REMKO ATK 25. Automatic oil heater with built-in oil burner, tank and exhaust gas connection. Operation Technology Spare Parts.

Size: px
Start display at page:

Download "REMKO ATK 25. Automatic oil heater with built-in oil burner, tank and exhaust gas connection. Operation Technology Spare Parts."

Transcription

1 REMKO ATK 25 Automatic oil heater with built-in oil burner, tank and exhaut ga connection Operation Technology Spare Part Edition GB-D05

2

3 Content Safety Notice 4 Environmental Protection and Recycling 4 Device Decription 5 Regulation for air heater 6 Mounting Regulation 7 Exhaut ga routing 8 Commiioning 9 Decommiioning 10 Maintenance and Care Exhaut ga analyi 12 Fuel pump 13 Cutomer Service and Guarantee 14 Intended ue 14 Electrical Wiring Diagram 14 Trouble Shooting 15 Exploded view 16 Spare Part Lit 17 Maintenance log 18 Technical Data 19 Before commiioning/ue of the equipment, thee operating intruction mut be read carefully! Thee intruction are a part of the device and mut thu alway be kept in the direct vicinity of the mounting ite or on the device itelf. Thi operating manual i a tranlation of the German original. Subject to change; error and typographical error excepted! 3

4 REMKO ATK Safety Notice When uing the appliance, alway oberve the repective local contruction and fire protection ordinance a well a the regulation of the employer liability inurance aociation. Environmental Protection and Recycling The appliance were ubjected to extenive material, functional and quality tet before delivery. Neverthele the equipment may preent a danger if it i ued by untrained peronnel, improperly or not according to regulation! Pleae oberve the following notice: Before maintenance or ervicing work, the main plug mut be removed from the ocket The unit may be operated only by peronnel who have been trained in it operation The unit mut be et up and operated in uch a way that people are not endangered by exhaut fume and radiated heat and no fire can break out The unit may be et up and operated in room only if there i a ufficient amount of air for the combution The unit may be operated without an exhaut duct only in well-ventilated room. People may not contantly be in the mounting room Correponding prohibition ign mut be poted at the entryway! The unit may not be operated without uperviion Mount the unit only on a level, non-flammable bae The unit may be et up and operated only in an environment not at rik of fire or exploion The unit may not be et up in atmophere containing oil, ulphur, or alt A afety zone of and 1.50 m around the unit and non-flammable object mut be oberved The protective air uction grille mut alway be free of dirt and looe object Never inert foreign matter into the unit The unit may not be expoed to direct water jet, uch a high-preure cleaning unit, and o on All electrical cable of the unit mut be protected from damage (e.g. due to animal) Safety equipment may neither be bridged nor blocked! Due to the deign, a permanent, fixed-location intallation i not intended for thi type of unit Dipoal of packaging When dipoing of the packaging material, think of the environment. Our equipment i carefully packed for tranport and delivered in a table cardboard tranport package on a wooden pallet, if neceary. The packaging material are environmentally friendly and can be reued. With the reue of packaging material, you make a valuable contribution to the reduction of wate and the preervation of raw material. You hould thu dipoe of the packaging material at the correponding dipoal ite. Dipoal of the old device The equipment manufacturing proce i ubject to contant quality control. Only high-quality material that are recyclable to a great extent are ued. You alo contribute to environmental protection by guaranteeing that your old unit i dipoed of an environmentally friendly manner. For thi reaon, bring the old unit only to an authoried recycling company or to a correponding dipoal ite. 4

5 Decription of Device The unit i fired directly with heating oil EL or dieel and can be operated with or without an exhaut-ga connection. It i intended for mobile and fully automatic deployment. A fuel container i built under the unit and it i equipped with automatic tank heating, a high-preure atomizing oil burner with optical flame monitoring, a low maintenance axial ventilator, a connection cable with plug, a room thermotat ocket and a fourfold filter ytem. The unit complie with the baic afety and health requirement of the relevant EU tipulation and i reliable and imple to operate. The unit can be ued e.g. in the following area: Drying new building; Point heating of outdoor workplace; Point heating of workplace in open, non firehazard fabrication room and hall; Temporary heating of cloed and open area; De-icing of machine, vehicle and non flammable torage good; Tempering frot-endangered part Working of Device When the power plug i connected to a power ocket, the automatic tank heater i activated for temperature below 10 C. When the unit ha been witched on or when heat i required (automatic function with room thermotat) the upply air fan tart. The fan blow air into and along the combution chamber. When the preliminary ventilation i over, the electromagnetic valve open and upplie fuel to the nozzle. The fuel, prayed under high preure, i enriched by an adequate quantity of oxygen according to the heating capacity and ignited by an electric park. Once a flame i burning, the automatic burner relay begin monitoring the flame. The automatic burner relay control all unit functionality fully automatically and monitor them for afety. After a few econd hot air i blown out.cae of any trouble, or if the flame i untable or tend to go out, the unit i witched off by the automatic burner relay. The fault indicator warning lamp of the automatic burner relay light up. A retart cannot be made before the manual releae of the automatic burner relay. When the unit ha been witched off via the operating witch or the room thermotat, the upply air fan continue running for ome time to cool down the combution chamber and then it top automatically. Depending on the required heat rate the function decribed above i repeated automatically in the cae of an operation with thermotat.. Safety temperature limiter (STB) The STB interrupt the upply of fuel if the unit overheat and caue the automatic burner relay to witch off. If the afety temperature limiter ha triggered, the caue of the diturbance mut firt be localied and eliminated. Reetting via the RESET key i only poible after the enor ha cooled to below ca. 90 C. CAUTION If the afety temperature limiter ha been tripped then the caue of the malfunction hould be identified and rectified before reetting it. The afety temperature limiter i unlocked by preing the reet key [2]. 1. Detach the protection cap[1]. 2. Pre the reet key [2]. 3. Replace the protection cap [1] 4. Releae the automatic burner relay a well. 1 2 In order to prevent the triggering temperature from being exceeded again, the operating condition of the unit hould be checked before reetting the afety temperature limiter. CAUTION Safety equipment may neither be bridged nor blocked! 5

6 REMKO ATK Proviion for Air Heater When uing the unit, the repective applicable guideline mut alway be oberved. For example for Germany: Combution plant order (FeuVo) for the individual tate Accident prevention regulation (UVV) Heating, flaming and melting device for contruction and intallation work (VBG 43) Workplace directive ASR 5 Workplace ordinance 5 and 14 - excerpt from the accident prevention regulation (VBG 43) Excerpt from the accident prevention regulation (VBG 43) 37 Operating peronnel The unit mut only be operated by peron who have been trained in it operation. 38 Intallation (1) The unit mut be intalled o that it can tand in a table poition. (2) The unit mut be intalled and operated in uch a way that the employee are not expoed to the danger of exhaut gae and radiant heat and that the occurrence of fire i ruled out. (3) The unit may only be intalled and operated in room if a quantity of air uffici ent for the combution i upplied to the unit and the exhaut gae are removed to the exterior. A natural air upply ufficient for the combution i preent if e.g. The room content in m² corre pond with at leat 10 time the nominal heat load in kw of all the unit operating in the room and if window and door enure a natural change of air. (4) In deviation from point 3, the unit can be operated without an exhaut ytem in room if thee room have a ufficient air upply and are well ventilated and if material harmful to health do not reach an unhealthy concentraton. A good natural air upply and ventilation i the cae if e. g.: 1. The room content in m² corre pond with at leat 30 time the nominal heat output of all unit operating in the room and a natural change of air i enured through window and door, or opening which are not locka ble are preent in the region of ceiling and floor for the air upply and for out going air and the ize of thee opening in m² correpond with at leat time the nominal heat output in kw of all unit operating in the room. (5) The unit mut not be intalled or operated in room and area where the danger of fire or exploion exit.. 44 Room drying (2) In derogation from 38 ection 3 heating unit can be ued for drying area with adequate air upply for combution without having to route the exhaut gae through exhaut ga ducting to the outide. It i forbidden for peronnel to remain in thee area for extended period. Appropriate prohibition ign hould be put up at the entran ce. 53 Examination (2) The unit mut be teted by an expert a to it work afety pecific condition in accordance with the required deployment condition but at leat once annually. The exhaut value of the burner mut be checked. 54 Monitoring (1) When tarting work, the peron commiioned with the operation of the unit mut check the unit for obviou defect or deficien cie on the operational and afety mechanim and check that the afety mechanim are preent. (2) If defect or deficiencie are dicovered, the upervior mut be informed.. (3) In the cae of defect or defici encie which en danger the operational afety of the unit, it operation mut be terminated. 55 Infringement Infringement in the ene of 710 ection 1 of the Imperial Inurance Code pertain to an intentional or negligent breach of the proviion of VBG 43. 6

