Electrical Systems Existing Conditions and Building Load Summary Broadway Plaza, Rochester, MN. Appendix A
|
|
- Milton Dixon
- 5 years ago
- Views:
Transcription
1 Appendix A Single Line Diagram Power Riser Diagram Dimming System Schematic Diagrams Dry-Type Transformer Schedule Primary Lamp and Ballast Table Mechanical Equipment Table Utility Rate Structure Breakdown
2
3
4 Dimming System Schematic Diagrams
5 Dry-Type Transformer Schedule
6 Primary Lamp and Ballast Table *Power Factor of lamp ballast is taken into consideration for current (A) calculation. Tag Lamp Lamp Ballast Power Input Current Ballast Voltage Watts Factor Factor Watts (A) DLI 150PAR/FL/STG 150 NA NA NA EX1 LED/INCLUDED 10 NA NA NA EX2 LED/INCLUDED 10 NA NA NA EX3 LED/INCLUDED 10 NA NA NA EX4 LED/INCLUDED 10 NA NA NA EX5 LED/INCLUDED 10 NA NA NA EX6 LED/INCLUDED 10 NA NA NA FC1 F40/30BX/SPX30 40 DIM-ELECTRONIC FC2 F54W/T5/830/HO 54 ELECTRONIC FC3 F54W/T5/830/HO 54 DIM-ELECTRONIC FC4 F40/30BX/SPX30 40 ELECTRONIC FD1 F26DBX/SPX30/4P 26 ELECTRONIC FD2 F32TBX/SPX30/A/4P 32 ELECTRONIC FD3 F18DBX/SPX30/4PLR 18 ELECTRONIC FD4 F18DBX/SPX30/4PLR 18 ELECTRONIC FD5 F32TBX/SPX30/A/4P 32 ELECTRONIC FD6 F32TBX/SPX30/A/4P 32 DIM-ELECTRONIC FD7 F32TBX/SPX30/A/4P 32 DIM-ELECTRONIC FD8 F18DBX/SPX30/4PLR 18 ELECTRONIC FP1 F32T8/SPX30/ECO 32 ELECTRONIC FP2 F32T8/SPX30/ECO 32 ELECTRONIC FS1 F32T8/SPX30/ECO 32 ELECTRONIC FS2 F32T8/SPX30/ECO 32 ELECTRONIC FS3 F32T8/SPX30/ECO/GVG 32 ELECTRONIC FS4 F32T8/SPX30/ECO 32 ELECTRONIC FS5 F32T8/SPX30/ECO 32 ELECTRONIC FS6 F32T8/SPX30/ECO 32 ELECTRONIC FS7 F32T8/SPX30/ECO 32 ELECTRONIC FS8 F32T8/SPX30/ECO 32 ELECTRONIC FT1 F32T8/SPX30/ECO 32 ELECTRONIC FT2 F40/30BX/SPX30 40 ELECTRONIC FT3 F32T8/SPX30/ECO 32 ELECTRONIC FT4 F40/30BX/SPX30 40 ELECTRONIC FT5 F32T8/SPX30/ECO 32 ELECTRONIC FT6 F40/30BX/SPX30 40 ELECTRONIC FWB1 F32T8/SPX30/ECO 32 ELECTRONIC FWS1 F54W/T5/830/HO 54 DIM-ELECTRONIC FWS2 F40/30BX/SPX30 40 ELECTRONIC FWW1 F26DBX/SPX30/4P 26 ELECTRONIC FWW2 F26DBX/SPX30/4P 26 DIM-ELECTRONIC FWW3 F40/30BX/SPX30 40 DIM-ELECTRONIC IC1 Q150T3/CL 150 NA NA NA ID1 Q50MR16/NSP/CG 50 LOW-VTG-MAG. 120/12 NA MHD1 CMH70/U/830/MED 70 ELECTRONIC MHD2 CMH70/U/830/MED 70 ELECTRONIC MHD3 MVR175/U/MED 175 CWA MHD4 MVR175/U/MED 175 CWA P1 100A/IF 100 NA NA NA P2 100A/IF 100 NA NA NA P3 HPS70/ECO 70 MAGNETIC S1 F13BX/SPX30/ ELECTRONIC S2 INCLUDED NA NA NA NA S3 F32TBX/SPX30/A/4P 32 ELECTRONIC S4 100A/IF 100 NA NA NA S5 LU100/MED-Q100DC 100 ELECTRONIC S6 LU100/MED 100 ELECTRONIC UC1 F13/T5/ ELECTRONIC WP1 100A/IF 100 NA NA NA WS1 40A/CL 40 NA NA NA WS2 60A/IF 60 NA NA NA WS3 F13BX/SPX30/ ELECTRONIC WS4 F24/T12/SP41/AC DEG. MAGNETIC WS5 Q75CL/MC 75 NA NA NA WS6 F13DBX/SPX30/4P 13 ELECTRONIC WS7 F24/T12/SP41/AC DEG. MAGNETIC CMH/70PAR30L/830L 70 ELECTRONIC WS8 F27BX/SPX30/RS 27 ELECTRONIC TR1 TRACK LOW-VTG-MAG. 120/ TR1-a Q50MR16/C/CG15 50 REMOTE:SEE ABOVE NA TR1-b Q20MR16/C/CG40 20 REMOTE:SEE ABOVE NA
