Report of the Committee on Makhoul (Mike) T. Kadri, Automotive and Marine Service Stations Patrick A. McLaughlin, John S. Robison, Robert L.

Size: px
Start display at page:

Download "Report of the Committee on Makhoul (Mike) T. Kadri, Automotive and Marine Service Stations Patrick A. McLaughlin, John S. Robison, Robert L."

Transcription

1 Report of the Committee on Automotive and Marine Service Stations John S. Robison, Chair Alabama State Fire Marshal s Office, AL [E] Rep. International Fire Marshals Association E. Joseph Bocci, US Department of the Treasury, DC [U] Frank J. Cihak, American Public Transportation Association, DC [U] Mel Cosgrove, Southern Building Code Congress Int l./icc, AL [E] Hugh Council, Worlds Best Truck Stops, CA [U] Sullivan D. Curran, Fiberglass Tank & Pipe Institute, TX [M] Brian C. Donovan, Steel Tank Insurance Company, VT [I] Arthur C. Fink, Jr., Husky Corporation, MO [M] Thomas J. Forsythe, Gage-Babcock & Associates, Inc., CA [ SE] Albert G. Garlatti, Intertek Testing Services NA Inc., MN [RT] Fred B. Goodnight, Amerex Corporation, AL [M] Rep. Fire Equipment Manufacturers Association Larry R. Gregory, ExxonMobil Fuels Marketing Company, VA [U] Rep. American Petroleum Institute Keith W. Gustafson, Chart Industries, Incorporated, GA [M] James W. Hannah, Jr., Jones & Frank Corporation, SC [I M] John P. Hartmann, Hartmann Management Services Inc., IL [SE] Donald Hausz, All Out Fire Equipment Company, Inc., NY [I M] Rep. National Assn. of Fire Equipment Distributors Inc. John P. Higgins, Mutual Service Office, NJ [I] Marshall A. Klein, Marshall A. Klein & Associates, Inc., MD [U] Rep. Automotive Oil Change Association Donald L. Leininger, OPW Fueling Components, OH [M] Martin E. Magera, Underwriters Laboratories Inc., IL [RT] Gerry E. Misel, Jr., Georgia Gas Distributors, Inc., GA [I M] Armin E. Mittermaier, Data Action, IN [U] Rep. Petroleum Marketers Association of America William E. Rehr, BOCA International, Inc., IL [E] Robert N. Renkes, Petroleum Equipment Institute, OK [M] Robert C. Schultz, University of Texas at Austin, TX [U] Henry E. Seiff, Natural Gas Vehicle Coalition, DC [M] Rep. Natural Gas Vehicle Coalition Richard Sharpe, Plasteel International Inc., CA [M] W. M. Shaughnessy, Nantucket Fire Department, MA [ E] Brian P. Stuber, Oldcastle Precast/Utility Vault, AZ [M] Rep. Oldcastle Precast, Inc. Andrea R. Zajac, Michigan Dept. of Environmental Quality, MI [E] Makhoul (Mike) T. Kadri, Michigan Dept. of Environmental Quality, MI [E] (Alt. to A. R. Zajac) Patrick A. McLaughlin, McLaughlin & Associates, RI [M] (Alt. to S. D. Curran) Robert L. Murray, OPW Fueling Components, OH [M] (Alt. to D. L. Leininger) Richard A. Powell, Autry Petroleum Company, GA [U] (Alt. to A. E. Mittermaier) Jeffrey M. Shapiro, International Code Consultants, TX [ M] (Alt. to B. P. Stuber) Bruce J. Swiecicki, National Propane Gas Association, IL [ I M] (Alt. to G. E. Misel) Nonvoting Donald M. Johnson, Walnut Creek, CA (Member Emeritus) Staff Liaison: Carl H. Rivkin Committee Scope: This Committee shall have primary responsibility for documents on safeguarding against the fire and explosion hazards associated with the storage, handling, and dispensing of flammable and combustible liquids at automotive and marine service stations and with related activities such as lubrication, minor repairs, adjustments, and routine maintenance work. This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time, changes in the membership may have occurred. A key to classifications is found at the front of this book. The Report of the Technical Committee on Automotive and Marine Service Stations is presented for adoption. This Report was prepared by the Technical Committee on Automotive and Marine Service Stations and proposes for adoption, the withdrawal of NFPA 88B, Standard for Repair Garages, 1997 edition. NFPA 88B-1997 is published in Volume 4 of the 2001 National Fire Codes and in separate pamphlet form. This Report has been submitted to letter ballot of the Technical Committee on Automotive and Marine Service Stations which consists of 30 voting members. The results of the balloting, after circulation of any negative votes, can be found in the report. Alternates David M. Hammerman, Marshall A. Klein and Associates, Inc., MD [U] (Alt. to M. A. Klein) Shari L. Hunter, Underwriters Laboratories Inc., CA [RT] (Alt. to M. E. Magera) 862

