TECHNICAL SPECIFICATION

Size: px
Start display at page:

Download "TECHNICAL SPECIFICATION"

Transcription

1 Vallox 50SE EFFECT E Code A VALLOX DIGIT SED ELECTONIC CONTOLLE WITH LCD DISLAY LV TECHNICAL SECIFICATION ODELS: L LV L LV Supply and extract air ventilation with heat recovery Silent operation Energy-efficient unit; high-efficiency cross-counter flow heat recovery cell and integrated direct current fans Electronic DIGIT SED control Week clock control as a Standard feature Humidity control (Option) Carbon dioxide control (Option) aintenance reminder Summer / winter automation Fireplace / booster switch function at the controller Good filtering Fixed air flow measurement outlets The LV model is especially designed for use with ground heat systems. Silencing unit (option) Electrical connection 30 V, 50 Hz, 5.9 A Class of protection I 34 Fans Extract air Supply air 0.75 kw 0.76 A 0.75 kw 0.76 A 46 dm 3 /s (00 a) 30 dm 3 /s (00 a) Heat recovery Cross-counter flow cell, >80 % Heat recovery bypass Summer / winter automation 0,3 A reheating unit (Standard) ost-heating unit (Option) LV reheating unit (Standard) ost-heating unit (Option) Electric, 000 W Electric, 000 W or VKL water radiator 5,9 A LV heating / cooling radiator unit VKL water radiator or electric 000 W Filters Weight Supply air Extract air G4 and F7 G4 0 kg Ventilation adjustment Options - control via control panel - week clock control - CO and %H control (Option) Options - CO sensor - %H sensor - filter guard (supply and/or extract air) - LON converter - ostheateing VKL water radiator for LV-model - Electric post-heating unit for LV unit - Silencer element

2 DIENSIONS AND AIN ATS Dimensions and duct outlets model LV radiator (liquid-circulating preheating) lead-throughs LV model 4 B A 4 A 3 B 3 odel VKL radiator (liquid-circulating post-heating) lead-throughs A B 4 DIGIT SED ELECTONIC CONTOLLE WITH LCD DISLAY A 3 B ain parts Options odel L Inner diameter of female outlets ø 00 mm Outdoor air to the unit Extract air from the dwelling 3 Supply air to the dwelling 4 Exhaust air out A eturn water/liquid B Supply water/liquid Weight of unit 0 kg 3 5 Extract air fan Supply air fan reheating radiator (electric 000 W or liquid, standard) Heat recovery cell 6 Outdoor air filter F Outdoor air filter G4 Extract air filter G4 Summer / winter damper Safety switch easurement outlets Control panel DIGIT SED ost-heating radiator electric 000 W or water Carbon dioxide sensor Humidity sensor LON converter Filter guard (supply and/or extract air)

3 EFOANCE Air volumes SULY / EXTACT AI VOLUES DC FANS a SF = Input power (total) (W) Air flow (max.) (dm 3 /s) = Extract air fan = Supply air fan SF (Specific Fan ower) guideline value <.5 (kw/m 3 /s) At a lower total pressure, SF will be smaller at this speed. ED and SD are examples of pressure losses in supply and extract ducts SF =,5 kw/m 3 /s easuring points after the connection outlet. Fan curves indicate the total pressure available for duct losses. Supply air Extract air ressure loss in ducts. Total pressure Sound values Adjustment position Air flow (dm 3 /s) 63 edium 5 frequency 50 of the octave 500 band, Hz L W, db L WA, db(a) Adjustment position Air flow (dm 3 /s) Volume flow rate L pa, db(a) Sound power level from the ventilation unit to supply air ducts by octave band Lw, db 5 ADJUSTENT OSITION / AI FLOW A-weighted sound pressure level db (A) coming from the unit through the envelope in rooms where the unit has been installed (0 m sound absorption) ADJUSTENT OSITION / AI FLOWS (supply / extract) /63 80/83 09/09 40/ Sound power level from the ventilation unit to extract air ducts by octave band Lw, db ED SD ADJUSTENT OSITION / AI FLOW ECOENDED OEATING ANGE SF = kw/m 3 /s dm 3 /s S Fan speeds Extract air flow (dm 3 /s) Note! When the system is being adjusted, post-heating must be selected (winter setting). E The total input power of the fans W

4 Note! During installation, circa 70 mm mounting space is needed above the silencing part. EFOANCE/VALLOX SILENCE UNIT The pipes of the LV radiator are not included in the delivery VKL radiator lead-throughs Air flows SULY/EXTACT AI VOLUES WITH SILENCE UNIT The silencer unit decreases both supply and extract air flow by to 3% (cf. supply/extract air volume curve on page 3). 93 min Sound values for silencer unit + 50 Effect SE Adjustment position Air flow (dm 3 /s) 63 edium 5 frequency of 50 the octave 500 band, Hz L W, db L WA, db(a) Sound power level by octave band in supply air ducts after the silencer unit L w (db) ADJUSTENT OSITION/AI FLOW Sound power level by octave band in extract air ducts after the silencer unit LW L w (db) ADJUSTENT OSITION/AI FLOW A-weighted sound pressure level db (A) coming from the unit through the envelope in the rooms where the unit has been installed (0m sound absorption) Adjustment position Air flow (dm 3 /s) L pa, db(a) ADJUSTENT OSITION/AI FLOWS (supply/extract) /50 57/63 65/7 76/8 85/9 00/07 4/4 6/

5 3 4 Start button With this button, you switch the unit on and off. When the indicator is lit, the unit is on. Carbon dioxide adjustment With this button, you set carbon dioxide adjustment on and off. When the indicator is lit, the adjustment is on. Humidity adjustment With this button, you set humidity adjustment on and off. When the indicator is lit, the adjustment is on. ost-heating ress this button to switch post-heating on and off. reheating also switches on. When the indicator is lit, post-heating is on. The summer function is active when the indicator is not lit. Control can be controlled with a control panel coming with the unit (3 at most) and with Optional CO (5 at most) and %H sensors ( at most). Fan speeds of the unit can be controlled via remote monitoring with a voltage signal. In case of disturbances, a potential-free relay contact signal is issued. With an Optional VALLOX LON converter, the whole operation of the unit can be controlled via remote monitoring. Week clock control The week clock in the control panel of the unit can be used to programme the desired fan power Option ( 8) for each hour in the day. Control panel Scrolling up With this button, you can scroll the displays upward. Scrolling down With this button, you can scroll the displays downward. Increase button With this button, you can increase values. Decrease button With this button, you can decrease values. CONTOL ANEL Keyboard 3 C 0:0 Fan speed (3). Supply air temperature ( C). ost-heating is on. Time. Filter guard alert. aintenance reminder alert. Fireplace / booster switch on. The fireplace / booster switch is activated in this display by simultaneously pressing down the + and buttons for seconds. Week clock control on. 3 C ain display 0:0 Fan speed can be changed in this display with the + and buttons ounting, removing and wiring of control panel The control panel is wired straight from the electrical connection box. The control panel can also be connected in series with a CO sensor or another control panel. (See External electrical connections on page 8). Control panel addresses If two or more control panels are connected to the system, the addresses of the control panels need to be changed. E.g. 3 control panels. Connect the first control panel to the unit and change its address to 3. Connect the second control panel to the unit and change its address to. Connect the third control panel and make sure that its address is. If control panels have the same address, they go to bus fault state. In this case, remove one of the control panels and change the address of the other panel. The above mentioned situation can arise in connection with the later installation of an additional control panel. aneelin osoite anel address 5

6 OUNTING THE CONTOL ANEL AND SENSOS Surface mounting of control panel A control panel is mounted on the wall or on a -part instrument box. Width Height Depth 90 mm 0 mm 3 mm Wiring A B Electronics board of control panel Cable: NOAK x x 0.5 mm mm NOTE! Faulty coupling of the (+) wire destroys the control panel! = orange = + = white = } ca. VDC 3 = orange = A 4 = white = B 5 = metal = signal ground ounting and wiring of humidity sensor The sensor is wired straight from the electrical connection box of the unit. Surface mounting Base plate of sensor Wiring Electronics board of %H sensor S + HUIDITY SENSOS When mounting two or more humidity sensors, connect them to the terminal block of the connection box by connecting the first humidity sensor to %H, in place of the resistor 6K8 in the terminal block (remove the resistor in this case), and the second humidity sensor to %H. See the electrical diagram. Cable: x 0,5 mm ounting and wiring of carbon dioxide sensor The CO sensor is connected directly from the connection box of the unit, or in series with another CO sensor or control panel (see External electrical connections on page 8). Surface mounting 4 Wiring A B Cable: NOAK x x 0.5 mm mm CABON DIOXIDE SENSOS Carbon dioxide sensors are connected individually. When the first carbon dioxide sensor has been connected to the system, the unit is switched on. After this, the unit gives the sensor an address. Follow the same steps for other carbon dioxide sensors NOTE! Faulty coupling of the (+) wire destroys the carbon dioxide sensor! = orange = + = white = } ca. VDC 3 = orange = A 4 = white = B 5 = metal = signal ground Base plate of the CO sensor Electronics card of the CO sensor (model may vary) 6

7 INTENAL CONNECTION DIAGA, integrated fans S E H L TK T T K L L V = Supply fan = Extract fan = Direct-current transformer with protective voltage coil = Interference suppressor = Earthed cord = Safety switch = Overheating protector 70 C (automatic reset) = Heating radiator safety thermostat 30 C (reset, switch the unit off) = Choke = reheating radiator = ost-heating radiator = Water radiator thermostat valve = Damper motor = Temperature sensors = Auxiliary resistor 6.8 kohm TE DS = Supply air duct filter guard (option) DS = Extract air duct filter guard (option) V = Solenoid valve = Circulation pump Wire colours: BU = blue BN = brown BK = black GNYE = yellow-green DS DS TE 4 (EXTACT AI) TE 3 (OUTDOO AI) TE (SULY AI) TE (EXHAUST AI) H CELL OTHEBOAD S S S S G N D -+ AB DS FAULT EOTE %H %H BOOSTE SIGNAL CONTOL SWITCH 0-0 V DC S + S GND + S + S D C T D C + S S S L N NC S-485 BUS - A B F3 30 V 0 V 6 V 0 V U3 U H L N V K TK LV L L L N L3 N NC 3 W W GND L4 N4 L N GNYE BU L BN BU BN BN BU 30 C 70 C 30 C T L T T L 70 C T V Water radiator actuator T BN YE BU BU BU BU GNYE GNYE BK BN BN YE BU BU BU BU GNYE GNYE BK BN C 7