7 Mounting Regulation When the unit i in ue, the afety guideline of the employer liability inurance aociation, the repective country contruction ordinance, and the burning appliance regulation baically apply. CAUTION Avoid underpreure or overpreure in mounting room ince thee tate alway lead to combution-technical problem. Make ure that there i an adequate freh air upply appropriate to the repective forced-air burner capacity (ee name plate) Outdoor mounting Due to the operation of the unit, no danger or unreaonable nuiance may arie The unit operator mut guarantee that unauthoried peron cannot manipulate the unit or the energy upply To avoid damage due to inclement weather, the unit mut be mounted in a protected manner The burner etting hould be checked after every change of location and adapted to the new environmental condition and atmopheric condition if neceary. Intallation in cloed, well aerated room without connection to a chimney The operation of the unit i permiible if the minimum air quantity cited in 38 ection 4 for combution i upplied A afe exhaution of the wate gae i to be enured to exclude inadmiible polluti on. Freh air i fed from below; wate gae are exhauted toward the top Heating Room Warm air generator may only be operated with a room ther motat when heating room. (Acceorie) Make ure that ufficient freh air i fed to enure perfect combution. Freh air i to be fed preferably through window and door or through ufficiently dimenioned opening in the outer wall Safety zone To enure afe operation and guarantee unhindered acce to the unit for maintenance work, a afety zone of 1.5 m hould be maintained around the unit Floor and ceiling mut be fire-reitant Intake and outlet diameter mut not be narrowed or blocked with foreign object CAUTION The unit mut only be intalled in well ventilated pace and not in living area or imilar recreational area. For optimum operation the unit hould not be operated above an ambient temperature of 25 C. Electrical Connection The unit are operated with 230 V / 1~ N / 50 Hz. The electrical connection i made uing a built-in main cable with earthed afety plug The electrical connection for the unit mut be made at a eparate feed point with a reidual current device in accordance with VDE 0100, Section 55. Extenion to the connection cable may only be carried out by authoried electrician, ubject to the length of the cable, connected load of the unit and taking into conide ration how the unit i ued at it location 7

8 REMKO ATK Exhaut ytem In the outdoor or in open room, the operation of the device i alo poible without an exhaut ytem. However, we recommend a 1 m exhaut-pipe (ee example 2) with a rain hood placed on top o a to rule out the penetration by rainwater and dirt. If the device i ued for temporary room heating, the combution gae may have to be removed to the exterior. The exhaut-pipe part mut be laid in uch a way that a minimum uction of 0.1 mbar i guaranteed It mut be made ure in all cae that counter preure due to an incorrect exhaut ytem i ruled out Malfunction-free operation i guaranteed if the exhaut ytem i intalled in an acen ding direction and with vertical end pipe The exhaut ytem mut terminate at leat above the height of the eave but better till above roof height in order to avoid counter preure caued by weatherrelated circumtance (e.g. wind) The minimum ditance of 0.6 m to combutible part mut not be exceeded Exhaut-pipe part including attachment material are available a acceorie All exhaut-pipe part mut be attached reliably. Their diameter mut not be maller than that of the exhaut nozzle of the device The lateral opening in the exhaut connection mut not be cloed or covered The exhaut pipe mut not be puhed beyond the top (wage) Note for implementing the 1t. BImSchV max. 1 m. More than 1 m. Unit that are not expected to be operated for longer than 3 month in the ame location are not ubject to any approval or monitoring a per the 1t. BImSchV Example 1 Example 2 Example 3 In order to prevent the combution chamber from becoming damaged due to condenation of moiture (condenate) in example 3, make ure that the exhaut ga ducting i correctly intalled with a condenate trap a hown in example 1. operating with extended wate ga pipe condenate trap necearily operating without extended wate ga pipe max. 1m Inadmiible arrangement. HINWEIS Counter preure mut not arie under any circumtance from the incorrect intallation of exhaut ga ducting. 8

9 Commiioning Prior the commiioning the unit i to be checked to make ure that there are no viible defect on the control and afety device, that the unit ha been intalled correctly and that it ha been properly connected to the main. A properly trained peron i to be charged with the operation and control of the unit. CAUTION In cae of defect that endanger the operating afety of the unit, the operation of the unit mut be hut down immediately and the upervior mut be informed! Intall unit in a table poition Make ure that combution air i upplied Make ure that the air can be ucked in and be exhauted freely Avoid overpreure and underpreure in the room where the unit ha been intalled Make ure that enough fuel i upplied. Fill fuel tank only with clean fuel oil EL or dieel with the unit witched off. Do not ue biodieel! Ue only appropriate and clean tank to fill with fuel Paraffin accumulation by low outide temperature. The upply of ufficient liquid fuel i to be enured, even with low outide temperature. The built-in tank heating i only active a long a the main plug i connected with a functioning main ocket and the urrounding temperature i below 10 C It i not poible to get rid of paraffin dicharge which i already preent uing the tank heating. The requirement for thi i the cleaning of the entire fuel ytem Paraffin accumulation can occur even at temperature a low a 5 C. Appropriate meaure mut be taken to avoid thi. (winteried heating oil) Fuel filter Prior to commiioning the unit and before the tank i filled each time, the main filter mut be checked for the preence of grime or the accumulation of paraffin. Connect the unit with the current upply 1. Put operating witch 1 into 0 poition (OFF). 2. Connect unit plug to a uitable main ocket. 230V / 1~ / 50 Hz.. The electrical connection for the unit mut be made at a eparate feed point with a reidual current device in accordance with VDE 0100, Section 55 Heating without a room thermotat The unit run in continuou operation. 1. Plug the upplied bridge circuit plug [2] into the thermotat ocket [1] Set the operating witch to I (ON). 1 The wate ga value of the oil-burner are to be checked and properly adjuted by authoried peronnel to enure compliance with local requirement. The main filter i poitioning beide the filler. Make ure to fill the fuel tank only with the tank filter inerted into the filler neck. 9

10 REMKO ATK 10 heating with room thermotat (acceorie) The unit run fully automatically with the temperature which ha been pre-elected on the room thermotat. 1. Remove the bridge circuit plug. 2. Plug the thermotat plug [4] of the room thermotat (acceorie) into the thermotat ocket [3] Put room thermotat [4] in a uitable place. The thermotat enor may not be placed directly in the warm air tream or attached to a cold urface. 4. Pre-elect deired room temperature on the room thermotat [4] Set the operating witch to I (ON). When heat i required, the forcedair burner witche on automatically; operation of the unit i fullyautomatic. 1 Shut-Down 1. Set the operating witch to 0 (OFF). The air upply fan continue running to cool down the combution chamber and then top at a later time. The fan can run everal time before the unit i finally witched off.! 2. In the cae of longer period of inactivity, diconnect the unit from the main power upply. CAUTION Never interrupt (except in emergency ituation) the power upply until the cool-down phae i completely finihed. Our guarantee doe not cover damage caued to the unit by overheating. In the cae of longer period of inactivity or if the unit are in torage, pleae enure that the fuel tank i alway filled with heating oil or dieel. 4 Maintenance and Service The unit i to be maintained regularly whereby ome fundamental rule are to be oberved to enure a long ervice life and trouble-free operation. After each heating period or even earlier, depending on the deployment condition, the entire unit including combution chamber and burner head mut be cleaned of oot ediment, dut and dirt. The oil filter mut alo be cleaned / replaced at leat once a year or, depending on the degree of contamination of the fuel, frequently.. CAUTION Prior to tarting any work make ure to pull the main plug out of the main ocket! There i extreme rik of injury epecially when the unit lining i open from the fan that witche on automatically Setting and maintenance i to be carried out only by authoried peronnel!. The unit i to be kept free from dut and other depoit and i to be cleaned only with a dry or humid cloth. Do not ue water jet! Do not ue any aggreive cleaning agent or thoe which are harmful or environmentally unfriendly Ue only clean fuel oil EL and dieel, repectively. Make ure to avoid paraffin formation

11 Empty fuel tank at leat twice a year and rine it with clean fuel Do not ue water! Cleaning the burner Clean the component of the burner a decribed below: Keep burner head clean Wearing part uch a e.g. oil filter, burner nozzle and gaket mut be checked and, if neceary, replaced. In any cae, we recommend the replacement of the oil nozzle before the tart of each heating eaon! The main oil filter i to be replaced (take care of flow direction) depending on the rate of pollution, but at leat before the tart of every heating period The oil filter in the filler neck of the fuel tank i to be cleaned regularly Only have the gauze filter in the fuel pump cleaned and the burner nozzle replaced by authoried ervice peronnel Check afety device regularly. In the cae of reducing heating capacity, formation of moke and/or bad ignition the unit i to be inpected and the burner i to be adjuted Oberve regular maintenance and care interval 1. Pull the photocell [1] from it mount [5] 2. Remove both ignition cable [2] 3. Looen the wivel nut [3] of the fuel line from the nozzle mount. Fuel may leak out! 4. Looen the wivel nut of the fuel line on the fuel pump and rotate the fuel line carefully to the ide. Remove both attachment crew of the aembly plate [4] and remove the burner from the burner chamber. 5. Clean the park plug [6], the oil nozzle, [7] the air flow plate and the opening for light [5]. 6. Check the park plug [6] etting to enure that they match the guideline value. 7. After ervice work, reaemble all part again carefully in the revere order Make ure that opening {5] i not overhadowed by the air flow plate. Attachment crew of the air flow plate [7] above and between the park plug. Adjutment value of the park plug 2-3 All meaurement are guideline in mm. The air throughput may only be adjuted to local condition. Only ue uitable tool to take apart the burner nozzle and apply counter-preure on the nozzle connection rod!