2 (Log #1) 88B-1-(1-1.2) : Reject This standard does not apply to Reference shall be made to NFPA 30A, Automotive and Marine Service Station Code, for requirements for automotive and marine service stations and buildings used for lubrication, inspection, and minor automotive maintenance work such as tune-ups and brake system repair as addressed in NFPA 30A, Automotive and Marine Service Station Code. SUBSTANTIATION: The proposed language better clarifies that issues not addressed by 88B are sent to NFPA 30A. Editorial clarification. COMMITTEE STATEMENT: The proposal states that NFPA 88B is not applicable which is not correct. The intent is to provide an additional reference to NFPA 30A not to the exlusion of NFPA 88B. COMMENT ON AFFIRMATIVE: SEIFF: Please change the old name of NFPA 30A in this section to reflect the new name. (Log #3) 88B-2-( ) : Reject Spray Painting and Undercoating Spray painting and undercoating shall conform to NFPA 33, Standard for Spray Application Using Flammable or Combustible Materials Where only a small portion of a vehicle is spray painted and no accumulations of paint residue are allowed to form, such occasional painting shall be permitted in the open in the structure if located not less than 20 ft (6.1 m) horizontally from all open flame devices or spark-producing electrical equipment or appliances Undercoating spray operations conducted in any area having adequate natural or mechanical ventilation shall be exempt from the requirements pertaining to spray finishing operations where the undercoating materials are nonflammable or where the solvents used have a flash point in excess of 100 F (37.8 C) (closed cup). There shall be no open flame devices or spark-producing electrical equipment or appliances within 20 ft (6.1 m) horizontally while such operations are conducted. Undercoating materials shall be dry before starting the engine of the undercoated vehicle Undercoating spray operations not conforming to the provisions of shall conform to all requirements of NFPA 33, Standard for Spray Application Using Flammable or Combustible Materials. SUBSTANTIATION: NFPA 88B should comply with the requirements of NFPA 33 and not deviate from those requirements. The proposed wording would add undercoating to comply with NFPA 33 and eliminate the requirements not consistent with NFPA 33. COMMITTEE STATEMENT: The submitter did not explain why the more restrictive requirements of NFPA 33 should apply. AFFIRMATIVE: 17 ABSTENTION: 1 EXPLANATION OF ABSTENTION: SEIFF: I am not familiar with the requirements of NFPA 33 and I have limited expertise in this area. NOTE: Since the ballot on this Proposal did not confirm the Committee Action, the Committee is soliciting public comment for review when the proposal is reconsidered by the Committee as a Public Comment. (Log #7) 88B-3-( ) : Reject Cleaning of parts shall not be performed with a flammable or combustible solvent. Exception: The use of combustible liquid with a flash point above 37.8 C(100 F) (closed cup) shall be permitted only in listed parts cleaning unit. SUBSTANTIATION: Better clarifies which type of cleaning solvent is to be used. Also clarifies that when combustible liquids are used that they be in a listed parts cleaner. 863 principle in part but because the document is to be withdrawn this proposal would be considered in the next revision of NFPA 30A, Code for Motor Fuel Dispensing Cleaning of parts shall not be performed with a flammable or combustible solvent. AFFIRMATIVE: 14 NEGATIVE: 4 EXPLANATION OF NEGATIVE: CURRAN: The exception needs to be retained and modified, without the exception cleaning solvents would be banned entirely and there should be a provision for small quantities of parts cleaning. MAGERA: I am voting No on 88B-3 (Log #7) because the Committee Action: statement is not clear and, in fact, could be potentially catastrophic to manufacturers and user of parts cleaners using mineral spirits based solvents. Also the Committee Statement: seems to lack validity. Committee Action: - 88B-3 (Log #7) included proposed text changes to both and the Exception to (although there is a remote possibility that the proposed Exception was intended to be in addition to the existing Exception). As I understand it, the Committee Action was to accept the revised text for , but to reject the proposed Exception. As submitted for Ballot the Revise to read: statement only addresses the text change for , while the disposition of the Exception, be it the original or the proposed (or possibly the additional) is not indicated. While it might be understood or implied that the Committee intended to retain the original Exception while rejecting the proposed Exception, this is not at all clear. If goes to print without the Exception, it should be noted that 95% of all existing parts cleaners (they being of the mineral spirits type) would be rendered not in compliance with Code requirements. Committee Statement: - The Committee Statement to reject the Proposed Exception was based on the lack of a minimum quantity statement. While it is true that no such statement was proposed, it should be noted that the original Exception made no reference to minimum quantity either. Since the Proposed Exception added little more than the need for listed parts cleaners (for those using flammable and combustible solvents but not water based solvents) the Committee Statement would need to address the issue (with great difficulty I believe) that the listing of a parts cleaner did not necessarily enhance its safety. Or, if the proposed Exception was intended to replace the existing exception, the Committee could have cited the lack of references to ventilation and ignition sources, which appeared in the original, but not the proposed Exception. This, too, would have been a weak justification as ventilation and ignition source statements could easily have been added by the committee. (This further raises the question as to whether the submitter intended his proposed Exception to replace or supplement the existing Exception.) SEIFF: In reference to the original proposal: if there is no evidence of a safety problem with the present requirements, there would seem to be no need for the additional requirement of a listed parts cleaning unit. The Committee Action seems to be even more restrictive by totally removing the exception (allowing limited use of combustible solvent) with no safety justification. SHAPIRO: I think that the committee, in processing this item overlooked the fact that there was an existing exception for parts cleaners. The intent of the committee action, as I understood it, was to NOT ADD a new requirement that parts cleaners be required for cleaning with flammable or combustible liquids without some quantity threshold. While I agree with this in concept, the non-quantity sensitive exception that already exists in the code is better than no exception at all. It makes no sense to delete the existing exception and make the code even more restrictive without justification. This is especially true when one considers the discussion at the committee meeting, which indicated that the proposed new exception should ve been more liberal. (Log #4) 88B-4-( ) : Reject Chassis cleaning shall not be performed with flammable liquids. having flash points below 140 F (60 C) (closed cup). If steam is used, it shall be supplied from a boiler located, installed, and safeguarded in accordance with the applicable requirements for heating equipment set forth in Section 3-2 of this standard and in the following documents: NFPA 31, Standard for the Installation of Oil-Burning Equipment; NFPA 54, National Fuel Gas Code; NFPA 8501, Standard for Single Burner Boiler Operation; and NFPA 8502, Standard for the Prevention of Furnace Explosions/ Implosions in Multiple Burner Boiler-Furnaces. SUBSTANTIATION: As currently worded all flammable liquids are below a flash point of 140 F. The deletion of the wording eliminates confusion.

