1 Appendix E: Photo Documentation Brown County Library Central Branch Building Assessment
2 Appendix E: Photo Documentation Architectural and Structural Brown County Library Central Branch Building Assessment Existing skylights: Inefficient system, Low R- Values allow high levels of heat loss. Leaks occur during spring thaw and driving rain. See Appendix D for potential upgrade options. Accessibility: Non ADA compliant toilet rooms and plumbing fixtures. No grab bars present. Clear floor space at toilet stalls, urinals, lavatories, mirrors and misc. toilet room accessories to not meet federal regulations. See Appendix D for reference guidelines. Stairways & Handrails: Non ADA compliant handrail extensions at top and bottom stair runs. See Appendix D for reference guidelines.
3 Appendix E: Photo Documentation Architectural and Structural Brown County Library Central Branch Building Assessment Heaving Concrete: Hazardous condition in front of building is a continuous maintenance issue. Uneven walking / wheelchair path. Acoustic Ceiling Tile: Existing spline ceiling tile contains asbestos, stains from condensation & water leaks, and dirty from airborne dust and pollutants. Blocked Exit Corridors: Exit paths must be kept clear. By code, large storage items, such as tables, chairs, etc. in exit corridors need to be relocated.
4 Appendix E: Photo Documentation Architectural and Structural Brown County Library Central Branch Building Assessment Guardrails: Guards must be designed up to a height of 42 and vertical posts spaced such that a 4 sphere cannot pass through. Building Glazing: Existing windows have poor insulation values, contributing to an inefficient exterior building envelope. Sealant has broken away in some areas along with glass buckling & movement within frames.
5 Appendix E: Photo Documentation Electrical Brown County Library Central Branch Building Assessment Elevator controller over heating. Doors kept open to allow air flow. Switchboard main disconnect should be replaced. Existing Onan Generator - In good working condition - Monthly running and occasional maintenance
6 Appendix E: Photo Documentation Electrical Brown County Library Central Branch Building Assessment Flagpole Light W seems high for use - Could replace with different technology - Direct lamp down to comply with dark skies Disconnect on roof top air cooled condenser - Disconnect should be replaced Data Intermediate Distribution Frame (IDF) - Relocate to safe location - Not accessible to library patrons
7 Appendix E: Photo Documentation Electrical Brown County Library Central Branch Building Assessment Branch panel used for controlling lighting - Recommend replacing breakers and utilizing local controls, such as occupancy sensors. Inside of a former branch panel. Now used for communication Junction Box. - Recommend cleaning inside of all branch panel boards.
8 Appendix E: Photo Documentation HVAC Brown County Library Central Branch Building Assessment AHU s: Air Handling Units #2 and #5 drain pans. Monitor and possibly replace. Steam Boiler: Existing exit steam boiler should be recommissioned. New Equipment: New VFD & HW pumps are in good working order.
9 Appendix E: Photo Documentation HVAC Brown County Library Central Branch Building Assessment Boilers: New and existing HW boilers are in good working order. Replacement for existing boiler is not required. Stormwater Pumps: Existing stormwater pumps are functioning properly and are in good working order. Rooftop Unit: Monitor components and replace as outlined in Appendix A.
