DDC POINT LIST. 004 Harry Griffith Hall. RFP #PW17-2 Exhibit J Page 1 of 9 AHU 1 BOILER BOX DUAL DUCT MIXING. Building: HUMBOLDT STATE UNIVERSITY

Size: px
Start display at page:

Download "DDC POINT LIST. 004 Harry Griffith Hall. RFP #PW17-2 Exhibit J Page 1 of 9 AHU 1 BOILER BOX DUAL DUCT MIXING. Building: HUMBOLDT STATE UNIVERSITY"

Transcription

1 Page 1 of Harry Griffith Hall AHU 1 OUTSIDE AIR TEMPERATURE 1 OA T AT LEAST ONE HARDWIRED OA SENSOR PER BUILDING HOT DUCT SUPPLY AIR TEMPERATURE 1 HD T 1ST FLOOR HOT DUCT STATIC PRESSURE 2 HD PRESS* * REQUIRES A UNIQUE (#1 THRU 6) 1ST FLOOR COLD DUCT STATIC PRESSURE 1 CD PRESS* * REQUIRES A UNIQUE (#1 THRU 6) 2ND FLOOR HOT DUCT STATIC PRESSURE 2 HD PRESS* * REQUIRES A UNIQUE (#1 THRU 6) 2ND FLOOR COLD DUCT STATIC PRESSURE 1 CD PRESS* * REQUIRES A UNIQUE (#1 THRU 6) RETURN AIR CO2 1 RA Q SUPPLY AIR STATIC PRESSURE 1 SA SP MIXED AIR DAMPER COMMAND 1 MAD O 1ST FLOOR HOT DUCT DAMPER COMMAND 2 HD* O * REQUIRES CORRESPONDING ID (#1 THRU 6) 1ST FLOOR COLD DUCT DAMPER COMMAND 1 CD* O * REQUIRES CORRESPONDING ID (#1 THRU 6) 2ND FLOOR HOT DUCT DAMPER COMMAND 2 HD* O * REQUIRES CORRESPONDING ID (#1 THRU 6) 2ND FLOOR COLD DUCT DAMPER COMMAND 1 CD* O * REQUIRES CORRESPONDING ID (#1 THRU 6) SF-1 START / STOP 1 SF C RF-1 START / STOP 1 RF C SF-1 STATUS 1 SF S RF-1 STATUS 1 RF S HIGH STATIC PRESSURE CUTOUT 1 HI PRESS BOILER HOT WATER PUMP P-1 START / STOP 1 P1 C HOT WATER PUMP P-2 START / STOP 1 P2 C HOT WATER PUMP P-1 STATUS 1 P 1_S HOT WATER PUMP P-2 STATUS 1 P 2_S BOILER TEMPERATURE RESET 1 BLR O HOT WATER CONTROL VALVE 1 HWV O CURRENTLY MANUALLY LOCKED OPEN BOILER ALARM 1 BLR A BOILER STATUS 1 BLR S DUAL DUCT MIXING BOX MIXING BOX DAMPER COMMAND_RM* 1 DPR O_RM* * REQUIRES A UNIQUE ROOM/LOCATION VIA COMMUNICATIONS FROM THERMOSTAT, * REQUIRES A UNIQUE ROOM/LOCATION

2 Page 2 of Harry Griffith Hall BUILDING STATIC PRESSURE 1 1 BSP FIRST FLOOR BUILDING STATIC PRESSURE 1 2 BSP SECOND FLOOR OUTSIDE LIGHTS COMMAND 1 OLTS C EF-2 START / STOP 1 EF2 C EF-3 START / STOP 1 EF3 C EF-4 START / STOP 1 EF4 C EF-5 START / STOP 1 EF5 C EF-2 STATUS 1 EF2 S EF-3 STATUS 1 EF3 S EF-4 STATUS 1 EF4 S EF-5 STATUS 1 EF5 S AIR CONDITIONING START / STOP_RM115 1 CLG C_RM115 SERVES COMPUTER LAB ZONE TEMPERATURE_RM115 1 ZN T_RM115 SERVES COMPUTER LAB ZONE SETPOINT_RM115 ZN SP_RM115 MAY BE VIA COMMUNICATIONS

3 Page 3 of NATURAL RESOURCES AH 1 OUTSIDE AIR TEMPERATURE 1 OA T AT LEAST ONE HARDWIRED OA SENSOR PER BUILDING RETURN AIR CO2 1 RA CO2 SUPPLY FAN SPEED 1 SF O AH 2 OUTSIDE AIR TEMPERATURE 1 OA T AT LEAST ONE HARDWIRED OA SENSOR PER BUILDING ALSO STARTS RETURN FAN BOILER BOILER TEMPERATURE 1 BLR T HOT WATER PUMP START / STOP 1 HWP C HOT WATER PUMP STATUS 1 HWP_S HOT WATER PUMP CP-1 START / STOP 1 CP1 C HOT WATER PUMP CP-1 STATUS 1 CP1_S BOILER TEMPERATURE RESET 1 BLR O BOILER ALARM 1 BLR A BOILER STATUS 1 BLR S EF-1 START / STOP 1 EF1 C EF-1 STATUS 1 EF1 S EF-2 START / STOP 1 EF2 C EF-2 STATUS 1 EF2 S LIGHTS - 1ST FLOOR E/W Corridor 1 LTS C_1EW LIGHTS - 1ST FLOOR N/S Corridor 1 LTS C_1NS LIGHTS - 2ND FLOOR E/W Corridor 1 LTS C_2EW LIGHTS - 2ND FLOOR N/S Corridor 1 LTS C_2NS

