Fire Safety Concept Hotel Jumeirah
|
|
- May McBride
- 6 years ago
- Views:
Transcription
1 Fire Safety Concept Hotel Jumeirah Dr.-Ing. Christoph Klinzmann hhpberlin Ingenieure für Brandschutz Department performance-based methods Office Hamburg
2 Part 2 Fire safety engineering Development of fire protection concept Regulations applied Fire safety engineering
3 Palais Quartier Development of fire safety concept Kick-off for project in 2002 Massimiliano Fuksas and KSP architects International planers Start of consulting with building-authorities and planners Design of basic concept for the entire Palais Quartier as well as single elements Duration of building permission In Germany the authority Bauaufsicht gives buildingauthority approval
4 Design principles in Germany Prescriptive and performancebased design Safety targets defined in building codes Prescriptive design Performance-based design Material requirements according to building codes and guidelines - Fire safety concept - Application of performance-based methods Building codes in Germany are mainly prescriptive performance-based design only for single elements 3/12/2012
5 Palais Quartier Applied regulations Hessische Bauordnung (Building regulations in Hessen) Muster-Hochhausrichtlinie (High-rise building guideline) Verkaufstättenverordnung (Regulation for shopping areas) Versammlungsstättenverordnung (Regulation for places of public assembly) Beherbergungsstättenverordnung (Regulation for accommodation) Garagenverordnung (Regulation for garage)
6 Application of performance-based methods Performance-based methods were used to prove the availability of escape route for necessary time span on the basis of the planned smoke exhaust concept CFD-Simulations of smoke and heat exhausts for open and combined floors in the shopping center, the garage and parts of Thurn & Taxis-Palais Computer-based simulations for the evacuation of the shopping center My Zeil (part of the high rise building) and garage were carried out
7 Fire scenarios Only one fire scenario at the same time in the whole building complex is considered for fire safety and smoke exhaust concept Two simultaneous or immediate scenarios had to be considered in the design of the sprinkler system according to regulations
8 Planned smoke exhaust measures Smoke exhaust in shopping-center MyZeil Mechanical smoke exhaust via shafts to top of the building with a maximum volume flow of m³/h Supply air by windows that open automatically in the façade of shopping center (91 m², max. air speed 1,9 m/s) Simulation via CFD
9 Application of performance-based methods Positions of smoke and heat exhausts and supply air
10 Application of performance-based methods In the simulations it must be proven that the effects of a fire (smoke, heat and radiation) do not have a significant impact on the escape routes Safety targets / performance criteria Limit values for radiation and temperature have to be met A smoke-free layer with a height of 2,5 m has to be proven, usually via visibility or optical density in the height of 2,5 m Visibility on floor with fire and in 4th floor must be >35 m during smoke spread over at least 15 min
11 Application of performance-based methods 3 different fire scenarios were investigated Ground floor, 1 st floor, 1 st Level below ground GF 1st Floor
12 Application of performance-based methods Heat release rate for all fire scenarios Sprinkler
13 Results of simulations Simulation of ground floor: visibility Only in area of fire source visibility was below target criteria Ground floor 4th Floor
14 Results of simulations Simulation of ground floor: visibility Ground floor 4th Floor
15 Results of simulations Simulation of 1st floor: visibility 1st floor after 5 min 4th floor after 5 min
16 Results of simulations Simulation of 1st floor: visibility 1st floor after 15 min 4th floor after 15 min
17 Results of simulations Before the grand opening of the shopping center, the results of simulation have been validated by a smoke test Positive smoke test Video smoke test ground floor
18 Hotel Jumeirah Conclusions The Palais Quartier and the Hotel Jumeirah were introduced In the first part the regulations for high-rise buildings >60 m in Germany and their application in the fire safety concept of the Jumeirah hotel were explained In this part of the presentation the applied regulations and performance-based methods were shown Thank you! Questions?