3 Delete the word flammable from the first line of and retain struck text. (Log #8) 88B-5-( ) : Reject Chassis cleaning shall not be performed with flammable liquids or combustible liquids having flash points below 60 C(140 F) (closed cup). If steam is used, it shall be supplied from a boiler located, installed, and safeguarded in accordance with the applicable requirements for heating equipment set forth in Section 3-2 of this standard and in the following documents: NFPA 31, Standard for the Installation of Oil-Burning Equipment; NFPA 54, National Fuel Gas Code; NFPA 8501, Standard for Single Burner Boiler Operation; and NFPA 8502, Standard for the Prevention of Furnace Explosions/Implosions in Multiple Burner Boiler-Furnaces. SUBSTANTIATION: The current wording is inconsistent with the definition of flammable liquid which is a flash point 100 F. The addition of the wording combustible is consistent Chassis cleaning shall not be performed with liquids having flash points below 60 C(140 F) (closed cup). If steam is used, it shall be supplied from a boiler located, installed, and safeguarded in accordance with the applicable requirements for heating equipment set forth in Section 3-2 of this standard and in the following documents: NFPA 31, Standard for the Installation of Oil-Burning Equipment; NFPA 54, National Fuel Gas Code; NFPA 8501, Standard for Single Burner Boiler Operation; and NFPA 8502, Standard for the Prevention of Furnace Explosions/Implosions in Multiple Burner Boiler-Furnaces. (Log #5) 88B-6-(3-5) : Reject 3-5 Storage and Handling of Flammable and Combustible Liquids, Liquefied Petroleum Gases, and Compressed Natural Gases The storage and handling of flammable and combustible liquids shall be in accordance with NFPA 30, Flammable and Combustible Liquids Code. The storage and handling of liquefied petroleum gas shall be in accordance with NFPA 58, Standard for the Storage and Handling of Liquefied Petroleum Gases. The storage and handling of flammable compressed gas fuels shall be in accordance with NFPA 55, Standard for the Storage, Use, and Handling of Compressed and Liquefied Gases in Portable Cylinders, and NFPA 52, Standard for Compressed Natural Gas (CNG) Vehicular Fuel Systems Dispensing of Flammable and Combustible Liquids. The design and installation of equipment used for the dispensing of flammable and combustible liquids shall be in accordance with the requirements for service stations as set forth in NFPA 30, Flammable and Combustible Liquids Code. SUBSTANTIATION: Combustible liquids should also be regulated by NFPA Storage and Handling of Flammable and Combustible Liquids, Liquefied Petroleum Gases, and Compressed Natural Gases Except as otherwise provided by this standard, the storage and handling of flammable and combustible liquids shall be in accordance with NFPA 30, Flammable and Combustible Liquids Code. The storage and handling of liquefied petroleum gas shall be in accordance with NFPA 58, Standard for the Storage and Handling of Liquefied Petroleum Gases. The storage and handling of flammable compressed gas fuels shall be in accordance with NFPA 55, Standard for the Storage, Use, and Handling of Compressed and Liquefied Gases in Portable Cylinders, and NFPA 52, Standard for Compressed Natural Gas (CNG) Vehicular Fuel Systems Dispensing of Flammable and Combustible Liquids. The design and installation of equipment used for the dispensing of flammable and combustible liquids shall be in accordance with the requirements for service stations as set forth in NFPA 30, Flammable and Combustible Liquids Code. COMMENT ON AFFIRMATIVE: SHAPIRO: The introductory text Except as otherwise provided by this standard should be underlined, as this was added by the committee as new text in the committee action. Please note that the committee also agreed during processing of this item to submit a committee proposal to NFPA 30A, Section to match the modified text of NFPA 88B, Section 3-5 (as revised by this item). I realize that this would not appear in the ballot, but I wanted to make sure that the action is not lost prior to processing of NFPA 30A in the next cycle. (Log #6) 88B-7-(4-1) : Reject 4-1 Automatic Sprinklers. Approved automatic sprinkler equipment installed in conformance with NFPA 13, Standard for the Installation of Sprinkler Systems, shall be provided in repair garages under the following conditions: (a) Repair garages more than one story in height or located beneath another occupancy that exceed an area on any one floor of 10,000 ft2 (929 m2) if of Type I construction; 8000 ft 2 (743 m 2 ) if of Type II (222) or Type II (111) construction; or 6000 ft 2 (557 m 2 ) if of Type II (000), Type III, Type IV, or Type V construction. (b) One-story repair garages exceeding an area of 15,000 ft 2 (1394 m 2 ) if of Type I construction; 12,000 ft 2 (1115 m 2 ) if of Type II (222) or Type II (111) construction; 9000 ft 2 (836 m 2 ) if of Type II (000), Type III, or Type IV construction; or 6000 ft 2 (558 m 2 ) if of Type V construction. (c) All below-grade floors of repair garages. the ceilings of which are less than 2 ft (.61 m) above grade Add a new definition of Below-grade to read: Below-Grade. A floor is considered below-grade when the ceiling is less than 2 ft (.61 m) above grade. SUBSTANTIATION: The proposed definition has been taken from (c) which provided the definition within the requirement. Other sections of the standard, in particular 3-3.3, uses the term below-grade with no definition. For consistency and usability we believe the proposed change is needed. Add 7.4.6(3) and the definition of basement from NFPA 30A to NFPA 88B. AFFIRMATIVE: 17 NEGATIVE: 1 EXPLANATION OF NEGATIVE: SEIFF: This issue appears to have been better handled by 88B-8 (Log #2). (Log #2) 88B-8-(4-1(b) Exception) : Reject 4-1 Automatic Sprinklers. Approved automatic sprinkler equipment installed in conformance with NFPA 13, Standard for the Installation of Sprinkler Systems, shall be provided in repair garages under the following conditions: (a) Repair garages more than one story in height or located beneath an-

