Auburn University Basketball Arena:

Size: px
Start display at page:

Download "Auburn University Basketball Arena:"

Transcription

1 Auburn University Basketball Arena: How Building Data Analytics Achieved Energy and O&M Savings While Improving Comfort and Sustainability Eric Moore, PE, CEM, Auburn University Hadas Webb, CEM, Cimetrics IDEA 27th Annual Campus Energy Conference Atlanta, GA February 20, 2014

2 Agenda Auburn University & Cimetrics Collaboration Auburn Arena Background Case Study Findings: Fan speed control Dehumidification control Damper controls Heat exchanger modification Ongoing Commissioning Results Questions

3 Auburn + Cimetrics Collaboration University Sustainability Goals American College & University Presidents Climate Commitment (ACUPCC) Carbon neutral by 2050 Reduce campus energy intensity 20% by 2020 based on 2006 baseline Ongoing commissioning identified annual savings Energy: $444,276 CHW: 108,000 kgal CO 2 : 4,560 metric tons Steam: 1,150 mlb Electrical: 2,560 MWh Natural gas: 1,257 MCF HW: 31,000 kgal Cumulative savings of $900,000 and 29% reduction in MMBTU/ft 2 between 2008 and 2013

4 Auburn Basketball Arena Built in ,568 ft 2, $92.5 million facility 9,121 seat main court Use: Men's and Women's basketball, Women's gymnastics, music events, camps, commencements Additional space: practice courts, locker rooms, weight training, sports medicine, offices, suites & lounges, food prep and service, athletics museum Connected to central hot water and chilled water systems

5 Issues Identified Main court AHUs: Supply fan VFDs running at constant speeds Cooling valves 100% open in dehumidification mode Economizer optimization Building pressurization Domestic hot water heat exchanger configuration Chilled water pump differential pressure exceeding setpoint AHU operation improvements: Occupancy scheduling Static pressure setpoint reset Damper control Temperature control VAV operation improvements

6 Arena Data Collection & Reporting Building automation system (HVAC) data collection, analysis, and reporting by Cimetrics started in Sept. 2011: 2,145 total JCI points polled 24/7/ minute polling frequency 7,798 computed points 200,000+ samples per day Equipment monitored and analyzed: 23 air handling units & 19 exhaust fans 5 hot water & chilled water pumps 100 terminal units Multiple system control valves

7 Main Court Supply Fan Speed Control Original Configuration: 2 fans at 100% AHU-4A-1 Fan Energy: 156,814 kwh Cooling Energy: 7,606 MMBTU Heating Energy: 4,868 MMBTU AHU-4D-1 Fan Energy: 248,882 kwh Cooling Energy: 8,790 MMBTU Heating Energy: 4,972 MMBTU

8 Main Court Supply Fan Speed Control Final Configuration: 4 fans variable speeds AHU-4A-1 Fan Energy: 15,900 kwh Cooling Energy: 2,444 MMBTU Heating Energy: 1,499 MMBTU AHU-4C-1 Fan Energy: 20,751 kwh Cooling Energy: 2,597 MMBTU Heating Energy: 1,594 MMBTU AHU-4B-1 Fan Energy: 22,109 kwh Cooling Energy: 2,625 MMBTU Heating Energy: 1,616 MMBTU AHU-4D-1 Fan Energy: 19,160 kwh Cooling Energy: 2,788 MMBTU Heating Energy: 1,665 MMBTU

9 Consumption (kwh) Main Court Fan Speed Control Results Arena Bowl Supply & Exhaust Fan Electrical Consumption 45,000 40,000 35,000 30,000 25,000 20,000 Control sequence update 72% decrease in kwh from 2011 to 2012 Increased summer usage under investigation 15,000 10,000 5,000 0 Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total AHU Supply Fan Total AHU Exhaust Fans 184,500 kwh reduction over 7 month period $9,200 savings over 7 months $15,700 annualized savings 72% reduction in electricity consumption

10 Signal (%), Temperature (F), Relative Humidity (%) Main Court Dehumidification Control AHU Dehumidification Control - Average Across 4 AHUs Cooling valve signal of 100% when return RH > 55% Cooling valve signal = 47% Cooling coil discharge = 52 F Reheat valve signal = 32% Cooling valve signal = 100% Cooling coil discharge = 50 F Reheat valve signal = 50% Cooling valve modulates to maintain return RH of 55% BEFORE Outside Air Enthalpy (BTU/lb) AFTER Cooling Valve Signal Cooling Coil Discharge Air Temperature Reheat Valve Signal Discharge Air Temperature Discharge Air Temperature Setpoint Return Humidity Return Humidity Setpoint