19 Contact details Ingenieure für Brandschutz GmbH Headquarters Berlin Rotherstraße Berlin Phone: +49 (30) Fax: +49 (30)
Fire Safety Concept Hotel Jumeirah
Fire Safety Concept Hotel Jumeirah Dr.-Ing. Christoph Klinzmann hhpberlin Ingenieure für Brandschutz Department performance-based methods Office Hamburg Part 1 Fire safety concept Palais Quartier and Jumeirah
More informationCHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN
CHANCES AND LIMITS OF THE TIME-EQUIVALENCE-METHOD IN STRUCTURAL FIRE DESIGN ABSTRACT P. Schaumann and S. Hothan University of Hannover, Institute for Steel Construction Appelstraße 9a, D-3167 Hannover,
More informationFire Engineering in High Rise 15 November 2013
Fire Engineering in High Rise 15 November 2013 Neal Butterworth Arup UK www.arup.com Neal.Butterworth@arup.com Contents How do we protect against fire? How do we know this works? Why evacuate? What assumptions
More informationProcedure for the Approval of New Fire Detection and Alarm Technologies
VdS Guidelines for Automatic Fire Detection and Fire Alarm Systems VdS 3469en Procedure for the Approval of New Fire Detection and Alarm Technologies VdS 3469en : 2016-01 (01) Publisher and publishing
More informationSMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN
, Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen
More informationSprinklers Modeling for Tunnel Road Fire Fighting
Sprinklers Modeling for Tunnel Road Fire Fighting P. Ciambelli, M.G. Meo, P. Russo, S. Vaccaro Department of Chemical and Food Engineering, University of Salerno - ITALY 1. INTRODUCTION Loss of lives and
More informationAre we using the wrong design fires for tall building fire strategies, in light of recent full height fires?
Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires? Tall Building Fire Safety Network meeting & seminar FIREX, London, 22 nd June 2016 Eoin O Loughlin
More informationTunnel Fire Dynamics and Evacuation Simulations
Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation
More informationctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title:
ctbuh.org/papers Title: Authors: Subjects: Keywords: Fire Engineering the Tallest Building in the Historic City of Manchester, UK Dean McGrail, Associate Director, WSP Group Simon Lay, Technical Director,
More informationFire safety engineering applied to high-rise building facades
MATEC Web of Conferences 46, 04002 (2016) DOI: 10.1051/matecconf/20164604002 C Owned by the authors, published by EDP Sciences, 2016 Fire safety engineering applied to high-rise building facades Samuele
More informationand Sprinkler System in Resalat Tunnel of Tehran
CFD Simulation of Water Mist and Sprinkler System in Resalat Tunnel of Tehran Motivation Resalat tunnel is the first road tunnel in Tehran one of most crowded tunnels of Tehran my every day route, home
More informationIncreasing Fire Safety of Cologne Main Station by High Pressure Water Mist
Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Background of this Presentation In recent years the
More informationConsiderations in the Design of Smoke Management Systems for Atriums
Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke
More informationREVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS
REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS Nikola TANASIĆ, Tomislav SIMONOVIĆ, Miloš IVOŠEVIĆ, Branislav
More informationSafely Using a Centrifuge Near a Biological Safety Cabinet in Your Cell Culture Laboratory
APPLICATION NOTE Safely Using a Centrifuge Near a Biological Safety Cabinet in Your Cell Culture Laboratory Authors: Marc Dunn, Thermo Fisher Scientific, United Kingdom and John Collings, Thermo Fisher
More informationCHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION
- 165 - CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION Wojciech Węgrzyński, Grzegorz Krajewski, Paweł Sulik Fire Research Department, Building Research Institute (ITB), Poland ABSTRACT
