DOCUMENT T CAWTHRA SHELTER RENOVATIONS, 2500 CAWTHRA ROAD, CITY OF MISSISSAUGA, PROJECT E ADDENDUM 2

Size: px
Start display at page:

Download "DOCUMENT T CAWTHRA SHELTER RENOVATIONS, 2500 CAWTHRA ROAD, CITY OF MISSISSAUGA, PROJECT E ADDENDUM 2"

Transcription

1 Thursday, March 29, 2018 DOCUMENT T CAWTHRA HELTER RENOVATION, 2500 CAWTHRA ROAD, CITY OF MIIAUGA, PROJECT E ADDENDUM 2 Number of Pages: 6 Referring to the above Document T, the following are changes and responses to the questions raised: 1. Question: Where is panel P being fed from? Panel P is being fed from the existing electrical panel locates at 2nd floor electrical room Question: Are all exits and emergency remote heads new or existing? All are new, please refer to attached Appendix 6.3, revised Drawing E101 Power Layout Ground Floor. Please note all emergency lights and exit signs to be connected to the existing emergency panel. Emergency lights are fed from the generator. 3. Question: Who is the current fire alarm vendor for the building? The current fire alarm vendor is Regal Fire Protection. 4. Question: As per the addendum #1, there is no base building Fire Alarm Contractor. If we have to include the Fire Alarm scope of work in our bid, we need the information on the existing Fire Alarm ystem (make & model). Current fire alarm system is Mircom eries FA1000. ee attached Picture 1.

2 DOCUMENT T CAWTHRA HELTER RENOVATION, 2500 CAWTHRA ROAD, CITY OF MIIAUGA, PROJECT E ADDENDUM 2 5. Question: As per drawing, we have to provide a New Electrical Panel. The panel schedule is provided but no single line diagram is provided. Please see attached ingle line diagram is attached, Appendix revised Drawing E301 New Panel P chedule. 6. Question: As per Addendum-1, Ques/Ans#5, there is NO base building contractor for the project under reference. But, According to E301, General Note-12, there is a base building fire alarm contractor for fire alarm work. Please clarify this, otherwise, please provide contact information of fire alarm base building sub if there is any. Please clarify fire alarm work is the part of our scope of work or NOT? If yes, please provide detail information about fire alarm work. Fire alarm work is part of the cope of Work. Please refer to question 3 and question 4 of this addendum. 7. Question: According to E301, new electrical panel is to be provided. But, there is NO single line diagram on any of electrical drawings. Please provide this. Please refer to question 5 of this addendum. 8. Question: We would like to submit alternate Automatic Door Operator supplier: Rhino Teck Entrance olution, Product- Rhino ADO Would you please advise us, how can we submit the specification & architectural detail of Rhino ADO 7000? Please refer to ection Product Requirements, 1.2 Product ubstitution Procedures. 9. Revise the Light Fixture pecifications (Legend): Proposed lights have been discontinued, please see attached Appendix 6.3 revised drawing E201 Lighting Layout Ground Floor with updated light schedule. 2

3 DOCUMENT T CAWTHRA HELTER RENOVATION, 2500 CAWTHRA ROAD, CITY OF MIIAUGA, PROJECT E ADDENDUM 2 harmila achdeva Purchasing Analyst Fax: The Addendum number and date must be included in the Form of Tender in order for your bid to be given consideration. Picture 1 3

4 CCCEI CANADIAN CONTRUCTION & CONULTANT ENGINEER INC. UNIT #205, TH AVE., MARKHAM, ON L3R 0A9, Canada E101

5 (EXITING TO 130 OFFICE 128 ERVERY 115 DINNING 114 ACTIVITY 113 LAUNDRY (EXITING TO (EXITING TO ELEC. (EXITING 109 TO 107 JANITOR (EXIT. TO UNIVERAL B/F TEL. WAH (EXITING 104 TO 111 MALE 105 WAH 105 CORRIDOR 112 TAIR NEW WAH WAH (EXITING TO 130 BARRIER FREE UNIT (EXITING TO 129 FIRE EXIT 118 TAFF B/F WAH 120 OFFICE 119 OFFICE INTER. RM 122 RECEPTION 106 REOURCE CENTER 102 CCCEI CANADIAN CONTRUCTION & CONULTANT ENGINEER INC. UNIT #205, TH AVE., MARKHAM, ON L3R 0A9, Canada VETIBULE 101 Philips LED strip TRUGROOVE TANDALONE Definition LED Philips Day-Brite / Philips CFI Recessed FluxGrid LED 2FGG45L850-2-D-120-DIM Philips Day-Brite / Philips CFI Recessed FluxGrid LED 2FGG43L850-4-D-120-DIM E201

6

UNDERGROUND FEEDER 120/240V - 1C + G EXISTING STORAGE BARN CONCRETE SLAB AT DOORWAY SLOPE AWAY FROM NEW FOUNDATION REMOVE