11 CHW Delta T (F) CHW Flow (GPM) Main Court Dehumidification Control AHU Dehumidification Control and Building Chilled Water Average increase in primary chilled water delta T of 2.3 F Average decrease in chilled water flow of 125 GPM Outside Air Enthalpy (BTU/lb) Delta T - Before Delta T - After Flow - Before Flow - After

12 Main Court AHU Damper Control Issues Identified: Building Over Pressurization Mixed Air Temperature Control Economizer Potential High CO 2 Levels Improvements: Building pressure sensors Dampers now used to control building pressure, CO 2 levels, and mixed air temperature

13 Average Daily Flow (GPM) Average Daily Delta T ( F) Heat Exchanger Modification Issue Identified: Instantaneous domestic hot water heaters had three-way valves on primary side Central Hot Water Plant Effect BEFORE AFTER /1/2012 7/3/2012 7/5/2012 7/7/2012 7/9/2012 7/11/2012 7/13/2012 7/15/2012 7/17/2012 7/19/2012 7/21/2012 7/23/2012 7/25/2012 7/27/2012 7/29/2012 7/31/ Average Daily Flow GPM Average Daily Delta T ( F) 0 Estimated Annual Savings: Central Plant - $10,000

14 Energy & Environmental Results Estimated results based on Cimetrics recommendations and Auburn University implementation Annual savings: $114,000 Annual carbon savings: 1,800 metric-tons CO 2 Energy intensity based on actual utility data 2010: 188,476 BTU/ft : 165,950 BTU/ft : 150,447 BTU/ft : 151,290 BTU/ft 2

15 Special thanks to: Auburn Athletics Department Ken Martin Energy Engineer, Auburn Mike Harris Director of Utilities & Energy, Auburn Rick Mitchell Johnson Controls Karim Bibawi VP of Sales & Marketing, Cimetrics Mary Ellen Cantabene Chief Operating Officer, Cimetrics Dean Taylor Manager of Analytics, Cimetrics

16 Questions? Eric Moore, PE, CEM, Auburn University Hadas Webb, CEM, Cimetrics IDEA 27th Annual Campus Energy Conference Atlanta, GA February 20, 2014

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Continuous Commissioning: A Valuable Partner to Retrofit Projects Continuous Commissioning: A Valuable Partner to Retrofit Projects Yeqiao Zhu Aamer Athar Kenneth Banks Ph.D. PE, CEM PE, CEM Energy Systems Laboratory Sempra Energy Solutions Sempra Energy Solutions Charles

More information

Dehumidification: Energy Efficiency Comparisons

Dehumidification: Energy Efficiency Comparisons Fourth Annual Energy Management Workshop Cocoa, Florida February 10-11, 2003 Dehumidification: Energy Efficiency Comparisons Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting,

More information

On Balance: Heat Rejection Control a Packaged Solution

On Balance: Heat Rejection Control a Packaged Solution On Balance: Heat Rejection Control a Packaged Solution Echelon Americas Channel Partner Conference March 11, 2005 Presented by Doug Scott VaCom Technologies La Verne, California Opportunity An integrated

More information

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-05 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Galveston (TAMU-G) Galveston, Texas Submitted to Texas A&M University

More information

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed

More information

Engineers and Contractors - Innovative Technologies to Achieve Highest GeoExchange System Efficiencies for Commercial Projects

Engineers and Contractors - Innovative Technologies to Achieve Highest GeoExchange System Efficiencies for Commercial Projects Engineers and Contractors - Innovative Technologies to Achieve Highest GeoExchange System Efficiencies for Commercial Projects Presented by: Warren (Trey) Austin, PE, CEM, CGD, LEED-AP Geo-Energy Services,

More information

The M & V Guided Recommissioning Process. Energy & Water Conservation Program. September 2015 MOO

The M & V Guided Recommissioning Process. Energy & Water Conservation Program. September 2015 MOO The M & V Guided Recommissioning Process MOO Energy & Water Conservation Program September 2015 EWC Agenda MOO EWC Overview Our approach Progress Fault Detection Zone & customer feedback Variance reporting

More information

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas

More information

DIGI-VAV APPLICATIONS

DIGI-VAV APPLICATIONS DIGI-VAV DIGI-VAV APPLICATIONS Digi-VAV: An optimization kit for Variable Air Volume Air Handling Units (VAV AHU) that ensures individual zone indoor air quality (IAQ), and minimizes system energy consumption.

