1 MEASURED PERFORMANCE DATA FOR HOUSE #4 INVERNESS GARDENS MILLER HOMES FEBRUARY 2013 Submitted to: NYSERDA 17 Columbia Circle Albany, NY Submitted by: HOMEPIC Team CDH Energy Corp. PO Box 641 Cazenovia, NY

2 Monitoring Approach A Campbell CR10x logger was installed to measure the performance of this house on Astilbe Path in Liverpool. The house was essentially unoccupied through May Table 1 lists the measurements that were taken and Figure 1 shows each point location in the system. Data collection started in late December 2011 and Continued through February TWC TWH Mixing Valve Space Heating Pump SRP Mixing Valve Space Heating Loop TWS TSHW Return/ Space Air TSHR TSHM Heating Coil Fan W Tankless Heater SDHW Solar Tank Ventilation Damper SV TSHS Outdoor Air Supply Air Figure 1. Schematic of System with Sensor Locations CDH Energy Corp. 1 February 2013

3 Table 1. Measured Points at Inverness Gardens House No. Label Monitored Points Channel Instrument/Meter Eng. Units 1 SRP Space Heating Pump Status/Runtime C6 Current Switch minutes 2 SDHW DHW Status/Runtime C7 Current Switch minutes 3 SV Fresh Air Ventilation Damper C8 Current Switch minutes 4 W Power MUX 1 Wattnode Power Meter kwh 5 WT Total House Power MUX 2 Wattnode Power Meter kwh 6 WAC A/C Power MUX 3 Wattnode Power Meter kwh 7 FDHW Hot Water Flowrate P1 1/2" Pulse Flow Meter gal 8 TWC Temperature Cold Water In SE2 Thermocouple F 9 TWH Temperature DHW Hot Water Out SE3 Thermocouple F 10 TWS Temperature Solar Tank Out SE4 Thermocouple F 11 TSHW Temperature Space Heating Hot Water In SE5 Thermocouple F 12 TSHM Temperature Space Heating MIXED Air SE6 Thermocouple F 13 TSHS Temperature Space Heating SUPPLY Air SE7 Thermocouple F 14 TSHR Temperature Space Heating RETURN/SPACE SE8 Thermocouple F 15 VBAT Battery Voltage V 16 TREF Reference Thermistor Temperature SE1 Thermistor C The measured power use is summarized in Table 2 and shown Figures 2, 3 and 4. Total power use was about 400 to 600 kwh per month once the house was occupied staring in June Hot water use was about gallons per day. The fan ran periodically throughout the year to provide ventilation. The total power for cooling was only 140 kwh for the 2012 cooling season, while fan power was about 450 kwh for the year (ranging from 25 kwh to 60 kwh per month once the controls were commissioned). Table 2. Summary of Measured Energy and DHW Use Total Power (kwh) Power (kwh) AC Power (kwh) DHW Use (gal/day) Data Collected Jan % Feb % Mar % Apr % May-12 58% Jun-12 93% Jul % Aug % Sep % Oct % Nov % Dec % Jan % Feb-13 14% Notes: Data were lost from May 19 to June 2 because we were not able to gain access to the house From October 5 28, 2012 the datalogger was unplugged by the HVAC technician so no power data was collected CDH Energy Corp. 2 February 2013

4 Utility bill data were only available for the early part of 2012 before the house was occupied (Table 3). We used a combination of the metered data and water heater runtime to predict some of the monthly values under occupied conditions (red data are estimates). Table 4 compares the measured data to the RemRate data. Table 3. Annual Electric and Gas Use for Occupied House Total Electric Use (kwh) Total Gas Use (therms) Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Annual 5, Notes: Red values are estimated Table 4. Comparing REMRate Data to Measured data (broken down by end use) Inverness Gardens (4944 Astible Path Liverpool) REMRATE Results Space Heating (MMBtu/yr) Peak Space Heating (MBtu/h) Fuel for Space Heating (MMBtu/yr) Fuel for Water Heating (MMBtu/yr) Space Ht & Water Ht Fuel (MMBtu/yr) Lights & Appliances (kwh) Relative Fuel Annual Cost Cost Savings Baseline , % $ 1,409 $ Proposed Improvements ,821 37% $ 522 $ 887 As Built Improvements ,606 50% $ 705 $ 704 MEASURED Results Annual Gas Use (from Bills) Annual Electric Use (from Bills) 4,953 CDH Energy Corp. 3 February 2013

5 The equipment runtimes are given in Table 5. The tankless unit runs to provide both space heating and water heating. The ventilation damper is set by the controls to operate about 60% of the time throughout the year. Table 5. Summary of Equipment Runtime in Each Month Unit Runtime (hrs) Htg Pump Runtime (hrs) Vent Damper Runtime (hrs) Data Collected Jan % Feb % Mar % Apr % May-12 58% Jun-12 93% Jul % Aug % Sep % Oct % Nov % Dec % Jan % Feb-13 14% Total Power (kw) Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Total AC Space Temperature (F) Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Figure 2. Power Use for Total House, Fan, and Air Conditioner (January 2012 to February 2013) CDH Energy Corp. 4 February 2013

6 24 Missing Data House Power Power Meters Off Hour of Day Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Day (MAX/MIN = 4.03/ 0.00 kw) Figure 3. Shade Plot Showing Power Use for Total House (January 2012 to February 2013) 2.0 Total Power (kw) January February March April May Total AC Figure 4. Power Use for Total House, Fan, and Air Conditioner (January May, 2012) CDH Energy Corp. 5 February 2013

