1 RECAPP Facility Evaluation Report East Central Health Viking Community Health Services B1178A Viking Report run on: March 22, 21 9:58 AM

2 Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement : Construction : Facility Details Viking Community Health Se Avenue Viking B1178A. $ Viking - Viking Community Health Services (B1178A) Evaluation Company: Evaluation Date: August Evaluator Name: Evaluation Details A&E Architectural & Engineering Group Inc. Vic Maybroda Total Maintenance Events Next 5 years: $2,973,59 5 year Facility Condition Index (FCI): % General Summary: The Health Centre is a single storey facility with basement originally constructed in with an addition constructed in. The facility contains two patient care wings with and assisted bath/shower area, a day dining room and lounge areas, a radiology area, a laboratory area, an ambulance bay with associated triage/treatment areas, an operating room, administration and support spaces. The approximate overall area is 3252 sq. M. Structural Summary: Foundations consist of cast in place concrete walls on strip footings and concrete piles supporting a concrete floor slab on metal deck supported by metal joists. Concrete slab on grade is located in the basement areas Superstructure is composed of metal roof deck on metal joists supported by metal beams and columns. Structural elements appear to be in good condition. Envelope Summary: Roofing is of built-up asphalt and SBS membrane with prefinished metal cladding over the main entry. Walls consist of face brick and EIFS elements housing sealed fixed windows in aluminum frames, aluminum framed storefronts, metal clad overhead doors and painted metal clad doors. Overall these elements appear to be in good condition. Interior Summary: Flooring consists of painted concrete, epoxy, ceramic and porcelain tile, VC tiles, sheet vinyl and carpeting. Walls are of painted concrete block, stained wood paneling, ceramic tile and gypsum wallboard housing stained wood and painted metal clad doors in metal frames and single glazed window units in metal frames. Ceilings consist of suspended acoustical tile and painted gypsum wallboard. Millwork consists of plastic laminated counter tops and vanities with plastic laminated and stained wood cabinetry. Overall these elements appear to be in acceptable condition. Mechanical Summary: Ventilation is provided by variety of air handling units located in Mechanical Rooms or in Penthouse. Total of six (6) air handling units. Air distribution system is via medium and low velocity single ductwork to VAV and constant volume boxes, grilles and diffusers. Air conditioning is provided by an outdoor air cooled chiller. Heating system includes two boiler plants from and. Two natural gas fired boilers provide steam to heat exchangers serving section as well as steam for humidifcation. Additional two gas fired boilers are located in Mechanical Room serving addition. Domestic hot water is generated by two hot water tanks fed from designated boiler in Mechanical Room and ondemand domestic water heater in Mechanical Room. Copper piping distribution to plumbing fixtures complete with domestic hot water recirculation systems. Controls include a combination of pneumatic and digital programmable building management control system. Medical gas systems include the piping, fittings, valves, air compressor and vacuum pumps. Medical oxygen, nitrous oxide, medical air and vacuum system are provided throughout. Alarms monitor system installed in Nurses Stations. Valved shut-off stations provided. Fire protection system for the facility consists of automatic sprinkler system, standpipe system and hand held fire extinguishers. Sanitary and storm services to Town's mains. Report run on: March 22, 21 9:58 AM Page 2 of 5

3 Viking - Viking Community Health Services (B1178A) Domestic water supplied from the municipal systems. Municipal natural gas service to gas fired appliances. Overall mechanical system is in good condition. Electrical Summary: The facility was originally built in and the major renovation and addition was completed. The main service is 347/6V, 3 phase, 4 wire and rated 16A and set at 12A. The service is underground fed from pad mounted transformer. Central and localized dry type transformers further covert to 12/28V for use with lighting, receptacles and other single and three phase equipment. Emergency power was provided by one 5KVA outdoor diesel generator. The Motor control equipment was centralized in 6V 3 phase MCC, located in mechanical room and some small mechanical loads were controlled by individual load switches or magnetic starters The interior fluorescent light fixtures were retrofit with T-8 lamps in section of building and new T-8 fixtures were installed at section of building. The exterior lighting system is combined wall packs around building perimeter and pole mounted lights in the parking lot. All fire alarm system, nurse call and PA systems meet current facility requirements. The fire alarm system and PA system have been recently upgraded. The telephone and cable TV system; the new master clock system was installed and has digital slave clocks installed through entire facility. A local area network provides the hospital with computer services for the operation of the facility and ties to Alberta Health Services through Supernet. The overall rating for the facility shall be "Good" Guide Condition Performance 1 - Critical Unsafe, high risk of injury or critical system failure. 2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs. 3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs. Meets present requirements, minor deficiencies. Average operating/maintenance costs. Meets all present requirements. No deficiencies. 6 - Excellent As new/state of the art, meets present and foreseeable requirements. Report run on: March 22, 21 9:58 AM Page 3 of 5

4 S1 STRUCTURAL Viking - Viking Community Health Services (B1178A) A11 Standard Foundations* - & Sections Perimeter cast in place concrete foundation walls on strip footings and concrete piles located in crawl spaces. 1 A1 Slab on Grade* - & Sections Cast in place concrete located in basement area. 1 A22 Basement Walls (& Crawl Space)* - & Sections Cast in place concrete foundation walls 1 B11.1 Floor Structural Frame (Building Frame)* - & Sections Concrete floor slab on metal deck supported by metal joists. 1 B11.3 Floor Decks, Slabs, and Toppings* - & Sections Cast in place concrete. 1 B11.6 Ramps: Exterior* - Section Asphalt driveway ramps to/from ambulance bay of section and concrete ramp to loading dock area. 4 B11.7 Exterior Stairs* Concrete stair adjacent ambulance bay accessing trauma entry area. 4 Report run on: March 22, 21 9:58 AM Page 4 of 5

5 B11.9 Floor Construction Fireproofing* - & Sections Concrete floor slab. Viking - Viking Community Health Services (B1178A) 5 B11.1 Floor Construction Firestopping* - & Sections Concrete floor slab. 5 B12.1 Roof Structural Frame* - & Sections Metal joists supported by metal beams and columns. 1 B12.3 Roof Decks, Slabs, and Sheathing* - & Sections Metal roof deck. B12.4 Canopies* - Section Exposed metal deck on exposed metal framing supported by metal columns over main entry area. Textured stucco clad metal framed canopy located adjacent Day Dining Room. Pre-cast concrete clad metal framed canopy over exterior staff lounge area supported of concrete clad metal column. 5 Report run on: March 22, 21 9:58 AM Page 5 of 5

6 S2 ENVELOPE Viking - Viking Community Health Services (B1178A) B Brick Masonry: Ext. Wall Skin* - & Sections Located on all areas. 75 B Exterior Insulation and Finish Systems (EIFS)* - Section Located in various areas of the wall area. 75 B Metal Siding** - Section Prefinished vertical metal cladding applied the penthouse structures. 4 Replace 64 sq. M Metal Siding 221 $21,76 : B Metal Siding** - Section Prefinished vertical siding applied to penthouse structure. 4 Replace 82 sq M Metal Siding 248 $27,88 : B Cement Plaster (Stucco): Ext. Wall* - Section Located in various upper areas of the exterior wall. 75 Report run on: March 22, 21 9:58 AM Page 6 of 5

7 B Expansion Control: Exterior Wall Skin* - & Sections Strategically located caulked joints in face brick and EIFS cladding. Viking - Viking Community Health Services (B1178A) 75 B Joint Sealers (caulking): Ext. Wall** - Section Caulking installed around all exterior openings. 2 Replace 42 M Joint Sealers (caulking): Ext. Wall 213 $14,7 : B Joint Sealers (caulking): Ext. Wall** - Section Caulking installed around all exterior openings. 2 Replace 178 M Joint Sealers (caulking): Ext. Wall 228 $6,2 : B Paints (& Stains): Exterior Wall** - Section 3 - Painted metal clad doors and frames, bollards and chimney vents. 15 Replace 2 sq. M Paints (& Stains): Exterior Wall 213 $1, : Report run on: March 22, 21 9:58 AM Page 7 of 5

8 B Masonry Units: Ext. Wall Const.* - & Sections Concrete block. Viking - Viking Community Health Services (B1178A) 1 B21.3 Exterior Wall Vapor Retarders, Air Barriers, and Insulation* - & Sections Not viewable. No concerns observed or reported. 1 B21.5 Parapets* - & Sections. Concrete block to section and metal stud to section. 5 B21.6 Exterior Louvers, Grilles, and Screens* - & Sections Prefinished metal louvres to mechanical room and roof top penthouses. 5 B21.9 Exterior Soffits* - Section Prefinished metal to canopy soffits. 5 B Aluminum Windows (Glass & Frame)** - Section Sealed units in aluminum frames. 4 Replace 118 Aluminum Windows (Glass & Frame) 221 $147,5 : Report run on: March 22, 21 9:58 AM Page 8 of 5

