Metasys Integrator Liebert Application

Size: px
Start display at page:

Download "Metasys Integrator Liebert Application"

Transcription

1 Application Note Issue Date May, 00 Metasys Integrator Liebert Application lntroduction Application Details Component Requirements 0 Vendor Contact Information Design Considerations Cable Connections Cable Pinouts Connecting to SiteLink/NIC Modules Connecting the Cable Metasys Integrator Unit Setup Point Mapping Tables Deluxe System/ (MCCI Configuration) Small Systems Controller (MCCI Configuration) Liebert ECA Level 0 Liebert ECA Level 0 and Level 0 Liebert DCLAN Environmental Unit Level 0 and Level 0 with On/Off Control (L00, L0A, and LSM) Liebert DCLAN Environmental Unit Small Systems Control (L0B) Liebert DCLAN Environmental Unit Level,, 0, and (L0, L0, L0, LA, and LAM) Liebert DCLAN Chiller - CW, CW, and CW Liebert DCLAN Chiller with Econocoil - CE, CE, and CE Liebert DCLAN Power Conditioning Unit Liebert DCLAN UPS Series 00 and 00 Liebert DCLAN Series 00 Static Control Cabinet (SCC) Liebert DCLAN Contact Closure Module (CCM) Liebert SiteLink/NIC CCM Function Block 0 00 Johnson Controls, Inc. Code No. LIT-0

2 Liebert SiteLink/NIC CSE Function Block Liebert SiteLink/NIC CSU Function Block Liebert SiteLink/NIC EDS Function Block Liebert SiteLink/NIC L00 Function Block Liebert SiteLink/NIC L0B Function Block Liebert SiteLink/NIC L0 Function Block Liebert SiteLink/NIC LAM and MM Function Blocks Liebert SiteLink/NIC LSM Function Block Liebert SiteLink/NIC MM Function Block Liebert SiteLink/NIC MMS Function Block Liebert SiteLink/NIC NPower IMP Function Block Liebert SiteLink/NIC PMP Function Block Liebert SiteLink/NIC RAC Function Block Liebert SiteLink/NIC SC Function Block Liebert SiteLink/NIC SCC Function Block Liebert SiteLink/NIC SM Function Block Liebert SiteLink/NIC SM Function Block Liebert SiteLink/NIC SMS Function Block Liebert SiteLink/NIC THM Function Block Liebert SiteLink/NIC VCF Function Block Liebert SiteLink/NIC VCM Function Block Liebert SiteLink/NIC WDU Function Block Metasys Network Setup 0 Mapping to a CS Object 0 Custom Integration Metasys Integrator Liebert Application Application Note

3 lntroduction Application Details This document explains Metasys Integrator Liebert applications. Use this document with the Metasys Integrator unit technical bulletins on the Johnson Controls Product Information site ( System Manuals > Integration > Metasys Integrator), which provide information on installing and commissioning the Metasys Integrator unit. For information on Liebert equipment, see Liebert documentation (obtainable from a Liebert representative). Note: If you are using a Universal Packaging Module (UPM) enclosure, you must install the Metasys Integrator unit 00 Series in a two high enclosure (EN-EWC-0) rather than a one high enclosure (EN-EWC-0) as shown in the figures for this application note. The Metasys Integrator unit allows Liebert equipment to become an integral part of the Metasys and Metasys Companion Networks. After a Liebert Multi-Channel Communications Interface (MCCI), Environmental Communication Adapter (ECA), DCLAN BMS, SiteLink Module, or Open Comms Network Interface Card (NIC) is connected to a Metasys or Companion Network via the Metasys Integrator unit, each of its Information Gathering Modules (IGMs) has access to the full complement of Metasys Building Automation System (BAS) features, including Change-of-State (COS) monitoring, alarm notification, trend, and totalization. IGMs maintain Liebert environmental systems to provide precise control of temperature, humidity, filtration, and distribution for heat generating equipment. The Metasys Integrator unit supports applications for many, but not all, SiteLink function blocks. With a Liebert SiteLink module configured for Modbus RTU protocol and downloaded with the appropriate SiteLink function block, the Metasys Integrator unit can communicate with most Liebert products. Liebert equipment equipped with a Liebert OpenComms Network Interface Card use the SiteLink vendor tables. IMPORTANT: For a complete list of products, controllers, and function blocks, see the Liebert Web site ( Metasys Integrator Liebert Application Application Note

4 You must verify that the product you want to integrate uses a function block that is listed in this document. Table lists examples of products that are supported by the Metasys Integrator unit. Table : Liebert SiteLink Products Supported by Metasys Integrator Unit Product Names Controller Name or Identification Environmental Products CSU000 CSU000 with Econocoil Chiller Deluxe System Level 0 Chiller with Econocoil Levels, 0 Challenger Level 0 Challenger 000 DataMate Industrial Cooling Series Levels, Advanced Microprocessor, Advanced with Graphics Levels 0 with On/Off Control, and Standard Microprocessor Standard Microprocessor Advanced Microprocessor, Advanced with Graphics Small System Controller Standard Microprocessor, Advanced Microprocessor Level 0 Logicool Level 0 Mini-Mate Mini-Mate Mini-Mate Plus Small System Controller MM Modular Plus Level Small System Controller Level 0 Liebert Monitoring Modules LDS0 and LDS000 Water Detection LDS0 and LDS000 RAC- Autochangeover CCM00 Contact Closure Module VSM00 age Sensing Module CSM00 Current Sensing Module Temperature/Humidity Module RCM Contact Closure Module Continued on next page... RAC- CCM00 VSM00 CSM00 THM00 RCM Metasys Integrator Liebert Application Application Note

5 Product Names (Cont.) Controller Name or Identification Power Products Static Transfer Switch PDU Single Output Breaker, Prior to / Datawave Precision Power Center MPU000 AP0/0 Single Module UPS Early Series 00/00/00 Single Module UPS Early Series 00/00 System Control Cabinet Early Series 00/00 Multi-Module UPS Series 00 Single Module UPS with Extended Protocol Series 00 Multi-Module UPS with Extended Protocol Series 00 System Control Cabinet with Extended Protocol Npower Single Module UPS Power Monitoring Panel age Current Frequency Monitoring Panel Power Monitoring Panel age Current Monitoring Panel age Current Frequency Monitoring Panel SM SMS SCC MMS SM MM SC IMP Metasys Integrator Liebert Application Application Note

6 With the Liebert MCCI, the Metasys Integrator unit supports seven Liebert IGMs: Deluxe System /Level 0 Deluxe System /Level Deluxe System /Level Deluxe System /Level Deluxe System /Level 0 Deluxe System /Level Small Systems Controller (SSC) With the Liebert ECA, the Metasys Integrator unit supports three IGMs: Deluxe System /Level 0 Deluxe System /Level 0 Deluxe System /Level With Liebert DCLAN, the Metasys Integrator unit communicates with the following devices: Environmental Unit Level 0 and Level 0 with On/Off Control (L00, L0A, and LSM) Environmental Unit Small Systems Control (L0B) Environmental Unit Level,, 0, and (L0, L0, L0, LA, and LAM) Chiller (CW, CW, and CW) Power Conditioning Unit Type PMP with IGM, VCMP with IGM UPS Series 00* and 00-Type Single Module System (SMS), Multi Module System (MMS), and Static Control Cabinet (SCC) Contact Closure Module (CCM) Chiller with Econocoil (CE, CE, and CE) *Series 00 with optional SiteScan Interface Card. The MCCI or ECA connects to the Metasys Integrator unit through the RS- Bus. Once connected, it is the interface between Liebert equipment and non Liebert devices (such as the Metasys Integrator unit). The Metasys Integrator unit allows status information and commands to be transmitted between the Liebert devices and the Metasys or Companion Network. Each Metasys Integrator vendor port can connect to one MCCI or ECA. Each MCCI can connect up to Liebert IGMs on individual RS- lines. Each ECA can connect to two Liebert IGMs on two individual RS- lines. Metasys Integrator Liebert Application Application Note

7 The Liebert DC00 can be used in place of the MCCI. The DC00 must be configured to use the MCCI protocol on Port, using SS software Version.0B or later. (The DC00 and MCCI are no longer available from Liebert.) The DCLAN BMS protocol can be used as an interface to monitor and control Environmental Units, chillers, power conditioning units, Uninterruptible Power Supplies (UPSs), and Contact Closure Modules. Liebert SiteLink modules provide a communication link between third-party Modbus devices and Liebert manufactured devices. The Liebert SiteLink-DCi module has ports. Each port may be connected to a Liebert device. A SiteLink-DCi module has ports. The OpenComms Network Interface Card has one port and is connected to one Liebert device. The SiteLink module (via downloaded Function Blocks) polls each device connected to it and stores the information in registers that a Modbus device can access. SiteLink modules can also be configured to communicate via DCLAN BMS protocol. Liebert OpenComms Network Interface Cards communicate with Modbus devices via their third-party interface port (-wire RS-). This port is connected via an RS- converter to a vendor port on the Metasys Integrator unit. Modbus RTU protocol (00, N,, standard) is used for communication with the OpenComms NIC. Figure shows a Metasys Network with the Metasys Integrator unit connected to one MCCI in a star configuration. Figure shows a Metasys Network with a Metasys Integrator unit connected to one DCLAN BMS, which can be connected to control modules such as DC- and DC-. For more information about DCLAN configurations, see Configuration Guide-Intermediate by Liebert Corporation. Figure and Figure show Metasys Companion and Liebert integration. Metasys Integrator Liebert Application Application Note

