AIR CONDITIONERS DATA BOOK. Model PUHY-P250YHM-A PFD-P250VM-E PFD-P500VM-E

Size: px
Start display at page:

Download "AIR CONDITIONERS DATA BOOK. Model PUHY-P250YHM-A PFD-P250VM-E PFD-P500VM-E"

Transcription

1 AIR CONDITIONERS Model PUHY-P0YHM-A PFD-P0VM-E PFD-P00VM-E DATA BOOK

2

3 Close control PUHY-P-YHM-A PFD-P-VM-E CONTENTS. Specifications - Main Features - List of Possible Combinations of Indoor and Outdoor Units - Unit Specifications. Capacity Curves - Cooling Capacity - Cooling Input - Part Load Performance - SHF Curves - Correction by refrigerant piping length - Operation limit. Sound Levels - Noise Level - NC Curves - Fan Characteristics Curves. External Dimensions. Electrical Wiring Diagrams. Refrigerant Circuit Diagram And Thermal Sensor 7. System Design 7- Refrigerant Piping System 7- Control Wiring 7- Types of switch settings and setting methods 7- Sample System Connection 7- External input/output specifications 7- System Rotation Control 7-7 Notes on the use of optional accessories 8. Air Conditioning the Computer Room 8- Main Features of the Floor-Duct Air Conditioners 8- Features of air-conditioner for computer room 8- Step-by-Step Plan for the Implementation of the Air-Conditioning 8- Conditions for the Installation of Computer-Room Air Conditioners 8- Setting the Air conditioners 8- Automatic Control of the Computer Room 9. Maintenance/Inspection 9- Maintenance/Inspection Schedule

4

5 UP UP POWER SUPPLY UNIT MODEL PAC-SC0KUA POWER RATING WEIGHT.kg SERIAL No. MITSUBISHI ELECTRIC CORPORATION POWER SUPPLY UNIT MODEL PAC-SC0KUA POWER RATING WEIGHT.kg SERIAL No. MITSUBISHI ELECTRIC CORPORATION. Specifications -.Main Features () List of Models PUHY-P0YHM-A Outdoor Unit 0HP(Down flow): PFD-P0VM-E 0HP(Down flow): PFD-P00VM-E PFD-type indoor units cannot be connected to outdoor units other than the ones specified above. PFD-type indoor units and other types of indoor units cannot coexist in the same refrigerant system. It is necessary to change pulley and V-belt when using it by the power supply frequency 0Hz. For restrictions when the PFD-type indoor units are connected (related to the system), see P0. <0HP System> G-0A } Indoor Unit TB7 Outdoor Unit PUHY-P0YHM-A TB Indoor Unit PFD-P0VM-E V DC M-NET PAC-SC0KUA When using a PFD-P0VM-E as an indoor unit, connect an outdoor unit PUHY-P0YHM-A to each indoor unit and operate with a built-in remote control for the indoor unit. : Bold line indicates refrigerant piping (gas/liquid). This system consists of single refrigerant circuit. : Indicates TB-type transmission line that connects the indoor and outdoor units. This system consists of single refrigerant circuit. : Indicates TB7-Type transmission line that allows the unit to communicate with the controller. <0HP System> Two refrigerant circuits G-0A Outdoor Unit PUHY-P0YHM-A TB7 TB Indoor Unit PFD-P00VM-E V DC M-NET TB7 PUHY-P0YHM-A TB PAC-SC0KUA When using a PFD-P00VM-E as an indoor unit, connect PUHY-P0YHM-A outdoor units to each indoor unit and operate with a built-in remote control for the indoor unit. At factory shipment, this model of indoor unit is designed and set to accommodate a single refrigerant circuit. Connection of two refrigerant circuits to the indoor unit requires setting change and pipe work. : Bold line indicates refrigerant piping (gas/liquid). This system consists of two refrigerant circuits. : Indicates TB-type transmission line that connects the indoor and outdoor units. This system consists of two refrigerant circuits. : Indicates TB7-type transmission line that allows the unit to communicate with the controller.

6 -. List of Possible Combinations of Indoor and Outdoor Units Model Name Indoor unit Outdoor unit 0HP system PFD-P0VM-E PUHY-P0YHM-A Cooling Heating System capacity kw 8.0. System Power input kw System current A.7/.9/.././. 0HP system PFD-P00VM-E PUHY-P0YHM-A x Cooling Heating /0.8/9.7.7/0.0/9. : Refer to the following pages for detailed specifications of each unit. : They were measured at operation under the following conditions: <Cooling> Indoor:7 CDB/9 CWB Outdoor: CDB <Heating> Indoor:0 CDB Outdoor: 7 CDB/ CWB Pipe length:7.m, Height difference:0m

7 -. Unit Specifications () Outdoor Unit Model name Capacity Power source Power input Current Fan Compressor Type Quantity Airflow rate Motor output Type Motor output kw kw A m /min kw kw Crankcase heater kw Heat exchanger Refrigerant / Lubricant External finish External dimension H x W x D mm Protection High pressure protection devices Compressor Fan Inverter circuit (COMP./FAN) Refrigerant High press. pipe piping diameter Low press. pipe Noise level Net weight Note: db(a) kg PUHY-P0YHM-A (-BS) connected with PFD series Cooling Heating 8.0. N ~ 80/00/V 0/0Hz.8../0.9/0../0./0. Propeller fan x 8 0. Hermetic x Salt resistant fin R0A/MEL Pre-coated galvanized steel sheets (+ powder coating for -BS type) <MUNSEL Y 8/ or similar>,70 (without legs,0) x 90 x 70 High pres. Sensor & High pres. Switch at.mpa Over heat protection Thermal switch Over-heat protection, Over current protection ø9. Brazed (ø.7 for over 90m) ø. Brazed 7 00 *. Cooling/Heating capacity indicates the maximum value at operation under the following condition. <Cooling> <Heating> Indoor : 7 CDB / 9 CWB Indoor : 0 CDB Outdoor : Outdoor : CDB 7 CDB / CWB Pipe length : 7.m Height difference : 0m *. It is measured in anechoic room. ** Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items shall be referred to the Installation Manual. () Indoor Unit Model name System capacity Power source Power input Current Type x Quantity Airflow rate Fan External static pressure Motor Output Refrigerant External finish External dimensions HxWxD Protection devices (Fan) Refrigerant piping diameter Single refrigerant circuit Two refrigerant circuit Refrigerant piping allowable length Noise level Heat exchanger Air filter Net weight Note: PFD-P0VM-E PFD-P00VM-E Cooling Heating Cooling Heating kw N~80/00/V(0Hz), 00/V(0Hz) kw..0 A./.0/.9 9./9.0/8.7 Sirocco fan x Sirocco fan x m /min 0 0 Pa 0 0 kw.. R0A Galvanized steel plate (with polyester coating) <MUNSEL.9GY 8./0.(White) 7.GB./.(Blue) or similar> mm,90 x,80 x 780,90 x,980 x 780 Thermal switch Liquid pipe ø 9. Brazed (ø.7 for over 90m) Liquid pipe ø.88 Brazed Gas pipe ø. Brazed Gas pipe ø 8.8 Brazed - Liquid pipe ø 9. Brazed (ø.7 for over 90m) Gas pipe ø. Brazed m 0 0 db(a) 9 Cross fin (Aluminum plate fin and copper tube) PP Honeycomb fabric (washable) kg 80 0 *. Heating can be used only by the indoor warming-up. *. At factory shipment, this model of indoor unit is designed and set to accommodate a single refrigerant circuit. Connection of two refrigerant circuits to the indoor unit requires setting change and pipe work. ** Installation/foundation work, electric connection work, duct work, insulation work, power source switch and other items are not specified in the specifications.

8 . Capacity Curves -. Cooling Capacity. Capacity correction coefficient Indoor unit inlet temperature ( CWB) Outdoor unit inlet temperature ( CDB) -. Cooling Input Input Correction Coefficient Indoor unit inlet temperature ( CWB) Outdoor unit inlet temperature ( CDB) The correction curves indicate the values measured at the point where the compressor was operated at its maximum capacity. indicates the standard value.

9 -. Part Load Performance 0HP System Indoor Unit : PFD-P0VM-E Outdoor Unit : PUHY-P0YHM-A Outdoor unit inlet temp. ( CDB) Cooling Capacity (kw) 00% Capacity 90% Capacity 80% Capacity 70% Capacity 0% Capacity 0% Capacity 0% Capacity 0 C C C C C C HP System Indoor Unit : PFD-P00VM-E Outdoor Unit : PUHY-P0YHM-A Outdoor unit inlet temp. ( CDB) Cooling Capacity (kw) 00% Capacity 90% Capacity System Power input (kw) * Indoor air temperature condition: 7 CDB/9 CWB 80% Capacity System Power input (kw) 70% Capacity 0% Capacity 0% Capacity 0% Capacity 0% Capacity 0 C C C C C C * Indoor air temperature condition: 7 CDB/9 CWB

10 -. SHF Curves Standard Capacity Ratio % 0%0%00% 90% 80% 70% Indoor Temperature 7 CDB 0.8 SHF RH (%) Standard Capacity Ratio 0% 0%0%00% 90% 80% 70% Indoor Temperature CDB SHF RH (%) Operation Temparature Range: Indoor : CWB~ CWB Outdoor: - CDB~ CDB (RH : 0~80%) Standard Point " " : Indoor : 7 CDB/9 CWB Outdoor: CDB/-

11 Standard Capacity Ratio 0% 0% 00% 90% 80% 70% Indoor Temperature CDB SHF RH (%) Standard Capacity Ratio 0% 0%00% 90% 80% 70% Indoor Temperature 0 CDB SHF RH (%) Operation Temparature Range: Indoor: CWB~ CWB Outdoor: - CDB~ CDB (RH: 0~80%) 7

12 -. Correction by refrigerant piping length To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacity correction factor based on the refrigerant piping equivalent length in the table below. Capacity correction coefficient Piping equivalent length (m) How to obtain piping equivalent length Equivalent length = (Actual piping length to the farthest indoor unit) + (0.0 number of bent on the piping)m -. Operation limit Cooling Indoor temperature ( CWB) Outdoor temperature ( CDB) * The height between the Outdoor PUHY-P-YHM-A and Indoor could make the running temperature range narrow. For details refer to P9, 7- Refrigerant Piping System. Heating Indoor temperature ( CDB) Outdoor temperature ( CWB) 8

13 . Sound Levels -. Noise Level () Outdoor Unit m Measurement location m Series Noise Level (db [Type A]) PUHY-P0YHM-A 7 () Indoor Unit m Measurement location m Series Noise Level (db [Type A]) PFD-P0VM-E 9 PFD-P00VM-E 9

