OPTICAL SMOKE DETECTOR Model: SPD-KADET

Size: px
Start display at page:

Download "OPTICAL SMOKE DETECTOR Model: SPD-KADET"

Transcription

1 OPTICAL SMOKE DETECTOR Model: SPD-KADET USER S MANUAL "ARTAR-PLUS" company 6 Prutska street Chernivtsi Ukraine EN 54-7 For further information please contact us:

2 The following abbreviations apply in the manual. FACP- fire alarm control panel AL- fire alarm line 1. FUNCTIONS 1.1 The SPD-KADET smoke optical point detector is designed to detect smoky fires indoors, and to transmit alarm signal to fire alarm control panels. 1.2 The SPD-KADET is counted on the continuous 24-hours operation in connection with fire alarm & fire-intruder control panels in DC or alternating 2-wire fire alarm loops with the 12/24V rated supply voltage. 1.3 The detector features: - Indication of the standby mode (red LED periodical short-time flashing); - Indication of the alarm mode (LED steady light - DC AL, pulsing - AC AL). 1.4 MUSH-3 - MUSH-6M modules are applied for connection of the detectors to 4-wire FACP. The detector complies with EN TECHNICAL SPECIFICATIONS 2.1 Supply voltage range, V Way of outgoing signal issue...non-contact 2.3 Wiring to control panel...2-wire 2.4 Standby current consumption, ma , Alarm current consumption set by external resistor (CLR) in value range, ma Internal resistance in alarm mode at 20 ma, Ohm Reverse current at -30V, μa Dimensions, mm ø95 х Weight, g Operating temperature range, С....from - 10 to Average lifespan, years ITEMS SUPPLIED WITH THE DETECTOR Name Quantity Note up to 25 pcs. SPD-KADET smoke photoelectric detector B95 base including (or B95M B95M/1) Manual 1 pc. per package Package 1 pc. per 25 detectors Protective cover (red) 1 pc. per detector For installation of the detectors on suspended ceilings you can separately order the K-4 mounting rings. Attention. The required base type should be indicated when you order the detectors. The appearance of the bases and their distinctions are shown in Figure 1- Figure 3. There is no possibility to connect Remote LED output in the B95M base. 3.2 You can separately order KM-95 mounting rings for installation to suspended ceilings. 3.3 MUSH-3 - MUSH-6M modules can be separately ordered. 4. DESIGN AND PRINCIPLES OF OPERATION 4.1 The principle of detector s operation is based on the control of optical medium density.