8 Deluxe System/ Deluxe System/ Deluxe System/ Del ux e Sys tem/ Del ux e Sys tem/ N LAN Standard NCU Metasys Integrator RS- (0 ft maximum) MCCI with RS- Ports RS- (Belden Cable 0 ft maximum) UNT N Bus Deluxe System/ Small System Controller liebert Note: If you use a UPM enclosure, you must install the Metasys Integrator unit 00 Series in a two high enclosure (EN-EWC-0) rather than a one high enclosure (EN-EWC-0) as shown in the figures for this application note. Figure : Liebert and Metasys System Integration NCM00 RS- (0 ft maximum) Liebert SiteLink DCI (or DCI) : : Liebert Device Liebert Device : : Liebert Device UNT N Bus Metasys Integrator (0 ft maximum) RS- DCLAN Liebert Liebert DC, DC, DCi, or DCi Note: liebert If you use a UPM enclosure, you must install the Metasys Integrator unit 00 Series in a two high enclosure (EN-EWC-0) rather than a one high enclosure (EN-EWC-0) as shown in the figures in this application note. Figure : Liebert DCLAN BMS and Metasys System Integration Metasys Integrator Liebert Application Application Note

9 um p um p Deluxe System/ Del ux e Sys tem/ Deluxe System/ Deluxe System/ Deluxe System/ Deluxe System/ Deluxe System/ Panel Unit Workstation RS- (0 ft maximum) Metasys Integrator MCCI with RS- Ports RS- (Belden Cable 0 ft maximum) Note: UNT N Bus Deluxe System/ Note: A PC version and converter may be substituted for the Panel unit. If you use a UPM enclosure, you must install the Metasys Integrator unit 00 Series in a two high enclosure (EN-EWC-0) rather than a one high enclosure (EN-EWC-0) as shown in the figures in this application note. Small System Controller Figure : Liebert MCCI and Metasys Companion Integration liebcomp Panel Unit Workstation RS- (0 ft maximum) ECA Metasys Integrator RS- (Belden Cable 0 ft maximum) UNT N Bus Deluxe System/ Note: A PC version and converter may be substituted for the Panel unit. liebcom Note: If you use a UPM enclosure, you must install the Metasys Integrator unit 00 Series in a two high enclosure (EN-EWC-0) rather than a one high enclosure (EN-EWC-0) as shown in the figures in this application note. Figure : Liebert ECA and Metasys Companion Integration Metasys Integrator Liebert Application Application Note

10 Component To integrate Liebert equipment, you need the following components: Requirements properly installed Liebert devices RS- cable (for connecting the MCCI, ECA, DCLAN, or SiteLink module to the Metasys Integrator unit) Note: If connecting a single Metasys Integrator unit to multiple SiteLink modules via the Modbus RTU protocol interface (that is standalone SiteLink modules that are not part of a DCLAN Network), additional RS- cables, RS- cables, and RS-/ converters are needed. See Cable Connections in this document for more information. Connection to one or more OpenComms Network Interface Cards also require a RS-/ Converter. Metasys Integrator unit N Bus (for connecting the Metasys Integrator unit to the Metasys or Companion Network) portable Personal Computer (PC) for downloading vendor communication tables (.VCT files) and network setup information into the Metasys Integrator unit and for running diagnostics cable for connecting portable PC to the Metasys Integrator unit the correct vendor communication table (.VCT file) to download into the Metasys Integrator unit (supplied on Metasys Integrator CD-ROM) This document describes the RS- cable and the vendor communication tables. Liebert documentation describes its equipment. The remaining components are described in the Metasys Integrator unit technical on the Johnson Controls Product Information site ( System Manuals > Integration > Metasys Integrator). Metasys Release Requirements Metasys Companion Release Requirements To integrate Liebert equipment into the Metasys Network, you need: Metasys Operator Workstation (OWS) software Release.0 or later Metasys Integrator unit software/firmware Release. or later To integrate Liebert equipment into the Metasys Companion Network, you need: Metasys Companion Release.0 or later Metasys Integrator unit software/firmware Release. or later 0 Metasys Integrator Liebert Application Application Note

11 Vendor Component Requirements Integration between the Metasys Integrator unit and Liebert has been tested with the equipment listed in Table. Changes to this equipment or integration of Liebert products not discussed in this document requires additional software development and testing by Systems Products. For information on integrating other products, refer to the Custom Integration section of this document. Table : Liebert Part and Software Version Numbers Liebert Product Part Number Firmware Version Number Multi-Channel Communications Interface G Revision.0 DC00 DC00BMS MCCI Card, Revision.0 Deluxe System /Level 0 N/A** Lev0 or Lev0A Deluxe System /Level * N/A** Lev Deluxe System /Level N/A** Lev or LevA Deluxe System /Level N/A** Lev or LevA Deluxe System /Level 0 N/A** Lev or LevA Deluxe System /Level N/A** LevA Single Module NPower UPS N/A*** N/A Small Systems Controller N/A** Lev0B Environmental Communication Adapter (ECA) DCLAN BMS Data Concentrator for Local Area Network (LAN) D0G DCLAN BMS Revision.0 DC IGM Interface Module DC -- DC- IGM Interface Module DC- N/A DC- IGM Interface Module DC- N/A SiteLink DCi- IGM Interface Module SiteLink DCi- IGM Interface Module OpenComms Network Interface Card SiteLink-DCi SiteLink-DCi OpenComms NIC N/A N/A N/A REPOPT RS-/ Converter REPOPT N/A * The System /Level IGM requires a Liebert Retrofit Kit with a Liebert Protocol Converter (Part Number KIT-00). ** Part number varies according to the system in which the System/ controller is mounted. *** Requires an OpenComms NIC or SiteScan Optional Module. Metasys Integrator Liebert Application Application Note

12 DCLAN The DCLAN BMS database is factory configured by Liebert. Only databases configured by a Liebert factory are supported. Obtain the following information from the Liebert representative: the address of each DCLAN BMS, which is configured with units to be monitored by the Metasys Integrator unit the DCLAN BMS database address of each unit, which includes the unit type (for example: DCLAN BMS Addresses 0 and 0 configured for an environmental unit type LAM) Note: Every CMnet device uses two sequential DCLAN addresses. Liebert supports a maximum of fifty devices per DCLAN BMS. To use SiteLink modules within a DCLAN system, the Liebert representative must configure SiteLink modules for DCLAN communication. DCLAN DC and DC drivers must be Version. or later. SiteLink/OpenComms NIC The Liebert representative must supply a Liebert Site Survey, which indicates which function blocks (for example, L00, PMP, EDS, etc.) are involved in the integration. The function blocks correspond to the three-character acronym associated with the name of each Metasys Integrator unit application for Liebert SiteLink. To communicate directly to SiteLink/NIC modules, the Liebert representative must configure each SiteLink/NIC module to communicate via Modbus RTU protocol. The representative must also supply the Modbus address and port numbers for each Liebert device. Vendor Contact Information Liebert P.O. Box 00 Dearborn Drive Columbus, OH 0 Site Application Engineering: Phone: 00-- Metasys Integrator Liebert Application Application Note

13 Design When integrating Liebert equipment, consider the following: Considerations Make sure all Liebert equipment is set up, started, and running properly before attempting to integrate with the Metasys or Companion Network. (The Liebert representative is responsible for operation of Liebert equipment.) MCCI/ECA If an environmental unit is commanded off at the local controller, it cannot be turned on remotely. The MCCI/ECA baud rate is fixed at 00 baud. The RS- port jumper settings on the MCCI should be set to DCE. (The Liebert representative is responsible for setting jumper settings on the MCCI.) Note: The DCE jumper pins are on the lower MCCI board and are labeled DTE/DCE. Cable distance between the master MCCI or ECA and the last IGM can be a maximum of 0 feet. (The Liebert representative is responsible for proper configuration of Liebert equipment.) Set the DIP switches on SW of the ECA as follows: =On, =On, =Off, =On, (not used), =Off, =Off, =Off. Set SW on the ECA to Terminal. DCLAN Liebert representatives must configure the DCLAN Network correctly. The DCLAN BMS must be configured so that echo is off. The default baud rate for the Metasys Integrator unit connection to a DCLAN Network is 00 baud. SiteLink Module/ OpenComms NIC Liebert representatives must configure each SiteLink/NIC module correctly. If the SiteLink module is directly connected to the Metasys Integrator unit, it must be downloaded with the function blocks and module drivers configured for Modbus. If connected to a DCLAN, it must be downloaded with the function blocks and module drivers configured for DCLAN. OpenComms NIC modules must be configured for Modbus RTU communication and a unique Modbus Slave Address assigned. The default baud rate for the Metasys Integrator unit connection to a SiteLink/NIC module is 00 baud. The SiteLink module can also be configured for 00 baud. If the SiteLink module supports automatic alarm reset, the auto-restore timer must be set as shown in Table to ensure all hardware-latched alarms are reported. Metasys Integrator Liebert Application Application Note