7 Mechanical Equipment Table Tag Description HP or kw Voltage Current Switch Fuse Size Phase Emerg. Type (A) Size (A) (A) VA kva ACU-1 Elev. Mach. Rm. Condenser 1/ X D ACU-2 Elev. Mach. Rm. Condenser 1/ X D ACU-3 Air Cooled Condenser 1/ X D ACU-4 Air Cooled Condenser 1/ D ACU-5 Air Cooled Condenser 0.087kW X D ACU-6 Air Cooled Condenser 1/ X D AH-1 Elev. Mach. Rm. AC Fan 3/ X D Electric Heat 3.0kW AH-2 Elev. Mach. Rm. AC Fan 1/ X D Electric Heat 3.0kW AH-3 Air Conditioning Handler 1/ X D Electric Heat 3.0kW AH-4 Air Conditioning Handler 0.045kW D AH-5 Air Conditioning Handler 0.035kW X D AH-6 Air Conditioning Handler 1/ X D Electric Heat 3.0kW AHU-1 Function Rm. Air Handler C AHU-2 Fitness Air Handler C AHU-3 Air Handler C BCP-1 Boiler Circulating Pump C BCP-2 Boiler Circulating Pump C BCP-3 Boiler Circulating Pump C BS-1 Domestic Booster Pumps J CH-1 Chiller 164kW J CH-2 Chiller 164kW J CHWP-1 Chilled Water Pump C CHWP-2 Chilled Water Pump C CP-1 Condensate Pump 1/ J CT-1 Cooling Tower Fans J Cooling Tower Sump Heater 24kW X J CUH-1 Cabinet Unit Heater 1/ S CUH-2 Cabinet Unit Heater 1/ S CUH-3 Cabinet Unit Heater 1/ S CUH-4 Cabinet Unit Heater 1/ S CUH-5 Cabinet Unit Heater 1/ S CUH-6 Cabinet Unit Heater 1/ S CUH-7 Cabinet Unit Heater 1/ S CUH-8 Cabinet Unit Heater 1/ S CUH-9 Cabinet Unit Heater 1/ S CUH-10 Cabinet Unit Heater 1/ S CWP-1 Condensate Water Pump C CWP-2 Condensate Water Pump C EBB-1 Electric Baseboard Heater 3.75kW J EBB-2 Electric Baseboard Heater 3.375kW J EBB-3 Electric Baseboard Heater 2.25kW J EBB-4 Electric Baseboard Heater 0.3kW J EBB-5 Electric Baseboard Heater 0.75kW J EDH-1 Electric Duct Heater 27kW D EF-1 Garage Ventilation Fan X C EF-2 Generator Rm. Exhaust Fan 0.494kW S EF-3 Exhaust Fan 0.029kW S EF-4 Exhaust Fan S EF-5 Exhaust Fan 0.105kW S EF-6 Exhaust Fan 0.105kW S EF-7 Exhaust Fan 1/ S EF-8 Exhaust Fan 3/ C EF-9 Exhaust Fan 3/ C ELEV. 1 Passenger Elevator X D ELEV. 2 Passenger Elevator X D ELEV. 3 Passenger Elevator X D ELEV. 4 Freight Elevator X D ELEV. 5 Passenger Elevator X D EUH-1 Generator Rm. Unit Heater 35kW J EUH-2 Electric Unit Heater 3.0kW J
8 Mechanical Equipment Table Tag Description HP or kw Voltage Current Switch Fuse Size Phase Emerg. Type (A) Size (A) (A) VA kva FCU-1 Fan Coil Unit S FCU-2 Fan Coil Unit S FCU-3 Fan Coil Unit S FCU-4 Fan Coil Unit S FCU-5 Fan Coil Unit S FCU-6 Fan Coil Unit S FCU-7 Fan Coil Unit S FCU-8 Fan Coil Unit S FCU-9 Fan Coil Unit S FCU-10 Fan Coil Unit S FCU-11 Fan Coil Unit S FCU-12 Fan Coil Unit S FCU-12 Fan Coil Unit S FP-1 Fire Pump X J JP-1 Jockey Pump X J FV-1 Water Heater Vent Fan D FV-2 Boiler Vent Fan D HCP-1 Hot Water Circ Pump 1/ J HRP-1 Heat Recovery Pump C HRP-2 Heat Recovery Pump C HWP-1 Hot Water Pump C HWP-2 Hot Water Pump C KEF-1 Kitchen Exhaust Fan X C KEF-2 Kitchen Exhaust Fan X C MUA-1 Make-up Air Handler X C PDU-1 Pool Dehumidification Unit 7.1kW D SE-1 Sewage Ejector C SEF-1 Smoke Exhaust Fan X C SP-1 Stair Pressurization Fan X C SP-2 Stair Pressurization Fan X C SS-1 Sump Pump System X C TEF-1 Toilet Exhaust Fan X C TEF-2 Toilet Exhaust Fan X C TSH-1 Toe Space Heater 0.750kW J CFP-1 Chemical Feed Pump C CFP-2 Chemical Feed Pump C CFP-3 Chemical Feed Pump C CFP-4 Chemical Feed Pump C CFP-5 Chemical Feed Pump C RF-1 Function Rm. Relief Fan 1/ Total kva Key D C J S Description Fused Disconnect Switch Comb. Starter / Fused Disconnect Switch Single Connection to Equip. Controller 120V Convenience Switch in Junction Box on outside of Equipment.