12 REMKO ATK Adjuting the air lide plate The air lide plate i et at the factory. The air throughput may only be adjuted to local condition by authoried peronnel. After the clamp crew [K] i a looened, the air lide plate can be adjuted uing the exhaut meaurement. Burner head ca. 3,5 mm Cleaning the fuel tank Slide plate CO 2 - value: approx %; Soot number: 0-1 lt. Bacharach K n If the main filter frequently become dirty n If condenation water accumulate in the fuel Pleae proceed in the following way when cleaning the fuel tank: 1. Uncrew the dicharging crew [D] and dicharge the fuel into a uitable veel. 2. Rine the container everal time if neceary with clean fuel thoroughly. Do not ue water! 3. Pleae ue no cleaning agent which contain olvent. Thee can detroy the inner layer of the tank! 4. Avoid the ue of high-preure cleaner. 5. Fit the dicharging crew [D]. The gaket ring [E] hould be replaced after each diaembly! 6. Fill tank with clean fuel. Do not ue biodieel! Exhaut Meaurement On account of the contructiondependent deign of the exhaut connection (connection nozzle with econdary air opening), it i not poible to perform a correct exhaut analyi in a conventional manner in the exhaut pipe behind the exhaut connection. For the performance of the exhaut analyi the enor of the exhaut-meaurement device mut be placed in the centre of the pipe ocket of the heat exchanger. The meaurement enor i placed through the appropriate lateral econdary air opening in the exhaut connection in the exiting meaurement opening in the pipe nozzle of the combution chamber (ee drawing below). Note for implementing the 1t. BImSchV Unit that are not expected to be operated for longer than 3 month in the ame location are not ubject to any approval or monitoring a per the 1t. BImSchV. Exhaut connection 7. Start unit and let it run for approx. 5 minute. 1 2 E D It i neceary to clean the fuel tank: n After each heating period or, depending on the deployment condition, even earlier n Before and after extended idle period 12 3 Legend: 1 = Exhaut connection 150 ø 2 = Pipe ocket / Heat exchanger 3 = Auxiliary air opening 4 = Meaurement Senor 4

13 Fuel Pump The tandard type of the pump run in a ytem of 1 pipe. The required fuel i ucked in through the uction line S. For the firt tarting and after having emptied the fuel tank, the fuel ytem i deaerated through the burner nozzle. For thi purpoe the unit i witched on. After a poible witch off through failure, the unit i retarted after having releaed the automatic burner relay (take care of waiting time). If, after the 3rd tart of the unit there i another witch off through fault, the fuel filter hould be checked to make ure that they are free from pollution and that they are tight.. Pleae enure that an adequate fill level i maintained in the fuel tank. Approx litre of fuel i required. Converting to a 2-way pipe ytem In thi cae, an additional topper [T],EDP No mut be intalled. 1. Remove topper [U] 2. Screw in topper [T] 3. Reintall topper [U] 4. Etablih return flow [R] T Setting the pump preure The pump preure can only be et if a manometer i connected to the connection [P]. The pump preure i changed by turning the preure etting crew [A]. Clockwie: increae the preure Counter clockwie: reduce the preure The required pump preure i determined according to the heating capacity (pleae refer to unit type plate) and to the nozzle ize. CAUTION P A U Never let the pump run without feeding fuel for a longer period. Make ure not to leave a unit with dry run pump unattended for a longer time. S Cleaning the cartridge filter Regularly clean the cartridge filter [B] of the fuel pump and replace it a neceary. 1. Turn the plug [C] with a hexagonal wrench and take it out of the pomp at the top. 2. Carefully pull the cartridge filter [B] out of the plug. 3. Clean or replace the filter [B]. 4. Pre the filter back onto the plug and crew both of them back into the pump. Adjutment and maintenance work may only be carried out by authoried qualified technician. C B R S U Perfect fuel quality i an abolute neceity for the lubrication of the pump drive. Suction of water reidue hould never take place and, in the cae of etting, uction hould not take place of warping fine dut (e.g. cement etc.). CAUTION An electrical afety check mut be carried out in accordance with VDE 0701 after any work on the unit. 13

14 REMKO ATK Cutomer Service and Guarantee For the guarantee to be valid, the cutomer mut completely fill out the guarantee certificate encloed with all heating unit and end it back to REMKO GmbH & Co. KG in a timely manner after purchaing of the unit and putting it into operation. The unit have undergone everal tet to enure proper functioning at the factory. If there are till malfunction that cannot be fixed by the operator uing the troublehooting intruction, pleae contact your dealer or contract partner. Intendend ue Due to their conception and equipping, the device are deigned olely for heating and ventilation purpoe in indutrial or commercial ue (no private living area heating). The unit may be operated only by accordingly trained peronnel. The manufacturer i not liable for damage that occur due to nonobervance of manufacturer intruction or the legal requirement or due to unauthoried change to the device. Another operation other than that decribed in thee operating intruction i not permitted. Nonobervance lead to the extinguihment of any liability and warranty claim. Wiring Diagram Legend: BS = Operating witch C = Capacitor F = Fue FZ = Photo cell HS = Auxiliary relay M = Fan motor MV = Solenoid valve NK = Nachkühlthermotat RS = Relay ocket RT = Thermotat ocket STB = Safety temperaturelimiter THZ = Tank heating with thermotat ZE = Ignition electrode ZT = Ignition tranformer 14

15 Troublehooting Trouble: Caue: Fan motor doe not tart Fan motor i running but burner will not be ignited. Unit hut down without flaming formation. Unit top during operation. (fault indicator lamp of the automatic burner relay light up) Smoke forming at the blow-out cone Unit can t be witched off CAUTION Setting and maintenance i to be carried out only by authoried expert! Trouble: 1. Air (bubble) in the fuel ytem during tarting procedure. Remedy: Pre fault clearance button of the automatic burner relay, repeat if neceary (max. 3 x). 2. No electrical connection. Check main, main plug and current. 3. No (bridge circuit-/thermotat-) plug in the thermotat ocket. Connect bridge circuit plug rep. thermotat plug with the thermotat ocket. 4. Thermotat etting i too low. Set thermotat higher than the room temperature. 5. Fault indicator lamp of the automatic burner relay light up. Unlock the automatic burner relay by preing the reet button. 6. Fault in the automatic burner relay. Replace automatic burner relay. 7. Fan motor i overcharged. (Fan blow irregularly or i blocked). Let motor cool down. Check light run of fuel pump. Check motor on electrical and mechanical function. 8. Fuel pump i blocked. Check rep. replace fuel pump. 9. Fuel tank i empty. Fill fuel tank with clean fuel. 10. Fuel filter i blocked (dirty).. Clean fuel filter rep. replace if neceary. 11. Nozzle i blocked rep. wrong dimenion (type/ize). Replace nozzle (take care of correct type and ize!). 12. Wrong etting of ignition electrode or damaged inulation. Adjut correctly rep. replace it. 13. Air flow plate of the burner head i miadjuted rep. dirty. 14. Solenoid valve doe not open. Adjut correctly by mean of CO 2 indicator and oot pump (CO 2 : %, oot figure by Bacharach: 0 1). Check olenoid valve rep. replace if neceary. The afety temperature limiter ha releaed / i defective. 15. Miadjuted pump preure. Set pump preure by mean of a preure-gauge. 16. Pump clutch i defective. Replace pump clutch. 17. Leakage in uction pipe or in fuel filter. Check uction pipe and fuel filter, replace if neceary. 18. Solenoid valve doe not cloe. Pull off the fuel pipe from the main filter - the flame die. 19. Air protecting grille i dirty. Clean air protecting grille. 20. Diconnection by the afety temperature limiter (STB). 21. Air (bubble) in the fuel ytem. Check air protecting grille, clean if neceary. Releae the STB and the automatic burner relay No adequate ventilation. Open door or window. Retart the unit in order to dicharge the air through the nozzle. (Thi procedure can be repeated up to max. 3 time). 23. Photo cell i dirty rep. defective. Clean photo cell rep. replace if neceary. 24. Improper exhaut ytem. See chapter Exhaut ytem. 25. Operating witch not functioning. Check operating witch rep. replace if neceary. 26. Fuel with paraffin accumulation. Clean the entire fuel ytem. See chapter Commiioning. 15

16 REMKO ATK Exploded View 16 We reerve the right to make modification in dimenion and contruction in the interet of technical progre.