3 4.2 The detector consists of the detector itself and the base. The optical system, the signal processing electronic unit and LED control circuit are in the plastic housing of the detector. The detector is connected to the base with a 4-contact joint. 4.3 If there is no smoke in the sensitive zone of the optical system, the detector connected to the control panel shall be in standby mode, the red LED periodical pulsing indicates about. 4.4 When smoke appears in the sensitive zone of the optical system, the electronic circuit issues the alarm signal by intermittent change of internal resistance that leads to current growth in alarm loop. When in alarm mode the red LED switches on and is steadily lit (if connected to DC AL) or pulsing (if connected to AC AL) with the frequency specified by FACP. 4.5 The reset of detectors to the standby mode occurs when the mains supply switches off for not less than 3 s with the following energizing. 5. PLACEMENT AND INSTALLATION 5.1 You should install detectors in places with the following conditions: -minimal vibrations of constructions; -minimal illumination intensity; -maximum distance from sources of electrical-magnetic interferences (electric wiring etc.), infra-red radiation (heat devices); -elimination of water ingress on the case and penetration out of the base; -no gas, steam, aerosol emission that can cause corrosion. 5.2 You should provide protection against construction debris and dusts while conducting repair of lodgings. Fit the protective cover on each detector. It must be removed from the detector before commissioning. 5.3 Detectors are connected to the loop with the help of bases. Bases should be secured onto the detectors place of mounting using two Ø6x25 mm expansion bolts and two Ø3x30 mm screws. The center-to-center distance between mounting holes of B95 base is 70±0,2 mm, B95M/1, B95M - 76±0,2 mm. 5.4 It is possible to connect up to 3 wires of section 0,5 mm 2 to one screw joint of B95 base and to one screwless joint of B95M, B95M/ The view and dimensions of the bases are shown in Figure 1- Figure The wiring diagrams for detectors to different control panels are shown in Figure 4- Figure PREPARATION FOR OPERATING AND SEQUENCE OF OPERATIONS 6.1 Open the package after receiving detectors, check contents. ATTENTION! If detectors were in below 0 o C temperature conditions before opening the package, allow them to acclimatize inside the structure for at least 4 hours. 6.2 Test detectors for proper operating Connect the detector with B95 base or B95M/1 to a DC power source of V and the load current 50 ma ( plus connect to the contact 6, between contacts 6 and 2 fit the 1 kohm±5% current limiting resistor, minus to the contact 3, see Figure 1 and Figure 2). When you wire the detector with B95M base, connect plus of the power supply to the contact 1, between contacts 1 and 2 fit the 1 kohm±5% current limiting resistor, minus to the contact 3, see Figure 3). Lay wires between a square nut and area contact (contact «1» - «4») in B95 base. To connect wires to area contacts «1» - «4» of B95M or B90M/1 bases follow the following steps: - remove isolation from wire(s) for 10-12mm and twist them with each other; - release a spring contact lever (push the lever, release it from the latch slot and position it vertically until it clicks);

4 - insert wire(s) into slot 5(see Figure 1 ) located under the area contact (wire has to be seen through the control opening 4); - clutch the wire by moving the lever to the initial position (fix the lever to the latch slot); - check the wiring with the contact for security Apply the power and in not less than 10 s introduce into the test opening on the detector s cover (plastic or metal pin Ø1-1,2 mm, 4-5 mm long) and simultaneously switch the stopwatch on When the LED is on, stop the stopwatch and determine the response time (lag) that should be 10s. 6.3 The resetting to standby mode is made by turning off the mains supply for at least 3 s. 7. MAINTENANCE 7.1 Vacuum at least every six months to keep the unit working efficiently by firstly turning off the mains supply and vacuuming through the vents during one minute using a soft brush attachment or using another compressor of 0,5-3 kg/cm Then test detectors for proper operating. If the detector is detached from a base then the test should be made according to p The test should be made by inserting a tester-pin into the hole on the detector s cover. The red LED will be lit when the detector operates properly, and the control panel will issue the alarm signal. While checking the fire alarm system insert the tester pin into the opening on the detector's cover. If the detector is healthy the optical indicator shall be on, and the control panel shall issue the FIRE signal. 8. GUARANTEE 8.1 The detector is warranted by the manufacturer for 18 months upon the date of the detector s commissioning but not longer than for 30 months from the date of approval by the manufacturer s quality control department. 8.2 The manufacturer shall repair or replace detectors within the guarantee term provided that the rules of installation, timely maintenance, transportation and storage of detectors have been kept. 8.3 In the case faults according to a reclamation have been removed the guarantee term is prolonged for the time the detectors were not in use because of faults.

5 Figure 1 B95 BASE 1 area contacts «1» - «4» 2 screw contacts «5», «6» 3 mounting openings Figure 2 B95M/1 1 area contacts «1» - «4» 2 screw contacts «5», «6» 3 spring contact lever 4 control opening of laid wire 5 wire installation slot Figure 3 B95M 1 area contacts «2» - «4» 2 screw contact «5» 3 spring contact lever 4 control opening of laid wire 5 wire installation slot 6 area contact «1» for plus AL wire connection

