Agenda Technical Committee on Protected Premises Fire Alarm Systems June 25-27, 2014 La Jolla, CA

Size: px
Start display at page:

Download "Agenda Technical Committee on Protected Premises Fire Alarm Systems June 25-27, 2014 La Jolla, CA"

Transcription

1 Agenda Technical Committee on Protected Premises Fire Alarm Systems June 25-27, 2014 La Jolla, CA Item No. Subject Call to Order (8:00 A.M) Roll Call Approval of Agenda Approval Meeting Minutes September 2013 [Enclosure] Staff Remarks & Using the New Process [Staff] UL Update on Fire Resistive Cable (tentative) Task Group Reports Public Comments and Second Revisions [Enclosures] Review of Committee Inputs [Enclosure] Other Business Adjournment

2 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: MEETING MINUTES NFPA TECHNICAL COMMITTEE ON PROTECTED PREMISES FIRE ALARM SYSTEMS (SIG-PRO) First Draft Meeting, September 09-11, 2013 St. Louis Union Station, St. Louis, MO Item No. Subject Call to Order and Welcome (8:04 AM) Chair Merton Bunker called the meeting to order at 8:04 AM Approve Agenda Motion to approve the Agenda, seconded, and approved Approve Meeting Minutes from San Antonio, TX, March 2013 Motion to approve the Minutes from , seconded, and approved Introduction of Members Those present introduced themselves (see attached Attendance Sheet for all attendees, Principles, Alternates, and Guests). A number of guests participated during the committee meeting over the 2½ days including: Mr. Bob Schifiliti, TCC Chair Mr. Bruce Fraser, SIG ECS Staff Remarks & Presentations Mr. Lee Richardson (NFPA Staff) provided presentations on the following: Overview of the New Process Strategy to Improve Correlation Assignment of Technical Committee Responsibility

3 o Goal: minimize the number of committees working on the same chapter o Chapter 12 is now completely under the purview of SIG PRO Task Group Work Review of Public Inputs In order to maximize the time the committee had to review the various Public Inputs, Mr. Merton Bunker, SIG PRO Committee Chair assigned task groups to review the Public Inputs, provide a recommendation on acting on the Public Inputs (i.e., Move to First Revision, Move to Resolve, etc.), and present the recommendation to the Committee for discussion. Task Groups below are identified in the order that each group of Public Inputs were addressed. Task Group 2: Circuits and Pathways: Horon, Capowski, Hayes, Weiss-Ishai, Novak, Shudak, Ruchala (Task Group Chair) Task Group 1: Definitions, Documentation, and System Requirements: Barrett, Hopple, Harris, Humm, Martorano, Shah, Olenick, Crowley, Doyle, Belliveau (Task Group Chair) Task Group 3: Emergency Controls: Doliber, Dix, Bisker, Leszczak, LeBlanc, Kuhta, Struck, Burkhart, Willms, Hammerberg (Task Group Chair) In addition to processing of all Public Inputs, the committee entertained discussions from the following Committee Members and guests on the following: Mr. Larry Shudak discussed alarm receipt capability during a fault condition Mr. Vic Humm discussed the possibility of adding new networking definitions The term required annunciators appeared in the code approximately three (3) times and the ambiguity was removed Chapter 2 references were reviewed and updated where required Mr. Bruce Fraser (SIG ECS) provided some insight on the current language of ASME A17.1/CSA B44Safety Code for Elevators and Escalators to ensure that NFPA 72 is not providing conflicting requirements Mr. Bill Hopple discussed whether the committee feels that the definition of a detector should change and discussed the protection of control units for dedicated function fire alarm control units Mr. Tom Hammerberg discussed some definitions that could be revised Processing Schedule Mr. Lee Richardson (NFPA Staff) provided dates for the NFPA 72 document cycle. NFPA 72 (A2015) Meeting Dates CC FD Meeting (Tampa*) though Posting of First Draft Report Comment Closing Date TC SD Meeting 1 (Indy* or Omaha*) through {SIG-IDS, SIG-NAS, SIG-SSS, SIG-HOU and SIG-PRS} TC SD Meeting 2 (Indy* or Omaha*) through {SIG-PRO, SIG-FUN, SIG-ECS and SIG-TMS}

4 CC SD Meeting (San Diego*) through Posting of Second Draft Report NITMAM Closing Date Posting of CAMs Annual Meeting (Chicago) through *Tentative location - pending venue availability Other Business No Other Business documented at this time. Mr. Lee Richardson (NFPA Staff) to review the processing schedule above and possibly recommend days be added to the Committee Meetings to review and process comments received on the First Draft document Adjournment Mr. Merton Bunker thanked the committee members for their hard work in reviewing and processing all the Public Inputs that were presented to the group. A motion to adjourn was moved, seconded, voted on and approved. The meeting was adjourned. The meeting spanned two (2 ½) days, , and Respectfully submitted, Leonard Belliveau, Jr. NFPA 72, SIG-PRO Secretary