17 Spare Part Lit No. Decription EDP-No. No. Decription EDP-No. 01 Exhaut connection Side cover, left Inpection cover Retaining ring Inpection cover Wheel cap Gaket (inpection cover) Tranport handle, front Combution chamber cpl Wheel Air lide plate Fuel tank Air flow plate Rubber grommet Nozzle Filler cap Holder (nozzle) Fuel filter Mounting plate Tranport handle Ignition electrode Gaket ring Ignition cable Drain crew Nut M Tank heating Photo cell cable Cover (tank heating) Photo cell Eectric board cpl Recool thermotat, Ignition tranformer Protecting grille Terminal trip cpl Mounting clip Mounting Fan blade Relay ocket Fan houing Automatic burner Air baffle plate, right Locking crew (PG-plate) Air baffle plate, left O-ring eal Protective ocket Cover with mounting plate Houing bae Fue Mounting clip Connecting cable with plug Blow-out cone Thermotat ocket Bracket STB feeler Bridge circuit plug Mounting clip STB feeler Operating witch I Fuel hoe L Safety temperature-limiter (STB) Hoe clamp Auxiliary relay Fuel filter (one-way) Photo cell bracket Cover (filler neck) Solenoid valve cpl. (Danfo) Protective ocket Connecting nipple 1/ Connection cable (olenoid valve) Oil preure pipe (flex) Fuel pump cpl Connecting nipple 1/ Solenoid Oil hoe L Pump clutch Burner head Capacitor Protective conductor plug flag Fan motor cpl Not hown: 52 Cover, front / back Thermotat plug Side cover, right Cartridge filter for oil pump When ordering pare part pleae indicate ref.-no. and machine no. (ee type plate)! 17

18 REMKO ATK Maintenance log Model... Model No.... Clean unit urface Clean unit interior Clean fan blade Clean fan houing Clean condener Clean evaporator Fan function checked Intake grille with filter cleaned Check unit for damage Protective device checked All fixing crew checked Electrical afety tet Tet run Remark: Date Date Date Date Date Date Date Date Date Date Date Date Date Date Date Date Date Date Date Date... The unit mut only be erviced by authoried pecialit in compliance with the tatutory requirement. 18

19 Technical Data Model ATK 25 Nominal heat output max. kw 25,00 Nominal heat output kw 22,50 Air output m 3 /h 1080 Increae of temperature Δ t K 70 Fuel 1) unit incluive tank heating 2) noie meauring according DIN KL 3 Heating oil EL or Dieel Fuel conumption, max. l/h 2,45 Nozzle (Danfo) 80 H USG 0,50 Pump preure approx. bar 11 to 12 Tank capacity Ltr. 40 Electrical connection 1~ V 230 Frequency Hz 50 Rated current max. A 2,3 Power conumption max. 1) kw 0,43 Fue protection (required) A 10 Sound preure level LpA 1m 2) db(a) 74 Exhaut connection ø mm 150 Dimeniom: Length mm 1265 Width mm 470 Height mm 685 Weight kg 68 We reerve the right to make modification in dimenion and contruction in the interet of technical progre. 19

20 REMKO INTERNATIONAL and omewhere near you! Take advantage of our experience and conulting ervice Conulting Through intenive training, we make ure the expert knowledge of our conultant i alway up-to-date. Thi ha given u the reputation of being more than jut a good, reliable upplier: REM- KO, a partner that help olve problem. Sale REMKO not only provide an extenive ale network in Germany and abroad, but alo unuually highly qualified ale expert. REMKO ale repreentative are more than jut alepeople: they mut alo be cutomer conultant in air conditioning and heating technology. REMKO GmbH & Co. KG Air conditioning and heating technology Cutomer care Our device function preciely and reliably. If a malfunction appear, however, REMKO Cutomer Care i on the job. Our extenive network of experienced dealer guarantee you contant, hortterm, and reliable ervice. Im Seelenkamp 12 D Lage Potfach 1827 D Lage Telephone Telefax info@remko.de Webite Subject to technical change!

INT 69 YF Diagnose. Application. Functional description

INT 69 YF Diagnose. Application. Functional description INT 69 YF Diagnoe Application The motor protector INT69 YF Diagnoe i a univeral and veratile protection unit. For the monitoring of electrical component, variou input for temperature, voltage, leakage/reitance

More information

THE QPL UFH EXTENSION KIT

THE QPL UFH EXTENSION KIT THE QPL UFH EXTENSION KIT The Qual-PEX underfloor heating ytem i perfectly uited to a ingle area extenion up to 40qm in floor area. It i deigned to link into an exiting radiator heating ytem or alternatively

More information

REMKO DZH. Oil Heaters. Operation Technology Spare Parts. Edition GB D04

REMKO DZH. Oil Heaters. Operation Technology Spare Parts. Edition GB D04 REMKO DZH Oil Heaters Operation Technology Spare Parts Edition GB D04 Contents Safety Notices 4 Device Description 4 Mounting Regulations 5 Commissioning 6 Shutdown 7 Maintenance and Care 8 Trouble Shooting

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual PRODUCT MANUAL TR200009.r1 Stainle Steel Range SSB, SSI and SST Serie Intallation, Operation and Maintenance Manual P R A C T I C A L, E F F I C I E N T & S U S TA I N A B L E BUILDING SERVICES SOLUTIONS

More information

F890. Relcom Installation Instructions. 8 Segment Redundant Fieldbus Power Supply for use with non-proprietary cabled systems

F890. Relcom   Installation Instructions. 8 Segment Redundant Fieldbus Power Supply for use with non-proprietary cabled systems F890 8 egment Redundant Fieldbu Power upply for ue with nonproprietary cabled ytem F890P Intallation Intruction Relcom www.mtlfieldbu.com CONTENT PAGE 1 OVERVIEW 1 2 DECRIPTION 1 3 COMPONENT AND ACCEORIE

More information

Building Technologies Division

Building Technologies Division 7 154 Burner control LMO39... Burner control for the uperviion of 1- or 2-tage oil burner of mall to medium capacity, with or without fan in intermittent operation. The LMO39 and thi Data Sheet are intended

More information

Stainless Steel Range

Stainless Steel Range PRODUCT MANUAL TR200009.r2 Stainle Steel Range SSB, SSI, and SST Intallation, Operation, and Maintenance Manual PRACTICAL, EFFICIENT & SUSTAINABLE BUILDING SERVICES SOLUTIONS Warning Thi manual hould be

More information

Gas burner controls. Building Technologies HVAC Products

Gas burner controls. Building Technologies HVAC Products 7 106 Ga burner control LME39... Ga burner control for the uperviion of 1- or 2-tage ga burner of mall to medium capacity (typically up to 350 kw), in intermittent operation. The LME39 and thi Data Sheet

More information

FREE & FORCED CONVECTION HEAT TRANSFER

FREE & FORCED CONVECTION HEAT TRANSFER FREE & FORCED CONVECION HEA RANSFER Objective he objective of thi experiment are: (1) o demontrate the relationhip between power input and urface temperature in free convection (2) o demontrate the relationhip

More information

F892. Relcom Installation Instructions. 8 Segment Redundant Fieldbus Power Supply for use with non-proprietary cabled systems

F892. Relcom  Installation Instructions. 8 Segment Redundant Fieldbus Power Supply for use with non-proprietary cabled systems F892 8 egment Redundant Fieldbu Power upply for ue with nonproprietary cabled ytem F892P Intallation Intruction Relcom www.mtlfieldbu.com CONTENT PAGE 1 OVERVIEW 1 2 DECRIPTION 1 3 COMPONENT AND ACCEORIE

More information

Sinumerik 808D Service Guide

Sinumerik 808D Service Guide Training manual Sinumerik 808D Service Guide Verion 2013-01 Note Service guide 808D Lit For Service cae of hardware Go to page 7 Service cae of For Go to page 23 PLC alarm For Service cae of NC program