14 -. NC Curves PUHY-P0YHM-A (External static pressure 0Pa) Hz Hz 0Hz 00Hz 000Hz 000Hz 000Hz 8000Hz db(a) Standard 0/0Hz NightMode 0/0Hz When Night Mode is set,the A/C system's capacity is limited. The system could return to normal operation from Night Mode automaticall in the case that the operation condition is severe Standard 0/0Hz Night Mode 0/0Hz OCTAVE BAND SOUND LEVEL (db) NC-0 NC-0 NC-70 NC-0 NC-0 0 Approximate minimum audible limit on NC-0 continuous noise 0 Hz Hz 0Hz 00Hz 000Hz 000Hz 000Hz 8000Hz OCTAVE BAND CENTER FREQUENCIES (Hz) PFD-P0VM-E (External static pressure 0Pa) Hz Hz 0Hz 00Hz 000Hz 000Hz 000Hz 8000Hz db(a) PFD-P00VM-E (External static pressure 0Pa) Hz Hz 0Hz 00Hz 000Hz 000Hz 000Hz 8000Hz db(a) , OCTAVE BAND PRESSURE LEVEL (db) 0dB = 0µPa NC-70 NC-0 NC-0 NC-0 NC-0 0 Approximate minimum audible limit on NC-0 continuous noise 0 Hz Hz 0Hz 00Hz 000Hz 000Hz 000Hz 8000Hz OCTAVE BAND CENTER FREQUENCIES (Hz) OCTAVE BAND PRESSURE LEVEL (db) 0dB = 0µPa NC-0 NC-70 NC-0 NC-0 NC-0 0 Approximate minimum audible limit on NC-0 continuous noise 0 Hz Hz 0Hz 00Hz 000Hz 000Hz 000Hz 8000Hz OCTAVE BAND CENTER FREQUENCIES (Hz) 0

15 -. Fan Characteristics Curves 000 PFD-P0VM-E : 0/0Hz, standard Total static pressure (Pa) Output.7kW Fan rotation speed 00rpm 00rpm 000rpm 900rpm 800rpm Internal resistance Air volume (m /min) 0Hz 0Hz No Rotational speed (rpm) Motor pulley ø0-b--8 ø-b--8 ø-b--8 ø-b--8 ø-b--8 ø70-b--8 ø0-b--8 ø70-b--8 ø0-b--8 Pulley and V-belt is procured on site. Fan pulley ø00-b-- ø-b-- ø-b-- ø-b-- ø0-b-- ø80-b-- ø80-b-- ø-b-- ø-b-- V-belte B8 B9 B0 B B B B B7 B Motor pulley ø-b--8 ø80-b--8 ø70-b--8 ø-b--8 ø-b--8 ø0-b--8 ø70-b--8 ø0-b--8 - Fan pulley ø0-b-- ø80-b-- ø80-b-- ø80-b-- ø00-b-- ø-b-- ø-b-- ø-b-- - V-belte B B B B B B B0 B9-800 PFD-P00VM-E : 0/0Hz, standard Total static pressure (Pa) Output.kW 800rpm Internal resistance 00rpm Fan rotation speed 000rpm 900rpm Standard Air volume (m /min) 0Hz 0Hz No Rotational speed (rpm) Motor pulley ø80-b--8 ø80-b--8 ø70-b--8 ø0-b--8 ø70-b--8 ø80-b--8 ø70-b--8 Fan pulley ø-b-- ø0-b-- ø0-b-- ø0-b-- ø80-b-- ø-b-- ø-b-- V-belte B B B B0 B B B Motor pulley ø0-b--8 ø80-b--8 ø0-b--8 ø0-b--8 ø0-b--8 ø70-b--8 ø0-b--8 Fan pulley ø0-b-- ø00-b-- ø80-b-- ø00-b-- ø-b-- ø-b-- ø-b-- V-belte B0 B B B B B8 B8 Pulley and V-belt is procured on site.

16 . External Dimensions PUHY-P0YHM-A(-BS) Unit : mm Refrigerant service valve <liquid> Refrigerant service valve <gas> Left side view Connecting pipe specifications Model PUHY-P0YHM Position dimensions for the refrigerant service valve Liquid A Gas B 7 Connection specifications for the refrigerant service valve Liquid ø9. Brazed Gas * ø. Brazed * Connect by using the connecting pipes (for bottom piping and front piping) that are supplied. 90 <Accessories> Top view Connecting pipe <Gas> Elbow(ID.XOD.) P0 pc. Pipe (ID.XOD.) P0 pc. <Liquid> Pipe (ID9.XOD9.) P0 pc. Note.Please refer to the next page for information regarding necessary spacing around the unit and foundation work..the detachable leg can be removed at site..at brazing of pipes,wrap the refrigerant service valve with wet cloth and keep the temperature of refrigerant service valve under 0 C. Detachable leg (front and back, points) Note * NO. For pipes For wires For transmission cables Usage Front through hole Bottom through hole Front through hole Front through hole Bottom through hole Front through hole Specifications 0X7 Knockout hole 0X9 Knockout hole ø or ø0 Knockout hole ø or ø7 Knockout hole ø Knockout hole ø Knockout hole 0 A B Control box Intake air 90 0 Intake air 0 70 Discharge air Intake air Service panel Front view (7 77) 8 (Mounting pitch) 70 Refrigerant service valve <liquid> Refrigerant service valve <gas> (Mounting pitch) Bottom view X-X0 Oval hole 9 8

17 PFD-P0VM-E Unit : mm Note. Be sure to set up a trap for Emergency drain piping. (Trap height:beyond 00mm) (Trap is not necessary for main drain piping.). Approve this figure because it is refused for the improvement and specification subject to change without notice.. Amputate a gas pipe/liquid pipe in the fixed height at the time of refrigerant circuit connection, and connect it with the local pipe. 00 or more 00 or more Air inlet Lamp Drain piping connection for humidifier or more 00 or more Indoor unit Service space Pipe execution space Unit surface figure Service space Indoor unit Unit front figure Changeover switch (SW9) <Nomal/Local> Filter Power supply:white Operating :Green Check :Yellow Failure :Red Air inlet Remote controller Lifting bolts (Accessory) Hole for the control wiring(ø0) Hole for the power supply(ø0) Main drain piping connection <Rp-/> Bolt holes:8-ø8 Hole for the power supply(body) <-ø knock out hole> <view from A> 00 Hole for the control wiring <ø knock out hole> 80 A Refrig. piping <gas> ø. braze Panel Air outlet Hole for liquid pipe connecting(ø) Hole for gas pipe connecting(ø) <Rp-/> Emergency drain piping connection <Rp-/> Air outlet Control box Hole for the power supply <ø knock out hole> Hole for the control wiring <ø knock out hole> Refrig. piping <liquid> ø9. braze Hole for gas pipe connecting(ø) Hole for liquid pipe connecting(ø) <Accessory> Lifting bolts pc. Front panel opening and closing key pc.

18 PFD-P00VM-E Unit : mm <Accessory> Lifting bolts pc. Front panel opening and closing key pc. Air inlet Note. Be sure to set up a trap for Emergency drain piping. (Trap height:beyond 00mm) (Trap is not necessary for main drain piping.). Approve this figure because it is refused for the improvement and specification subject to change without notice.. Amputate a gas pipe/liquid pipe in the fixed height at the time of refrigerant circuit connection, and connect it with the local pipe. Panel opening and closing dimension 00 or more Indoor unit Service space 00 or more Pipe execution space Unit surface figure Service space Indoor unit Drain piping connection for humidifier Main drain piping connecting<rp-/> Hole for gas pipe connecting(ø 8) Hole for No. gas pipe connecting(ø ) in refrig. circuit system Bolt holes:8-ø 8 Hole for No. liquid pipe connecting (ø ) in refrig. circuit system Hole for liquid pipe connecting(ø ) Hole for No. liquid pipe connecting(ø ) in refrig. circuit system or more Unit front figure 000 or more. It is necessary for the removal of the panel beyond 00mm. Filter Power supply:white Operating :Green Check :Yellow Failure :Red Failure :Red Air inlet Lamp Changeover switch (SW9) <Normal/Local> Remote controller Lifting bolts (Accessory) <Rp-/> Emergency drain piping connection <Rp-/> Hole for the power supply(ø 0) Hole for the control wiring(ø 0) <-ø knook out hole> Air outlet Hole for No. gas pipe connecting(ø ) in refrig. circuit system <view from A> Refrig. piping <gas> in refrig. circuit system type P0:ø 9.0 braze, type P0:ø. braze No. Hole for No. gas side pipe connecting(ø ) in refrig. circuit system Air outlet Hole for the power supply(body) 7 Panel Refrig. piping <liquid> in refrig. circuit system ø 9. braze No. Hole for No. liquid side pipe connecting (ø ) in refrig. circuit system Hole for gas side pipe connecting or No. liquid side pipe connecting(ø 8) in refrig. circuit system 00 Hole for the control wiring <ø knook out hole> Air outlet Control box A Hole for the power supply <ø knook out hole> Hole for the control wiring <ø knook out hole> Refrig. piping <liquid> in refrig. circuit system ø 9. braze No. Refrig. piping <liquid> ø.88 braze Refrig. piping <gas> in refrig. circuit system type P0:ø 9.0 braze, type P0:ø. braze No. Refrig. piping <gas> ø 8.8 braze Hole for liquid side pipe connecting or No. gas side pipe connecting(ø ) in refrig. circuit system

19 . Electrical Wiring Diagrams PUHY-P0YHM-A Fan motor (Heat exchanger) U V M W CN CN blue R D CN red R F,F,F AC0V.A T DSA Z U F F C7 Noise Filter R U Z Diode Bridge Z Z Z U U U R R F C C C C0 C9 C8 C7 C C C F AC0V.A T red white black R CNA CNB L L TB L TB N TB TB CN green TB L L L N Power Source N 0/0Hz 80/00/V L L L N <Symbol explanation> Symbol Explanation Sa,b -way valve H Pressure switch Pressure HS Discharge pressure LS sensor Low pressure 7C Magnetic relay(inverter main circuit) CT,, Current sensor(ac) CH Crankcase heater(for heating the compressor) DCL DC reactor LEV Linear HIC bypass,controls refrigerant expansion flow in HIC circuit LEVa,b valve Pressure control,refrigerant flow rate control SVa SVb Solenoid valve High pressure protection for the outdoor unit For opening/closing the bypass circuit under the O/S Outdoor unit heat exchanger capacity control Symbol SV9 TB TB TB7 TH TH TH TH TH TH7 THBOX THHS Z, FAN Board CNVDC CNINV F0 DC700V A T C0 C R0 IPM R CN CN8V blue CN red LED:CPU in operation CN red THBOX LED:Normal operation LED:Error CN blue C00 DCL R R * black red SC-P red 7C black SC-P CN CNV yellow CN CN C0 C C C R0 R R P N * FT-P FT-N red white C C C C7 R R R IGBT SC-L LED Normal operation(lit) /Error(blink) THHS SC-U SC-L C RSH SC-V CN CNTYP black SC-W black CT SC-L CT CT INV Board red white black red white black V U W MS Motor (Compressor) Solenoid valve Terminal block Explanation For opening/closing the bypass circuit Power supply Indoor/Outdoor transmission cable Central control transmission cable Thermistor Subcool bypass outlet temperature Pipe temperature Discharge pipe temperature ACC inlet pipe temperature Subcooled liquid refrigerant temperature OA temperature Control box internal temperature IGBT temperature Function setting connector P H 7C Sb SVa CNAC black CN0 CNDC pink CPU power supply circuit CN7 ZNR0 red U X0 CN0 X0 CNT0 Power failure detection circuit CN80 yellow CNT0 CN blue CN Control Board LED CN CNLVC red CNLVA CNLVB red CH Sa SV9 CN0 blue CN0 green SVb CN0 CN07 red CN08 black X0 X0 X0 X0 X07 X08 X09 X0 V SWU SWU 0's digit CN * 's digit Unit address setting OFF ON 0 SW OFF ON 0 SW Compressor ON/OFF output Error detection output LED:Lit when powered OFF ON 0 SW Function setting OFF ON 0 SW OFF ON 0 SW LED Display setting CNTYP black CNTYP green CNTYP green CN red CN CN990 CNAC red F0 AC0V.A T LED:CPU in operation yellow CNK blue CNN red CNS CND CN0 CN0 CN TB7 Power selecting connector ON OFF yellow CNS red CNIT CN0 red CN0 CN black CN * *.Single-dotted lines indicate wiring not supplied with the unit. *.Dot-dash lines indicate the control box boundaries. *.Refer to the Data book for connecting input/output signal connectors. *.Daisy-chain terminals (TB) on the outdoor units in the same refrigerant system together. *.Faston terminals have a locking function.make sure the terminals are securely locked in place after insertion.press the tab on the terminals to removed them. *.Control box houses high-voltage parts. Before inspecting the inside of the control box,turn off the power,keep the unit off for at least 0 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC0V or less. CN0 red M-NET power supply circuit M-NET Board CN0 CNS CNIT yellow red LED:Power supply to Indoor/Outdoor transmission line TB TB7 M M M M S TP TP * Indoor/Outdoor transmission cable Central control transmission cable Z Z M LEV M LEVa M LEVb TH TH7 TH TH LS HS TH TH L 7 t t 7 7 t t t t t t