5 38 of 346 5/19/ :24 AM Public Comment No. 235-NFPA [ Global Input ] Delete references to the National Electrical code article 760 or any specific article, and just use the wording as per the National Electrical Code. Statement of Problem and Substantiation for Public Comment The direct reference to only article 760 is leading to confusion as some persons do not understand how the NEC is arranged. Articles in chapters 1-4 apply to ALL wiring including Fire alarm and signaling circuits. Chapters 5-7 modify the requirements of chapters 1-4 therefore article 760 is not designed to be a stand alone chapter and should not be referred to as if it is. Chapter 8 is designed to be a stand alone chapter, except when specifically referenced back to a previous chapter. Related Item First Revision No. 92-NFPA [Section No ] Public Input No. 514-NFPA [Section No ] Submitter Information Verification Submitter Full Name: Thomas Parrish Organization: Telgian Corporation Street Address: City: State: Zip: Submittal Date: Fri May 16 15:13:48 EDT 2014

6 75 of 346 5/19/ :24 AM Public Comment No. 147-NFPA [ New Section after ] New Definition 3.x * cross-connect. An apparatus which enables the connection of network and telecommunications cabling from devices, systems or equipment to the network and telecommunications cabling of other systems or equipment. Statement of Problem and Substantiation for Public Comment Substantiation (FCR 17) With the addition of Class N, some terminology used to express telecommunications and network concepts specifically within the context of Class N were not defined. This change is to reduce ambiguity when this term is encountered both within the text of this document and within real-world application. Related Item First Correlating Revision No. 17-NFPA [Global Input] Submitter Information Verification Submitter Full Name: Jeff Silveira Organization: BICSI Street Address: City: State: Zip: Submittal Date: Wed May 14 11:50:29 EDT 2014

7 1 of 2 5/27/2014 2:17 PM Public Comment No. 128-NFPA [ New Section after A ] Device (Class N) Class N devices includes components connected to a class N network that monitor the environment (e.g., smoke, heat, contact closure, manual in case of fire pull), and/or provide some output(s), (e.g., dry contact, audible/visual alert/notification, addressable speaker), that are required to provide the real-time functionality necessary for the protection of life and property. In this way a component connected to the network used for non-critical functions (i.e., maintenance) may be differentiated and excluded from the monitoring for integrity requirements of class N. Also in this way, transport equipment (e.g., switches, routers, hubs, media converters ) and other equipment (e.g., printers, storage devices) may be differentiated from the requirements applied to class N devices, if they do not provide life safety specific environmental monitoring, inputs, or outputs for the life safety system. This is not to say that this equipment is not important to the overall operation of the system, just that this equipment is not considered a device in the context of Class N. Equipment that does not meet the definition of a device may not be specifically supervised, but rather generally supervised as they are part of the supervised pathways that service the Class N devices themselves. Statement of Problem and Substantiation for Public Comment Additional clarification for the definition of device as it relates to class N was warranted to both illustrate examples of what is a class N device and what is not and how the distinction is drawn. The proposal is the recommendation by the Correlating Committee Task Group members that was comprised of TC members from Chapters 10, 14, 23, 24 and 26 as well as individuals outside of the committees. Wayne Moore A.J. Capowski Joe L. Collins Dan Horon Vic Humm Michael Pallett Charles Pugh Robert Schifiliti Aviv Siegel Larry Shudak Bob Elliott Paul Crowley Jeff Silveira Jeff Knight Andrew Berezowski Related Public Comments for This Document Related Comment Public Comment No. 127-NFPA [New Section after ] Related Item First Revision No. 99-NFPA [New Section after ] Relationship Submitter Information Verification Submitter Full Name: Michael Pallett Organization: Telecor Inc. Street Address: City:

8 2 of 2 5/27/2014 2:17 PM State: Zip: Submittal Date: Tue May 13 19:43:55 EDT 2014 Copyright Assignment I, Michael Pallett, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Comment (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which this Public Comment in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Comment and that I have full power and authority to enter into this copyright assignment. By checking this box I affirm that I am Michael Pallett, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature

9 48 of 346 5/19/ :24 AM Public Comment No. 127-NFPA [ New Section after ] Device (Class N) A supervised component of a life safety system, that communicates with other components of life safety systems, and that collects environmental data, or performs specific input or output functions necessary to the operation of the life safety system. Statement of Problem and Substantiation for Public Comment With the addition of Class N pathways in the first draft, the term device was used specifically in the context of Class N, but not defined. The proposal is the recommendation by the Correlating Committee Task Group members that was comprised of TC members from Chapters 10, 14, 23, 24 and 26 as well as individuals outside of the committees. Wayne Moore A.J. Capowski Joe L. Collins Dan Horon Vic Humm Michael Pallett Charles Pugh Robert Schifiliti Aviv Siegel Larry Shudak Bob Elliott Paul Crowley Jeff Silveira Jeff Knight Andrew Berezowski Related Item First Revision No. 99-NFPA [New Section after ] Submitter Information Verification Submitter Full Name: Michael Pallett Organization: Telecor Inc. Street Address: City: State: Zip: Submittal Date: Tue May 13 19:19:25 EDT 2014