More informationEmergency Ventilation System Design - Preliminary Report Shishir Gupta
Emergency Ventilation System Design - Preliminary Report Shishir Gupta (shishir@mechartes.com), Abstract The existing stations and tunnels of Metro Railway, Kolkata are not equipped with effective emergency
More informationCase Study of Underground Car Park. Team Japan
11th Conference on Performance Based Codes and Fire Safety Design Methods Case Study of Underground Car Park Team Japan We focused on the characteristics of the fire behavior of car fire. Car fire is not
More informationWATER MIST CONVENTION AND EXHIBITION
INTERNATIONAL WATER MIST ASSOCIATION IWMA SEMINARS S ON WATER MIST TECHNOLOGY DUBAI INTERNATIONAL CONVENTION AND EXHIBITION CENTRE Water mist fire protection: The most innovative fire fighting technology
More informationSOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM
- 157 - SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM Kratzmeir S. FOGTEC Fire Protection, Research & Development, Germany Keywords: Fire Protection, Fire suppression,
More informationCOSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN
COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING
More informationProven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist
Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Water Mist for Transformer Fire Protection
More informationCase Study 2 (Production and Storage Buildings) - Spain
Case Study 2 (Production and Storage Buildings) - Spain OBJECTIVE Developed by the SFPE Spanish Chapter Editor: Jimmy Jönsson, JVVA Fire & Risk The objective of this case study is to show how a project
More informationFAÇADE FIRE TESTS Towards a new European standard method
FAÇADE FIRE TESTS Towards a new European standard method Lars Boström November 22, 2017 RISE Research Institutes of Sweden Safety Content Current state in Europe regarding façade fire tests History on
More informationFLACS-Risk Unique 3D risk modelling software. FLACS-Risk: Product presentation FLUG May 2016
FLACS-Risk Unique 3D risk modelling software Outline FLACS-Risk Overview Motivation for developing FLACS-Risk Features of FLACS-Risk v1.0 Development process and timeline Possible future added modules
More informationFire Safety Management
Fire Safety Management Wednesday 20 th June 2018 Russ Timpson www.bcptesting.com 24-storey Grenfell Tower in Kensington, West London June 14, 2017 We shape our buildings, thereafter they shape us Winston
More informationFIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA
93 FIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA INTRODUCTION 94 Legal requirements for the protection of firefighters Requirements of Building Act Fire Prevention Act Technical Guidelines OIB
More informationCase Study 1 Underground Car Park
Case Study 1 Underground Car Park Dorota Brzezińska 1, Janusz Paliszek 2, Piotr Smardz 2, Renata Ollesz 1, Karol Kaczor 2 1 Lodz University of Technology, GRID - Lodz, 2 INBEPO Wroclaw, Poland Building
More informationFire Scenarios Assessment
Fire Scenarios Assessment Kristian Börger 1 and Gregor Jäger 1 1 BFT Cognos GmbH, Aachen, Germany Abstract DIN 18009 Part 1 describes the fundamentals of the system for the selection of design fire scenarios.
More informationCOST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS
, Volume 1, Number 3, p.123-128, 1999 COST-EFFECTIVE FIRE-SAFETY RETROFITS FOR CANADIAN GOVERNMENT OFFICE BUILDINGS D. Yung and G.V. Hadjisophocleous Fire Risk Management Program, Institute for Research
More informationHow to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs
How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada
More informationInternational Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.