20 u PFD-P0VM-E Dehumidify X I.B. CNA CN CN CN7V 7 F ZNR Inside section of control box TB SHIELD S B A TB ZNR CN DSA S.B. F L L L N TB CN CN TB TB TB AC A A BC B B C IFB X L L L CN CN L CNM RC Address (odd) Indoor unit Control wiring DC~0V LED display(failure) LED display(status) LED display(power supply) PE Power supply N~ 80/00/V(0Hz) 00/V(0Hz) SW9 Switch(normal/local) Power supply DC~V Distant location on/off <with voltage and current> Distant location on/off <no voltage or current> Power supply DC0V, AC00/00V Status output Failure output LED display(check) PE L L A B C D E F F90 ZNR X0 X0 X0 ZNR90 DSA X0 X07 TH TH TH TH LEV SYMBOL NAME MF Fan motor I.B. Indoor controller board S.B. Surge absorber board IFB External input/output board TB Power source terminal bed TB Transmission terminal bed TB Transmission terminal bed TB Terminal bed for distant location on/off <No voltage or current> TB Terminal bed for distant location display TB Terminal bed for distant location on/off <With voltage and current> F90 Fuse<-/A> F Fuse<A> ZNR, ZNR, ZNR90 Varistor DSA Surge absorber T Transformer LEV Electronic linear expan.valve F Contactor(fan I/D) F Over current relay (fan I/D) P Float switch TH Thermistor (inlet temp.detection) TH Thermistor (piping temp.detection/liquid) TH Thermistor (piping temp.detection/gas) TH Thermistor (outlet temp.detection) SW(I.B.) Switch (for mode selection) SW(I.B.) Switch (for capacity code) SW(I.B.) Switch (for mode selection) SW(I.B.) Switch (for model selection) SW9 Switch (normal/local) SW(I.B.) Switch (st digit address set) SW(I.B.) Switch (nd digit address set) SW(I.B.) Switch (connection No.set) SWC(I.B.) Switch (outlet/inlet temp.control) X Auxiliary relay(check) Z Auxiliary relay(fan) Z Auxiliary relay(fan failure detection) L LED display (failure) L LED display (status) L LED display (check) L LED display (power supply) RC Remote controller The signal input of the dehumidify order is to connect wiring referring to the bottom figure. (field supply and construction) Indoor unit External input adapter control board (PAC-SA88HA) Relay circuit CN SW (st digit) SW SW (nd digit) SWC SW SW8 SW SW7 SW SW SW CNT CND CNP CN CN90 CNT CN8 CN CN0 CN CN9 CN CN0 T Z Z P Z F Z FAN over current detection F F MF Note:. The dotted lines show field wiring.. The address setting of the indoor unit should always be odd.. The outdoor unit to which the indoor unit is connected with the transmission line, the address of the outdoor unit should be the indoor unit +0.. Mark indicates terminal bed, connector, board insertion connector or fastening connector of control board. Distant control panel CN Power (green) Z SW (brown) Z SW:Defumidify order Z:Relay (Contact : Minimum applicable load DCV ma or less) t t t t u u u

21 t t t t t t t t PFD-P00VM-E SWC SW SW8 SW SW7 SW Note:. The dotted lines show field wiring.. It is wiring for refrigerant system at the time of shipping. Change wiring and SW,, (No.&No.)as this figure in field when you change it to refrigerant circuit. Set up the address of No. board in the odd number, and set up the address of No. board in the even number. But, set up the address of the No. board in the No. board +.. The outdoor unit to which the indoor unit is connected with the transmission line, the address of the outdoor unit should be the indoor unit +0.. Mark indicates terminal bed, connector, board insertion connector or fastening connector of control board A B CDE F X Dehumidify CN CN Address (odd) CN7V TH- SW SW SW (nd digit) SW SW (st digit) CN8 Z No. CN CN9 CN CN0 CN CN0 P CNT ZNR90 CN DSA CN I.B. F90 ZNR X0 X07 X0 X0 X0 CNP CN CNT CND CNP 7 CN90 9 Z CNA CNM CN TH- TH- LEV AD.B. TH- LEV LEVA LEVB LEV X Dehumidify SWC SW SW SW7 SW8 SW SW SW (nd digit) SW SW CN SW (st digit) CN CN8 Z CN7V Address (odd) CN CN0 CN 7 CN9 CN P CN F90 ZNR ZNR90 DSA CN I.B. X0 X07 X0 X0 X0 CN0 CNT CNT CND CNP CN CN <note> Z CNA CNM CN <note> Inside section of control box DSA S.B. ZNR IFB CN CN X X CN F TB SHIELD L TB TB TB B A TB- L L N TB L L L AC A A BC B B C SHIELD B A TB- PE RC No. Indoor unit Control wiring DC~0V LED display(no. failure) LED display(status) LED display(power supply) Power supply N~ 80/00/V(0Hz) 00/V(0Hz) SW9 Switch(normal/local) L L L L PE Power supply DC~V Distant location on/off <with voltage and current> Distant location on/off <no voltage or current> Power supply DC0V, AC00/00V No.Status output No.Failure output No.Status output No.Failure output No. Indoor unit Control wiring DC~0V LED display(no. failure) LED display(check) T T S S L L 9 A B CDE F TH- No. TH- TH- F TH- MF F Z Z F Z FAN over current detection F ZNR SYMBOL MF I.B., I.B. AD.B. S.B. IFB TB TB-, - TB TB TB TB F90 F T ZNR, ZNR, ZNR90 DSA LEV, F F P, P TH-, TH- TH-, TH- TH-, TH- TH-, TH- SW(I.B.) SW(I.B.) SW(I.B.) SW(I.B.) SW9 SW(I.B.) SW(I.B.) SW(I.B.) SWC(I.B.) X, X Z, Z Z L L L L L RC NAME Fan motor Indoor controller board Adapter board Surge absorber board External input/output board Power source terminal bed Transmission terminal bed Transmission terminal bed Terminal bed for distant location on/off <No voltage or current> Terminal bed for distant location display Terminal bed for distant location on/off <With voltage and current> Fuse <./A> Fuse <A> Varistor Surge absorber Transformer Electronic linear expan.valve Contactor(fan I/D) Over current relay (fan I/D) Float switch Thermistor (inlet temp.detection) Thermistor (piping temp.detection/liquid) Thermistor (piping temp.detection/gas) Thermistor (outlet temp.detection) Switch (for mode selection) Switch (for capacity code) Switch (for mode selection) Switch (for model selection) Switch (normal/local) Switch (st digit address set) Switch (nd digit address set) Switch (connection No.set) Switch (outlet/inlet temp.control) Auxiliary relay(check) Auxiliary relay(fan) Auxiliary relay(fan failure detection) LED display (No. failure) LED display (No. failure) LED display (status) LED display (check) LED display (power supply) Remote controller How to connect in case of refrigerant circuit. Remove the LEVB connector from AD.B. board, and connect it to CN0 of I.B. board. LEV CN0 I.B. CNA CNM Connect a connector to CNA, CNM of I.B. board. <note> External input-output board (IFB) TB TB AC A A BC B B A B When using the external input function on the indoor unit that is connected to a two-refrigerant circuit, connect the short-circuit plate that is supplied with the unit to the appropriate terminals on the external input-output board. The case of with-voltage input... A The case of no-voltage input... B How to set up to SW,,. (In case of refrigerant circuit) <note> The signal input of the dehumidify order is to connect wiring referring to the bottom figure. (field supply and construction) PFD-P00VM-E refrigerant circuit (at the time of shipping) refrigerant circuit ON ON SW SW SW ON ON ON ON Indoor unit control board CN External input adapter (PAC-SA88HA) (green) (brown) Relay circuit SW:Defumidify order Z:Relay (Contact : Minimum applicable load DCV ma or less) Z Z Distant control panel SW Power u u u u u u 7

22 . Refrigerant Circuit Diagram And Thermal Sensor Outdoor Unit : PUHY-P0YHM-A Indoor Unit : PFD-P0VM-E TH7 SVb TH Sb SV9 Sa CV TH CP TH SCC(HIC Circuit) LEV O/S COMP CJ H HS LS CJ SVa ST CP TH ACC ST7 ST TH LEVa LEVb ST ST BV BV TH TH 8

23 Outdoor Unit : PUHY-P0YHM-A x Indoor Unit : PFD-P00VM-E Sb Sa ST BV TH7 CV O/S CJ H HS ST SVa CP LS TH CJ TH ACC COMP SVb SV9 TH CP ST7 ST ST BV TH- TH- TH SCC (HIC circuit) LEV TH LEVa LEVb Sb Sa ST BV TH7 CV O/S CJ H HS ST SVa CP LS TH CJ TH- TH- TH ACC COMP SV9 CP ST7 ST SVb TH ST BV TH SCC (HIC circuit) LEV TH LEVa LEVb 9

24 7. System Design 7-.Refrigerant Piping System Sample connection <Refrigerant system with one outdoor unit> Outdoor unit <Refrigerant system with two outdoor units> Outdoor unit A A L L L H H Allowable piping length Allowable height difference Pipe selection Farthest piping length(l) Indoor unit Height difference between indoor and outdoor units (H) m or less in actual length Indoor unit 0 m or less (0 m if outdoor unit is below indoor unit, m if outside temperature is 0 C or below) Outdoor unit model Liquid pipe size Gas pipe size P0 ø 9. ø. Use ø.7 pipes when the pipe length exceeds 90 m. Amount of refrigerant charge Refrigerant for extension piping is not included at factory shipment. Add an appropriate amount of refrigerant for each system on site. Write down the size and the length of the piping in each system as well as the amount of added refrigerant on the outdoor unit as a reference for servicing. Calculating the amount of refrigerant to be added The amount of refrigerant that is necessary for extension piping is calculated based on the size and the length of the liquid piping. Use the following formula to figure out the amount of refrigerant to be added. Round up the calculation result to the nearest 0. kg. (e.g., If the result is.08 kg, round up the.08 to., which yields. kg.) <Amount of refrigerant to be added> Refrigerant charge calculation Amount of charged refrigerant at factory shipment Liquid pipe size Total length of the ø.7 pipes x 0. (m) x 0.(kg/m) + Sample calculation Liquid pipe size Total length of the ø 9. pipes x 0.0 (m) x 0.0(kg/m) + Total capacity of connected indoor units P0 model P00 model Amount for the indoor unit.0kg.0kg kg x when connected to a system with two outdoor units Outdoor unit model P0 Charged refrigerant amount(kg) 9.0 <Connection to a system with two outdoor unit> 00 model indoor unit : When ø 9. pipes are used and the piping length is 80 m 80(m) x 0.0(kg/m)+.0kg=.8kg (Amount for the extension pipe to each outdoor unit) Caution Charge Liquid Refrigerant Filling the equipment with gas refrigerant will result in a power loss due to transformation of refrigerant in the tank. 0