UNDERGROUND FEEDER 120/240V - 1C + G EXISTING STORAGE BARN CONCRETE SLAB AT DOORWAY SLOPE AWAY FROM NEW FOUNDATION REMOVE ¾ ¾ ¾ E00 EXITING OFFICE BUNGALOW 6.30 REMOVE FROM NEW FOUNDATION 00mmØ UBDRAIN CONCRETE LAB AT DOORWAY 2.00 00mmØ UBDRAIN GRANULAR APRON 8m - 50mmØ CP EXITING GRAVEL ENTRANCE EXITING TORAGE BARN 25kVA

More information

NOTICE TO ALL FIRMS. Bid RFI Questions and Answers

NOTICE TO ALL FIRMS. Bid RFI Questions and Answers Purchasing Department 227 West 27 th Street New York, NY 10001 Purchasing Dept. Tel. 212-217-3630 Purchasing Dept. Fax 212-217-3631 Purchasing@fitnyc.edu NOTICE TO ALL FIRMS Date: March 8, 2018 To: From:

More information

Arlington Public Schools Purchasing Office

Arlington Public Schools Purchasing Office Arlington Public Schools Purchasing Office NOTICE OF ADDENDUM NO. 1 Issued on March 30, 2018 TITLE: ITB NO.: YORKTOWN HIGH SCHOOL INTERIOR MODIFICATIONS PROJECT 57FY18 ITB CLOSING DATE PRIOR TO 2:00 P.

More information

ADDENDUM No. 1. OPSB Central Office Relocation & Renovation

ADDENDUM No. 1. OPSB Central Office Relocation & Renovation Addendum No. ADDENDUM No. Date August 7, 208 Project: OPB Central Office Relocation & Renovation NOTICE TO CONTRACTOR GENERAL: The following does hereby become a part of the Contract Documents and all

More information

22A Belvedere Avenue, Parry Sound Sprinkler System Consulting Review

22A Belvedere Avenue, Parry Sound Sprinkler System Consulting Review Parry Sound District Social Services Administration Board Housing and Community Services October 10, 2018 c/o Andrew Ball, Properties and Capital Projects Coordinator Email:aball@psdssab.org 22A Belvedere

More information

Savings, control, and comfort without complexity

Savings, control, and comfort without complexity Controls Indoor SpaceWise DT Savings, control, and comfort without complexity Philips SpaceWise wireless technology DT, featuring dwell time functionality, is a flexible intuitive controls solution for

More information

Pinky Lewis Recreation Centre Interior Renovations in the City of Hamilton

Pinky Lewis Recreation Centre Interior Renovations in the City of Hamilton Mathew Brown Procurement Specialist City of Hamilton Corporate Services Department Procurement Section Phone: (905) 546-2424, ext.: 3669 Fax: (905) 546-2327 E-Mail: Mathew.brown@hamilton.ca Date Issued:

More information

Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc.

Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc. Memphis Housing Authority High Rise Fire Alarm Upgrades Questions from Contractors (Through Addendum #2) Communications Systems, Inc.: Legend 1. DL - Dome light symbol should be on the tenant emergency

More information

b. For Clarification: Added Dimming Zone number next to each fixture in Computer Classroom 102.

b. For Clarification: Added Dimming Zone number next to each fixture in Computer Classroom 102. UNC New East Building D Compliant Elevator DDENDUM NO. CO ID# 6-6-0 Code: 6 Item: Chapel Hill, North Carolina December, 08 Page HUFFMN RCHITECT, P 6 PERHING ROD RLEIGH, NORTH CROLIN 7608 PHONE (99) 70-669

More information

Addendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017

Addendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017 Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD 21801 Ph. 410-548-4805 Fax 410-334-3130 Email: purchasing@wicomicocounty.org Addendum # 2 Wicomico County Circuit Court Second Floor

More information

DONALD H. BERG, ARCHITECT

DONALD H. BERG, ARCHITECT DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:

More information

INVITATION TO QUOTE. Page 1 of 7. Fire & Emergency Safety Plan Control Number: 2018-CFS-003 Issue Date: March 7, Purpose

INVITATION TO QUOTE. Page 1 of 7. Fire & Emergency Safety Plan Control Number: 2018-CFS-003 Issue Date: March 7, Purpose INVITATION TO QUOTE Title: Fire & Emergency Safety Plan Control Number: 2018-CFS-003 Issue Date: March 7, 2018 Purpose The District of Sparwood (Sparwood) invites interested parties (Respondents) to submit

More information

VERIFICATION OF FIRE ALARM SYSTEMS

VERIFICATION OF FIRE ALARM SYSTEMS DEVELOPMENT, BUILDINGS AND LICENSING Chief Building Official (CBO) and Building Code and Policy Building Policy Branch The intent of this bulletin is to clarify requirements of verification of the fire

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#57297 /Page 1/July 21, 2017 ELECTRICAL SYSTEMS NARRATIVE REPORT The following is the Electrical Systems narrative, which defines the scope of work and capacities of the Power and Lighting systems, as

More information

ELECTRICAL SYMBOLS AND ABBREVIATIONS NOT ALL SYMBOLS, DEVICES OR ABBREVIATIONS MAY BE USED

ELECTRICAL SYMBOLS AND ABBREVIATIONS NOT ALL SYMBOLS, DEVICES OR ABBREVIATIONS MAY BE USED SYMBOLS AND ABBREVIATIONS ABBREVIATIONS GENERAL NOTES LINE TYPE LEGEND CIRCUITS TELECOMMUNICATION SYSTEM ING EQUIPMENT POWER DEVICES FIRE ALARM SYSTEM NOT ALL SYMBOLS, DEVICES OR ABBREVIATIONS MAY BE USED