International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.800(19) Magnus Arvidson SP Fire Research SP Technical Research Institute
More informationDevelopment of a European approach to assess the fire performance of facades
Development of a European approach to assess the fire performance of facades This presentation was made in Brussels on December 8, 2017, for EC, AGF and stakeholders Lars Boström, Roman Chiva, Anja Hofmann-Böllinghaus,
More informationAnimals:Goats:Bleat.Calls,Warbling.Baa,Movements.Rubbing,Barn,Medium.Close,Interior,BG.Dog.Barks 01:21.618
Description Duration Animals:Goats:Bleat.Calls,Warbling.Baa,Movements.Rubbing,Barn,Medium.Close,Interior,BG.Dog.Barks 01:21.618 Animals:Goats:Herd,Bleat.Calls,Intensity.Increase,Warbling,Baby.Baa,Movements.Rubbing,Barn,Occasional.Dog.Barks,Medium.Close,Interior,BG.Crows.Squawks
More informationHIGH PRESSURE WATER MIST SYSTEM Application: High Rise Building Bindreiter Michael London,
HIGH PRESSURE WATER MIST SYSTEM Application: High Rise Building Bindreiter Michael London, 2018-09-19 1 Application High Rise Building Hotel & Apartment Office & Walkways Shopping mall & Lobbies Parking
More informationImpact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams
Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams Risto Kosonen 1, Arsen Melikov 2, Boryana Yordanova 2 and Lyuben Bozkhov 2 1 Halton Oy 2 International
More informationCalculation. Danish Concrete Institution DIFLAGER DIFT. Industry, plastics Concrete :51:00 13
Calculation Basic information Client: Scenario name: Consultant: Reference no.: Company type: Basic bldg. construction: Last revision: Revision No.: Danish Concrete Institution DIFLAGER DIFT Industry,
More informationApplication of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia
Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia A Challenging Application for the New Italian Fire Code
More informationNUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM
, Volume 11, Number 2, p.43-48, 2012 NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM Q. Kui Institute of Building Fire Research, China Academy of Building Research, Beijing,
More informationThird Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG
1 Third Runway Project APM Depot Fire Engineering Design Presented by Ir Wilson Sau-kit TSANG 1 2 Presentation Overview 1. Project Background and Depot Overview 2. Building Information and Challenge for
More informationJANSEN BRANDSCHUTZ. Special solutions - Protection without limits
JANSEN BRANDSCHUTZ Special solutions - Protection without limits Recess shutters Special sizes Corner fire protection Fire protection via semi-circular lifting door JANSEN BRANDSCHUTZ Special solutions
More informationSTATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT
STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device
More informationY. ORMIERES. Fire risk analysis method for nuclear installations
Y. ORMIERES Fire risk analysis method for nuclear installations 2 Fire risk analysis method for nuclear installations A position on the management of fire safety analysis in nuclear installations by specifying:
More informationThe Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD
The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD BFS 2011:27 with amendments up to BFS 2013:12 The
More informationOptimized fan system design for the one-year cycle of a Heat Pump. Ziehl-Abegg SE Frieder Lörcher
Optimized fan system design for the one-year cycle of a Heat Pump Ziehl-Abegg SE Frieder Lörcher Outline Targets for the energetical optimization of fan unit Numerical optimization procedure Results with
More informationFIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING. Fabio Mazza June 2016
FIRE PROTECTION AND SAFETY ANALYSIS FOR AN OFFICE HIGH RISE BUILDING Fabio Mazza June 2016 Introduction Codes & Standards Building description Performance based design Prescriptive based design Structural
More informationNarrative Reports As Regulated by 780 CMR, Section 903.0
EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for
More informationAspirating Gas Detection CFD Modelling Predicts Application Performance
Aspirating Gas Detection CFD Modelling Predicts Application Performance Yun Jiang Xtralis, Bentleigh East, Australia Claudio Groppetti Xtralis, Avon, MA, USA Abstract Historically gas detection has utilized
More informationSCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /
SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL 60202 fpeschulte@aol.com 504/220-7475 A CRITIQUE OF HUGHES ASSOCIATES, INC. PAPER TITLED: Analysis of the Performance of Ganged