9 ROCHESTER PUBLIC UTILITIES RATE SCHEDULE MGS (RPU) SHEET 1 OF 2 MEDIUM GENERAL SERVICE AVAILABILITY: At all locations for loads where the demand is at least 75 kw or more for three or more billing periods in a given calendar year, but less than 1,000 kw, and where facilities of adequate capacity and suitable voltage are adjacent to the premises to be served. For loads where the service desired by the customer is not adjacent to the premises to be served, additional contract arrangements may be required prior to service being furnished. APPLICATION: To commercial, industrial, and governmental customers with all service taken at one point and measured through one meter. Also applicable to temporary service in accordance with RPU's published Electric Service Rules and Regulations. Not applicable to standby service. CHARACTER OF SERVICE: Single or three phase, 60 Hertz, alternating current at any one of the standard secondary service voltages as described in RPU's published Electric Service Rules and Regulations. RATE: Non-Summer Summer Demand Charge: $ per kw $ per kw Energy Charge: per kwh per kwh Rural Demand Charge: $ per kw $ per kw Rural Energy Charge: per kwh per kwh Definition of Season: Summer months are June through September. Non-summer months are January through May and October through December. PURCHASED POWER ADJUSTMENT CLAUSE: Bills computed under this rate schedule are subject to adjustment in accordance with the Purchased Power Adjustment Clause (PPAC). POWER FACTOR ADJUSTMENT: The customer agrees to maintain an average power factor of 0.95 or greater for the billing period and to prevent a leading power factor. If the customer's average power factor is less than 0.95 for the billing period, the billing demand will be determined by multiplying the measured demand by 0.95 and dividing the results by the customer's average power factor. The average power factor is defined to be the quotient obtained by dividing the kwh used during the month by the square root of the sum of the squares of the kwh used and the lagging reactive kilovoltampere-hours supplied during the same period. The customer's average power factor will be determined by means of permanently installed meters. PRIMARY METER DISCOUNT: Customers approved for metering at 13.8 kv will receive a discount of 1.25% on base rate charges for measured demand and energy.
10 ROCHESTER PUBLIC UTILITIES RATE SCHEDULE MGS (RPU) SHEET 2 OF 2 MEDIUM GENERAL SERVICE (Cont.) TRANSFORMER OWNERSHIP CREDIT: Customers owning transformers will receive a credit of $.20 per kw on each month's measured demand. SURCHARGE: Customers whose service is taken outside the Rochester City limits are subject to a 10% surcharge on their bills (excluding charges computed under the Purchased Power Adjustment Clause). DETERMINATION OF DEMAND: Measured demand is defined as the maximum rate at which energy is used for any period of fifteen consecutive minutes during the billing period. The billing demand shall be the greater of the measured demand for the billing period adjusted for power factor, or 75% of the maximum measured demand for the most current June - September months adjusted for power factor. MINIMUM BILL: The minimum bill shall not be less than the billing demand, as provided above, whether or not energy is used. PAYMENT: Payments are due on or before the due date. CONDITIONS OF DELIVERY: 1. Service furnished under this rate schedule is subject to applicable provisions of RPU's published Electric Service Rules and Regulations. 2. Unless authorized by separate written agreement, standby electric generating equipment installed by the customer shall not be interconnected or operated in parallel with the RPU system. Customer shall own, install, operate, and maintain electrical interlocking equipment, which will prevent parallel operation, and such equipment shall be approved by RPU prior to installation. 3. RPU shall not be liable for any damage or loss sustained by customer resulting from interruptions, deficiencies, or imperfections of service provided under this rate. 4. Energy furnished under this rate shall not be resold. Approved by Rochester Public Utility Board: December 30, 2003 Effective Date: January 6, 2004
Executive Summary. CNBC Global Headquarters Christine Cajilig
Executive Summary This report contains an analysis and description of the existing electrical distribution of the including the distribution type, emergency power, uninterruptible power system, over current
More informationNovember 11, City of Sparks 215 S. 21 st St. Sparks, NV
November 11, 2014 City of Sparks 215 S. 21 st St. Sparks, NV 89432-0857 Attn: Brian Cason Re: Sparks City Hall HVAC Upgrade Project-Alerton Direct Digital HVAC Control System to Match Existing City of