More information

RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan

RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan ADDENDUM NO. 2 RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan TO: All Bidders Gentlemen: You are hereby directed to make the following changes in the Project Manual and/or

More information

JLLP DESIGN AND CONSULTING

JLLP DESIGN AND CONSULTING LOCATIONS: OPEN CEILING. DESCRIPTION: CEILING PENDANT MOUNT AJUSTABLE LENSED 6" ROUND DOWNLIGHT. PURPOSE: GENERAL ILLUMINATION. LAMP: PAR38 LED PHILIPS LAMP 19PAR38/F35 3000 DIM. WATT: 19 WATTS. TRANS./DRIVER:

More information

Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus

Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus ADDENDUM FORM INVITATION TO TENDER: 2016-067 ADDENDUM NO: 1 DATE ISSUED: June 23, 2016 ISSUED BY: Monty Thibeault DESCRIPTION: Replacement of Fire Pump and Generator Upgrade, H Building, Sexton Campus

More information

Electronic Safety and Security

Electronic Safety and Security 28 Electronic Safety and Security NOTE: This is a new section, which includes content from previous sections of the KU Design Standards, along with appropriate revisions and updates. Significant revisions

More information

COUNTY OF ROCKLAND Department of General Services Purchasing Division

COUNTY OF ROCKLAND Department of General Services Purchasing Division Department of General Services Purchasing Division Title: Contract Period: Laundry Products-Liquid Laundry Products, Automatically Dispensed with Dispensing Equipment March 1, 2013 through February 28,

More information

ADDENDUM #1: MODIFICATIONS AND ADDITIONS TO CONTRACT DOCUMENTS

ADDENDUM #1: MODIFICATIONS AND ADDITIONS TO CONTRACT DOCUMENTS Annex Laundry and Shower Alterations ADDENDUM #1 March 7, 2019 ADDENDUM #1: MODIFICATIONS AND ADDITIONS TO CONTRACT DOCUMENTS A. Invitation to Bid - Call for Bids has been modified as follows: 1. Notice

More information

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means

More information

Philips Lighting North America Corporation 200 Franklin Square Drive Somerset, NJ Tel

Philips Lighting North America Corporation 200 Franklin Square Drive Somerset, NJ Tel 2015 Koninklijke Philips N.V. All rights reserved. Philips reserves the right to make changes in specifications and/or to discontinue any product at any time without notice or obligation and will not be

More information

Cherokee Nation

Cherokee Nation Cherokee Nation www.cherokee.org REQUEST FOR BIDS CUBICLES & FURNITURE ADDENDUM 01 Bid Due Date: August 08, 2016 CHEROKEE NATION P.O. Box 948 Tahlequah, OK 74465 (918) 453-5000 1 CHEROKEE NATION BID REQUEST

More information

Fire Department Of New York

Fire Department Of New York Fire Department Of New York Joseph Barracato Director Construction, Demolition & Abatement Unit (CDA Unit) Bureau of Fire Prevention,FDNY Joseph Barracato, Director Fire Department, City of New York Construction,

More information

PROJECT NO. CWA SEPTEMBER 24, 2014 ADDENDUM NO. 6 BESSEMER RECREATION & WELLNESS CENTER

PROJECT NO. CWA SEPTEMBER 24, 2014 ADDENDUM NO. 6 BESSEMER RECREATION & WELLNESS CENTER PROJECT NO. CWA 2013-04 SEPTEMBER 24, 2014 ADDENDUM NO. 6 BESSEMER RECREATION & WELLNESS CENTER BIDS RECEIVED: CITY HALL, CITY OF BESSEMER TIME: 2:00pm DATE: October 2, 2014 City of Bessemer --------------------------------------------------------------------------------------------------------------------------------------------

More information

Wayne State University

Wayne State University 5557 Cass Ave WSU Project #048-251652 Issued For Bids February 24, 2015 FTC&H Project Number Fishbeck, Thompson, Carr & Huber, Inc. Engineers Scientists Architects Constructors 39500 MacKenzie Drive, Suite

More information

SPECIFICATIONS FOR TENDER # SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH

SPECIFICATIONS FOR TENDER # SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH SPECIFICATIONS FOR TENDER #0371-0739 SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH CLOSING DATE: 8 June 2007 CLOSING TIME: 11:00 AM (Newfoundland Time) Invitation to Tender for a

More information

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 27 05 05 Communication Rooms Design Guidelines 2.13 1.2 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations Electrical

More information

BOMA Calgary Luncheon Thursday, October 11, 2012 Building Owners Responsibilities for Fire Safety Equipment (Fire Alarm) Canadian Fire Alarm

BOMA Calgary Luncheon Thursday, October 11, 2012 Building Owners Responsibilities for Fire Safety Equipment (Fire Alarm) Canadian Fire Alarm 1 BOMA Calgary Luncheon Thursday, October 11, 2012 Building Owners Responsibilities for Fire Safety Equipment (Fire Alarm) Canadian Fire Alarm Association 2 Presentation Overview The Codes Your responsibilities