6 Figure 4 WIRING DIAGRAM FOR SPD-KADET WITH B95M BASES TO DC FACP Number of detectors in AL, CLR and EOL resistors are specified by FACP specifications Figure 5 WIRING DIAGRAM FOR SPD-KADET WITH B95 (B95M/1) BASES TO DC FACP Number of detectors in AL, CLR and EOL resistors are specified by FACP specifications Figure 6 WIRING DIAGRAM FOR SPD-KADET WITH B95 (B95M/1) BASES TO AC FACP Number of detectors in AL, EOL resistors are specified by FACP specifications VD diode 1N4148

7 Figure 7 WIRING DIAGRAM FOR SPD-KADET WITH B95 (B95M/1) BASES TO INTRUDER-FIRE CONTROL PANELS THROUGH MUSH-6M MODULE R detector= 510 Ohm, Rv=2,4 kohm CLR and EOL resistors are specified by FACP specifications

8 QUALITY AND PACKING CERTIFICATE Optical smoke detector, model SPD-KADET, serial numbers: pieces with B95M base pieces with B95 base pieces with B95M/1 base Compliant with EN 54-7 Packed in compliance with the factory rules Manufacturing date..201 Packing date..201 Quality control mark

D250A/D253/D261AW/D280A/D290 Series

D250A/D253/D261AW/D280A/D290 Series D0A/D/D6AW/D80A/D90 Series EN Installation Instructions / Smoke/Heat Detector Bases EN. D0A/D/D6AW/D80A/D90 Series Installation Instructions.0 Trademarks M Weatherban is a trademark of M. All rights reserved.

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

FEC400 Series. Installation Manual

FEC400 Series. Installation Manual FEC400 Series Conventional microprocessor controlled fire detection and alarm panels with extinguishing control Installation Manual Version 2.3 / August 2004 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea

More information

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres 1) Introduction The BExBG05D-SIL is a flameproof beacon which is certified

More information

CONVENTIONAL FIRE ALARM CONTROL PANEL Model: ARTON-08F

CONVENTIONAL FIRE ALARM CONTROL PANEL Model: ARTON-08F ISO 9001:2008 CONVENTIONAL FIRE ALARM CONTROL PANEL Model: ARTON-08F OPERATIONAL MANUAL Private enterprise "ARTON" 6 Prutska street Chernivtsi 58008 Ukraine EN 54-2 EN 54-4 For further information please

More information

D285DH. Installation Instructions Photoelectric Duct Smoke Detector

D285DH. Installation Instructions Photoelectric Duct Smoke Detector D85DH EN Installation Instructions Photoelectric Duct Smoke Detector D85DH Installation Instructions.0 Introduction FCC Notice The D85DH Photoelectric Duct Smoke Detector complies with Part 5 of the Federal

More information

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

ZIOU/230 - MAINS IO INSTRUCTION MANUAL Description ZIOU/230 - MAINS IO INSTRUCTION MANUAL The Mains IO Modules are fully monitored loop powered devices which permit the interfacing of third party equipment with the Fire Alarm Control panel

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

Installation Manual. Detector Bases: PAD100-IB, PAD100-RB & PAD100-SB

Installation Manual. Detector Bases: PAD100-IB, PAD100-RB & PAD100-SB - + - + - + 1. Description This document provides instructions for mounting and wiring the Detector Bases PAD100-, PAD100-RB and PAD100-SB. The following detectors are compatible with Detector Bases PAD100-,

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Conventional Smoke Detectors KFAPO

Conventional Smoke Detectors KFAPO Kingfisher Company, inc. Conventional Smoke Detectors KFAPO Features: Wide operating voltage, 9-33 VDC Advanced electronic technology Flashing LED Magnetic test switch Proven detection performance Designed

More information

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector

D7050DH. Installation Instructions. Multiplex Photoelectric Duct Smoke Detector D700DH EN Installation Instructions Multiplex Photoelectric Duct Smoke Detector D700DH Installation Instructions.0 Description Notices These instructions cover the installation of the D700DH Multiplex