8 EXTENAL ELECTICAL DIAGA LonWorks-FT0 BLACK = WHITE = B OANGE = A WHITE = - OANGE = + LON CONVETE OTION A B + - A B A B + - A B NOAK xx NOTE! Faulty coupling of the + wire DESTOYS THE CONTOL ANEL. CONTOL ANEL ONE O OE INCLUDED AS STANDAD NOTE! Faulty coupling of the + wire DESTOYS THE SENSO. CO -SENSO ONE O OE OTION S + S + THE FIST HUIDITY SENSO IS CONNECTED TO ELACE THE 6k8 ESISTO. NOAK xx VDC HUIDITY SENSO %H (OTION) HUIDITY SENSO %H (OTION) EOTE CONTOL The short-circuit wire has to be removed before connection. x0.5 x0.5 x0.5 FAULT SIGNAL AX A, 4 VDC (OTENTIAL-FEE CONTACTS) x0.5 FIELACE SWITCH Button switch (self-resetting contact) x0.5 x0,5 DS FAULT SIGNAL FAN CONTOL %H %H S-485 BUS BOOSTE S + S GND + S + S SWITCH + - A B L L L N SOLENOID VALVE CICULATION U VALLOX 50 EFFECT SE lug connection 6 A when the unit is equipped with electric pre- and post-heating.8 m from top of the unit 8

9 FILTEING, HEAT ECOVEY, HEATING Filtering Efficient filtering of outdoor air (G4 + F7) prevents harmful particles from entering the ductwork and rooms via the unit. Good filtering of extract air (G4) diminishes the contamination of the unit and ensures efficient heat recovery and extract air fan operation. Clogging of the supply/ extract air filters can be monitored by equipping the unit with a pressure difference switch. Heat recovery and heating With efficient heat recovery most of the heat from contaminated extract air can be transmitted to outdoor air coming inside. The efficiency of the heat recovery cell is circa 80%. If outdoor air does not get sufficiently warm in the heat recovery cells, it can be heated with a water or electric post-heating unit. The unit features an automatic heat recovery bypass function, which eliminates needless heating of outdoor air during summer. Antifreezing The automatic antifrost function of the heat recovery cell intermittently stops the supply air fans when the temperature of exhaust air goes under the set threshold value. In order to minimise momentary stoppages of the supply air fans the unit is also equipped with an electric preheating unit or a liquid-circulating preheating radiator (LV). Electric preheating unit (standard equipment) In unit ower.0 kw, 4.3 A LV radiator heating power ( W) The outdoor temperature starting preheating is set at the control panel. The value set must be lower than that of the liquid coming from the ground collector. Ethylene glycol 5% ti = - C (supply air temperature) Vn = dm 3 /s (liquid volume flow rate) LV heating/cooling preheating unit (Standard) In LV unit LV radiator cooling power ( W) Supply air temperature is chosen at the control panel. Because of the risk of humidity damage supply air temperature in a duct with no condensation insulation should not go below C in hot weather. Ethylene glycol 5% ti = 5 C (supply air temperature) elative humidity H 50% Vn = dm 3 /s (liquid volume flow rate) Temperature of air leaving the radiator C dm 3 /s 50 dm 3 /s 70 dm 3 /s Air flow dm 3 /s Temperature of air leaving the radiator C dm 3 /s 50 dm 3 /s Airflow dm 3 /s Geothermal liquid temperature C Geothermal liquid temperature C LV radiator pressure loss in liquid circulation (LV radiator causes a small pressure loss also in air flow.) Ethylene glycol 5% 35 ressure loss Δp ka ,0 0,04 0,06 0,08 Liquid flow dm 3 /s Temperature of geothermal liquid leaving radiator C Cooling of geothermal liquid of LV radiator Ethylene glycol 5% Flow dm 3 /s Air coming in - C Air coming in -30 C Temperature of geothermal liquid coming to radiator C Air flows dm 3 /s 9

10 OST-HEATING Electric post-heating unit (option equipment) Option in and 50 Effect SE LV units. ower.0 kw, 4.3 A. Water post-heating unit (option equipment) erformance of the water post-heating radiator (VKL) in and LV ti = 3 C (temperature of air coming to the radiator) tv = 50 C (temperature of water coming to the radiator) ti = 3 C (temperature of air coming to the radiator) tv = 30 C (temperature of water coming to the radiator) Total power of the radiator kw Water flow dm 3 /s dm 3 /s 35 dm 3 /s 95 dm 3 /s Total power of the radiator kw Water flow dm 3 /s dm 3 /s 60 dm 3 /s 35 dm 3 /s Cooling of water in the radiator C Cooling of water in the radiator C ti = 3 C (temperature of air coming to the radiator) tv = 35 C (temperature of water coming to the radiator) VKL water radiator pressure loss in water circulation.5 Water flow dm 3 /s Defined for 00% water Total power of the radiator kw dm 3 /s 60 dm 3 /s 35 dm 3 /s Total pressure loss ka Cooling of water in the radiator C Water flow dm 3 /s 0

11 CONTOL DIAGA/ Electric post-heating unit CONTOL DIAGA, electric post-heating unit DISTIBUTION ANEL 6 A LUG 30V 50Hz EOTE ONITOING CONTOL CENTE OF THE OETY ALA OEATION STATUS CONTOL EASUEENT ADJUSTENT LON CONVETE VALLOX 50 EFFECT SE INTENAL ELECTICAL AND CONTOL CONNECTIONS TE TE3 SILENCE SILENCE UNIT SILENCE TE4 G4 G4 T T DS T L OST-HEATING UNIT, ELECTIC ESSUE DIFFEENCE SWITCH T T EHEATING UNIT, ELECTIC F 7 L H FG TE DS ESSUE DIFFEENCE SWITCH S CO H %H %H BOOSTE SWITCH/ FIELACE SWITCH CABON DIOXIDE SENSO (5 AT OST) CONTOL ANEL (3 AT OST) HUIDITY SENSO VENTILATION ZONE B arts list Code Name Technical data Standard / (factory settings in parentheses) Option CO Carbon dioxide sensor, 5 at most Adjustment range ppm (900) Option Carbon dioxide control Adjustment range...5 min. (0) G4 Filter Supply air, extract air Standard F7 Filter Supply air Standard FG Damper motor H bypass automation, 4 V, W, 8 Nm Standard H Control panel, 3 at most User interface Standard L reheating unit Electric radiator kw Standard L ost-heating unit Electric radiator kw Option H Heat recovery cell Cross-counter flow, efficiency = 80% Standard DS ressure difference switch Adjustment range a (30) Option ressure guard on the supply air side DS ressure difference switch Adjustment range a (30) Option ressure guard of the extract air filter Extract air fan DCqv = 40 dm 3 /s (50 a) Standard Code Name Technical data Standard / Option (factory settings in parentheses) %H Humidity sensor, at most Automatic / Adjustment range...99% (99) Option Humidity control Adjustment range...5 min. (0) TE Temperature sensor, Exhaust air temperature Standard H antifreeze, Adjustment range C (H bypass) preheating control Adjustment range 6 +5 C (preheating) TE Temperature sensor Supply air temperature Standard TE3 Temperature sensor Outdoor air temperature Standard TE4 Temperature sensor Extract air temperature Standard T Supply air fan DC qv=30 dm 3 /s (50 a) Standard T Heating unit overheat protection Automatic + 70 C included in L and L T Heating unit overheat protection anual reset +30 C included in L and L S Fireplace / booster switch function Functions as either a fireplace or booster switch Option (fireplace switch) LON LON converter emote monitoring control Option

12 DESCITION OF OEATION / Electric post-heating unit Control of operation ower supply to the unit can be controlled with a contactor in the distribution panel if needed, e.g. with a timer programme. After starting, the unit first operates at base fan speed. After that power is adjusted based either on the measurement data from air quality sensors and/or on manual control at the control panel. Fan speed adjustment anual control Fan speed of the ventilation unit is controlled in 8 steps at control panel H. Week clock control The fan power of the ventilation unit is controlled in 8 steps using the week clock in control panel H. The week clock can be used to programme the desired fan power option and the setpoint for supply air temperature for each day of the week and each hour in the day. Carbon dioxide and humidity control The fan power of the ventilation unit is controlled in multiple steps depending on load and based on the measurement results of the air quality sensors (CO and %H sensors) located in the ventilation zone. The aim is to keep carbon dioxide and/or humidity content below the threshold set at control panel H. It is also possible to select an automatic search for the humidity content threshold at control panel H. One or more modes of control may be used simultaneously the mode demanding boosting is the dominant one. Fan speed varies depending on load between the base and maximum fan speeds. The base and maximum fan speeds can be set at the desired level at the control panel. Voltage signal control The fan power of the ventilation unit is controlled in 8 steps with a voltage signal of VDC. However, fan power cannot be raised above the set maximum fan speed. Voltage signal control is used to control base fan speed. This means that fan speed can be raised when necessary, but not lowered, by the manual, CO and %H controls. Voltage signal values Voltage values for each fan speed: 0 0,0...,5 VDC,75...,5 VDC,75...3,5 VDC 3 3,75...4,5 VDC 4 4,75...5,5 VDC 5 5,75...6,5 VDC 6 6,75...7,5 VDC 7 7,75...8,5 VDC 8 8,75...0,00 VDC Supply air temperature Supply air temperature can be controlled with either constant temperature control or cascade control. Supply air constant temperature control The control unit directs the operation of post-heating unit L on the basis of the measurement data given by temperature sensor TE, aiming at keeping supply air temperature at the temperature value set on control panel H ( ºC). Supply air cascade control The control unit directs the operation of post-heating unit L on the basis of the measurement data given by extract air sensor TE4, aiming at keeping extract air temperature at the temperature value set on control panel H ( ºC). Heat recovery bypass Heat recovery is enabled whenever post-heating has been switched on. Automatic heat recovery bypass is active whenever post-heating has been switched off and outdoor temperature is more than the set threshold value (to be set between ºC). In this case, the control unit directs the operation of damper motor FG on the basis of measurement results given by outdoor temperature sensor TE3 and extract air temperature sensor TE4. The aim is to get as cool supply air to the ventilation zone as possible. However, heat recovery is on whenever outdoor temperature is below the threshold set, or whenever outdoor air is warmer than extract air. Heat recovery antifreeze The control centre of the unit controls the operation of preheating unit L on the basis of the measurement data given by temperature sensors TE and TE3, thus preventing freezing alerts and the intermittent stopping of supply air fan T. If the capacity of preheating unit L is not sufficient, the control centre keeps stopping supply air fan T on the basis of the measurement data of temperature sensors TE and TE3, thus preventing the H cell from freezing. As soon as the risk passes, the fan restarts automatically. The threshold temperature ( C) and the difference area (...0 C) for antifreeze can be set at the control panel H. When fan T stops, power supply from radiator L is stopped and postheating radiator L continues to heat. For preheating to work, its threshold temperature has to be set by at least one degree higher than the threshold temperature controlling the stopping of the fan. Temperatures are adjusted at control panel H. Heating unit overheat protection Overheat protection thermostats T and T monitor the surface temperature of heating units L and L. When surface temperature exceeds the threshold, overheat protection is triggered and power supply to the heating unit is stopped. Overheat protection T is reset automatically, whereas overheat protection TS is reset by switching the unit off. Alarms ressure difference switches DS and DS monitor the pressure difference of the supply and exhaust air sides. If the pressure difference rises too high because of dirty filters or clogged ducts, an alarm will be issued. This is indicated by a symbol ( ) in the main display of the control panel. If the unit is not equipped with pressure difference switches, the symbol ( ) appearing in the main display of the control panel reminds of the need for maintenance of the unit. The reminder interval can be set between...5 months. The factory setting is 4 months. This function is active all the time. The fault signal relay in the unit gives potential-free alarm indications on the following fault conditions. Alarm of high carbon dioxide content (> 5000 ppm) switches the relay at -second intervals. In other fault situations, such as sensor faults, the contacts of the relay close. Booster or fireplace switch function The booster or fireplace switch function of the ventilation unit is controlled either at control panel H and/or separate switch S, which can be connected to the connection box of the unit. The mode of operation of the switch is selected at control panel H. The booster switch function raises fan speed to the set maximum fan speed for 45 minutes. The fireplace switch stops the extract air fan for 5 minutes and produces overpressure in the ventilation zone. LON remote monitoring control can be implemented with a VALLOX LON converter. See a separate brochure.