10 DSC_0001.JPG DSC_0002.JPG DSC_0003.JPG DSC_0004.JPG DSC_0005.JPG DSC_0006.JPG DSC_0007.JPG DSC_0008.JPG DSC_0009.JPG DSC_0010.JPG DSC_0011.JPG DSC_0012.JPG DSC_0013.JPG DSC_0014.JPG DSC_0015.JPG DSC_0016.JPG DSC_0017.JPG DSC_0018.JPG DSC_0019.JPG DSC_0020.JPG DSC_0021.JPG DSC_0022.JPG DSC_0023.JPG DSC_0024.JPG DSC_0025.JPG DSC_0026.JPG DSC_0027.JPG DSC_0028.JPG DSC_0029.JPG DSC_0030.JPG DSC_0031.JPG DSC_0032.JPG DSC_0033.JPG DSC_0034.JPG DSC_0035.JPG
11 DSC_0036.JPG DSC_0037.JPG DSC_0038.JPG DSC_0039.JPG DSC_0040.JPG DSC_0041.JPG DSC_0042.JPG DSC_0043.JPG DSC_0044.JPG DSC_0045.JPG DSC_0046.JPG DSC_0047.JPG DSC_0048.JPG DSC_0049.JPG DSC_0050.JPG DSC_0051.JPG DSC_0052.JPG DSC_0053.JPG DSC_0054.JPG DSC_0055.JPG DSC_0056.JPG DSC_0057.JPG DSC_0058.JPG DSC_0059.JPG DSC_0060.JPG DSC_0061.JPG DSC_0062.JPG DSC_0063.JPG DSC_0064.JPG DSC_0065.JPG DSC_0066.JPG DSC_0067.JPG DSC_0068.JPG DSC_0069.JPG DSC_0070.JPG
12 DSC_0071.JPG DSC_0072.JPG DSC_0073.JPG DSC_0074.JPG DSC_0075.JPG DSC_0076.JPG DSC_0077.JPG DSC_0078.JPG DSC_0079.JPG DSC_0080.JPG DSC_0081.JPG DSC_0082.JPG DSC_0083.JPG DSC_0084.JPG DSC_0085.JPG DSC_0086.JPG DSC_0087.JPG IMG_5626.JPG IMG_5627.JPG IMG_5628.JPG IMG_5629.JPG IMG_5630.JPG IMG_5631.JPG IMG_5632.JPG IMG_5633.JPG IMG_5634.JPG IMG_5635.JPG IMG_5636.JPG IMG_5637.JPG IMG_5638.JPG IMG_5639.JPG IMG_5640.JPG IMG_5641.JPG IMG_5642.JPG IMG_5643.JPG
13 IMG_5644.JPG IMG_5645.JPG IMG_5646.JPG IMG_5647.JPG IMG_5648.JPG IMG_5649.JPG IMG_5650.JPG IMG_5651.JPG IMG_5652.JPG IMG_5653.JPG IMG_5654.JPG IMG_5655.JPG IMG_5656.JPG IMG_5657.JPG IMG_5658.JPG IMG_5659.JPG IMG_5660.JPG IMG_5661.JPG IMG_5662.JPG IMG_5663.JPG IMG_5664.JPG IMG_5665.JPG IMG_5666.JPG IMG_5667.JPG IMG_5668.JPG IMG_5669.JPG IMG_5670.JPG IMG_5671.JPG IMG_5672.JPG IMG_5673.JPG IMG_5674.JPG IMG_5675.JPG IMG_5676.JPG IMG_5677.JPG IMG_5678.JPG
14 IMG_5679.JPG IMG_5680.JPG IMG_5681.JPG IMG_5682.JPG IMG_5683.JPG IMG_5684.JPG IMG_5685.JPG IMG_5686.JPG IMG_5687.JPG IMG_5688.JPG IMG_5689.JPG IMG_5690.JPG IMG_5691.JPG IMG_5692.JPG IMG_5693.JPG IMG_5694.JPG IMG_5695.JPG IMG_5696.JPG IMG_5697.JPG IMG_5698.JPG IMG_5699.JPG IMG_5700.JPG IMG_5701.JPG IMG_5702.JPG IMG_5703.JPG IMG_5704.JPG IMG_5705.JPG IMG_5706.JPG IMG_5707.JPG IMG_5708.JPG IMG_5709.JPG IMG_5710.JPG IMG_5711.JPG IMG_5712.JPG IMG_5713.JPG
15 IMG_5714.JPG IMG_5715.JPG IMG_5716.JPG IMG_5717.JPG IMG_5718.JPG IMG_5719.JPG IMG_5720.JPG IMG_5721.JPG IMG_5722.JPG IMG_5723.JPG IMG_5724.JPG IMG_5725.JPG IMG_5726.JPG IMG_5727.JPG IMG_5728.JPG IMG_5729.JPG IMG_5730.JPG IMG_5731.JPG IMG_5732.JPG IMG_5733.JPG IMG_5734.JPG IMG_5735.JPG IMG_5736.JPG IMG_5737.JPG IMG_5738.JPG IMG_5739.JPG IMG_5740.JPG IMG_5741.JPG IMG_5742.JPG IMG_5743.JPG IMG_5744.JPG IMG_5745.JPG IMG_5746.JPG IMG_5747.JPG IMG_5748.JPG
16 IMG_5749.JPG IMG_5750.JPG IMG_5751.JPG IMG_5752.JPG IMG_5753.JPG IMG_5754.JPG IMG_5755.JPG IMG_5756.JPG IMG_5757.JPG IMG_5758.JPG IMG_5759.JPG IMG_5760.JPG IMG_5761.JPG IMG_5762.JPG IMG_5763.JPG IMG_5764.JPG IMG_5765.JPG IMG_5766.JPG IMG_5767.JPG IMG_5768.JPG IMG_5769.JPG IMG_5770.JPG IMG_5771.JPG IMG_5772.JPG IMG_5773.JPG IMG_5774.JPG IMG_5775.JPG IMG_5776.JPG IMG_5777.JPG IMG_5778.JPG IMG_5779.JPG IMG_5780.JPG IMG_5781.JPG IMG_5782.JPG IMG_5783.JPG
17 IMG_5784.JPG IMG_5785.JPG IMG_5786.JPG IMG_5787.JPG IMG_5788.jpg IMG_5789.jpg IMG_5790.jpg IMG_5791.jpg IMG_5792.jpg IMG_5793.jpg IMG_5794.jpg IMG_5795.jpg IMG_5796.jpg IMG_5797.jpg IMG_5798.jpg IMG_5799.jpg IMG_5800.jpg IMG_5801.jpg IMG_5802.jpg IMG_5803.jpg IMG_5804.jpg IMG_5805.jpg IMG_5806.jpg IMG_5807.jpg IMG_5808.jpg IMG_5809.jpg IMG_5810.jpg IMG_5811.jpg IMG_5812.jpg IMG_5813.jpg IMG_5814.jpg IMG_5815.jpg IMG_5816.jpg IMG_5817.jpg IMG_5818.jpg