4 other occupancy that exceed an area on any one floor of 10,000 ft2 (929 m2) if of Type I construction; 8000 ft 2 (743 m 2 ) if of Type II (222) or Type II (111) construction; or 6000 ft 2 (557 m 2 ) if of Type II (000), Type III, Type IV, or Type V construction. (b) One-story repair garages exceeding an area of 15,000 ft2 (1394 m2) if of Type I construction; 12,000 ft 2 (1115 m 2 ) if of Type II (222) or Type II (111) construction; 9000 ft 2 (836 m 2 ) if of Type II (000), Type III, or Type IV construction; or 6000 ft 2 (558 m 2 ) if of Type V construction. Exception to (b): When a four-hour fire resistance rated fire wall is installed in accordance with NFPA 221 and each area separated by the fire wall does not exceed those specified in 4-1(b). (c) All below-grade floors of repair garages, the ceilings of which are less than 2 ft (.61 m) above grade. SUBSTANTIATION: This change is to address Formal interpretation If a fire wall is installed to divide the area to below those specified in 4-1(b) automatic sprinklers do not need to be provided. Revise to read: Automatic sprinkler protection installed in accordance with the requirements of NFPA 13, Standard for the Installation of Sprinkler Systems, shall be provided in major repair garages, as herein defined, when any of the following conditions exist: (1) The major repair garage is two or more stories in height, including basements, and any one floor exceeds 10,000 ft 2 (930 m 2 ). (2) The major repair garage is one story and exceeds 15,000 ft /2 (1400 m 2 ) in floor area. (3) The major repair garage is in the basement of a building. (Log #9) 88B-9 (4-1(d) (New) ) : Reject SUBMITTER: Kenneth E. Bush, Office of the Maryland State Fire Marshal/Rep. Chair WFCA/NFPA General Ad-Hoc Committee RECOMMENDATION: Add a new (d) to 4-1 to read: (d) All repair garages over 3,000 sq ft. SUBSTANTIATION: The proposed text would provide for a new trigger for the automatic suppression requirements to be applied, premised upon the area of the occupancy. The proposal merely recognizes the hazards associated with repair garages and establishes a threshold to appropriately contain the challenges of such an occupancy that could be unprotected to only 3,000 sq ft. The introduction of special hazards inherent with the major repair operations on automobiles, including, but not limited to the storage and handling, including spray application, of flammable and combustible liquids require additional fire safety measures in order to maintain adequate levels of protection for building occupants, contents and structural features. Where such operations are not confined to a small area or building in occupancies of this nature, the installation of automatic sprinkler protection should be 865

5 required in order to provide the necessary minimum levels of protection. COMMITTEE STATEMENT: The submitter has not provided substantiation for the 3,000 square foot cut off number given in the proposal. However, the committee will review the concept described in the proposal at the next NFPA 30A Report on Proposal Meeting. NFPA 88B is proposed to be withdrawn and this proposal, if adopted, would likely reside in NFPA 30A. NUMBER OF COMMITTEE MEMBERS ELIGIBLE TO VOTE: (Log #CP2) 88B-10-(Entire Document) : Accept SUBMITTER: Technical Committee on Automotive and Marine Service Stations, RECOMMENDATION: The Technical Committee on Automotive and Marine Service Stations proposes a withdrawal of NFPA 88B, Standard for Repair Garages, 1997 edition. The document would be withdrawn and any changes would be made in the appropriate sections of NFPA 30A at the next revision cycle. SUBSTANTIATION: As an effort to increase ease of use, the requirements of NFPA 88B were incorporated into the 2000 edition of NFPA 30A. The document was not withdrawn immediately to allow for a phased out transition. COMMITTEE ACTION:Accept 866