More information

REMKO CLK Mobile automatic heater

REMKO CLK Mobile automatic heater REMKO CLK Mobile automatic heater Operation Technology Spare Parts Edition GB M04 REMKO - powerful like a bear. Operating Instructions Read these instructions carefully before setting up/operating the

More information

Gas Burner Controls. Building Technologies HVAC Products

Gas Burner Controls. Building Technologies HVAC Products 7 106 Ga Burner Control LME39... Ga burner control for the uperviion of 1- or 2-tage ga burner of mall to medium capacity (typically up to 350 kw), in intermittent operation. The LME39 and thi Data Sheet

More information

Propane Heater REMKO PGM 30 REMKO PGM 60

Propane Heater REMKO PGM 30 REMKO PGM 60 Propane Heater REMKO PGM 30 REMKO PGM 60 Operation Technology Spare Parts Edition GB L07 REMKO strong as a bear. Operating instructions Make sure to read these instructions carefully before starting/using

More information

Gas burner controls. Building Technologies

Gas burner controls. Building Technologies 7 106 Ga burner control LME39... Burner control for the uperviion of 1- or 2-tage ga or ga burner of mall to medium capacity, with or without fan in intermittent operation. The LME39 and thi Data Sheet

More information

Bulk Handling of Paraplex and Plasthall Plasticizers

Bulk Handling of Paraplex and Plasthall Plasticizers Bulk Handling of Paraplex and Plathall Platicizer Buying and handling platicizer in bulk i attractive becaue the reulting cot per pound i alway lower than the cot in drum quantitie. Other advantage include

More information

Building Technologies Division Infrastructure & Cities Sector

Building Technologies Division Infrastructure & Cities Sector Ditribuitor: FLAE POWER SRL 021-3121727 ; 0744-340566 contact@arzatoare.ro ; www.arzatoare.ro 7 106 Burner control LE39... Burner control for the uperviion of 1- or 2-tage ga or ga / oil burner of mall

More information

United States Patent (19)

United States Patent (19) United State Patent (19) Hopkin (11 Patent Number: () Date of Patent: Aug. 23, 1988 54 MICROWAVE HIGHWAY PAINT DRYING APPARATUS 76 Inventor: Harry C. Hopkin, Rte. 5, Box 883, Williamton, N.C. 27892 (21)

More information

PANIC EXIT HARDWARE DX-200 Serie

PANIC EXIT HARDWARE DX-200 Serie PANIC EXIT HARDWARE DX-200 Serie Explanation of European tandard The tandard EN 1125 and EN 179 were created at the European level with the acceptance and cooperation of the Dutch tandard committee. The

More information

1/2" [15mm] HANGER ROD SECURED TO STRUCTURE ABOVE (TYP) BOSS FOR HANGER ROD WELDED. [1200mm] CC SPACING (TYP)

1/2 [15mm] HANGER ROD SECURED TO STRUCTURE ABOVE (TYP) BOSS FOR HANGER ROD WELDED. [1200mm] CC SPACING (TYP) 1/2" [15mm] HANGER ROD ECURED TO TRUCTURE ABOVE (TYP) TURNBUCKLE (TYP) PREFAB. CEILING PANEL A PECIFIED BO FOR HANGER ROD WELDED TO CHANNEL. MAX. 4'-0" [1200mm] CC PACING (TYP) 3" [75mm] 5 U CHANNEL LOCATED

More information

REMKO CLK 20 Mobile Heaters

REMKO CLK 20 Mobile Heaters REMKO CLK 20 Mobile Heaters Operation Technology Spare Parts Edition GB M08 REMKO powerful like a bear Operating Instructions Before commissioning/use of the equipment, these operating instructions must

More information

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80 IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80 EN OPERATING MANUAL OIL HEATER TRT-BA-IDE20-30-50-60-80-TC-001-EN Table of contents Information on the use of this manual... 1 Scope of delivery... 1 General safety...

More information

Temperature and humidity ranges. Operating the GC within the recommended ranges insures optimum instrument performance and lifetime.

Temperature and humidity ranges. Operating the GC within the recommended ranges insures optimum instrument performance and lifetime. Temperature and humidity range Operating the GC within the recommended range inure optimum intrument performance and lifetime. Recommended temperature range 20 to 27 C 5 to 40 C Temperature range Recommended

More information

Vista Underground Distribution Switchgear Outdoor Distribution. Pull Box Specifications for UnderCover Style

Vista Underground Distribution Switchgear Outdoor Distribution. Pull Box Specifications for UnderCover Style Vita Underground Ditribution Outdoor Ditribution Pull Box Specification I. GENERAL 1.1 The pull box for the witchgear hall be deigned, detailed, and fabricated in accordance with the requirement of thi

More information

(12) Patent Application Publication (10) Pub. No.: US 2009/ A1

(12) Patent Application Publication (10) Pub. No.: US 2009/ A1 (19) United State US 20090266567A1 (12) Patent Application Publication (10) Pub. No.: US 2009/0266567 A1 Muer, JR. (43) Pub. Date: Oct. 29, 2009 (54) FIRE SUPPRESSION DEVICE (76) Inventor: John E. Muer,

More information

25iSA. United States Patent (19) 4,614,303. Sep. 30, Moseley, Jr. et al.

25iSA. United States Patent (19) 4,614,303. Sep. 30, Moseley, Jr. et al. United State Patent (19) Moeley, Jr. et al. (54) 76) 21 22 (51) 52) (58) (56) WATERSAVING SHOWER HEAD Inventor: Charle D. Moeley, Jr., P.O. Box 449, Lynchburg, Va. 2; Charle D. Waring, 3952 Boworth Dr.

More information

DH-Direct Fired Poultry Farm Diesel Heater

DH-Direct Fired Poultry Farm Diesel Heater DH-Direct Fired Poultry Farm Diesel Heater Comparison of Diesel Heater to Gas Heater Diesel LPG Gas LPG Gas KW 43 70 120 Fuel consumption/hr 3 5.1 8.8 Heat output 37000 60000 100000 Cost of fuel/lit or

More information

REMKO CLK CLK 30, CLK 50, CLK 70, CLK 120, CLK 150

REMKO CLK CLK 30, CLK 50, CLK 70, CLK 120, CLK 150 REMKO CLK CLK 30, CLK 50, CLK 70, CLK 120, CLK 150 Automatic oil/gas heaters Operation Technology Spare parts Edition GB I12 Contents Safety notes 4 Unit description 4 Specifications for fan-assisted

More information

Oper at ion Technology

Oper at ion Technology CLA 25-100 Aut omat i c Oil/ Gas Heat er s Edit ion GB- 709 Oper at ion Technology Or iginal REM KO Spar e Par ts REM KO - alles bär enst ar k. Oper at ing inst r uct ions Make sure to read these instructions

More information

RTU 02 S x14. 16x16. 18x20 RTU x20. 10x14 S-1. MAU 01 12x12

RTU 02 S x14. 16x16. 18x20 RTU x20. 10x14 S-1. MAU 01 12x12 YMBOL & ABBREV. T D Ø DL UC M E ME A/UP RA/RET EA/EH CD/R RR/RG ER/EG FC MVD FD (L) FLE T-TAT T-TAT D DIA. DL UC UPPLY AIR (RIE/DROP) RETURN AIR DUCT (RIE/DROP) EHAUT AIR DUCT (RIE/DROP) CEILING DIFFUER/UPPLY

More information

Measuring & Order Guide

Measuring & Order Guide Meauring & Order Guide SIMPLE STEPS TO A BRAND NEW VIEW Our meauring guide will take you through the tep you need to meaure your window. Jut a few imple meaurement are all you ll need and if you d like

More information

General. Mode of operation and application. Input

General. Mode of operation and application. Input Dataheet for SITRANS P DSIII / P410 GAUGE PRESSURE SITRANS P DS III / P410, HART,4-20 ma tranmitter for preure 7MF40331BA101NC6 General Manufacturer Supplier Product deignation Brand name Type deignation

More information

Instruction Manual RK 25 - RKR 25. for models. Premix condensing boiler CE Installation, operating, commissioning and maintenance instructions.

Instruction Manual RK 25 - RKR 25. for models. Premix condensing boiler CE Installation, operating, commissioning and maintenance instructions. Instruction Manual for models RK 25 - RKR 25 Premix condensing boiler EDBUK BAND A GA COUNCIL NUMBER: RK 25: 41-651-15 RKR 25: 41-651-14 Installation, operating, commissioning and maintenance instructions.