13 CONTOL DIAGA/ Water-circulating post-heating unit ADJUSTENT DIAGA, water post-heating unit DISTIBUTION ANEL 0 A LUG 30V 50Hz EOTE ONITOING CONTOL CENTE OF THE OETY ALA OEATION ODE CONTOL EASUEENT ADJUSTENT LON CONVETE VALLOX 50 EFFECT SE INTENAL ELECTICAL AND CONTOL CONNECTIONS TE TE3 SILENCE UNIT SILENCE SILENCE G4 TE4 V G4 Ljp DS ESSUE DIFFEENCE SWITCH F 7 T L OST-HEATING UNIT, WATE Ljm S CO H %H %H T T ELECTIC EHEATING UNIT L H FG TE DS ESSUE DIFFEENCE SWITCH BOOSTE SWITCH /FIELACE SWITCH CABON DIOXIDE SENSO (5 AT OST) CONTOL ANEL (3 AT OST) HUIDITY SENSO VENTILATION ZONE arts list VKL Code Name Technical data Standard / (factory settings in parentheses) Option CO Carbon dioxide sensor, 5 at most Adjustment range ppm (900) Option Carbon dioxide control Adjustment range...5 min. (0) G4 Filter Supply air, extract air standard F7 Filter Supply air Standard FG Damper motor H bypass automation, 4 V, W, 8 Nm Standard H Control panel, 3 at most User interface Standard L reheating unit Electric radiator kw Standard L ost-heating unit Water radiator Option H Heat recovery cell Cross-counter flow, efficiency = 80% Standard DS ressure difference switch Adjustment range a (30) Option ressure guard on the supply air side DS ressure difference switch Adjustment range a (30) Option ressure guard of the extract air filter Extract air fan DC DCqv = 40 dm 3 /s (50 a) Standard V Water radiator thermostat valve Standard Code Name Technical data Standard / (factory settings in parentheses) Option %H Humidity sensor, at most Automatic / Adjustment range...99% (99) Option Humidity control Adjustment range...5 min. (0) TE Temperature sensor, Exhaust air temperature Standard H antifreeze, Adjustment range C (H bypass) preheating control Adjustment range 6 +5 C (preheating) TE Temperature sensor Supply air temperature Standard TE3 Temperature sensor Outdoor air temperature Standard TE4 Temperature sensor Extract air temperature Standard T Supply air fan DC qv=30 dm 3 /s (50 a) Standard T Heating unit overheat protection Automatic + 70 C included in L T Heating unit overheat protection anual reset +30 C included in L S Fireplace / booster switch function Functions as either a fireplace or booster switch Option (fireplace switch) LON LON converter emote monitoring control Option 3

14 DESCITION OF OEATION / Water-circulating post-heating unit Control of operation ower supply to the unit can be controlled with a contactor in the distribution panel if needed, e.g. with a timer programme. Upon starting, the unit first operates at base fan speed. After that power is adjusted based either on the measurement data from air quality sensors and/or on manual control at the control panel. Fan speed adjustment anual control Fan speed of the ventilation unit is controlled in 8 steps at control panel H. Week clock control The fan power of the ventilation unit is controlled in 8 steps using the week clock in control panel H. The week clock can be used to programme the desired fan power option and the setpoint for supply air temperature for each day of the week and each hour in the day. Carbon dioxide and humidity control The fan power of the ventilation unit is controlled in multiple steps depending on load and based on the measurement results of the air quality sensors (CO and %H sensors) located in the ventilation zone. The aim is to keep carbon dioxide and/or humidity content below the threshold set at control panel H. It is also possible to select an automatic search for the humidity content threshold at control panel H. One or more modes of control may be used simultaneously the mode demanding boosting is the dominant one. Fan speed varies depending on load between the base and maximum fan speeds. The base and maximum fan speeds can be set at the desired level at the control panel. Voltage signal control The fan power of the ventilation unit is controlled in 8 steps with a voltage signal of VDC. However, fan power cannot be raised above the set maximum fan speed. Voltage signal control is used to control base fan speed. This means that fan speed can be raised when necessary, but not lowered, by the manual, CO and %H controls. Voltage signal values Voltage values for each fan speed: 0 0,0...,5 VDC,75...,5 VDC,75...3,5 VDC 3 3,75...4,5 VDC 4 4,75...5,5 VDC 5 5,75...6,5 VDC 6 6,75...7,5 VDC 7 7,75...8,5 VDC 8 8,75...0,00 VDC Supply air temperature Supply air temperature can be controlled with either constant temperature control or cascade control. Supply air constant temperature control The control unit directs the operation of post-heating unit L on the basis of the measurement data given by temperature sensor TE, aiming at keeping supply air temperature at the temperature value set on control panel H ( ºC). Supply air cascade control The control unit directs the operation of post-heating unit L on the basis of the measurement data given by extract air sensor TE4, aiming at keeping extract air temperature at the temperature value set on control panel H ( ºC). Heat recovery bypass Heat recovery is enabled whenever post-heating has been switched on. Automatic heat recovery bypass is active whenever post-heating has been switched off and outdoor temperature exceeds the setpoint (to be set between C). In this case, the control unit directs the operation of damper motor FG on the basis of measurement results given by outdoor temperature sensor TE3 and extract air temperature sensor TE4. The aim is to get as cool supply air to the ventilation zone as possible. However, heat recovery is on whenever outdoor temperature is below the threshold set, or whenever outdoor air is warmer than extract air. Heat recovery antifreeze The control centre of the unit controls the operation of preheating unit L on the basis of the measurement data given by temperature sensors TE and TE3, thus preventing freezing alerts and the intermittent stopping of supply air fan T. If the capacity of preheating unit L is not sufficient, the control centre keeps stopping supply air fan T on the basis of the measurement data of temperature sensors TE and TE3, thus preventing the H cell from freezing. As soon as the risk passes, the fan restarts automatically. The threshold temperature ( C) and the difference area (...0 C) for antifreeze can be set at control panel H. When fan T stops, power supply from radiator L stops and the actuated valve V of post-heating radiator L starts to open and remains open. For preheating to work, its threshold temperature has to be set by at least one degree higher than the threshold temperature controlling the stopping of the fan. Temperatures are adjusted at control panel H. Heating unit overheat protection Overheat protection thermostats T and T monitor the surface temperature of heating unit L. When surface temperature exceeds the threshold, overheat protection is triggered and power supply to the heating unit is stopped. Overheat protection T is reset automatically, whereas overheat protection T is reset by switching the unit off. Water radiator freezing protection Based on the measurement data of outdoor temperature sensor TE3 (outdoor air < 0 C) and supply air temperature sensor TE (supply air <7 C), the control centre of the unit stops fans T and and leaves valve V open, thereby decreasing the freezing risk in water circulating heating unit L. A freezing alert appears in the display of the control panel. The fans restart automatically as soon as the risk of freezing passes (supply air > 0 C). Alarms ressure difference switches DS and DS monitor the pressure difference on the supply and extract air sides. If the pressure difference rises too high because of dirty filters or clogged ducts, an alarm will be issued. This is indicated by a symbol ( ) in the main display of the control panel. If the unit is not equipped with pressure difference switches, the symbol ( ) appearing in the main display of the control panel reminds of the need for maintenance of the unit. The reminder interval can be set between and 5 months. The factory setting is 4 months. This function is always active. The fault signal relay in the unit gives potential-free alarm indications on the following fault conditions: When the antifreeze function of the water-circulating radiator is on, the contacts of the the relay open and close at 0-second intervals. Alarm of high carbon dioxide content (> 5000 ppm) switches the relay at -second intervals. In other fault situations, such as sensor faults, the contacts of the relay close. Booster or fireplace switch function The booster or fireplace switch function of the ventilation unit is controlled either at control panel H and/or separate switch S, which can be connected to the connection box of the unit. The mode of operation of the switch is selected at control panel H. The booster switch function raises fan speed to the set maximum fan speed for 45 minutes. The fireplace switch stops the extract air fan for 5 minutes and produces overpressure in the ventilation zone. LON remote monitoring control can be implemented with a VALLOX LON converter. See a separate brochure. 4