More informationTechnical Report #2. Newseum and Freedom Forum Headquarters. Washington, D.C. Ryan Wise Lighting/Electrical Prof. Dannerth November 2, 2007
Technical Report #2 Ryan Wise Lighting/Electrical Prof. Dannerth November 2, 2007 Newseum and Freedom Forum Headquarters Washington, D.C. Table of Contents Power Distribution Systems Executive Summary
More informationChandler City Hall Chandler, Arizona
Chandler City Hall Chandler, Arizona AE481W: Architectural Engineering Senior Thesis Wednesday October 27 th, 2010 Stephanie Romanias Lighting/Electrical Faculty Consultant Dr. Kevin Houser/Professor Dannerth
More informationTechnical Assignment #2 Electrical Systems Existing Conditions & Building Load Summary
Technical Assignment #2 Electrical Systems Existing Conditions & Building Load Summary William H. Gates Hall Seattle, WA Katherine Jenkins Lighting/Electrical Option October 27, 2006 Faculty Advisor: Ted
More informationExisting Mechanical System Operation
majority of the air handlers. There are louvers along the north side of the building that allow for outdoor air to come in and feed the air handlers. On levels 4-8 the research laboratories are variable
More informationThis is to inform you the Equipment List has been added to this Invitation for Bid and the BID OPENING date has been postponed
June 2, 2014 MEMORANDUM TO WHOM IT MAY CONCERN FROM: Janell Kim Financial Services Director SUBJECT: ADDENDUM NO. 2 INVITATION FOR BID NO. J15013 TO PROVIDE MAINTENANCE SERVICE, AND CHEMICAL WATER TREATMENT
More informationELECTRICAL EXISTING CONDITIONS AND DESIGN ANALYSIS
Executive Summary ELECTRICAL EXISTING CONDITIONS AND DESIGN ANALYSIS Sara Lappano Ltg./Elec. Corron Cultural Center Middletown, VA Faculty Advisor: Dr. Moeck 11.4.2002 As in the prior lighting technical
More informationTechnical Report #3 Mechanical Systems Existing Conditions Evaluation
Mechanical Option Technical Report #3 Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor: Dr. Bahnfleth 11.15.04 Building Sponsor: CCG Facilities Integration Table of Contents
More informationHo-Chunk Gaming THUNDERBIRD ENGINEERING, INC. MILWAUKEE: (414) MADISON: (608)
Ho-Chunk Gaming POWER SYMBOLS X ELECTRICAL PANEL - REFER TO DRAWINGS FOR WIDTH AND PANEL SCHEDULES PANEL NAMING: XXP-#X: DENOTES PANEL FUNCTION: L = LIGHTING P = GENERAL POWER E = EMERGENCY S = OPTIONAL
More informationFLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK
FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK ENERGY CONSERVATION MEASURE 1 Partial Steam System Decentralization SIEMENS will Furnish and Install condensing hot water boilers with associated
More informationAIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University
AIR-CONDITIONING SYSTEMS AND APPLICATIONS Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS Earliest air conditioning system used only for heating (winter) Provided heated air for comfort
More informationRules for Application of DUoS Tariff Group
DOC-111004-AHV Rules for Application of DUoS Tariff Group ESB 31/08/04 Rules for Application of DUoS Tariff Group Status: Approved by CER Commercial and Customer ESB Networks September 2004 September 2004,
More information21. Plumbing fixture mixing valves, PRV, electronic faucets and flush valve(excluding batteries)optional Cost proposal to include these device
DIVISION 23800 APPENDIX A ASHTABULA CAMPUS: 1. Air Handling Equipment And Appurtenances 2. Exhaust Fans 3. Fume Hood Exhaust Fans 4. Fume Hood monitoring devices and annual certification of face velocity
More informationNYC Department of Education
Asset: J. K. ONASSIS HS FOR INT CAREERS-M, 120 WEST 46 STREET, New York, 10036 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-11 11:37 AM 2017-12-26 12:18 PM Asset Data Are there
More informationDDC POINT LIST. 004 Harry Griffith Hall. RFP #PW17-2 Exhibit J Page 1 of 9 AHU 1 BOILER BOX DUAL DUCT MIXING. Building: HUMBOLDT STATE UNIVERSITY
Page 1 of 9 004 Harry Griffith Hall AHU 1 OUTSIDE AIR TEMPERATURE 1 OA T AT LEAST ONE HARDWIRED OA SENSOR PER BUILDING HOT DUCT SUPPLY AIR TEMPERATURE 1 HD T 1ST FLOOR HOT DUCT STATIC PRESSURE 2 HD PRESS*
More informationNYC Department of Education
Asset: P.S./I.S. 194 - BRONX, 2365 WATERBURY AVENUE, New York, 10462 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-24 8:34 AM 2018-02-01 10:02 AM Asset Data Are there fuel tanks?
More informationLIGHT LEVEL REQUIREMENTS MINIMUM ACCEPTABLE FOOT CANDLES
LIGHT LEVEL REQUIREMENTS LOCATION Classrooms and instrumental areas- Study Halls, Lecture Rooms, Art Rooms, Offices, Libraries, Conference Rooms, Work Rooms, Shops, Laboratories and Secondary School Cafeterias.