More informationFIRE SAFETY LOG BOOK
FIRE SAFETY LOG BOOK Regulatory Reform (Fire Safety) Order 2005 If you own, manage or operate a business, you will need to comply with fire safety law. The main law is the Regulatory Reform (Fire Safety)
More informationFire Safety in Tall Building: Performance-Based Solutions. Chris Jelenewicz, P.E., FSFPE
Fire Safety in Tall Building: Performance-Based Solutions Chris Jelenewicz, P.E., FSFPE Kingdom Tower -- Jeddah Central Park Tower Philadelphia, PA One Meridian Plaza February 23, 1991 SFPE/ICC Guide
More informationOpen to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP
Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com
More informationSTUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED
- 133 - STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED Y. Mikame 1,2, N. Kawabata 1, M. Seike 1, M. Hasegawa 1 1 Kanazawa University, Japan 2 Metropolitan Expressway Company
More informationFIRE RESISTANCE OF ROLLING STOCK ELEMENTS STANDARD AND SPECIAL CASE OF TUNNELS
FIRE RESISTANCE OF ROLLING STOCK ELEMENTS 45545-3 STANDARD AND SPECIAL CASE OF TUNNELS www.efectis.com May 2016 1 SUMMARY EN 45545-3 What is a fire barrier? Requirements regarding fire resistance Tests
More informationRecent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications
Recent Advances in Fire Suppression Modeling Issues & Perspectives of Fire Safety Engineering Applications Pianet Grégoire Studies and modelling section manager Fire and Environmental Department, CNPP
More informationSmoke Control Design and Activation. CFAA NCA Technical Seminar 2015
Smoke Control Design and Activation CFAA NCA Technical Seminar 2015 2 Overview Principles of smoke control Codes CACF controls Programming Commissioning Testing Goals To provide an introduction to smoke
More informationComputer Simulation Investigation on the Effect of Channelled and Unchannelled Screens on Smoke Contamination in Atriums Upper Balconies
MATEC Web of Conferences 13, 27 (214) DOI: 1.151/ matecconf/ 21413 27 C Owned by the authors, published by EDP Sciences, 214 Computer Simulation Investigation on the Effect of Channelled and Unchannelled
More informationTechnical Presentation on
Technical Presentation on PID _00012345 Heating and refrigeration system using waste heat energy Photo (Author 1) Photo (Author 2) Author 1 Name Author 2 Name Restricted Circulation L&T Technology Services
More informationBR-BO Adopted June 1, Evacuation Safety Performance Evaluation Manual
BR-BO-07-01 Adopted June 1, 2000 Evacuation Safety Performance Evaluation Manual Article 1: Scope of Application This manual applies to the following types of performance evaluations: (1) Performance evaluations
More informationDate: Place: Technical University of Denmark. Knowledge FOr Resilient society
Date: 27-06-2017 Place: Technical University of Denmark Knowledge FOr Resilient society 11B25 Smoke and temperature ACTION 11B04 11B12 fire development 11B01 Evacuation human behaviour building response
More informationIQ8Quad. The right sensor for every environment. The detection principles of the IQ8Quad detector. Fire detection technology
IQ8Quad The right sensor for every environment The detection principles of the IQ8Quad detector Fire detection technology 02 03 The right choice is decisive No two fires are alike. The course and velocity
More informationSHEVTEC Extended Travel Distance. System for Chettles Yard, Nottingham
Case Study SHEVTEC Extended Travel Distance System for Chettles Yard, Nottingham Name: Chettles Yard, Nottingham Background: Chettles Yard student accommodation is a typical example of modern high specification
More informationInteraction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS)
Fire Protection Leaflet Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS) 0 General Regulations and recommendations missing from this leaflet do not entitle
More informationSmoke control in car parks
Smoke control in car parks The actual situation in CEN TC 191 SC1 WG9 Imagine the result Jean-Claude DE SMEDT MIFireE,MSFPE,MNFPA Senior Fire Safety Engineering Consultant @ ARCADIS Belgium Convener of
More informationResidential ventilation concepts based on the idea of displacement airflow distribution
A strategy for reducing energy demand Student: Aris Gkitzias (I.D:4180380) Mentors: Dr. Regina Bokel, Ir. John van der Vliet MSc graduation project Department of Building Technology, faculty of architecture
More informationD-GF 150. Burner Control for Gas and Oil Burners Flame Sensor D-GF 150 D-LE 103