9 B Aluminum Windows (Glass & Frame)** - Section Sealed fixed units in aluminum frames. Viking - Viking Community Health Services (B1178A) 4 Replace 22 Aluminum Windows (Glass & Frame) 248 $27,5 : B22.2 Storefronts: Windows** - Section Sealed units in aluminum frames each side of access door to Day Dining area 4 Replace 2 Storefronts: Windows 221 $2,8 : B2.1.1 Aluminum-Framed Storefronts: Doors** - Section Sealed glazed units in aluminum frames located at access to Day Dining area and from lounge area in patient care wing. Replace 2 Aluminum-Framed Storefronts: Doors 213 $7,5 : B2.1.1 Aluminum-Framed Storefronts: Doors** - Section Double sealed glazed aluminum framed doors accessing Emergency entry. Repace 2 Aluminum-Framed Storefronts: Doors 238 $7,5 : Report run on: March 22, 21 9:58 AM Page 9 of 5

10 B2.1.6 Automatic Entrance Doors** - Section Viking - Viking Community Health Services (B1178A) 2 - double power actuated swinging doors in aluminum frames with sensors at main entry. Replace 4 Automatic Entrance Doors 213 $6, : B2.1.6 Automatic Entrance Doors** - Section 2-1/2 glazed painted metal swinging doors with sensor in metal frame accessing Ambulance Bay. Replace 2 Automatic Entrance Doors 238 $7,5 : B2.2 Exterior Utility Doors** - Section Painted metal clad doors and frames. 4 Replace 4 Exterior Utility Doors 221 $4,4 : B2.3 Large Exterior Special Doors (Overhead)* - Section Prefinished metal clad overhead doors accessing Ambulance Bay. Report run on: March 22, 21 9:58 AM Page 1 of 5

11 B1.1 Deck Vapor Retarder and Insulation* - & Sections Not viewable. No concerns observed or reported. Viking - Viking Community Health Services (B1178A) 25 B1.4.1 Built-up Bituminous Roofing (Asphalt & Gravel)** - Section Built-up roof area between air handling units. 25 Replace 36 sq. M Built-up Bituminous Roofing (Asphalt & Gravel) 213 $7,56 : B1.4.4 Modified Bituminous Membrane Roofing (SBS)** - Section SBS membrane replaced in Replace 266 sq. M Modified Bituminous Membrane Roofing (SBS) 22 $532, : B1.4.4 Modified Bituminous Membrane Roofing (SBS)** - Section SBS membrane. 25 Replace 615 sq. MModified Bituminous Membrane Roofing (SBS) 233 $123, : Report run on: March 22, 21 9:58 AM Page 11 of 5

12 Viking - Viking Community Health Services (B1178A) B1.7 Sheet Metal Roofing** - Section Prefinished metal roof over entry area. 4 Replace 55 sq. M Sheet Metal Roofing 221 $14,25 : B2.2 Other Roofing Openings (Hatch,Vent, etc)* - & Sections Roof hatch in section with exhaust fan housings, chimney and plumbing vents and roof drains located in each section. 25 Report run on: March 22, 21 9:58 AM Page 12 of 5

13 S3 INTERIOR Viking - Viking Community Health Services (B1178A) C11.1 Interior Fixed Partitions* - & Sections Concrete block and metal stud. C11.5 Interior Windows* - & Sections There are clear glass window units in painted metal frames located in each section of the facility. 8 C12.1 Interior Swinging Doors (& Hardware)* - & Sections Painted and stained wood doors in painted metal frames in all areas of the facility with lever handled hardware to public areas. 4 C12.3 Interior Fire Doors* - & Sections Rated doors and frames interlocked with fire alarm system located between & sections. Rated doors and frames to service rooms in each section. 5 C1.1 Visual Display Boards** - Section White and tack boards located in various areas of the section. 2 Replace 12 Visual Display Boards 213 $9, : Report run on: March 22, 21 9:58 AM Page 13 of 5

14 Viking - Viking Community Health Services (B1178A) C1.1 Visual Display Boards** - Section White and tack boards are located in various area of this section. 2 Replace 8 Visual Display Boards 228 $6, : C1.2 Fabricated Compartments(Toilets/Showers)** - Section Prefinished metal toilet partitions. Replace 3 Fabricated Compartments(Toilets/Showers) 213 $4,8 : C1.5 Wall and Corner Guards* - & Sections Combination of PVC and stainless steel corner guards located in various areas of the facility. 15 C1.6 Handrails* - & Sections Stained wood wall mounted handrails located in section and PVC handrails locate in section. 4 C1.7 Fireplaces and Stoves* - Section Brick constructed fireplace located in lounge area of lounge area of patient care wing. Report run on: March 22, 21 9:58 AM Page 14 of 5

15 C1.8 Interior Identifying Devices* - & Sections Room names and numbers applied to doors. Viking - Viking Community Health Services (B1178A) 2 C1.1 Lockers** - Section Prefinished metal lockers located in staff change rooms. Replace 42 Lockers 213 $27,9 : C1.1 Lockers** - Section Prefinished metal lockers located in laboratory area. Replace 5 Lockers 238 $3,325 : C1.12 Storage Shelving* - & Sections Painted wood and prefinished metal located in each section, C1.14 Toilet, Bath, and Laundry Accessories* - & Sections Toilet paper, paper towels and soap dispensers, mirrors and waste containers located in wash rooms of each section. 2 Report run on: March 22, 21 9:58 AM Page 15 of 5

16 Viking - Viking Community Health Services (B1178A) C21 Stair Construction* - Section Concrete stair to basement level from main floor and from basement to exterior vestibule. Metal stair to roof access. 1 C22.5 Resilient Stair Finishes** Rubber tile on basement stair. 2 Replace 16 sq. M Resilient Stair Finishes 213 $1,6 : C22.8 Stair Railings and Balustrades* Painted metal handrails and balustrades. 4 C1.2 Wall Paneling** Stained wood paneling installed on west wall of Family Room. Replace 7 sq M Wall Paneling 213 $1,5 : Report run on: March 22, 21 9:58 AM Page 16 of 5

17 Viking - Viking Community Health Services (B1178A) C1.6 Tile Wall Finishes** Paver tiles installed in entry foyer. Replacement $31/sq. M = $6,82. Ceramic tiles installed in Assisted Bath area and showers. Replacement $2/sq. M = $7,2. 4 Replace Tile Wall Finishes 221 $14,2 : C1.11 Interior Wall Painting* - & Sections Painted concrete block and gypsum wallboard. 1 C1.12 Wall Coverings* Vinyl wall covering applied to basement staff lounge area and administration office areas. 15 C2.1.1 Epoxy Concrete Floor Finishes* Located in Assisted Bath area. C2.1.2 Paint Concrete Floor Finishes* Applied to mechanical and electrical rooms. 1 Report run on: March 22, 21 9:58 AM Page 17 of 5

18 Viking - Viking Community Health Services (B1178A) C2.2 Tile Floor Finishes** Applied to 2 showers in Assisted Bath area. 5 Replace 3 sq. M Tile Floor Finishes 231 $1, : C2.7 Resilient Flooring** - Section Combination of VCT and sheet vinyl installed in patient areas, corridors, treatment areas and basement areas. 2 Replace187 sq. M Resilient Flooring 213 $187, : C2.7 Resilient Flooring** - Section Sheet vinyl installed in Kitchen area. 3 - Marginal 2 Replace 62 sq. M Resilient Flooring Concern: Sheet flooring is badly deteriorated and worn in Kitchen area. Recommendation: Replace sheet vinyl flooring. Failure Replacement 21 $6,2 Low : Report run on: March 22, 21 9:58 AM Page 18 of 5

19 Viking - Viking Community Health Services (B1178A) C2.7 Resilient Flooring** - Section Sheet vinyl located in all areas. 2 Replace 572 sq. M Resilient Flooring 228 $57,2 : C2.8 Carpet Flooring** in staff lounge, offices areas and conference room. 15 Replace 8 sq. M Carpet Flooring 213 $5,2 : C.6 Acoustic Ceiling Treatment (Susp.T-Bar)** - Section Located in patient rooms, corridors, treatment rooms and administration areas. 25 Replace 164 sq. M Acoustic Ceiling Treatment (Susp.T-Bar) 213 $98,4 : Report run on: March 22, 21 9:58 AM Page 19 of 5