More informationJob Name Control Systems Description Date
Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In
More informationMT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS
CARROLL COUNTY PUBLIC SCHOOLS LIFE CYCLE COST ANALYSIS SUMMARY DGS PROCEDURES FOR THE IMPLEMENTATION OF LIFE CYCLE COST ANALYSIS AND ENERGY CONSERVATION OCTOBER, 2010 G.A.I.#09090 GIPE ASSOCIATES, INC.
More informationNYC Department of Education
Asset: LIBERTY HS - MANHATTAN, 250 WEST 18 STREET, New York, 10011 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-29 11:32 AM 2018-02-01 10:16 AM Asset Data Are there fuel tanks?
More informationTechnical Assignment 3 11/15/04. Executive Summary
Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria
More informationElement Z Owner Standards and Other Requirements ODG010107
Part 1. General This section identifies mechanical, electrical, and plumbing (MEP) equipment naming conventions and acronyms for the A/E to use when identifying equipment in the Contract Documents. Part
More informationNYC Department of Education
Asset: P.S. 69 - STATEN ISLAND, 144 KEATING PLACE, New York, 10314 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-19 8:39 AM 2018-01-23 4:33 PM Asset Data Are there fuel tanks?
More informationMID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN
MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN September 30, 2015 PBA Project No. 2015.0140.00 PETER BASSO ASSOCIATES INC. CONSULTING ENGINEERS 5145 LIVERNOIS ROAD,
More informationREQUEST FOR PROPOSALS FOR THE PROVISION OF PREVENTIVE MAINTENANCE ON FACILITY HVAC SYSTEMS FOR SKOKIE PUBLIC LIBRARY
REQUEST FOR PROPOSALS FOR THE PROVISION OF PREVENTIVE MAINTENANCE ON FACILITY HVAC SYSTEMS FOR SKOKIE PUBLIC LIBRARY Skokie Public Library is requesting proposals for a contract for the provision of preventive
More informationTechnical II Report Electrical Systems
Technical II Report Electrical Systems Kelly Chan Consultant: Prof T. Dannerth, P.E. Part A Drawings Drawings needed for single-line diagram EE1.01 title sheet (electrical drawings) EE2.09 penthouse/roof
More informationCIVIC CONDOMINIUM PREVENTIVE MAINTENANCE SCHEDULE
Index No. Category/Component DescripCon Doors & Windows DW- 1 Door Hardware & Closers X DW- 2 Exterior Metal Doors X DW- 3 Garage & Loading Ramp Doors DW- 4 Interior Wood & Metal Doors X DW- 5 Storefront
More informationSingle zone RTU, controlled by a programmable thermostat. Single zone RTU, generic description, with power exhauster
Rooftop Units CV Reheat RTU Reheat Reheat system RTU, serving electric reheat coils, w/dehumidification cycle & RA CO2 override of OAD CV Single Zone RTU SZ (from PC) RTU SZ Generic RTU SZ Multiple Units
More informationMECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY
MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY 2018 57 MECHANICAL ASSESSMENT MECHANICAL ASSESSMENT This report section includes an overview of the existing
More informationTemperature. In the HVAC area, we talk about two kinds of temperatures.
HEATING and COOLING HEATING and COOLING PSYCHROMETRIC CHART Temperature In the HVAC area, we talk about two kinds of temperatures. One is called dry bulb (DB) temperature, a fancy name for the reading
More informationNYC Department of Education
Asset: P.S. 78 - QUEENS, 48-09 CENTER BLVD., New York, 11109 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-02 11:40 AM 2018-04-19 9:04 AM Asset Data Are there fuel tanks? Total
More informationNYC Department of Education
Asset: P.S. 111 - MANHATTAN, 440 WEST 53 STREET, New York, 10019 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-16 8:47 AM 2018-03-21 8:02 AM Asset Data Are there fuel tanks?
More informationNYC Department of Education
Asset: P.S. 22 - STATEN ISLAND, 1860 FOREST AVENUE, New York, 10303 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-08 8:51 AM 2017-12-18 4:14 PM Asset Data Are there fuel tanks?
More informationComputing Services Center
Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory
More informationTechnical Assignment 3. Mechanical Systems Existing Conditions Evaluation
Technical Assignment 3 Mechanical Systems Existing Conditions Evaluation The Milton Hershey School New Supply Center Prepared for: William P. Bahnfleth, Ph.D., P.E., Professor Department of Architectural
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section
More informationNYC Department of Education
Asset: P.S. 198 - BRONX, 1180 TINTON AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-24 8:14 AM 2018-01-24 9:32 PM Asset Data Are there fuel tanks? Total
More informationTable of Contents. List of Figures and Tables. Executive Summary: 3 ASHRAE Standard 62.1 Section 6 Analysis 7
Army Reserve Center Newport, Rhode Island Technical Report One: ASHRAE Standard 62.1 Ventilat tion and Standard 90.1 Energy Design Evaluations October 4, 2010 2 Table of Contents Executive Summary: 3 ASHRAE
More informationELECTRICAL Seminar. B A L A Consulting Engineers, Inc. Edward J. Lynch, PE Vice President, Electrical Department Manager.