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on

Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on Report on Proposals F2007 Copyright, NFPA NFPA 499 Report of the Committee on This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time, changes

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

NFPA Technical Committee on Fire Tests

NFPA Technical Committee on Fire Tests National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Tracy

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

Report on Comments F2006 Copyright, NFPA NFPA 560 Report of the Committee on

Report on Comments F2006 Copyright, NFPA NFPA 560 Report of the Committee on Report on Comments F2006 Copyright, NFPA NFPA 560 Report of the Committee on Nonvoting Industrial and Medical Gases Michael W. St. Clair, Chair Ostrander, OH [U] Rep. NFPA Industrial Fire Protection Section

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Construction

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Industrial and Medical Gases

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fire Code (FCC-AAA) Gregory

More information

Report of the Committee on Industrial Trucks

Report of the Committee on Industrial Trucks Report of the Committee on Industrial Trucks John IL Bouchard, Chair Sedgwick of New England, MA [I] Lewis C. Barbe, World Safety Organization, MN [SE] Bryan Bower, Buckeye Fire Equipment, NC [M] Rep.

More information

Committee on NFPA 30A

Committee on NFPA 30A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Automotive and Marine Service Stations Patti Mucci, Administrative Assistant DATE: February 5, 00 SUBJECT: ROP Letter Ballot The ROP

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels

More information

TECHNICAL COMMITTEE ON FIRE CODE

TECHNICAL COMMITTEE ON FIRE CODE TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2

More information

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Portable Fire Extinguishers

More information

Report of the Committee on. Hazardous Chemicals

Report of the Committee on. Hazardous Chemicals Report of the Committee on Hazardous Chemicals Samuel Vanover, Chair Jefferson Parish Fire Department, LA [E] Rep. International Fire Marshals Association Anthony Andrews, Crompton Corporation, TX [M]

More information

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies

More information

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas

Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Preliminary Agenda Technical Committee on Liquefied Petroleum Gas Tuesday, March 10; All Day Wednesday, March 11; All Day DRURY PLAZA HOTEL San Antonio Riverwalk 0. Administrative. A. Meeting Schedule.

More information

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement 1 of 7 3/4/2016 12:02 PM Second Revision No. 5-NFPA 56-2016 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by

More information

2016 Annual Revision Cycle Consent Document NFPA 75

2016 Annual Revision Cycle Consent Document NFPA 75 2016 Annual Revision Cycle Consent Document NFPA 75 The Committee on Electronic Computer Systems produced a Technical Committee Report that received at least one Notice of Intent to Make a Motion (NITMAM)

More information

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Correlating Committee on Signaling Systems for

More information

1. Call to Order. The meeting was called to order at 1:05 PM. (See Enclosure A [Agenda])

1. Call to Order. The meeting was called to order at 1:05 PM. (See Enclosure A [Agenda]) FINAL MINUTES Healthcare Interpretations Task Force Tuesday, June 15, 2016 Mandalay Bay Convention Center South Convention Center, Level 2 Room Surf F Las Vegas, NV 1. Call to Order. The meeting was called

More information

NFPA Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems

NFPA Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems San Antonio, TX October 12-14, 2016 The following are the meeting minutes from the third meeting of the Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems held in San Antonio,

More information

Page 1 of 19 Committee Input No. 14-NFPA 33-2013 [ Global Input ] Type your content here... Supplemental Information File Name IndoorDraftforCI.docx Description This committee input would be added to new

More information

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

Report on Proposals A2006 Copyright, NFPA NFPA 105 Report of the Committee on

Report on Proposals A2006 Copyright, NFPA NFPA 105 Report of the Committee on Report of the on David F. Mauldin, Schindler Elevator Corporation, PA [M] (Alt. to Edward A. Donoghue) Fire Doors and Windows Kurt A. Roeper, Ingersoll Rand Security and Safety, OH [M] (Alt. to Thomas

More information

Committee on 51A M E M O R A N D U M. NFPA Technical Committee on Industrial and Medical Gases

Committee on 51A M E M O R A N D U M. NFPA Technical Committee on Industrial and Medical Gases Committee on 51A M E M O R A N D U M To: From: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant Date: June 14, 2010 Subject: NFPA 51A ROC Letter Ballot Circulation

More information

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017)

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Fire Code Kelly Carey,

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M National Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Industrial and Medical Gases Joanne

More information

Public Comment No. 7-NFPA 30A-2013 [ Section No ]

Public Comment No. 7-NFPA 30A-2013 [ Section No ] Page 1 of 13 Public Comment No. 7-NFPA 30A-2013 [ Section No. 6.4.2 ] 6.4.2 Additional Proposed Changes Each pump shall have installed on the discharge side a listed leak detection device that will provide

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS

REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS REPORT OF THE NFPA MOTIONS COMMITTEE* ON FALL 2013 REVISION CYCLE STANDARDS I. Introduction. This is the Motions Committee Report on Standards in the Fall 2013 Revision Cycle. The report identifies Certified

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018) M EM O RA N D UM TO: FROM: DATE: SUBJECT: Correlating Committee on Combustible Dusts Yiu Lee, Project Administrator January 27, 2017 NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

More information

Correlating Committee on Automatic Sprinkler Systems

Correlating Committee on Automatic Sprinkler Systems Correlating Committee on Automatic Sprinkler Systems M E M O R A N D U M DATE: May 14, 2014 TO: FROM: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems Matt Klaus,

More information

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES 1.