More information

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL

Heating, Air Conditioning, Ventilation. Отопление-Кондиционеры-Вентиляция. MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL Heating, Air Conditioning, Ventilation Отопление-Кондиционеры-Вентиляция MTM 8-30 kw UNIVERSAL OIL HEATER OPERATING MANUAL 1. Usage MTM 8-30 universal oil heater is designed for heating commercial rooms

More information

United States Patent (19)

United States Patent (19) United State Patent (19) Thompon (54) Two STAGE COOLING TOWER 75 Inventor: Tommy L. Thompon, Tucon, Ariz. 73 Aignee: Planetary Deign Corporation, Tucon, Ariz. (21) Appl. No.: 505,767 (22 Filed: Apr. 6,

More information

(12) Patent Application Publication (10) Pub. No.: US 2004/ A1

(12) Patent Application Publication (10) Pub. No.: US 2004/ A1 (19) United State US 2004O144124A1 (12) Patent Application Publication (10) Pub. No.: US 2004/0144124 A1 Bottom (43) Pub. Date: Jul. 29, 2004 (54) RETAIL BANANA STORAGE UNIT (76) Inventor: Kenneth H. Bottom,

More information

Tenney Seri LRE.com

Tenney Seri LRE.com 800-574-2748 LRE.com Tenney Seri 1111 -------,------- The Tenney Serie Chamber employ leading edge technology to upply our cutomer with the mot efficient and environmentally friendly tet equipment poible.

More information

~,~. June 10, ,838,077 A VG.. 2. AOy A. COOAA4. Filed Oct. 20, 1954 R. L. COOFPER. 9 Sheets-Sheet DISPENSING MACHINE FOR BEWERAGES

~,~. June 10, ,838,077 A VG.. 2. AOy A. COOAA4. Filed Oct. 20, 1954 R. L. COOFPER. 9 Sheets-Sheet DISPENSING MACHINE FOR BEWERAGES June 10, 1958 Filed Oct. 20, 1954 R. L. COOFPER DISPENSING MACHINE FOR BEWERAGES 2,838,077 9 Sheet-Sheet D --------- ~,~. N A VG.. 2 AOy A. COOAA4 INVENTOR June 10, 1958 R. L. COOPER 2,838,077 DISPENSING

More information

A HOLLOW FIBER MEMBRANE-BASED LIQUID DESICCANT AIR DEHUMIDIFICATION SYSTEM FOR SOLAR ENERGY RECLAMATION

A HOLLOW FIBER MEMBRANE-BASED LIQUID DESICCANT AIR DEHUMIDIFICATION SYSTEM FOR SOLAR ENERGY RECLAMATION SASEC01 Third Southern African Solar Energy Conference 11 13 May 01 Kruger National Park, South Africa A HOLLOW FIBER MEMBRANE-BASED LIQUID DESICCANT AIR DEHUMIDIFICATION SYSTEM FOR SOLAR ENERGY RECLAMATION

More information

DF400/DF600. Construction Heaters. Installation and Maintenance Manual

DF400/DF600. Construction Heaters. Installation and Maintenance Manual 342 N. Co. Rd. 400 East Valparaiso, IN 46383 219-464-8818 Fax 219-462-7985 www.heatwagon.com Installation and Maintenance Manual Please retain this manual for future reference. DF400/DF600 Construction

More information

Owner s Manual ! WARNING PLUS 95S - MODEL 355CAV DIRECT VENT 4 -WAY MULTIPOISE MODULATING CONDENSING GAS FURNACE WITH PERFECT SENSET PERFECT HUMIDITYT

Owner s Manual ! WARNING PLUS 95S - MODEL 355CAV DIRECT VENT 4 -WAY MULTIPOISE MODULATING CONDENSING GAS FURNACE WITH PERFECT SENSET PERFECT HUMIDITYT PLU 95 - MODEL 355CAV DIRECT VENT 4 -WAY MULTIPOIE MODULATING CONDENING GA FURNACE WITH PERFECT ENET PERFECT HUMIDITYT Owner s Manual NOTE TO INTALLER: THI MANUAL MUT BE LEFT WITH THE EQUIPMENT UER. UER:

More information

NODIA AND COMPANY. Model Test Paper - I GATE Refrigeration and Air Conditioning. Copyright By Publishers

NODIA AND COMPANY. Model Test Paper - I GATE Refrigeration and Air Conditioning. Copyright By Publishers No part of thi publication may be reproduced or ditributed in any form or any mean, electronic, mechanical, photocopying, or otherwie without the prior permiion of the author. Model Tet Paper - I GATE

More information

SI 3080 / SI 3100 / SI 3200

SI 3080 / SI 3100 / SI 3200 SI 3080 / SI 3100 / SI 3200 Mini pump for air conditioner up to 10 kw (SI 3080 & SI 3100) and up to 20 kw (SI 3200) SILENCIEUSES SILENT o Integral quick / connector plug Anti-vibration mount SI 3080 SI

More information

infrared paraffin / kerosene / diesel heater

infrared paraffin / kerosene / diesel heater instructions for infrared paraffin / kerosene / diesel heater model no: IR20.V3 Thank you for purchasing a Sealey product. Manufactured to a high standard, this product will, if used according to these

More information

REMKO AMT 45-E to 115-E

REMKO AMT 45-E to 115-E REMKO AMT 45-E to 115-E Air dehumidifiers Operation Technology Spare parts Edition GB D09 Contents Air dehumidification 4 Safety notes 6 Intended use 7 Customer service and guarantee 7 Environmental protection

More information

Oil burners Brûleurs fioul Stookoliebranders

Oil burners Brûleurs fioul Stookoliebranders Installation, use and maintenance instructions Manuel d entretien Installatie-, gebruiks- en onderhoudsvoorschriften GB F NL Oil burners Brûleurs fioul Stookoliebranders One stage operation Fonctionnement

More information

REMKO AMT 60-E - 90-E Mobile Dehumidifier

REMKO AMT 60-E - 90-E Mobile Dehumidifier REMKO AMT 60-E - 90-E Mobile Dehumidifier Operation Technology Spare Parts Edition GB M02 REMKO powerful like a bear. Operating Instructions Make sure to read these instructions carefully before starting/using

More information

Light oil burners. One stage operation

Light oil burners. One stage operation Installation, use and maintenance instructions Light oil burners One stage operation CODE MODEL TYPE 3505 RDB CF 38 50 T3 350050 RDBR CF 6 50 TR 35050 RDBR CF 33 50 TR 35050 RDBR CF 38 50 T3R 350650 RDBR

More information

PRAIRIE VIEW A&M UNIVERSITY AUSTIN GREAUX ENGINEERING BUILDING CHANCELLOR'S RESEARCH INITIATIVE RENOVATION PRAIRIE VIEW, TEXAS 77445

PRAIRIE VIEW A&M UNIVERSITY AUSTIN GREAUX ENGINEERING BUILDING CHANCELLOR'S RESEARCH INITIATIVE RENOVATION PRAIRIE VIEW, TEXAS 77445 C C C PRAIRIE VIEW A&M UNIVERITY GENERAL NOTE: THE INTENT I TO HAVE NO EXPOED WIRING, CONDUIT OR CABLE ON WALL OR IN OPEN CEILING. ARCHITECT I URRING OUT WALL WHERE VERTICAL CONDUIT RUN ARE NEEDED. I THERE

More information

Boiler Manual. Installation Instructions Commissioning Instructions Maintenance Instructions Commissioning Certificate Service Record

Boiler Manual. Installation Instructions Commissioning Instructions Maintenance Instructions Commissioning Certificate Service Record Boiler Manual Incorporating: User Instructions Installation Instructions Commissioning Instructions Maintenance Instructions Commissioning Certificate ervice Record High Efficiency Condensing Gas Boilers

More information

Operating instructions

Operating instructions Operating instructions (Translation of the original operating instructions) Type TEKA FILTERCUBE-MV TEKA Absaug- und Entsorgungstechnologie GmbH Industriestraße 13 D-46342 Velen Postfach 1137 D-46334 Velen

More information

Parts Available from

Parts Available from Montage und Bedienungsanleitung Manuel d entretien Installation, use and maintenance instructions Installatie-, gebruiks- en onderhoudsvoorschriften Oδηγίες εγκατάστασης, χρήσης και συντήρησης D F GB NL

More information

For internal use only. Distribution (please mark): Product Solution Multi-channel x

For internal use only. Distribution (please mark): Product Solution Multi-channel x For internal ue only Building Technologie Fire Safety & Security Product Ditribution (pleae mark): Product family Product name: Order-No: Sinteo TM, AlgoRex, Synova 600 FDBZ292 Air ampling moke detection