4 Page 4 of NATURAL RESOURCES SINGLE DUCT CAV BOX w/reheat REHEAT VALVE COMMAND_RM* 1 HWV O_RM* * REQUIRES A UNIQUE ROOM/LOCATION VIA COMMUNICATIONS FROM THERMOSTAT, * REQUIRES A UNIQUE ROOM/LOCATION

5 Page 5 of SIEMENS HALL SF 1 & SF 2 OUTSIDE AIR TEMPERATURE 1 OA T AT LEAST ONE HARDWIRED OA SENSOR PER BUILDING HOT DUCT SUPPLY AIR TEMPERATURE 1 HD T SUPPLY DUCT DIFFERENTIAL PRESSURE 1 SD DP RETURN AIR CO2 1 RA Q RETURN AIR DAMPER 1 RAD O MINIMUM OUTSIDE AIR DAMPER COMMAND 1 MOAD O HOT DUCT DAMPER COMMAND 1 HD O ALSO STARTS SF 2 SUPPLY FAN SF-1 STATUS 1 SF1 S SUPPLY FAN SF-2 STATUS 1 SF2 S BOILER HOT WATER PUMP P-1 START / STOP 1 HWP1 C HOT WATER PUMP P-2 START / STOP 1 HWP2 C HOT WATER PUMP P-1 STATUS 1 HWP1 S HOT WATER PUMP P-2 STATUS 1 HWP2 S BOILER TEMPERATURE RESET 1 BLR O BOILER STATUS BLR S VIA BACNET COMMUNICATIONS DUAL DUCT MIXING BOX MIXING BOX DAMPER COMMAND_RM* 1 DPR O_RM* * REQUIRES A UNIQUE ROOM/LOCATION VIA COMMUNICATIONS FROM THERMOSTAT, * REQUIRES A UNIQUE ROOM/LOCATION EF-1 START / STOP (LOW) 1 EF1LOW C EF-1 START / STOP (HI) 1 EF1HI C EF-1 STATUS 1 EF1 S EF-5 START / STOP (LOW) 1 EF5LOW C EF-5 START / STOP (HI) 1 EF5HI C EF-5 STATUS 1 EF5 S EF-2 START / STOP 1 EF2 C EF-2 STATUS 1 EF2 S EF-3 START / STOP 1 EF3 C EF-3 STATUS 1 EF3 S BUILDING STATIC PRESSURE 2 BSP

6 Page 6 of STUDENT HEALTH CENTER AH 3 AH 2 AH 1 HOT DUCT SUPPLY AIR TEMPERATURE 1 HD T RETURN AIR CO2 1 RA CO2 HEATING VALVE COMMAND 1 HWV O OUTSIDE AIR TEMPERATURE 1 OA T SUPPLY AIR TEMPERATURE 1 SA T SUPPLY AIR DUCT STATIC PRESSURE 1 SA P BUILDING STATIC PRESSURE 1 BLDG P (FUTURE, DAMPERS CURRENTLY HAVE FIXED POSITIONS) HOT WATER VALVE COMMAND 1 HWV O SUPPLY FAN VFD SPEED COMMAND 1 SF O RETURN FAN VFD SPEED COMMAND 1 RF O OUTSIDE AIR TEMPERATURE 1 OA T SUPPLY AIR TEMPERATURE 1 SA T SUPPLY AIR DUCT STATIC PRESSURE 1 SA P BUILDING STATIC PRESSURE 1 BLDG P HOT WATER VALVE COMMAND 1 HWV O SUPPLY FAN VFD SPEED COMMAND 1 SF O RETURN FAN VFD SPEED COMMAND 1 RF O