More information

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc.

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc. M&V Real Results of High Performance Design Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc. Overview Measurement & Verification (M&V) Plan for New

More information

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS 1 AIR HANDLING UNIT TRENDS 2 1. The trending charts provided on the following pages prepared as part of a retro-commissioning investigation. The

More information

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church

IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report. East Liberty Presbyterian Church East Liberty Presbyterian Church IES Whole-Building Energy Model Baseline Energy Model Input/ Output Report East Liberty Presbyterian Church 14 009 For: By: East Liberty Presbyterian Church Jeffery Ison, James Construction Date: October

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and

More information

Civil Engineering Building

Civil Engineering Building Continuous Commissioning Report For the Civil Engineering Building Building 492 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

WLAC Facilities Committee Meeting. September 18, 2017

WLAC Facilities Committee Meeting. September 18, 2017 Campus Program Report WLAC Facilities Committee Meeting September 18, 2017 Page 1 DSA approved the plans on May 15, 2017. Notice to Proceed was issued June 8, 2017 and the project remains on schedule for

More information

Design Standard. Thermal Systems (Chilled Water and Hot Water Systems) Detailed specifications follow. CHW AND HHW SUPPLY TEMPERATURE RESET

Design Standard. Thermal Systems (Chilled Water and Hot Water Systems) Detailed specifications follow. CHW AND HHW SUPPLY TEMPERATURE RESET Design Standard Detailed specifications follow. PART 1 CHW AND HHW SUPPLY TEMPERATURE RESET 1.1 The Utilities & Energy Services Department (UES) at Texas A&M University is actively identifying and implementing

More information

A New Approach to Museum HVAC Design ASHRAE TECHNOLOGY AWARD CASE STUDIES

A New Approach to Museum HVAC Design ASHRAE TECHNOLOGY AWARD CASE STUDIES A New Approach to Museum HVAC Design PHOTO CREDIT JON MCNEAL, SNØHETTA.JPG The San Francisco Museum of Modern Art (SFMOMA) consists of a 10-story addition and a renovated existing five-story building.

More information

The Temperature and Relative Humidity Control in Cushing Library

The Temperature and Relative Humidity Control in Cushing Library The Temperature and Relative Humidity Control in Cushing Library Chenggang Liu Research Associate Song Deng Assistant Director Homer L. Bruner, Jr., CEM Mechanical Systems Specialist Utilities Office of

More information

Computing Services Center

Computing Services Center Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1

More information

Time-Based Scheduling of Residential Ventilation

Time-Based Scheduling of Residential Ventilation Time-Based Scheduling of Residential Ventilation by Armin Rudd USDOE Building America Program for EEBA Conference 2000 Building for Peak Performance Denver, Colorado 26 October 2000 Climate Specific Design

More information

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled

More information

Continuous Commissioning Report

Continuous Commissioning Report Continuous Commissioning Report for the Bush Academic Facility (Bldg. 1607) Submitted to: Office of Energy Management Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Paul McCown, PE, CEM, LEED AP, CxA Sr. Mechanical Engineer SSRCx, LLC Nashville, TN USA

Paul McCown, PE, CEM, LEED AP, CxA Sr. Mechanical Engineer SSRCx, LLC Nashville, TN USA Continuous Commissioning of a LEED-EB Gold Certified Office Building Paul McCown, PE, CEM, LEED AP, CxA Sr. Mechanical Engineer SSRCx, LLC Nashville, TN USA KEYWORDS Continuous Commissioning, Retro-Commissioning,

More information

Selected Laboratory Energy Efficiency Measures

Selected Laboratory Energy Efficiency Measures Selected Laboratory Energy Efficiency Measures These are some of the most effective energy efficiency measures for laboratories 1. Reduce (optimize) air changes per hour in lab space 2. Design to the proper