More information

Light oil / kerosene burner

Light oil / kerosene burner Installation, use and maintenance instructions Light oil / kerosene burner One stage operation CODE MODEL TYPE 374445 G5 444T50 290238 (5) - 05/20 TECHNICAL DATA Thermal power output 28 60 kw 2.3 5 kg/h

More information

CATERING SPARES. T: W:

CATERING SPARES. T: W: CATERING SPARES T: 0845 688 7122 W: www.undercontrol.co.uk At Under Control Intrument we are upplier of catering equipment and pare. We are upplier to many catering equipment manufacture, re-eller and

More information

OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25

OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25 OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25 NOT FOR DOMESTIC USE SPACE HEATING ONLY Made By: Spitwater Australia Pty Ltd 953 Metry St North Albury, NSW, Australia

More information

1. GENERAL SAFETY RULES

1. GENERAL SAFETY RULES ID180 & ID290 Indirect-Fired Diesel/Oil Construction Heaters Sure Flame Products Lethbridge, Alberta, Canada Telephone: (403)328-5353 Fax: (403)328-9956 www.sureflame.ca July 12, 2006 Service and Maintenance

More information

model No: ir20.v2 FUSE

model No: ir20.v2 FUSE InstructioNS for: model No: ir20.v2 INFRARED PARAFfIN / KEROSENE / diesel HEATER 70000Btu 230V Thank you for purchasing a Sealey product. Manufactured to a high standard this product will, if used according

More information

Installation and Maintenance Manual Please retain this manual for future reference.

Installation and Maintenance Manual Please retain this manual for future reference. 342 N. Co. Rd. 400 East Valparaiso, IN 46383 219-464-8818 Fax 219-462-7985 www.heatwagon.com Installation and Maintenance Manual Please retain this manual for future reference. Electric Construction Heaters

More information

Instruction Manual for model

Instruction Manual for model Instruction Manual for model RKA 100 Premix condensing boiler with storage cylinder EDBUK BAND A GA COUNCIL NUMBER: 47-651-22 Installation, operating, commissioning and maintenance instructions. CE 0694

More information

INFRARED PARAFfIN / KEROSENE / model No: ir20.v2 1. SAFETY INSTRUCTIONS RECOMMENDED FUSE RATING: 5AMP

INFRARED PARAFfIN / KEROSENE / model No: ir20.v2 1. SAFETY INSTRUCTIONS RECOMMENDED FUSE RATING: 5AMP InstructioNS for: INFRARED PARAFfIN / KEROSENE / diesel HEATER model No: ir20.v2 Thank you for purchasing a Sealey product. Manufactured to a high standard this product will, if used according to these

More information

Product Manual Glue Applicators MS 80 and MS 200

Product Manual Glue Applicators MS 80 and MS 200 Product Manual www.pakarte.com Glue Applicators MS 80 and MS 00 Translation from German to English Table of Contents Product Description General Safety Instructions Safety Measures to be taken during Operation

More information

FTM-L SERIES SINGLE OR TWIN DIRECT STEAM MIXER KETTLE COMPLETE WITH HYDRAULIC POWER TILT BRIDGE INSTALLATION - OPERATION - MAINTENANCE

FTM-L SERIES SINGLE OR TWIN DIRECT STEAM MIXER KETTLE COMPLETE WITH HYDRAULIC POWER TILT BRIDGE INSTALLATION - OPERATION - MAINTENANCE FTM-L ERIE INGLE OR TWIN DIRECT TEAM MIXER KETTLE COMPLETE WITH HYDRAULIC POWER TILT BRIDGE INTALLATION - OPERATION - MAINTENANCE INGLE MODEL FTM-40L FTM-60L FTM-80L FTM-100L TWIN MODEL FTM-(2)40L FTM-(2)60L

More information

Cycle Analysis and Turbo Compressor Sizing With Ketone C6F as Working Fluid for Water-Cooled Chiller Applications

Cycle Analysis and Turbo Compressor Sizing With Ketone C6F as Working Fluid for Water-Cooled Chiller Applications Purdue Univerity Purdue e-pub International Compreor Engineering Conference School of Mechanical Engineering 4 Cycle Analyi and Turbo Compreor Sizing With Ketone a Working Fluid for Water-Cooled Chiller

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

Thermo 230 / 231 / 300 / 301 / Troubleshooting

Thermo 230 / 231 / 300 / 301 / Troubleshooting Thermo 230 / 231 / 300 / 301 / 350 5 Troubleshooting 5 Troubleshooting 5.1 General This section describes troubleshooting procedures for the heaters Thermo 230, 231, 300, 301 and 350. CAUTION Troubleshooting

More information

Herringbone Linked Flue System

Herringbone Linked Flue System Herringbone Linked Flue ystem INTALLATION, ERVICING AND OPERATING INTRUCTION CBU09//5-HB, RU(ERU)5-HB, RU30/35/40/45-HB RL09//5-HB,RL5-HB, RL30/35/40/45-HB Gas Fired Products (UK) Ltd. Chapel Lane, Claydon,

More information

INSTALLATION GUIDE XR150/XR550 SERIES CANADIAN CONTROL PANEL

INSTALLATION GUIDE XR150/XR550 SERIES CANADIAN CONTROL PANEL INSTALLATION GUIDE XR150/XR550 SERIES CANADIAN CONTROL PANEL MODEL XR150CAN/XR550CAN Serie CANADIAN INSTALLATION GUIDE INDUSTRY CANADA NOTICE Thi Cla A digital apparatu complie with Canadian ICES-003.

More information

Models Vallox 096 MC R Vallox 096 MC L. Document D2609 MANUAL. Valid from Type Updated Manual.

Models Vallox 096 MC R Vallox 096 MC L. Document D2609 MANUAL. Valid from Type Updated Manual. Models Vallox 096 MC R Vallox 096 MC L Type 3721-1 Document D2609 Valid from 24.2.2017 Updated 12.2.201 MANUAL Manual Ventilation unit MAIN PART Extract air fan (behind the protective cover) upply air

More information

F-T, FT-P, F-L AND F-P SERIES

F-T, FT-P, F-L AND F-P SERIES F-T, FT-P, F-L AND F-P ERIE 2/3 JACKETED DIRECT TEAM TILTING & TATIONARY KETTLE INTALLATION - OPERATION - MAINTENANCE TILTING TRI-LEG TILTING PEDETAL TATIONARY TRI-LEG TATIONARY PEDETAL FT-L FT-30L FT-40L

More information

EEE. eff 4S5. see-tail 17, ESS SY. 1,33,779. Patented Aug. 19, 1919, QO \SYU. O (at J, E, BELL, FURNA CE, APPLICATION FLED AUG, 7, 1915, N Es NE N

EEE. eff 4S5. see-tail 17, ESS SY. 1,33,779. Patented Aug. 19, 1919, QO \SYU. O (at J, E, BELL, FURNA CE, APPLICATION FLED AUG, 7, 1915, N Es NE N J, E, BELL, FURNA CE, APPLICATION FLED AUG, 7, 1915, 1,33,779. Patented Aug. 19, 1919, HEE-HEET N E NE N Y. it i ae A i n N. 1 EEE. Y - 17, E eff 45 ee-tail () A er & it - it QO \YU. O (at 784%&é2eeze-

More information

(12) United States Patent (10) Patent No.: US 8,181,474 B2

(12) United States Patent (10) Patent No.: US 8,181,474 B2 US008181474B2 (12) United State Patent (10) Patent No.: US 8,181,474 B2 Chen (45) Date of Patent: May 22, 2012 (54) SOLAR-POWERED AIR CONDITIONER RE34,542 E * 2/1994 Rockenfeller... 165,104.12 USING AMIXTURE

More information

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A cod. 6272262A GENERAL DATA Heating Data Heat Output Input (Adjustable) (Adjustable) Format 34i 11.2 34KW 45 145MJ/hr Format 34e 11.2 34KW 45 145MJ/hr General Specifications FORMAT 34i 34e Main burner injectors

More information

Experimental Assessment on Performance of a Heat Pump Cycle Using R32/R1234yf and R744/ R32/R1234yf

Experimental Assessment on Performance of a Heat Pump Cycle Using R32/R1234yf and R744/ R32/R1234yf Purdue Univerity Purdue e-pub International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Experimental Aement on Performance of a Heat Pump Cycle Uing R32/R1234yf

More information

Simulation Model of an Automatic Commercial Ice Machine

Simulation Model of an Automatic Commercial Ice Machine Purdue Univerity Purdue e-pub International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Simulation Model of an Automatic Commercial Ice Machine Haithem Murgham Univerity

More information

Sinumerik 808D Commissioning Guide

Sinumerik 808D Commissioning Guide Training manual Sinumerik 808D Commiioning Guide Verion 2013-01 Note Commiioning Guide Page 2 808D Turning and Milling Workflow For Commiioning of Prototype Machine uing Sample PLC go to page 5 For Serie

More information

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING FLAME115 INFRARED HEATER SERVICE MANUAL INDEX 1. CONTROLS AND COMPONENTS 2. FLAME CONTROL CYCLES 3. MAINTENANCE SCHEDULE 4. TROUBLESHOOTING GUIDE 5. REPAIR PROCEDURES 1. FAN MOTOR ASSEMBLY 2. FUEL FILTER

More information

Installation & Maintenance Manual

Installation & Maintenance Manual Installation & Maintenance Manual MOL 200 S1L (B30A) Oil Burner 11/12 Tel: +44 (0) 1905 794331 Fax: +44 (0) 1905 794017 Email: info@nu-way.co.uk Web: www.nu-way.co.uk DESCRIPTION COMPONENTS 1. Shrouded

More information

User s Manual RA-3030SS RA-3036SS. NOTE: This unit was designed for indoor residential use and DUCTED operation only.