7 Page 7 of STUDENT HEALTH CENTER HEATING HOT WATER SYSTEM (AH 1) BOILER RETURN TEMPERATURE 1 BR T HOT WATER PUMP P-1 START / STOP 1 P1 C HOT WATER PUMP P-1 STATUS 1 P1 S HOT WATER MIXING VALVE 1 HWV O HEATING HOT WATER SYSTEM (AH 2 & AH 3) HOT WATER MIXING VALVE 1 HWV O HOT WATER PUMP P-1 START / STOP 1 P1 C HOT WATER PUMP P-1 STATUS 1 P1 S HOT WATER PUMP P-2 START / STOP 1 P2 C HOT WATER PUMP P-2 STATUS 1 P2 S DUAL DUCT MIXING BOX MIXING BOX DAMPER COMMAND_RM* 1 DPR O_RM* * REQUIRES A UNIQUE ROOM/LOCATION VIA COMMUNICATIONS FROM THERMOSTAT, * REQUIRES A UNIQUE ROOM/LOCATION SINGLE DUCT VAV BOX w/reheat VAV DAMPER COMMAND_RM* 1 DPR O_RM* * REQUIRES A UNIQUE ROOM/LOCATION REHEAT VALVE COMMAND_RM* 1 HWV O_RM* * REQUIRES A UNIQUE ROOM/LOCATION VIA COMMUNICATIONS FROM THERMOSTAT, * REQUIRES A UNIQUE ROOM/LOCATION

8 Page 8 of 9 003D & 003E SCIENCE D & E AH 1 SUPPLY AIR TEMPERATURE 1 SA T OUTSIDE AIR TEMPERATURE 1 OA T AT LEAST (1) HARDWIRED POINT PER BUILDING SUPPLY AIR DUCT STATIC PRESSURE 1 SA P BUILDING STATIC PRESSURE 1 BLDG P FILTER DIFFERENTIAL PRESSURE 1 FILT P RETURN AIR CO2 1 RA CO2 HOT WATER VALVE COMMAND 1 HWV O CHILLED WATER VALVE COMMAND 1 CHWV O SUPPLY FAN VFD SPEED COMMAND 1 SF O RETURN FAN VFD SPEED COMMAND 1 RF O RETURN AIR SMOKE DETECTOR 1 RA SD MAINTAIN EXISTING SHUTOWN AND ALARM CONNECTIONS AH 2 SUPPLY AIR TEMPERATURE 1 SA T OUTSIDE AIR TEMPERATURE 1 OA T AT LEAST (1) HARDWIRED POINT PER BUILDING SUPPLY AIR DUCT STATIC PRESSURE 1 SA P BUILDING STATIC PRESSURE 1 BLDG P FILTER DIFFERENTIAL PRESSURE 1 FILT P RETURN AIR CO2 1 RA CO2 HOT WATER VALVE COMMAND 1 HWV O CHILLED WATER VALVE COMMAND 1 CHWV O SUPPLY FAN VFD SPEED COMMAND 1 SF O RETURN FAN VFD SPEED COMMAND 1 RF O RETURN AIR SMOKE DETECTOR 1 RA SD MAINTAIN EXISTING SHUTOWN AND ALARM CONNECTIONS CHILLED WATER SYSTEM CHILLED WATER RETURN TEMPERATURE 1 CHWR T CHILLED WATER SUPPLY TEMPERATURE 1 CHWS T CHILLED WATER PUMP CHWP-1 START / STOP 1 CHWP1 C CHILLED WATER PUMP CHWP-2 START / STOP 1 CHWP2 C CHILLED WATER PUMP CWWP-1 STATUS 1 CHWP1 S CHILLED WATER PUMP CHWP-2 STATUS 1 CHWP2 S CHILLED WATER FLOW SWITCH 1 CHW F CHILLER ENABLE 1 CH ENA

9 Page 9 of 9 003D & 003E SCIENCE D & E HEATING HOT WATER SYSTEM HOT WATER DIFFERENTIAL PRESSURE 1 HW DP HOT WATER PUMP HWP-1 START / STOP 1 HWP1 C HOT WATER PUMP HWP-2 START / STOP 1 HWP2 C HOT WATER PUMP HWP-1 STATUS 1 HWP1 S HOT WATER PUMP HWP-2 STATUS 1 HWP2 S HOT WATER FLOW SWITCH 1 HW F SCIENCE D ISOLATION VALVE 1 ISOV C HOT WATER LOOP FLOWRATE 1 HW F CURRENTLY ON (E) METASYS CONTROLS HOT WATER FLOWRATE - BLDG E 1 E_HW F CURRENTLY ON (E) METASYS CONTROLS HOT WATER RETURN TEMPERATURE - BLDG E 1 E_HWR T CURRENTLY ON (E) METASYS CONTROLS HOT WATER SUPPLY TEMPERATURE - BLDG E 1 E_HWS T CURRENTLY ON (E) METASYS CONTROLS OUTSIDE AIR TEMPERATURE 1 OA T WALK-IN BOX TEMPERATURE #1 1 WB1 T WALK-IN BOX TEMPERATURE #2 1 WB2 T CHILLER KW METER 1 CH KWM FIELD CONFIRM POINT TYPE DHW PUMP START / STOP 1 DHWP C SINGLE DUCT VAV BOX w/reheat VAV DAMPER COMMAND_RM* 1 DPR O_RM* * REQUIRES A UNIQUE ROOM/LOCATION REHEAT VALVE COMMAND_RM* 1 HWV O_RM* * REQUIRES A UNIQUE ROOM/LOCATION VIA COMMUNICATIONS FROM THERMOSTAT, * REQUIRES A UNIQUE ROOM/LOCATION