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

2000 Series Sensors Installation Guide

2000 Series Sensors Installation Guide 2000 Series Sensors Installation Guide Revision 5.1: August 2000 (unreleased) Aritech is a trademark of SLC Technologies B.V. COPYRIGHT SLC Technologies B.V. 2000. All rights reserved. SLC Technologies

More information

PAD100-6DB & PAD100-4DB PAD100-PD

PAD100-6DB & PAD100-4DB PAD100-PD Installation Manual Detector Bases: PAD100-6DB & PAD100-4DB PAD100-PD Photoelectric Smoke Detector (ANSI/UL 268 Listed) PAD100-PHD Photoelectric Smoke / Heat Detector Combination (ANSI/UL 268 and ANSI/UL

More information

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI E N G L I S H FIRE ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL0EI, MI-FL0EI AND MI-FL0EI mm mm 0 mm DESCRIPTION The LT MI-FL0 Series is part of the Fire Alarm

More information

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

System 800 Addressable Fire Detection & Alarm System

System 800 Addressable Fire Detection & Alarm System SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools

More information

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels CF5000, MF5000 and FXP5000 Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels 16 zone panels Contents PANEL INSTALLATION...3 Installation...3 PANEL WIRING... 3 Mains power

More information

Series 65 Product Guide MAN 3036

Series 65 Product Guide MAN 3036 Series 65 Product Guide MAN 3036 TABLE OF CONTENTS Page No. 1 Ionisation Smoke Detector... 1 1.1 Operating Principles:... 1 1.2 Product Codes... 2 1.3 Integrating Version:... 2 1.4 Options:... 2 1.5 Safety

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd OPERATIONAL NOTES FOR CONCEPT FIRE PANEL. NOTE ON NEW FIRE PANELS, POSITION 1 ON THE SIX WAY INTERNAL OPTION SWITCH IS TURNED ON, DISABLING THE ZONAL SOUNDERS. TO ENABLE ZONAL SOUNDERS TURN OFF. Operation

More information

The EN54 Part 2 and 4 Fire System

The EN54 Part 2 and 4 Fire System Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire

More information

Duct smoke housing, 2-wire D340/D340P

Duct smoke housing, 2-wire D340/D340P Duct smoke housing, 2-wire D340/D340P en Installation manual Duct smoke housing, 2-wire Notices en 3 1 Notices These instructions cover the installation of the D340 Duct smoke housing and D340P Duct smoke

More information

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No...G108WO1.DOC Serial No... Issue Date...17 th SEPTEMBER 1999 Software Version...1.4 APPROVED TO: NZS 4512:1997 AS/NZS 3548:1992 Fire Alarm

More information

Control Panel Engineering and Commissioning Instructions

Control Panel Engineering and Commissioning Instructions Twinflex - V3 Fire Detection & Alarm System Control Panel Engineering and Commissioning Instructions (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0338 Issue 9 Fike s policy is one of continual improvement

More information

Application, Installation, Operation & Maintenance Manual

Application, Installation, Operation & Maintenance Manual APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...

More information

Intruder - Fire - Water Combined Alarm

Intruder - Fire - Water Combined Alarm 65 Intruder - Fire - Water Combined Alarm Installation Manual and User Operating Instructions TALE OF CONTENTS Page First Power-Up 2 Power Supply Unit 3 Input & Detection Circuits 3 Output & Alarm Circuits

More information

IDP-Zone-6 Six Zone Interface Module

IDP-Zone-6 Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS IDP-Zone-6 Six Zone Interface Module BEFORE INSTALLING If the modules will be installed in an existing operational system, inform the operator and local authority

More information

MODEL 5100 VOTING LOGIC MODULE

MODEL 5100 VOTING LOGIC MODULE DESCRIPTION DESCRIPTION The SST Model 5100 Multi-Input Voting Logic Module is used to monitor the status of up to 14 different points in a hazard zone, and report when a selectable number of these points