More information

HPNLS-LO. Installation Manual

HPNLS-LO. Installation Manual Installation Manual WARNING: DO NOT LIFT FIXTURE BY CABLES. Do not attempt to install or use the fixture without reading the installation instructions and safety labels completely. This could result in

More information

Main Lobby Area (North Vestibule thru South Vestibule):

Main Lobby Area (North Vestibule thru South Vestibule): Main Lobby Area (North Vestibule thru South Vestibule): Overview of Space: This is the entrance level from both the North, city street entrance, and the South, campus entrance. The space is 190 x 30 x

More information

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR 5/9/18 Procurement Towson University 8000 York Road Towson, MD 21252-0001 t. 410 704-2171 f. 410 704-8233 Ladies and Gentlemen:

More information

FIRE SAFETY STRATEGY REPORT ADIDAS MUSEUM FITOUT NATHAN AUSTRALIS CUSTOMS STREET AUCKLAND CITY. For COOPER AND COMPANY. 9 May 2011 Version A.

FIRE SAFETY STRATEGY REPORT ADIDAS MUSEUM FITOUT NATHAN AUSTRALIS CUSTOMS STREET AUCKLAND CITY. For COOPER AND COMPANY. 9 May 2011 Version A. FIRE AFETY TRATEGY REPORT Auckland Telephone +6 9 08 700 ADIDA MUEUM FITOUT Holmes Fire & afety Ltd Level NATHAN AUTRALI CUTOM TREET AUCKLAND CITY For 9 Market Place Viaduct Harbour PO Box 9075 Victoria

More information

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

IMPERIAL COLLEGE LIGHTING REVISION 1 REV. COMMENTS REVISED BY DATE CHECKED APPROVED

IMPERIAL COLLEGE LIGHTING REVISION 1 REV. COMMENTS REVISED BY DATE CHECKED APPROVED IMPERIAL COLLEGE LIGHTING REVISION 1 LIGHTING Revision Log REV. COMMENTS REVISED BY DATE CHECKED APPROVED 1 First Issue NDY 18.03.05 Notes 1 Amendments to this specification are struck out and new added

More information

SANTA FE COUNTY IFB# PW/KE CONSTRUCTION FOR THE SANTA FE MOUNTAIN CENTER KITCHENETTE AND OFFICE SPACE ADDENDUM #2

SANTA FE COUNTY IFB# PW/KE CONSTRUCTION FOR THE SANTA FE MOUNTAIN CENTER KITCHENETTE AND OFFICE SPACE ADDENDUM #2 Henry P. Roybal Commissioner, District 1 Anna Hansen Commissioner, District 2 Robert A. Anaya Commissioner, District 3 2017-0262-PW/KE Anna T. Hamilton Commissioner, District 4 Ed Moreno Commissioner,

More information

CHATHAM AREA TRANSIT AUTHORITY IFB , ADDENDUM NO.2

CHATHAM AREA TRANSIT AUTHORITY IFB , ADDENDUM NO.2 CHATHAM AREA TRANSIT AUTHORITY IFB 2012-04, ADDENDUM NO.2 DATE: January 24, 2012 ORIGINAL IFB NUMBER: 2012-04 PROJECT: REHABILITATION AND CONSTRUCTION OF THE CHATHAM AREA TRANSIT AUTHORITY OPERATIONS AND

More information

CITY OF FARMINGTON 800 Municipal Drive Farmington, NM (505) Fax (505)

CITY OF FARMINGTON 800 Municipal Drive Farmington, NM (505) Fax (505) CITY OF FARMINGTON 800 Municipal Drive Farmington, NM 87401-2663 (505) 599-1373 Fax (505) 599-1377 http://www.fmtn.org IMMEDIATE ATTENTION Construction Services for Municipal Operations Center Expansion

More information

BULLETIN. Temperature Controls (Chilled / Hot Water)

BULLETIN. Temperature Controls (Chilled / Hot Water) BULLETIN Temperature Controls (Chilled / Hot Water) (05-07-2013) This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. Tenant Responsibility:

More information

Recessed. DuaLED 2x , 2700, 3000, 3400, 3800, or 4400lm

Recessed. DuaLED 2x , 2700, 3000, 3400, 3800, or 4400lm Recessed Dua 2x2 Project: Location: Cat.No: Type: Lamps: Notes: Qty: 2100, 2700, 3000, 3400, 3800, or 4400lm Philips Day-Brite / Philips CFI Dua recessed is a highly efficient, visually comfortable, architecturally

More information

Oakdale Primary School Expansion Project Appendix C Elec Equipment Schedule

Oakdale Primary School Expansion Project Appendix C Elec Equipment Schedule Oakdale Primary School Expansion Project Appendix C Elec Equipment Schedule HBS-SH-MEP-803 May 2017 For Peterborough City Council ver. author date checked comment P1 DH 19-05-17 TJC TENDER ISSUE 1 Ref