14 Table : SiteLink Auto-Restore Timer Settings Number of SiteLink Modules Connected to One Metasys Integrator Port Number of Minutes Needed for SiteLink Configuration Number of Minutes Needed for DCLAN Configuration to to 0* * We do not recommend more than 0 modules be connected to one port because of performance considerations. The Liebert representative is responsible for configuring the SiteLink module for setpoints and unit on/off control. If a SiteScan system is connected to the SiteLink module along with the Metasys Integrator unit, only one system is allowed to update setpoints (Analog Outputs [s]) and the unit on/off control. Metasys Integrator Liebert Application Application Note

15 Cable Connections Cable Pinouts MCCI Use the following cable pinouts for the RS- connection between the Metasys Integrator unit and the Liebert MCCI: Vendor Port A or B on Metasys Integrator RS- Port MCCI (set to DCE) DB- Female DB- Male Signal RD TD DTR GND RTS CTS Pin RS- (0 ft maximum) Pin 0 Signal RD TD DTR GND RTS CTS liebert Figure : Cable Pinouts (MCCI) ECA Use the following cable pinouts for the RS- connection between the Metasys Integrator unit and the Liebert ECA: Vendor Port A or B on Metasys Integrator RS- Port ECA DB- Female DB- Female Signal RD TD RTS CTS GND Pin RS- (0 ft maximum) Pin Signal TD RD CTS RTS GND liebert Figure : Cable Pinouts (ECA) Metasys Integrator Liebert Application Application Note

16 DC00 Use the following cable pinouts for the RS- connection between the Metasys Integrator unit and the Liebert DC00: Vendor Port A or B on Metasys Integrator RS- Port DC00 Port (DTE) DB- Female DB- Female Signal RD TD DTR GND RTS CTS Pin RS- (0 ft maximum) Pin 0 Signal TD RD DTR GND RTS CTS liebert Figure : Cable Pinouts (DC00 Port ) DCLAN Use the following cable pinouts for the RS- connection between the Metasys Integrator unit and the Liebert DCLAN Port. Use a DB- female to DB- female null modem to connect the Metasys Integrator unit to the Liebert DCLAN Port. Vendor Port A or B on Metasys Integrator RS- Port DCLAN DB- Female DB- Female Signal DCD RD TD DTR GND Pin RS- (0 ft maximum) Pin 0 Signal DCD TD RD DTR GND liebert Figure : Cable Pinouts (DCLAN) Metasys Integrator Liebert Application Application Note

17 Connecting to SiteLink/NIC Modules Direct RS- Connection Use the following cable pinout for the RS- connection between the Metasys Integrator unit and a single Liebert SiteLink module: Vendor Port A or B on Metasys Integrator DB- Female Signal RD TD GND Pin P or P on Panel RS- (0 ft maximum) RS- Port on SiteLink (DTE) DB- Female Pin Signal RD GND Third Party Interface Port Liebert Figure : Cable Pinouts for Single SiteLink Module RS- Connection Use Figures 0 through to wire multiple SiteLink/OpenComms NIC modules using Liebert REPOPT RS- to RS- Converters: Vendor Port A or B on Metasys Integrator DB- Female Signal RD TD GND Pin P or P on Panel RS- (0 ft maximum) Liebert REPOPT RS- to RS- Converter DB- Female Pin Signal RD GND RS- Connector Lieb Figure 0: Cable Pinout for Liebert REPOPT RS- to RS- Converter Metasys Integrator Liebert Application Application Note

18 REPOPT RS- to RS- Converter RS- Daisy-chained REPOPTs (000 ft maximum) RS- Liebert Figure : RS- Network of REPOPTs REPOPT RS- to RS- Converter DB- Female RS Connector on SiteLink Module DB- Female Signal RD TD GND Pin RS- Connector on Daisy-chained REPOPT RS- (0 ft maximum) Pin Signal RD GND Liebert Figure : Null Modem Cable from Liebert REPOPT to SiteLink Module Metasys Integrator Liebert Application Application Note

19 Connecting the Cable Connect the female end of the RS- cable to either Vendor Port A or Vendor Port B on the Metasys Integrator unit. Connect the other end of the cable to the RS- port on the MCCI, DC00, ECA, DCLAN or SiteLink module. Metasys Integrator Vendor Port A or B RS- Liebert MCCI. ECA, DC00, DCLAN, or SiteLink RS- Port Liebert Figure : Port-to-Port Connection Connection to Multiple SiteLink Modules Metasys Integrator RS- Liebert REPOPT RS- Liebert REPOPT RS- Liebert SiteLink Liebert REPOPT RS- Liebert SiteLink Liebert Figure : Connecting Metasys Integrator Unit to Multiple SiteLink Modules Metasys Integrator Liebert Application Application Note

20 Connecting Metasys Integrator Unit to OpenComms Network Interface Cards Metasys Integrator Unit RS- Liebert REPOPT RS- OpenComms Network Interface Card OpenComms Network Interface Card Lieberta Figure : Connecting Metasys Integrator Unit to OpenComms Network Interface Card 0 Metasys Integrator Liebert Application Application Note

21 Metasys Integrator Unit Setup To set up the Metasys Integrator unit, use a portable PC connected to Metasys Integrator Terminal Port. Metasys Integrator unit setup involves: downloading the correct vendor communication table (.VCT file) setting up the ports assigning network addresses to the controllers Tables through provide setup information specific to Liebert applications. For detailed procedures, see the Metasys Integrator unit technical bulletins on the Johnson Controls Product Information site ( System Manuals > Integration > Metasys Integrator). Table : Metasys Integrator Unit Setup for Liebert MCCI Applications Vendor Communication Table (.VCT File) System /Level 0 and System /Level,, 0, and System /Level 0 and with On/Off Control Small Systems Controller Port Setup Baud Rate 00 Word Length Stop Bits Parity Interface Network Setup LI_LEV0.VCT LI_LEV.VCT LI_LEVA.VCT LI_SSC.VCT None RS- Vendor Address Port Number (-) Timeout Value Poll Delay Performance Guide System /Environmental Units Small Systems Controller 000 ms 0 ms seconds seconds Metasys Integrator Liebert Application Application Note

22 Table : Metasys Integrator Unit Setup for Liebert ECA Applications Vendor Communication Table (.VCT File) Environmental Communication Adapter (ECA) Level 0 Environmental Communication Adapter (ECA) Levels 0 and Port Setup Baud Rate 00 Word Length Stop Bits Parity Interface Network Setup LI_ECA.VCT LIECA0.VCT None RS- Vendor Address Channel (-) Timeout Value Poll Delay Performance Guide ECA Environmental Communication Adapter 000 ms 0 ms seconds Metasys Integrator Liebert Application Application Note

23 Table : Metasys Integrator Unit Setup for Liebert DCLAN Applications Vendor Communication Table (.VCT File) Environmental Units Level 00 (L00) Small Systems Control (L0B) Level 0 (L0) and Level 0 (L0) Level 0 with On/Off Control (L0A) and Standard Microprocessor (LSM) Level 0 without On/Off Control (L0) Level 0 with On/Off Control (LA) and Level with On/Off Control (LAM) Chillers Single Module (CW) Two Module (CW) Three Module (CW) Chillers with Econocoil-Single Module (CE) Chillers with Econocoil-Two Module (CE) Chillers with Econocoil-Three Module (CE) Power Conditioning Units UPS Power Monitoring Panel (PMP) Series 00 and 00 Single Module System (SMS) LIDCLL00.VCT LIDCLL0B.VCT LIDCLL0.VCT LIDCLL0A.VCT LIDCLL0.VCT LIDCLLA.VCT LIDCLCW.VCT LIDCLCW.VCT LIDCLCW.VCT LIDCLCE.VCT LIDCLCE.VCT LIDCLCE.VCT LIDCLPMP.VCT LIDCLSMS.VCT Series 00 Multi Module System (MMS) LIDCLMMS.VCT Series 00 Static Control Cabinet (SCC) Contact Closure Module (CCM) Port Setup Baud Rate 00 Word Length Stop Bits Parity Interface Continued on next page... LIDCLSCC.VCT LIDCLCCM.VCT None RS- Metasys Integrator Liebert Application Application Note

24 Network Setup (Cont.) Vendor Address Timeout Value Poll Delay Performance Guide DCLAN BMS Units D,aaa* where D is: the address of the DCLAN ( -, A - Z, or a - y ); where aaa is: the DCLAN configured address (0 - ); each unit uses two consecutive DCLAN addresses**, only the first address is entered. For example, to address the first DCLAN device in DCLAN, enter, ms 0 ms seconds * The comma (,) between D and aaa of the Vendor Address is a required delimiter, which must be included in the vendor address. ** For the latest information on obtaining addressing information, please refer to The Advisor. It may be displayed or printed as needed. Metasys Integrator Liebert Application Application Note