7 Space Heating Performance The Rheem Tankless unit was originally set to supply water at 133 F. However this was not sufficient to provide space heating to the house. The supply air was only 75 to 80 F. On Jan 15, 2012 the fan speed was slowed down and the supply air temperature increased to about 86 F (fan power decreased from 230 Watts to 118 Watts). However the house was still not maintained at set point temperature as shown by Figure 5 below. Unit 01/10/12 to 01/15/12 Vnt Dmpr Htg Pmp Temperature (F) Supply Air Return Air Mixed Air Water Temperatures 01/10/12 to 01/15/12 Temperature (F) HW to Coil DHW Hot DHW Cold Solar Out Figure 5. System Performance for January 10 15, 2012 CDH Energy Corp. 6 February 2013

8 Total Power (kw) Total Boiler Power is about 450 Watts 0.0 Total AC Fan power is reduced from 230 to 118 Watts Space Temperature (F) Space Set point not maintained Figure 6. Power and Space Conditions for January 10 15, 2012 CDH Energy Corp. 7 February 2013

9 On February 6 the supply water set point was increased to be F to increase the heating capacity of the heating coil in the. This increased the supply air set point to just over 100 F. The system satisfied the space heating set point at this condition (as evidenced by the cycling in Figure 8). Unit 02/05/12 to 02/10/12 Vnt Dmpr Htg Pmp Temperature (F) Supply Air Return Air Mixed Air Water Temperatures 02/05/12 to 02/10/12 Temperature (F) HW to Coil DHW Hot DHW Cold Solar Out Figure 7. System Performance for February 5 10, 2012 CDH Energy Corp. 8 February 2013

10 2.0 Total Power (kw) Total AC Space Temperature (F) 70 Space Set point is maintained Setback each night Figure 8. Power and Space Conditions for February 5 10, 2012 CDH Energy Corp. 9 February 2013

11 Ventilation Controller The data from May show the operation of the Honeywell Controller (fan cycler) which opens the damper (and runs the fan) for 36 minutes out of ever hour (60% of the time) to provide ventilation to the home. When the operated at 230 Watts the measured ventilation flow was 86 cfm, so the average ventilation across the hour was 52 cfm. The 2 3 F fluctuations in the return/space temperature in Figure 10 confirm the cyclic operation of the fan and ventilation damper on May (when no heating was required). Unit 05/10/12 to 05/15/12 Vnt Dmpr Htg Pmp Temperature (F) Supply Air Return Air Mixed Air Water Temperatures 05/10/12 to 05/15/12 Temperature (F) HW to Coil DHW Hot DHW Cold Solar Out Figure 9. System Performance for May 10 15, 2012 CDH Energy Corp. 10 February 2013

12 2.0 Total Power (kw) Total AC Space Temperature (F) Figure 10. Power and Space Conditions for May 10 15, 2012 CDH Energy Corp. 11 February 2013

13 Solar Tank Performance In the summer the solar tank provides a large portion of the hot water heating. However, with the high hot water set point (near 190 F) the tankless unit is still required to operate more than expected. Water Temperatures 08/04/12 to 08/09/12 Temperature (F) HW to Coil DHW Hot DHW Cold Solar Out Unit 08/04/12 to 08/09/12 Vnt Dmpr Htg Pmp Figure 11. Hot Water Temperatures and Equipment Runtimes when Solar Collector is Operating, August 4 9, 2012 CDH Energy Corp. 12 February 2013

14 Air Conditioner Performance The home owner operated the air conditioner intermittently. For the period shown in in Figure 12 below, the AC was activated when the space temperature exceeded 80 F on August 4, For the remainder of that week the set point was F. 2.0 Total Power (kw) Total AC Space Temperature (F) Figure 12. Air Conditioner Operation, August 4 9, 2012 CDH Energy Corp. 13 February 2013

Hot Water a Hot Commodity Better Buildings by Design, February 2012 Burlington, VT

Hot Water a Hot Commodity Better Buildings by Design, February 2012 Burlington, VT Hot Water a Hot Commodity Better Buildings by Design, February 2012 Burlington, VT Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability.com Gary Klein, 2012 Efficiency

More information

Performance of Solar Water Heating Systems in the United States

Performance of Solar Water Heating Systems in the United States Performance of Solar Water Heating Systems in the United States Danny Parker & Camilo Gil Florida Solar Energy Center ACEEE Hot Water Forum June 2009, Asilomar,, California Rebate situation in Florida

More information

Laboratory Evaluation of Hybrid and Advanced Water Heaters: Performance Overview in Hot Humid Climate

Laboratory Evaluation of Hybrid and Advanced Water Heaters: Performance Overview in Hot Humid Climate Laboratory Evaluation of Hybrid and Advanced Water Heaters: Performance Overview in Hot Humid Climate American Council for an Energy Efficient Economy ACEE Hot Water Forum Nov. 4-5, 2013 Carlos J. Colon

More information

Evaluating Domestic Water Heater Performance for NY Homes NYSERDA Agreement 15606

Evaluating Domestic Water Heater Performance for NY Homes NYSERDA Agreement 15606 Evaluating Domestic Water Heater Performance for NY Homes NYSERDA Agreement 15606 Report 1 Laboratory Test Results Deliverable 7a http://cloud.cdhenergy.com/dhw_lab November 2013 Submitted to: NYSERDA

More information

Strategies for Summer Utility Savings. Residential Environmental Program Series May 15, 2013

Strategies for Summer Utility Savings. Residential Environmental Program Series May 15, 2013 Strategies for Summer Utility Savings Residential Environmental Program Series May 15, 2013 Are FC Summers Getting Hotter? 200 Fort Collins Annual Hours 90 F or Above 150 100 50 1970 1980 1990 2000 2010

More information

Sivu 2/8 Rate data Description Suomi Shut off times total 0.0 h/day Weekends with shut off times yes Daytime rate of heat pump Time for daytime rate 5

Sivu 2/8 Rate data Description Suomi Shut off times total 0.0 h/day Weekends with shut off times yes Daytime rate of heat pump Time for daytime rate 5 Sivu 1/8 Design of a heat pump heating system with Aquarea Designer Project: Suomi 1 Date: Created by:?, (no data provided), (no data provided) Phone: (no data provided) Email: (no data provided) Building

More information

Better Buildings By Design 2013 Building the Renewable Energy Ready Home Solar Thermal Lessons Learned and Results

Better Buildings By Design 2013 Building the Renewable Energy Ready Home Solar Thermal Lessons Learned and Results Image Courtesy of Harvestar Better Buildings By Design 2013 Building the Renewable Energy Ready Home Solar Thermal Lessons Learned and Results Doug Merrill, Sunward Systems Doug Merrill 20 + years of manufacturing

More information

Copyright 2003 IBACOS, Inc. All rights reserved.