18 IMG_5819.jpg IMG_5820.jpg IMG_5821.jpg IMG_5822.jpg IMG_5823.jpg IMG_5824.jpg IMG_5825.jpg IMG_5826.jpg IMG_5827.jpg IMG_5828.jpg IMG_5829.jpg IMG_5830.jpg IMG_5831.jpg IMG_5832.jpg IMG_5833.jpg IMG_5834.jpg IMG_5835.jpg IMG_5836.jpg IMG_5837.jpg IMG_5838.jpg IMG_5839.jpg IMG_5840.jpg IMG_5841.jpg IM JPG IM JPG IM JPG IM JPG IM JPG IM JPG
19
VOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED
Ashton Elementary School 1 Masonry Repair $ 42,781.50 2 Replace HVAC $ 375,000.00 3 Replace SAT @ Various Locations $ 92,364.00 3 Recoat & Resurface Exterior Paved Play Area $ 135,978.30 3 Various Technological
More informationMARY CRAPO CENTER Miller Road, Swartz Creek, Michigan
MARY CRAPO CENTER 8197 Miller Road, Swartz Creek, Michigan MARY CRAPO CENTER 8197 Miller Road, Swartz Creek General Information: - Instructional, Child Care Development Center (West Wing) o (2) Infant/Toddler
More informationPLATTEVILLE MIDDLE SCHOOL
Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle
More informationAshland School District Facility & Capacity Assessment Report 2005
Ashland School District Facility & Capacity Assessment Report 2005 Briscoe Elementary School (Closed Facility) Address: 265 N Main Street Area: 33,980 square feet Buildings: Original Building 1948 Music
More informationMUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY
ARCHITECTURE ROLLING HILLS ELEMENTARY SCHOOL Rolling Hills Elementary was built in 1999 and is the newest addition to the Mukwonago Area School District. The building contains approximately 64,900 gross
More informationPLAN REVIEW SUBMITTAL GUIDE
PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide
More informationForest Hills Facilities Plan
Forest Hills Facilities Plan Extensive updates to 8 of our 9 schools Replace Wilson Elementary Enhance learning environments across the district Build additional classrooms to accommodate gradual implementation
More informationFlorence High School / Middle School Page 1 of 3 Florence, WI
Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October
More information3. 21st Century Learning A. Districtwide Flexible Learning - Allowance for Flexible Furniture $600,000 Subtotal $600,000
1. Safety and Security A. Additional Cameras District Wide $382,000 B. Interior Locks Upgrades Allowance $300,000 C. Tilden Entrance Upgrades D. Door and Glass Improvements Allowance $500,000 E. Alert
More informationFacility Improvements
AP-SI-03 BICYCLE RACK ADDITION AP-SI-05 EXTERIOR BENCH ADDITIONS Installation of bike rack will allow for designated and secure storage of bicycles. Installation of exterior benches will provide an outdoor
More informationMechanical Inspection Plumbing
0811 Fixtures Sinks, drinking fountains, water closets, showers, etc. Classroom Sinks. Classroom sinks (19) are enameled cast iron self rimming side ledge with gooseneck faucet trim with index handles,
More informationSUMMARY 1234 Main St.Edmonton AB T5T3E9 Buyer Name 07/05/2018 9:00AM
SUMMARY 1234 Main St.Edmonton AB T5T3E9 Buyer Name 07/05/2018 9:00AM Banti Shaw InspecUs InspecUs 7808623549 bantishaw@inspecus.ca This Summary outlines potentially significant issues from a cost, safety
More informationSCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003
SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 No. Discipline Sent to Name Item Date Noted Date Resolved How item was resolved SCO # 1Punch listed items were noted below on
More informationHOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District
HOLUM EDUCATION CENTER Architectural The existing building has approximately 41,823 square feet and sets on a lot about 4.14 acres in size. Parking lots are located along the east and west sides of the
More informationSprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS
EXISTING MECHANICAL CONDITIONS SUMMARY The items listed below are based on our site visit on Nov 10, 2016. Our review is based on current conditions and anticipated future use of these building. In the
More informationUnit # H ± 2,000 SF Width ± 25' Depth ± 80'
±80' Lease Line Lease Outline Drawing Sunnymead Plaza 24907 Sunnymead Blvd., Unit # H, Moreno Valley, CA 92553 Unit # H ± 2,000 SF Width ± 25' Depth ± 80' Unit # H Plans produced by: ID Plans 6/13/2017
More informationUnit # 1038 ± 900 SF Width ± 15' Depth ± 60'
±60' Lease Line Lease Outline Drawing Needles Towne Center 1004 E. Broadway St.,, Needles, CA 92363 ± 900 SF Width ± 15' Depth ± 60' Plans produced by: ID Plans 6/16/2017 (813) 657-2545 C 2017 Site map
More informationPENNSYLVANIA. Downloaded
Housekeeping/Laundry/Maintenance 205.26. Laundry. PENNSYLVANIA Downloaded 01.15.11 (a) A laundry room shall be provided in a facility where commercial laundry service is not used for the washing of soiled
More informationBC Building Code Checklist Part 3 Planning and Development Department
BC Building Code Checklist Part 3 Planning and Development Department Project: Civic address: Permit No.: CRP: Certified Professional: Date: 1 Value of Construction: $ Developed Site Area: m2 2 BUILDING
More informationExisting Facilities Assessment
DRAFT Patrick Henry Elementary School 4643 Taney Ave, Alexandria, VA 22304 Existing Facilities Assessment Alexandria City Public Schools Planning, Design & Construction Office 1340 Braddock Place Alexandria,
More informationDMTF: Specific Building Recommendations
DMTF: Specific Building Recommendations Asset Name Project Title Total Cost BLOCKER BUILDING 22,503,303 Capital Renewal 7,640,013 DOMESTIC WATER HEATER REPLACEMENT 16,374 EXTERIOR DOOR REPLACEMENT 133,623
More informationUnit # E ± 1,200 SF Width ± 20' Depth ± 60'
Lease Outline Drawing ±60' Lease Line Sunnymead Plaza 24907 Sunnymead Blvd., Unit # E, Moreno Valley, CA 92553 Unit # E ± 1,200 SF Width ± 20' Depth ± 60' Plans produced by: ID Plans 6/13/2017 (813) 657-2545
More informationPlot # R019A ± 74' ± 74' ± 65' Plot # R019A LEASE OUTLINE DRAWING GROSS LEASABLE AREA ± 4,631 S.F. DEMISING FRONT WIDTH DEPTH ± 13' ± 32' Lease Line
± 4' ± 13' ± 72' Lease Line ± 6' ± 7' Plot # R019A ± 18' Lease Line Site N o : Site N ame: Lo catio n: Submitted B y: D rawn by D ate: 991 Santee Trolley Square Santee, CA ID Plans 11/10/2016 This drawing
More informationIchabod Crane Central School District 2018 Capital Project Preliminary Estimate
Health & Safety 1,399,000 Academics & Program 17,140,800 Physical Education & Athletics 5,922,000 Building Infrastructure 3,103,800 Site Infrastructure 1,049,600 TOTAL SCOPE OF WORK 28,615,200 PROPOSED
More informationHome Safety Checklist From Adaptive Remodeling Solutions, LLC Monona, WI
Home Safety Checklist From Adaptive Remodeling Solutions, LLC 608-234-7440 Monona, WI Are you able to use every part of your home efficiently and safely? Take a good look at the rooms in your home and
More informationRichard Henry Lee Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationFrancis M McKay Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationSCOPE OF WORK. 506 N. Chadbourne Ave, San Angelo, TX. 1. Build and outfit kitchen are in accordance with established drawing
SCOPE OF WORK 506 N. Chadbourne Ave, San Angelo, TX Contractor shall be required to provide labor, supervision, and equipment to build a small multipurpose kitchen and Americans with Disabilities Act (ADA)