More information

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator

Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator TECHNICAL GUIDE Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator The XPlorer Range XPlorer is a new range of analogue addressable detectors and interfaces developed for all who

More information

200 SERIES ADVANCED PHOTO/THERMAL/IR DETECTOR PRODUCT SPECIFICATION

200 SERIES ADVANCED PHOTO/THERMAL/IR DETECTOR PRODUCT SPECIFICATION GENERAL DESCRIPTION This product is the photo/thermal/ir variant of 2 Series Advanced, the redesigned 2 Series all SMD adopting the new chamber and a new style of covers. It works with the 2 Series extended

More information

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL 26 Aug 2015 V1.8 Page 1 SECTION CONTENTS PAGE NO. 1.0 SYSTEMS DESCRIPTION 1.1 General descriptions 2 1.2 Master Alarm PCB 2 1.3 Zone Display Board 2 1.4

More information

Heat Sensor Cable Alarm Units DT650L / DT950L

Heat Sensor Cable Alarm Units DT650L / DT950L Heat Sensor Cable Alarm Units DT650L / DT950L For conventional and 950 series analogue addressable systems Installation and Commissioning Manual Version 2.1 / May 2004 http://www.geindustrial.com/ge-interlogix/emea

More information

1400 Direct Wire Ionization Smoke Detector

1400 Direct Wire Ionization Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS 1400 Direct Wire Ionization Smoke Detector A Division of Pittway 3825 Ohio Avenue, St. Charles, Illinois 60174 1800SENSOR2, FAX: 6303776495 Specifications Diameter:

More information

Installation Manual. Detector Base: PAD100-SPKB

Installation Manual. Detector Base: PAD100-SPKB 1. Description This document provides instructions for mounting and wiring the detector base PAD100-SPKB. The following detectors are compatible with detector base PAD100-SPKB. PAD100-PD: Photoelectric

More information

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door CAUTION Hinge Edge of Door Wiring Instructions Checkmate Series with Single Point Hold-Open Combination Door Closer-Holder and Releasing Device with or without Integral Smoke Detector INSTALLER: LEAVE

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Duct smoke housings, 4-wire D341/D341P and D342/D342P Duct smoke housings, 4-wire D341/D341P and D342/D342P en Installation manual Duct smoke housings, 4-wire Notices en 3 1 Notices These instructions cover the installation of the D341/D342 Duct smoke housings

More information

INPUT / OUTPUT MINI MODULES

INPUT / OUTPUT MINI MODULES INPUT / OUTPUT MINI MODULES APPLICATION The Addressable Control and Monitor mini modules are the latest technology for a loop powered module. Installed on the same loop with other devices such as detectors

More information

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System SYSTEM MANUAL FT1-SB Single Zone Fire Alarm System DOCUMENT HISTORY Issue Date Description Written By Checked By Draft 0 2/9/2008 Original Document. A. Shenouda C. Orr Issue 1 4/11/2011 Update drawing

More information

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

DUAL MONITORED INPUT/OUTPUT UNIT BN-305 DUAL MONITORED INPUT/OUTPUT UNIT BN-30 Interactive fire detection systems Product Datasheet Features Interactive For interfacing and controlling external units to Autronica s interactive fire detection

More information

Secure the other corner. bracket using the remaining screw,

Secure the other corner. bracket using the remaining screw, Mount the E-FENCE1 directly to the fabric of the chain link or wire mesh, on the interior side of the protected area as shown in the illustrated examples, at a height of 4 5 feet and 1 foot from a post.