More information

5383 Cambie Street AL-2 FF Path of Travel Width April 26, 2017 Project Address Title/Descriptor Initial Submission Date

5383 Cambie Street AL-2 FF Path of Travel Width April 26, 2017 Project Address Title/Descriptor Initial Submission Date AL-1 PLANNING AND DEVELOPMENT ERVICE Office of the Chief Building Official BP-2017-01610 X Alternative olution / Minor Relaxation* August 14, 2017 Related Building Permit elect One Last Revision Date APPLICANT

More information

Document Information Cover Sheet

Document Information Cover Sheet Document Information Cover Sheet Asite/Document Reference Number: LOR-CO-SW-RP-0015 Document Title: Equipment Interface Document Revision: F02 Publisher: Laing O Rourke Published: 23/04/2013 Outline Description/Comments

More information

Product Specifications Dialog Room Controller* (*patent pending)

Product Specifications Dialog Room Controller* (*patent pending) 1 Product Specifications Dialog Room Controller* (*patent pending) 1. GENERAL 1.1. OVERVIEW 1.1.1. Provide a complete stand-alone, decentralized, low voltage, digital lighting control system for classrooms,

More information

F & S Caretaking Department Design Standards For New or Renovated U of T Premises February 2015

F & S Caretaking Department Design Standards For New or Renovated U of T Premises February 2015 F & S Caretaking Department Design Standards For New or Renovated U of T Premises February 2015 Caretaking Department Space Requirements: Caretaking Manager must sign off on Caretaking space allocations.

More information

Yes, any other system must be clean agent, and the Fire Alarm Control Panel must be a single addressable Fire Alarm Control Panel.

Yes, any other system must be clean agent, and the Fire Alarm Control Panel must be a single addressable Fire Alarm Control Panel. Please respond to: SB-8 Mayo Building Tallahassee, Florida 32399 TO: FROM: RE: Vendors Christie Hutchinson, Purchasing Director INVITATION TO BID NUMBER ITB/PI-12/13-53 INSTALLATION OF A FIRE SUPPRESSION

More information

ELECTRICAL BULLETIN

ELECTRICAL BULLETIN PO Box 697 Halifax, Nova Scotia B3J 2T8 Labour and Workforce Development ELECTRICAL BULLETIN 2011-01 From: David MacLeod,C.E.I.,P.Eng. Pg 1 of 6 Provincial Chief Electrical Inspector Date: January 5,2011

More information

Clarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group

Clarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group Summary of Changes CAN/ULC-S524-06 Installation of Fire Alarm Systems Alan Cavers Area Manager Fire & Security Systems Group Course Title Rev Date: Summary of Changes Correct Deficiencies noted CAN/ULC-S524-01

More information

Philips MASTER LEDbulb DIM W & W E27/B K 230 V

Philips MASTER LEDbulb DIM W & W E27/B K 230 V MASTER LEDbulb Technical Application Guide Philips MASTER LEDbulb DIM 13-75 W & 18-100 W E27/B22 2700 K 230 V Dimmable LED replacement for a 75 W/100 W GLS bulb with warm white light all around. Philips

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

BULLETIN. Temperature Controls (10/2013)

BULLETIN. Temperature Controls (10/2013) BULLETIN Temperature Controls (10/2013) This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. This applies to Phase I & II only. Tenant Responsibility:

More information

BULLETIN. Temperature Controls (VAV) (3/11/2010)

BULLETIN. Temperature Controls (VAV) (3/11/2010) BULLETIN Temperature Controls (VAV) (3/11/2010) This bulletin is to advise you of the fees and responsibilities associated with Tenant s temperature controls. Tenant Responsibility: 1. Unit power is by

More information

W. DAYTON ST. L-001 LANDSCAPE PLAN LAYOUT 30" 15" " 24" MADISON, W I. GENERAL NOTES:

W. DAYTON ST. L-001 LANDSCAPE PLAN LAYOUT 30 15  24 MADISON, W I. GENERAL NOTES: R.R. TRACK LANDCAPE PLAN LAYOUT unny lope Road Brookfield, Wisconsin 00 GENERAL NOTE:. LANDCAPE CONTRACTOR HALL CONTACT CITY FORETRY AT LEAT HOUR IOR TO PLANTING TO VERIFY PLANTING ITE, INPECT NURURY TOCK,

More information

Brighton Area Fire Authority

Brighton Area Fire Authority 615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following

More information

RFP DRAINAGE OUTFALL DESIGN AND PERMITTING. Mandatory Meeting for Proposers August 15, 2015

RFP DRAINAGE OUTFALL DESIGN AND PERMITTING. Mandatory Meeting for Proposers August 15, 2015 RFP 2018-02 DRAINAGE OUTFALL DESIGN AND PERMITTING Mandatory Meeting for Proposers August 15, 2015 IMPORTANT DATES August 15 th, 2:00pm August 17 th, 5:00pm August 22 nd, 5:00pm September 5 th, 2:00pm

More information

ISO Submissions on Revised Working Draft (N 348)

ISO Submissions on Revised Working Draft (N 348) ISO/TC 145/SC 2/WG 1 N 359 Date: 2006-05-29 Source: ISO/TC 145/SC 2/WG 1 Secretariat Project: ISO 23601 Status: 20.20 (WD study initiated) Requested action: for discussion at next WG 1 meeting Distribution:

More information

Section 11. Electrical System. 42--CF200--MA--08 (formerly 42-65) Issued 5/96 P/N B. E 1996 Nordson Corporation All rights reserved

Section 11. Electrical System. 42--CF200--MA--08 (formerly 42-65) Issued 5/96 P/N B. E 1996 Nordson Corporation All rights reserved ection 11 Electrical ystem 11-0 Electrical ystem Table of Contents i Table of Contents ection 11 Electrical ystem 1. Introduction... 11-1 Electrical Operation... 11-1 Heating Zones... 11-2 2. Electrical

More information

UNIVERSITY OF TOLEDO

UNIVERSITY OF TOLEDO UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect

More information

St. Vincent s Health System Page 1 of 6

St. Vincent s Health System Page 1 of 6 St. Vincent s Health System Page 1 of 6 TITLE: Fire Plan Code Red FACILITY: St. Vincent s East FUNCTION: ORIGINATING DEPT: HOSPITAL SHARED POLICY? EFFECTIVE DATE: _X Yes No DOCUMENT NUMBER: 801 ORIGINATION

More information

TENDER CRFQ NO (E-TENDER REF NO.13020)

TENDER CRFQ NO (E-TENDER REF NO.13020) ADDENDUM NO:2 AGAINST TENDER FOR DESIGN, ENGINEERING, SUPPLY, INSTALLATION, TESTING, COMMISSIONING AND POST WARRANTY AMC OF RIM SEAL FIRE PROTECTION SYSTEM FOR BPCL- MUMBAI REFINERY (BPCL MR) TENDER CRFQ

More information

APPLICATION FOR COSMETOLOGY/SPA PLAN REVIEW

APPLICATION FOR COSMETOLOGY/SPA PLAN REVIEW Wilton Health Department Barrington A. Bogle, RS, MPH, CHES DIRECTOR OF HEALTH barry.bogle@wiltonct.org Town Hall Annex 238 Danbury Road Wilton, CT 06897 P-203-563-0174 F-203-563-0148 Jennifer M. Zbell,

More information

ENGINEERING STANDARDA FOR FIRE FIGHTING HOSE BOX AND SHELTER FIRST EDITION APRIL 2015

ENGINEERING STANDARDA FOR FIRE FIGHTING HOSE BOX AND SHELTER FIRST EDITION APRIL 2015 ENGINEERING STANDARDA FOR FIRE FIGHTING HOSE BOX AND SHELTER FIRST EDITION APRIL 2015 This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner. Neither whole

More information

MIXED USE RESIDENTIAL AND COMMERCIAL DEVELOPMENT AT 3636 BATHURST STREET

MIXED USE RESIDENTIAL AND COMMERCIAL DEVELOPMENT AT 3636 BATHURST STREET REPORT N O 111-12400 MIXED USE RESIDENTIAL AND COMMERCIAL DEVELOPMENT AT 3636 BATHURST STREET TRAFFIC IMPACT STUDY AND PARKING STUDY - RESPONSE TO COMMENTS - ADDENDUM AUGUST 2014 111-12400 August 28,

More information

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S.

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. NAME OF TENDER: CONSTRUCT, DELIVER AND COMMISSION 3 (THREE) LIFT STATION ELECTRICAL LOCATION OF WORK: 3 Separate work sites in

More information

PART 3-O REQUIREMENTS FOR SPRINKLER SYSTEMS MAINTENANCE AND SUPERVISION. 3-O Introduction O.1 Scope of Maintenance and Supervision...

PART 3-O REQUIREMENTS FOR SPRINKLER SYSTEMS MAINTENANCE AND SUPERVISION. 3-O Introduction O.1 Scope of Maintenance and Supervision... CONTENTS Schedule of amendments for this part of the scheme document Page 1 of 14 3-O Introduction...3 3-O.1 Scope of Maintenance and Supervision...3 3-O.2 Certification conditions...5 3-O.3 LPS 1233 Service

More information

PRAIRIE VIEW A&M UNIVERSITY AUSTIN GREAUX ENGINEERING BUILDING CHANCELLOR'S RESEARCH INITIATIVE RENOVATION PRAIRIE VIEW, TEXAS 77445

PRAIRIE VIEW A&M UNIVERSITY AUSTIN GREAUX ENGINEERING BUILDING CHANCELLOR'S RESEARCH INITIATIVE RENOVATION PRAIRIE VIEW, TEXAS 77445 C C C PRAIRIE VIEW A&M UNIVERITY GENERAL NOTE: THE INTENT I TO HAVE NO EXPOED WIRING, CONDUIT OR CABLE ON WALL OR IN OPEN CEILING. ARCHITECT I URRING OUT WALL WHERE VERTICAL CONDUIT RUN ARE NEEDED. I THERE

More information

CCDC EXPANSION PROJECT

CCDC EXPANSION PROJECT CCDC EXPANSION PROJECT TEMPORARY MOBILE KITCHEN RFP NO. 12-0132-3 Addendum #1 ADDENDUM #1 IS BASED ON THE INFORMATION DISCUSSED AT THE MANDATORY PRE-BID MEETING THAT WAS HELD ON THURSDAY, JANUARY 10, 2013

More information

Florida Department of Transportation 1000 NW 111 th Avenue, Room 6203 Miami, Florida

Florida Department of Transportation 1000 NW 111 th Avenue, Room 6203 Miami, Florida RICK SCOTT GOVERNOR Florida Department of Transportation 1000 NW 111 th Avenue, Room 6203 Miami, Florida 33172-5800 ANANTH PRASAD, P.E. SECRETARY ADDENDUM No. 02 ISSUED ON OCTOBER 14, 2014 TO THE PROJECT

More information

This addendum responds to initial questions submitted by vendors.