More informationUnit HH Gregg. ± 30,000 SF Width ±26' Lakeland Retail Center. Lease Outline Drawing. Unit HH Gregg. Depth ± 145' HVAC Units & Information
Lease Outline Drawing Lakeland Retail Center 4000 US Hwy. 98, Unit HH Gregg, Lakeland, FL 33809 ±26' ±200' Lease Line Unit HH Gregg ±46' Lease Line ±21' Unit HH Gregg ±145' Lease Line ± 30,000 SF Width
More informationAgustin Lara Elementary Academy
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationPROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:.
2012 B.C. Building Code Checklist (Division B Part 3) This checklist is provided as a reference only. The submission of this checklist with a Building Permit application should not be considered as a substitute
More informationFacility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building
Facility Condition Assessment Summary Report British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Submitted by: VFA Canada Corp. Burnaby Centre 4211 Kingsway Burnaby, BC V5H 1Z6
More informationGenevieve Melody Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationState College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT
State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Calgary School District #19 Queen Elizabeth Junior / Senior High School B2745A Calgary Report run on: March, 2010 10:02 AM Building Name: Address: Location: Building Id:
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Edmonton School District No. 7 Stratford Academic High School B3336A Edmonton Report run on: April 3, 29 1:6 AM Building Name: Address: Location: Building Id: Gross Area
More informationEdward Jenner Elementary Academy of the Arts
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationSPACE TYPE: JUDICIAL CHAMBER
SPACE TYPE: JUDICIAL CHAMBER Construction Criteria The unit costs for Judicial Chamber space types are based on the construction quality and design features in the following table. This information has
More informationMAINE. Downloaded g. Maintain an effective pest control program so that the facility is free of pests and rodents;
Housekeeping/Laundry/Maintenance Each licensed facility shall: MAINE Downloaded 01.15.11 g. Maintain an effective pest control program so that the facility is free of pests and rodents; 20.J.2. Soiled
More informationShort-Term & Accessory Short-Term Rental Safety Certification
Short-Term & Accessory Short-Term Rental Safety Certification Permit Application Center (City Hall) 555 Liberty St. SE, Room 320 Salem, OR 97301 503-588-6213 (For office use only) License #: If you need
More information2 Main Office Building BLDG-955A Building Purpose Building Area Administration offices. Training room 7,610 SF Inspection Date August 16, 2016 Inspect
1 Site Summary Address 7200 Bluff Springs Road Austin, TX 78744 Number of Permanent Campus Facilities 2 Original Year of Construction 2014 Total Campus Building Area (combined) 25,314 SF Introduction The
More informationARCHITECTURAL ASSESSMENT
Killington Fire Station Feasibility Study Architectural Assessment ARCHITECTURAL ASSESSMENT The current facility was constructed at three different times: 1974 Original 1984 Middle bays 1998 Apparatus
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Edmonton School District No. 7 Harry Ainlay Composite High School B3145A Edmonton Report run on: March 2, 27 3:27 PM Building Name: Address: Location: Building Id: Gross
More informationPreliminary Study Document. Horicon. Horicon, Wisconsin
Preliminary Study Document Horicon School District Horicon, Wisconsin Monday table of contents i 1 2 Introduction Section One: Van Brunt Elementary School a. Building Evolution b. Existing Site Plan c.