More information

NFPA 30. Flammable and Combustible Liquids Code Edition. Copyright 2003, National Fire Protection Association, All Rights Reserved

NFPA 30. Flammable and Combustible Liquids Code Edition. Copyright 2003, National Fire Protection Association, All Rights Reserved NFPA 30 Flammable and Combustible Liquids Code 2003 Edition Copyright 2003, National Fire Protection Association, All Rights Reserved This edition of NFPA 30, Flammable and Combustible Liquids Code, was

More information

NEC ROP/ROC Code Making Panel Meetings

NEC ROP/ROC Code Making Panel Meetings Phoenix AZ - December 4-16 2000 Log # 2367 2-64 - ( 210-8(b)(3) ): SUBMITTER: Monte R. Ewing State of Wisconsin The panel reaffirms its action and statement on Proposal 2-81. There is no supporting data

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Residential

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

- Residential Fire Sprinkler -

- Residential Fire Sprinkler - - Residential Fire Sprinkler - Update as of September 15, 2014 The information provided is a state-by-state status of the 2009 IRC adoption and legislation activities as reported by HBA s. NAHB staff monitors

More information

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12.

Location of Requirements Listed Category I appliances Type B gas vent 12.7 Listed appliances equipped with. Chimney Single wall metal pipe 12. 2/18/2016 National Fire Protection Association Report Committee Input No. 70 NFPA 54 2015 [ Section No. 12.5 ] This was a First Revision that failed ballot. 12.5 Type of Venting System to Be Used. 12.5.1

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Residential Occupancies Kelly

More information

Fire Code Action Committee (F-CAC) Meeting Minutes June 19-20, 2012 Chicago IL. Summary of Actions and Regional Work Group (RWG) Assignments

Fire Code Action Committee (F-CAC) Meeting Minutes June 19-20, 2012 Chicago IL. Summary of Actions and Regional Work Group (RWG) Assignments Fire Code Action Committee (F-CAC) Meeting Minutes June 19-20, 2012 Chicago IL Fire-CAC Members in Attendance Anthony Apfelbeck (Vice-Chairman) Daniel Finnegan Howard Hopper, P.E. Andrew King Kelly Nicolello

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 14 From: Kimberly Shea, Project Administrator

More information

Report of the Committee on. Airport Facilities. Gene E. Benzenberg, Chair Alison Control Incorporated, NJ [M]

Report of the Committee on. Airport Facilities. Gene E. Benzenberg, Chair Alison Control Incorporated, NJ [M] Report of the Committee on Airport Facilities Gene E. Benzenberg, Chair Alison Control Incorporated, NJ [M] Dennis C. Kennedy, Secretary Tyco Suppression Systems, WI [M] (Alt. to C. J. Marsolo) Michael

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Correlating Committee on Combustible Dusts Susan

More information

NFPA 211. Standard for Chimneys, Fireplaces, Vents, and Solid Fuel- Burning Appliances Edition

NFPA 211. Standard for Chimneys, Fireplaces, Vents, and Solid Fuel- Burning Appliances Edition NFPA 211 Standard for Chimneys, Fireplaces, Vents, and Solid Fuel- Burning Appliances NFPA, 1 Batterymarch Park, Quincy, MA 02169-7471 An International Codes and Standards Organization IMPORTANT NOTICES

More information

First Revision No. 20-NFPA [ Section No ]

First Revision No. 20-NFPA [ Section No ] of 25 7/15/2015 8:30 AM First Revision No. 20-NFPA 56-2015 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by NFPA

More information

Circulation Report for SIG-TMS Comments Document # 72

Circulation Report for SIG-TMS Comments Document # 72 1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15

More information

Donald E. Major, Report of the Committee on James Murphy, Finishing Processes Kenneth J. Pilat, Steven J. Gunsel, John Schweitzer,

Donald E. Major, Report of the Committee on James Murphy, Finishing Processes Kenneth J. Pilat, Steven J. Gunsel, John Schweitzer, Report of the Committee on Finishing Processes Steven J. Gunsel, Chair Environmental Consultant, OH [SE] Thomas G. Euson, Secretatry 3S Incorporated, OH [IM] William C. Anderson, Approved Fire Protection

More information

TECHNICAL COMMITTEE MEMBERS WHO PARTICIPATED

TECHNICAL COMMITTEE MEMBERS WHO PARTICIPATED MEETING MINUTES NFPA Correlating Committee on Safety to Life (SAF-AAC) November 7, 2013 Second Draft Meeting Embassy Suites Atlanta Hartsfield Airport Hotel Atlanta, GA 1. Call to Order. The meeting was