25 7-.Control Wiring Restrictions when the PFD-type indoor units are connected (related to the system) () The PFD-type indoor units cannot be connected to the ME remote controller. () The address settings must be made on this system. () The following functions cannot be selected on the PFD-type indoor units. ) Switching between automatic power recovery Enabled/Disabled (Fixed to "Enabled" in the PFD-type indoor units) ) Switching between power source start/stop (Fixed to "Disabled" in the PFD-type indoor units) () The PFD-type indoor units and other types of indoor units cannot be grouped. () The following functions are limited when the system controller (such as G-0A) is connected. ) To perform group operation in the system with two refrigerant circuits (combination of two outdoor units and one indoor unit: P00 model only), the addresses of the controller boards No. and No. on a indoor unit must be set within a group. ) The local operation cannot be prohibited with the system controller. ) When the switches of the PFD-type indoor units are set as follows, the unit ON/OFF operation cannot be made with the system controller. When the Normal/Local switching switch is set to "Local" When the DipSW-0 on the control circuit board is set to "ON" ) The PFD type indoor units cannot be grouped with other types of indoor units. () Specifications of control wiring and maximum length of wiring Transmission line is a type of control line. When the source of noise is located adjacent to the unit, the use of shield cable as well as moving the unit as far away from the noise source are recommended. Transmission line (M-NET transmission line) System component Length of transmission line Facility type (noise level measurement) Wiring specifications Cable type n/a All types of facilities Shield cable CVVS CPEVS MVVS No. of cable -core cable Diameter Over.mm For multiple-refrigerant system Total length of indoor/outdoor transmission line Maximum length: 00m Maximum length of centralized control transmission line and Indoor/Outdoor transmission line via indoor/outdoor units: 00m maximum

26 Remote control wiring Wiring specifications Cable type No. of cable Diameter -core cable remote controller VCTF VCTFK CVV CVS VVR VVF VCT 0.~.mm (0.7~.mm ) Total Length Maximum length: 00 m : remote controller includes remote controller, Simple controller, and wireless remote controller. : Cables with a diameter of 0.7mm or smaller recommended for easier handling. : When connecting to Simple controller terminal, use a cable with a diameter within the range shown in the parenthesis. 7-.Types of switch settings and setting methods Whether a particular system requires switch settings depends on its components. Refer to the section 7- Sample System Connection before conducting electrical work. Keep the power turned off while setting the switches. If settings are changed while being powered, the changed settings will not register, and the unit may malfunction. Unit Symbol Outdoor unit OC Indoor unit Main/sub controllers IC 0HP has only the main controller Turn off the power to Outdoor unit Indoor and outdoor units () Address setting The need for address settings and the range of address setting depend on the configuration of the system. Refer to Sample System Connection. Unit or controller Symbol Address setting range Address setting method Factory setting Model Indoor unit Main Sub IC 0~0 (Note ) In case of 0HP system, assign an odd number starting with "0". In case of 0HP system with two refrigerant circuits, assign a sequential odd number starting with "0" to the upper indoor controller, and assign "the address of the upper indoor controller + " to the lower indoor controller. (For the system with one refrigerant circuit, the lower circuit board is not used.) 00 remote controller No address setting required. (The main/sub switch must be configured if two remote controllers are connected to the system or if the indoor units are connected to different outdoor units.) Main Outdoor unit OC ~00 Add 0 to the address assigned to the indoor unit connected the system with one outdoor unit. 00 (Note) If a given address overlaps any of the addresses that are assigned to other outdoor units, use a different, unused address within the setting range.

27 () Power supply switch connector connection on the outdoor unit (Factory setting: The male power supply switch connector is connected to CN.) System configuration System in which indoor units connected to one outdoor unit System in which indoor units connected to multiple outdoor units Connection to the system controller Not connected With connection to indoor-outdoor transmission line With connection to transmission line for centralized control Power supply unit for transmission lines Not required Not required (Powered from the outdoor unit) Required Grouping the indoor units connected to different outdoor units Not grouped Grouped Grouped /Not grouped Grouped /Not grouped Grouped /Not grouped Power supply switch connector connection Leave the male connector on CN as it is. (Factory setting) Disconnect the male connector from the female power supply switch connector (CN) and connect it to the female power supply switch connector (CN0) on only one of the outdoor units (OC). *Connect the S (shielded) terminal on the terminal block (TB7) on the outdoor unit whose male connector on CN was disconnected and connected to CN0 to the earth terminal ( ) on the control box. Leave the male connector on CN as it is. (Factory setting) When the system controller is connected to the indoor/outdoor transmission line and the power is supplied from the outdoor unit, do not to turn off the outdoor unit. If its power supply is cut, the power is not supplied to the system controller, and the functions will not work. () Choosing the temperature detection spot by indoor unit (Factory Setting: SWC Standard ) When using the suction temperature sensor, set SWC to Option. (The discharge temperature sensor is supplied as standard specification.) () Setting the Sub controller When using two remote controllers or running two indoor units as a group, one of the controllers must be set to Sub controller. No more than two remote controllers can be connected to a group. (Factory setting: Main ) Set the controller according to the following procedure. Refer also to the instructions manual supplied with the remote controller. Remove the cover on the remote controller Insert a flat-head screwdriver in the groove shown in the picture, and move the screwdriver in the direction shown in the arrow. Screwdriver Set Dip Switch No. on the remote controller to OFF (Main to Sub) ON Dip switches Remote controller body () Connection of two refrigerant circuits When two refrigerant circuits are connected on site, make the switch settings on the controller circuit board following the instructions described in the installation manual for the indoor unit.

28 7-.Sample System Connection () An example of a system to which an remote controller is connected System connected to one outdoor unit Control Wiring Diagram Leave the male connector on CN as it is. OC TB7 TB M M S M M L IC TB- A B S 0 One indoor controller (controller circuit board) is equipped in the indoor unit (0HP), and two indoor controllers (controller circuit boards) are equipped in the indoor unit (0HP). TB A B 0 TB- A B S Notes Maximum Allowable Length. Leave the male connector on the female power supply switch connector (CN) as it is.. Grounding to S terminal on the terminal block for transmission line for centralized control (TB7) is not required.. Although two indoor controllers (controller circuit boards) are equipped inside the indoor unit (0HP), the board on No. side (lower side) is not used. Do not connect wiring to the lower controller circuit board.. The outdoor unit cannot be connected to the units other than the PFD series indoor units. <a. Indoor/Outdoor transmission line> Maximum Length (.mm or more) L 00m Wiring and Address Setting <a. Indoor/Outdoor transmission line> Connect M, M terminals of the indoor/outdoor transmission line terminal block (TB) on the outdoor unit (OC) and A, B terminals of the indoor/outdoor terminal block (TB-) on the indoor unit (IC). (Non-polarized -core cable) *Only use shielded cables. [Shielded cable connection] Connect the earth terminal of the OC and S terminal of the IC terminal block (TB-). <b. Switch setting> Address setting is required as follows. Steps Indoor unit Unit or controller Main Sub IC IC Address setting range 0~0 0~0 Address setting method Assign a sequential odd number starting with "0" to the upper indoor controller. Assign sequential numbers starting with the address of the main unit in the same group. (Main unit address +) Notes Factory setting 00 Outdoor unit OC ~00 Add 0 to the address assigned to the indoor unit connected to the system with one outdoor unit. 00 remote controller Main Controller Sub Controller Setting not required. Sub Controller Settings to be made with the sub/main switch Main

29 () An example of a system to which an remote controller is connected System connected to two outdoor units Control Wiring Diagram L Disconnect the male power supply connector from CN0 and connect it to CN. OC TB7 TB MM S M M IC TB- A B S 0 One indoor controller (controller circuit board) is equipped in the indoor unit (0HP), and two indoor controllers (controller circuit boards) are equipped in the indoor unit (0HP). Connection TB L Leave the male connector on CN as it is. A B OC TB7 TB M M S M M 0 TB- AB S not connect L Notes. Assign a sequential number to the outdoor unit.. Do not connect the terminal blocks (TB) of the indoor units connected to different outdoor units.. Disconnect the male connector on the controller board from the female power supply switch connector (CN), and connect it to the female power supply switch connector (CN0) on only one of the outdoor units.. Provide grounding to S terminal on the terminal block for transmission line for centralized control (TB7) on only one of the outdoor units.. When the power supply unit is connected to the transmission line for centralized control, leave the male connector on the female power supply switch connector (CN) as it is at factory shipment.. The outdoor unit cannot be connected to the units other than the PFD series indoor units. Maximum Allowable Length Wiring and Address Setting <a. Indoor/Outdoor transmission line> Connect M, M terminals of the indoor/outdoor transmission line terminal block (TB) on the outdoor unit (OC) and A, B terminals of the indoor/outdoor terminal block (TB-) on the indoor unit (IC). (Non-polarized -core cable) *Only use shielded cables. [Shielded cable connection] Connect the earth terminal of the OC and S terminal of the IC terminal block (TB-). <b. Transmission line for centralized control> Daisy-chain terminals M and M on the terminal block for transmission line for centralized control (TB7) on each outdoor unit (OC). Disconnect the male connector on the controller board from the female power supply switch connector (CN), and connect it to the female power supply switch connector (CN0) on only one of the outdoor units. *Only use shielded cables. [Shielded cable connection] <c. Switch setting> Address setting is required as follows. Steps Indoor unit Unit or controller Main Sub To ground the shielded cable, daisy-chain the S-terminals on the terminal block (TB7) on each of the outdoor units. Connect the S (shielded) terminal on the terminal block (TB7) on the outdoor unit whose male connector on CN was disconnected and connected to CN0 to the earth terminal ( ) on the electric box. IC IC Address setting range 0~0 0~0 Address setting method Assign a sequential odd number starting with "0" to the upper indoor controller. Assign sequential numbers starting with the address of the main unit in the same group. (Main unit address +) <a. Indoor/Outdoor transmission line> Maximum Length (.mm or more) L, L 00m <b. Transmission line for centralized control> Maximum Length via outdoor unit (.mm or more) L + L + L 00m Notes Factory setting 00 Outdoor unit OC ~00 Add 0 to the address assigned to the indoor unit connected to the system with one outdoor unit. 00 remote controller Main Controller Sub Controller Setting not required. Sub Controller Settings to be made with the sub/main switch Main