More informationGeorge B Swift Elementary Specialty School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationCommon Area Cleaning Guide
1 P a g e Common Area Cleaning Guide It is the responsibility of every occupant, owner, tenant, contractor, employee & visitor and ALL users of this facility to ensure they take all reasonably practical
More informationSpringpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp.
Volume 1 Bidding Requirements, Contract Forms, Conditions of the Contract, Division 1, Architectural and Site Specifications 000107 Certification Page 000110 Table of Contents DIV00 PROCUREMENT AND CONTRACTING
More informationUniversity of Wisconsin-Stevens Point REQUEST FOR ARCHITECTURAL & ENGINEERING DESIGN SERVICES NEALE RESIDENCE HALL RENOVATION PROJECT.
University of Wisconsin-Stevens Point REQUEST FOR ARCHITECTURAL & ENGINEERING DESIGN SERVICES NEALE RESIDENCE HALL RENOVATION PROJECT January 2009 DSF Project # 09L2E TABLE OF CONTENTS PAGE Project Scope
More informationFire/General Safety Review Program Key Performance Indicators Environmental Health and Safety
Fire/General Safety Review Program Key Performance Indicators Environmental Health and Safety Fire and CO Detection Systems Fire alarm pull station obstructed. Annunciation panel obstructed. Lack of approved
More information2012 B.C. Building Code Compliance Review (Division B Part 3)
Planning and Building Department 2012 B.C. Building Code Compliance Review PROJECT NAME:.. CIVIC ADDRESS:...... PERMIT APPLICATION NO.:. DATE:... I,, have: 1. reviewed the design, plans and supporting
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Calgary School District #19 John G Diefenbaker High School B2686A Calgary Report run on: January 1, 28 9:31 AM Building Name: Address: Location: Building Id: Gross Area
More informationCalmeca Academy of Fine Arts and Dual Language
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationOscar DePriest Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Edmonton RCSSD #7 Bishop Savaryn Catholic Elementary School B58A Edmonton Report run on: July 10, 2008 3:31 PM Building Name: Address: Location: Building Id: Gross Area
More informationCharles W Earle Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationWashington Irving Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Edmonton School District No. 7 Clara Tyner Elementary School B375A Edmonton Report run on: March 16, 212 2:11 PM Building Name: Address: Location: Building Id: Gross Area
More information2015 Building Condition Survey Summary Mosaic Associates Architects 02/19/16
1. General: This summary is offered as a supplement to the 2015 Building Condition Survey being filed with SED on behalf of the District. All cost estimates are preliminary, and should be re-evaluated
More informationJoseph Brennemann Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationAlessandro Volta Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More information4. Plumbing fixtures. a) The plumbing fixtures are from the original building. They are appear old and not to comply with ADA requirements.