pending pending Controlling and Monitoring of Gas, Oil and Combined Burners of any Capacity Integrated Gas Valve Proving System Separated Outputs for Gas- and Oil Fuel Valves Quick Fuel Change on the fly
More informationCOMPLEX COMMISSIONING AND QUANTITATIVE TESTING GOTTHARD BASE TUNNEL VENTILATION SYSTEM
COMPLEX COMMISSIONING AND QUANTITATIVE TESTING GOTTHARD BASE TUNNEL VENTILATION SYSTEM 8 th International Conference Tunnel Safety & Ventilation 2016 Martin Viertel OVERVIEW Gotthard Base Tunnel Ventilation
More informationEPSRC Research Project: Real Fires for the Safe Design of Tall Buildings
EPSRC Research Project: Real Fires for the Safe Design of Tall Buildings Prof Luke Bisby, Acting Director BRE Centre for Fire Safety Engineering Arup Chair of Fire and Structures BRE Centre for Fire Safety
More information22 BISHOPSGATE Lift Evacuation Strategy
June 28, 2018 22 BISHOPSGATE Lift Evacuation Strategy Romain Hourqueig, Head of UK Fire Engineering Neil Allardice, Senior Fire Engineer AGENDA The project Fire Safety Strategy Why lift evacuation? The
More informationGeneral Principles of Smoke Control
AMCA International General Principles of Smoke Control Patrick Janssens, Sales Manager Colt International www.coltinco.co.uk or www.coltinfo.be Air System Engineering & Technology (ASET) Conference Europe
More informationSolutions for airports and railway stations
Solutions for airports and railway stations Solutions for airports and railway stations Airports and railway stations aren t just places where countless people pass through every day. They also provide
More informationOverview. Executive Summary. Solution Description CHAPTER
CHAPTER 1 Executive Summary In large and complex urban environments, it is critical for decision makers to reduce the time from detection of an incident to response by first responders. Additionally, it
More informationOverview of the PRISME project Technical Description and Main Outcomes
OECD PRISME Project on Fire Propagation Final Seminar Overview of the PRISME project Technical Description and Main Outcomes Audouin L., Rigollet L., Pretrel H., Le Saux W. IRSN / ETIC Summary (1) Context
More informationDesign of Fire safety in Multi Occupancy Residential Accommodation
Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability
More informationCase Study 2 Production and Storage. SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB)
Case Study 2 Production and Storage SFPE Polish Chapter Wojciech Węgrzyński, Grzegorz Krajewski Building Research Institute (ITB) So What Are You We Going to Show You? A lot of tables, simplified methods
More informationHealthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland
Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0141 ISBN: 978-83-7947-232-1 Prediction of exhaust gas stagnation in common corridor of apartments with gas water heater Takuro Nakamura
More informationFixed fire protection solutions
Risk Engineering Fixed fire protection solutions At a glance Fixed fire protection can reduce the severity of fire events and positively impact Risk Engineering Assessments. To provide an effective solution
More informationSIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS
SIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS Dr. Arnd Rogner Metaphysics SA 1 Contents Actual detection technologies (in Europe) Field experience in tunnel fire detection System integration 2 Road
More informationHigh-pressure water mist systems and fire testing. Max Lakkonen IFAB Institute for Applied Fire Safety Research
High-pressure water mist systems and fire testing Max Lakkonen IFAB Institute for Applied Fire Safety Research Content of presentation IFAB Company Application fields Services High-pressure water mist
More informationCOMPETENCE. Lead Fire Warden. Standard Title Lead Fire Warden Competence Assessment Standard Lead Fire Warden Competence Assessment Standard
Lead Fire Warden COMPETENCE CRO EMERGENCY RESPONSE COMPETENCE ASSESMENT Standard Title Code Lead Fire Warden Competence Assessment Standard 4502 Revision 0 (28th October 2016) Page 1 of 29 OPITO STANDARDS
More informationAll the security you need in one housing
IQ8Quad All the security you need in one housing IQ8Quad: The highlight of every fire detection scenario Fire detection technology 02 03 Safety is the result of efficiency and innovation This applies to
More informationGAS DETECTOR LOCATION. Ø.Strøm and J.R. Bakke, GexCon AS, Norway
AUTHOR BIOGRAPHICAL NOTES GAS DETECTOR LOCATION Ø.Strøm and J.R. Bakke, GexCon AS, Norway Øyvind Strøm graduated in 1996 from Stavanger University College with a M.Sc. degree in Offshore Safety Technology.