20 C.6 Acoustic Ceiling Treatment (Susp.T-Bar)** - Section Located in treatment areas, corridors and administration areas. Viking - Viking Community Health Services (B1178A) 25 Replace 44 sq. M Acoustic Ceiling Treatment (Susp.T-Bar) 233 $26,4 : C.7 Interior Ceiling Painting* - & Sections Located in patient room vestibule and bath rooms, Day Dining Room, Assisted Bath and service rooms of section. Located in service areas of section. 2 C.9 Other Ceiling Finishes* Prefinished metal lineal ceiling located in main entry area. 5 D Hydraulic Passenger Elevators** One hydraulic elevator having a capacity of 48 lbs with front and rear entry doors. Replace 1 Hydraulic Passenger Elevators 213 $1, : Report run on: March 22, 21 9:58 AM Page 2 of 5

21 S4 MECHANICAL Viking - Viking Community Health Services (B1178A) D21.4 Sinks** - Single and double compartment stainless steel sinks located throughout the facility. Stainless steel commercial sinks serving Kitchen. 6X6 mop sinks, molded stone, floor mounted, SS strainer. 316 Gauge stainless steel sinks serving Labs. Replace Approx. 36 Sinks 213 $9, : D21.4 Sinks** - 6X6 mop sinks, molded stone, floor mounted, SS strainer. Single and double compartment stainless steel sinks complete with chrome plated swing spout, aerator, lever handles. Replace Approx. Sinks 238 $65, : D21.5 Showers** - Handicap shower stalls, acrylic tub with chrome grab bars. Thermostatic mixing valve, pressure balanced. Replace Approx. 12 Showers 213 $36, : Report run on: March 22, 21 9:58 AM Page 21 of 5

22 Viking - Viking Community Health Services (B1178A) D21.5 Showers** - Handicap shower stalls, acrylic tub with chrome grab bars. Thermostatic mixing valve, pressure balanced. Ceramic tile surface showers with mixing valve. Replace 4 Showers 238 $2, : D21.6 Bathtubs** Assisted bath tub Bowl, disinfections system, locking door, thermoscopic mixing valve. Fiberglass bathtubs, holders, mixing valves and removable shower heads. Replace Approx. 1 Bathtubs 213 $81, : D21.8 Drinking Fountains / Coolers** - Stainless steel wall hung, refrigerated drinking fountains. 35 Replace Approx. 6 Drinking Fountains / Coolers 216 $, : Report run on: March 22, 21 9:58 AM Page 22 of 5

23 Viking - Viking Community Health Services (B1178A) D21.8 Drinking Fountains / Coolers** - Stainless steel wall hung, refrigerated drinking fountains. 35 Replace 2 Drinking Fountains / Coolers 243 $1, : D21.1 Washroom Fixtures (WC, Lav, Urnl)** - WC - Vitreous china, open front seat, flush valve. LV - Enameled steel countertop lavatories c/w two handle faucets. Wall mounted vitreous china lavatories. UR - wall mounted, vitreous china with flush valve. 35 Replace Approx. 58 Washroom Fixtures 216 $116, : D21.1 Washroom Fixtures (WC, Lav, Urnl)** - WC - Vitreous china, open front seat, flush valve. LV - Stainless steel countertop lavatories c/w two handle faucets. Wall mounted vitreous china lavatories with infrared faucets. UR - wall mounted, vitreous china with flush valve. 35 Replace Approx. 28 Washroom Fixtures 243 $56, : D Pipes and Tubes: Domestic Water* Copper piping distribution throughout. Piping installed in and. Some portion of older piping replaced during modernization. 4 Report run on: March 22, 21 9:58 AM Page 23 of 5

24 Viking - Viking Community Health Services (B1178A) D Valves: Domestic Water** - Domestic water distributed to commercial flush valve fixtures installed throughout the building. Plumbing fixtures grouped in zones. 4 Replace Domestic Water Valves 221 $95, : D Valves: Domestic Water** - Domestic water distributed to commercial flush valve fixtures installed throughout the building. Globe and ball isolation valves. 4 Replace Domestic Water Valves 248 $45, : D Piping Specialties (Backflow Preventors)** Reduced pressure backflow preventors serving incoming domestic water line and fire line. Double check valves assembly on fire line from siamese connections. Backflow prevention installed on boiler make-up water. Double check valve arrangement serving chilled water system. Vacuum breakers serving NFHB. 2 Replace Backflow Preventors 228 $12, : Report run on: March 22, 21 9:58 AM Page 24 of 5

25 Viking - Viking Community Health Services (B1178A) D Plumbing Pumps: Domestic Water** Four in-line domestic hot water recirculation pumps serving domestic hot water systems (6 and 8 deg.c). 2 Replace Plumbing Pumps: Domestic Water 213 $15, : D Domestic Water Conditioning Equipment** Duplex water softener package complete with brine tank and two resin tanks. 2 ReplaceReplace Domestic Water Conditioning Equipment 213 $15, : D Domestic Water Heaters** Domestic hot water heating system consist of two hot water tanks complete with heating coils and 3-way mixing valves. Tank serves 6 and 8 deg.c domestic water system. Tanks have capacity of 1,415 and 99 l. System is fed from main boiler loop complete with all associated recirculation pumps, control valves, piping and controls. 2 Replace Domestic Hot Water Heaters and Accessories 213 $95, : D22.3 Water Supply Insulation: Domestic* Water piping insulated throughout. 4 Report run on: March 22, 21 9:58 AM Page 25 of 5

26 Viking - Viking Community Health Services (B1178A) D2.1 Waste and Vent Piping* Cast iron and PVC sanitary lines. 5 D2.3 Waste Piping Equipment* Grease trap serving Kitchen sinks. Sump pit complete with duplex pump serving weeping tile system. Double compartment sump complete with trench serving Ambulance Bay. D24.1 Rain Water Drainage Piping Systems* Cast iron and PVC. 5 D Roof Drains* Large dome, sump roof drains with flashing flange and integral gravel stop. Open flow roof drains. 4 D29.1 Nitrous Oxide Gas Systems** NO gas supply manifolds and tanks. Unit consists of two banks of high pressure cylinders, pressure relief valve, high pressure header valves and cylinder connection coils. Replace Nitrous Oxide Gas System 213 $15, : Report run on: March 22, 21 9:58 AM Page 26 of 5

27 Viking - Viking Community Health Services (B1178A) D29.11 Oxygen Gas Systems** The medical supply manifold and tanks. Manifold consists of header connections and pigtails for oxygen cylinders. Replace Oxygen Gas Systems 213 $145, : D29.13 Vacuum Systems (Medical)** Vacuum drawn by duplex vacuum pump complete with piping and exhaust mufflers. Pumps are equipped with guards, automatic water valves, strainer and regulating valves, vacuum gauge, water-air outlet separator, receiver and isolation valves. Replace Vacuum Systems (Medical) 238 $15, : D29.16 Medical Air System* Medical air provided from duplex compressor. System consists of packaged compressor with low water pressure alarm sensor, fresh air intake filters, aftercooler, refrigerated air dryers, line pressure regulator and main shut-off valve. D1.1 Oil Supply Systems (Fuel, Diesel)* Supply oil to the boilers and emergency generator system consists of a main tank, auxiliary tank, two transfer pumps and level alarm switches. Main fuel oil tank (455 l) is located outside, one (682 l) day tank located in mechanical room. 6 D1.2 Gas Supply Systems* Pressure gas service for all gas fired appliances. Regulator at each fixture. Steel schedule 4 piping. 6 Report run on: March 22, 21 9:58 AM Page 27 of 5

28 D2.1.1 Heating Boilers & Accessories: Steam** Viking - Viking Community Health Services (B1178A) Two gas fired boilers are located in Mechanical Room. Heating boilers are manufactured by Cleaver Brooks - 4, Natural gas, 14 psi, 14 kw heating output each. Two base mounted primary heating pumps circulate steam via closed loop to heat exchangers. 35 Replace Boiler Plant and Accessories 216 $35, : D2.1.3 Chimneys (&Comb. Air) : Steam Boilers** Individual breechings to common vent up through the roof. Combustion air up to code. 35 Replace Chimneys &Comb. Air 216 $2, : D2.2.1 Heating Boilers and Accessories: H.W.** Two forced draft boilers Aerco Modulex complete with two Armstrong circulation pumps and accessories. 35 Replace Boiler Plant 243 $, : Report run on: March 22, 21 9:58 AM Page 28 of 5