From: Jian Zhang Sheet: 1 of 8 Date of Visit: 12/7/10 Coach House: Plumbing Systems b) All original building storm piping shows significant signs of aging. b) All original building sanitary piping shows
More informationHigh Performance Building Guide 1
Description This Guide is intended to be used for projects with a Vermont Certified: High Performance energy efficiency goal. This High Performance goal is a whole-building efficiency approach rather than
More informationGarfield Elementary School Feasibility Study for New Library Building Project Number A C
Larry Teixeira Selma Unified School District 3036 Thompson Avenue Selma, CA 93662 Subject: Feasibility Study for New Library Building Project Number A 12-8581.00 C Dear Mr. Teixeira: At your request, we
More informationJosefa Ortiz De Dominguez Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationS AGE E NGINEERING A SSOCIATES, LLP
S AGE E NGINEERING A SSOCIATES, LLP 1211 Western Avenue Albany, NY (518) 453 6091 F (518) 453 6092 Kingston Library Mechanical and Electrical Systems Field Report Date of Visits: Mechanical - September
More informationMassachusetts School Building Authority
Massachusetts School Building Authority School District Revere District Contact Paul Dakin TEL: (781) 286-8226 Name of School Submission Date 3/6/2007 The following Priorities have been included in the
More informationVanilla Box Design Criteria
Description: 1. Floor: 2. Walls: 3. Ceiling: A. Finished and sealed 4 thick concrete slab on 10 mil poly vapor barrier on 4 of crushed stone throughout, including toilets. A. Interior gypsum board walls
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Calgary RCSSD #1 Ecole St. Matthew Elementary / French Immersion Jr. High School B2614A Calgary Report run on: March 25, 2010 10:11 AM Building Name: Address: Location:
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Edmonton RCSSD #7 Bishop Savaryn Catholic Elementary School B358A Edmonton Report run on: March 11, 213 5:9 PM Building Name: Address: Location: Building Id: Gross Area
More informationSafe at Home. Suggestions for Homeowner Created in partnership with the Administration on Aging. Assessor: Assessor: Homeowner Name: Address:
Assessor: Assessor: 1. EXTERIOR ENTRANCES AND EXITS Do you any difficulty getting in and out of your home? Which entrance(s) do you use the most? Have you had any falls or safety concerns? I want you to
More information7/14/2016 CITY HALL ADA ENHANCEMENT/REMODEL ACTION PLAN 1978 Construction
CITY HALL ADA ENHANCEMENT/REMODEL 2016 ACTION PLAN 1978 Construction 1 HISTORY At the February 2, 2016 Council Workshop Council Motions included: The direction to staff to move forward with the City Hall
More informationSidney Sawyer Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationState College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT
State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Lakeland Roman Catholic Separate School District No. 1 Ecole Notre Dame High School B266A Bonnyville Report run on: January 26, 2 : PM Bonnyville - Ecole Notre Dame High
More informationElectrical Information
Electrical Information Breaker Panel 1: Service Type: Unreadable Panel Type: Unreadable Panel Number: Unreadable Manufacturer: Unreadable Amps: Unreadable Location: Storage Room Notes: Exterior Disconnect
More informationEl 0. El 0. El El. El El. El 0 TWO FAMILY HOUSING INSPECTINO CHECKLIST
ONE TWO FAMILY HOUSING INSPECTINO CHECKLIST Owner Name Property address Date of Inspection Inspector AREA OF INSPECTION COMPLAINT COMMENTS 1 Fences 2 Dumpsters 3 Trash building materials junk cars branches
More informationFacilities Master Planning
Facilities Master Planning DeForest Area School District DeForest, WI PRA Project #130343-01 January 13, 2014 DRAFT Table of Contents DeForest Area School District PRA Project # 130217-01 Section 1 Existing
More informationMUKWONAGO SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY
MUKWONAGO SCHOOL DISTRICT ARCHITECTURE PARK VIEW MIDDLE SCHOOL The original school building was dedicated in 1954 as the High School, with an addition in 1959, a library addition in 1970, and an addition/renovation
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Calgary School District #19 Sir William Van Horne High School B2852A Calgary Report run on: March 25, 2010 10:19 AM Building Name: Address: Location: Building Id: Gross
More informationRental Housing Inspection Guide
BOONE FIRE DEPARTMENT Rental Housing Division 515-432-3446 www.boonegov.com/rental BUILDING DEPARTMENT Rental Housing Inspection Guide Boone Fire Department Welcome to the Rental Housing Inspection Guide
More information2015 Bernice Bienenstock Furniture Library Interior Design Competition