30 () An example of a system to which an remote controller is connected System in which two remote controllers are connected to one indoor unit Control Wiring Diagram Leave the male connector on CN as it is. TB7 M M S OC TB M M L IC 0 TB- A B S One indoor controller (controller circuit board) is equipped in the indoor unit (0HP), and two indoor controllers (controller circuit boards) are equipped in the indoor unit (0HP). m TB m A B (Main) A B (Sub) A B TB- A B S 0 Notes Maximum Allowable Length. Leave the male connector on the female power supply switch connector (CN) as it is.. Grounding to S terminal on the terminal block for transmission line for centralized control (TB7) is not required.. Although two indoor controllers (controller circuit boards) are equipped inside the indoor unit, the board on No. side (lower side) is not used. Do not connect wiring to the lower controller circuit board.. No more than two remote controllers (including both main and sub controllers) can be connected to a group of indoor units. If three or more remote controllers are connected, remove the wire for the remote controller from the terminal block (TB).. The outdoor unit cannot be connected to the units other than the PFD series indoor units. <a. Indoor/Outdoor transmission line> Same as (). Wiring and Address Setting <b. remote controller wiring> [When two remote controllers are connected to the system] When two remote controllers are connected to the system, connect terminals and of the terminal block (TB) on the indoor unit (IC) to the terminal block on the remote controllers (option). *Set the Main/Sub switch on the connected remote controllers (option) to SUB. (See the installation manual for the remote controller for the setting method.) <c. Switch setting> Address setting is required as follows. Steps Indoor unit Unit or controller Main Sub IC IC Address setting range 0~0 0~0 Address setting method Assign a sequential odd number starting with "0" to the upper indoor controller. Assign sequential numbers starting with the address of the main unit in the same group. (Main unit address +) <a. Indoor/Outdoor transmission line> Same as (). <b. remote controller wiring> Maximum overall length (0.-.mm or more) m + m 00m Notes Factory setting 00 Outdoor unit OC ~00 Add 0 to the address assigned to the indoor unit connected to the system with one outdoor unit. 00 remote controller Main Controller Sub Controller Setting not required. Sub Controller Settings to be made with the sub/main switch Main

31 () An example of a system to which an remote controller is connected System in which two indoor units are grouped with the remote controller Control Wiring Diagram Leave the male connector on CN as it is. OC L IC Leave the male connector on CN as it is. OC L IC TB7 MM S TB MM 0 TB- A B S TB7 M M S TB MM 0 TB- A B S One indoor controller (controller circuit board) is equipped in the indoor unit (0HP), and two indoor controllers (controller circuit boards) are equipped in the indoor unit (0HP). TB TB m m A B (Main) A B (Sub) 0 0 TB- A B S TB- A B S m Notes Maximum Allowable Length. Leave the male connector on the female power supply switch connector (CN) as it is.. Grounding to S terminal on the terminal block for transmission line for centralized control (TB7) is not required.. Although two indoor controllers (controller circuit boards) are equipped inside the indoor unit, the board on No. side (lower side) is not used. Do not connect wiring to the lower controller circuit board.. No more than two remote controllers (including both main and sub controllers) can be connected to a group of indoor units. If three or more remote controllers are connected, remove the wire for the remote controller from the terminal block (TB).. The outdoor unit cannot be connected to the units other than the PFD series indoor units. <a. Indoor/Outdoor transmission line> Same as (). Wiring and Address Setting <b. remote controller wiring> [Group operation of indoor units] To perform a group operation of indoor units (IC), daisy-chain terminals and on the terminal block (TB) on all indoor units (IC). (Non-polarized - core cable) *Set the Main/Sub switch on one of the remote controllers to SUB. <c. Switch setting> Address setting is required as follows. Steps Indoor unit Unit or controller Main Sub IC IC Address setting range 0~0 0~0 Address setting method Assign a sequential odd number starting with "0" to the upper indoor controller. Assign sequential numbers starting with the address of the main unit in the same group. (Main unit address +) <a. Indoor/Outdoor transmission line> Same as (). <b. remote controller wiring> Maximum overall length (0.-.mm or more) m + m + m 00m Notes Factory setting 00 Outdoor unit OC ~00 Add 0 to the address assigned to the indoor unit connected to the system with one outdoor unit. 00 remote controller Main Controller Sub Controller Setting not required. Sub Controller Settings to be made with the sub/main switch Main 7

32 () System with remote controller and G-0A System with multiple indoor units (0HP, 0HP) L Control Wiring Diagram There is one indoor controller board inside indoor unit. L Use CN as is. OC IC There are two indoor controller boards inside indoor unit. Use CN as is. OC L IC 0 0 TB7 TB MMS MM TB- A BS TB7 TB MM S MM TB- A B S TB not connect TB L Power Supply ABS m A B L Use CN as is. OC m A B L G-0A ABS DC power supply line (DCV) TB7 TB MM S MM TB- A B S 0 Option not connect L Notes. Be sure to use odd numbers to set the address for indoor units (0 HP and 0HP connected to the one outdoor unit).. To set the indoor unit address for 0 HP connected to two outdoor units, use odd numbers for the top controllers and use even numbers for the bottom controllers (Main controller plus ).. Use the power supply switch connector (CN) on the outdoor unit as is.. It is not necessary to ground the S terminal of transmission line terminal board for centralized controller on the outdoor unit. No more than two main/sub remote controllers can be connected to the indoor unit in the same group. When more than two remote controllers are present in the system, disconnect remote controller from TB in the indoor unit.. Put both types of the addresses for P00-type indoor units in the same group when setting groups for indoor units with system controller (ex. G-0A). Maximum Allowable Length <a. Indoor/Outdoor transmission line> L, L, L 00m <b. Transmission Line for Centralized Control > L + L + L + L + L 00m L + L + L + L 00m <c. Remote Controller Line > Total Length (0. ~.mm ) m 00m Wiring and Address Setting <a. Indoor/Outdoor transmission line> Same as (). <b. Transmission line for centralized control> Daisy-chain terminals M and M on the terminal block for transmission line for centralized control (TB7) on each outdoor unit (OC). *Only use shielded cables. [Shielded cable connection] To ground the shielded cable, daisy-chain the S-terminals on the terminal block (TB7) on each of the outdoor units. <c. Switch setting> Address setting is required as follows. Address Unit or controller Address setting method Notes setting range Steps Indoor unit Main (0HP, 0HP) Sub (0HP) IC IC 0~0 0~0 Assign a sequential odd number starting with "0" to the upper indoor controller. Assign sequential numbers starting with the address of the main unit in the same group. (Main unit address +) Factory setting 00 Outdoor unit OC ~00 Add 0 to the address assigned to the indoor unit connected to the system with one outdoor unit. 00 remote controller Main Controller Sub Controller Setting not required. Sub Controller Settings to be made with the sub/main switch Main 8

PUHY-P250YHM-A PUHY-P500YSHM-A PQHY-P250YHM-A PFD-P250VM-E PFD-P500VM-E

PUHY-P250YHM-A PUHY-P500YSHM-A PQHY-P250YHM-A PFD-P250VM-E PFD-P500VM-E AIR CONDITIONERS MODEL PUHY-P0YHM-A PUHY-P00YSHM-A PQHY-P0YHM-A PFD-P0VM-E PFD-P00VM-E DATA BOOK The water circuit should be a closed circuit. Always use an air cleaner, humidifier, electric heater, and

More information

PUHY-P250YJM-A PUHY-P500YSJM-A PQHY-P250YHM-A PFD-P250VM-E PFD-P500VM-E

PUHY-P250YJM-A PUHY-P500YSJM-A PQHY-P250YHM-A PFD-P250VM-E PFD-P500VM-E AIR CONDITIONERS MODEL PUHY-P0YJM-A PUHY-P00YSJM-A PQHY-P0YHM-A PFD-P0VM-E PFD-P00VM-E DATA BOOK The water circuit should be a closed circuit. Always use an air cleaner, humidifier, electric heater, and

More information

AIR CONDITIONERS MODELS PQHY-P650YSHM-A PQHY-P700YSHM-A PQHY-P750YSHM-A PQHY-P800YSHM-A PQHY-P850YSHM-A PQHY-P900YSHM-A DATA BOOK

AIR CONDITIONERS MODELS PQHY-P650YSHM-A PQHY-P700YSHM-A PQHY-P750YSHM-A PQHY-P800YSHM-A PQHY-P850YSHM-A PQHY-P900YSHM-A DATA BOOK AIR CDITIERS MODELS PQHY-P6YSHM-A PQHY-P700YSHM-A PQHY-P7YSHM-A PQHY-P800YSHM-A PQHY-P8YSHM-A PQHY-P900YSHM-A DATA BOOK WY SERIES DATA G7 HEAT SOURCE UNITS I.WY SERIES. SPECIFICATIS... 2 2. EXTERNAL DIMENSIS...

More information

PURY-M YNW-A (-BS) PURY-EM YNW-A (-BS)

PURY-M YNW-A (-BS) PURY-EM YNW-A (-BS) AIR CONDITIONING SYSTEMS MODEL PURY-M00-00YNW-A (-BS) PURY-EM00-00YNW-A (-BS) GENERAL LINE-UP GENERAL LINE-UP I.GENERAL LINE-UP Heat Recovery R-Series PURY-M00YNW-A(-BS) PURY-M0YNW-A(-BS) PURY-M00YNW-A(-BS)

More information

PUHY-P-Y(S)JM-A PFAV-P-VM-E(-F)

PUHY-P-Y(S)JM-A PFAV-P-VM-E(-F) AIR CONDITIONING SYSTEMS MODEL PUHY-P-Y(S)JM-A PFAV-P-VM-E(-F) DATA BOOK Contents!. General Cautions. Indoor Unit Line-up. Temperature range. Notes on selecting equipments () Notes on using the Fresh

More information

PMFY-P-VBM-E. Ceiling cassette (1-way flow type) R410A Data G8 1. SPECIFICATIONS EXTERNAL DIMENSIONS CENTER OF GRAVITY 1-100

PMFY-P-VBM-E. Ceiling cassette (1-way flow type) R410A Data G8 1. SPECIFICATIONS EXTERNAL DIMENSIONS CENTER OF GRAVITY 1-100 Ceiling cassette (-way flow type) RA Data G8 -P-VBM-E. SPECIFICATIONS - 98. EXTERNAL DIMENSIONS - 99 3. CENTER OF GRAVITY -. ELECTRICAL WIRING DIAGRAMS -. SOUND LEVELS -. Sound levels -. NC curve 6. TEMPERATURE/AIRFLOW

More information

PURY-P200YMF-C, PURY-P250YMF-C CONTENTS

PURY-P200YMF-C, PURY-P250YMF-C CONTENTS Outdoor units / R series / R407C / PURY-P00 0YMF-C PURY-P00YMF-C, PURY-P0YMF-C COTETS. Specifications. Capacity Tables 8 - Correction by temperature 8 - Correction by total indoor 0 - Correction by refrigerant

More information

AIR CONDITIONING SYSTEMS MODEL CMH-WM-V-A

AIR CONDITIONING SYSTEMS MODEL CMH-WM-V-A AIR CONDITIONING SYSTEMS MODEL CMH-WM-V-A CONTENTS CMH-WM-V-A 1. SPECIFICATIONS... 2 2. EXTERNAL DIMENSIONS... 5 3. CENTER OF GRAVITY... 7 4. ELECTRICAL WIRING DIAGRAMS... 8 5. SOUND LEVELS... 9 5-1. Sound