29 Viking - Viking Community Health Services (B1178A) D2.2.2 Chimneys (&Comb. Air): H.W. Boiler** Insulated boilers vent up through the roof. Combustion air up to code. Replace Chimneys &Comb. Air 238 $1, : D2.2.3 Water Treatment: H. W. Boiler* Chemical pot feeder, by-pass filter, by-pass filter cartridge, in-line flow restrictor device. D.2 Centrifugal Water Chillers** McQuay AGS series, air cooled screw compressor chiller, 21 tons cooling capacity Replace Chiller 229 $5, : D4.1.1 Air Handling Units: Air Distribution** - Ventilation system consist of four air handling units located in Mechanical Room and penthouses. All units complete with supply and return air fans, pre-heat and re-heat coils, summer and winter filters, steam grid humidifier and cooling coils. Airflow capacities vary from 5,l/s to 19,l/s. Replace 4 Air Handling Units 213 $9, : Report run on: March 22, 21 9:58 AM Page 29 of 5

30 D4.1.1 Air Handling Units: Air Distribution** - Viking - Viking Community Health Services (B1178A) Two indoor air handling units serving Acute Care Addition and Ambulance Bay. Unit serving Acute Care is located in penthouse mechanical room, complete with S/A, R/A fans, heat recovery section, glycol heating and cooling coils, mixed air section, dampers section etc. Unit is manufactured by Engineered_Air model LM-HRW and has capacity of 75 l/s. Air handling unit serving Ambulance Bay is suspended from the ceiling and interlock with exhaust fans and CO/NOx detectors. Packaged gas fired complete with stainless steel heat exchanger, Engineered_air DJ-2, 5 l/s. D4.1.3 Air Cleaning Devices:Air Distribution* Replaceable media filters serving air handling units. D4.1.4 Ducts: Air Distribution* The majority of air distribution systems are insulated galvanized steel ducts installed in the ceiling spaces and distributed via ceiling diffusers. Stainless steel ductwork serving HEPA filters. 5 D4.1.6 Air Terminal Units: Air Distribution (VAV Box)** - Variable volume, single duct boxes, fan powered terminal boxes provide cooling and ventilation. Airflow varies from 45 to 7 l/s. Replace Approx. 12 VAV Boxes 213 $48, : Report run on: March 22, 21 9:58 AM Page of 5

31 D4.1.6 Air Terminal Units: Air Distribution (VAV Box)** - Viking - Viking Community Health Services (B1178A) Constant and variable volume, single duct boxes, fan powered terminal boxes provide cooling and ventilation with 1% primary air shut-off. Airflow varies from 45 to 5 l/s. Replace Approx. 4 VAV Boxes 238 $16, : D4.1.7 Air Outlets & Inlets:Air Distribution* The majority of air outlets throughout the various wings of the facility are square cone ceiling diffusers or wall mounted louver face grilles. D4.2 Steam Distribution Systems: Piping/Pumps** Steam generator complete with feed lines, condensate receiver tank with pumps, blow down tank, supply headers, steel piping distribution to heat exchangers. 4 Replace Steam Distribution System 221 $125, : Report run on: March 22, 21 9:58 AM Page 31 of 5

32 D4.3.1 Hot Water Distribution Systems** - Viking - Viking Community Health Services (B1178A) Steel and copper piping distribution from primary heating loop to secondary loops and heat exchangers serving perimeter radiation, re-heat coils and domestic hot water system. HWS and HWR loop to perimeter radiation and unit heaters. HWS and HWR loop to ceiling radiant panels. HWS and HWR loop to hot water/ glycol heat exchanger. Radiant panels loop and radiation loop are completed with two base mounted circulation pumps each. Glycol heat exchanger is fed of the two primary heating pumps. Two base mounted circulation pumps distribute hot water/glycol to air handling units re-heat coils. 4 Replace Hot Water Distribution System Serving Section B.O.E. $93. / sq/m/ 221 $45, : D4.3.1 Hot Water Distribution Systems** - Steel piping distribution from primary heating loop to heat exchanger serving re-heat coils. Radiant panels loop and radiation loop are completed with two base mounted circulation pumps each. Glycol heat exchanger is fed of the two primary heating pumps. Two in-line circulation pumps distribute hot water/glycol to air handling units re-heat coils. 4 Replace Hot Water Distribution System Serving Section B.O.E. $93. / sq/m/ 248 $1, : D4.3.2 Chilled Water Distribution Systems** CWS and CWR lines serving chiller. 15mm diameter chilled water loop to cooling coils serving air handling units. Base mounted circulation pumps. Copper and steel pipes. 4 Replace Chilled Water Distribution System 221 $1, : Report run on: March 22, 21 9:58 AM Page 32 of 5

33 Viking - Viking Community Health Services (B1178A) D4.4.1 Fans: Exhaust** - Variety of exhaust fans provided on roof or in ceiling space serving original building. Fans serve general exhaust system, kitchen exhaust, and laundry areas. Fans are centrifugal cabinet or roof mounted up-blast mashroom type fans. Replace Approx. 28 Exhaust Fans 213 $6, : D4.4.1 Fans: Exhaust** - Central Exhaust System is provided by heat recovery unit which is integral part of air handling units located in mechanical room. For replacement cost refer to section D Roof mounted exhaust fans serving fume hood and ambulance bay exhaust. Replace 3 Exhaust Fans 238 $12, : D4.4.3 Ducts: Exhaust* Galvanized exhaust ducts are located throughout the ceiling spaces as required from the washrooms, other special areas and general exhaust. Exhaust ducts in Wing gather into exhaust air plenums where heat is extracted with a heat recovery coil prior to exhaust to the outdoors. 5 D4.4.5 Air Outlets and Inlets: Exhaust* Metal exhaust grilles of various types and sizes are located throughout the ceiling areas of the facility. Newer grilles in addition and renovated areas. Report run on: March 22, 21 9:58 AM Page 33 of 5

34 Viking - Viking Community Health Services (B1178A) D4.5 Heat Exchangers** - Shell tube heat exchangers steam to glycol water in mechanical room serving air handling units heating coils and domestic hot water heaters. Replace 5 Heat Exchangers 213 $75, : D4.5 Heat Exchangers** - One plate heat exchanger serving addition located in penthouse mechanical room. HE-1 Armstrong, 15 2 F. D5.3 Humidifiers** - Steam grid humidifiers serving Air Handling Units. Individual duct mounted humidifiers serving Operating Room, Circulation Room, Major Treatment Room, Nursery and Special Care. 25 Replace 7 Humidifiers 213 $84, : D5.3 Humidifiers** - Dri Steam gas fired humidifer serving Section. 25 Replace Humidifer 233 $2, : Report run on: March 22, 21 9:58 AM Page 34 of 5

35 Viking - Viking Community Health Services (B1178A) D5.5.2 Fan Coil Units** - Recessed force flow heaters serving vestibules complete with hot water heating coils and control valves. Replace 7 FF Heaters 213 $28, : D5.5.2 Fan Coil Units** - Recessed force flow heaters serving vestibules complete with hot water heating coils and control valves. Replace 3 FF Heaters 238 $12, : D5.5.3 Finned Tube Radiation** Perimeter wall fin radiation complete with various type enclosure cabinets. 4 Replace Finned Tube Radiation B.O.E. $52/ sq.m. 221 $125, : Report run on: March 22, 21 9:58 AM Page 35 of 5

36 Viking - Viking Community Health Services (B1178A) D5.5.6 Unit Heaters** - Cabinet horizontal and vertical discharge, propeller, hot water unit heaters serving Mechanical Rooms and Maintenance areas. Replace 1 Unit Heaters 213 $4, : D5.5.6 Unit Heaters** - Cabinet horizontal and vertical discharge, propeller, hot water unit heaters serving Mechanical Room and Ambulance Bay. Replace 4 Unit Heaters 238 $16, : D5.5.8 Radiant Heating (Ceiling & Floor)** - Radiant ceiling panels serving Patients Rooms and common areas in new and renovated areas, 61mm width aluminum linear type, mounted in the T-bar, or GWB ceiling along the perimeter wall. 35 Replace Radiant Heating (Ceiling) 216 $125, : Report run on: March 22, 21 9:58 AM Page 36 of 5