Copyright 2003 IBACOS, Inc. All rights reserved. Domestic Hot Water Research Research conducted by Bill Rittelmann Presented by Duncan Prahl Partners for High Performance Homes Meeting Westminster, CO, June 23, 2005 DHW Systems: Current Technologies

More information

The house has 4 inches of exterior foam board (in two layers) and 2 inches closed cell spray foam with cellulose in the wall cavities.

The house has 4 inches of exterior foam board (in two layers) and 2 inches closed cell spray foam with cellulose in the wall cavities. Monitoring Plan for TED House The 1200 sq ft TED House has radiant floor heating with a 96.5% gas-fired Rinnai E75CN water heater. The Rinnai unit has a separate water circuit to provide space heating.

More information

Dehumidification: Energy Efficiency Comparisons

Dehumidification: Energy Efficiency Comparisons Fourth Annual Energy Management Workshop Cocoa, Florida February 10-11, 2003 Dehumidification: Energy Efficiency Comparisons Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting,

More information

Time-Based Scheduling of Residential Ventilation

Time-Based Scheduling of Residential Ventilation Time-Based Scheduling of Residential Ventilation by Armin Rudd USDOE Building America Program for EEBA Conference 2000 Building for Peak Performance Denver, Colorado 26 October 2000 Climate Specific Design

More information

Farm Energy Audit Workshop

Farm Energy Audit Workshop Farm Energy Audit Workshop Sponsored by the Western Mountains Alliance, a member of the Maine Rural Partners Farm Energy Partners Network and Efficiency Maine Skowhegan, Maine May 14, 2008 Walk-Through

More information

The Ed Roberts Campus Berkeley, CA

The Ed Roberts Campus Berkeley, CA The Ed Roberts Campus Berkeley, CA Anderson Clemenceau Mechanical Option Penn State A.E. Senior Thesis April 14, 2015 Leddy Maytum Stacy Architects, Photo by Tim Griffith ASHRAE Climate Zone 3C 99.6% Heating

More information

Cork County Energy Agency

Cork County Energy Agency Cork County Energy Agency Energy Audit Midleton Area Office December 2009 Table of Contents 1. Introduction...1 2. Site description...2 3. On site energy use...3 3.1 Energy management...3 3.2 Breakdown

More information

Practical and Effective Approaches to Residential Ventilation for Production Builders

Practical and Effective Approaches to Residential Ventilation for Production Builders Practical and Effective Approaches to Residential Ventilation for Production Builders by Armin Rudd USDOE Building America Program for Affordable Comfort Conference 2002 Cincinnati, Ohio 18 April 2002

More information

Sustainable Hot Water: Better Design, Delivery, and Use

Sustainable Hot Water: Better Design, Delivery, and Use Sustainable Hot Water: Better Design, Delivery, and Use March 24, 2009 Don Fisher Amin Delagah Fisher-Nickel, inc. PG&E Food Service Technology Center The Food Service Technology Center (FSTC) program

More information

Storing excess daytime solar energy to heat greenhouse at night!

Storing excess daytime solar energy to heat greenhouse at night! Storing excess daytime solar energy to heat greenhouse at night Russell Benoy March 21, 2014 Having built a well insulated greenhouse, I was amazed at how often the exhaust fan ran to maintain a reasonable

More information

Asparagus Response to Water and Nitrogen

Asparagus Response to Water and Nitrogen Asparagus Response to Water and Nitrogen Item Type text; Article Authors Roth, Robert L.; Gardner, Byrant R. Publisher College of Agriculture, University of Arizona (Tucson, AZ) Journal Vegetable Report

More information

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report East Liberty Presbyterian Church 14 009 For: By: East Liberty Presbyterian Church Jeffery Ison, James Construction Date: October

More information

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Continuous Commissioning: A Valuable Partner to Retrofit Projects Continuous Commissioning: A Valuable Partner to Retrofit Projects Yeqiao Zhu Aamer Athar Kenneth Banks Ph.D. PE, CEM PE, CEM Energy Systems Laboratory Sempra Energy Solutions Sempra Energy Solutions Charles

More information

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed

More information

INEEL (1500) [45] 5.6 C 217 mm 60. Precipitation (mm) Temperature (oc) Month

INEEL (1500) [45] 5.6 C 217 mm 60. Precipitation (mm) Temperature (oc) Month Figure 1. Water balance of a vegetated plot. Plants extract water from throughout the soil profile, to depths that may exceed 2 m in deep soils. In contrast, most water lost by direct evaporation comes

More information

Innovative Technologies [and Design Concepts] in Commercial Foodservice

Innovative Technologies [and Design Concepts] in Commercial Foodservice Innovative Technologies [and Design Concepts] in Commercial Foodservice Don Fisher, P. Eng. Fisher Consultants PG&E Food Service Technology Center 925-866-5770 dfisher@fishnick.com Food Service Technology

More information

Heating and Hot Water

Heating and Hot Water Heating and Hot Water Funding Funding for this class was provided by the Alaska Housing Finance Corporation (AHFC). This course is designed to empower homeowners with the knowledge to live in and maintain

More information

New Steps towards Compact Solar Combisystems in Scandinavia

New Steps towards Compact Solar Combisystems in Scandinavia New Steps towards Compact Solar Combisystems in Scandinavia Compact Solar Combisystem High Efficiency by Minimizing Temperatures Alexander Thür, Simon Furbo Technical University of Denmark DK-2800 Kgs.