B A L A Consulting Engineers, Inc. PECO Line 13.2kV Incoming Service No. 1 Utility/Generator Medium Voltage Switchgear PECO Line 13.2kV Incoming Service No. 2 Unit Substation ELECTRICAL Seminar HVAC Equip.
More informationNYC Department of Education
Asset: MID MAN ADULT LRNG CTR (81) - M, 212 W 120TH ST, New York, 10027 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-17 8:16 AM 2018-01-17 8:17 PM Asset Data Are there fuel
More information2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems
2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems Dieter Bartel, Manitoba Hydro September 17 th, 2014 Outline Scope and compliance Prescriptive path
More informationNYC Department of Education
Asset: P.S. 146 - BRONX, 968 CAULDWELL AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-01 8:57 AM 2018-05-31 2:59 PM Asset Data Are there fuel tanks? Total
More informationBMS Commissionability Review. October Four Seasons Hotel Park Lane PROJECT:
BMS Commissionability Review October 2009 PROJECT: Four Seasons Hotel Park Lane Summary This report details our review of the BMS specification produced by i.d.a. Building Services Consulting Engineers,
More informationCHILLED WATER SYSTEM 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods
230510 CHILLED WATER SYSTEM PART 1: GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 230000 Basic HVAC Requirements B. Section 230500 HVAC Basic Materials and Methods C. Section
More informationHeat Recovery Units. EXTERNAL STATIC REQUIRED (in.h2o) (Pa) MOTOR (Bhp/Hp) (bkw/kw) SPEED (rpm)
Heat Recovery Units AIR HANDLING UNIT No. SERVICE AREA MANUFACTURER MODEL HRU-3 & HRU-4 B-Section Low Rate Ventilation Tempeff RG 16000 (9500) SUPPLY FAN - SIZE/TYPE AIRFLOW RATE (cfm) (l/s) TOTAL STATIC
More informationDiesel Fuel System Report
Transbay Transit Center San Francisco, CA Prepared for: Pelli Clarke Pelli Architects 1056 Chapel Street New Haven, CT 06510 Prepared by: WSP 405 Howard Street, Suite 500 San Francisco, CA 94105 Mechanical
More informationNYC Department of Education
Asset: P.S. 86 ANNEX - BRONX, 124 EAMES PLACE, New York, 10468 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-05 1:03 PM 2018-04-27 1:35 PM Asset Data Are there fuel tanks? Total
More information4. OVERVIEW OF MECHANICAL SYSTEM
4. OVERVIEW OF MECHANICAL SYSTEM The 87,000 SF SLCC is served by six (6) Trane M-Series Climate Changer Air Handing Units (AHUs). Each unit serves a distinct zone within the facility that is unique in
More informationElement Z General Design Requirements Existing Facilities Information
Charles M. LeMaistre PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and
More informationSequence of Operations (excerpt)
Sequence of Operations (excerpt) Chilled Water System Consists of one (1) 600 cooling ton Trane CVHE 3 stage centrifugal chiller, with associated chilled water pumps, condenser water pumps and one (1)
More informationTechnical Assignment 3
0 David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option Technical Assignment 3 Mechanical Systems and Existing Conditions Report David H. Koch Institute for Integrative
More informationOld Jail HVAC Replacement Feasibility Report
Old Jail HVAC Replacement Feasibility Report Madera, CA Prepared by Kitchell for the County of Madera, California Job No. 6168A3 Executive Summary On October 21, 2016, Kitchell conducted a Feasibility
More informationULTRA-SAFE Explosion-proof Duct Heaters
Standard Construction Heat Exchanger has copper tubes with integral aluminum fins. Each unit undergoes hydrostatic testing at 350 psig, five times the pressure relief valve setting of 70 psig. Heat Transfer
More informationNZECP 19: 1994 ISSN COVER PAGE
NZECP 19: 1994 ISSN 0114-0663 COVER PAGE NZECP:19 1994 NEW ZEALAND ELECTRICAL CODE OF PRACTICE for DETERMINATION OF MAXIMUM DEMAND in ELECTRICAL INSTALLATIONS Issued by the Office of The Chief Electrical
More informationI. Introduction and Arrangement
Joseph Firrantello - Mechanical Option Primary Faculty Consultant: Freihaut Laboratory Facility, Eastern Pennsylvania Mechanical Assignment 3 Existing Conditions Report 11.14.03 Executive Summary The purpose
More information1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT
Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story
More informationELECTRICAL/MECHANICAL INFRARED INSPECTION REPORT. The Corporate Facility 2001 Freedom Way United City, USA
ELECTRICAL/MECHANICAL INFRARED INSPECTION REPORT for The Corporate Facility 2001 Freedom Way United City, USA January 01, 2012 Job Number: 1111-12 TABLE OF CONTENTS I - Introduction to the Report Explains
More informationBusiness Energy Efficiency Incentives 2007