15 DISTIBUTION ANEL 0 A LUG CONTOL DIAGA/LV radiator/post-heating water CONTOL DIAGA LV/water-circulating post-heating radiator unit 30V 50Hz EOTE ONITOING CONTOL CENTE OF THE OETY ALA OEATION ODE CONTOL EASUEENT ADJUSTENT LON CONVETE VALLOX 50 EFFECT SE LV INTENAL ELECTICAL AND CONTOL CONNECTIONS TE TE3 SILENCE SILENCE UNIT SILENCE TE4 G4 V DS ESSUE DIFFEENCE SWITCH F 7 T G4 L OST-HEATING UNIT, LIQUID V Ljp Ljm S CO H %H %H H BOOSTE SWITCH / FIELACE SWITCH CABON DIOXIDE SENSO (5 AT OST) EHEATING UNIT, LIQUID L FG TE DS ESSUE DIFFEENCE SWITCH CONTOL ANEL (3 AT OST) HUIDITY SENSO VENTILATION ZONE arts list LV with water-circulating post-heating radiator Code Name Technical data Standard/ (factory settings in parentheses) Option CO Carbon dioxide sensor, 5 at most Adjustment range ppm (900) Option Carbon dioxide control Adjustment interval 5 min (0) G4 Filter Supply air, extract air Standard F7 Filter Supply air Standard FG Damper motor Automatic heat recovery bypass Standard 4 V, W, 8 Nm H Control panel, 3 at most User interface Standard L reheating unit Liquid radiator Standard L ost-heating unit Liquid radiator Option H Heat recovery cell Counter-current, efficiency = 80% Standard DS ressure difference switch Adjustment range a (30) Option ressure guard on supply air side DS ressure difference switch Adjustment range a (30) Option ressure guard on extract air side Extract air fan DC qv = 40dm 3 /s (50 a) Standard %H Humidity sensor, at most Automatic/Adjustment range 99% (99) Option Humidity control Adjustment interval 5 min. (0) Code Name Technical data Standard/ (factory settings in parentheses) Option TE Temperature sensor, Exhaust air temperature Standard H cell antifreeze Adjustment range C (H) TE Temperature sensor Supply air temperature Standard TE3 Temperature sensor, Outdoor air temperature Standard preheating control Adjustment range C (preheating) TE4 Temperature sensor Extract air temperature Standard T Supply air fan DC qv = 30 dm 3 /s (50a) Standard V Water radiator thermostat valve Standard V Solenoid valve Not included in delivery l Circulation pump Not included in delivery S Fireplace/booster switch function Either fireplace or booster switch Option function (fireplace switch) can be selected. LON LON converter emote monitoring control Option 5

16 CONTOL DIAGA/LV radiator/post-heating electric CONTOL DIAGA LV/electric post-heating radiator unit DISTIBUTION ANEL 0 A LUG 30V 50Hz EOTE ONITOING CONTOL CENTE OF THE OETY ALA OEATION ODE CONTOL EASUEENT ADJUSTENT LON CONVETE VALLOX 50 EFFECT SE LV INTENAL ELECTICAL AND CONTOL CONNECTIONS TE TE3 SILENCE SILENCE UNIT SILENCE TE4 G4 V DS ESSUE DIFFEENCE SWITCH T F 7 G4 L T T OST-HEATING UNIT, ELECTIC S CO H %H %H H BOOSTE SWITCH / FIELACE SWITCH CABON DIOXIDE SENSO (5 AT OST) EHEATING UNIT, LIQUID L FG TE DS ESSUE DIFFEENCE SWITCH CONTOL ANEL (3 AT OST) HUIDITY SENSO VENTILATION ZONE B arts list LV with electric post-heating radiator Code Name Technical data Standard/ (factory settings in parentheses) Option CO Carbon dioxide sensor, 5 pcs Adjustment range a (900) Option Carbon dioxide control Adjustment interval 5 min. (0) G4 Filter Supply air, extract air Standard F7 Filter Supply air Standard FG Damper motor Automatic heat recovery bypass Standard 4 V, W, 8 Nm H Control panel, 3 at most User interface Standard L reheating unit Liquid radiator Standard L ost-heating unit Electric radiator, 000 W Option H Heat recovery cell Counter-current, efficiency = 80% Standard DS ressure difference switch Adjustment range a (30) Option ressure guard on supply air side DS ressure difference switch Adjustment range a (30) Option ressure guard on extract air side Extract air fan DC qv = 40dm 3 /s (50 a) Standard %H Humidity sensor, at most Automatic/Adjustment range 99% (99) Option Humidity control Adjustment interval 5 min. (0) Code Name Technical data Standard/ (factory settings in parentheses) Option TE Temperature sensor, Exhaust air temperature Standard H cell antifreeze Adjustment range C (H) TE Temperature sensor Supply air temperature Standard TE3 Temperature sensor, Outdoor air temperature Standard preheating control Adjustment range C (preheating) TE4 Temperature sensor Extract air temperature Standard S Supply air fan DC qv = 30 dm 3 /s (50 a) Standard T Electric heating unit Automatic + 70 C Included in L overheat protection T Electric heating unit anual reset +30 C Included in L overheat protection V Solenoid valve Not included in delivery l Circulation pump Not included in delivery T Fireplace/booster switch Either fireplace or booster switch function Option function (fireplace switch) can be selected. LON LON converter emote monitoring control Option 6

17 Control of operation ower supply to the unit can be controlled with a contactor in the distribution panel if needed, e.g. with a timer programme. Upon starting, the unit first operates at minimum power. After that power is adjusted based either on the measurement data from air quality sensors and/or on manual control at the control panel. Fan speed adjustment anual control Fan speed of the ventilation unit is controlled in 8 steps at control panel H. Week clock control The fan power of the ventilation unit is controlled in 8 steps using the week clock in control panel H. The week clock can be used to programme the desired fan power option and the setpoint for supply air temperature for each day of the week and each hour in the day. Carbon dioxide and humidity control The fan power of the ventilation unit is controlled in multiple steps depending on load and based on the measurement results of the air quality sensors (CO and %H sensors) located in the ventilation zone. The aim is to keep carbon dioxide and/or humidity content below the threshold set at control panel H. It is also possible to select an automatic search for the humidity content threshold at control panel H. One or more modes of control may be used simultaneously the mode demanding boosting is the dominant one. Fan speed varies depending on load between the base and maximum fan speeds. The base and maximum fan speeds can be set at the desired level at the control panel. Voltage signal control The fan power of the ventilation unit is controlled in 8 steps with a voltage signal of VDC. However, fan power cannot be raised above the set maximum fan speed. Voltage signal control is used to control base fan speed. This means that fan speed can be raised when necessary, but not lowered, by the manual, CO and %H controls. Voltage signal values Voltage values for each fan speed: 0 0,0...,5 VDC,75...,5 VDC,75...3,5 VDC 3 3,75...4,5 VDC 4 4,75...5,5 VDC 5 5,75...6,5 VDC 6 6,75...7,5 VDC 7 7,75...8,5 VDC 8 8,75...0,00 VDC Supply air temperature Supply air temperature can be controlled with either constant temperature control or cascade control. Supply air constant temperature control The control unit directs the operation of post-heating unit L on the basis of the measurement data given by temperature sensor TE, aiming at keeping supply air temperature at the temperature value set at control panel H ( ºC). The cooling function of the LV radiator starts when the post-heating radiator has been switched off and supply air temperature exceeds the setpoint for supply air. Supply air cascade control The control unit directs the operation of post-heating unit L on the basis of the measurement data given by extract air sensor TE4, aiming at keeping extract air temperature at the temperature value set at control panel H ( ºC). DESCITION OF OEATION / LV radiator Heat recovery bypass Heat recovery is always active when post-heating is switched on. Automatic heat recovery bypass is active when post-heating is switched off and outdoor temperature exceeds the threshold set (can be set at C). However, heat recover is always active when outdoor temperature is less than the threshold set. Heat recovery antifreezing Controlling preheating in a liquid-circulating LV radiator is different from that in an electric preheating radiator. The liquid radiator switches on based on the measurement data from outdoor air temperature sensor TE3. The control centre of the unit starts the pump and opens the solenoid valve when post-heating is on and outdoor air temperature goes below the setpoint for preheating. The setpoint must be lower than the temperature of the liquid coming from the ground collector. If the capacity of preheating unit L is not sufficient, the control centre keeps stopping supply air fan T on the basis of the measurement data on temperature sensor TE, thus preventing the heat recovery cell from freezing. As soon as the risk passes, the fan restarts automatically. The threshold temperature ( C) and the difference area (...0 C) for antifreezing can be set at control panel H. Heating unit overheat protection (electric post-heating unit) Overheat protection thermostats T and T monitor the surface temperature of heating unit L. When surface temperature exceeds the threshold, overheat protection is triggered and power supply to the heating unit is stopped. Overheat protection T is reset automatically, whereas overheat protection T is reset by switching the unit off. Water radiator freezing protection Based on the measurement data of outdoor temperature sensor TE3 (outdoor air < 0 C) and supply air temperature sensor TE (supply air <7 C) the control centre of the unit stops fans T and and leaves valve V open, thereby decreasing the freezing risk in water circulating heating unit L. A freezing alert appears in the display of the control panel. The fans restart automatically as soon as the risk of freezing passes (supply air > 0 C). Alarms ressure difference switches DS and DS monitor the pressure difference on the supply and extract air sides. If the pressure difference rises too high because of dirty filters or clogged ducts, an alarm will be issued. This is indicated by a symbol ( ) in the main display of the control panel. If the unit is not equipped with pressure difference switches, the symbol ( ) appearing in the main display of the control panel reminds of the need for maintenance of the unit. The reminder interval can be set between...5 months. The factory setting is 4 months. This function is always active. The fault signal relay in the unit gives potential-free alarm indications on the following fault conditions: When the antifreeze function of the water-circulating radiator is on, the contacts of the the relay open and close at 0-second intervals. Alarm of high carbon dioxide content (> 5000 ppm) switches the relay at -second intervals. In other fault situations, such as sensor faults, the contacts of the relay close. Booster or fireplace switch function The booster or fireplace switch function of the ventilation unit is controlled either at control panel H and/or separate switch S, which can be connected to the connection box of the unit. The mode of operation of the switch is selected at control panel H. The booster switch function raises fan speed to the set maximum fan speed for 45 minutes. The fireplace switch stops the extract air fan for 5 minutes and produces overpressure in the ventilation zone. LON remote monitoring control can be implemented with a VALLOX LON converter. See a separate brochure. LV ADIATO CONTOL OST-HEATING OFF OST-HEATING ON TEEATUE SETTING ) 0 C ) INSTUCTIONS FO USE AND AINTENANCE: INSTUCTIONS FO USING CONTOL ANEL 3..6 ) INSTUCTIONS FO USE AND AINTENANCE: INSTUCTIONS FO USING CONTOL ANEL EHEATING SETOINT TEEATUE ) 7 C SULY AI TEEATUE > 0 C SULY AI TEEATUE < 0 C OUTDOO AI TEEATUE < 7 C OUTDOO AI TEEATUE > 7 C COOLING ON COOLING OFF EHEATING ON EHEATING OFF 7