More information

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc.

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc. M&V Real Results of High Performance Design Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc. Overview Measurement & Verification (M&V) Plan for New

More information

Special Topics on Residential HVAC

Special Topics on Residential HVAC Special Topics on Residential HVAC by Armin Rudd USDOE Building America Program for EEBA Conference 2002 Phoenix, Arizona 10 October 2002 Page 1 of 25 Two Main Topics: 1. Cyclical trade-offs between building

More information

Auburn University Basketball Arena:

Auburn University Basketball Arena: Auburn University Basketball Arena: How Building Data Analytics Achieved Energy and O&M Savings While Improving Comfort and Sustainability Eric Moore, PE, CEM, Auburn University Hadas Webb, CEM, Cimetrics

More information

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9 Index Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8 Fire Risk Assessments 9 Fire Alarm Systems 10-20 Locations 10 Servicing 11 12 Activations 13 14 Weekly Checks

More information

announcements 4/10/08

announcements 4/10/08 Psychrometrics & Design Strategies ARCH 331/431 Spring 2008 Lecture 4 announcements 4/10/08 course website: http://courses.washington.edu/arch3431/index.shtml Course materials (readings, assignments, lectures,

More information

Energy & Water Savings in Commercial Food Service

Energy & Water Savings in Commercial Food Service Energy & Water Savings in Commercial Food Service Don Fisher Manager Food Service Technology Center 925-866-5770 dfisher@fishnick.com The Food Service Technology Center (FSTC) program is funded by California

More information

Designing and Operating an Energy Efficient Foodservice Facility March 12, 2014 Winnipeg, MB

Designing and Operating an Energy Efficient Foodservice Facility March 12, 2014 Winnipeg, MB Designing and Operating an Energy Efficient Foodservice Facility March 12, 2014 Winnipeg, MB Don Fisher, P. Eng. Fisher Consultants PG&E Food Service Technology Center 925-866-5770 dfisher@fishnick.com

More information

Daikin Altherma Selection Report

Daikin Altherma Selection Report Daikin Altherma Selection Report Produced on 20.10.2014 with Daikin Altherma Simulator V4.4.7 - database Central 9.7.9 Project name Energa Sistemi Reference Airabela Client name Energa Sistemi Revision

More information

SOLAR THERMAL HEATING: ALIVE AND WELL

SOLAR THERMAL HEATING: ALIVE AND WELL Michael E Dion michael.dion@stiebel-eltron-usa.com SOLAR THERMAL HEATING: ALIVE AND WELL Donavin A Gratz donavin.gratz@stiebel-eltron-usa.com E Christopher Wetherby chris.wetherby@stiebel-eltron-usa.com

More information

The Lara. Site Contact. Summary. 113 Nassau Site Information. 113 Nassau Street New York, NY 10038

The Lara. Site Contact. Summary. 113 Nassau Site Information. 113 Nassau Street New York, NY 10038 The Lara 113 Nassau Street New York, NY 10038 Site Contact Alex Cuscovitch Project Engineer Aegis Energy Services Inc. 55 Jackson St Holyoke MA, 10603 413-536-1156 acuscovitch@aegisenergyservices.com CDH

More information

DISTRICT HEATING SCHEME FEASIBILITY STUDY FRANKTON FLATS QUEENSTOWN

DISTRICT HEATING SCHEME FEASIBILITY STUDY FRANKTON FLATS QUEENSTOWN DISTRICT HEATING SCHEME FEASIBILITY STUDY FRANKTON FLATS QUEENSTOWN 2010 ALPINE AQUALAND EVENTS CENTRE QUEENSTOWN AIRPORT LAKES DISTRICT HOSPITAL Prepared by building services design engineers 2 District

More information

RECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES FOR RESIDENTIAL BUILDINGS

RECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES FOR RESIDENTIAL BUILDINGS ESL-TR-7-9-1 RECOMMENDATIONS FOR 15% ABOVE-CODE ENERGY EFFICIENCY MEASURES FOR RESIDENTIAL BUILDINGS A Project for Texas Senate Bill 5 Legislation For Reducing Pollution in Nonattainment and Affected Areas

More information

Acknowledgement: Ralph Prahl, Prahl & Associates, contributed critical review and analysis

Acknowledgement: Ralph Prahl, Prahl & Associates, contributed critical review and analysis Subject Focus on Energy Evaluation Dehumidifiers Deemed Savings Review for Targeted Home Performance with ENERGY STAR To Oscar Bloch, Public Service Commission of Wisconsin cc Suzanne Harmelink, Wisconsin

More information

Zero Net Energy Retrofit Projects The Domes Final Performance Assessment & Verification

Zero Net Energy Retrofit Projects The Domes Final Performance Assessment & Verification Zero Net Energy Retrofit Projects The Domes Final Performance Assessment & Verification ET Project Number: ET12PGE1442 Project Manager: Peter Turnbull Pacific Gas and Electric Company Prepared By: NORESCO

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 3 Page 1 of 6 I. PURPOSE This policy establishes the steps required for performing the monthly fixed systems inspections and the semi-annual systems testing. Fixed systems include; wet chemical

More information

The owner has future plans to install a photovoltaic array on the house.

The owner has future plans to install a photovoltaic array on the house. Monitoring Plan for Live-Work House (Cook+Fox). This 1,500 sq ft house at 317 Marcellus Street includes an HRV for ventilation and small Munchkin 80 MBtu/h Condensing Boiler for radiant floor heating and

More information

Countywide Recycling and Disposal Facility Weekly Progress Report 08/22/08

Countywide Recycling and Disposal Facility Weekly Progress Report 08/22/08 Countywide Recycling and Disposal Facility Weekly Progress Report 08/22/08 This Weekly Progress Report is prepared by Countywide and submitted to the OEPA weekly by the close of business on each Friday.