More information

The Ed Roberts Campus Berkeley, CA

The Ed Roberts Campus Berkeley, CA The Ed Roberts Campus Berkeley, CA Anderson Clemenceau Mechanical Option Penn State A.E. Senior Thesis April 14, 2015 Leddy Maytum Stacy Architects, Photo by Tim Griffith ASHRAE Climate Zone 3C 99.6% Heating

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

Energy efficient climate control in museum stores. Poul Klenz Larsen

Energy efficient climate control in museum stores. Poul Klenz Larsen Energy efficient climate control in museum stores Poul Klenz Larsen A shelter for fighter airplanes protecting against a nuclear strike. The roof is 50 cm solid concrete covered with plastic paint Dehumidifiers

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

TECHNICAL REPORT 3 Mechanical Systems and Existing Conditions Northfield Mental Healthcare Center Northfield, Ohio

TECHNICAL REPORT 3 Mechanical Systems and Existing Conditions Northfield Mental Healthcare Center Northfield, Ohio Technical Report 3 Northfield Mental Healthcare Center Dr. Stephen Treado Ji Won Park Mechanical Option Fall 2012 TECHNICAL REPORT 3 Mechanical Systems and Existing Conditions Northfield Mental Healthcare

More information

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS) MSP WRAP-ARUND MULTIPLE SMALL PLATE DEHUMIDIFICATIN TECHNLGY VS. CNVENTINAL DEHUMIDIFICATIN IN DEDICATED UTDR AIR SYSTEMS (DAS) ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++

More information

Sustainable Hot Water: Better Design, Delivery, and Use

Sustainable Hot Water: Better Design, Delivery, and Use Sustainable Hot Water: Better Design, Delivery, and Use March 24, 2009 Don Fisher Amin Delagah Fisher-Nickel, inc. PG&E Food Service Technology Center The Food Service Technology Center (FSTC) program

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

Identification of Aberrant Railroad Wayside WILD and THD Detectors: Using Industry-wide Railroad Data. June 10, 2014

Identification of Aberrant Railroad Wayside WILD and THD Detectors: Using Industry-wide Railroad Data. June 10, 2014 Identification of Aberrant Railroad Wayside WILD and THD Detectors: Using Industry-wide Railroad Data June 10, 2014 1 Agenda Background / Overview Solution Approach Groupings Criteria Sites Speed Weight

More information

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION BES-TECH TECHNOLOGY & SYSTEM INTEGRATION BES-TECH TECHNOLOGY & SYSTEM INTEGRATION DIGI-ACC Digi-ACC is a control kit for air cooled chiller systems, optimizing both chiller and pumps thereby reducing consumption

More information

Best Practices for Applied Rooftop ` Systems - Application and. Jerry Cohen President Jacco & Assoc. Installation

Best Practices for Applied Rooftop ` Systems - Application and. Jerry Cohen President Jacco & Assoc. Installation Best Practices for Applied Rooftop ` Systems - Application and Jerry Cohen President Jacco & Assoc. Installation Who is Jacco Established 1968 Hudson, Ohio Columbus, Ohio Toledo, Ohio Systems Knowledgeable

More information

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,

More information

MASTER PLAN KICK-OFF Open House #1A, April 28, 2015

MASTER PLAN KICK-OFF Open House #1A, April 28, 2015 "The beginning is the most important part of the work." Plato, The Republic MASTER PLAN KICK-OFF Open House #1A, April 28, 2015 YOUR CAMPUS PLANNING TEAM Campus Planners Landscape Architects Urban Designers

More information

Practical and Effective Approaches to Residential Ventilation for Production Builders

Practical and Effective Approaches to Residential Ventilation for Production Builders Practical and Effective Approaches to Residential Ventilation for Production Builders by Armin Rudd USDOE Building America Program for Affordable Comfort Conference 2002 Cincinnati, Ohio 18 April 2002

More information

Best Practices for Applied Rooftop ` Systems, Applications and. Jerry Cohen President Jacco & Assoc. Installation

Best Practices for Applied Rooftop ` Systems, Applications and. Jerry Cohen President Jacco & Assoc. Installation Best Practices for Applied Rooftop ` Systems, Applications and Jerry Cohen President Jacco & Assoc. Installation Established 1968 Hudson, Ohio Columbus, Ohio Toledo, Ohio Focused on the Engineered Environment