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

ISC-PDL1-W18G-H. Installation Instructions Professional Series Dual Detector

ISC-PDL1-W18G-H. Installation Instructions Professional Series Dual Detector ISC-PDL1-W18G-H EN Installation Instructions Professional Series Dual Detector 1.0 General Information 1.1 Unlock and remove the cover The ISC-PDL1-W18x Professional Series TriTech Detectors are exceptionally

More information

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN 04-350 Product Installation

More information

CZ-6A Six Zone Interface Module

CZ-6A Six Zone Interface Module INSTALLATION AND MAINTENANCE INSTRUCTIONS CZ-6A Six Zone Interface Module 658 Kitimat Rd. Unit #6 Mississauga, Ontario L5N T5-800-SENSOR, FAX: 905-8-077 www.systemsensor.ca SPECIFICATIONS Normal Operating

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

FL2011EI-HS FL2012EI-HS FL2022EI-HS

FL2011EI-HS FL2012EI-HS FL2022EI-HS Fire Aspiration Sensing Technology ENGLISH FL0EI-HS FL0EI-HS FL0EI-HS ADDRESSABLE FAAST LT-00 MODELS QUICK INSTALLATION GUIDE I - - 00 CONTENTS Introduction Parts List Specifications Physical Installation

More information

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

D326A/D334A/D339A. Installation Instructions. Point Contact Modules D326A/D334A/D339A EN Installation Instructions Point Contact Modules D326A/D334A/D339A Installation Instructions 1.0 Description Notice Use these instructions to install the D326A, D334A, and D339A Point

More information

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE Fire Door Release MODEL AR-D2 MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D2 GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

Addressable Detectors & Bases

Addressable Detectors & Bases Edwards Signaling Catalog u Intelligent Initiating Addressable Detectors & Bases Detectors: E-PD, E-PHD, E-HD Bases: B4U, RB4U, IB4U, SB4U Overview Edwards intelligent addressable detectors are meticulously

More information

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2 DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2 Interactive fire detection systems Product Datasheet Features Interactive For interfacing and controlling external units to Autronica s interactive fire detection

More information

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors Hinge Edge of Door Hinge Edge of Door Wiring Instructions for the Sargent 0 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector CAUTION: FAILURE TO INSTALL

More information

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control File: S8485 Wiring Diagram This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control Panel. The operation of this product is intended for indoor

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

Fire Alarm System FMS3000 Installation Instructions

Fire Alarm System FMS3000 Installation Instructions Fire Alarm System FMS3000 Installation Instructions Version history Version Date Author Checked Note 0.1 16/09/13 JB TK Produced based on the old operating instructions 0.2 27/09/16 TK STO Configuration

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

EXTINGUISHING AGENT RELEASE MODULE

EXTINGUISHING AGENT RELEASE MODULE EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153

More information

FDMM01S - FDMM02 - FDMM10- FDMM11S FDMM12 - Input / output mini modules

FDMM01S - FDMM02 - FDMM10- FDMM11S FDMM12 - Input / output mini modules Application The Addressable Control and Monitor mini modules are the latest technology for a loop powered module. Installed on the same loop with other devices such as detectors and manual call points,

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

ECO N DATE DESCRIPTION OF CHANGE CHG

ECO N DATE DESCRIPTION OF CHANGE CHG Model Number: M21E-24-DIN Description: The product is a loop powered device which controls an unsupervised dual pole output channel suitable to manage 24VAC loads. The M21E-24-DIN is micro-controller operated,

More information

Flair 500 Series Annunciators

Flair 500 Series Annunciators Flair 500 Series s Basics Flair Multi-Zone s (MZAs) are fully functional, flexible, programmable micro controller based alarm control panels. They can be used independently d or in conjunction with other

More information

English. Italiano. Português. Françias. Español

English. Italiano. Português. Françias. Español DT AM Grade 3 Español Françias Português Italiano English High Ceiling Mount Detector Installation Guide English DT AM Grade 3 High Ceiling Mount Detector Installation Guide General Description The Industrial

More information

These instructions detail procedures to follow in order to avoid damage to equipment.