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

November 11, City of Sparks 215 S. 21 st St. Sparks, NV November 11, 2014 City of Sparks 215 S. 21 st St. Sparks, NV 89432-0857 Attn: Brian Cason Re: Sparks City Hall HVAC Upgrade Project-Alerton Direct Digital HVAC Control System to Match Existing City of

More information

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK ENERGY CONSERVATION MEASURE 1 Partial Steam System Decentralization SIEMENS will Furnish and Install condensing hot water boilers with associated

More information

Civil Engineering Building

Civil Engineering Building Continuous Commissioning Report For the Civil Engineering Building Building 492 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

Single zone RTU, controlled by a programmable thermostat. Single zone RTU, generic description, with power exhauster

Single zone RTU, controlled by a programmable thermostat. Single zone RTU, generic description, with power exhauster Rooftop Units CV Reheat RTU Reheat Reheat system RTU, serving electric reheat coils, w/dehumidification cycle & RA CO2 override of OAD CV Single Zone RTU SZ (from PC) RTU SZ Generic RTU SZ Multiple Units

More information

Computing Services Center

Computing Services Center Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES HVAC non CENTRAL PLANT 1) Zone Level Scheduling & Override for all air handlers (supply and exhaust) to match occupied hours by zone DDC or occupancy sensors (OS) allowed. (403.2.4.3,

More information

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-05 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Galveston (TAMU-G) Galveston, Texas Submitted to Texas A&M University

More information

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3 Existing System Evaluation Executive Summary The MBNA Career Services Center is a 44,000 square foot, 4-story office type building at Penn State University, University Park Campus. The building is located

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS 1 AIR HANDLING UNIT TRENDS 2 1. The trending charts provided on the following pages prepared as part of a retro-commissioning investigation. The

More information

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT Taylor Engineering 1080 Marina Village Parkway, Suite 501 Alameda, CA 94501-1142 (510) 749-9135 Fax (510) 749-9136 LLC HVAC DESIGN INTENT PART 1 - GENERAL 1.1 Overview A. The project consists of a 3-story

More information

PURCHASING DEPARTMENT LOUISVILLE, KENTUCKY

PURCHASING DEPARTMENT LOUISVILLE, KENTUCKY PURCHASING DEPARTMENT LOUISVILLE, KENTUCKY Date: June 14, 2017 Invitation No: IB-096-17 Title: Student Activity Center Renovation and Addition, Bid Package V Addendum No. Three (3) The following shall

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER Printed in the USA ADSOOASHPRAE 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located

More information

4. OVERVIEW OF MECHANICAL SYSTEM

4. OVERVIEW OF MECHANICAL SYSTEM 4. OVERVIEW OF MECHANICAL SYSTEM The 87,000 SF SLCC is served by six (6) Trane M-Series Climate Changer Air Handing Units (AHUs). Each unit serves a distinct zone within the facility that is unique in

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Continuous Commissioning: A Valuable Partner to Retrofit Projects Continuous Commissioning: A Valuable Partner to Retrofit Projects Yeqiao Zhu Aamer Athar Kenneth Banks Ph.D. PE, CEM PE, CEM Energy Systems Laboratory Sempra Energy Solutions Sempra Energy Solutions Charles

More information

DX-9100 Applications from Engineering Services

DX-9100 Applications from Engineering Services System 9100 Technical Manual 636.4 Application Examples Section Technical Bulletin Issue Date 0896 DX-9100 Applications from Engineering Services Introduction Page 3 Overview 3 Air Handling Unit Applications

More information

HVAC Controls Upgrades: Requirement Details ( )

HVAC Controls Upgrades: Requirement Details ( ) REQUIRED CONTROLS/FEATURES To qualify the upgrade must add or substantially modify 3 or more sequences/system capabilities. Also, all sequences and items listed under the required section are needed in

More information

To: Steve Ardolf, MSU Mankato From: Chris Plum, CEE. CC: Tim Ellingson, CEE. Angela Vreeland, CEE Dan Briese, MSU Mankato Date: April 21, 2014.

To: Steve Ardolf, MSU Mankato From: Chris Plum, CEE. CC: Tim Ellingson, CEE. Angela Vreeland, CEE Dan Briese, MSU Mankato Date: April 21, 2014. To: Steve Ardolf, MSU Mankato From: Chris Plum, CEE CC: Tim Ellingson, CEE Angela Vreeland, CEE Dan Briese, MSU Mankato Date: April 21, 2014 Re: MSU Mankato Verification State PBEEEP Executive Summary

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

DIGI-VAV APPLICATIONS

DIGI-VAV APPLICATIONS DIGI-VAV DIGI-VAV APPLICATIONS Digi-VAV: An optimization kit for Variable Air Volume Air Handling Units (VAV AHU) that ensures individual zone indoor air quality (IAQ), and minimizes system energy consumption.