More information

Heat Consumption Assessment of the Domestic Hot Water Systems in the Apartment Buildings

Heat Consumption Assessment of the Domestic Hot Water Systems in the Apartment Buildings 1.2478/cons-213-6 213 /14 Heat Consumption Assessment of the Domestic Hot Water Systems in the Apartment Buildings Dzintars Grasmanis 1, Aldis Grekis 2, Normunds Talcis 3, 1-3 Riga Technical University

More information

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS) MSP WRAP-ARUND MULTIPLE SMALL PLATE DEHUMIDIFICATIN TECHNLGY VS. CNVENTINAL DEHUMIDIFICATIN IN DEDICATED UTDR AIR SYSTEMS (DAS) ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++

More information

New Westminster Downtown Parking Strategy Public Open House #1 September 13, 2012

New Westminster Downtown Parking Strategy Public Open House #1 September 13, 2012 New Westminster Downtown Parking Strategy Public Open House #1 September 13, 2012 The City is preparing a strategy for parking in Downtown New Westminster. The study team and a group of key stakeholders

More information

McQuay. Incremental. PSEA, PSEC, PSEH, PSEI, PSES, PSHA, PSHC, PSHI, PSHS Suite II, 1 Motor 007, 009, 012, 015 Design A (1)

McQuay. Incremental. PSEA, PSEC, PSEH, PSEI, PSES, PSHA, PSHC, PSHI, PSHS Suite II, 1 Motor 007, 009, 012, 015 Design A (1) Replacement Parts List No. 110509900 Revision E 07/2016 McQuay Incremental PSEA, PSEC, PSEH, PSEI, PSES, PSHA, PSHC, PSHI, PSHS Suite II, 1 Motor 007, 009, 012, 015 Design A (1) To find your Daikin Applied

More information

Heritage Park Irrigation System Inspection Review of Water Use Estimated Water Budget Potential for Savings

Heritage Park Irrigation System Inspection Review of Water Use Estimated Water Budget Potential for Savings Heritage Park Irrigation System Inspection Review of Water Use Estimated Water Budget Potential for Savings Site Visit: January 17, 2008 Address: 611 Village Drive, Suisun City Key Action Items Re-nozzle

More information

TECHNICAL NOTE JULY Dr. Thomas Butcher Brookhaven National Laboratory Building 526, P.O. Box 5000 Upton, L. I. NY 11719

TECHNICAL NOTE JULY Dr. Thomas Butcher Brookhaven National Laboratory Building 526, P.O. Box 5000 Upton, L. I. NY 11719 TECHNICAL NOTE MODELED ENERGY AND ECONOMIC PERFORMANCE ASSESSMENT OF A PORTLAND, ME. HOME WITH AN EXISTING OIL-FIRED NON-CONDENSING BOILER AND A TWO-HEAD MINI- SPLIT 38,000 BTU HEAT-PUMP OPERATING IN THREE

More information

Evaluating Domestic Water Heater Performance for NY Homes NYSERDA Agreement 15606

Evaluating Domestic Water Heater Performance for NY Homes NYSERDA Agreement 15606 Evaluating Domestic Water Heater Performance for NY Homes NYSERDA Agreement 15606 Screen and Select DHW Systems and Distribution Architecture for Testing (Task 2 deliverable) Draft July 2012 Submitted

More information

Kimberly Rollins, Professor, Department of Economics, University of Nevada, Reno

Kimberly Rollins, Professor, Department of Economics, University of Nevada, Reno Modeling Multiple Factors of Residential Water Demand to Assess Price and Non-Price Instruments under Climate Change: An Application to Las Vegas, Nevada Kimberly Rollins, Professor, Department of Economics,

More information

WATER HEATING PAGETTE

WATER HEATING PAGETTE WATER HEATING PAGETTE HISTORY PAGette Started July 2005 Based on PAG meeting comments PAG members suggested we form group to examine Water Heating opportunities PAGette to report back to the PAG on its

More information

Boulder County Comprehensive Drilling Plan Surface Owner Meeting. Thursday, Oct. 19, 2017

Boulder County Comprehensive Drilling Plan Surface Owner Meeting. Thursday, Oct. 19, 2017 Boulder County Comprehensive Drilling Plan Surface Owner Meeting Thursday, Oct. 19, 2017 Contact Crestone Crestone Peak Resources Quick Facts www.crestonepeakresources.com cdpboulder@crestonepr.com (720)

More information

Equipment ATA 12 April 2016

Equipment ATA 12 April 2016 05-00-01 Time limits and Maintenance Frequencies Various JUN 14 1 25-00-01 Charging Head Mk 2 & Accessories WKA26592 WKA26592A 25-60-15 Submersion Actuator K38215 58178-001 AUG 92 JAN 15 Initial Issue

More information

Site Evaluation. for. Oregon School for the Deaf. 999 Locust Street Northeast Salem, OR BE15178

Site Evaluation. for. Oregon School for the Deaf. 999 Locust Street Northeast Salem, OR BE15178 Site Evaluation for Oregon School for the Deaf 999 Locust Street Northeast Salem, OR 97301-0999 BE15178 Sponsored by: Energy Trust of Oregon Existing Buildings Program Submitted by: ATAC Contact Information

More information

Data driven insights from the nation s deepest ever customer energy research

Data driven insights from the nation s deepest ever customer energy research Pecan Street Research Institute Pike Powers Lab and Center for Commercialization Data driven insights from the nation s deepest ever customer energy research Change in peak load 70,000 by customer class

More information

SOLAR HOT WATER AND HEAT PUMP BOOSTER ENERGY CALCULATION METHODOLOGY

SOLAR HOT WATER AND HEAT PUMP BOOSTER ENERGY CALCULATION METHODOLOGY SOLAR HOT WATER AND HEAT PUMP BOOSTER ENERGY CALCULATION METHODOLOGY PART A: CALCULATION METHODOLOGY FOR SOLAR WATER HEATERS AND HEAT PUMP WATER HEATERS WITH A VOLUMETRIC CAPACITY OF UP TO AND INCLUDING

More information

WLAC Facilities Committee Meeting. September 18, 2017

WLAC Facilities Committee Meeting. September 18, 2017 Campus Program Report WLAC Facilities Committee Meeting September 18, 2017 Page 1 DSA approved the plans on May 15, 2017. Notice to Proceed was issued June 8, 2017 and the project remains on schedule for

More information

Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I.

Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I. Air System Sizing Summary for AHU/CU-1 AHU/CU-1 Floor Area 1678.0 ft² Central Cooling Coil Total coil load 4.8 Tons Total coil load 57.8 MBH Sensible coil load 41.8 MBH Coil CFM at Jul 1500 1909 CFM Max

More information

Living the (Solar) Dream Powering your lifestyle with the sun Ron Kube. Photo: Great Canadian Solar

Living the (Solar) Dream Powering your lifestyle with the sun Ron Kube. Photo: Great Canadian Solar Living the (Solar) Dream Powering your lifestyle with the sun Ron Kube Photo: Great Canadian Solar Today's talk ACT I Energy Efficiency (EE) ACT II Solar Energy (SE) ACT III Electric Vehicles (EV) What

More information

SOUTHEND CARELINE ANNUAL REPORT

SOUTHEND CARELINE ANNUAL REPORT SOUTHEND CARELINE ANNUAL REPORT 2015-2016 Meet some of the CareLine Team Southend Careline TSA accredited 2015-2016 Southend Careline offers reassurance and peace of mind to our service users their family

More information

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN -9 The 5 World Sustainable Building Conference, Tokyo, 7-9 September 5 (SB5Tokyo) ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN Kahori GENJO Dr.Eng. Shin-ichi MATSUMOTO Dr.Eng

More information

Biosolids Dewatering, Monitoring, and Disposal Programs

Biosolids Dewatering, Monitoring, and Disposal Programs Water and Waste Department Environmental Standards Division Biosolids Dewatering, Monitoring, and Disposal Programs Environment Act Licence #1089E RR 2016 Water and Waste Department Service des eaux et

More information

TRAINING SCHEDULE. Peachtree City, Georgia Course Schedules for 2018

TRAINING SCHEDULE. Peachtree City, Georgia Course Schedules for 2018 Peachtree City, Georgia Course Schedules for 2018 Non-Condensing & Condensing Tankless Water Heaters Direct Vent Wall Furnaces / Vent- Free Fan Convectors Condensing Boilers TRAINING REVIEW Who Should

More information

Boulder County Comprehensive Drilling Plan Surface Owner Meeting. Thursday, Nov. 2, 2017

Boulder County Comprehensive Drilling Plan Surface Owner Meeting. Thursday, Nov. 2, 2017 Boulder County Comprehensive Drilling Plan Surface Owner Meeting Thursday, Nov. 2, 2017 Contact Crestone Crestone Peak Resources Quick Facts www.crestonepeakresources.com cdpboulder@crestonepr.com (720)

More information

Thermal equalization is the obvious answer to the situation. But, how is "thermal equalization" achieved?

Thermal equalization is the obvious answer to the situation. But, how is thermal equalization achieved? OVERVIEW The Airius Thermal Equalizer product line is designed to create a more pleasant working/living environment and to reduce total energy consumption, which results in significant annual cost savings.

More information

Transfer Station Recycling Update SWANA Technical Session-Waste Diversion 4 2/24/2017 2/28/2017

Transfer Station Recycling Update SWANA Technical Session-Waste Diversion 4 2/24/2017 2/28/2017 Transfer Station Recycling Update SWANA Technical Session-Waste Diversion 4 2/24/2017 1 Todays Outline Roadmap to 70% A look back on how we started.. Vashon yard & food waste Styrofoam & plastic film Resource

More information

The following table summarizes information from various sources on corn development.

The following table summarizes information from various sources on corn development. October 7, 2009 2009 Post-Harvest Tips for Later Maturing Corn Ken Hellevang, Ph.D., PE, Extension Engineer, Professor NDSU Extension Service, Ag & Biosystems Engineering Department Corn Maturity Progression

More information

VARIABLE HEAT RECOVERY IN DOUBLE BUNDLE ELECTRIC CHILLERS. Richard J Liesen 1, Rahul J Chillar 2 1 University of Illinois at Urbana Champaign

VARIABLE HEAT RECOVERY IN DOUBLE BUNDLE ELECTRIC CHILLERS. Richard J Liesen 1, Rahul J Chillar 2 1 University of Illinois at Urbana Champaign VARIABLE HEAT RECOVERY IN DOUBLE BUNDLE ELECTRIC CHILLERS Richard J Liesen 1, Rahul J Chillar 2 1 University of Illinois at Urbana Champaign Dept of Mechanical & Industrial Engineering 1206 WGreen St Urbana,

More information

Lifestyle Electric Thermal Radiator

Lifestyle Electric Thermal Radiator Lifestyle Electric Thermal Radiator Complies with Lot 20 Eco-design Heating Directive 2009/12/EC. Effective January 2018 ALUMINIUM Euro Edition Issue 1 August 2017 Next Day Delivery Order before 3.00pm

More information

Lifestyle Electric Thermal Radiator

Lifestyle Electric Thermal Radiator Lifestyle Electric Thermal Radiator Complies with Lot 20 Eco-design Heating Directive 2009/12/EC. Effective January 2018 ALUMINIUM Euro Edition Issue 1 August 2017 Next Day Delivery Order before 3.00pm

More information

Fisher Slough Tidal Marsh Restoration Project Scaling Down the Restoration Planning & Analysis Framework to Evaluate Project Alternatives