37 D5.5.8 Radiant Heating (Ceiling & Floor)** - 29 Viking - Viking Community Health Services (B1178A) Radiant ceiling panels serving Patients Rooms and common areas in new and renovated areas, 61mm width aluminum linear type, mounted in the T-bar, or GWB ceiling along the perimeter wall Replace Radiant Heating (Ceiling) 24 $75, : D6.2.2 Pneumatic Controls** Duplex air compressors complete with refrigerated dryers. 4 Replace Pneumatic Controls 221 $125, : D6.2.5 Building Systems Controls (BMCS, EMCS)** Reliable Controls BMCS Replace Building Systems Controls (BMCS, EMCS) 224 $, : D41 Sprinklers: Fire Protection* The building is partially sprinkled. Automatic sprinkler system consists of wet and dry pipes. Fire department connection at the front entrance. 6 Report run on: March 22, 21 9:58 AM Page 37 of 5

38 Viking - Viking Community Health Services (B1178A) D42 Standpipes* Original building is provided with a wet standpipe system. A ULC rated fire pump is provided for the standpipe system. 6 D4.1 Fire Extinguisher, Cabinets and Accessories* Fire extinguishers provided throughout:- carbon dioxide, multi-purpose dry chemical. All units complete with up-to-date certification tags. D49.4 Dry Chemical Fire Extinguishing Systems (Kitchen Hood)** Range Guard kitchen fire suppression system. 4 Replace Dry Chemical Fire Extinguishing Systems (Kitchen Hood) 221 $25, : D49.7 Fire Pumps & Water Storage Tanks* One fire pump 32 l/s flow at m head. Sprinkler trees complete with jockey pumps. 4 Report run on: March 22, 21 9:58 AM Page 38 of 5

39 S5 ELECTRICAL Viking - Viking Community Health Services (B1178A) D51.2 Secondary Electrical Transformers (Interior)-** There are 2 6V-12/28V, stepdown transformers rated 225KVA and 112.5KVA. 4 Replacement 2 Secondary Electrical Transformers (Interior) 221 $32, : D51.2 Secondary Electrical Transformers (Interior)-** There are 4 6V-12/28V, stepdown transformers rated 45KVA, 75KVA, 15KVA and 225KVA. 4 Replace 4 Secondary Electrical Transformers (Interior) 248 $5, : D51.3 Main Electrical Switchboards (Main Distribution)** The distribution panelboard was 347/6V, 3 phase, 4 wire and rated 16A set at 12A; the distribution was equipped with 5KVAR power fact correction and TVSS. The main distribution was underground fed from site padmounted transformer 4 Replace Main Electrical Switchboards (Main Distribution) 248 $18, : Report run on: March 22, 21 9:58 AM Page 39 of 5

40 D51.5 Electrical Branch Circuit Panelboards (Secondary Distribution)-** Viking - Viking Community Health Services (B1178A) The branch panels were mixed with 12/28V and 347/6V. Some panels have isolated grounding for medical equipment. Most panels have 1% space for future uses. Replace 15 Electrical Branch Circuit Panelboards (Secondary Distribution) 213 $9, : D51.5 Electrical Branch Circuit Panelboards (Secondary Distribution)-** The branch panels were mixed with 12/28V and 347/6V. Some panels have isolated grounding for medical equipment. Most panels have 2% space for future uses. Replace 22 Electrical Branch Circuit Panelboards (Secondary Distribution) 238 $132, : D Switchboards, Panelboards, and (Motor) Control Centers-** Supplied by normal power, the MCC was used for mechanical pumps and ventilation equipment Replace Motor Control Centers 213 $, : Report run on: March 22, 21 9:58 AM Page 4 of 5

41 D Switchboards, Panelboards, and (Motor) Control Centers-** Viking - Viking Community Health Services (B1178A) Replace Motor Control Centers 238 $6, : D Motor Starters and Accessories** The load switches were used for some small mechanical loads. Replace 12 Motor Starters and Accessories 213 $7,2 : D Variable Frequency Drives** The VFD's were used for major ventilation equipment supply and return air fans 1999 Replace 2 Variable Frequency Drives 229 $24, : D52.1 Electrical Branch Wiring* Most wirings were installed with different sections of the original building. The wires were installed in the conduits for major runs from panel and junction boxes and Bix wires were used from junction boxes to power and lighting outlets. 5 Report run on: March 22, 21 9:58 AM Page 41 of 5

42 D Lighting Accessories (Lighting Controls)* Viking - Viking Community Health Services (B1178A) The line voltage switching was used in section of the building and low voltage control was used for section of building. D Interior Incandescent Fixtures* The incandescent fixtures were retrofit with self-ballast compact fluorescent lamps. D Interior Florescent Fixtures** The fixtures at section of the building were retrofit with T-8 fluorescent lamps and all the fixtures at section of the building are T-8 fluorescent lamps Replace Interior Florescent Fixtures 238 $711,932 : D Exit Signs* The Exit signs at section of the building were retrofit with LED type lamps; the Exit signs at section of building were all LED lamp type. D Operating Room Lighting* The Skytron type lights were used in operation rooms D Exterior H.P. Sodium Fixtures* The wall packs were installed around building perimeter and pole mounted lights in the parking lot. Report run on: March 22, 21 9:58 AM Page 42 of 5

43 D Lighting Accessories: Exterior (Lighting Controls)* The outdoor lighting was controlled by photocell Viking - Viking Community Health Services (B1178A) D5.1 Detection and Fire Alarm** The fully addressable Mircom FX-2 fire alarm panel was used for fire alarm system. The PDRP-11A panels were used to monitor the sprinkler systems and tied to main fire alarm system 25 Replace Detection and Fire Alarm 233 $27, : D5.2.3 Security Access** The Keyscan access control panel was used for Security Access system and have keypads located at all exterior access doors 25 Replace Security Access 233 $83, : D5.2.4 Video Surveillance** The PELCO was used for video surveillance system and 4 Cameras installed to monitor rear door, waiting room, Ambulance entrance and in side EM bay. 25 Replace Video Surveillance 233 $4, : Report run on: March 22, 21 9:58 AM Page 43 of 5

44 Viking - Viking Community Health Services (B1178A) D5.3 Clock and Program Systems* The Rauland -Borg Model 2515 was used for Clock and have digital clocks installed through facility hallways. 25 D5.4.1 Telephone Systems* The NEC Univerge NEAX 2IPS panel was used for telephone system and tied with nurse call system to perform facility paging functions. 25 D5.4.3 Nurse Call Systems** The Rauland Call-A-Nurse Responder systems were used for nurse call system 25 Replace Nurse Call Systems 233 $17, : D5.4.4 Data Systems* One server was installed for the facility and tied to Alberta Health Services through Supernet D5.4.5 Local Area Network Systems* Combine Cat 5e and Cat 6 wires were used for network system and has data outlets installed through entire offices and nurse stations Report run on: March 22, 21 9:58 AM Page 44 of 5

45 Viking - Viking Community Health Services (B1178A) D5.5 Public Address and Music Systems** The TOA 7 series AMP was used for PA system, the speakers and wiring were still installed with original building. 25 Replace Public Address and Music Systems 233 $42, : D5.6 Television Systems* The Star Choice Satellite TV was used for cable TV services and has TV outlets installed in all patient rooms and common areas 29 2 D5.7 Other Communications and Security Systems* The Supernet was used for data system connection to Alberta Health Services 25 D59.1 Uninterruptible Power Supply Systems** The stand alone UPS units were used for server computer and mechanical controls. 25 Replace Uninterruptible Power Supply Systems 235 $15, : Report run on: March 22, 21 9:58 AM Page 45 of 5

46 D59.2 Packaged Engine Generator Systems (Emergency Power System)** The outdoor 5KVA diesel generator was installed for emergency power system. Viking - Viking Community Health Services (B1178A) 35 Replace Packaged Engine Generator Systems 243 $4, : Report run on: March 22, 21 9:58 AM Page 46 of 5

47 Viking - Viking Community Health Services (B1178A) S6 EQUIPMENT, FURNISHINGS AND SPECIAL CONSTRUCTION E12.7 Laboratory Equipment* Fume hood located in laboratory of section. 25 E1.3 Loading Dock Equipment* Dock leveler located in loading dock area. 25 E19.3 Food Service Equipment* Commercial kitchen serving patient meal preparation and staff cafeteria consisting of: Soiled dishwasher c/w 2-compartment pot sink Dishwasher Hot water booster Clean dish table Vegetable preparation table Garbage disposal unit Exhaust hood with dry chemical fire protection system Single oven natural gas range Convection oven Steam cooker Deep fat fryer Baker's table Cook's table c/w sink Refrigerated display case 25 E19.4 Residential Equipment* Electric range and refrigerator located in Day Dining Room. Washer/dryer located in laundry area. 1 E19.7 Athletic, Recreational, and Therapeutic Equipment* 1 set stair climbing unit, 1 tread mill, 1 wall pulley unit and 1 set of parallel bars located in Rehabilitation area also containing wheel chairs and walkers. 15 Report run on: March 22, 21 9:58 AM Page 47 of 5