2015 Bernice Bienenstock Furniture Library Interior Design Competition Competition Objective The objective of this project is to test students interior design skills. The format has been modeled after
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Edmonton RCSSD #7 Cardinal Leger Catholic Junior High School B371A Edmonton Report run on: April 3, 29 1:1 AM Building Name: Address: Location: Building Id: Gross Area
More informationJohn Palmer Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationOriginal Building Plans 1954
Building Asbury Kitchen Chancel Sanctuary Pastor Study Narthex Original Building Plans 1954 4 Entrances Main Entry Building Evolution Original Building 1954 New Parking 5 Entrances Main Entry Building
More informationFACILITY ACTION PLAN
FACILITY Mary Baker Russell Music Center CURRENT ENERGY USE INDEX (EUI) 293 kbtu/sq Ft 26.83 kwh/sq Ft FACILITY LIASON(S) David Robbins Chair of the Department of Music FACILITY ACTION PLAN TARGET EUI
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Edmonton RCSSD #7 Our Lady Of The Prairies Catholic Elementary School B3241A Edmonton Report run on: July 17, 2008 4:00 PM Building Name: Address: Location: Building Id:
More informationJudge s Checklist 2015 Bernice Bienenstock Furniture Library Interior Design Competition
Judge: Sponsored by: Project#: Judge s Checklist 2015 Bernice Bienenstock Furniture Library Interior Design Competition Competition Objective The objective of this project is to test students interior
More informationBriar Crest Elementary
Promises Kept This document includes partial lists of major projects completed at Pattonville Schools since 1986 as part of past bond issues approved by the Pattonville community. Briar Crest Elementary
More informationAGING IN PLACE CHECKLIST Use this checklist to identify fall hazards and accessibility for the homeowner and family members.
AGING IN PLACE CHECKLIST Use this checklist to identify fall hazards and accessibility for the homeowner and family members. EXTERIOR ENTRANCES AND EXITS: Note condition of walk and drive surface; existence
More informationRECAPP Facility Evaluation Report
RECAPP Facility Evaluation Report Edmonton RCSSD #7 Blessed Kateri School B36A Edmonton Report run on: April 3, 29 1:1 AM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement
More informationENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING
Mechanical Systems Information The mechanical system at Reed Middle School is comprised of seventy six Trane DX/Gas rooftop units (RTUs). The recommended useful life for DX equipment is 15 years. Seventy
More information1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT
Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story
More informationSummary of Repairs and Deficiencies
Summary of s and Deficiencies Organization Building: Station #1 178 Safety & Compliance Inspections and Certifications Sprinkler System Certifications This building is sprinkled but no inspection/ certification
More informationDeWitt Clinton Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationInside Out Home Inspections
Cover Page Inside Out Home Inspections Property Inspection Report Inspection prepared for: John Doe & Jane Doe Date of Inspection: 5/10/2014 Inspector: Lucas Sargent PO Box 514, Tioga, PA 16946 Phone:
More informationMaintenance Road Show
Maintenance Road Show What does it take to maintain a campus? What are the costs? Buildings: 267 Campus Sq. Feet: 3,470,408 GSF Roads: 8.28 miles Walkways: 8.81 miles Exterior lights: 1,000 Exterior stairways:
More informationHabitability Guidelines
Habitability Guidelines for Relocated Manufactured Homes dced.pa.gov/mh @PADCEDnews Purpose The purpose of these habitability guidelines is to provide a reasonable level of assurance that the relocated
More informationChariho Regional School District Five-Year Capital Facilities Improvement Plan (2/10/15)
Chariho Regional School District Five-Year Capital Facilities Improvement Plan (2/10/15) School/Department FY 16 FY 17 FY18 FY19 FY20 Chariho Regional High School FY 16 FY 17 FY18 FY19 FY20 *Repair Bleachers
More informationElectrical Inspection Lighting & Power
0921 Light Fixtures & Controls Fixtures, controls, conduit, wiring, etc. Interior classroom and corridor lighting consists of T12 fluorescent lamps with magnetic ballasts. In the classrooms the luminaires
More informationBranch Capital Improvement Feasibility Update
Branch Capital Improvement Feasibility Update Ocean View Mission Chinatown Work to date - Conducted a Survey Monkey Design charrettes for each branch Issue charrette findings Conceptual feasibility analysis
More information