More information

Virginia Tech Standards for Building Automation System

Virginia Tech Standards for Building Automation System March 1, 2016 Virginia Tech Standards for Building Automation System A. Existing Conditions: The Campus Building Automation System is Siemens Apogee and controls all significant campus facilties. Virginia

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR Printed in the USA ADSOOASHPOA 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located on its front

More information

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN September 30, 2015 PBA Project No. 2015.0140.00 PETER BASSO ASSOCIATES INC. CONSULTING ENGINEERS 5145 LIVERNOIS ROAD,

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and

More information

Building Automation System (BAS) Design Criteria

Building Automation System (BAS) Design Criteria 25 0520 Building Automation System (BAS) Design Criteria 1. Design Statement a. During the various design phases of this project, the Engineer will develop options and strategies for selection of the appropriate

More information

American University Design Standards

American University Design Standards 25 95 00 CONTROL SEQUENCES FOR HVAC PART 1. GENERAL 1.01 SECTION INCLUDES A. Description of Work B. Control Sequences General Requirements C. System Specific Control Sequences 1.02 RELATED DOCUMENTS A.

More information

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana ADDENDUM NO. 2 RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana TO: All Bidders Gentlemen: This Addendum

More information

HVAC Mandatory Provisions Part II, Page 1

HVAC Mandatory Provisions Part II, Page 1 HVAC Mandatory Provisions Part II, Page 1 Mandatory Equipment Efficiency Worksheet (6.4.1.1) System Equipment Type Size Category (Tables 6.8.1A through K) Sub-Category or Rating Condition Units of Efficiency

More information

Physical Plant Complex

Physical Plant Complex Continuous Commissioning Report For the Physical Plant Complex Building #1156 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

FACILITY ACTION PLAN

FACILITY ACTION PLAN FACILITY Mary Baker Russell Music Center CURRENT ENERGY USE INDEX (EUI) 293 kbtu/sq Ft 26.83 kwh/sq Ft FACILITY LIASON(S) David Robbins Chair of the Department of Music FACILITY ACTION PLAN TARGET EUI

More information

Harrington Tower Building

Harrington Tower Building Continuous Commissioning Report For the Harrington Tower Building Building #435 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Song Deng, P.E. Assistant Director Energy Systems Laboratory Texas A&M University College Station, TX

Song Deng, P.E. Assistant Director Energy Systems Laboratory Texas A&M University College Station, TX Room Temperature ontrol during Season Switchover with Single Duct Variable Air Volume System without Reheat henggang Liu Research Associate Song Deng, P.E. Assistant Director Homer L. Bruner, Jr., EM Mechanical

More information

Technical Assignment 3 11/15/04. Executive Summary

Technical Assignment 3 11/15/04. Executive Summary Executive Summary This report is an analysis of the existing systems within the Outreach Innovation Building in University Park, PA. One significant design criteria was a lower than average noise criteria

More information

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled

More information

Appendices. Included in this section are

Appendices. Included in this section are Appendices Included in this section are Appendix A Building Overview Appendix B Alternative Mechanical Designs Appendix C Integration of Structural System and Constructability 68 Appendix A Building Overview

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

An HVAC Audit of the Canberra Institute of Technology

An HVAC Audit of the Canberra Institute of Technology An HVAC Audit of the Canberra Institute of Technology 30 th November 2016 Amnon Holland amnon.holland@esbsconsult.com.au www.esbsconsult.com.au Agenda Overview CIT and various other sites The sites Type

More information

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION Telephone:

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION Telephone: ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION 2.0 www.addison-hvac.com Telephone: +1.407.292.4400 1 SEQUENCE OF OPERATION The ALC controller is turned on

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

Power and Energy Management Solutions

Power and Energy Management Solutions Selection Guide Power and Energy Management Solutions Heating, Ventilating and Air Conditioning (Bulletin 1414) Selection Guide 2 HVAC Selection Guide Instrumentation Selection Checklist Use the following

More information

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone:

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone: ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION 2.0 www.addison-hvac.com Telephone: +1.407.292.4400 1 2 OCCUPIED MODE: When the program control source calls for

More information

Memorial Student Center Complex (Bldg. 454)

Memorial Student Center Complex (Bldg. 454) ontinuous ommissioning Assessment eport For Memorial Student enter omplex (Bldg. 5) By henggang Liu David E. laridge, Ph.D., P.E. omer L. Bruner, Jr., EM ontact: David E. laridge (979-85-80) omer L. Bruner,

More information

Re-Engineering Votey Hall:

Re-Engineering Votey Hall: Re-Engineering : Investment of Deferred Maintenance $$ into an aged Engineering Building by: Lynn Wood Retro-Commissioning Engineer Physical Plant Department New Construction: STEM $104M Central Campus

More information

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner ESL-TR-99/12-09 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Commerce (TAMU-Commerce) Commerce, Texas Submitted to Texas