48 Viking - Viking Community Health Services (B1178A) E21.2 Fixed Casework** - Section Plastic laminated counter tops and cabinetry located in patient rooms, Day Dining area, treatment areas and administration spaces. Replacement $125/sq. M = $33, Replace Fixed Casework 216 $332,5 : E21.2 Fixed Casework** - Section Plastic laminated patient room vanities and counter in laundry room. 3 - Marginal 35 Replace 2 Counter Top Units Concern: Badly worn and chipped plastic laminated finish in patients room vanities and laundry room counter. Recommendation: Replace plastic laminated finish to effected areas. Consequences of Deferral: Further deterioration on finishes and possible injury to occupants. Failure Replacement 21 $2, Low : E21.2 Fixed Casework** - Section Plastic laminated counter tops and cabinetry located in treatment, laboratory and service areas. Replace $15/sq. M = $77,5. 35 Replace Fixed Casework 243 $77,5 : Report run on: March 22, 21 9:58 AM Page 48 of 5

49 Viking - Viking Community Health Services (B1178A) F12.2 Special Purpose Rooms - Section Rehabilitation area containing 4 beds and exercise area. 5 F22.1 Asbestos* - & Sections No asbestos observed or reported. F22.4 Mould* - & Sections No mould conditions observed or reported. F22.9 Other Hazardous Materials* - & Sections No other hazardous materials observed or reported. Report run on: March 22, 21 9:58 AM Page 49 of 5

50 S8 FUNCTIONAL ASSESSMENT Viking - Viking Community Health Services (B1178A) K41.1 Barrier Free Route: Parking to Entrance* - Section Hard surfaced level walkway. K41.2 Barrier Free Entrances* - Section Power operated swinging doors with sensor at main entry. K41.3 Barrier Free Interior Circulation* - & Sections Wide corridors with wall mounted handrails in public areas. K41.4 Barrier Free Washrooms* - & Sections Public washrooms BFA equipped and sized. Report run on: March 22, 21 9:58 AM Page 5 of 5

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Calgary School District #19 John G Diefenbaker High School B2686A Calgary Report run on: January 1, 28 9:31 AM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Calgary RCSSD #1 Ecole St. Matthew Elementary / French Immersion Jr. High School B2614A Calgary Report run on: March 25, 2010 10:11 AM Building Name: Address: Location:

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton RCSSD #7 Bishop Savaryn Catholic Elementary School B58A Edmonton Report run on: July 10, 2008 3:31 PM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Stratford Academic High School B3336A Edmonton Report run on: April 3, 29 1:6 AM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton RCSSD #7 Our Lady Of The Prairies Catholic Elementary School B3241A Edmonton Report run on: July 17, 2008 4:00 PM Building Name: Address: Location: Building Id:

More information

MUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY

MUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY ARCHITECTURE ROLLING HILLS ELEMENTARY SCHOOL Rolling Hills Elementary was built in 1999 and is the newest addition to the Mukwonago Area School District. The building contains approximately 64,900 gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Calgary School District #19 Queen Elizabeth Junior / Senior High School B2745A Calgary Report run on: March, 2010 10:02 AM Building Name: Address: Location: Building Id:

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Alberta Health Services-Central Breton Health Centre B999A Breton Report run on: March 7, 214 11:1 AM Building Name: Address: Location: Building Id: Gross Area (sq. m):

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Alberta Health Services-Edmonton Glenrose Energy Centre B25I Edmonton Report run on: February 15, 213 1:9 AM Building Name: Address: Location: Building Id: Gross Area

More information

DOCUMENT TABLE OF CONTENTS

DOCUMENT TABLE OF CONTENTS DOCUMENT 00003 June 16, 2005 TABLE OF CONTENTS DOCUMENT NO. INTRODUCTORY INFORMATION DOCUMENT 00003 TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS SECTION 01011 SECTION 01025 SSP21.1-1 SECTION 01026

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton RCSSD #7 Cardinal Leger Catholic Junior High School B371A Edmonton Report run on: April 3, 29 1:1 AM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Wild Rose School Div #66 Pioneer School B3972A Rocky Mountain House Report run on: March 26, 213 9:48 AM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton RCSSD #7 Bishop Savaryn Catholic Elementary School B358A Edmonton Report run on: March 11, 213 5:9 PM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton RCSSD #7 Sir John Thompson Catholic Junior High School B3275A Edmonton Report run on: March 5, 29 1:43 AM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Clara Tyner Elementary School B375A Edmonton Report run on: March 16, 212 2:11 PM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Alberta Health Services-Edmonton Capital Care - Norwood - North Pavilion B25A Edmonton Report run on: March 12, 214 12:41 PM Building Name: Address: Location: Building

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Harry Ainlay Composite High School B3145A Edmonton Report run on: March 2, 27 3:27 PM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Calgary School District #19 Sir William Van Horne High School B2852A Calgary Report run on: March 25, 2010 10:19 AM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Canadian Rockies Reg Div #12 Exshaw School B3390A Exshaw Report run on: March 26, 2010 9:29 AM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton RCSSD #7 Blessed Kateri School B36A Edmonton Report run on: April 3, 29 1:1 AM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Lakeland Roman Catholic Separate School District No. 1 Ecole Notre Dame High School B266A Bonnyville Report run on: January 26, 2 : PM Bonnyville - Ecole Notre Dame High

More information

AVS. Asset Assessment Report. Cold Lake Health Centre B1012A

AVS. Asset Assessment Report. Cold Lake Health Centre B1012A AVS Asset Assessment Report Cold Lake Health Centre B1012A Page 1 of 117 Asset ID Asset Name Location Address B1012A Cold Lake Health Centre Cold Lake 314-25 Street Verification Audit Maintenance Costs

More information

MUKWONAGO SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY

MUKWONAGO SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY MUKWONAGO SCHOOL DISTRICT ARCHITECTURE PARK VIEW MIDDLE SCHOOL The original school building was dedicated in 1954 as the High School, with an addition in 1959, a library addition in 1970, and an addition/renovation

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Coronation Elementary School B381A Edmonton Report run on: January 22, 27 11:33 AM Building Name: Address: Location: Building Id: Gross

More information

Existing Conditions Assessment November 14, 2006 NORTH MIDDLESEX REGIONAL HIGH SCHOOL Townsend, MA L21366/ /Page 1

Existing Conditions Assessment November 14, 2006 NORTH MIDDLESEX REGIONAL HIGH SCHOOL Townsend, MA L21366/ /Page 1 L21366/101 090 00.00/Page 1 HVAC EXECUTIVE SUMMARY The North Middlesex Regional High School has received average maintenance of the HVAC systems over its occupied years. Even with adequate maintenance,

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Alberta Health Services-Edmonton Strathcona County Health Centre B1421A Sherwood Park Report run on: March 18, 214 1:22 PM Building Name: Address: Location: Building Id:

More information

Residential Construction and Remodeling Estimates. compliments of. pillartopost.com

Residential Construction and Remodeling Estimates. compliments of. pillartopost.com Residential Construction and Remodeling Estimates compliments of STRUCTURE/EXTERIOR Structure > addition (foundation to roof) $95 $130/sq.ft. > basement entrance $5250 $10500 > basement main beam $2100

More information

Calmeca Academy of Fine Arts and Dual Language

Calmeca Academy of Fine Arts and Dual Language Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

2 Main Office Building BLDG-955A Building Purpose Building Area Administration offices. Training room 7,610 SF Inspection Date August 16, 2016 Inspect

2 Main Office Building BLDG-955A Building Purpose Building Area Administration offices. Training room 7,610 SF Inspection Date August 16, 2016 Inspect 1 Site Summary Address 7200 Bluff Springs Road Austin, TX 78744 Number of Permanent Campus Facilities 2 Original Year of Construction 2014 Total Campus Building Area (combined) 25,314 SF Introduction The

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

Mechanical Inspection Plumbing

Mechanical Inspection Plumbing 0811 Fixtures Sinks, drinking fountains, water closets, showers, etc. Classroom Sinks. Classroom sinks (19) are enameled cast iron self rimming side ledge with gooseneck faucet trim with index handles,

More information

Florence High School / Middle School Page 1 of 3 Florence, WI

Florence High School / Middle School Page 1 of 3 Florence, WI Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Evergreen Catholic Separate Regional Division #2 St. Mary School B4244A Westlock Report run on: January 22, 27 2:4 PM Building Name: Address: Location: Building Id: Gross