18 INSTALLATION INSTUCTIONS A B E D C A Duct outlets B easurement outlets C Base plate D Nameplate E Lead-in seals Location of condensing water connection odel L in the figure Location of the ventilation unit The unit is mounted indoors, in a place where temperature does not fall below +0 C. The unit is mounted in a place where the sound pressure level coming through the envelope is not acoustically disturbing (storerooms, corridors, technical rooms, and in some cases rooms where people spend time). The unit is equipped with an adjustable base. If the unit is mounted on the wall, attention needs to be paid to the weight of the unit (0 kg) and to vibration isolation. The unit is splash protected (I 34) and can thus also be mounted in a damp room. Electrical connections The unit has a plug connection. The electrical connection box of the unit is located inside the unit next to the connection outlet of the exhaust air ductwork. The cables to be connected to the unit are wired through the lead-in seals located next to the connection outlet of the exhaust air ductwork. Installation emove the door of the unit (latches on top edge). emove the cover of the electrical connection box ( screws 3.5 x 9.5). ount and connect necessary cables to the terminal block as specified in the connection instructions. These instructions include the internal and external electric diagrams. Channel outlets of the unit The unit is equipped with four ø00 external connection outlets. Necessary connecting pieces (e.g. inner or bent connectors) can be attached to external connection outlets. Fix the ducts steadily and tightly to the relevant outlets. (NOTE! Unit models L/). Implement duct insulation if needed as defined in the ventilation plan. Air flow measurement outlets The fixed measurement outlets are located behind the nameplate. Via the measurement outlets, the total pressure of the supply and extract air ductwork can be measured with a differential pressure instrument. ressure readings and the unit s air volume tables (p. 3) show volume air flows at various adjustment positions. The red measurement hose is on the pressure side and the black hose on the suction side of the fan. Condensing water connections The delivery includes a water seal. With a pipe connected to the water seal, water condensing from extract air can be led to a floor drain (not straight to the drain). The pipe must not rise after the water seal. As the condensing water connection is located in the middle of the unit, the unit has to be mounted level with the horizontal. ipe connections If the unit is equipped with a liquid-circulating post-heating or LV preheating /cooling unit, it is connected to the liquid circuit using a plastic or copper pipe with a recommended inner diameter of mm. The outer diameter of the the LV radiator s plastic pipes coming from the unit is mm. Note! When using a plastic pipe pay attention to the temperature stability of the pipe! LV radiator is connected to plastic pipes. When needed, the connections can be reached by taking the heat recovery cell away. The following figures describe different ways of connecting the LV radiator and the VKL post-heating radiator. NOTE! WATE-CICULATING OST-HEATING ADIATO INCLUDES A CONTOL VALVE. 8

19 ADIATO CONNECTIONS Connection of LV preheating/cooling radiator to the ground collector of ground-source heat pump V Y I Y Circulation pump Because of the risk of condensing the pump should be suitable for pumping liquid that is colder than the ambient temperature (e.g. agna 5-60). When choosing a circulation pump, take into account the pressure loss in the whole system. Solenoid valve The valve has to be suitable for the liquid in the ground collector (for example ELV05006, Stig Wahlström). Non-return valve Stop valve Air bleeder Air bleeder is placed after the pump and at the highest point in the network. Non-return valve The pressure loss of the valve has to be lower than that of the heat pump. V I Y Y HEAT U ALWAYS IAILY FOLLOW THE CONNECTION LAN EAED BY THE HVAC LANNE O THE HEAT U ANUFACTUE. LV CICUIT See the adjoining example of connecting an LV unit to the ground collector. The supply pipe of the LV circuit is connected to the pipe returning from the collector. eturn Supply The liquid returning from the LV circuit is taken to the return pipe of the ground collector. GOUND COLLECTO If the internal pressure losses of the heat pump in the ground collector are known to be high, it is recommended to bypass the heat pump. The liquid then circulates when the heat pump is stopped. In this case the pressure loss of the bypass non-return valve has to be lower than that of the heat pump. When the requirements for starting the heating or cooling function are met, the control function of the unit opens the solenoid valve (V) and starts the pump (). The components of the LV circuit mentioned in the diagram are not included in the delivery. Observe the freeze resistance of the liquid used in the ground collector. The connection pipes of the LV radiator have to insulated against condensation. If the heat pump has an open expansion tank, it must be situated at the highest point of the network. Note! Because of the risk of humidity damage, supply air temperature in a duct with no condensation insulation should not go below C. Connection of LV preheating/cooling radiator to ground collector made for the radiator K Circulation pump Because of the risk of condensing the pump should be suitable for pumping liquid that is colder than the ambient temperature (e.g. agna 5-60). When choosing a circulation pump, take into account the pressure loss in the whole system. V Solenoid valve The valve has to be suitable for the liquid in the ground collector (for example ELV05006, Stig Wahlström). I Air bleeder Air bleeder is placed after the pump and at the highest point in the network. U ipe of ground collector (for example plastic pipe 3/0 00 m) VV elief valve ressure gauge K Diaphragm expansion tank L Connector Stop valve The LV radiator is connected to the pipe returning from the ground collector and going to the LV circuit. When the requirements for starting the heating or cooling function are met, the control function of the unit opens the solenoid valve (V) and starts the pump (). The components of the LV circuit mentioned in the diagram are not included in the delivery. The radiator has Ø mm plastic pipes () coated with an oxygen diffusion barrier. Observe the freeze resistance of the liquid used in the ground collector. The connection pipes of the LV radiator have to insulated against condensation. Note! Because of the risk of humidity damage, supply air temperature in a duct with no condensation insulation should not go below C. VV V I L U eturn Supply GOUND COLLECTO 9

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION VALLOX-product code: HVAC code: 358500 L 35850 R 79076 L 79077 R SOUND ATTENUATOR (OPTIONAL) IVALLOX 252 WATER OPERATED POST- HEATING UNIT (OPTIONAL) ELECTRICAL POST-HEATING UNIT (OPTIONAL) ELECTRICAL

More information

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter VALLOX Product Code: 3158400 L 3158410 R SILENCER (OPTIONAL) INSTRUCTIONS FOR USE AND MAINTENANCE WATER CIRCULATED POST-HEATING UNIT (OPTIONAL) ELECTRIC POST-HEATING UNIT (OPTIONAL)) PREHEATER (OPTIONAL)

More information

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION Vallox 50C FFCT.09.79b.8.009 Code 5 VALLOX Code 5 TCHNICAL PCIFICATION For dwelling-specific ventilation upply and extract air ventilation with heat recovery ilent operation nergy-efficient unit; high-efficiency

More information

145SE. Vallox. Operating, maintenance and technical instructions

145SE. Vallox. Operating, maintenance and technical instructions Code 370 Models VALLOX 45 SE R VALLOX 45 SE L Low-energy ventilation unit with heat recovery and demand-controlled automatic melting Vallox.09.600E 7.6.203 Operating, maintenance and technical instructions

More information

096SE. Vallox. Operating, maintenance and technical instructions

096SE. Vallox. Operating, maintenance and technical instructions Vallox Code 3720 Models VALLOX 096 SE R VALLOX 096 SE L Low-energy ventilation unit with heat recovery and demand-controlled automatic melting Vallox.09.602 EN 3.2.203 Operating, maintenance and technical

More information

Manual. Document ENG

Manual. Document ENG Models Vallox TSK Multi 50 MV Vallox TSK Multi 50 MV EH Vallox TSK Multi 80 MV Vallox TSK Multi 80 MV EH Vallox TSK Multi 80 MV EHX (EH = post-heating) (EHX= post-heating and additional heating) Document

More information

121 SE. Vallox. Low-energy ventilation unit with heat recovery. Operating, maintenance and technical instructions

121 SE. Vallox. Low-energy ventilation unit with heat recovery. Operating, maintenance and technical instructions Code A3560 Models VALLOX R VALLOX L Low-energy ventilation unit with heat recovery 1.09.413E 14.5.2013 Operating, maintenance and technical instructions 1 Extract air fan 2 Supply air fan 3 ost-heating

More information

Swegon CASA W130. Ventilation unit with counter-flow plate heat exchanger HOME VENTILATION

Swegon CASA W130. Ventilation unit with counter-flow plate heat exchanger HOME VENTILATION Swegon CASA W130 Ventilation unit with counter-flow plate heat exchanger Ventilation unit for residential houses under 250 m². The unit has counter-flow plate heat exchanger. Suitable also for renovation

More information

Models Vallox 096 MC R Vallox 096 MC L. Document D2609 MANUAL. Valid from Type Updated Manual.

Models Vallox 096 MC R Vallox 096 MC L. Document D2609 MANUAL. Valid from Type Updated Manual. Models Vallox 096 MC R Vallox 096 MC L Type 3721-1 Document D2609 Valid from 24.2.2017 Updated 12.2.201 MANUAL Manual Ventilation unit MAIN PART Extract air fan (behind the protective cover) upply air

More information

Vallox INSTRUCTIONS FOR USE AND MAINTENANCE. Compact. Supply and extract air ventilation with heat recovery

Vallox INSTRUCTIONS FOR USE AND MAINTENANCE. Compact. Supply and extract air ventilation with heat recovery Vallox 1.09.349E 19.5.2009 VALLOX INSTRUCTIONS FOR USE AND MAINTENANCE 70 Compact CODE 3475 Supply and extract air ventilation with heat recovery For blocks of flats, terraced houses and detached houses.