More information

Free cooling on RTAF Chiller. Integrated option

Free cooling on RTAF Chiller. Integrated option Free cooling on RTAF Chiller Integrated option Water based free cooling principle. Use full aluminum (car radiator based) flat channel dry cooler exchangers. Modulate 3 way to reach required free cooling

More information

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE

More information

Implementation of the Laboratory Air Handling Unit Systems (LAHU)

Implementation of the Laboratory Air Handling Unit Systems (LAHU) University of Nebraska - Lincoln DigitalCommons@University of Nebraska - Lincoln Architectural Engineering -- Faculty Publications Architectural Engineering 2003 Implementation of the Laboratory Air Handling

More information

WLAC Facilities Committee Meeting. May 15, 2017

WLAC Facilities Committee Meeting. May 15, 2017 Campus Program Report WLAC Facilities Committee Meeting May 15, 2017 Page 1 DSA completed the initial review June 24, 2016 and the Design Builder is proceeding through the back check process. DSA reports

More information

District Heat Montpelier. Customer Training

District Heat Montpelier. Customer Training District Heat Montpelier Customer Training 1 Welcome & Overview of Training Introductions District Heat Montpelier Overview In Building Components On Going Maintenance and Best Practices Optimizing Performance

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner ESL-TR-99/12-09 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Commerce (TAMU-Commerce) Commerce, Texas Submitted to Texas

More information

FACILITY ACTION PLAN

FACILITY ACTION PLAN FACILITY Mary Baker Russell Music Center CURRENT ENERGY USE INDEX (EUI) 293 kbtu/sq Ft 26.83 kwh/sq Ft FACILITY LIASON(S) David Robbins Chair of the Department of Music FACILITY ACTION PLAN TARGET EUI

More information

Technical Assignment 3 11/15/04. Executive Summary

Technical Assignment 3 11/15/04. Executive Summary Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria

More information

MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY

MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY 2018 57 MECHANICAL ASSESSMENT MECHANICAL ASSESSMENT This report section includes an overview of the existing

More information

Harrington Tower Building

Harrington Tower Building Continuous Commissioning Report For the Harrington Tower Building Building #435 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Energy & Water Savings in Commercial Food Service

Energy & Water Savings in Commercial Food Service Energy & Water Savings in Commercial Food Service Don Fisher Manager Food Service Technology Center 925-866-5770 dfisher@fishnick.com The Food Service Technology Center (FSTC) program is funded by California

More information

Bergen Community College 400 Paramus Road Paramus, NJ 07652

Bergen Community College 400 Paramus Road Paramus, NJ 07652 Steven Winter Associates, Inc. 293 Route 18, Suite 330 Telephone (866) 676-1972 Building Systems Consultants East Brunswick, NJ 08816 Facsimile (203) 852-0741 www.swinter.com June 9, 2010 Local Government

More information

Hot Water a Hot Commodity Better Buildings by Design, February 2012 Burlington, VT

Hot Water a Hot Commodity Better Buildings by Design, February 2012 Burlington, VT Hot Water a Hot Commodity Better Buildings by Design, February 2012 Burlington, VT Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability.com Gary Klein, 2012 Efficiency

More information

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Mingsheng Liu, Ph.D., P.E. Energy Systems Laboratory Texas A&M University College Station, Texas

More information

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates Prescriptions for Critical Healthcare Cx John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. Medical Industry Changes and how they impact Design, Construction,

More information

SOLAR HOT WATER AND HEAT PUMP BOOSTER ENERGY CALCULATION METHODOLOGY

SOLAR HOT WATER AND HEAT PUMP BOOSTER ENERGY CALCULATION METHODOLOGY SOLAR HOT WATER AND HEAT PUMP BOOSTER ENERGY CALCULATION METHODOLOGY PART A: CALCULATION METHODOLOGY FOR SOLAR WATER HEATERS AND HEAT PUMP WATER HEATERS WITH A VOLUMETRIC CAPACITY OF UP TO AND INCLUDING

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

MEASURED PERFORMANCE DATA FOR

MEASURED PERFORMANCE DATA FOR MEASURED PERFORMANCE DATA FOR HOUSE #4 INVERNESS GARDENS MILLER HOMES FEBRUARY 2013 Submitted to: NYSERDA 17 Columbia Circle Albany, NY 12203 Submitted by: HOMEPIC Team CDH Energy Corp. PO Box 641 Cazenovia,