More information

Agustin Lara Elementary Academy

Agustin Lara Elementary Academy Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

VOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED

VOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED Ashton Elementary School 1 Masonry Repair $ 42,781.50 2 Replace HVAC $ 375,000.00 3 Replace SAT @ Various Locations $ 92,364.00 3 Recoat & Resurface Exterior Paved Play Area $ 135,978.30 3 Various Technological

More information

Dates of Construction Construction Start 2/28/1999 Date of Completion 4/2000 Occupancy 5/2000

Dates of Construction Construction Start 2/28/1999 Date of Completion 4/2000 Occupancy 5/2000 Executive Summary The Milton S. Hershey Medical Center Academic Support Building is located on The Pennsylvania State University's campus in Hershey, PA. The building is owned by The Pennsylvania State

More information

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building

Facility Condition Assessment Summary Report. British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Facility Condition Assessment Summary Report British Columbia Institute of Technology NE6 - Plumbing and Pipefit Building Submitted by: VFA Canada Corp. Burnaby Centre 4211 Kingsway Burnaby, BC V5H 1Z6

More information

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance Groton Heights School Mechanical Evaluation TO: FROM: Amy Vaillancourt, Project Manager Harley Langford, Project Manger Jason Curtis, P.E. DATE: February 24, 2016; Revised May 31, 2016 On Monday, December

More information

Estimated Repair, Replacement, and Upgrade Costs

Estimated Repair, Replacement, and Upgrade Costs Description Electrical Attic ventilator-mechanical $250 Baseboard heater (4') $150-$400 Ceiling fan $200 Doorbell system $80-$100 Dryer duct $100-$150 Hardwired smoke detector $60-$120 Exhaust Fan-Bathroom

More information

SPACE TYPE: JUDICIAL CHAMBER

SPACE TYPE: JUDICIAL CHAMBER SPACE TYPE: JUDICIAL CHAMBER Construction Criteria The unit costs for Judicial Chamber space types are based on the construction quality and design features in the following table. This information has

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report E Central Francophone Ed Reg# Ecole Du Sommet School B89A St. Paul Report run on: January 26, 2 :28 PM St. Paul - Ecole Du Sommet School (B89A) Facility Details Building

More information

DESIGNER KITCHEN WITH PREMIUM APPLIANCES 1407 & 1409 Military Trail Features & Finishes 1. Open concept kitchen with NEFF designer cabinetry and Caesa

DESIGNER KITCHEN WITH PREMIUM APPLIANCES 1407 & 1409 Military Trail Features & Finishes 1. Open concept kitchen with NEFF designer cabinetry and Caesa DESIGNER KITCHEN WITH PREMIUM APPLIANCES 1407 & 1409 Military Trail Features & Finishes 1. Open concept kitchen with NEFF designer cabinetry and Caesarstone countertop. 2. 4 x 16 ceramic tile backsplash.

More information

SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL)

SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL) SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL) Basketball Courts 15 25 Built Improvements Playgrounds, Site Furniture, etc. 20 20 Catch Basin 40 40 Cold Water Lines 40 40 Compactors DHW Supply

More information

Genevieve Melody Elementary School

Genevieve Melody Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

PLAN REVIEW SUBMITTAL GUIDE

PLAN REVIEW SUBMITTAL GUIDE PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Parkland School Division #7 Duffield School B938A Duffield Report run on: May 11, 26 4:38 PM Duffield - Duffield School (B938A) Facility Details Building Name: Duffield

More information

Edward Jenner Elementary Academy of the Arts

Edward Jenner Elementary Academy of the Arts Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Josefa Ortiz De Dominguez Elementary School

Josefa Ortiz De Dominguez Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Parkland School Division #7 Meridian Heights School B9397A Stony Plain Report run on: January 22, 27 2:45 PM Building Name: Address: Location: Building Id: Gross Area

More information

Oscar DePriest Elementary School

Oscar DePriest Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Axiom Property Inspections

Axiom Property Inspections Cover Page Axiom Property Inspections Property Inspection Report 868 Wally Avenue, Henderson NV, 89178 Inspection prepared for: John Doe Agent: David Lawson - Axiom Inspection Date: 8/12/2010 Time: 2:30

More information

REPAIR ESTIMATE GUIDE

REPAIR ESTIMATE GUIDE REPAIR ESTIMATE GUIDE STRUCTURE Foundation Addition (foundation to roof)... $125 - $170/sq.ft. Basement entrance... $6485 - $13690 Basement main beam... $2740 Basement support post/foundation... $650 -

More information

PLATTEVILLE MIDDLE SCHOOL

PLATTEVILLE MIDDLE SCHOOL Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle

More information

Richard Henry Lee Elementary School

Richard Henry Lee Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Francis M McKay Elementary School

Francis M McKay Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#58619/Page 1/November 1, 2017 PLUMBING Executive Summary: Presently, the Plumbing Systems serving the building are cold water, hot water, sanitary, waste and vent system, storm drain piping, and natural

More information

Cook - Wissahickon Elementary School

Cook - Wissahickon Elementary School Cook - Wissahickon Elementary School 201 E. Salaignac St., Philadelphia, PA 19128 HVAC Replacement Project Scope Determination Report May 10, 2018 Prepared by: G.P. Lamina, Jr., P.E., MBA School District

More information

Washington Irving Elementary School

Washington Irving Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Joseph Brennemann Elementary School

Joseph Brennemann Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Inspecta-Homes 2469 University Avenue West St. Paul MN Ph#: (651)

Inspecta-Homes 2469 University Avenue West St. Paul MN Ph#: (651) Page 1 Doc #: Inspector: Date: Dwelling Address: Client Name: Client's Agent: Real Estate Company: Please refer to the General Home Inspection Contract. Thank you for using Minnesota and Western Wisconsin's

More information

SCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE

SCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE SCHEDULE OF S Penalty Fees. The fee for construction work performed before securing permit(s), where required, may be charged a fee of TWO TIMES THE COST OF THE PERMIT (S). Building Fee Schedule Residential

More information

Safe at Home. Suggestions for Homeowner Created in partnership with the Administration on Aging. Assessor: Assessor: Homeowner Name: Address:

Safe at Home. Suggestions for Homeowner Created in partnership with the Administration on Aging. Assessor: Assessor: Homeowner Name: Address: Assessor: Assessor: 1. EXTERIOR ENTRANCES AND EXITS Do you any difficulty getting in and out of your home? Which entrance(s) do you use the most? Have you had any falls or safety concerns? I want you to

More information

QUALITY FEATURES Trent 24 7 & ascot semi-detached

QUALITY FEATURES Trent 24 7 & ascot semi-detached QUALITY FEATURES Trent 24 7 & ascot 27 10 semi-detached and elevations, loose precast concrete steps will be used when grading requires less than three (3) steps. windows with pre-finished white or coloured

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Prairie Land Regional Div #25 Berry Creek Community School B2933A Cessford Report run on: March 21, 213 9:46 AM Building Name: Address: Location: Building Id: Gross Area

More information

Charles W Earle Elementary School

Charles W Earle Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Design Standards Manual

Design Standards Manual Design Standards Manual Table of Contents: Part III (Divisions 1-32) Section No. Title Revision DIVISION 1: GENERAL REQUIREMENTS 01524 Construction Waste Management 05/07 01815 HVAC Commissioning Requirements

More information

Canadian Property Inspections

Canadian Property Inspections Cover Page Canadian Property Inspections Home Inspection Report L9Z-1K4 Inspection prepared for: K.C. Pitman Date of Inspection: 3/6/2017 Time: 3pm Age of Home: 42 Size: 500-1000 Weather: Cloudy, cool.

More information

TABLE OF CONTENTS. Part I Administrative... 1

TABLE OF CONTENTS. Part I Administrative... 1 Part I Administrative............................ 1 CHAPTER 1 ADMINISTRATION............... 1 R101 Title, Scope and Purpose.................... 1 R102 Applicability.............................. 1 R103

More information

SPACE TYPE: CHILD CARE

SPACE TYPE: CHILD CARE SPACE TYPE: CHILD CARE Construction Criteria The unit costs for Child Care Center space types are based on the construction quality and design features in the following table. This information has been

More information

AFFORDABLE CANADIAN HOME INSPECTIONS

AFFORDABLE CANADIAN HOME INSPECTIONS AFFORDABLE CANADIAN HOME INSPECTIONS Al Wright Hamilton, Ontario Cell: 905-730-9300 Expectancy of Household Components Appliances Compactors 7-12 Dishwashers 9-16 Disposal, Food Waste 11-16 Dryers 11-16

More information

Extra Mile Inspection, Inc.