25 Table : Metasys Integrator Unit Setup for Liebert SiteLink/NIC Applications Vendor Communication Table (.VCT) CCM Function Block CSE Function Block CSU Function Block EDS Function Block IMP Function Block L00 Function Block L0B Function Block L0 Function Block LAM Function Block LSM Function Block MM Function Block MMS Function Block PMP Function Block RAC Function Block SC Function Block SCC Function Block SM Function Block SM Function Block SMS Function Block THM Function Block VCF Function Block VCM Function Block WDU Function Block Port Configuration Baud Rate Word Length Stop Bits Parity Interface Network Configuration Vendor Address Timeout Value Poll Delay Retries LiSL_CCM.VCT LiSL_CSE.VCT LiSL_CSU.VCT LiSL_EDS.VCT LiSL_IMP.VCT LiSL_L00.VCT LiSL_L0B.VCT LiSL_L0.VCT LiSL_LAM.VCT LiSL_LSM.VCT LiSL_MM.VCT LiSL_MMS.VCT LiSL_PMP.VCT LiSL_RAC.VCT LiSL_SC.VCT LiSL_SCC.VCT LiSL_SM.VCT LiSL_SM.VCT LiSL_SMS.VCT LiSL_THM.VCT LiSL_VCF.VCT LiSL_VCM.VCT LiSL_WDU.VCT 00 (00 also can be used if the SiteLink module is configured for it.) None RS- <Modbus Address>, <Port #> (for example,, ) SiteLink Modbus Address -, Port - NIC Modbus Address -, Port For example: If the SiteLink Modbus address is, and the IGM is connected to Port, enter,. If NIC Modbus address is, enter, Note: <Modbus Address> defaults to. 00 ms 0 ms Approximate Scan Time (for a single Metasys Integrator device) SiteLink/NIC Modbus second Metasys Integrator Liebert Application Application Note

26 Point Mapping Tables Deluxe System/ (MCCI Configuration) To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Percent Heating point is. Use the following point mapping tables to map Metasys objects to the Liebert Deluxe System/ IGMs. Table applies to System/ Levels 0,,,, 0, and. Table : Deluxe System/ (MCCI Configuration) NPT NPA Unit Description 0 0 DegF Step Step DegF DegF Network Point Type Network Point Address Continued on next page... Temperature Humidity Percent Heating Stages Heating Percent Cooling Stages Cooling Temperature Setpoint (0 to ) Temperature Tolerance ( to ) Humidity Setpoint (0 to 0) Humidity Tolerance ( to 0) Cooling 0-Heat, -Cool Glycol 0-Off, -On Humidifying 0-Off, -On Dehumidifying 0-Off, -On High Head Pressure Compressor High Head Pressure Compressor Loss of Airflow Standby Glycol Pump On Water Under Floor Change Filters High Temperature Alarm Low Temperature Alarm High Humidity Alarm Low Humidity Alarm High Water in Humidifier Pan No Water in Humidifier Pan Compressor # Overload Compressor # Overload Main Fan Overload Manual Override Smoke Detected Loss of Water Flow Standby Unit On Low Suction Pressure 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm Metasys Integrator Liebert Application Application Note

27 NPT (Cont.) BO BO NPA Unit Description 0 Network Point Type Network Point Address Short Cycle Alarm Loss of Power Alarm Local Alarm Local Alarm User Alarm User Alarm Alarm Condition Exists 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm 0-Normal, -Alarm Reset All Alarms 0-N/A, -Reset Unit Mode 0-Off, -On Unit Start Status 0-Off, -On Local Command Status 0-Off, -On The Reset All Alarms command has no effect on the System/ Level 0. If you want to reset alarms on the Level 0, reset them directly on the System/ controller panel. Do not map these points to Companion Binary Output (BO) points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object s Definition and Focus window is disabled. Available only on units that include start/stop control. Metasys Integrator Liebert Application Application Note

28 Small Systems Controller (MCCI Configuration) To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Percent Heating point is. Table : Small Systems Controller (MCCI Configuration) NPT NPA Unit Description DegF Step Step Temperature Humidity Percent Heating Stages Heating Percent Cooling Stages Cooling Coolon 0-Heat, -Cool Glyavail 0-Off, -On Humidifying 0-Off, -On Dehumidifying 0-Off, -On High Head Pressure Compressor 0-Normal, High Head Pressure Compressor 0-Normal, -Alarm -Alarm Loss Of Airflow 0-Normal, -Alarm Standby Glycol Pump On 0-Normal, -Alarm Water Under Floor 0-Normal, -Alarm Change Filters 0-Normal, -Alarm High Temperature Alarm 0-Normal, -Alarm Low Temperature Alarm 0-Normal, -Alarm High Humidity Alarm 0-Normal, -Alarm Low Humidity Alarm 0-Normal, -Alarm High Water In Humidifier Pan 0-Normal, -Alarm No Water In Humidifier Pan 0-Normal, -Alarm Compressor Overload 0-Normal, -Alarm Compressor Overload 0-Normal, -Alarm Main Fan Overload 0-Normal, -Alarm Manual Override 0-Normal, -Alarm Smoke Detected 0-Normal, -Alarm Loss Of Water Flow 0-Normal, -Alarm Standby Unit On 0-Normal, -Alarm Low Suction Pressure 0-Normal, -Alarm Short Cycle Alarm 0-Normal, -Alarm Loss Of Power Alarm 0-Normal, -Alarm Local Alarm 0-Normal, -Alarm Local Alarm 0-Normal, -Alarm User Alarm 0-Normal, -Alarm User Alarm 0-Normal, -Alarm Alarm Condition Exists 0-Normal, -Alarm BO Reset Alarms 0-N/A, -Reset Network Point Type Network Point Address Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object s Definition and Focus window is disabled. Metasys Integrator Liebert Application Application Note

29 Liebert ECA Level 0 To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Humidity Reading point is. Table 0: Liebert ECA Level 0 NPT NPA Unit Description BO BO 0 0 DegF RH Step DegF DegF RH RH Network Point Type Network Point Address Temperature Reading Humidity Reading Percent Heating/Cooling Stages Heating/Cooling Temperature Setpoint 0- Temperature Sensitivity - Humidity Setpoint 0-0 Humidity Sensitivity -0 Cooling 0-Heat, -Cool Glycol 0-Off, -On Humidifying 0-Off, -On Dehumidifying 0-Off, -On High Head Pressure Compressor 0-Ok, High Head Pressure Compressor 0-Ok, -Alarm -Alarm Loss Of Airflow 0-Ok, -Alarm Standby Glycol Pump On 0-Ok, -Alarm Water Under Floor 0-Ok, -Alarm Change Filters 0-Ok, -Alarm High Temperature Alarm 0-Ok, -Alarm Low Temperature Alarm 0-Ok, -Alarm High Humidity Alarm 0-Ok, -Alarm Low Humidity Alarm 0-Ok, -Alarm High Water In Humidifier Pan 0-Ok, -Alarm No Water In Humidifier Pan 0-Ok, -Alarm Compressor Overload 0-Ok, -Alarm Compressor Overload 0-Ok, -Alarm Main Fan Overload 0-Ok, -Alarm Manual Override On 0-Ok, -Alarm Smoke Detected 0-Ok, -Alarm Loss Of Water Flow 0-Ok, -Alarm Standby Unit On 0-Ok, -Alarm Low Suction Pressure 0-Ok, -Alarm Short Cycle Alarm 0-Ok, -Alarm Loss Of Power Alarm 0-Ok, -Alarm Alarm Present 0-Ok, -Alarm Reset All Alarms 0-N/A, -Reset Unit Mode 0-Off, -On Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object s Definition and Focus window is disabled. Metasys Integrator Liebert Application Application Note

30 Liebert ECA Level 0 and Level To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Humidity Reading point is. Table : Liebert ECA Level 0 and Level NPT NPA Unit Description 0 0 DegF Step Hours Hours Hours DegF DegF DegF DegF Network Point Type Network Point Address Continued on next page... Temperature Reading Humidity Reading Percent Heating/Cooling Stages Heating/Cooling Compressor Run Hours Compressor Run Hours Glycol Hours Temperature Setpoint 0- Temperature Sensitivity - Humidity Setpoint 0-0 Humidity Sensitivity -0 High Temperature Alarm Setpoint 0- Low Temperature Alarm Setpoint 0- High Humidity Alarm Setpoint 0-0 Low Humidity Alarm Setpoint 0-0 Cooling 0-Heat, -Cool Glycol 0-Off, -On Humidifying 0-Off, -On Dehumidifying 0-Off, -On High Head Pressure Compressor 0-Ok, -Alarm High Head Pressure Compressor 0-Ok, -Alarm Loss Of Airflow 0-Ok, -Alarm Standby Glycol Pump On 0-Ok, -Alarm Water Under Floor 0-Ok, -Alarm Change Filters 0-Ok, -Alarm High Temperature Alarm 0-Ok, -Alarm Low Temperature Alarm 0-Ok, -Alarm High Humidity Alarm 0-Ok, -Alarm Low Humidity Alarm 0-Ok, -Alarm High Water In Humidifier Pan 0-Ok, -Alarm No Water In Humidifier Pan 0-Ok, -Alarm Compressor Overload 0-Ok, -Alarm Compressor Overload 0-Ok, -Alarm Main Fan Overload 0-Ok, -Alarm Manual Override On 0-Ok, -Alarm Smoke Detected 0-Ok, -Alarm Loss Of Water Flow 0-Ok, -Alarm Standby Unit On 0-Ok, -Alarm Low Suction Pressure 0-Ok, -Alarm Short Cycle Alarm 0-Ok, -Alarm Loss Of Power Alarm 0-Ok, -Alarm Alarm Present 0-Ok, -Alarm 0 Metasys Integrator Liebert Application Application Note