More information3. Managing smoke: Our strategies and opportunities
3. Managing smoke: Our strategies and opportunities Dr. Zifei Liu zifeiliu@ksu.edu Pasture burning smoke management and air quality workshop March 28 th, 2015 Engineering Two strategies for reduction Minimize
More informationFire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel
Safety and Security Engineering VI 73 Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel M. Lombardi & G. Rossi Dipartimento di Ingegneria Chimica
More informationOur service. Your protection. Safety: Even when things are on fire.
Our service. Your protection. Safety: Even when things are on fire. This is what sets our company apart: many years of experience and the certificate of Trust through Security (VdS) as a recognised installer
More informationIndicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number
Indicative hoarding fire experiment Prepared for: London Fire Brigade 21 May 2014 Client report number 292366 1 Hoarding fire demonstration Prepared on behalf of BRE Fire and Security by Name Dr Sung-Han
More informationIn recent years the Hungarian Fire Protection Regulation has changed much more frequently and in greater extent than in previous years.
In recent years the Hungarian Fire Protection Regulation has changed much more frequently and in greater extent than in previous years. National Fire Protection Regulations (NFR) is the"bible" of fire
More informationFire Protection for Printing Machines with High Pressure Water Mist
Fire Protection for Printing Machines with High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Case Study PRINOVIS Printing Company - PRINOVIS is Europe s
More informationVoice Alarm Systems. Inform Selectively, Evacuate Safely Complete systems for voice alarm and fire detection technology
Voice Alarm Systems Inform Selectively, Evacuate Safely Complete systems for voice alarm and fire detection technology A New Dimension of Voice Alarm For use everywhere: The new voice alarm systems from
More informationSelecting appropriate egress strategies
Selecting appropriate egress strategies The selection of an appropriate egress strategy requires a good understing of the building its occupants, the protection measures in place, the expected emergency
More informationSaving lives with coatings
Saving lives with coatings The essentials of passive fire protection. Paul Mather. Passive fire protection by means of intumescent, cementitious or ceramifying coatings or layers has gained importance
More informationSignificance of the Construction Products Regulation, including for data centers WHITEPAPER
Significance of the Construction Products Regulation, WHITEPAPER The aim of the Construction Products Regulation is to protect people in buildings against the consequences of a fire. The priorities in
More informationNumerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand
Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand Mohammed Mutafi 1, Mohammad Nasif 1*, William Pao 1 and
More informationNUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT. PO Box 522, Belgrade, Serbia and Montenegro
Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 NUMERICAL SIMULATION OF FIRE SPREAD IN TERMINAL 2 OF BELGRADE AIRPORT Z. Stevanovic 1, T. Valentina 1, N. Kadic 1, Z. Markovic 1,
More information1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c
1.0 INTRODUCTION This report presents the results of a fire performance evaluation in accordance with the 2011 Edition of National Fire Protection Association (NFPA) Standard 265, Standard Methods of Fire
More informationfulfils all requirements for extended protection of the criteria catalogue The appendix is part of the certificate and consists of 4 pages.
The certification body of TÜV Informationstechnik GmbH hereby awards this certificate to the company Beiersdorf Shared Services GmbH Quickbornstraße 24 20253 Hamburg, Germany to confirm that its security
More informationfire resistant cables
Building Technology fire resistant cables Special electrical and optical cables www.tecnikabel.com Special electrical and optical cables 2 INTRODUCTION Structured cabling solutions. Tecnikabel can provide
More informationRecent BRANZFIRE enhancements and validation
Recent BRANZFIRE enhancements and validation Michael Spearpoint University of Canterbury Summary BRANZFIRE is a multi-compartment fire zone model that has been under development since 1996 predominately
More informationNew developments in Nordic countries in fire safety engineering guidance
New developments in Nordic countries in fire safety engineering guidance Vidar Stenstad Senior Engineer National Office of Building Technology and Administration, Norway Madrid, del 23 al 25 de febrero
More informationAmerican Society of Heating, Refrigerating and Air-Conditioning Engineers
Flow Pattern and Thermal Comfort in Office Environment with Active Chilled Beams Journal: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Manuscript ID: Draft Publication:
More information