More information

Analyzing Air Handling Unit Efficiency. Michael Rosenberg, PE, CEM

Analyzing Air Handling Unit Efficiency. Michael Rosenberg, PE, CEM Analyzing Air Handling Unit Efficiency Michael Rosenberg, PE, CEM Analyzing Air Handling Unit Efficiency Introduction...1 Air Handlers and Energy...2 Air Handler Case Study...7 Optimizing Economization

More information

Transfer Station Recycling Update SWANA Technical Session-Waste Diversion 4 2/24/2017 2/28/2017

Transfer Station Recycling Update SWANA Technical Session-Waste Diversion 4 2/24/2017 2/28/2017 Transfer Station Recycling Update SWANA Technical Session-Waste Diversion 4 2/24/2017 1 Todays Outline Roadmap to 70% A look back on how we started.. Vashon yard & food waste Styrofoam & plastic film Resource

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER Printed in the USA ADSOOASHPRAE 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located

More information

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK ENERGY CONSERVATION MEASURE 1 Partial Steam System Decentralization SIEMENS will Furnish and Install condensing hot water boilers with associated

More information

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.

More information

SELECTED TOPICS IN HIGH RISE MECHANICAL DESIGN

SELECTED TOPICS IN HIGH RISE MECHANICAL DESIGN SELECTED TOPICS IN HIGH RISE MECHANICAL DESIGN Simcoe Towers Toronto and Dubai Shangri-la Hotel NORR SWEGON ACADEMY MAY 2010 INTRODUCTION Topic A comparison of building mechanical practices in hot and

More information

Owner Municipality Built in 1978 Rebuilt in 2001 Rink and bleachers. Surface area (footprint) 4,140 m 2 (44,700 ft 2 )

Owner Municipality Built in 1978 Rebuilt in 2001 Rink and bleachers. Surface area (footprint) 4,140 m 2 (44,700 ft 2 ) Project profile Refrigeration Technological Innovation RAPB REFRIGERATION ACTION PROGRAM For BUILDINGS Colisée des Bois-Francs Victoriaville (Québec) MAJOR RETROFIT Summary Potential for substantial heat

More information

Sustainability Best Practices for HVAC Retrofits. Cal Poly State University, San Luis Obispo. Presented to the UC/CSU/CCC Sustainability Conference

Sustainability Best Practices for HVAC Retrofits. Cal Poly State University, San Luis Obispo. Presented to the UC/CSU/CCC Sustainability Conference Sustainability Best Practices for HVAC Retrofits Cal Poly State University, San Luis Obispo Presented to the UC/CSU/CCC Sustainability Conference June 22, 2009 Presented by Dennis K. Elliot, PE, CEM Sustainability

More information

Physical Plant Complex

Physical Plant Complex Continuous Commissioning Report For the Physical Plant Complex Building #1156 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

4. OVERVIEW OF MECHANICAL SYSTEM

4. OVERVIEW OF MECHANICAL SYSTEM 4. OVERVIEW OF MECHANICAL SYSTEM The 87,000 SF SLCC is served by six (6) Trane M-Series Climate Changer Air Handing Units (AHUs). Each unit serves a distinct zone within the facility that is unique in

More information

Displacement Ventilation in Classrooms

Displacement Ventilation in Classrooms TWO DIFFUSERS, THE WHITE COLUMNS ON EACH SIDE OF THE WHITEBOARD, PROVIDE COOL SUPPLY AIR TO THE DEMONSTRATION DV CLASSROOM. THE DV CLASSROOM DEMONSTRATION FEATURED A CUSTOMIZED ROOFTOP HVAC UNIT. Displacement

More information

Don t Flood The Rodeo! Preparing for Fort Worth s New Arena

Don t Flood The Rodeo! Preparing for Fort Worth s New Arena Don t Flood The Rodeo! Preparing for Fort Worth s New Arena T F M A S P R I N G C O N F E R E N C E APRI L 27 2017 Scott Hubley, P.E., CFM Justin Oswald, P.E., CFM Christopher Johnson, P.E., CFM PHOTO

More information

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001 This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.