31 NPT (Cont.) BO BO NPA Unit Description Network Point Type Network Point Address Reset All Alarms 0-N/A, -Reset Unit Mode 0-Off, -On Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object s Definition and Focus window is disabled. Liebert DCLAN Environmental Unit Level 0 and Level 0 with On/Off Control (L00, L0A, and LSM) To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Humidity Reading point is. Table : Liebert DCLAN Environmental Unit Level 0 and Level 0 with On/Off Control (L00, L0A, and LSM) NPT NPA Unit Description DegF DegC DegF DegC Deg Temperature Reading (F) Temperature Reading (C) Humidity Reading Temperature Setpoint (F) - Temperature Setpoint (C) - Temperature Tolerance Setpoint -0 Humidity Setpoint - Humidity Tolerance Setpoint -0 Alarm Present 0-No, -Alarm Humidifying On 0-Off, -On Dehumidifying On 0-Off, -On Cooling On 0-Off, -On Heating On 0-Off, -On High Temperature 0-Ok, -Alarm Low Temperature 0-Ok, -Alarm High Humidity 0-Ok, -Alarm Low Humidity 0-Ok, -Alarm Loss Of Air Flow 0-Ok, -Alarm Water Under Floor 0-Ok, -Alarm Change Filters 0-Ok, -Alarm High Head Pressure 0-Ok, -Alarm BO Unit Run 0-Off, -On Network Point Type Network Point Address Only for L0A Metasys Integrator Liebert Application Application Note

32 Liebert DCLAN Environmental Unit Small Systems Control (L0B) To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Humidity point is. Table : Liebert DCLAN Environmental Unit Small Systems Control (L0B) NPT NPA Unit Description DegF DegC Temperature (F) Temperature (C) Humidity Alarm Present 0-No, -Alarm High Temperature 0-Ok, -Alarm Low Temperature 0-Ok, -Alarm High Humidity 0-Ok, -Alarm Low Humidity 0-Ok, -Alarm BO Unit Run 0-Off, -On Network Point Type Network Point Address Liebert DCLAN Environmental Unit Level,, 0, and (L0, L0, L0, LA, and LAM) To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Humidity point is. Table : Liebert DCLAN Environmental Unit Level,, 0, and (L0, L0, L0, LA, and LAM) NPT NPA Unit Description 0 Deg Deg Deg Deg Deg DegF DegF DegF Deg F Min Min Network Point Type Network Point Address Temperature Reading (F) Temperature Reading (C) Humidity Available only for Level 0 and 0. Continued on next page... Temperature Setpoint (F) - Temperature Setpoint (C) - Temperature Tolerance Setpoint -0 Humidity Setpoint - Humidity Tolerance Setpoint -0 High Temperature Alarm Setpoint (F) 0-0 High Temperature Alarm Setpoint (C) -- Low Temperature Alarm Setpoint (F) 0-0 Low Temperature Alarm Setpoint (C) -- High Humidity Alarm Setpoint - Low Humidity Alarm Setpoint 0-0 Auto Restart Delay Setpoint 0- CW Flush Cycle Setpoint 0- Metasys Integrator Liebert Application Application Note

33 NPT NPA Unit Description BO BO 0 0 Network Point Type Network Point Address Available only for Level 0 and 0. Alarm Present 0-No, -Alarm Humidifying On 0-Off, -On Dehumidifying On 0-Off, -On Cooling On 0-Off, -On Heating On 0-Off, -On High Temperature 0-Ok, -Alarm Low Temperature 0-Ok, -Alarm High Humidity 0-Ok, -Alarm Low Humidity 0-Ok, -Alarm Loss Of Air Flow 0-Ok, -Alarm Water Under Floor 0-Ok, -Alarm Change Filters 0-Ok, -Alarm High Head Pressure 0-Ok, -Alarm High Head Pressure 0-Ok, -Alarm High Water Humidifier Pan 0-Ok, -Alarm Manual Override 0-Ok, -Alarm Customer Alarm 0-Ok, -Alarm Customer Alarm 0-Ok, -Alarm Standby Glycol Pump On 0-Ok, -Alarm Compressor Overloaded 0-Ok, -Alarm Compressor Overloaded 0-Ok, -Alarm Main Fan Overloaded 0-Ok, -Alarm Smoke Detected 0-Ok, -Alarm Loss Of Water Flow 0-Ok, -Alarm Standby Unit On 0-Ok, -Alarm Low Suction Pressure 0-Ok, -Alarm Short Cycle 0-Ok, -Alarm Loss Of Power 0-Ok, -Alarm Low Water Humidifier Pan 0-Ok, -Alarm Alarm Reset 0-N/A, -Reset Unit Run 0-Off, -On Available only for devices which have on/off control. Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object s Definition and Focus window is disabled. Metasys Integrator Liebert Application Application Note

34 Liebert DCLAN Chiller - CW, CW, and CW To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Module Start point is. Table : Liebert DCLAN Chiller - CW, CW, and CW NPT NPA Unit Description 0 0 Network Point Type Network Point Address Alarm Present 0-No, -Alarm Module Start Module Pump On Module Cooling On Module Start Module Pump On Module Cooling On Module Start Module Pump On Module Cooling On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On High Head Pressure Module 0-Ok, -Alarm No Water Flow Module 0-Ok, -Alarm High Water Temperature Module 0-Ok, -Alarm Low Water Temperature Module 0-Ok, -Alarm No Power Module 0-Ok, -Alarm High Head Pressure Module 0-Ok, -Alarm No Water Flow Module 0-Ok, -Alarm High Water Temperature Module 0-Ok, -Alarm Low Water Temperature Module 0-Ok, -Alarm No Power Module 0-Ok, -Alarm High Head Pressure Module 0-Ok, -Alarm No Water Flow Module 0-Ok, -Alarm High Water Temperature Module 0-Ok, -Alarm Low Water Temperature Module 0-Ok, -Alarm No Power Module 0-Ok, -Alarm Available for CW (two module unit) or CW (three module unit). Available for CW. Metasys Integrator Liebert Application Application Note

35 Liebert DCLAN Chiller with Econocoil - CE, CE, and CE To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Module Start point is. Table : Liebert DCLAN Chiller with Econocoil CE, CE, and CE NPT NPA Unit Description 0 0 Network Point Type Network Point Address Alarm Present 0-No, -Alarm Module Start Module Pump On Module Cooling On Module Econocoil Operating Module Start Module Pump On Module Cooling On Module Econocoil Operating Module Start Module Pump On Module Cooling On Module Econocoil Operating 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On 0-Off, -On High Head Pressure Module 0-Ok, -Alarm No Water Flow Module 0-Ok, -Alarm High Water Temperature Module 0-Ok, -Alarm Low Water Temperature Module 0-Ok, -Alarm No Power Module 0-Ok, -Alarm High Head Pressure Module 0-Ok, -Alarm No Water Flow Module 0-Ok, -Alarm High Water Temperature Module 0-Ok, -Alarm Low Water Temperature Module 0-Ok, -Alarm No Power Module 0-Ok, -Alarm High Head Pressure Module 0-Ok, -Alarm No Water Flow Module 0-Ok, -Alarm High Water Temperature Module 0-Ok, -Alarm Low Water Temperature Module 0-Ok, -Alarm No Power Module 0-Ok, -Alarm Available for CE (two-module unit) or CE (three-module unit). Available for CE. Metasys Integrator Liebert Application Application Note