Business Energy Efficiency Incentives 2007 1 DSM s Energy & Environmental Impact since 1981 9,378,000,000 kwh 2 1 Year Round Savings on EnergyWise 2 Cars driven 12,000 Miles Progress Energy Growth Trend
More informationBrown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA
PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities
More informationContact Information. Steven Potratz, P.E. WSU Facilities Services, Engineering Services Manager Phone
Contact Information Steven Potratz, P.E. WSU Facilities Services, Engineering Services Manager Phone 509 335 9300 steve_potratz@wsu.edu WSU Utilities WSU primary systems are all based on district type
More informationTechnical Report 2: Electrical Systems Existing Conditions and Building Load Summary Report. 100% Submission. Sherrerd Hall, Princeton University, NJ
Technical Report 2: Electrical Systems Existing Conditions and Building Load Summary Report 100% Submission Sherrerd Hall, Princeton University, NJ Faculty Consultant: Ted Dannerth 4 November 2009 Table
More informationChilled Water system
Chilled Water system Introduction For large installations the Condenser, Evaporator, Compressor and Expansion device can be purchased as a package unit, known as a Chiller. The usual package consists of
More informationMendenhall Wastewater Treatment Plant Energy Audit
Mendenhall Wastewater Treatment Plant Energy Audit Final Report August 18, 2009 Mendenhall Wastewater Treatment Plant City and Borough of Juneau Prepared for: City and Borough of Juneau Contract No. RFP
More informationHVAC Mandatory Provisions Part II, Page 1
HVAC Mandatory Provisions Part II, Page 1 Mandatory Equipment Efficiency Worksheet (6.4.1.1) System Equipment Type Size Category (Tables 6.8.1A through K) Sub-Category or Rating Condition Units of Efficiency
More informationNYC Department of Education
Asset: P.S. 128 - MANHATTAN, 560 WEST 169 STREET, New York, 10032 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-07 8:50 AM 2018-06-14 1:16 PM Asset Data Are there fuel tanks?
More informationAttachment F. Campus Capital Needs Sales Surtax Funded Detail Report
Facility Attachment F Campus Capital Needs Sales Surtax Funded Detail Report Facilities Services 2700 Judge Fran Jamieson Way Viera, Florida 32940-6601 Condition Code Estimate Williams Elementary 1.40
More informationSECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS
PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 23 0993 SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS A. This section defines the manner and method by which controls function. Requirements for each type of
More informationChoosing Heating and Cooling Systems
Choosing Heating and Cooling Systems 2005 Building Science Corporation PR-0510d: BuildBoston 2005 Choosing Heathing and Cooling Systems Page 1 of 23 Ducted Systems vs. Radiant Systems Radiant hot water
More informationSECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS
SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section
More informationFans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans. Topvex SoftCooler TR. Specification data
Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Topvex SoftCooler TR Specification data 2 Topvex SoftCooler TR Comfort cooling, ready from factory
More information"This is only the scope of work for the project. For more information, interested parties should contact Procurement at
"This is only the scope of work for the project. For more information, interested parties should contact Procurement at purchasing@stpgov.org to ensure receipt of a full bid package, to be listed as a
More informationRE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana
ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum
More informationEnergy Management Wiring Guide
Energy Management Wiring Guide Runestone Electric Association 6839 Power Lane SW Alexandria, MN 56308 (320) 762-1121 or (800) 473-1722 Fax: (320) 763-4149 www.runestoneelectric.com Table of Contents Basic
More informationMatt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc.
M&V Real Results of High Performance Design Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc. Overview Measurement & Verification (M&V) Plan for New
More informationAHRI Product Section and Subsection Scopes
Air Control and Distribution Devices Product Section Air-Cooled and Evaporative Condensers Subsection Air-Cooling and Air Heating Coils Subsection Air-to-Air Energy Recovery Ventilation Product Section
More informationMechanical Technical Report #3. Mechanical Systems Existing Conditions Report. Faculty Advisor: Dr. William P. Bahnfleth.