More information

MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY

MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION CONDITIONS FACILITIES MASTER PLAN MAY 2018 57 MECHANICAL ASSESSMENT MECHANICAL ASSESSMENT This report section includes an overview of the existing

More information

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1

More information

OPERATIONS DIVISION STANDARD OPERATING PROCEDURE

OPERATIONS DIVISION STANDARD OPERATING PROCEDURE OPERATIONS DIVISION STANDARD OPERATING PROCEDURE Freeze Protection Protocol DATE: October 27, 2014 PURPOSE This Operations Division Operating Policy and Procedure (OD/OP) establishes procedures to be followed

More information

Continuous Commissioning Report

Continuous Commissioning Report Continuous Commissioning Report for the Bush Academic Facility (Bldg. 1607) Submitted to: Office of Energy Management Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Technical Assignment 3. Mechanical Systems Existing Conditions Evaluation

Technical Assignment 3. Mechanical Systems Existing Conditions Evaluation Technical Assignment 3 Mechanical Systems Existing Conditions Evaluation The Milton Hershey School New Supply Center Prepared for: William P. Bahnfleth, Ph.D., P.E., Professor Department of Architectural

More information

SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,

More information

Mechanical Systems Existing Conditions Evaluation. Instructor: Dr. Bahnfleth. November 12, Thesis Building Sponsor s: INOVA Fairfax Hospital

Mechanical Systems Existing Conditions Evaluation. Instructor: Dr. Bahnfleth. November 12, Thesis Building Sponsor s: INOVA Fairfax Hospital David J. Peterson Mechanical Option Mechanical Technical Report #3 The INOVA HEART INSTITUTE AT, Falls Church, VA. Mechanical Technical Report #3 Mechanical Systems Existing Conditions Evaluation Instructor:

More information

FUNCTIONAL DESIGN SPECIFICATION

FUNCTIONAL DESIGN SPECIFICATION Issue Date: Issued To: Revision: FUNCTIONAL DESIGN SPECIFICATION Specification Number: SP-XXXX Company Name Signature Date Issued By: Manutec Ltd. Approved By: Approved By: Approved By: Approved By: Authorised

More information

Sigler Controls Technical Development Program

Sigler Controls Technical Development Program Sigler Controls Technical Development Program SIGLER CONTROLS TDP o Define BIOT and associated industries o Learn fundamental Controls building blocks o Understand 3 rd Party Integration challenges SIGLER

More information

DACC Health Sciences Building Air Handler Assessment/Study

DACC Health Sciences Building Air Handler Assessment/Study DACC Health Sciences Building Air Handler Assessment/Study NMSU Facilities and Services Department P.O. Box 30001 Las Cruces, NM 88003-8001 June 14, 2016 Final Submittal 1065 S. Main St., Bldg. D, Ste.

More information

Continuous Commissioning SM Report. For. Wing 86, Chemistry Complex (Building # 376) Hui Chen Song Deng Homer L. Bruner, Jr., CEM.

Continuous Commissioning SM Report. For. Wing 86, Chemistry Complex (Building # 376) Hui Chen Song Deng Homer L. Bruner, Jr., CEM. Continuous Commissioning SM Report For Wing 86, Chemistry Complex (Building # 376) By Hui Chen Song Deng Homer L. Bruner, Jr., CEM Contact: Song Deng (979-862-1234) Homer L. Bruner, Jr. (979-862-7185)

More information

HVAC Myths and Realities Trane Engineers Newsletter Live Series

HVAC Myths and Realities Trane Engineers Newsletter Live Series HVAC Myths and Realities Trane Engineers Newsletter Live Series AGENDA Low delta T is unavoidable 55 F supply air temperature is adequate for today s loads ASHRAE Standard 15 has to be updated before new

More information

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee ASHRAE WILL GIVE YOU THE WORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique CTTC

More information

Electrical Systems Existing Conditions and Building Load Summary Broadway Plaza, Rochester, MN. Appendix A

Electrical Systems Existing Conditions and Building Load Summary Broadway Plaza, Rochester, MN. Appendix A Appendix A Single Line Diagram Power Riser Diagram Dimming System Schematic Diagrams Dry-Type Transformer Schedule Primary Lamp and Ballast Table Mechanical Equipment Table Utility Rate Structure Breakdown

More information

MECHANICAL INFRASTRUCTURE ASSESSMENT FOR VICTOR VALLEY COLLEGE

MECHANICAL INFRASTRUCTURE ASSESSMENT FOR VICTOR VALLEY COLLEGE MECHANICAL INFRASTRUCTURE ASSESSMENT FOR VICTOR VALLEY COLLEGE 18422 Bear Valley Road Victorville, CA 92395 Date 25 September 2012 dha Job No. 12155 TABLE OF CONTENTS I. Purpose.... Page 1 II. Existing

More information

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE

More information

Your Home. Jacco & Assoc.