36 Liebert DCLAN Power Conditioning Unit To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Frequency point is. Table : Liebert DCLAN Power Conditioning Unit - Type PMP with IGM, VCMP with IGM NPT NPA Unit Description 0 kv kw Hz s Out X-Y s Out Y-Z s Out Z-X s Out X-N s Out Y-N s Out Z-N Out X Out Y Out Z Ground Current Neutral Current kva kw Frequency Capacity Phase X Capacity Phase Y Capacity Phase Z Alarm Present 0-No, -Alarm 0 Transformer Over Temperature 0-Ok, -Alarm Frequency Deviation 0-Ok, -Alarm Ground Over Current 0-Ok, -Alarm Output Over Current 0-Ok, -Alarm Output Over age 0-Ok, -Alarm Output Under age 0-Ok, -Alarm Ground System Fault 0-Ok, -Alarm Water Under Floor 0-Ok, -Alarm Security Alarm 0-Ok, -Alarm Phase Rotation 0-Ok, -Alarm Datawave Over Temperature 0-Ok, -Alarm Emergency Shutdown 0-Ok, -Alarm Unit In Bypass 0-Ok, -Alarm Customer Alarm 0-Ok, -Alarm Customer Alarm 0-Ok, -Alarm Local Alarm 0-Ok, -Alarm Ground Failure 0-Ok, -Alarm BO Alarm Reset 0-N/A, -Reset Network Point Type Network Point Address Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object s Definition and Focus window is disabled. Metasys Integrator Liebert Application Application Note

37 Liebert DCLAN UPS Series 00 and 00 To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Frequency point is. Table : Liebert DCLAN UPS Series 00* and 00 - Type Single Module System (SMS) and Multi Module System (MMS) NPT NPA Unit Description 0 0 kv kw Hz s Out A-B s Out B-C s Out C-A s Out A-N s Out B-N s Out C-N Out A Out B Out C KVA kw Frequency Capacity Phase A Capacity Phase B Capacity Phase C Battery Current DC Bus age Input s Phase A-B Input s Phase B-C Input s Phase C-A Alarm Present 0-No, -Alarm 0 Output Overload 0-Ok, -Alarm Load On Bypass 0-Ok, -Alarm Static Switch Disabled 0-Ok, -Alarm Emergency Power Off 0-Ok, -Alarm Module Cooling Failure 0-Ok, -Alarm Ambient Over Temperature 0-Ok, -Alarm Battery Discharging 0-Ok, -Alarm Low Battery Reserve 0-Ok, -Alarm Battery Disconnect 0-Ok, -Alarm Fuse Cleared 0-Ok, -Alarm Control Power Failure 0-Ok, -Alarm BO Alarm Reset 0-N/A, -Reset Network Point Type Network Point Address Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object s Definition and Focus window is disabled. Not available on MMS. * Series 00 with optional SiteScan Interface Card Metasys Integrator Liebert Application Application Note

38 Liebert DCLAN Series 00 Static Control Cabinet (SCC) To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Frequency point is. Table : Liebert DCLAN Series 00 Static Control Cabinet (SCC) NPT NPA Unit Description 0 Amp Amp Amp kv kw Hz s Out A-B s Out B-C s Out C-A s Out A-N s Out B-N s Out C-N Out A Out B Out C KVA kw Frequency Capacity Phase A Capacity Phase B Capacity Phase C Bypass age Phase A-B Bypass age Phase B-C Bypass age Phase C-A Alarm Present 0-No, -Alarm 0 Output Overload 0-Ok, -Alarm Emergency Power Off 0-Ok, -Alarm Load on Bypass 0-Ok, -Alarm Static Switch Disabled 0-Ok, -Alarm System Output Out of Limits 0-Ok, -Alarm Module Alarm 0-Ok, -Alarm Module Alarm 0-Ok, -Alarm Module Alarm 0-Ok, -Alarm Module Alarm 0-Ok, -Alarm Module Alarm 0-Ok, -Alarm Module Alarm 0-Ok, -Alarm BO Alarm Reset 0-N/A, -Reset Network Point Type Network Point Address Do not map these points to Companion BO points. If you map these points to Metasys BO objects, make sure the Auto Restore option in the BO object s Definition and Focus window is disabled. Metasys Integrator Liebert Application Application Note

39 Liebert DCLAN Contact Closure Module (CCM) To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Input Contact point is. Table 0: Liebert DCLAN Contact Closure Module (CCM) NPT NPA Unit Description Network Point Type Network Point Address Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Input Contact 0 0-Off, -On Input Contact 0-Off, -On Input Contact 0-Off, -On Alarm Flags 0-Ok, -Alarm Loss of Communications Metasys Integrator Liebert Application Application Note

40 Liebert SiteLink/NIC CCM Function Block To get the hardware reference for mapping points to CS object attributes (via the software model), combine the Network Point Type (NPT) and Network Point Address (NPA). For example, the hardware reference for the Input Contact point is. Table : Liebert SiteLink/NIC CCM Function Block NPT NPA Unit Description Network Point Type Network Point Address Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact 0 Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact 0 Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact Input Contact 0 Input Contact Input Contact 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed 0-Open, -Closed Alarm Flags 0-Ok, -Alarm Loss of Communications 0 Metasys Integrator Liebert Application Application Note

Metasys Integrator Airflow Application

Metasys Integrator Airflow Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0998 APPLICATION NOTE Metasys Integrator Airflow Application lntroduction Page Application Details * Component

More information

Metasys Integrator Compu-Aire Application

Metasys Integrator Compu-Aire Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 0496 APPLICATION NOTE Metasys Integrator Compu-Aire Application lntroduction Page 3 Application Details

More information

Metasys Integrator TITUS Application

Metasys Integrator TITUS Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date October 12, 2005 APPLICATION NOTE Metasys Integrator TITUS Application lntroduction Page 3 Application

More information

Metasys Integrator Cleaver-Brooks Application

Metasys Integrator Cleaver-Brooks Application Metasys Connectivity Technical Manual 69. Metasys Integrator Section Application Note Issue Date 0900 APPLICATION NOTE Metasys Integrator Cleaver-Brooks Application lntroduction Page Application Details

More information

Metasys Integrator Vilter Application

Metasys Integrator Vilter Application Metasys Connectivity Technical Manual 629.5 Metasys Integrator Section Application Note Issue Date 1294 APPLICATION NOTE Metasys Integrator Vilter Application lntroduction Page 3 Application Details *3

More information

Metasys Integrator McQuay Application

Metasys Integrator McQuay Application Metasys Connectivity Technical Manual. Metasys Integrator Section Application Note Issue Date 000 APPLICATION NOTE Metasys Integrator McQuay Application Introduction Page * Application Details * Component

More information

Metasys Integrator York Application

Metasys Integrator York Application Metasys Connectivity Technical Manual. Metasys Integrator Section Application Note Issue Date 000 APPLICATION NOTE Metasys Integrator York Application lntroduction Page * Application Details * Component

More information

P2267 NETWORK INTERFACE

P2267 NETWORK INTERFACE P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

FCD-wire Contents. List of Figures

FCD-wire Contents. List of Figures FCD-wire Contents FCD-X21 Configuration 1 Introduction... 1 2 Opening the FCD Application... 1 3 FCD Window... 2 4 FCD LEDs... 3 5 Configuration Operations... 4 FCD Info...4 FCD System Info...5 FCD Interface

More information

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer Installation and interface must be performed by a qualified controls technician. IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND CONFIGURATION OF THIS EQUIPMENT. READ

More information

Multiple Battery Cabinets Dual-Lite TRN. External Maintenance Switch Configuration Options. External Maintenance Switch Options

Multiple Battery Cabinets Dual-Lite TRN. External Maintenance Switch Configuration Options. External Maintenance Switch Options Table 4 External Maintenance Switch Configuration Options External Maintenance Switch Options Installed with Interlock Option Option Auxiliary Contact Status open = On Test position or Maintenance position,

More information

RS485 MODBUS Module 8AI

RS485 MODBUS Module 8AI Version 1.4 15/04/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features. CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse

More information

A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS

A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE INSTRUCTIONS SCADA INTERFACE INSTRUCTIONS - OPTION 21S - FOR A36D/TPSD SYSTEMS with option 500 and 550. A36D/TPSD Modbus RTU (Serial) SCADA INTERFACE OPTION 21S INSTRUCTIONS This manual is valid for A36D/TPSD Chargers

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for A36D & TPSD Chargers with S2A-341S and S2A-383S communication cards. Option 21P,

More information

DAP III Zone Master User s Guide

DAP III Zone Master User s Guide DAP III Zone Master User s Guide Data Aire, Inc. 230 West BlueRidge Avenue Orange, California 92865 Document Number 600-000-788 March 2010 Revision 1.0 Document # 600-000-788 1 Overview The Data Aire DAP

More information

Liebert LDMF Distribution Monitoring. User Manual

Liebert LDMF Distribution Monitoring. User Manual Liebert LDMF Distribution Monitoring User Manual TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS................................................1 1.0 GLOSSARY OF ABBREVIATIONS.............................................2

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS Firmware versions up to V2.0.X INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGCUIT2Protocol-IM-H57880 06/15 1/32 Contents Section I Introduction

More information

Reciprocating Chiller

Reciprocating Chiller HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 1094 Reciprocating Chiller Reciprocating Chiller Page 3 Description 3 Theory of Operation 5 Overview 5 Control Sequence

More information

Instruction Manual Model Backup Switch, 1 for 8

Instruction Manual Model Backup Switch, 1 for 8 Instruction Manual Model 2582-282 Backup Switch, 1 for 8 December 2011, Rev. 0 MODEL 2582 SWITCH CROSS TECHNOLOGIES INC. SWITCH ALARM PSA PSB ALARM OFFLINE ONLINE UNIT STATUS 1 2 3 4 5 6 7 8 BU PROT MODE

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

MicroTech Unit Ventilator

MicroTech Unit Ventilator Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This

More information

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1 NGC-40 Bridge Overview Raychem-AR-H58862-NGC40BridgeOV-EN-1805 nvent.com 1 Table of Contents 1. NGC-40 Overview... 9 1.1 Example NGC-40 System... 10 2. Legal stuff... 11 3. Protocols... 12 3.1 Data es...