More information

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop Energy-Savings Strategies for Rooftop VAV Systems Occupied set-point temperature Unoccupied set-point temperature Rooftop variable-air-volume (VAV) s are used to provide comfort in a wide range of building

More information

EarthWise System Seminar

EarthWise System Seminar EarthWise System Seminar Tim Gasper, P.E. Solutions Engineer Brady-Trane Services, Inc. EarthWise Systems? Energy Efficiency Emissions Buildings use 39% of the Primary Energy Consumed in the United States

More information

Site Evaluation. for. Oregon School for the Deaf. 999 Locust Street Northeast Salem, OR BE15178

Site Evaluation. for. Oregon School for the Deaf. 999 Locust Street Northeast Salem, OR BE15178 Site Evaluation for Oregon School for the Deaf 999 Locust Street Northeast Salem, OR 97301-0999 BE15178 Sponsored by: Energy Trust of Oregon Existing Buildings Program Submitted by: ATAC Contact Information

More information

High Efficiency Dehumidification System (HEDS)

High Efficiency Dehumidification System (HEDS) Advanced HVAC Technologies High Efficiency Dehumidification System (HEDS) Scot Duncan, P.E., Jim Meacham, P.E. Conservant Systems, Inc. August 16, 2017 Tampa Convention Center Tampa, Florida Why Was HEDS

More information

Tech Report III. Technology and Engineering Development (TED) Building. Thomas Jefferson National Accelerator Facility.

Tech Report III. Technology and Engineering Development (TED) Building. Thomas Jefferson National Accelerator Facility. Technology and Engineering Development (TED) Building Thomas Jefferson National Accelerator Facility Newport News, VA Tech Report III Mechanical Systems Existing Conditions Report 11/29/2010 Architectural

More information

Song Deng, P.E. Assistant Director Energy Systems Laboratory Texas A&M University College Station, TX

Song Deng, P.E. Assistant Director Energy Systems Laboratory Texas A&M University College Station, TX Room Temperature ontrol during Season Switchover with Single Duct Variable Air Volume System without Reheat henggang Liu Research Associate Song Deng, P.E. Assistant Director Homer L. Bruner, Jr., EM Mechanical

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

Re-Engineering Votey Hall:

Re-Engineering Votey Hall: Re-Engineering : Investment of Deferred Maintenance $$ into an aged Engineering Building by: Lynn Wood Retro-Commissioning Engineer Physical Plant Department New Construction: STEM $104M Central Campus

More information

Special Topics on Residential HVAC

Special Topics on Residential HVAC Special Topics on Residential HVAC by Armin Rudd USDOE Building America Program for EEBA Conference 2002 Phoenix, Arizona 10 October 2002 Page 1 of 25 Two Main Topics: 1. Cyclical trade-offs between building

More information

Improving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks

Improving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks Improving Performance with a Building Tune-Up Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks How much is too much? Most buildings can cut total energy use by 5-30% while

More information

Integrated Building Environmental Design Case Study: Beijing Parkview Green

Integrated Building Environmental Design Case Study: Beijing Parkview Green Integrated Building Environmental Design Case Study: Beijing Parkview Green The 7th International Energy Agency Annex 44 Forum 24 October 2007 Dr Raymond Yau Director Ove Arup & Partners Hong Kong Ltd.

More information

Copyright 2003 IBACOS, Inc. All rights reserved.

Copyright 2003 IBACOS, Inc. All rights reserved. Domestic Hot Water Research Research conducted by Bill Rittelmann Presented by Duncan Prahl Partners for High Performance Homes Meeting Westminster, CO, June 23, 2005 DHW Systems: Current Technologies

More information

Equipment ATA 12 April 2016

Equipment ATA 12 April 2016 05-00-01 Time limits and Maintenance Frequencies Various JUN 14 1 25-00-01 Charging Head Mk 2 & Accessories WKA26592 WKA26592A 25-60-15 Submersion Actuator K38215 58178-001 AUG 92 JAN 15 Initial Issue

More information

VARIABLE HEAT RECOVERY IN DOUBLE BUNDLE ELECTRIC CHILLERS. Richard J Liesen 1, Rahul J Chillar 2 1 University of Illinois at Urbana Champaign

VARIABLE HEAT RECOVERY IN DOUBLE BUNDLE ELECTRIC CHILLERS. Richard J Liesen 1, Rahul J Chillar 2 1 University of Illinois at Urbana Champaign VARIABLE HEAT RECOVERY IN DOUBLE BUNDLE ELECTRIC CHILLERS Richard J Liesen 1, Rahul J Chillar 2 1 University of Illinois at Urbana Champaign Dept of Mechanical & Industrial Engineering 1206 WGreen St Urbana,