Your Home. Jacco & Assoc. Your Home Fan on with call for heating or cooling Heating on with call from space thermostat Stage as required to maintain The 75F Basics adj. - First stage of heating shall be heat pump Cooling on with

More information

Designing Mega-AHUs BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE

Designing Mega-AHUs BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE his article was published in ASHRAE Journal, April 2018. Copyright 2018 ASHRAE. Posted at www.ashrae.org. his article may not be copied and/or distributed electronically or in paper form without permission

More information

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information Charles M. LeMaistre PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and

More information

ASHRAE Guideline 36 Advanced HVAC Control Sequences

ASHRAE Guideline 36 Advanced HVAC Control Sequences ASHRAE Guideline 36 Advanced HVAC Control Sequences Rick Stehmeyer - Senior Engineer Matt Napolitan, P.E., CCP, CPMP, LEED AP BD+C - Principal Image Source: http://worldatdistance.com/2013/10/07/the-complete-noobs-guide-to-making-a-website//

More information

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings INTRODUCTION TO: ASHRAE STANDARD 90.1, 2013 HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings Rocky Mountain ASHRAE Technical Conference, April 29, 2016 SEAN BEILMAN, P.E.,

More information

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size...

More information

2009 IECC Commercial Mechanical Requirements

2009 IECC Commercial Mechanical Requirements BUILDING ENERGY CODES UNIVERSITY 2009 IECC Commercial Mechanical Requirements Ken Baker PNNL-SA-66171 Learning(Objec-ves(( ( 1. Find(minimum(equipment(efficiency(requirements( and(recite(at(least(3(common(terms(for(measuring(

More information

Technical Report #2. Newseum and Freedom Forum Headquarters. Washington, D.C. Ryan Wise Lighting/Electrical Prof. Dannerth November 2, 2007

Technical Report #2. Newseum and Freedom Forum Headquarters. Washington, D.C. Ryan Wise Lighting/Electrical Prof. Dannerth November 2, 2007 Technical Report #2 Ryan Wise Lighting/Electrical Prof. Dannerth November 2, 2007 Newseum and Freedom Forum Headquarters Washington, D.C. Table of Contents Power Distribution Systems Executive Summary

More information

Pharmaceutical Facility Design

Pharmaceutical Facility Design PhEn-602 Pharmaceutical Facility Design J. Manfredi Notes 9A PhEn-602 J. Manfredi 1 Primary & Secondary HVAC units Primary Primary air handling unit arrangement: One unit is responsible for all of the

More information

Building Systems: HVAC

Building Systems: HVAC Building Systems: HVAC Committee on Microbiomes of the Built Environment June 21, 2016 Washington DC Dennis Stanke (dstanke47@gmail.com) Retired rane (IR) Outline Ventilation Systems Moisture sources Low

More information

Existing Mechanical System Operation

Existing Mechanical System Operation majority of the air handlers. There are louvers along the north side of the building that allow for outdoor air to come in and feed the air handlers. On levels 4-8 the research laboratories are variable

More information

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges. Service Literature The LGH/LCH high and standard efficiency 5, 0, 5 and 50 ton (, 0.7, 58. and 75.9 kw) units, are configure to order units (CTO) with a wide selection of factory installed options. The

More information

MEP CONDITION ASSESSMENT

MEP CONDITION ASSESSMENT MAINE EAST MEP CONDITION ASSESSMENT MAINE EAST HIGH SCHOOL This report section includes an overview of the existing mechanical cooling and heating systems serving Maine East High School. The sections will

More information

REQUEST FOR PROPOSALS FOR THE PROVISION OF PREVENTIVE MAINTENANCE ON FACILITY HVAC SYSTEMS FOR SKOKIE PUBLIC LIBRARY

REQUEST FOR PROPOSALS FOR THE PROVISION OF PREVENTIVE MAINTENANCE ON FACILITY HVAC SYSTEMS FOR SKOKIE PUBLIC LIBRARY REQUEST FOR PROPOSALS FOR THE PROVISION OF PREVENTIVE MAINTENANCE ON FACILITY HVAC SYSTEMS FOR SKOKIE PUBLIC LIBRARY Skokie Public Library is requesting proposals for a contract for the provision of preventive

More information

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Code No. LIT-1201737 Release 1.2 Issued January 10, 2005 Document Introduction.................................................