More information

Fire Operator Workstation (Fire OWS) User s Guide

Fire Operator Workstation (Fire OWS) User s Guide Fire Operator Workstation (Fire OWS) User s Guide 1-1 Fire Operator Workstation (Fire OWS) User s Guide Introduction This user s guide details the components, capabilities, and operation procedures of

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

Modbus RTU RS485 Manual

Modbus RTU RS485 Manual Modbus RTU RS485 Manual AUTOMATED FUEL MAINTENANCE SYSTEMS FTI-5A, FTI-10A, FTI-20A FUEL TECHNOLOGIES INTERNATIONAL 06/10/2014 Rev B - Fuel Technologies - Modbus The Modbus Communications Setup Button

More information

Two-Channel Gas Controller

Two-Channel Gas Controller Two-Channel Gas Controller Specifications subject to change without notice. USA 09 Page of DESCRIPTION Highly configurable, UL 0 performance-tested and -certified, and wall-mounted gas monitor; continuously

More information

SIMPLICITY BY DESIGN M52 CONTROLLER

SIMPLICITY BY DESIGN M52 CONTROLLER SIMPLICITY BY DESIGN M52 CONTROLLER CO-WORK TM CONNECTIVITY Our controller is at the heart of all of ClimateWorx product intelligence. Co-Work TM is based on a unique multi-master network system designed

More information

AIS750 Series Alarm Annunciator User Manual (Ver. 2.3 / JUNE. 2014)

AIS750 Series Alarm Annunciator User Manual (Ver. 2.3 / JUNE. 2014) AIS750 Series Alarm Annunciator User Manual (Ver 23 / JUNE 2014) 3-350 John Street, Thornhill, tario L3T 5W6 Phone: 289 597 APEX (2739) Fax: 289 597 2200 Toll Free: 1 866 776 2943 Email: mail@annunciatorca

More information

ACCURATE ELECTRONICS INC

ACCURATE ELECTRONICS INC ACCURATE ELECTRONICS INC Page 1 of 7 Model 108078 2 Sept 09 WWW.ACCURATE.ORG PO BOX 1654 97075-1654 8687 SW Hall Blvd 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 Practice Section 108078 Rev A

More information

ModBus DE-1 INSTALLATION AND USER MANUAL

ModBus DE-1 INSTALLATION AND USER MANUAL ModBus DE-1 INSTALLATION AND USER MANUAL INTESIS Software, SL Distributed by DURAN ELECTRONICA S.L Tomás Bretón 50 28045 MADRID, España duran@duranelectronica.com www.duranelectronica.com 2 2010 DURAN

More information

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX Page 1 of 10 Model 10807800 January 2014 ACCURATE ELECTRONICS INC PO BOX 1654 97075-1654 8687 SW HALL BLVD 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 WWW.ACCURATE.ORG Practice Section 10807800

More information

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems Honeywell Life Safety Iberia C/Pau Vila 15-19; 08911 Badalona Barcelona T. 902 03 05 45; Internacional:+34932424236 www.honeywelllifesafety.es infohlsiberia@honeywell.com ibox Modbus Server Gateway for

More information

Liebert OVERHEAD COOLING IN A VARIETY OF CAPACITIES AND CONFIGURATIONS. Mini-Mate2. 1 to 8 Tons. Provides Precision Cooling And Humidity Control

Liebert OVERHEAD COOLING IN A VARIETY OF CAPACITIES AND CONFIGURATIONS. Mini-Mate2. 1 to 8 Tons. Provides Precision Cooling And Humidity Control GFGDFDFGFGFYUIUIYUITUYIUIUOG GFGDFDFGFGFYUIUIYUITUYIUIUOG GFGDFDFGFGFYUIUIYUITUYIUIUOG GFGDFDFGFGFG Liebert Mini-Mate2 1 to 8 Tons H e a t R e m o v a l OVERHEAD COOLING IN A VARIETY OF CAPACITIES AND

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

MicroTech Series-200 Flooded Screw Chiller

MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Infomation Packet Version 1.0 Group: Controls Date: February 1997 MicroTech Series-200 Flooded Screw Chiller Open Protocol Data Communications 2002 McQuay International - C O N F I D

More information

VCM-X Controller Technical Guide

VCM-X Controller Technical Guide 2 2 www.orioncontrols.com VCM-X Controller Technical Guide VCM-X Controller Code: SS1026 & Y200920 Version 2.0 and up; VCM-X Modular Controller: Tulsa - SS1030; Coil - SS1034 VCM-X WSHP Controller: Tulsa

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

HRX Technical Manual. Version 1.2

HRX Technical Manual. Version 1.2 HRX 5000 Technical Manual Version 1.2 Contents: Specification...2 Connectors...5 RS-485 Network Connectors (J6 and J7)...5 RS-232 to Printer (J19)...6 RS-232 to PC (J8)...7 TCP/IP...8 Power (J21)...9 Fire

More information

Symmetra MW Modbus Data Points

Symmetra MW Modbus Data Points Symmetra MW Modbus Data Points Version 0.11.19.05 rev 1 General Information: There are two devices that constitute the Symmetra MW system: the UPS and the EBS. There is a separate point mapping for each

More information

Liebert SiteScan Web. Modbus and BACnet Protocols. Installer/User Guide

Liebert SiteScan Web. Modbus and BACnet Protocols. Installer/User Guide Liebert SiteScan Web Modbus and BACnet Protocols Installer/User Guide Technical Support Site If you encounter any installation or operational issues with your product, check the pertinent section of this

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TT-1343 5/06b INSTALLATION INSTRUCTIONS Original Issue Date: 8/03 Model: Automatic Transfer Switches Equipped with Series 1000 Programmable Controller Market: ATS Subject: Remote Annunciator Kits GM28938-KP1,

More information

Metasys Integrator Carrier Application

Metasys Integrator Carrier Application Application Note Issue Date April 15, 2003 Metasys Integrator Carrier Application lntroduction 3 Application Details 3 Component Requirements 6 Vendor Contact Information 7 Design Considerations 7 Cable

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

M1000 Alarm Annunciator

M1000 Alarm Annunciator Data Sheet Alarm Annunciator Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment

More information

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT-1201739 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL 1 Operations Manual for the VTI Model itc5000 Heat Tracing Control System Description The VTI Model itc5000 Heat Tracing Control System consists

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL

ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL PRODUCT Specification FEATURES Designed To Meet The Requirements Of EN54 Expandable From 1 To 5 Loops As Standard A Variety Of Networking Options

More information

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS.  A4741 / Rev.1 DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS User Manual and Menu Map A4741 / Rev.1 www.entes.com.tr ATTENTION -Disconnect all power before connecting the device. -Don t remove

More information

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Metasys Network Technical Manual 636 DX-9100/9120 Applications Section Application Note Issue Date 0497 APPLICATION NOTE DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit Introduction

More information

Added password for IP setup page : Password must be in IP format!

Added password for IP setup page : Password must be in IP format! NETWORK POWER MONITOR Release : 21 August 2014 Hardware Version : Version 7 Firmware version 1.00 PC Application Software : Version (latest)...2 Added password for IP setup page : Password must be in IP

More information

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm

More information

TC-9102 Applications

TC-9102 Applications Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...

More information

Installation, Configuration and User Manual

Installation, Configuration and User Manual Model 8826 System Controller Model 8826 System Controller Installation, Configuration and User Manual READ AND SAVE THESE INSTRUCTIONS WELCOME Thank you for choosing the Aprilaire HVAC Automation System.

More information

Liebert Mini-Mate2 1 To 8 Tons

Liebert Mini-Mate2 1 To 8 Tons Liebert Mini-Mate2 1 To Overhead Precision Cooling And Humidity Control Precision Cooling For Business-Critical Continuity Precision Cooling In A Space-Saving, Ceiling-Installed System When IT equipment

More information

Water Source Heat Pump Module Technical Guide

Water Source Heat Pump Module Technical Guide Factory Packaged Controls Tulsa Water Source Heat Pump Module WSHP WSHP Protection Module Module Orion No.: OE334-23-WPM-A NON-DIGITAL COMPRESSORS #1 THRU #4 +5V SUCT. +5V SUCTION PR. SENSOR PRES PRES

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction.................................................