More information

PEFY-P20VMS-E, PEFY-P40VMS-E PEFY-P25VMS-E, PEFY-P50VMS-E PEFY-P32VMS-E, PEFY-P63VMS-E

PEFY-P20VMS-E, PEFY-P40VMS-E PEFY-P25VMS-E, PEFY-P50VMS-E PEFY-P32VMS-E, PEFY-P63VMS-E 2006 Air-Conditioners TECHNICAL & SERVICE MANUAL Models PEFY-P20VMS-E, PEFY-P40VMS-E PEFY-P25VMS-E, PEFY-P50VMS-E PEFY-P2VMS-E, PEFY-P6VMS-E For use with R40A, R407C, & R22 Safety Precautions Read before

More information

Air to Air Heat Exchanger

Air to Air Heat Exchanger Air to Air Heat Exchanger VN-M1HE / VN-M2HE VN-M3HE / VN-MHE VN-M6HE / VN-M8HE VN-M1HE VN-M1HE VN-M2HE Air to Air Heat Exchanger MMD VN2HEXE MMD VN82HEXE MMD VN12HEXE with DX-coil Type CONTENTS 1. Specifications

More information

Digital Inverter 4 series 8 & 10HP

Digital Inverter 4 series 8 & 10HP E6-H Digital Inverter 4 series 8 & 0HP High static duct type Indoor unit RAV-SM2244DTP-E RAV-SM2804DTP-E Outdoor unit RAV-SM2244AT8-E RAV-SM2804AT8-E Contents. Line up... 2. Indoor unit (High static duct

More information

TECHNICAL & SERVICE MANUAL. Ceiling Concealed

TECHNICAL & SERVICE MANUAL. Ceiling Concealed STAND BY DEFROST CHECK CLOCK ON OFF NOT AVAILABLE FILTER CHECK MODE TEST RUN FUNCTION SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL Series SEZ Ceiling Concealed R40A.OC0 REVISED EDITION-A

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE OUTDOOR AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE DR_AS037EF_01 2016.12.05 Notices: Product

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LMCA AS G09LMCA AS G12LMCA AS G14LMCA OUTDOOR AO G07LMCA AO G09LMCA AO G12LMCA AO G14LMCA 1. INDOOR UNIT : AS G07LMCA AS G09LMCA

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA OUTDOOR AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA DR_AS049EF_02 2017.10.11 Notices: Product

More information

Mitsubishi Electric's

Mitsubishi Electric's 3rd edition CONTENTS What is HYBRID CITY MULTI? - System Structure - 3 The reason why HYBRID CITY MULTI is unbeatable - Features - 4 - pplication example - 8 Mitsubishi Electric's Lineup 9 Specifications

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL AIR CONDITIONERS 0 TECHNICAL & SERVICE MANUAL Models P0VMA(L)-E, P5VMA(L)-E, PVMA(L)-E, P40VMA(L)-E, P50VMA(L)-E, P6VMA(L)-E P7VMA(L)-E P80VMA(L)-E P00VMA(L)-E P5VMA(L)-E P40VMA(L)-E Safety Precautions

More information

SEZ-KD25VAQ.TH SEZ-KD35VAQ.TH SEZ-KD50VAQ.TH SEZ-KD60VAQ.TH SEZ-KD71VAQ.TH

SEZ-KD25VAQ.TH SEZ-KD35VAQ.TH SEZ-KD50VAQ.TH SEZ-KD60VAQ.TH SEZ-KD71VAQ.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL December No.HWE0 REVISED EDITION-B Indoor unit [Model names] SEZ-KD25VAQ SEZ-KD35VAQ SEZ-KDVAQ SEZ-KDVAQ SEZ-KD71VAQ [Service Ref.] SEZ-KD25VAQ.TH

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 12 TECHNICAL & SERVICE MANUAL Series SEZ Model name SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KDVA(L) SEZ-KDVA(L) SEZ-KD71VA(L) INDOOR UNIT ON/OFF TEMP TEMP.

More information

PKFY-P15VBM-E PKFY-P20VBM-E PKFY-P20VBM-ER1 PKFY-P25VBM-E PKFY-P25VBM-ER1

PKFY-P15VBM-E PKFY-P20VBM-E PKFY-P20VBM-ER1 PKFY-P25VBM-E PKFY-P25VBM-ER1 SPLIT-TYPE, HEAT PUMP AIR CDITIERS November No. OCH REVISED EDITI-A TECHNICAL & SERVICE MANUAL RA R7C R Indoor unit [Model names] PKFY-PVBM-E PKFY-PVBM-E PKFY-PVBM-E [Service Ref.] PKFY-PVBM-E PKFY-PVBM-E

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL For Extra Cold Climate Area INDOOR ASU18RLF ASU24RLF OUTDOOR AOU18RLXFWH AOU24RLXFWH DR_AS014EF_04 2017.03.10 Notices: Product specifications

More information

11. WALL MOUNTED TYPE PACKAGED AIR CONDITIONER Split system, Air cooled cooling only type

11. WALL MOUNTED TYPE PACKAGED AIR CONDITIONER Split system, Air cooled cooling only type 11. WALL MOUNTED TYPE PACKAGED AIR CONDITIONER ( Split system, Air cooled ) cooling only type FDKN8CEN-S, FDKN8CEP-S, FDKN8CEN FDKN8CEP, FDKN258CEN-S, FDKN258CEP-S FDKN258CEN, FDKN258CEP, FDKN8CEN FDKN8CEP,

More information

WY-14 WY ELECTRICAL WIRING DIAGRAMS WY REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS WY SYSTEM DESIGN GUIDE WY-20

WY-14 WY ELECTRICAL WIRING DIAGRAMS WY REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS WY SYSTEM DESIGN GUIDE WY-20 WY SERIES R0A Data G CITY MULTI HEAT SOURCE UNITS WY SERIES WY SERIES. SPECIFICATIONS. CAPACITY TABLES WY WY5. Correction by temperature WY5. Correction by total indoor WY9. Correction by refrigerant piping

More information

TABLE OF CONTENTS ERSQ-AAY1

TABLE OF CONTENTS ERSQ-AAY1 Daikin Altherma High Temperature Outdoor units ERSQ-AAY1 TABLE OF CONTENTS ERSQ-AAY1 1 Features............................................................ 6 2 Specifications......................................................

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL RESET SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. OC0 TECHNICAL & SERVICE MANUAL Series SLZ Ceiling Cassettes R0A Indoor unit [Model names] SLZ-A09AR SLZ-AAR SLZ-A8AR [Service Ref.] SLZ-A09AR.TH SLZ-AAR.TH

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL RA December 22 No. OCH REVISED EDITI-C Indoor unit [Model names] PKFY-PVBM-E PKFY-P2VBM-E PKFY-P2VBM-E [Service Ref.] PKFY-PVBM-E PKFY-PVBM-ER2

More information

High Efficiency, Powerful Heating and Cooling HEAT PUMP PEH-7, 8, 10 AIR COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS. Series

High Efficiency, Powerful Heating and Cooling HEAT PUMP PEH-7, 8, 10 AIR COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS. Series AIR COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS Series HEAT PUMP PEH-7, 8, PEH-7 PEH-8 PEH- Cooling capacity () 18.8 22.0 28.8 Heating capacity () 19.4 22.0 28.8 High Efficiency, Powerful Heating and Cooling

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G09LTCB AS G12LTCB AS G14LTCB OUTDOOR AO G09LTCN AO G12LTCN AO G14LTCN 1. INDOOR UNIT : AS G09LTCB AS G12LTCB AS G14LTCB DTR_AS057E_01

More information

TECHNICAL MANUAL. PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) MULTI-TYPE (V-MULTI) PACKAGED AIR-CONDITIONER

TECHNICAL MANUAL. PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) MULTI-TYPE (V-MULTI) PACKAGED AIR-CONDITIONER Manual No. '06 PAC, KX-T-110 TECHNICAL MANUAL Collection data PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) FDUMVA201HEN2R 251HEN2R 302HEN2R 402HEN2R 502HEN2R 602HEN2R MULTI-TYPE (V-MULTI)

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH530 Models MU-GE50VB- E1 - E1 Indoor unit service manual MS/MSH-GE VB Series (OBH529) CONTENTS 1. TECHNICAL CHANGES 2 2. PART

More information

250mm dia straight pipe length SP4 SP3. Air volume

250mm dia straight pipe length SP4 SP3. Air volume MODEL LGH-100RVX-E SIGN Heat exchange system Heat recovery ventilating system Heat exchanger material Special treated paper plate heat exchanger Cladding Galvanized steel sheet Heat insulation material

More information

6. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air cooled cooling only type)

6. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air cooled cooling only type) 6. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air cooled cooling only type) (OUTDOOR UNIT) (INDOOR UNIT) SKM222CENG-L SKM252CENG-L SKM402CENG-L 221 CONTENTS 6.1 GENERAL INFORMATION... 223 6.1.1

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A09LEC AS A12LEC OUTDOOR AO R09LECN AO R12LECN 1.INDOOR UNIT : AS A09LEC AS A12LEC DTR_AS047E_01 2010.10.05 1. INDOOR UNIT CONTENTS

More information

TABLE OF CONTENTS RMXS-E8V1B

TABLE OF CONTENTS RMXS-E8V1B Outdoor Units R-410A RMXS-E8V1B TABLE OF CONTENTS RMXS-E8V1B! 1 Features........................................................... 814 2 Specifications.....................................................

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL October 202 No. OCH446 REVISED EDITION-E HFC utilized R40A [Model name] PUMY-P00VHMB PUMY-P25VHMB PUMY-P40VHMB PUMY-P00VHMB-BS

More information

TECHNICAL & SERVICE MANUAL. Floor Standing Type. Series PFFY. For use with the R407C & R22. Air-Conditioners For Building Application

TECHNICAL & SERVICE MANUAL. Floor Standing Type. Series PFFY. For use with the R407C & R22. Air-Conditioners For Building Application Air-Conditioners For Building Application 00 TECHNICAL & SERVICE MANUAL Series PFFY Floor Standing Type Models PFFY-P0VLEM-A,PFFY-P0VLRM-A PFFY-PVLEM-A,PFFY-PVLRM-A PFFY-PVLEM-A,PFFY-PVLRM-A

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG18KLCA ASYG24KLCA OUTDOOR AOYG18KLTA AOYG24KLTA DR_AS069EF_01 2018.03.16 Notices: Product specifications and design are subject to

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Duct type DESIGN & TECHNICAL MANUAL INDOOR ARU9RLF ARU12RLF ARU18RLF OUTDOOR AOU9RLFC AOU12RLFC AOU18RLFC 1. INDOOR UNIT : ARU9RLF ARU12RLF ARU18RLF DTR_AR059E_05 2015.06.01 1. INDOOR UNIT

More information

MUH-24RV - MSH-30RV -

MUH-24RV - MSH-30RV - SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models Refer to the Service Manual OB85 REVISED EDITION C when MSH-8RV- E is connected with MXZ-NV- E or MXZ-NV- E as multi system units.

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Duct type DESIGN & TECHNICAL MANUAL INDOOR AR GLLTB AR G4LLTB AR G8LLTB OUTDOOR AO GLALL AO G4LALL AO G8LALL . INDOOR UNIT : AR GLLTB AR G4LLTB AR G8LLTB DTR_AR54E_ 3..8 . INDOOR UNIT CONTENTS.