User s Manual RA-3030SS RA-3036SS. NOTE: This unit was designed for indoor residential use and DUCTED operation only. www.windsterhood.com User s Manual UNDER CABINET SERIES RA-3030SS RA-3036SS NOTE: This unit was designed for indoor residential use and DUCTED operation only. DO NOT USE OVER A WOOD GRILL OR MOUNT OUTDOOR

More information

HD 525 S 06/03 A ! 5.960

HD 525 S 06/03 A ! 5.960 HD 525 S 5 960 845 A2005225 06/03! Please read these operating instructions before starting and strictly observe the Safety Instructions for High Pressure Cleaners (5.951-949). WARNING DO NOT SPRAY ELECTRICAL

More information

Millo / Millo pro. Nr x000 / 1805-x000. Ideen für die Dentaltechnik A

Millo / Millo pro. Nr x000 / 1805-x000. Ideen für die Dentaltechnik A Millo / Millo pro Nr. 1804-x000 / 1805-x000 0609 21-6543 A Ideen für die Dentaltechnik 1 2 3 4 5 6 7 8 9 10 11 12 Millo / Millo pro No. 1804-x000 / 1805-x000 ENGLISH Content Introduction... 15 Symbols...

More information

IDE 20 D / IDE 30 D / IDE 50 D / IDE 60 D / IDE 100 D

IDE 20 D / IDE 30 D / IDE 50 D / IDE 60 D / IDE 100 D IDE 20 D / IDE 30 D / IDE 50 D / IDE 60 D / IDE 100 D EN OPERATING MANUAL OIL HEATER TRT-BA-IDE20D-30D-50D-60D-100D-TC-001-EN Table of contents Notes regarding the operating manual... 1 Safety... 2 Information

More information

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2 Cleaning unit for coolant :_decftez`_>r_fr] Book No.: 1271526-02 V2 Alfa Laval Separation AB Separator Manuals, dept. SKEL S-147 80 Tumba, Sweden Telephone: +46 8 53 06 50 00 Telefax: +46 8 53 03 10 40

More information

hp Dust Collector With Vacuum Attachment

hp Dust Collector With Vacuum Attachment Please dispose of packaging for the product in a responsible manner. It is suitable for recycling. Help to protect the environment, take the packaging to the local amenity tip and place into the appropriate

More information

TTV 4500 / TTV 4500 HP / TTV 7000

TTV 4500 / TTV 4500 HP / TTV 7000 TTV 4500 / TTV 4500 HP / TTV 7000 EN OPERATING MANUAL AXIAL FAN TRT-BA-TTV4500-4500HP-7000-TC-003-EN Table of contents The current version of the operating manual can be found at: Notes regarding the operating

More information

ST 40 Oil Burner. Installation & Maintenance Manual

ST 40 Oil Burner. Installation & Maintenance Manual ST 40 Oil Burner Installation & Maintenance Manual 178 093 13 Thank you for choosing a Nu-way burner. As you would expect from a Company who has a pedigree of more than 75 years in the heating industry,

More information

Operational Instructions. Glue Applicator MS Translation from German to English

Operational Instructions. Glue Applicator MS Translation from German to English Operational Instructions Glue Applicator MS 200 Translation from German to English Table of Contents Product Description 1 General Safety Instructions 2 Safety Measures to be taken during Operation 3 Start-up

More information

Operation Manual 322 KL

Operation Manual 322 KL Operation Manual 322 KL 8/07 von Oertzen GmbH Ferdinand-Harten-Str. 10 22949 Ammersbek Tel. +49 40 604110 Fax +49 40 6041149 www.oertzen-gmbh.de info@oertzen-gmbh.de Table of Content 1. Introduction Page

More information

Model No: Little Devil II (inc ss)

Model No: Little Devil II (inc ss) GAS HEATER Model No: Little Devil II (inc ss) PART NO: 6926020, 6926025 (SS) OPERATION & MAINTENANCE INSTRUCTIONS LS1213 INTRODUCTION Thank you for purchasing this CLARKE Gas Heater. Before attempting

More information

Operating Instructions

Operating Instructions Operating Instructions BA-003 Read and understand this manual before use. Keep this manual for future reference. CONFORMS TO UL STD.No.1017 Certified to CSA STD C22.2 No.243-10 For questions or concerns

More information

en Direct oil-fired space heaters HD... Operator's manual

en Direct oil-fired space heaters HD... Operator's manual 0211670en 002 12.2007 Direct oil-fired space heaters HD... Operator's manual Table of contents 1. Foreword 5 2. Safety information 6 2.1 General recommendations... 6 2.2 Safety devices... 7 2.3 Labels...

More information

Installation Instructions

Installation Instructions Electric Heater Kit For use with GB, GP and GT eries Geothermal Heat Pumps KWAEH0101N05 KWAEH0101N10 KWAEH0101F15 KWAEH0101F20 Installation Instructions NOTE: Read the entire instruction manual before

More information

MOBILE HOT AIR HEATING SYSTEMS

MOBILE HOT AIR HEATING SYSTEMS MOBILE HOT AIR HEATING SYSTEMS Issue 2012 Mobile hot air heating systems Mobile Heaters Heating Centers Quality with systems RAPID HEAT ADAPTED TO YOUR NEEDS Hot air heating systems for air, to feel good,

More information

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS INSTRUCTION MANUAL FOR OIL BURNER MODELS X400 Bio B10 E90-803-001-001-03 Rev 13-1 - Contents Technical specifications Technical data... 3 Working field... 3 Dimensions... 4 Head and electrode settings...

More information

UV Flame Supervision System

UV Flame Supervision System 7 783 UV Flame Supervision System DETACTOGYR LFE50 Series 02 ISO 9001 The LFE50 is a self-checking UV flame supervision system designed for use with continuously operating burners or for burners running

More information

Infrared Diesel Heater

Infrared Diesel Heater Infrared Diesel Heater Model No: IRD40 PART NO: 6920415 OPERATING & MAINTENANCE INSTRUCTIONS GC0812 INTRODUCTION Thank you for purchasing this CLARKE Diesel Infrared Heater. Before attempting to use the

More information

INSTALLATION, USE AND MAINTENANCE MANUAL MPE

INSTALLATION, USE AND MAINTENANCE MANUAL MPE GB INTALLATION, UE AND MAINTENANCE MANUAL MPE 4 kw - 76 kw MPE 1 THE MPE ERIE... 5 1.1 Field of application... 5 1.2 Models and versions... 5 1.3 Components lay-out... 6 1.4 Water circuits... 13 2 INPECTION,

More information

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215)

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215) National Comfort Products 539 Dunksferry Road Bensalem, PA 19020 (215) 244-1400 1-800-523-7138 Fax: (215) 639-1674 14299575-10/29/2014 NOTE: These installation and maintenance instructions should be left

More information

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 HG 675 X 60 HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 1 2 1. : 93/68: 90/396: 2006/95/CE: 2004/108/CE: - 1935/2004:. 2002/95/CE: RoHS 2.,.,,,,...,. (,..)..,,.,. ( ),,, ;,,.,.....,.,,,,,,...,. (..),,.,..,.,,,,

More information

TECHNICAL SUPPLEMENT For Container Refrigeration Units with NATUREFRESH Humidity Management System

TECHNICAL SUPPLEMENT For Container Refrigeration Units with NATUREFRESH Humidity Management System r Container Refrigeration TECHNICAL UPPLEMENT For Container Refrigeration Units with NATUREFREH Humidity Management ystem Models 69NT541--001 to 199 T--325 TECHNICAL UPPLEMENT CONTAINER REFRIGERATION UNIT

More information