More information

45 Commerce Ave., Unit #2 South Burlington, VT tel: fax:

45 Commerce Ave., Unit #2 South Burlington, VT tel: fax: SMAT ZONE TM VAV Electronic Diffusers SMAT ZONETM www.smartdiffuser.com SMAT ZONE SE-HC/M, Type LT, Lay-in, T-Bar, VAV Fully Modulating Diffuser Specifications APPLICATION: The Model SE-HC/M VAV Smart

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

Swegon CASA R120. Ventilation unit with rotary heat exchanger HOME VENTILATION

Swegon CASA R120. Ventilation unit with rotary heat exchanger HOME VENTILATION Swegon CASA R120 Ventilation unit with rotary heat exchanger Ventilation unit for residential houses, multi-storey buidings and holiday cottages under 230 m 2. The unit is equipped with rotary heat exchanger.

More information

N M AirControl AHU. Control manual

N M AirControl AHU. Control manual N 10.63 M 03-2016 AirControl AHU Control manual EN CONTENTS PAGE 1 - MONITORING AND CONTROL 2 1.1 The program 2 1.2 The HMI terminal 2 1.3 The controller 4 1.4 Description of the air handling units 4

More information

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English Rectifier RC-series Manual RC-series English Manual Wall and 19 English Presentation The RC-series is a rectifier for either directly powering the load or for use together with batteries. It is designed

More information

PM100 Room pressure monitor

PM100 Room pressure monitor Room ressure monitor Product descrition Functional descrition Performance features Product descrition For use as a room ressure controller for rooms in which constant air ressure must be maintained. Clean

More information

panel filters with filtering class G4. Supply filter F7 can be supplied with the few models.

panel filters with filtering class G4. Supply filter F7 can be supplied with the few models. AIR HANDLING UNITS WITH HEAT RECOVERY Series Series VUT 350 PE EC VUT 600 PE EC VUT 1000 PE EC VUT 2000 PE EC VUT 3000 PE EC VUT 600 PW EC VUT 1000 PW EC VUT 2000 PW EC VUT 3000 PW EC Ceiling mounted air

More information

panel filters with filtering class G4. Supply filter F7 can be supplied with the few models.

panel filters with filtering class G4. Supply filter F7 can be supplied with the few models. AIR HANDLING UNITS WITH HEAT RECOVERY Series Series VUT 350 PE EC VUT 600 PE EC VUT 1000 PE EC VUT 2000 PE EC VUT 3000 PE EC VUT 600 PW EC VUT 1000 PW EC VUT 2000 PW EC VUT 3000 PW EC Ceiling mounted air

More information

KOMFORT EC DB Suspended heat recovery air handling units

KOMFORT EC DB Suspended heat recovery air handling units 2018 AIR HANDLING UNITS KOMFORT EC DB Suspended heat recovery air handling units Features Air handling units for efficient supply and exhaust ventilation in flats, houses, cottages and other buildings.

More information

Product is subject to and complies with Regulation (UE) N.327/2011. cert. n Fan Coil Unit Cassette SkyStar Jumbo ECM. technical catalogue

Product is subject to and complies with Regulation (UE) N.327/2011. cert. n Fan Coil Unit Cassette SkyStar Jumbo ECM. technical catalogue cert. n. 0545 Product is subject to and complies with Regulation (UE) N.327/2011 Fan Coil Unit Cassette SkyStar Jumbo ECM technical catalogue SkyStar Jumbo ECM Table of contents SkyStar Jumbo ECM TABLE

More information

Swegon CASA W80 EC, version B

Swegon CASA W80 EC, version B Swegon CASA W80 EC, version B Instructions for Installation, Operation and Maintenance W80B_e_EN-m Contents Instructions for Installation, Operation and Maintenance 1. Important information... 3 2. Quick

More information

THERMOSTATS & CONTROLLERS

THERMOSTATS & CONTROLLERS THETATS & CONTOLLES T70 SEIES POAABLE COEIAL THETATS AND W70 CONTOLLE T70, W70 SEIES DESCIPTION The Honeywell T70 Commercial Programmable Thermostat controls VAC single zone heating, ventilating and air

More information

PRO greenair HP. Ventilation unit with heat recovery and integrated heat pump. Design, installation, and operation instructions

PRO greenair HP. Ventilation unit with heat recovery and integrated heat pump. Design, installation, and operation instructions THE UNIT MUST NOT BE TILTED MORE THAN 45 PRO greenair HP Ventilation unit with heat recovery and integrated heat pump Design, installation, and operation instructions Please read this manual thoroughly

More information

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h PRODUCT DATA COMFORT 5000 BY NILAN Ventilation & passive heat recovery Commercial Passive heat recovery Ventilation < 5300 m 3 /h COMFORT 5000 The Comfort 5000 is a ventilation unit suitable for central

More information

Swegon CASA R85. Ventilation unit with rotary heat exchanger HOME VENTILATION

Swegon CASA R85. Ventilation unit with rotary heat exchanger HOME VENTILATION Swegon CASA R85 Ventilation unit with rotary heat exchanger Ventilation unit for residential houses, multi-storey buidings and holiday cottages under 170 m 2. The unit is equipped with rotary heat exchanger.

More information

VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual

VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual EN Table of Contents 1. INSTALLATION MANUAL...3 1.1. Air Handling Units Sections Connection...3

More information

OVERVIEW and SYSTEM GUIDE. Swegon CASA. Residential ventilation for optimal operating economy and the greatest comfort.

OVERVIEW and SYSTEM GUIDE. Swegon CASA. Residential ventilation for optimal operating economy and the greatest comfort. OVERVIEW and SYSTEM GUIDE Swegon CASA Residential ventilation for optimal operating economy and the greatest comfort. www.swegon.com Swegon your system supplier Supply air diffuser Vapour barrier for duct

More information

Swegon CASA R120. Instructions for installation, operation and maintenance. R120_h_EN-m

Swegon CASA R120. Instructions for installation, operation and maintenance. R120_h_EN-m Swegon CASA R120 Instructions for installation, operation and maintenance R120_h_EN-m Content Instructions for Use For the user Important information... 3 Control from a Premium control panel... 4 Control

More information

Heat Recovery ventilation Dee Fly Cube 550 Field of application Description Advantages Range Technical details Installation Remote controls Servicing

Heat Recovery ventilation Dee Fly Cube 550 Field of application Description Advantages Range Technical details Installation Remote controls Servicing Field of application Description Advantages Range Technical details Installation Remote controls Servicing Remote control ErP * ** Conpliance compliance. ErP ready. Advantages Reversible connections. Ventilation

More information

The new Xcell EC High Efficiency Range Fresh air pure and simple

The new Xcell EC High Efficiency Range Fresh air pure and simple The new Xcell EC High Efficiency Range Fresh air pure and simple The new Xpelair saving energy, saving money 2 www.xpelair.co.uk Introducing the NEW Xpelair Xcell EC High Efficiency range. The Xcell EC

More information

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models:

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models: INSTALLATION, OPERATION AND MAINTENANCE MANUAL BHW MEDIUM STATIC PRESSURE DUCTABLE TYPE Models: 174 205 358 410 515 720 724 Cooling capacities from 3,1 to 25 KW Heating capacities from 4,5 to 55,5 KW Thank

More information

Vallox Oy. manufactures. over LOW POWER EFFICIENCY Specific electrical

Vallox Oy. manufactures. over LOW POWER EFFICIENCY Specific electrical Vallox 150 Effect SE MLV Vallox 150 Effect SE MLV Vallox Oy manufactures Certificate No VTT-C-3514-08 Translation 1 (2) ventilation units Vallox 150 Effect SE MLV (preheating with ground heat) Vallox 150

More information

Healthy, comfortable and energy-efficient ventilation

Healthy, comfortable and energy-efficient ventilation Healthy, comfortable and energy-efficient ventilation partner Renovent Excellent 180, 300 and 400 Silent and energy-efficient ventilation 300/400 180 Central ventilation The Renovent Excellent is a mechanical

More information

Swegon Home Solutions CASA. W9 Smart. Installation, commissioning and maintenance instruction. W9_e_EN-t

Swegon Home Solutions CASA. W9 Smart. Installation, commissioning and maintenance instruction. W9_e_EN-t Swegon Home Solutions CASA W9 Smart Installation, commissioning and maintenance instruction W9_e_EN-t Contents Installation, operation and maintenance instructions for design engineers, installation engineers

More information

VALLOX VENTILATION PRICELIST 2018

VALLOX VENTILATION PRICELIST 2018 VALLOX VENTILATION PRICELIST 2018 1.1.2018 VENTILATION SYSTEM YOUR BEST LIFE INSURANCE Good ventilation is an important investment in the health of the house and its inhabitants, and also affects the lifespan

More information

Series. Suspended air supply units with the air capacity up to 4100 m 3 /h in the sound- and heat-insulated casing with the water heater

Series. Suspended air supply units with the air capacity up to 4100 m 3 /h in the sound- and heat-insulated casing with the water heater SUPPLY UNITS Series VENTS PA E Series VENTS PA W A13 control panel A13 control panel Suspended air supply units with the air capacity up to 3350 m 3 /h in the sound- and heat-insulated casing with the

More information

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h PRODUCT DATA COMFORT 40 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 40 m /h COMFORT 40 Product description The Comfort 40 is an energy-efficient ventilation

More information

MAXI CENTRALIZED VENTILATION WITH HEAT RECOVERY

MAXI CENTRALIZED VENTILATION WITH HEAT RECOVERY MAXI CENTRALIZED VENTILATION WITH HEAT RECOVERY Product Overview www.orcaenergy.eu MAXI Device for heat recovery MAXI is designed to provide permanent controlled air exchange by means of mechanical ventilation

More information

LER kw. Indoor motor-driven evaporating units. Motor-driven evaporating units LER PLUS

LER kw. Indoor motor-driven evaporating units. Motor-driven evaporating units LER PLUS Indoor motor-driven evaporating units LER 0-0 kw Compact and silent machines with remote dissipation into the air Scroll compressor PLUS R-0A R-0A refrigerant Cooling only Split version Electronic expansion

More information

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction Air Comfort Air Treatment Energy Recovery eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction eco PREMIUM - Technical Instruction REDA 2 Contents Description Applications... 3 Quality & environment...