This addendum responds to initial questions submitted by vendors. 5761 Keyo Building Orono, ME 04469-5761 Main:207-581-2712 ldd/tdy:207-973-3262 www.maine.edu REQUEST FOR PROPOSALS #125-2017 Mechanical & HVAC Preventative Maintenance, Inspection & Repair Services for

More information

Dear Customer. Section Old F8 January 2017 Amendment 4. Replace with new title page and document history pages 1 2B

Dear Customer. Section Old F8 January 2017 Amendment 4. Replace with new title page and document history pages 1 2B Dear Customer Please find enclosed Amendment 4, effective 14 February 2014, to the Acceptable Solution and Verification Method for Clause F8 Signs of the New Zealand Building Code. THe previous amendment

More information

Subject: Addendum #3 IFB No CNG Gas Detection Repair and Maintenance

Subject: Addendum #3 IFB No CNG Gas Detection Repair and Maintenance October 12, 2012 Subject: Addendum #3 IFB No. 112-12 CNG Gas Detection Repair and Maintenance Please be advised of the following questions and responses: 1. Question #1: If the MBTA Everett and Arborway

More information

PACDA Application Forms. 5/15/2018 Aman Fire Protection Consultants 1

PACDA Application Forms. 5/15/2018 Aman Fire Protection Consultants 1 PACDA Application Forms 5/15/2018 Aman Fire Protection Consultants 1 PACDA Submission Forms Preliminary Approval Form Final Approval Form Hazards Material Approval Form 5/15/2018 Aman Fire Protection Consultants

More information

Indoor Controls. SpaceWise SWZG2. Wireless technology

Indoor Controls. SpaceWise SWZG2. Wireless technology Project: Indoor Controls SpaceWise SWZG2 Location: Cat. No: Type: Lamps: Notes: Qty: Philips luminaires with SpaceWise wireless technology SWZG2 are stand alone LED lighting systems with integrated occupancy

More information

Alcon Lighting P Continuum 23 Architectural LED Linear Pendant Mount Direct/Indirect Light Fixture

Alcon Lighting P Continuum 23 Architectural LED Linear Pendant Mount Direct/Indirect Light Fixture Type: Quantity: FIXTURE PECIFICATION INTENDED UE The specification grade Continuum 23 LED uspension Architectural Linear Luminaire delivers continuous clean lines and clear light to commercial, hospitality

More information

AMENDMENT NO.: III INVITATION FOR BID NO.: GPA FOR

AMENDMENT NO.: III INVITATION FOR BID NO.: GPA FOR January 26, 2018 AMENDMENT NO.: III TO INVITATION FOR BID NO.: GPA-022-18 FOR PHYSICAL SECURITY AND ACCESS CONTROL SYSTEM (ACS) REPAIR AND UPGRADE AT VARIOUS GPA LOCATIONS Prospective Bidders are hereby

More information

MAZAGON DOCK SHIPBUILDERS LIMITED

MAZAGON DOCK SHIPBUILDERS LIMITED MAZAGON DOCK SHIPBUILDERS LIMITED (Formerly known as Mazagon Dock Ltd.) CIN : U35100MH1934GOI002079 (A Government of India Undertaking) Shipbuilders to the Nation Dockyard Road, Mazagon, Mumbai 400 010.

More information

Date Issued: December 14, 2017 Revision: 2.1

Date Issued: December 14, 2017 Revision: 2.1 2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,

More information

CoreLine Wall-mounted the clear choice for LED

CoreLine Wall-mounted the clear choice for LED Lighting CoreLine Wall-mounted the clear choice for LED CoreLine Wall-mounted Whether for a new building or renovation of an existing space, customers want solutions that provide quality of light and substantial

More information

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 69 PRESIDENT SEPTEMBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report: 69

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 371 (OLD 615) - BROOKLYN, 355 37 STREET, New York, 11232 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-23

More information

Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1

Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1 12/4/2017 Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1 This bulletin is to advise you of the fees and responsibilities associated with the tenant s temperature controls. Tenant

More information

Exterior Façade Lighting Design

Exterior Façade Lighting Design Exterior Façade Lighting Design Duques Hall is located on George Washington campus in downtown Washington DC. It is located amidst some other university buildings, however, the façade is very visible from

More information

THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO TELEPHONE: (440) FAX: (440) Building Department

THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO TELEPHONE: (440) FAX: (440) Building Department THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO 44039 TELEPHONE: (440) 353-0822 FAX: (440) 353-0823 Building Department INSTRUCTIONS FOR DECKS REQUIREMENTS FOR PERMIT: Completed