More information

30% Design Community Meeting

30% Design Community Meeting Monday, September 17, 2018 30% Design Community Meeting Site 85-E-W-4 Please sign in on your mobile device: http//communitymeeting.ocps.net/ Site 85-E-W-4 Meeting Agenda September 17, 2018, 6:45PM Welcome

More information

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency Digital Precise Air Control System D-PAC Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency AAON 24 South Yukon Avenue Tulsa, Oklahoma 747 (918) 583-2266 Fax (918)

More information

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012 HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.

More information

Description of All Alternatives Considered-

Description of All Alternatives Considered- Description of All Alternatives Considered- Energy efficiency is an area where the Tubman design can be improved. The design heating load is 1807.8 MBH and the design cooling load is 1702.2 MBH or 142

More information

2014 ASHRAE TECHNOLOGY AWARD CASE STUDIES

2014 ASHRAE TECHNOLOGY AWARD CASE STUDIES This article was published in ASHRAE Journal, April 2014. Copyright 2014 ASHRAE. Posted at www. ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

Farm Energy Audit Workshop

Farm Energy Audit Workshop Farm Energy Audit Workshop Sponsored by the Western Mountains Alliance, a member of the Maine Rural Partners Farm Energy Partners Network and Efficiency Maine Skowhegan, Maine May 14, 2008 Walk-Through

More information

Asparagus Response to Water and Nitrogen

Asparagus Response to Water and Nitrogen Asparagus Response to Water and Nitrogen Item Type text; Article Authors Roth, Robert L.; Gardner, Byrant R. Publisher College of Agriculture, University of Arizona (Tucson, AZ) Journal Vegetable Report

More information

McQuay. Aircon Air Cooled Condenser. AMB, APB AMD, APD Vintage A. Last Manufacture: 1978

McQuay. Aircon Air Cooled Condenser. AMB, APB AMD, APD Vintage A. Last Manufacture: 1978 Replacement Parts List No. 055224800 Revision C 10/2017 McQuay Aircon Air Cooled Condenser AMB, APB 020-140 AMD, APD 008-030 Vintage A Last Manufacture: 1978 To find your Daikin Applied parts distributor,

More information

MAYEKAWA MFG. CO., LTD Botan Koto-ku, Tokyo , JAPAN TEL:(81) FAX:(81)

MAYEKAWA MFG. CO., LTD Botan Koto-ku, Tokyo , JAPAN TEL:(81) FAX:(81) * mayekawa, MYCOM, NewTon are registered trademarks of Mayekawa Mfg.Co.,Ltd. * Subject to change without notice. MAYEKAWA MFG. CO., LTD. 3-14-15 Botan Koto-ku, Tokyo 135-8482, JAPAN TEL:(81)-3-3642-8181

More information

NATURAL GAS ENERGY ANALYSIS PROGRAM (NGEA)

NATURAL GAS ENERGY ANALYSIS PROGRAM (NGEA) NATURAL GAS ENERGY ANALYSIS PROGRAM (NGEA) CENTERPOINT ENERGY Prepared by: Tanuj Gulati, Sr. Energy Engineer Tuesday, May 21 st of 2014 ENERGY INSIGHT INC 7935 Stone Creek Drive, Suite 140 Chanhassen,

More information

Countywide Recycling and Disposal Facility Weekly Progress Report 08/22/08

Countywide Recycling and Disposal Facility Weekly Progress Report 08/22/08 Countywide Recycling and Disposal Facility Weekly Progress Report 08/22/08 This Weekly Progress Report is prepared by Countywide and submitted to the OEPA weekly by the close of business on each Friday.

More information

Efficient Irrigation, Smart Controllers and Climate Appropriate Shade Trees. Clovis Community College Center Clovis, CA

Efficient Irrigation, Smart Controllers and Climate Appropriate Shade Trees. Clovis Community College Center Clovis, CA Efficient Irrigation, Smart Controllers and Climate Appropriate Shade Trees Clovis Community College Center Clovis, CA June 28, 2017 Evapotranspiration Adjustment Factor Study Department of Water Resources

More information