More information

Instruction, Operation, and Maintenance: Controls Software Versions: R37+

Instruction, Operation, and Maintenance: Controls Software Versions: R37+ Instruction, Operation, and Maintenance: Controls Software Versions: R37+ VPR Series VPRX Series VPRE Series VPRP Series Version October 2011 Table of Contents Safety... 3 Special Design Requests... 3

More information

HVAC DISTRIBUTION and DELIVERY SYSTEMS

HVAC DISTRIBUTION and DELIVERY SYSTEMS HVAC DISTRIBUTION and DELIVERY SYSTEMS (Part 1) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 REMINDER HVAC = Heating, Ventilating, Air-Conditioning The AC part of HVAC implies a system that

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc. System Components with ` Emphasis on Packaged Rooftop Application and Installation Jerry Cohen President Jacco & Assoc. Agenda Define and relate in practical terms the following components: System Effect

More information

Air Handler Unit (AHU) Equipment Purchase and Delivery Invitation to Bid

Air Handler Unit (AHU) Equipment Purchase and Delivery Invitation to Bid DATE: February 1, 2018 SUBJECT: Letter of Clarification #2 RE: TO: Air Handler Unit (AHU) Equipment Purchase and Delivery Invitation to Bid All Prospective Bidders Houston First Corporation ( HFC ) issues

More information

RCE # April 30, 2013 Centennial School District William Tennent HS, Region 3 ES, Region 1 ES, Region 2 ES

RCE # April 30, 2013 Centennial School District William Tennent HS, Region 3 ES, Region 1 ES, Region 2 ES RCE #12-4181 April 30, 2013 Centennial School District William Tennent HS, Region 3 ES, Region 1 ES, Region 2 ES Commissioning Progress Report The Commissioning Technician returned to visit R2ES and R1ES

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

10+ HVAC Troubleshooting Tips for Healthcare Facilities Jerry Hirsch JCI Facility O&M Performance Development Manager.

10+ HVAC Troubleshooting Tips for Healthcare Facilities Jerry Hirsch JCI Facility O&M Performance Development Manager. 10+ HVAC Troubleshooting Tips for Healthcare Facilities Jerry Hirsch JCI Facility O&M Performance Development Manager 2019 WHEA Webinar Johnson Controls Institute Overview Operation & Maintenance (O&M)

More information

Auburn University Basketball Arena:

Auburn University Basketball Arena: Auburn University Basketball Arena: How Building Data Analytics Achieved Energy and O&M Savings While Improving Comfort and Sustainability Eric Moore, PE, CEM, Auburn University Hadas Webb, CEM, Cimetrics

More information

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx Case Study: Furman University Charles H. Townes Center for Science Michael K. Mantai, PE, CCP President System WorCx AIA Quality Assurance Learning Objectives 1. Case study example of Chilled Beam technology

More information

AHU Air Handling Unit Fundamentals. j.ilangumaran

AHU Air Handling Unit Fundamentals. j.ilangumaran AHU Air Handling Unit Fundamentals j.ilangumaran Objectives Review primary components of an AHU Understand the basic progression and advantages of advanced AHU control Understand the basic control sequences

More information

Your Home. Jacco & Assoc. Fan on with call for heating or cooling Heating on with call from space thermostat Stage as

Your Home. Jacco & Assoc. Fan on with call for heating or cooling Heating on with call from space thermostat Stage as Your Home Fan on with call for heating or cooling Heating on with call from space thermostat Stage as required Controlling to maintain 75F HVAC adj. Systems First stage of heating shall be heat pump Cooling

More information

Welsh Commissioning Group, Inc.

Welsh Commissioning Group, Inc. Ongoing Commissioning with Building Automation System and Data Loggers Bryan W. Welsh, P.E. President Welsh Commissioning Group, Inc. AIA Quality Assurance Learning Objectives 1. General understanding

More information

I. Introduction and Arrangement

I. Introduction and Arrangement Joseph Firrantello - Mechanical Option Primary Faculty Consultant: Freihaut Laboratory Facility, Eastern Pennsylvania Mechanical Assignment 3 Existing Conditions Report 11.14.03 Executive Summary The purpose

More information

ASHRAE Illinois Chapter 2015 Excellence in Engineering Awards

ASHRAE Illinois Chapter 2015 Excellence in Engineering Awards ASHRAE Illinois Chapter 2015 Excellence in Engineering Awards PROJECT Chicago Vocational Career Academy Chicago, Illinois OWNER Chicago Public Schools PREPARED FOR American Society of Heating Refrigerating

More information

NYC Department of Education

NYC Department of Education Asset: J. K. ONASSIS HS FOR INT CAREERS-M, 120 WEST 46 STREET, New York, 10036 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-11 11:37 AM 2017-12-26 12:18 PM Asset Data Are there

More information

Terminal. Las Vegas, NV. Technical

Terminal. Las Vegas, NV. Technical McCarran International port Terminal 3 Technical Assignment 3 Mechanical System Existing Conditions Evaluation December 3, 2007 Prepared By: Faculty Advisor: Dr. William Bahnfleth, Ph.D., P..E. Table of

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Continuous Commissioning Report

Continuous Commissioning Report ontinuous ommissioning Report for the Price Hobgood Building (Bldg. 1507) Submitted to: Office of Energy Management Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

COMcheck Software Version Review Mechanical Compliance Certificate

COMcheck Software Version Review Mechanical Compliance Certificate COMcheck Software Version 4.0.7.2 Review Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: Benton County Health Project

More information