More information

NFPA Technical Committee on Fire Tests FALL 2010 ROC MEETING MINUTES April 15-16, 2010 Southwest Research Institute San Antonio, TX

NFPA Technical Committee on Fire Tests FALL 2010 ROC MEETING MINUTES April 15-16, 2010 Southwest Research Institute San Antonio, TX NFPA Technical Committee on Fire Tests FALL 2010 ROC MEETING MINUTES April 15-16, 2010 Southwest Research Institute San Antonio, TX 1. Call to Order. The meeting of the Technical Committee on Fire Tests

More information

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Pumps Patti

More information

Report on Proposals June 2013 NFPA 70

Report on Proposals June 2013 NFPA 70 14-1 Log #1170m NEC-P14 Russell LeBlanc, The Peterson School In articles 90 through 830, if the wording is not already there, then add the words (or other structure(s)) after the word BUILDING(S) wherever

More information

Report on Proposals Copyright, NFPA NFPA 505 Report of the Committee on

Report on Proposals Copyright, NFPA NFPA 505 Report of the Committee on Report of the Committee on Staff Liaison: James D. Lake Industrial Trucks Joseph John Dahlstrom, Chair UK and Associates, IL [SE] Lewis C. Barbe, World Safety Organization, MN [SE] Denise Beach, National

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Sprinkler System

More information

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 Kenneth Kretchman, CIH, CSP Mgr, Industrial Hygiene NC State University Ken_Kretchman@ncsu.edu International Building

More information

1. Call to Order. The meeting was called to order by Chair Jeffrey Collins at 8:00 AM, October 24, REPRESENTING

1. Call to Order. The meeting was called to order by Chair Jeffrey Collins at 8:00 AM, October 24, REPRESENTING NFPA Technical Committee on Fire Code (FCC-AAA) NFPA 1-2015 SECOND DRAFT MEETING MINUTES October 24, 2013 DoubleTree Suites by Hilton Hotel Austin, Texas 1. Call to Order. The meeting was called to order

More information

Standards and Safety Update

Standards and Safety Update Standards and Safety Update Presented By: Michael J. Johnston Executive Director Standards and Safety, NECA Update Objectives Update on NFPA 70E and NECA Safety products Update on NECA S National Electrical

More information

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM 1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling

More information

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting

TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, :00 AM - 5:00 PM EST Web/Teleconference Meeting TECHNICAL COMMITTEE ON MANUFACTURE OF ORGANIC COATINGS First Draft Meeting Agenda March 19, 2014 9:00 AM - 5:00 PM EST Web/Teleconference Meeting 1. Welcome. George Seuss, Chair 2. Introductions and Update

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

NFPA 550 ROP Meeting Minutes

NFPA 550 ROP Meeting Minutes NFPA 550 ROP Meeting Minutes NFPA Technical Committee on Fire Risk Assessment Methods (FIR-AAA) June 24, 2010 Microsoft Live Meeting 1. Call to order. The meeting was called to order at 1:00 PM on Monday,

More information

Report on Proposals F2007 Copyright, NFPA Report of the Committee on Dry and Wet Chemical Extinguishing Systems

Report on Proposals F2007 Copyright, NFPA Report of the Committee on Dry and Wet Chemical Extinguishing Systems Report of the Committee on Dry and Wet Chemical Extinguishing Systems Edward J. Kaminski, Chair Schirmer Engineering Corporation, NV [I] Paul E. Buchhofer, Building Inspection Underwriters, Inc., PA [E]

More information

MEMORANDUM. NFPA Technical Correlating Committee on Building Code. NFPA 5000 TCC Report on Proposals Letter Ballot (A2011)

MEMORANDUM. NFPA Technical Correlating Committee on Building Code. NFPA 5000 TCC Report on Proposals Letter Ballot (A2011) MEMORANDUM TO: FROM: NFPA Technical Correlating Committee on Building Code Robert Solomon DATE: April 1, 2010 SUBJ: NFPA 5000 TCC Report on Proposals Letter Ballot (A2011) In accordance with the NFPA Regulations

More information

FINAL* REPORT OF THE MOTIONS COMMITTEE

FINAL* REPORT OF THE MOTIONS COMMITTEE FINAL* REPORT OF THE MOTIONS COMMITTEE ON CERTIFIED AMENDING MOTIONS FOR PRESENTATION AT THE 2012 ASSOCIATION TECHNICAL MEETING JUNE 13-14, 2012 LAS VEGAS, NEVADA I. Introduction. This is the second and

More information

Committee Comment No. 212-NFPA [ Section No [Excluding

Committee Comment No. 212-NFPA [ Section No [Excluding of 27 12/12/2016 12:23 PM Committee Comment No. 212-NFPA 30-2016 [ Section No. 16.4.1 [Excluding any Sub-Sections] ] This was a Second Revision that has been modified or deleted as the result of Second

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE MEMORANDUM TO: FROM: NFPA 30 Technical Committee on Storage and Warehousing of Containers and Portable Tanks R. P. Benedetti DATE: September 16, 2010 SUBJECT:

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical on Fluidized Bed Boilers AGENDA Web/Teleconference 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of Members and Guests 3. Approval of Minutes from

More information

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification of 4 9/23/2016 10:20 AM Second Revision No. 6501-NFPA 5000-2016 [ Section No. 17.2.2.2.4 ] 17.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Standpipes Elena