More information

Series PEAD SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS R32/R410A PEAD-SM100JA(L) PEAD-SM125JA(L) PEAD-SM140JA(L) Models PEAD-SM71JA(L)

Series PEAD SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS R32/R410A PEAD-SM100JA(L) PEAD-SM125JA(L) PEAD-SM140JA(L) Models PEAD-SM71JA(L) SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 2018 SERVICE MANUAL Series PEAD R32/R4A Models PEAD-SM71JA(L) PEAD-SM0JA(L) PEAD-SM125JA(L) PEAD-SM1JA(L) NOTE: This manual describes only service data

More information

Highly Efficient,Powerful Heating and Cooling.

Highly Efficient,Powerful Heating and Cooling. AIR-COOLED ROOFTOP PACKAGED AIR CONDITIONERS Series HEAT PUMP PRHG-8,,,20 Cooling Capacity kw Heating Capacity kw PRHG-8 PRHG- PRHG- PRHG-20 PRHG-8 PRHG- PRHG- PRHG-20 23.8 29.7.3 60.8 23.0 32.0 45.5 61.2

More information

Air Conditioners. Technical Data FBQ-C

Air Conditioners. Technical Data FBQ-C Air Conditioners Technical Data C o n c e a l e d C e i l i n g U n i t E E D E N 1 0-1 0 0 FBQ-C Air Conditioners Technical Data C o n c e a l e d C e i l i n g U n i t E E D E N 1 0-1 0 0 FBQ-C Indoor

More information

SERVICE MANUAL MXZ-A18WV - MXZ-A26WV - MXZ-A32WV - E1 HFC. Inverter-controlled multi system Models SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No.

SERVICE MANUAL MXZ-A18WV - MXZ-A26WV - MXZ-A32WV - E1 HFC. Inverter-controlled multi system Models SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Inverter-controlled multi system Models E MXZ-A8WV - E MXZ-A6WV - MXZ-AWV - E HFC utilized R40A No. OB9 Indication of model name MXZ-A8WV - E CONTENTS.

More information

SERVICE MANUAL AIR CONDITIONER SPLIT TYPE

SERVICE MANUAL AIR CONDITIONER SPLIT TYPE FILE No. A90-961 SERVICE MANUAL AIR CONDITIONER SPLIT TYPE WAY CASSETTE TYPE RAV-133TU-PE/RAV-13A-PE RAV-163TU-PE/RAV-18A-PE Printed in UK Dec 1996 s CONTENTS 1. SPECIFICATION...3. CONSTRUCTION VIEWS...5

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Duct type DESIGN & TECHNICAL MANUAL INDOOR AR G24LMLA OUTDOOR AO G24LALA 1. INDOOR UNIT : DTR_AR063E_01 2013.02.28 - (3) - 1. INDOOR UNIT CONTENTS 1. FEATURES... 01-01 2. WIRED REMOTE CONTROLLER...

More information

PEFY-P40VMH-E,PEFY-P50VMH-E PEFY-P63VMH-E,PEFY-P71VMH-E PEFY-P80VMH-E,PEFY-P100VMH-E PEFY-P125VMH-E,PEFY-P140VMH-E PEFY-P200VMH-E,PEFY-P250VMH-E

PEFY-P40VMH-E,PEFY-P50VMH-E PEFY-P63VMH-E,PEFY-P71VMH-E PEFY-P80VMH-E,PEFY-P100VMH-E PEFY-P125VMH-E,PEFY-P140VMH-E PEFY-P200VMH-E,PEFY-P250VMH-E Air-Conditioners For Building Application 004 TECHNICAL & SERVICE MANUAL Series PEFY Ceiling Concealed Models PEFY-P40VMH-E,PEFY-P50VMH-E PEFY-P6VMH-E,PEFY-P7VMH-E PEFY-P80VMH-E,PEFY-P00VMH-E

More information

SERVICE MANUAL PUHZ-RP35VHA PUHZ-RP50VHA PUHZ-RP60VHA PUHZ-RP71VHA PUHZ-RP100VHA PUHZ-RP125VHA PUHZ-RP140VHA PUHZ-RP100YHA PUHZ-RP125YHA PUHZ-RP140YHA

SERVICE MANUAL PUHZ-RP35VHA PUHZ-RP50VHA PUHZ-RP60VHA PUHZ-RP71VHA PUHZ-RP100VHA PUHZ-RP125VHA PUHZ-RP140VHA PUHZ-RP100YHA PUHZ-RP125YHA PUHZ-RP140YHA SPLIT-TYPE, HEAT PUMP AIR CDITIERS June 005 No.OC334 SERVICE MANUAL R40A Outdoor unit [model names] PUHZ-RP35VHA PUHZ-RP50VHA PUHZ-RP60VHA PUHZ-RP7VHA PUHZ-RP00VHA PUHZ-RP5VHA PUHZ-RP40VHA PUHZ-RP00YHA

More information

Compact 4-way Cassette ( ) Type

Compact 4-way Cassette ( ) Type E08-0 Engineering Data Compact 4-way Cassette (600 600) Type Indoor Unit RAV-SM40MUT-E RAV-SM4MUT-E Outdoor Unit RAV-SP404AT-E RAV-SP44AT-E Contents. Specifications. Connecting pipe length and lift difference

More information

PUHZ-SHW140YHA PUHZ-SHW230YKA

PUHZ-SHW140YHA PUHZ-SHW230YKA 1 Specifications Model Name PUHZ-SHW1YHA PUHZ-SHWYKA Power supply (phase, cycle, voltage) 3φ, 0V, Hz 3φ, 0V, Hz Max. current A 13.0 6.0 Breaker size A 16 3 Outer casing Galvanized plate Galvanized plate

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LLCC AS G09LLCC AS G12LLCC OUTDOOR AO G07LLCC AO G09LLCC AO G12LLCC 1.INDOOR UNIT : AS G07LLCC AS G09LLCC AS G12LLCC DTR_AS087E_02

More information

OUTDOOR AIR UNIT DTV_OAE034E_03--CHAPTER

OUTDOOR AIR UNIT DTV_OAE034E_03--CHAPTER DTV_OAE034E_03--CHAPTER01 2015.01.16 CONTENTS 1. FEATURES... A-01 2. SPECIFICATIONS... A-02 3. ELECTRIC CHARACTERISTICS... A-03 4. DIMENSIONS... A-05 5. REFRIGERANT CIRCUIT...A-11 6. WIRING... A-12 6-1.

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 19,100 BTU/h,200 BTU/h 30,600 BTU/h Outdoor Model No. CU-3KE19NBU CU-4KE24NBU

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G18LFCA AS G24LFCA AS G30LFCA OUTDOOR AO G18LFC AO G24LFL AO G30LFT 1. INDOOR UNIT : AS G18LFCA AS G24LFCA AS G30LFCA DTR_AS052E_01

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC Revision E: MUZ-FH25VE- E4, ER4, ET3, MUZ- FH35VE- E3, ER3, ET3 and MUZ- FH50VE- E2, ER2, ET2 have been added. Please void OBH624 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624

More information

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA PEAD-RP100EA(2) PEAD-RP125EA PEAD-RP140EA

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA PEAD-RP100EA(2) PEAD-RP125EA PEAD-RP140EA SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 005 SERVICE MANUAL Series PEAD R7C/RA Service ref. Models RP35EA() RP50EA RPEA RP7EA RP00EA() RP5EA RPEA NOTE: This manual describes only service data

More information

1 Features. Outdoor Units R-410A RYN-E3V1B. Split Sky Air Outdoor Units

1 Features. Outdoor Units R-410A RYN-E3V1B. Split Sky Air Outdoor Units Features O u t d o o r U n i S p l i t S k y R Y N - E V B R - 4 0 a Outdoor units for pair application Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply

More information

technical data air conditioning systems Indoor Units FBQ-C7VEB

technical data air conditioning systems Indoor Units FBQ-C7VEB technical data Indoor Units FBQ-C7VEB air conditioning systems technical data Indoor Units FBQ-C7VEB air conditioning systems Indoor Units R-40A FBQ-C7VEB TABLE OF CONTENTS FBQ-C7VEB Features.............................................................

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR ASU9RL2 ASU12RL2 OUTDOOR AOU9RL2 AOU12RL2 1.INDOOR UNIT : ASU9RL2 ASU12RL2 DTR_AS072E_01 2012.11.02 1. INDOOR UNIT CONTENTS 1. FEATURE...

More information

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E Revision E: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH629 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH629 REVISED EDITION-E Models

More information

Ceiling Cassettes PLH-3AKH1.UK PLH-3AKH.UK PLH-4AKHS1.UK PLH-4AKHS.UK PLH-5AKHS1.UK PLH-5AKHS.UK PLH-6AKHS1.UK PLH-6AKHS.UK

Ceiling Cassettes PLH-3AKH1.UK PLH-3AKH.UK PLH-4AKHS1.UK PLH-4AKHS.UK PLH-5AKHS1.UK PLH-5AKHS.UK PLH-6AKHS1.UK PLH-6AKHS.UK T AVAILABLE C AMPM AMPM SPLIT-TYPE, HEAT PUM PAIR CDITIERS No. OC REVISED EDITI-A TECHNICAL & SERVICE MANUAL Series PLH Indoor unit [Model names] PLH-3AK PLH-3AKH PLH-AKS PLH-AKHS PLH-5AKS PLH-5AKHS PLH-6AKS

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Duct type DESIGN & TECHNICAL MANUAL INDOOR ARU9RLF ARU12RLF ARU18RLF OUTDOOR AOU9RLFC AOU12RLFC AOU18RLFC 1. INDOOR UNIT : ARU9RLF ARU12RLF ARU18RLF DTR_AR059E_01 2013.02.28 1. INDOOR UNIT

More information

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC Revision F: The descriptions of the expansion valve coil have been corrected. (11-4.) Please void OBH590 REVISED EDITION-E. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED EDITION-F

More information

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type)

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) TECHNICAL MANUAL & PARTS LIST DRAFT INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type) SRK20ZD-S - 1 - INDOOR UNIT Model SRK20ZD-S OUTDOOR UNIT Model SRC20ZD-S REMOTE

More information

GUF-RD3 GUF-RDH3. OA Processing unit CONTENTS. OA Processing unit R410A

GUF-RD3 GUF-RDH3. OA Processing unit CONTENTS. OA Processing unit R410A OTETS GUF-RD3 GUF-RDH3. Specifications -6 2. Sound evels -7 2. oise levels -7 2.2 Fan characteristics curves -8 3. External Dimension -9 4. Wiring Diagrams - - . Specifications Item Power supply urrent

More information

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467. SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-HC35VA- E2 and MUZ-HC35VAB- E2 have been added. Please void OBH467 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH467 REVISED EDITION-B

More information

Launching of new SET-FREE Outdoor Units - RAS-FSXN1E Series (8-54HP)-

Launching of new SET-FREE Outdoor Units - RAS-FSXN1E Series (8-54HP)- Suary PAGE: 1 / 47 1 This Technical Bulletin introduces the new outdoor units of the SET-FREE FSXN1E Series (8 to 54HP) using R410A. 2 The details are indicated in the description. Index 1. Main concepts...