More information

INVITATION TO TENDER ITT PS CONSTRUCTION OF STANLEY PARK MINI TRAIN STATION. AMENDMENT No. 4

INVITATION TO TENDER ITT PS CONSTRUCTION OF STANLEY PARK MINI TRAIN STATION. AMENDMENT No. 4 FINANCIAL SERVICES GROUP Supply Management July17, 2015 INVITATION TO TENDER ITT PS20150687 CONSTRUCTION OF STANLEY PARK MINI TRAIN STATION AMENDMENT No. 4 RE: REVISED DRAWINGS 1. ARCHITECTURAL DRAWINGS

More information

00 Galleria Officentre Southfield, Michigan 80 phone 8.5.80 fax 8.5.8 Student Center 5th Floor Renovation 5 Gullen Mall Detroit, Michigan 80 WSU No. 0-6688 CENTER BUILDING FIFTH FLOOR RENOVATION\s\5-806-E.dwg,

More information

ADDENDUM NO. 1. for. MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140. Marquette, Michigan.

ADDENDUM NO. 1. for. MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140. Marquette, Michigan. ADDENDUM NO. 1 for MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140 Marquette, Michigan December 12, 2016 TO: ALL BIDDERS OF RECORD This addendum forms a part of

More information

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion Table-1: Clarifications and modification in tender s based on Pre-bid meeting discussion Sr. Ref Page. 1 4 Clause Site Preparation and Partitions walls 2 11 SLD 3 18 Batteries 4 18 Batteries 5 32 to 34

More information

FIRE SAFETY POLICY. 2.0 Under national, provincial and municipal fire regulations, the Board will ensure compliance with:

FIRE SAFETY POLICY. 2.0 Under national, provincial and municipal fire regulations, the Board will ensure compliance with: FIRE SAFETY POLICY 1.0 The Halifax Regional School Board recognizes the need for a planned program of fire safety to ensure a safe environment for all personnel and pupils. 2.0 Under national, provincial

More information

Instruction manual APU Hard alarm output contacts

Instruction manual APU Hard alarm output contacts Instruction manual APU Hard alarm output contacts Instruction manual APU Hard alarm output contacts January 2010 Part no.: 4416.579 Rev. 3 Enraf BV PO Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701

More information

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section Wiring Devices for wall-box dimmers and manual light switches. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 2 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 3 1.7 COORDINATION... 3 1.8 DELIVERY, STORAGE, AND

More information

Tennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities

Tennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities Tennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities 1 Colby Henson Fire Safety Supervisor 665 Mainstream Drive 2nd floor 615-806-4798 Colby.Henson@tn.gov

More information

Northeast Corner of Steeles Avenue West and Jane Street, City of Vaughan

Northeast Corner of Steeles Avenue West and Jane Street, City of Vaughan STAFF REPORT ACTION REQUIRED Northeast Corner of Steeles Avenue West and Jane Street, City of Vaughan Date: June 1, 2010 To: From: Wards: Reference Number: North York Community Council Director, Community

More information

Design Review of Facility Improvement Projects

Design Review of Facility Improvement Projects Design Review of Facility Improvement Projects Agenda Board Meeting Schedule Scope of Work Summary Overall Building Plans and Scope Summary Update on Areas of Design Development Programming and Space planning

More information

ClearAccent - Affordable recessed LED spot

ClearAccent - Affordable recessed LED spot Lighting ClearAccent - Affordable recessed LED spot ClearAccent ClearAccent is an entry-level recessed spot range designed to replace halogen-based luminaires. Its attractive price and high lumen per watt

More information

PUR933- Christmas Decoration Installation Addendum 1. Pricing:

PUR933- Christmas Decoration Installation Addendum 1. Pricing: PUR933- Christmas Decoration Installation Addendum 1 Pricing: Bidders should submit cost per item pricing list for all items requested. The annual pricing for purchased items should include all installation,

More information

CCS-100. Installation Manual

CCS-100. Installation Manual Installation Manual CCS-100 WARNING: DO NOT ATTEMPT TO INSTALL USE THE FIXTURE WITHOUT READING THE INSTALLATION INSTRUCTIONS AND SAFETY LABELS COMPLETELY. Failure to adhere to these instructions could

More information

Item No. Description 1. BID PROPOSAL FORM Make the following revisions: a. Replace the BID PROPOSAL FORM with the attached BID PROPOSAL FORM.

Item No. Description 1. BID PROPOSAL FORM Make the following revisions: a. Replace the BID PROPOSAL FORM with the attached BID PROPOSAL FORM. City of Raleigh, Fire Station No. 11 Renovation September 28, 2018 274-CM2018-15A Page 1 HUFFMAN ARCHITECTS, PA 632 PERSHING ROAD RALEIGH, NORTH CAROLINA 27608 PHONE (919) 740-5669 TO: ALL PRIME BIDDERS

More information

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY. STATE OF LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BOULEVARD, BATON ROUGE, LA 70806 800-256-5452 225-925-4920

More information

1.2. The system records images only and does not have sound capability.

1.2. The system records images only and does not have sound capability. Closed Circuit Television (CCTV) Policy 1. Introduction Royal Academy of Dance (RAD) uses closed circuit television (CCTV) images to monitor the RAD s premises at 36 Battersea Square, SW11 3RA in areas

More information