More information

MEMORANDUM. NFPA 99 Second Draft Correlating Committee FINAL Ballot Results (A2017)

MEMORANDUM. NFPA 99 Second Draft Correlating Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Correlating Committee on Health Care Facilities Elena

More information

ROP MEETING MINUTES. 2. Introduction of Attendees. The following committee members and guests were in attendance. TECHNICAL COMMITTEE MEMBERS PRESENT

ROP MEETING MINUTES. 2. Introduction of Attendees. The following committee members and guests were in attendance. TECHNICAL COMMITTEE MEMBERS PRESENT BLD/SAF-FIR 24-25 September 2009 ROP Meeting Minutes ROP MEETING MINUTES Building Code Life Safety Technical Committee on Fire Protection Features Thursday-Friday, September 24-25, 2009 Meeting Embassy

More information

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM of 66 5/18/2015 1:01 PM Second Revision No. 36-NFPA 32-2015 [ Detail ] 6.5 Solvents (See Annex C for additional information on solvents) Submittal Date: Tue Mar 17 17:20:03 EDT 2015 Committee Statement:

More information

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Furnishings

More information

1. The meeting was called to order by Chair James Lathrop at 8:00 AM (CDT) on Wednesday, August 26, 2015.

1. The meeting was called to order by Chair James Lathrop at 8:00 AM (CDT) on Wednesday, August 26, 2015. MINUTES NFPA Technical Committee on Residential Occupancies NFPA 101 and NFPA 5000 First Draft Meeting Wednesday, August 26, 2015 InterContinental Milwaukee Milwaukee, WI 1. The meeting was called to order

More information

Compliance Guidance for non-technical managers

Compliance Guidance for non-technical managers 11699 Brookpark Road Cleveland, OH 44130 USA P: 888-826-3473 F: 216-398-8403 www.combustionsafety.com -WHITEPAPER- NFPA 56 (2012 Ed.) Standard for Fire and Explosion Prevention During Cleaning and Purging

More information

Report of the Committee on Craig C. Campbell, Venting Systems for Cooking Appliances Leonard E. Griffes, David P. Demers, Harry P.

Report of the Committee on Craig C. Campbell, Venting Systems for Cooking Appliances Leonard E. Griffes, David P. Demers, Harry P. Copyright 2001, NFPA Report of the Committee on Venting Systems for David P. Demers, Chair Demers Associates Inc., MA [SE] Phil Ackland, Phillip Ackland Holdings Ltd., Canada [SE] Bernard P. Besal, Besal

More information

MEMORANDUM. 22 Members Eligible to Vote 7 Not Returned (Bowdoin Jr., Cirone, Convery, Donsbach, Jr., Kovach, Levengood, Naper)

MEMORANDUM. 22 Members Eligible to Vote 7 Not Returned (Bowdoin Jr., Cirone, Convery, Donsbach, Jr., Kovach, Levengood, Naper) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Technical Committee on Gas Process Safety Kimberly

More information

CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS

CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS CITY OF GREATER SUDBURY (CGS) ARENA EVENTS FIRE REGULATIONS Last Updated: April 28, 2008 FIRE REGULATIONS The purpose of fire regulations is to maintain an acceptable level of fire safety within CGS facilities.

More information

CONSOLIDATED REPORT OF THE MOTIONS COMMITTEE

CONSOLIDATED REPORT OF THE MOTIONS COMMITTEE CONSOLIDATED REPORT OF THE MOTIONS COMMITTEE ON CERTIFIED AMENDING MOTIONS FOR PRESENTATION AT THE 2010 ASSOCIATION TECHNICAL MEETING, JUNE 9-10, 2010, LAS VEGAS, NEVADA I. Introduction. This is the Consolidated

More information

Report on Proposals Copyright, NFPA NFPA 1 Report of the Committee on

Report on Proposals Copyright, NFPA NFPA 1 Report of the Committee on Report of the on Jennifer Nelson, AT&T - EH&S, NY [U] (Alt. to Brian J. Denk) James S. Peterkin, HLM Design, PA [U] Uniform Fire Code (Alt. to Thomas T. Bulow) Paul J. Pinigis, Gage-Babcock & Associates,

More information

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Protected Premises Fire Alarm

More information

Diane D. Matthews, Administrator, Technical Projects. The September 19, 2013 date for receipt of the NFPA 5000 Second Draft Ballot has passed.

Diane D. Matthews, Administrator, Technical Projects. The September 19, 2013 date for receipt of the NFPA 5000 Second Draft Ballot has passed. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: Technical Committee on Fire Protection Features Diane D. Matthews,

More information

NFPA. Fire Safety Standard for Powered Industrial Trucks Including Type Designations, Areas of Use, Conversions, Maintenance, and Operations

NFPA. Fire Safety Standard for Powered Industrial Trucks Including Type Designations, Areas of Use, Conversions, Maintenance, and Operations NFPA 505 Fire Safety Standard for Powered Industrial Trucks Including Type Designations, Areas of Use, Conversions, Maintenance, and Operations 2018 IMPORTANT NOTICES AND DISCLAIMERS CONCERNING NFPA STANDARDS

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information