More information

SERVICE MANUAL R410A PUHZ-SP100VHA.UK PUHZ-SP125VHA.UK PUHZ-SP125VHA PUHZ-SP140VHA.UK PUHZ-SP140VHA PUHZ-SP100YHA.UK PUHZ-SP100YHA PUHZ-SP125YHA.

SERVICE MANUAL R410A PUHZ-SP100VHA.UK PUHZ-SP125VHA.UK PUHZ-SP125VHA PUHZ-SP140VHA.UK PUHZ-SP140VHA PUHZ-SP100YHA.UK PUHZ-SP100YHA PUHZ-SP125YHA. SPLIT-TYPE, HEAT PUMP AIR CDITIERS SERVICE MANUAL R40A January 05 No. OCH566 REVISED EDITI-A Outdoor unit [Model Name] PUHZ-SP00VHA PUHZ-SP5VHA PUHZ-SP40VHA PUHZ-SP00YHA PUHZ-SP5YHA PUHZ-SP40YHA [Service

More information

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-SP100JA(L) PEAD-SP125JA(L) PEAD-SP140JA(L) Models PEAD-SP71JA(L) <indoor unit>

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-SP100JA(L) PEAD-SP125JA(L) PEAD-SP140JA(L) Models PEAD-SP71JA(L) <indoor unit> SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 4 SERVICE MANUAL Series PEAD R4A Models PEAD-SP7JA(L) PEAD-SPJA(L) PEAD-SP5JA(L) PEAD-SPJA(L) NOTE: This manual describes only service data of the indoor

More information

Engineering Data Book

Engineering Data Book 40VMV Vertical Air Handling Indoor Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs

More information

TECHNICAL CATALOGUE MONO SPLIT RAK-25PSC RAK-35PSC RAC-35WSC

TECHNICAL CATALOGUE MONO SPLIT RAK-25PSC RAK-35PSC RAC-35WSC TECHNICAL CATALOGUE MONO SPLIT RAK-18PSC RAK-25PSC RAK-35PSC RAC-18WSC RAC-25WSC RAC-35WSC HITACHI Specifications in this catalogue are subject to change without prior notice in order for HITACHI to bring

More information

EEDEN technical data ERHQ AA

EEDEN technical data ERHQ AA EEDEN08-70 technical data Altherma Outdoor units R-410A Altherma Outdoor units 34 1 Features 1 O u t d o o r u n i A l t h e r m a E R H Q 0 1 1-0 1 6 A A R - 4 1 0 A Cost effective alternative to a fossil

More information

4. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air to air heat pump type)

4. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air to air heat pump type) 4. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air to air heat pump type) (OUTDOOR UNIT) SCM68ZA (INDOOR UNIT) SKM22ZA SKM25ZA SKM28ZA SKM32ZA SKM40ZA SKM50ZA SRRM40ZA 117 CONTENTS 4.1 GENERAL INFORMATION...

More information

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 Indoor unit service manual MSZ-DM VA Series (OBH750) CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES

More information

6. DUCT TYPE AR 60FUAK, AR 60UUAK

6. DUCT TYPE AR 60FUAK, AR 60UUAK R410A 6. AR 60FUAK, AR 60UUAK ART60UUAK D2D_AR010E/04 2006.05.30 - (06-01) - 6-1. FEATURE MODELS : AR 60FUAK / AO 60FMAYT AR 60UUAK / AO 60UMAYT ART60UUAK / AOT60UMAYT FEATURES Universal design indoor

More information

Engineering Data Book

Engineering Data Book 40VML Low Static Ducted Indoor Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS TECHNICAL & SERVICE MANUAL R07C Outdoor unit [model names] No.OC6 REVISED EDITION-B PUH-PVGAA PUH-P.6VGAA PUH-P.6YGAA PUH-PVGAA PUH-PYGAA

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Cassette type DESIGN & TECHNICAL MANUAL SINGLE INDOOR AU GLVLB AU G4LVLB AU G8LVLB AU G4LVLA OUTDOOR AO GLALL AO G4LALL AO G8LALL AO G4LALA . INDOOR UNIT : AU GLVLB AU G4LVLB AU G8LVLB

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information

TECHNICAL & SERVICE MANUAL. Wall Mounted. Series PKFY PKFY-P20VAM-A PKFY-P25VAM-A R407C R22 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No.

TECHNICAL & SERVICE MANUAL. Wall Mounted. Series PKFY PKFY-P20VAM-A PKFY-P25VAM-A R407C R22 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. SPLIT-TYPE, HEAT PUMP AIR CDITIERS 00 No. OC TECHNICAL & SERVICE MANUAL Series PKFY Wall Mounted R07C R Indoor unit [Model names] PKFY-P0VAM-A [Service Ref.] PKFY-P0VAM-A CTENTS INDOOR UNIT. SAFETY PRECAUTI.

More information

Fresh Master. Installation Instructions (For use by dealer/contractor) GUF-50RDH3 GUF-50RD3 GUF-100RDH3 GUF-100RD3. Models:

Fresh Master. Installation Instructions (For use by dealer/contractor) GUF-50RDH3 GUF-50RD3 GUF-100RDH3 GUF-100RD3. Models: Fresh Master Models: GUF-0RDH GUF-0RD GUF-00RDH GUF-00RD Installation Instructions (For use by dealer/contractor) GUF-0RDH shown above. Contents. Safety precautions... -. Accessories.... Outline drawings....

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL KHS308 + CH308 KHS368 + CH368 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KHS308 KHS368 Product Code No. 85 354 8 85 354 9 Outdoor

More information

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. Please void OBH733 REVISED EDITION-A. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH733 REVISED EDITION-B Models MUZ-GL09NA

More information

AIR-CONDITIONER TOSHIBA SERVICE MANUAL SPLIT TYPE, HEAT PUMP COOLING ONLY FILE NO. A Tel: Fax:

AIR-CONDITIONER TOSHIBA SERVICE MANUAL SPLIT TYPE, HEAT PUMP COOLING ONLY FILE NO. A Tel: Fax: Tel: 08 0 www.heronhill.co.uk Fax: 08 80 TOSHIBA Heronhill - for all your Toshiba requirements FILE NO. A90-00 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE, HEAT PUMP COOLING ONLY WAY CASSETTE TYPE RAV-0TUH--PE

More information

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA ARGO 245C / 3SC Cooling only model ARGO 235H / 3HP Heat pump model 0.8180.405.2 09/2006 Table of contents Page A SPECIFICATIONS 1) Unit specifications 3

More information

Your Climate. We're There. TM: MDB B 2140B. Ducted Split Systems. Models: MDB 075B - MDB750B MDB 075B/B - MDB500BR. Air Conditioning REGISTERED

Your Climate. We're There. TM: MDB B 2140B. Ducted Split Systems. Models: MDB 075B - MDB750B MDB 075B/B - MDB500BR. Air Conditioning REGISTERED Your Climate. We're There. TM: MDB B 2140B Ducted Split Systems Models: MDB 075B - MDB750B MDB 075B/B - MDB500BR REGISTERED Air Conditioning Contents Nomenclature System... 2 Features... 2 General Specifications...3-5

More information

technical data air conditioning systems RZQ-B Pair/Twin/Triple/Double Twin Application, Inverter Controlled Unit Split Sky Air

technical data air conditioning systems RZQ-B Pair/Twin/Triple/Double Twin Application, Inverter Controlled Unit Split Sky Air technical data RZQ-B ///Double Application, Inverter Controlled Unit air conditioning systems Split Sky Air Split - Sky Air ISO14001 assures an effective environmental management system in order to help

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH Revision D: Capacity corrections have been corrected [7-1. 2), 3)]. OBH684 REVISED EDITION-C is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH684 REVISED EDITION-D Models MUZ-FH06NA MUZ-FH09NA

More information

TABLE OF CONTENTS ERHQ BAV3

TABLE OF CONTENTS ERHQ BAV3 TABLE OF CONTENTS ERHQ006-016BAV3 1 Features........................................................... 134 2 Specifications..................................................... 135 Nominal Capacity and

More information

SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE

SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE Indoor unit ABYF8LAT ABYF8LAT ABYF8LAT ABYF8LAT ABYF8LBT ABYF8LBT ABYFLAT ABYFLAT ABYFLAT ABYFLAT ABYFLBT ABYFLBT Outdoor unit AOYA8LACL

More information

OA Processing unit GUF-RD4, GUF-RDH4

OA Processing unit GUF-RD4, GUF-RDH4 Processing unit DT G GUFRD4, GUFRDH4 I. Processing unit. SPEIFITIOS... 27 2. SOUD EVES... 28 2. Measurement ondition... 28 22. curves... 28. F HRTERISTIS URVES... 29 4. EXTER DIMESIOS... 240 5. EETRI WIRIG

More information

SUBMITTAL DATA: PVA-A42AA7 & PUZ-A42NKA7(-BS) 42,000 BTU/H AIR HANDLER HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A42NKA7

SUBMITTAL DATA: PVA-A42AA7 & PUZ-A42NKA7(-BS) 42,000 BTU/H AIR HANDLER HEAT PUMP SYSTEM. Job Name: System Reference: Outdoor Unit: PUZ-A42NKA7 P-SERIES SUBMITTAL DATA: PVA-A42AA7 & PUZ-A42NKA7(-BS) 42,000 BTU/H AIR HANDLER HEAT PUMP SYSTEM Job Name: System Reference: Date: Indoor Unit: Outdoor Unit: PVA-A42AA7 PUZ-A42NKA7 PUZ-A42NKA7-BS INDOOR

More information

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC Revision A: MUZ-HM09/12NA- U8, MUZ-HM09/12NA2- U8, MUZ-HM15/18NA- U1, MUZ-HM15/18NA2- U1 and MUZ-HM24NA2- U1 have been added. Please void OBH747. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A.

More information

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2 Revision F: "How to check miswiring and serial signal error" has been corrected (11-5. M ). OBH648 REVISED EDITION-E is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH648 REVISED EDITION-F Models

More information

Engineering Data Book

Engineering Data Book 40VMU Under Ceiling/Floor Indoor Unit for Variable Refrigerant Flow (VRF) Systems Engineering Data Book Manufacturer reserves the right to discontinue, or change at any time, specifications or designs

More information

SERVICE MANUAL MXZ-2A40VA - MXZ-2A52VA - MXZ-3A54VA - MXZ-3A54VA - MXZ-4A71VA - MXZ-4A71VA - MXZ-4A80VA - E1 OUTDOOR UNIT. No. OB377 REVISED EDITION-A

SERVICE MANUAL MXZ-2A40VA - MXZ-2A52VA - MXZ-3A54VA - MXZ-3A54VA - MXZ-4A71VA - MXZ-4A71VA - MXZ-4A80VA - E1 OUTDOOR UNIT. No. OB377 REVISED EDITION-A SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Revision : A MXZ-A5/A7VA- MXZ-A0/A5VA- Please void OB77 E E has been added. has been added. OUTDOOR UNIT SERVICE MANUAL HFC utilized R0A No. OB77 REVISED EDITION-A

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL KS1872 + C1872 + CL1872 KS2472 + C2472 + CL2472 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. KS1872 KS2472 Product

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL XHS1271 & PNR-XS1872 + CH1271 XHS1872 & PNR-XS1872 + CH1872 FILE NO. Destination: North America DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) XHS1271

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CLM97 CLM7 CLM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No.

More information