Fisher Slough Tidal Marsh Restoration Project Scaling Down the Restoration Planning & Analysis Framework to Evaluate Project Alternatives Fisher Slough Tidal Marsh Restoration Project Scaling Down the Restoration Planning & Analysis Framework to Evaluate Project Alternatives Project Sponsor/Partners The Nature Conservancy Dike District #3

More information

ENERGY COST AND FEATURE REPORT

ENERGY COST AND FEATURE REPORT ENERGY COST AND FEATURE REPORT Building Name: Rating Org.: GREEN DREAM GROUP, LLC ANNUAL ENERGY COSTS Heating $ 565 Cooling $ 0 Water Heating $ 0 Lights & Appliances $ 1402 Photovoltaics $ -189 Service

More information

INSTRUCTIONS MANUAL FOR MED75HD - UPRIGHT GLASS DOOR FRIDGE

INSTRUCTIONS MANUAL FOR MED75HD - UPRIGHT GLASS DOOR FRIDGE TC900E Version 7 Version230817 INSTRUCTIONS MANUAL FOR MED75HD - UPRIGHT GLASS DOOR FRIDGE PLEASE NOTE: THE VACCINE REFRIGERATOR WILL IMMEDIATELY GO INTO A DEFROST AFTER BEING POWERED ON Thank you for

More information

Free cooling on RTAF Chiller. Integrated option

Free cooling on RTAF Chiller. Integrated option Free cooling on RTAF Chiller Integrated option Water based free cooling principle. Use full aluminum (car radiator based) flat channel dry cooler exchangers. Modulate 3 way to reach required free cooling

More information

MODEL 9308 ENERGY MANAGEMENT COMPUTER OWNER'S MANUAL

MODEL 9308 ENERGY MANAGEMENT COMPUTER OWNER'S MANUAL Computerized Energy Management MODEL 9308 ENERGY MANAGEMENT COMPUTER OWNER'S MANUAL Helping you to use energy more efficiently Energy Sentry 9308 Owner's Manual P/N 09308-94100B REV. 1/26/10 Copyright

More information

Irrigating Olives. Janet Caprile UCCE Farm Advisor Alameda & Contra Costa Counties

Irrigating Olives. Janet Caprile UCCE Farm Advisor Alameda & Contra Costa Counties Irrigating Olives Janet Caprile UCCE Farm Advisor Alameda & Contra Costa Counties Olive Production Basics: Introduction to Irrigation Management Sunday, July 21, 1 3:30 pm, Livermore Why do olives need

More information

Remodeling Market. Kermit Baker. Remodeling Futures Conference November 9, Harvard University JOINT CENTER FOR HOUSING STUDIES

Remodeling Market. Kermit Baker. Remodeling Futures Conference November 9, Harvard University JOINT CENTER FOR HOUSING STUDIES Remodeling Market Trends and Update Kermit Baker Remodeling Futures Conference November 9, 2010 Remodeling Market Trends 1. Remodeling spending saw significant decline during recession; greatest fall-off

More information

4/8/2015 Item #10D Page 1

4/8/2015 Item #10D Page 1 MEETING DATE: April 8, 2015 PREPARED BY: Christy Villa, Associate Civil Engineer DEPT. DIRECTOR: Glenn Pruim DEPARTMENT: Public Works CITY MANAGER: Larry Watt SUBJECT: NORTH COAST HIGHWAY 101 STREETSCAPE

More information

Orange Solar Pump HD50

Orange Solar Pump HD50 Orange Solar Pump HD5 36 volt DC brushless step motor Loss of prime protection - Automatic tank filling How the pump works The HD5 centrifugal solar pump is made of stainless steel with a plastic impeller.

More information

Unvented Roof Summary Article

Unvented Roof Summary Article building science.com 2008 Building Science Press All rights of reproduction in any form reserved. Unvented Roof Summary Article Research Report - 0301 2003 Kohta Ueno Abstract: This article was written

More information

Tech Report III. Technology and Engineering Development (TED) Building. Thomas Jefferson National Accelerator Facility.

Tech Report III. Technology and Engineering Development (TED) Building. Thomas Jefferson National Accelerator Facility. Technology and Engineering Development (TED) Building Thomas Jefferson National Accelerator Facility Newport News, VA Tech Report III Mechanical Systems Existing Conditions Report 11/29/2010 Architectural

More information

McQuay. Aircon Air Cooled Condenser. AMB, APB AMD, APD Vintage A. Last Manufacture: 1978

McQuay. Aircon Air Cooled Condenser. AMB, APB AMD, APD Vintage A. Last Manufacture: 1978 Replacement Parts List No. 055224800 Revision C 10/2017 McQuay Aircon Air Cooled Condenser AMB, APB 020-140 AMD, APD 008-030 Vintage A Last Manufacture: 1978 To find your Daikin Applied parts distributor,

More information

Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards

Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards Date: February 15, 2018 Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards Grantee Name: University of Central

More information

2 Safety valve. 3 Pressure gauge. 4 Thermometer. 8 Ball valves

2 Safety valve. 3 Pressure gauge. 4 Thermometer. 8 Ball valves Standard solar system for domestic hot water heating (please adapt chart according to standard systems in your country) Standard engineering in Germany for a household of 4 people: 4 6 m² of collector

More information

Zero Net Energy Retrofit Project at The Domes: Interim Performance Assessment & Verification

Zero Net Energy Retrofit Project at The Domes: Interim Performance Assessment & Verification PG&E s Emerging Technologies Program ET12PGE1442 Zero Net Energy Retrofit Project at The Domes: Interim Performance Assessment & Verification ET Project Number: ET12PGE1442 Project Manager: Peter Turnbull

More information

System Using Exhaust Heat from Residential GHPs

System Using Exhaust Heat from Residential GHPs Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 System Using Exhaust Heat from Residential GHPs K. Tanokashira Tokyo Gas

More information

Appendix A. Reference Evapotranspiration (ETo) Table.

