heckt Visteon Automotive Systems, Visteon Deutschland GmbH, Kerpen, Germany Abstract: The paper deals with the importance

More information

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015 Peter McDonnell, PE, LEED AP BD+C McClure Engineering UL DAMPER TEST STANDARDS UL 555 - FIRE DAMPERS UL555S SMOKE DAMPERS UL555C CEILING

More information

Results from a Full-Scale Smoke Alarm Sensitivity Study

Results from a Full-Scale Smoke Alarm Sensitivity Study Results from a Full-Scale Smoke Alarm Sensitivity Study Thomas Cleary Building and Fire Research Laboratory National Institute of Standards and Technology Gaithersburg, MD (301) 975-6858 thomas.cleary@nist.gov

More information

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom Improvement of Temperatures Stratification caused by Air-conditioner by means of Ceiling Fan in Classroom Natsuka Wakamatsu 1, Yoshihisa Momoi 1, Toshio Yamanaka 1, Kazunobu Sagara 1, Hisashi Kotani 1

More information

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential

More information

Collection of Data on Fire and Collapse, Faculty of Architecture Building, Delft University of Technology

Collection of Data on Fire and Collapse, Faculty of Architecture Building, Delft University of Technology NSF GRANT #0840601 NSF PROGRAM NAME: HMSE & IMEE Collection of Data on Fire and Collapse, Faculty of Architecture Building, Delft University of Technology Brian Meacham Worcester Polytechnic Institute

More information

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems 233100 AIR DISTRIBUTION PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230700 HVAC Insulation B. Section 237300 Air Handling C. Section 230900 Building Automation and Control System Guidelines D. Section

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea 5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea PRACTICAL APPLICATIONS OF FIRE MODELING IN INDUSTRIAL APPLICATIONS By James M. Dewey, Advisor Risk Management

More information

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING M. POIRIER, D. GIGUÈRE, Z. AIDOUN, M. OUZZANE Natural Resources Canada, CANMET Energy Technology Centre-Varennes 1615, Lionel

More information

COURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE

COURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE COURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE 100126 The course is organized into three bands. Band A covers HVACrelated building components and other types

More information