More information

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

FieldServer Driver - Serial FS McQuay Microtech Open Protocol Description FieldServer Driver - Serial FS-8700-80 McQuay Microtech Open Protocol This is an active client protocol. The driver is capable of acting as a master or slave. As a master, the Fieldserver polls

More information

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47 WSHP Open v3 CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-539-01 2/8/2017 Verify that you have the most current version of this document

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

Liebert PPC Second Generation Power Distribution Cabinet

Liebert PPC Second Generation Power Distribution Cabinet Liebert PPC Second Generation Power Distribution Cabinet Emerson Network Power Delivers The Packaged Power Solution Creating high quality power is a major step towards protecting the operation of a critical

More information

A36D/TPSD Modbus TCP SCADA INTERFACE INSTRUCTIONS

A36D/TPSD Modbus TCP SCADA INTERFACE INSTRUCTIONS SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS with 500 and 550 option. A36D/TPSD Modbus TCP SCADA INTERFACE OPTION 21Q INSTRUCTIONS This manual is valid for A36D/TPSD Chargers equipped

More information

Variable Frequency Drive SERIES MP800 VFD

Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controls and Accessories Variable Frequency Drive SERIES MP800 VFD Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance Checklist Code No. LIT-1201754 Release 1.2 Issued February 10, 2005 Document Introduction.................................................

More information

Open Protocol Data Communications

Open Protocol Data Communications MicroTech Series-100 Centrifugal Chiller Open Protocol Data Communications Information Packet Version 3.2 April, 1996 - C O N F I D E N T I A L - This Document may not be copied or reproduced in any way

More information

ATS Annunciator - MODBUS

ATS Annunciator - MODBUS GE Zenith Controls ATS Annunciator - MODBUS Model 150047443 Quick Start Guide ATS Annunciator monitors and controls up to 8 Automatic Transfer Switches equipped with the MX150/250 Controller. Before getting

More information

Table of Contents. WSHP Open v3

Table of Contents. WSHP Open v3 WSHP Open v3 Integration Guide CARRIER CORPORATION 2012 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-500-01 11/29/2012 Table of Contents Introduction... 1

More information

PowerLogic Branch Circuit Power Meter (BCPM)

PowerLogic Branch Circuit Power Meter (BCPM) PowerLogic Branch Circuit Power Meter (BCPM) Panel Board Monitoring System Installation Guide Branch Circuit Power Meter (BCPM) HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and

More information

Temperature Controllers

Temperature Controllers Model TEC-4100 1/4 DIN Model TEC-4100 1/4 DIN Temperature Controller Ordering Code: Power Input BOX 1 4 = 90-250 VAC 5 = 11-26 VAC / VDC TEC-4100- Configurable for 4 Programmable Outputs and NEMA 4X/IP65

More information

Across-the-Line SERIES MP300 Combined Manual and Automatic

Across-the-Line SERIES MP300 Combined Manual and Automatic Across-the-Line SERIES MP300 Combined Manual and Automatic Metron Fire Pump Controllers conform to the latest requirements of National Fire Protection Association s Standard for Centrifugal Fire Pumps

More information

Liebert Mini-Mate2 1 To 8 Tons

Liebert Mini-Mate2 1 To 8 Tons Liebert Mini-Mate2 1 To Overhead Precision Cooling And Humidity Control Precision Cooling For Business-Critical Continuity Precision Cooling In A Space-Saving, Ceiling-Installed System When IT equipment

More information

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide Aurora Touch UPC Kit Instruction Guide For use in single compressor water-to-air equipment utilizing fi rmware UPCSWASTD01-01 Aurora Touch UPC Kit Instruction Guide *IG1583EW* IG1583EW 08/14 Aurora Touch

More information

RPM1600 Series Room Pressure Monitors

RPM1600 Series Room Pressure Monitors RPM1600 Series Room Pressure Monitors Technical Bulletin LB-RPM1611-0, LB--0 Code No. LIT-12012228 Issued October 2017 Refer to the QuickLIT website for the most up-to-date version of this document. How

More information

Ethernet General Purpose

Ethernet General Purpose Ethernet General Purpose Technical Manual Revision 1.03 8 November 2013 Pakton Technologies IO PAE224 Ethernet GPIO Manual.docx Page 1 of 22 Revision 1.03 Last updated 8/11/2013 Table of Contents INTRODUCTION...3

More information

PBI Manual. Paradox to KNX-BUS Interface

PBI Manual. Paradox to KNX-BUS Interface PBI 64-192 Paradox to KNX-BUS Interface Manual GDS Intelligence in Buildings El. Benizelou 116 Nea Erithrea, 14671 Phone: +30 2108071288 Email: info@gds.com.gr Web: gds.com.gr Contents 1 Device description...

More information

Model A2100 Series Annunciator

Model A2100 Series Annunciator Seekirk Model A2100 Series Annunciator Applications: For usage within transformers, switchgear, breakers and/or within any processing equipment or control room applications either attended or unattended

More information

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual Revision 1.03 8 November 2013 JVA Technologies Ethernet General Purpose IO Technical Manual www.jva-fence.com.au Table of Contents INTRODUCTION...3 Scope and Purpose...3 Glossary...3 SPECIFICATIONS...4

More information

ION Meter Alerts TECHNICAL NOTE NOVEMBER In This Document

ION Meter Alerts TECHNICAL NOTE NOVEMBER In This Document 70072-0125-01 TECHNICAL NOTE NOVEMBER 2006 ION Meter Alerts A PowerLogic ION meter can send alerts to indicate a user specified power system condition such as a power quality problem (including surges,

More information

Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C

Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C 1. General The hand-held micro terminal is used for setting the motor parameters of the SILVER C. 2. Installation

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-7 Group: Controls Part Number: ED 15121 Date: July 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHRAE 135-2004, BACnet

More information

OPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL

OPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL ap15_2manual04/22/13 Page 1 4/22/2013 1 Serial Number : Option: OPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL Micro Seven, Inc. 1095-K N.E. 25th Hillsboro, OR 97124 U.S.A. phone: 503-693-6982

More information

Liebert Mini-Mate2 1 To 8 Tons

Liebert Mini-Mate2 1 To 8 Tons Liebert Mini-Mate2 1 To 8 Tons Overhead Precision Cooling And Humidity Control Precision Cooling For Business-Critical Continuity The Solution For Your Cooling Needs May Be Right Above You When the need

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

Liebert Mini-Mate2. 8-Ton (28kW) Capacity, Air, Water, Glycol, GLYCOOL, Chilled Water; 50 & 60 Hz. Technical Data Manual

Liebert Mini-Mate2. 8-Ton (28kW) Capacity, Air, Water, Glycol, GLYCOOL, Chilled Water; 50 & 60 Hz. Technical Data Manual Liebert Mini-Mate2 8-Ton (28kW) Capacity, Air, Water, Glycol, GLYCOOL, Chilled Water; 50 & 60 Hz Technical Data Manual Technical Support Site If you encounter any installation or operational issues with

More information

mti085 Temperature Interface

mti085 Temperature Interface Temperature Interface 1-WIRE INTRINSICALLY SAFE mti085 mti085 Temperature Interface Document No. 10432 Revision H July 2007 2001-2006 CMC Industrial Electronics Ltd. This page intentionally left blank

More information

ME 3011C / Alarm Indication / Quick Reference Guide

ME 3011C / Alarm Indication / Quick Reference Guide Tables of Contents Page Application 1 Features 1 Important Safety Information! 2 Note to this Guide 2 Further Information 2 Device Variants 2 General Functions 3 Annunciator Sequences - ISA 18.1 3 Plan

More information

DiaLog Elite. Quick Reference Guide. Remote Monitoring, Control and. Alarm Notification System. # Enter. 1 Prog. 2 Run. 5 SpkrPh. Ack. Arm.

DiaLog Elite. Quick Reference Guide. Remote Monitoring, Control and. Alarm Notification System. # Enter. 1 Prog. 2 Run. 5 SpkrPh. Ack. Arm. DiaLog Elite 1 Prog Remote Monitoring, Control and 2 Run Alarm Notification System 5 SpkrPh 0 Status # Enter Quick Reference Guide Ack Clear Arm Reset Disarm Bksp Home Antx, inc. 2008 RUN Mode Commands

More information

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV CyCLO User Guide Version 2.00 19 th December 2017 REV 2.00 1 Contents 1. Hardware... 3 1.1. Introduction... 3 1.2. Electrical Specification... 3 1.3. Board Overview... 4 1.4. Electrical Installation...

More information

Flexible & Innovative. Cooling Solutions

Flexible & Innovative. Cooling Solutions Flexible & Innovative Cooling Solutions Flexible & Innovative Compu-Aire Inc. offers a variety of high performance precision cooling systems that can adapt to your application needs. With today s rapidly

More information

RACK MONITORING SYSTEM - RAMOS Ultra

RACK MONITORING SYSTEM - RAMOS Ultra CONTEG DATA SHEET version: 9-05-0 COMPLEMENTARY SYSTEMS RACK MONITORING SYSTEM marketing@dafnia.com www.dafnia.com ABU DHABI UAE +97 55575 DUBAI JAFZA +97 4 5995 +97 4 8840 MUSCAT DOHA OMAN +968 4 75005

More information