These instructions detail procedures to follow in order to avoid damage to equipment. D326A, D334A, D339A Point Contact Modules Installation Guide 1.0 Notice These instructions are for the installation of the D326A, D334A and D339A Point Contact Modules in an analog system controlled by

More information

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147) -961112-0003 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3

More information

The new detector from Rafiki

The new detector from Rafiki The new detector from Rafiki Three smoke detectors Three heat detectors Combined smoke/heat detector Full alarm sounder Strobe End-of-line device/loop isolator Rafiki s Multipoint ASD detector range have

More information

OPERATION AND INSTALLATION MANUAL

OPERATION AND INSTALLATION MANUAL EX+Plus 2 ZONE, 1AREA EXTINGUISHANT CONTROL PANEL OPERATION AND INSTALLATION MANUAL INTRODUCTION The Premier EX Plus is a 2 zone, single area panel for controlling the release of extinguishing gases in

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

E-PDD Duct Smoke Detector Installation Sheet

E-PDD Duct Smoke Detector Installation Sheet E-PDD Duct Smoke Installation Sheet E-PDD operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from

More information

MMF Six Zone Interface Module

MMF Six Zone Interface Module Installation and Maintenance Instructions I56-900-005 MMF-0-6 Six Zone Interface Module SPECIFICATIONS Normal Operating Voltage: 5- VDC Stand-By Current: ma Alarm Current: 40 ma (assumes all six LEDs solid

More information

Annexure - 1. Detectors: Fire Alarm Control Panel :

Annexure - 1. Detectors: Fire Alarm Control Panel : Item 1. Supply Part This Specification includes Supply, Warranty, Installation, Testing and Commissioning and integration of the Fire Alarm System mainly consisting of the Fire Alarm Control Panel (FACP),

More information

Precept Marine Control Panel Application Guide

Precept Marine Control Panel Application Guide Precept Marine Control Panel Application Guide Contents Page 1.0 Cabinet Specifications 2 2.0 Panel Hardware Specifications 5 3.0 Panel Configuration 8 4.0 Technical Specifications 8 5.0 Battery Sizes

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. ( 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2) Connect

More information

Reflective Optical Beam Smoke Detector User Guide

Reflective Optical Beam Smoke Detector User Guide Reflective Optical Beam Smoke Detector User Guide 1. Installation IMPORTANT NOTE: The infrared beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the system initiating

More information

Interface and EOL Modules 8

Interface and EOL Modules 8 Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface

More information

Fire Control Panel FS4000

Fire Control Panel FS4000 Fire Control Panel FS4000 INSTRUCTION MANUAL Revision 4/02.11 Contents 1. Introduction... 4 2. Terminology... 4 3. Function... 5 4. Technical features... 5 4.1 Fire alarm lines... 5 4.2. Current thresholds

More information

MO144. Operators Guide. Universal Timer Module

MO144. Operators Guide. Universal Timer Module EN Operators Guide Universal Timer Module Operators Guide Notices EN Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems, Inc. ( Bosch ). All rights

More information

DI601AM Outdoor PIR/AM Detector Installation Sheet

DI601AM Outdoor PIR/AM Detector Installation Sheet DI601AM Outdoor PIR/AM Detector Installation Sheet EN DE ES FR IT NL PL PT SV Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 TOP Figure 8 Figure 9 TOP Long range 30m section Short/ medium

More information

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm.

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm. E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0E FL0E FL0E mm mm 0 mm DESCRIPTION The LT FL0 Series is part of the Fire Alarm Aspiration

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING 48ESEP-01 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

Ç Consilium Consilium US, Inc. 59 Porter Rd Littleton, MA USA

Ç Consilium Consilium US, Inc. 59 Porter Rd Littleton, MA USA INSTRUCTION MANUAL and DETAILED PRODUCT SPECIFICATION TRIPLEX BACKUP PUMP CONTROL SYSTEM MODEL NUMBER BPC-3 November 22, 1999 Ç Consilium Consilium US, Inc. 59 Porter Rd Littleton, MA 01460-1431 USA Telephone:

More information

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS GENERAL DESCRIPTION... 2 STANDARD AND OPTIONAL PARTS LIST... 2 PARTS DIAGRAM... 3 TERMINAL DRAWING AND SPECIAL NOTES...