Appendix A. Reference Evapotranspiration (ETo) Table. Appendix A. Reference Evapotranspiration (ETo) Table. Appendix A - Reference Evapotranspiration (ETo) Table* KINGS Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total Caruthers 1.6 2.5 4.0 5.7 7.8 8.7

More information

Efficient Irrigation, Smart Controllers and Climate Appropriate Shade Trees. Clovis Community College Center Clovis, CA

Efficient Irrigation, Smart Controllers and Climate Appropriate Shade Trees. Clovis Community College Center Clovis, CA Efficient Irrigation, Smart Controllers and Climate Appropriate Shade Trees Clovis Community College Center Clovis, CA June 28, 2017 Evapotranspiration Adjustment Factor Study Department of Water Resources

More information

On Balance: Heat Rejection Control a Packaged Solution

On Balance: Heat Rejection Control a Packaged Solution On Balance: Heat Rejection Control a Packaged Solution Echelon Americas Channel Partner Conference March 11, 2005 Presented by Doug Scott VaCom Technologies La Verne, California Opportunity An integrated

More information

CHART PERUVIAN TECHNICAL STANDARDS

CHART PERUVIAN TECHNICAL STANDARDS CHART PERUVIAN TECHNICAL STANDARDS Peruvian Technical Standards Elaborated by the Normative Technical Committee Rational Use of Energy and the Energy Efficiency - (December 2007) Electric Motors Industrial

More information

Economic Analysis of Solar Assisted Chemical Heat Pump Dryer

Economic Analysis of Solar Assisted Chemical Heat Pump Dryer Economic Analysis of Solar Assisted Chemical Heat Pump Dryer M. I. FADHEL 1, W. R. W. DAUD 2, M.A. ALGHOUL 2, A.ZAHARIM 2 & K. SOPIAN 2 1 Faculty of Engineering and Technology Multimedia University Jalan

More information

HEAT LOAD AND SOLAR GAIN PREDICTION FOR SOLID WALL DWELLINGS RETROFITTED WITH TRIPLE VACUUM GLAZING FOR SELECTED WINDOW TO WALL AREA RATIOS

HEAT LOAD AND SOLAR GAIN PREDICTION FOR SOLID WALL DWELLINGS RETROFITTED WITH TRIPLE VACUUM GLAZING FOR SELECTED WINDOW TO WALL AREA RATIOS HEAT LOAD AND SOLAR GAIN PREDICTION FOR SOLID WALL DWELLINGS RETROFITTED WITH TRIPLE VACUUM GLAZING FOR SELECTED WINDOW TO WALL AREA RATIOS Saim Memon & Philip C. Eames Centre for Renewable Energy Systems

More information

CROWN YEARLY PROPERTY SCHEDULE

CROWN YEARLY PROPERTY SCHEDULE This Yearly Property Schedule is simply a guide to managing your Facility. Please reallocate duties as they suit the management of your Facility, however, note that all tasks should be listed on the schedule

More information

2018 thesimple, Inc.

2018 thesimple, Inc. TM User Guide 2018 thesimple, Inc. Introduction The Simple thermostat supports supports 2 heating stages and 2 cooling stages for conventional systems, and 2 heating/cooling stages for heat pumps, with

More information

Your 2017 Annual Account Summary: One more way that Sears MasterCard provides you with the tools to make smart decisions about your spending.

Your 2017 Annual Account Summary: One more way that Sears MasterCard provides you with the tools to make smart decisions about your spending. Your 2017 Annual Account Summary: One more way that Sears MasterCard provides you with the tools to make smart decisions about your spending. Dear Johna L Thornton, It is my pleasure to provide you with

More information

SED ENGINEERING TECHNICAL LETTER AD-A I I 1111 li 11 I1'1 FIRE PROTECTION ENGINEERING CRITERIA EMERGENCY LIGHTING AND MARKING OF EXITS

SED ENGINEERING TECHNICAL LETTER AD-A I I 1111 li 11 I1'1 FIRE PROTECTION ENGINEERING CRITERIA EMERGENCY LIGHTING AND MARKING OF EXITS AD-A237 389 ( ETL 91-5 18 JUNE 1991 ENGINEERING TECHNICAL LETTER FIRE PROTECTION ENGINEERING CRITERIA EMERGENCY LIGHTING AND MARKING OF EXITS 0l ELECTE JUN 2 7 1991. SED OFFICE of THE CIVIL ENGINEER DIRECTORATE

More information

R4 Ventures LLC White Paper

R4 Ventures LLC White Paper R4 Ventures LLC White Paper Preliminary Temperature Performance Evaluation of New Cooling Technologies consisting of the Multistage Evaporative Cooling System (MECS) for Phoenix, AZ; Newark, DE; Houston,

More information

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae APPENDIX C Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 12:56PM Air System Information Air System Name Equipment Class Air System Type Lobby System CW AHU SZCAV Number

More information

Analogue to Digital Telecare. Technical Advisory Board. 21 st June 2017 Work Stream 3 Procurement

Analogue to Digital Telecare. Technical Advisory Board. 21 st June 2017 Work Stream 3 Procurement Analogue to Digital Telecare Technical Advisory Board 21 st June 2017 Work Stream 3 Procurement Euan Kidd Senior Procurement Specialist Euan.kidd@scotland-excel.org.uk 1 Purpose of Work stream 3 - procurement

More information

Heat Pumps and Public Swimming Pools, a Perfect Match

Heat Pumps and Public Swimming Pools, a Perfect Match TOPICAL ARTICLE Heat Pumps and Public Swimming Pools, a Perfect Match M. Zuliani, P. Pattijn - Belgium Public swimming pools have a very high energy consumption, due to high demands of heating and climatisation

More information