More information

PRODUCT DATA COMFORT 600 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 800 m 3 /h

PRODUCT DATA COMFORT 600 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 800 m 3 /h PRODUCT DATA COMFORT 00 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 800 m /h COMFORT 00 Product description The Comfort 00 is an energy-efficient ventilation

More information

DUCTIMAX 2-8 kw. Medium available static pressure ducted hydronic units. Duct unit DUCTIMAX

DUCTIMAX 2-8 kw. Medium available static pressure ducted hydronic units. Duct unit DUCTIMAX Duct unit DUCTIMAX Medium available static pressure ducted hydronic units DUCTIMAX - 8 kw NEW PRODUCT JUNE 05 Performance and compactness in recessed ceiling installations ERGO Supervision Plus -pipe system

More information

Framework is anodised aluminium with airtight door seals and manual door catches which can be tool locked in position.

Framework is anodised aluminium with airtight door seals and manual door catches which can be tool locked in position. VMD Range Features & Benefits Performance range up to.4m /s Motor Insulation Class F Anodised aluminium pentapost frame Double skinned panels Compact direct drive units Electric heater battery Built-in

More information

Air handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses

Air handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses REC Temovex 4S-EC-RS Experts on indoor climate in low-energy houses RT 4S-EC-RS REC Temovex 4S-EC-RS ECO2 control system for low-energy and passive houses Comprises: - Air flow boost for warm and cold

More information

Ventilation Unit Zehnder ComfoAir 350

Ventilation Unit Zehnder ComfoAir 350 Use The ComfoAir 350 ventilation unit was developed for residential and small commercial buildings. It combines maximum comfort, simple operation and very high efficiency. The CA350 moves up to 218 cfm

More information

IN LINE MIXED FLOW DUCT FANS AND ELECTRIC HEATER TD-MIXVENT HEATING System

IN LINE MIXED FLOW DUCT FANS AND ELECTRIC HEATER TD-MIXVENT HEATING System HEATING System fan (from model 25) and a MBE electric heater installed on the discharge side of the fan. + MBE ELECTRIC HEATER MBE heater type - Insulated element rods. - Automatic overheat thermostat

More information

MRXBOXAB-ECO3 MRXBOX-ECO3

MRXBOXAB-ECO3 MRXBOX-ECO3 NUAIRE MVHR MRXBOX-ECO3 and Opposite Handed versions ACHIEVES 100% DUTY IN BYPASS MODE The has been designed with automatic 100% bypass as listed on the SAP Product Characteristics Database (PCDB). Due

More information

MRXBOXAB-ECO2 MRXBOX-ECO2

MRXBOXAB-ECO2 MRXBOX-ECO2 NUAIRE MVHR MRXBOX-ECO2 and Opposite Handed versions ACHIEVES 100% DUTY IN BYPASS MODE The has been designed with automatic 100% bypass as listed on the SAP Product Characteristics Database (PCDB). Due

More information

Heating controller with optimisation functions

Heating controller with optimisation functions TAC 2112 C-10-42 Heating controller with optimisation functions 1999.12 The TAC 2112 offers for control of hot water systems. The radiator circuit is controlled according to an outdoor -compensated reset

More information

Series VUT PW EC. wool internal heat and sound-insulating layer for VUT PE/PW 350, 600, 1000 units and 50 mm for VUT PE/PW 200, 3000 units.

Series VUT PW EC. wool internal heat and sound-insulating layer for VUT PE/PW 350, 600, 1000 units and 50 mm for VUT PE/PW 200, 3000 units. AIR HANDLING UNITS WITH HEAT RECOVERY Series VUT PE EC Series SAS908 control panel SAS908 control panel Ceiling mounted energy saving Air Handling Units (AHU) with the air capacity up to 4000 m 3 /h and

More information

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery. PRODUCT DATA COMPACT P - SERIES BY NILAN Domestic Passive heat recovery Active heat recovery Ventilation < 300 m 3 /h Comfort heating Comfort cooling Sanitary hot water production Heating THE VENTILATION

More information

Compact Horizontal Air-Air Heat Pump Model RTH 07L to 30L. Technical information. Ref.: N

Compact Horizontal Air-Air Heat Pump Model RTH 07L to 30L. Technical information. Ref.: N Compact Horizontal Air-Air Heat Pump Model RTH 07L to 30L Ref.: N-27661 0608 Technical information Johnson Controls Manufacturing España, S.L. is participating in the EUROVENT Certification Program. Products

More information

Packaged air conditioning unit condensed by air model RTC 07L to 30L. Technical information. Ref.: N

Packaged air conditioning unit condensed by air model RTC 07L to 30L. Technical information. Ref.: N Packaged air conditioning unit condensed by air model RTC 07L to 30L Ref.: N-27656 0608 Technical information Johnson Controls Manufacturing España, S.L. is participating in the EUROVENT Certification

More information

HCompact2 HA. Compact air-air stand-alone units. Compact horizontal Reduced dimensions Centrifugal fans RANGE DESCRIPTION OPERATING LIMITS SERIES

HCompact2 HA. Compact air-air stand-alone units. Compact horizontal Reduced dimensions Centrifugal fans RANGE DESCRIPTION OPERATING LIMITS SERIES Cooling capacity: Heating capacity: 7,0 to 36,8 kw 8,7 to 40,1 kw Compact horizontal educed dimensions Centrifugal s Ducted aspiration and discharge DESCPTON The heat pumps and cooling unit are compacts

More information

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories > HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION Available range Unit type IP Reversible heat pump (reversible on the refrigerant side) ECO-FRIENDLY REFRIGERANT GAS Versions (heat recovery) VB Base

More information

Heating / Air Conditioning Energy Heat Recovery Units ENVIRONMENTAL COMFORT

Heating / Air Conditioning Energy Heat Recovery Units ENVIRONMENTAL COMFORT Heating / Air Conditioning Energy Heat Recovery Units ISO 9001 - Cert. n 0545/4 Unit heaters Radiant panels Fan coils Air handling units Flues ENVIRONENTAL COFORT Heating Air Conditioning ENVIRONENTAL

More information

- Data Brochure Boiler Control 274

- Data Brochure Boiler Control 274 - Data Brochure Boiler Control 274 274_D 03/17 The Boiler Control 274 operates up to four on/off boilers to provide outdoor reset operation, domestic hot water and setpoint operation with priority. When

More information

MRXBOXAB-ECO-LP1 100% Typical Installation. (including opposite handed versions)

MRXBOXAB-ECO-LP1 100% Typical Installation. (including opposite handed versions) NUAIRE MVHR (including opposite handed versions) ACHIEVES 100% DUTY IN BYPASS MODE and MRXBOXAB- ECO-LP1-OH are specically designed for apartment applications where space is a premium. The new MRXBOX95-LP1

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA OUTDOOR AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA DR_AS049EF_02 2017.10.11 Notices: Product

More information

for a considerable reduction of the supply air temperature which, in turn, reduces the air conditioning

for a considerable reduction of the supply air temperature which, in turn, reduces the air conditioning AIR HANDLING UNITS WITH HEAT RECOVERY Series VENTS enthalpy membrane in the warm season. This allows for a considerable reduction of the supply air temperature and humidity which, in turn, reduces the

More information

Renovent Excellent 180 (Plus)

Renovent Excellent 180 (Plus) Renovent Excellent 180 (Plus) INSTALLATION INSTRUCTIONS (English) WWW.BRINKAIRFORLIFE.NL 614293-D Installation instructions Heat recovery appliance Renovent Excellent 180 (Plus) STORE NEAR THE APPLIANCE

More information

Entwicklung + Fertigung + Service: Heerweg 15 D, Denkendorf Tel.: / Fax.: /

Entwicklung + Fertigung + Service: Heerweg 15 D, Denkendorf Tel.: / Fax.: / Planungsbüro + Service: Esteraustr. 10, 56379 Holzappel Tel.: 0 64 39 / 90 19 90 Fax.: 0 64 39 / 90 19 91 E-Mail: u.ramakers@umsitec.de Entwicklung + Fertigung + Service: Heerweg 15 D, 73770 Denkendorf

More information

APC BC300 Series 40kW 208/450/480V User Guide

APC BC300 Series 40kW 208/450/480V User Guide APC BC300 Series 40kW 208/450/480V User Guide Copyright 2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor Thank You Thank

More information

Datasheet: K-22 LO Sensor

Datasheet: K-22 LO Sensor Datasheet: K-22 LO Sensor The K- 22 LO is a CO2 sensor module designed to be built- in into stationary ventilation equipment, such as window vent or duct exhaust actuators, serving as a linear transmitter

More information

23 October Enervent Neo. Ventilation unit installation instructions

23 October Enervent Neo. Ventilation unit installation instructions 23 October 2017 Enervent Neo Ventilation unit installation instructions Copyright Enervent 2017. Unauthorised copying and distribution is forbidden. 2 CONTENTS READ FRST...4 Type plate...5 SAFETY...6 General...6

More information

Air heater/cooler in combination with ground source heat pump

Air heater/cooler in combination with ground source heat pump Swegon CASA Air heater/cooler in combination with ground source heat pump Installation, operation and maintenance instructions for design engineers, installation engineers and service personnel SDHWM_c_EN

More information

Automatic Digital Humidifier Control

Automatic Digital Humidifier Control Automatic Digital umidifier Control Safety and Installation Instructions EAD COMPLETE INSTALLATION INSTUCTIONS AND TEMPLATE BEFOE STATING. WANING ATTENTION INSTALLE: This product must be installed by a

More information

Swegon Home Solutions CASA. R2 Smart. Installation, commissioning and maintenance instruction. R2_a_EN-t

Swegon Home Solutions CASA. R2 Smart. Installation, commissioning and maintenance instruction. R2_a_EN-t Swegon Home Solutions CASA R2 Smart Installation, commissioning and maintenance instruction R2_a_EN-t Contents Technical Guide for design engineers, installation engineers and service personnel The section