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

Reflective Beam Smoke Detector

Reflective Beam Smoke Detector Reflective Beam Smoke Detector SRA-ET Features! 5-30m range! Small flat reflector! Powered directly from the zone! Full line continuity options! Automatic compensation! Approved by LPCB & VdS Description

More information

Conventional Leaflets

Conventional Leaflets Conventional Leaflets Panels Last updated October 1999 Make leaflet selection by clicking on appropriate bookmark Return to Menu Installation and Basic Commissioning guide for the range of 1,2,4 and 8

More information

5000 INSTALLATION GUIDE

5000 INSTALLATION GUIDE 5000 INSTALLATION GUIDE Table of Contents Section Page No 1. INTRODUCTION... 3 2. WARNINGS AND CAUTIONS... 3 3. UNPACKING... 3 4. INSTALLATION... 4 5. CONTROL PANEL - REMOVING ITEMS BEFORE MOUNTING...

More information

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk

More information

D296/D297. Installation Instructions Long-Range Beam Smoke Detectors

D296/D297. Installation Instructions Long-Range Beam Smoke Detectors D96/D97 EN Installation Instructions Long-Range Beam Smoke Detectors D96/D97 Installation Instructions.0 Description FCC Compliance Notice This equipment was tested and complies with the limits for a Class

More information

You in Control PRODUCT OVERVIEW

You in Control PRODUCT OVERVIEW AIR PRODUCTS AND CONTROLS You in Control AIR PRODUCTS AND CONTROLS INC. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR SERIES PLENUM DUCT SMOKE DETECTORS NO-FLOW LOW-FLOW SPECIAL APPLICATION -N -P PRODUCT

More information

SOUNDER CONTROL MODULE SCM-AS4

SOUNDER CONTROL MODULE SCM-AS4 1 of 9 INTRODUCTION DESCRIPTION The forms part of the Nittan (UK)'s SENSORTEC-ANALOGUE range of Analogue Addressable Devices. This module is designed to control a group of bells or sounders from the detection

More information

ESSEX ENGINEERING CORPORATION

ESSEX ENGINEERING CORPORATION WATER/WASTEWATER TREATMENT CONTROL SYSTEMS AND SUBSYSTEMS 2000 SERIES CONTROL SYSTEMS: 2000 series are for surface mounting inside a control cabinet Model 2024 Electronic Alternator Duplex (two pump) pump

More information

RMS-I-DE-01 Smoke Detector

RMS-I-DE-01 Smoke Detector RMS-I-DE-01 Smoke Detector 2012 CONTEG, spol. s r.o. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted or stored in any retrieval system of any nature,

More information

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops... GUIDE MANUAL INDEX 1- Introduction...5...5...6 4- The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops...7 4.2- The Control Panel 4 and 8 Loops...9 5- Installation Guide...10 5.1- Pre-Installation

More information

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING -961212-0004 SOFTWARE VERSI 3.10 CTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)

More information

End To End Optical Beam Smoke Detector. Additional Information

End To End Optical Beam Smoke Detector. Additional Information End To End Optical Beam Smoke Detector Additional Information EN 1. Multiple Zone Wiring When using more than one System Controller on a single zone of a conventional Fire Control Panel (FCP), it is important

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

Interface Modules for SENTRI

Interface Modules for SENTRI EQUIPMENT INTERFACED Data and Installation Interface s for SENTRI Low voltage (LV) / SEN-INT-INPUT 1- Interface (low voltage) SEN-INT-OUTPUT 1- & 1- Interface (low voltage) SEN-INT-4IO # 4- / Interface

More information