Mechanical Option Mechanical Technical Report #3 The Montgomery County Conference Center and Hotel (MCCCH), Architectural renderings compliments of RTKL Associates Mechanical Technical Report #3 Mechanical
More informationTerminal. Las Vegas, NV. Technical
McCarran International port Terminal 3 Technical Assignment 3 Mechanical System Existing Conditions Evaluation December 3, 2007 Prepared By: Faculty Advisor: Dr. William Bahnfleth, Ph.D., P..E. Table of
More informationCook - Wissahickon Elementary School
Cook - Wissahickon Elementary School 201 E. Salaignac St., Philadelphia, PA 19128 HVAC Replacement Project Scope Determination Report May 10, 2018 Prepared by: G.P. Lamina, Jr., P.E., MBA School District
More informationMechanical Systems Existing Conditions Evaluation. Instructor: Dr. Bahnfleth. November 12, Thesis Building Sponsor s: INOVA Fairfax Hospital
David J. Peterson Mechanical Option Mechanical Technical Report #3 The INOVA HEART INSTITUTE AT, Falls Church, VA. Mechanical Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor:
More informationNYC Department of Education
Asset: I.S. 2 - BROOKLYN, 655 PARKSIDE AVE, New York, 11226 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-05-11 9:35 AM 2018-05-22 3:53 PM Asset Data Are there fuel tanks? Total
More informationBuilding Automation System (BAS) Design Criteria
25 0520 Building Automation System (BAS) Design Criteria 1. Design Statement a. During the various design phases of this project, the Engineer will develop options and strategies for selection of the appropriate
More informationTECHNICAL REPORT 3: Mechanical Systems and Existing Conditions. Michael Morder Mechanical Option Advisor: Dr. William Bahnfleth
TECHNICAL REPORT 3: Mechanical Systems and Existing Conditions Michael Morder Mechanical Option Advisor: Dr. William Bahnfleth INOVA South Patient Tower Falls Church, VA November 16, 2011 Table of Contents
More informationTechnical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: ,
Purpose 355 West Queens Road Technical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: 604-990-2480, building@dnv.org The purpose of this document is to provide
More informationFUNCTIONAL DESIGN SPECIFICATION
Issue Date: Issued To: Revision: FUNCTIONAL DESIGN SPECIFICATION Specification Number: SP-XXXX Company Name Signature Date Issued By: Manutec Ltd. Approved By: Approved By: Approved By: Approved By: Authorised
More informationDOUBLE EFFECT ABSORPTION CHILLER /HEATER MG MODEL 1
DOUBLE EFFECT ABSORPTION CHILLER /HEATER MG MODEL 1 Specifications CH-MG150CE CH-MG200CE Version 9.10 Contents Page 1. General Information 1.1 Chiller-heater... 2 1.1.1 Chiller-heater Specification. 2
More informationNYC Department of Education
Asset: CLINTON AF - BRONX, 100 W. MOSHOLU PKWY S, New York, 10468 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-20 8:24 AM 2017-12-31 2:04 PM Asset Data Are there fuel tanks?
More informationNYC Department of Education
Asset: ACHIEVEMENT FIRST ENDEAVOR CHARTER SCHOOL- BROOKLYN, 510 WAVERLY AVENUE, New York, 11238 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-14 8:42 AM 2018-03-23 10:17 AM
More informationAIR HANDLING UNITS ASSET REFERENCE: DESIGN AHU 1 AHU 2
AIR HANDLING UNITS DESIGN System INFORMATION No off Access Handing Viewed in direction of supply air Finish / Colour Duct Connections Height: Width Velocity: Design Airflow (m3/s) Supply Fan Ability Supply
More informationUNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationSchedule of Fees Schedule B
Schedule of Fees Schedule B BUILDING DEPARTMENT 2. Building Permit* $65.00 for value or valuation up to $1,000. After $1,000 of value $8.00 per $1,000. After $1,000,000 of value $6 per $1,000 3. Demolition
More informationINTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings
INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,
More informationAHU Air Handling Unit Fundamentals. j.ilangumaran
AHU Air Handling Unit Fundamentals j.ilangumaran Objectives Review primary components of an AHU Understand the basic progression and advantages of advanced AHU control Understand the basic control sequences
More information2013 Nonresidential Appendices Appendix NA8-1. Appendix NA8 Luminaire Power... 1 NA8.1 Luminaire Power... 1
2013 Nonresidential Appendices Appendix NA8-1 Nonresidential Appendix NA8... 1 NA8.1 Luminaire Power... 1 NA8.1 Luminaire Power The following tables contain a limited list of lamp and ballast combinations.
More informationPresentation Outline. Coppin State University Physical Education Complex Kaylee Damico Mechanical Option April 12 th, 2011
Project Team Proposed Redesign Mechanical Depth Electrical Breadth Construction Management Breadth Cost and Energy Savings Summary and Conclusion Coppin State University Physical Education Complex Kaylee
More informationAn HVAC Audit of the Canberra Institute of Technology
An HVAC Audit of the Canberra Institute of Technology 30 th November 2016 Amnon Holland amnon.holland@esbsconsult.com.au www.esbsconsult.com.au Agenda Overview CIT and various other sites The sites Type
More informationNYC Department of Education
Asset: BAYSIDE AF - QUEENS, 204-29 29TH AVENUE, New York, 11361 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-10-31 9:42 AM 2017-11-20 4:21 PM Asset Data Are there fuel tanks?
More informationSCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE
SCHEDULE OF S Penalty Fees. The fee for construction work performed before securing permit(s), where required, may be charged a fee of TWO TIMES THE COST OF THE PERMIT (S). Building Fee Schedule Residential
More informationNYC Department of Education
Asset: AUTOMOTIVE TRADES VOC HS - K, 50 BEDFORD AVENUE, New York, 11222 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-05-01 8:09 AM 2018-05-10 2:18 PM Asset Data Are there fuel
More informationNYC Department of Education
Asset: P.S. 32 - BRONX, 690 EAST 183 STREET, New York, 10458 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-13 9:25 AM 2017-11-16 5:46 PM Asset Data Are there fuel tanks? Total
More information