More information

Suxess Compact Top HEALTHY INDOOR ENVIRONMENT WITH ENERGY EFFICIENT VENTILATION

Suxess Compact Top HEALTHY INDOOR ENVIRONMENT WITH ENERGY EFFICIENT VENTILATION Suxess Compact Top HEALTHY INDOOR ENVIRONMENT WITH ENERGY EFFICIENT VENTILATION Quality and performance with skills and tradition Suxess is based in Enköping, Sweden, where we both develop and produce

More information

Heat recovery unit RDKS

Heat recovery unit RDKS Heat recovery unit RDKS Heat recovery unit RDAS is based on our RDAR unit and develops this further. The unit has a rotary heat exchanger with stepless speed control. This allows for very precise temperature

More information

Swegon Home Solutions CASA. W3 Smart. Installation, commissioning and maintenance instruction. W3_f_EN-t

Swegon Home Solutions CASA. W3 Smart. Installation, commissioning and maintenance instruction. W3_f_EN-t Swegon Home Solutions CASA W3 Smart Installation, commissioning and maintenance instruction W3_f_EN-t Contents Installation, operation and maintenance instructions for design engineers, installation engineers

More information

INSTALLATION AND USER MANUAL

INSTALLATION AND USER MANUAL INSTALLATION AND USER MANUAL t Thank you for choosing Aqua inverter heat pump. This manual provides you necessary information for optimal use and maintenance, please read it carefully and keep it for subsequent

More information

VEX250H with rotary heat exchanger and EXact control system

VEX250H with rotary heat exchanger and EXact control system 3003433-2014-04-11 VEX250_EXact VEX250H with rotary heat exchanger and EXact control system Unit supplied with (factory fitted): Compact filter FP Filter bag FB Trim damper and blowout zone,tb250 The following

More information

HRU-MinistAir-W-450. Elementy dachowe. Heat recovery units. Dimensions. Description. Control. ALNOR systemy wentylacji

HRU-MinistAir-W-450. Elementy dachowe. Heat recovery units. Dimensions. Description. Control. ALNOR systemy wentylacji Heat recovery units -W-450 Dimensions 160 710 725 797 Elementy dachowe Description The -W-450 heat recovery unit is designed for single-family houses up to 200 m 2 in usable floor area. 610 630 Key performance

More information

CHAPTER 4. HVAC DELIVERY SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer

More information

TSEK VHR EC HEAT RECOVERY UNITS

TSEK VHR EC HEAT RECOVERY UNITS TSEK EC HEAT RECOVERY UNITS TS EN ISO 9001:2008 SN: 01 100 901925 General Information TSEK VENCO Heat Recovery Ventilation Units () are designed for saving energy and also improving indoor air quality.

More information

SINGLE-ROOM VENTILATION. for schools and public spaces

SINGLE-ROOM VENTILATION. for schools and public spaces SINGLE-ROOM VENTILATION for schools and public spaces Industrial and commercial ventilation (Catalogue no. 1) Industrial and commercial ventilation components - fans for round and rectangular ducts, sound-insulated,

More information

Description of the functions, IQlogic

Description of the functions, IQlogic , IQlogic General Control...168 Status...168 IQnavigator hand-held terminal and image management...169 Dashboard...169 Main setup...170 Air flow Regulation mode...171 Boost...171 Unit...171 Air adjustment...171

More information

Healthy, comfortable and energy-efficient ventilation

Healthy, comfortable and energy-efficient ventilation Healthy, comfortable and energy-efficient ventilation 300/400/450 180 Renovent Excellent 180, 300, 400 and 450 Silent and energy-efficient ventilation Central ventilation The Renovent Excellent is a mechanical

More information

ACTIVA SERIES ROOF TOP Air Conditioners 017/040

ACTIVA SERIES ROOF TOP Air Conditioners 017/040 ACTIVA SERIES ROOF TOP Air Conditioners 017/040 Installation manual Ref.: N-40388_EN 0112 Index Index 1 Installation manual...1 1.1 Safety instructions...2 1.2 Icons used in this document...2 1.3 Instructions

More information

KOMFORT EC S5B KOMFORT EC D5B KOMFORT EC S. Heat and Energy Recovery Ventilators

KOMFORT EC S5B KOMFORT EC D5B KOMFORT EC S. Heat and Energy Recovery Ventilators KOMFORT EC S5B KOMFORT EC D5B KOMFORT EC S Heat and Energy Recovery Ventilators 2018 AIR HANDLING UNITS 2 CONTENT KOMFORT EC S5B270(-E) 4 KOMFORT EC D5B1(-E) 8 KOMFORT EC S(B)(-E) 12 AIR HANDLING UNITS

More information

CASA. W5 Smart. Installation, commissioning and maintenance instructions. W5_d_EN-t

CASA. W5 Smart. Installation, commissioning and maintenance instructions. W5_d_EN-t CASA W5 Smart Installation, commissioning and maintenance instructions W5_d_EN-t Contents Installation, operation and maintenance instructions for design engineers, installation engineers and service personnel

More information

TURBO HOODS. Product Brochure

TURBO HOODS. Product Brochure TURBO HOODS Product Brochure TABLE OF CONTENTS FUNCTIONING PRINCIPLE... 04 PRODUCT CODE... 0 PRODUCT STRUCTURE... 06 TURBOSWING GREASE FILTER... 07 EXHAUST AIR... 08 SUPPLY AIR... 09 LIGHTS... 0 DIENSIONS...

More information

DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION

DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION DX SYSTEM HEAT RECOVERY ENHANCED BY DEMAND CONTROLLED VENTILATION 2 AERECO DX system DX SYSTEM A COMPLETELY NEW HEAT RECOVERY VENTILATION RANGE With the experience of a very innovative room-by-room demand

More information

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20 INSTALLATION, OPERATION AND MAINTENANCE Ariterm Hybrid 20 TABLE OF CONTENTS General...3 Installation... 4-5 Dimensions - with flue gas exhauster...6 Dimensions - without flue gas exhauster...7 Pipe installations...8

More information

Energy recovery unit. Projection documents

Energy recovery unit. Projection documents Energy recovery unit Projection documents 1. Technical charakteristics 1.1. Function and uses The energy recovery unit Futura is a device designed for controlled ventilation and interior adjustment of

More information

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE CAS Product Specifications Single stage cooling capacity control on all models with Micro channel

More information

"WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use

WHHR125DC Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use "WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor Installation, Operating and Maintenance Instructions domestic and commercial use Page 2 Contents Section Page Number Introduction 3 How

More information

AIR HEATING UNIT HEATMASTER ACJB INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS

AIR HEATING UNIT HEATMASTER ACJB INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS AIR HEATING UNIT HEATMASTER ACJB INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS 2 Air Heating unit ACJB - Technical manual CONTENTS OPERATION AND MAINTENANCE (FOR USER) System, functions, main components...3

More information

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10 Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW Compressors Scroll Serie: Series: Emissione: Issue: SCAEY Catalogo: Leaflet: Sostituisce: Supersedes: DE 88 04/11 12/10 Index

More information

INSTALLATION/OPERATING INSTRUCTIONS HEAT-TROL Elite Series. HWE-Motorized Valve

INSTALLATION/OPERATING INSTRUCTIONS HEAT-TROL Elite Series. HWE-Motorized Valve INSTALLATION/OPEATING INSTUCTIONS HEAT-TOL Elite Series HWE-Motorized Valve How Water eset Control with Setback and Boost For Motorized Valve Operation The HWE-Motorized Valve (HWE-MOV) establishes ambient

More information

UV-TURBO HOODS. Product Brochure

UV-TURBO HOODS. Product Brochure UV-TURBO HOODS Product Brochure TABLE OF CONTENTS FUNCTIONING PRINCIPLE... 0 PRODUCT CODE... 0 PRODUCT STRUCTURE... 06 UV-TURBO GREASE FILTER... 07 EXHAUST AIR... 08 SUPPLY AIR... 09 LIGHTS... 0 DIENSIONS...

More information

STR-600 Impact Dryer

STR-600 Impact Dryer STR-600 Impact Dryer 1. STR-600 Main Features The STR-600 is designed for moisture damage drying of targeted areas. The device can be used for drying various stone-based materials, such as concrete, brick

More information

ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller

ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller PB_ER65-DRW_ 202 ER65-DRW Controller Heating Applications Product Bulletin The controller is a digital device for domestic or residential heating units. It covers water and air heating applications. All-in-one

More information

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers Self-adjusting electronic control Cooling capacity: 35 to 700 kw 410A Cooling Operation DYNACIAT - DYNACIAT POWER

More information

VEX100 series Air handling units with cross-flow heat exchanger

VEX100 series Air handling units with cross-flow heat exchanger Product information - Version 6 VEX100 series Air handling units with cross-flow heat exchanger VEX140: 400-2200 m 3 /h VEX150: 700-3600 m 3 /h VEX160: 1100-5000 m 3 /h VEX170: 1400-8400 m 3 /h Contents

More information

Digital Inverter 4 series 8 & 10HP

Digital Inverter 4 series 8 & 10HP E6-H Digital Inverter 4 series 8 & 0HP High static duct type Indoor unit RAV-SM2244DTP-E RAV-SM2804DTP-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E Contents. Line up... 2. Indoor unit (High static duct

More information

Installation, operation and care Wall-mounted electric boiler MP THL nr. - rev 02

Installation, operation and care Wall-mounted electric boiler MP THL nr. - rev 02 Installation, operation and care Wall-mounted electric boiler MP 4 150206 THL nr. - rev 02 Contents Notes... 3 Safety and handling... 4 Operation... 5 Technical data... 6 Pipe installation... 8 System

More information

Installer Manual KNX Touchscreen Thermostat

Installer Manual KNX Touchscreen Thermostat Installer Manual 02952 KNX Touchscreen Thermostat Index GENERAL FEATURES AND FUNCTIONALITY from page 5 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 7 COMMUNICATION OBJECTS GENERAL FEATURES AND FUNCTIONALITY

More information

Sentinel Kinetic MVHR RANGE

Sentinel Kinetic MVHR RANGE V:\Technical\ARTWORK\Fitting & Wiring\Word Files COMPLETE\442073 W.doc Sentinel Kinetic MVHR RANGE User Instructions Stock Ref. N 438342 Kinetic V 438222 Kinetic B Right 438222L Kinetic B Left 443319 Kinetic

More information