Extra Mile Inspection, Inc. Cover Page Property Inspection Report Inspection prepared for: Jerry and Lynne Richardson Real Estate Agent: Polly Richardson - BHKR Lake Forest Date of Inspection: 3/13/2017 Time: 12 pm Age of Home: built

More information

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School North Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

DESIGN STANDARDS SECTION PLUMBING FIXTURES AND EQUIPMENT. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.

DESIGN STANDARDS SECTION PLUMBING FIXTURES AND EQUIPMENT. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type. PART 1 - GENERAL 1.1 Toilet rooms and utility rooms to have floor drains at lowest point. 1.2 Utilize Exposed Flushometers. 1.3 Wall hung toilet room fixtures. Urinals for handicapped may be stall type.

More information

room data sheet CORDOVA RESIDENCE 1/11 54 EAST CORDOVA STREET, VANCOUVER, BC RESIDENTIAL ROOM RM DIVISION ELEMENT REQUIREMENT

room data sheet CORDOVA RESIDENCE 1/11 54 EAST CORDOVA STREET, VANCOUVER, BC RESIDENTIAL ROOM RM DIVISION ELEMENT REQUIREMENT RESIDENTIAL ROOM Window Provide an operable window New pressed metal door, 20 min. FPR, in new metal buck or existing wood frame, made good Proximity access control technology door hardware, closer in

More information

DeWitt Clinton Elementary School

DeWitt Clinton Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District HOLUM EDUCATION CENTER Architectural The existing building has approximately 41,823 square feet and sets on a lot about 4.14 acres in size. Parking lots are located along the east and west sides of the

More information

Landscape Includes sprinkler system Irrigation, system maintenance, and landscape upkeep are all included in H.O.A. dues

Landscape Includes sprinkler system Irrigation, system maintenance, and landscape upkeep are all included in H.O.A. dues Current as of 7/24/17 Construction & Design Specifications for: 3803 Echo Farms Blvd Priced as described below: $236,500 Exterior Raised slab foundation o pretreated for termites -- termite bond maintained

More information

Examples of Acclaim s Energy-Efficiency Green Technology

Examples of Acclaim s Energy-Efficiency Green Technology Examples of Acclaim s Energy-Efficiency Green Technology This packet shows examples of some of the energy-efficiency materials that we provide as standard in our homes at Creekmoor. At the end of the packet,

More information

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN September 30, 2015 PBA Project No. 2015.0140.00 PETER BASSO ASSOCIATES INC. CONSULTING ENGINEERS 5145 LIVERNOIS ROAD,

More information

Aging-In-Place Remodeling Checklist

Aging-In-Place Remodeling Checklist 5867 West Hidden Springs Dr. Hidden Springs, Idaho 83714-9405 (208) 229-2553 Fax (208) 229-2554 Idaho Registration No. RCE-91 www.chuckmillerconstruction.com Aging-In-Place Remodeling Checklist Have you

More information

Asurity 1. Property Inspection Report S Gurd Rd., Hastings, MI Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski -

Asurity 1. Property Inspection Report S Gurd Rd., Hastings, MI Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski - Cover Page Property Inspection Report Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski - Date of Inspection: 3/28/2017 Time: 2:00 Age of Home: Built 1999 Size: 2015 Weather: 50 Overcast.

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Graminia School B451A Spruce Grove Report run on: January 3, 26 1:36 PM Facility Details Building Name: Graminia School Address: 5111 R. R. 271 Location: Spruce Grove

More information

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information Charles M. LeMaistre PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and

More information

The Villas of Wyldewood

The Villas of Wyldewood The Chalet 1442 Sq. Ft. 2 Bedrooms 2 Full Baths 2 Car Garage 1st Floor Laundry Stain Resistant Carpet Gas Fireplace Central Air Easy Access - No Steps Private Deck Lake & Walking Trail All Dimensions,

More information

George B Swift Elementary Specialty School

George B Swift Elementary Specialty School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Sidney Sawyer Elementary School

Sidney Sawyer Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

MOLSON S BANK BUILDING 166 EAST HASTINGS STREET, VANCOUVER, BC

MOLSON S BANK BUILDING 166 EAST HASTINGS STREET, VANCOUVER, BC RESIDENTIAL ROOM Window Provide an operable window New pressed metal door, 20 min. FPR, in new metal buck or existing wood frame, made good Proximity access control technology door hardware, closer in

More information

Plot # R019A ± 74' ± 74' ± 65' Plot # R019A LEASE OUTLINE DRAWING GROSS LEASABLE AREA ± 4,631 S.F. DEMISING FRONT WIDTH DEPTH ± 13' ± 32' Lease Line

Plot # R019A ± 74' ± 74' ± 65' Plot # R019A LEASE OUTLINE DRAWING GROSS LEASABLE AREA ± 4,631 S.F. DEMISING FRONT WIDTH DEPTH ± 13' ± 32' Lease Line ± 4' ± 13' ± 72' Lease Line ± 6' ± 7' Plot # R019A ± 18' Lease Line Site N o : Site N ame: Lo catio n: Submitted B y: D rawn by D ate: 991 Santee Trolley Square Santee, CA ID Plans 11/10/2016 This drawing

More information

THERE IS NOTHING STANDARD ABOUT OUR FIXTURES AND FINISHES.

THERE IS NOTHING STANDARD ABOUT OUR FIXTURES AND FINISHES. Duplex Specifications 2019 THERE IS NOTHING STANDARD ABOUT OUR FIXTURES AND FINISHES. Fall in love with your new home! 3 YOUR HOME HAS A SOLID FOUNDATION TO STAND ON FOUNDATION, STRUCTURE & EXTERIOR Damp

More information

AGING IN PLACE CHECKLIST Use this checklist to identify fall hazards and accessibility for the homeowner and family members.

AGING IN PLACE CHECKLIST Use this checklist to identify fall hazards and accessibility for the homeowner and family members. AGING IN PLACE CHECKLIST Use this checklist to identify fall hazards and accessibility for the homeowner and family members. EXTERIOR ENTRANCES AND EXITS: Note condition of walk and drive surface; existence

More information

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE 1. BUILDING FEES: 1 AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE ESTABLISHMENT OF FEES PURSUANT TO N.J.A.C.

More information

CMHC HOME MAINTENANCE CHECKLIST

CMHC HOME MAINTENANCE CHECKLIST Make sure air vents indoors and outdoors (intake, exhaust and forced air) are not blocked by snow or debris. Check and clean range hood filters on a monthly basis. Test ground fault circuit interrupter(s)

More information

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on HOME PROPERTY SCAN INSPECTIONS The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on January 11, 2010 and

More information

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS City of Redwood City Community Development Department Building and Inspection Department 1017 Middlefield Road Redwood City, CA 94063 Phone (650) 780-7350 2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY

More information

Alessandro Volta Elementary School

Alessandro Volta Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Unit # 1038 ± 900 SF Width ± 15' Depth ± 60'

Unit # 1038 ± 900 SF Width ± 15' Depth ± 60' ±60' Lease Line Lease Outline Drawing Needles Towne Center 1004 E. Broadway St.,, Needles, CA 92363 ± 900 SF Width ± 15' Depth ± 60' Plans produced by: ID Plans 6/16/2017 (813) 657-2545 C 2017 Site map

More information

Replacement Cost Questionnaire

Replacement Cost Questionnaire Replacement Cost Questionnaire 1. Please provide some general information about yourself: A) Name and address of insured location (as it appears on your Homeowners policy): Name: Street Address: City:

More information

Campbell County Memorial Hospital Radiology Renovation Addition Gillette, Wyoming

Campbell County Memorial Hospital Radiology Renovation Addition Gillette, Wyoming Campbell County Memorial Hospital Radiology Renovation Addition Schematic Design Systems Narrative April 19, 2013 CTA, Inc. 204-1/2 South Gillette Ave. 82716 (307) 686-7121 CIVIL - SITE Geotechnical The

More information

Springpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp.

Springpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp. Volume 1 Bidding Requirements, Contract Forms, Conditions of the Contract, Division 1, Architectural and Site Specifications 000107 Certification Page 000110 Table of Contents DIV00 PROCUREMENT AND CONTRACTING

More information

Jeff Brown Inspections

Jeff Brown Inspections Cover Page Jeff Brown Inspections Property Inspection Report Vegas NV, 89145 Inspection prepared for: Jim Shen Agent: Lauren Paris - Resolution Realty Inspection Date: 6/13/2013 Time: 10:00 Age: 26 years

More information