10 7 of 346 5/19/ :24 AM Public Comment No. 31-NFPA [ Section No ] * Emergency Control Functions. Building, fire, and emergency control elements or systems that are initiated by the fire alarm or signaling system and either increase the level of life safety for occupants or control the spread of the harmful effects of fire or other dangerous products. (SIG-PRO) Statement of Problem and Substantiation for Public Comment Removes unnecessary and limiting qualifiers. Related Item First Revision No. 124-NFPA [Section No ] Submitter Information Verification Submitter Full Name: Robert Schifiliti Organization: R. P. Schifiliti Associates, I Street Address: City: State: Zip: Submittal Date: Thu Apr 03 08:53:53 EDT 2014

11 51 of 346 5/19/ :24 AM Public Comment No. 130-NFPA [ New Section after A ] Endpoint (Class N) An endpoint device originates and/or terminates a communication stream, and does not forward it to other devices. An FACU, ACU, ECCU endpoint originates and/or terminates a communication stream with autonomy. If data is sent to, or received from other locations, that communications stream forms a new path. The new path may even employ a different communications protocol, and where permitted, have a different Pathway Class Designation as defined in The exception in section (1) shows Class N communication paths do not require redundant paths when connected to a single endpoint device. However, connections to an FACU, ACU or ECCU must be redundant even when those elements are an endpoint on a Class N communication path, with the excepted allowance of 20 feet inside a raceway or enclosure defined in Statement of Problem and Substantiation for Public Comment Additional clarification for the definition of endpoint as it relates to class N was warranted to explain the distinction between endpoints that are devices and endpoints that are control units, and their relationship to communications. The proposal is the recommendation by the Correlating Committee Task Group members that was comprised of TC members from Chapters 10, 14, 23, 24 and 26 as well as individuals outside of the committees. Wayne Moore A.J. Capowski Joe L. Collins Dan Horon Vic Humm Michael Pallett Charles Pugh Robert Schifiliti Aviv Siegel Larry Shudak Bob Elliott Paul Crowley Jeff Silveira Jeff Knight Andrew Berezowski Related Public Comments for This Document Related Comment Public Comment No. 129-NFPA [New Section after ] Related Item First Revision No. 99-NFPA [New Section after ] Relationship Submitter Information Verification Submitter Full Name: Michael Pallett Organization: Telecor Inc. Street Address: City: State: Zip:

12 50 of 346 5/19/ :24 AM Public Comment No. 129-NFPA [ New Section after ] Endpoint (Class N) The end of a pathway where a single addressable device or a control unit (FACU, ACU, or ECCU) is connected. Statement of Problem and Substantiation for Public Comment With the addition of Class N pathways in the first draft, the term endpoint was used specifically in the context of Class N, but not defined. The proposal is the recommendation by the Correlating Committee Task Group members that was comprised of TC members from Chapters 10, 14, 23, 24 and 26 as well as individuals outside of the committees. Wayne Moore A.J. Capowski Joe L. Collins Dan Horon Vic Humm Michael Pallett Charles Pugh Robert Schifiliti Aviv Siegel Larry Shudak Bob Elliott Paul Crowley Jeff Silveira Jeff Knight Andrew Berezowski Related Item First Revision No. 99-NFPA [New Section after ] Submitter Information Verification Submitter Full Name: Michael Pallett Organization: Telecor Inc. Street Address: City: State: Zip: Submittal Date: Tue May 13 20:02:40 EDT 2014

13 76 of 346 5/19/ :24 AM Public Comment No. 148-NFPA [ New Section after ] New Definition 3.x * media converter. A network device that connects two dissimilar types of cabling media, such as balanced twisted-pair cabling and coaxial cabling, or balanced twisted-pair cabling and optical fiber cabling. Statement of Problem and Substantiation for Public Comment Substantiation (FCR 17) With the addition of Class N, some terminology used to express telecommunications and network concepts specifically within the context of Class N were not defined. This change is to reduce ambiguity when this term is encountered both within the text of this document and real-world application. Related Item First Correlating Revision No. 17-NFPA [Global Input] Submitter Information Verification Submitter Full Name: Jeff Silveira Organization: BICSI Street Address: City: State: Zip: Submittal Date: Wed May 14 11:59:21 EDT 2014

14 77 of 346 5/19/ :24 AM Public Comment No. 149-NFPA [ New Section after ] New Definition 3.x * ring topology. A physical or logical arrangement of a system or network in which nodes are connected in a point-to-point serial fashion and forming an unbroken circular configuration. Each node receives and retransmits the signal to the next node. Statement of Problem and Substantiation for Public Comment Substantiation (FCR 17) With the addition of Class N, some terminology used to express telecommunications and network concepts specifically within the context of Class N were not defined. This change is to reduce ambiguity when this term is encountered both within the text of this document and within real-world application. Related Item First Correlating Revision No. 17-NFPA [Global Input] Submitter Information Verification Submitter Full Name: Jeff Silveira Organization: BICSI Street Address: City: State: Zip: Submittal Date: Wed May 14 12:02:29 EDT 2014

15 03 of 346 5/19/ :24 AM Public Comment No. 162-NFPA [ New Section after ] New Definition 3.x * switch (class N). A device that provides a centralized point of connection for network enabled equipment, enabling communications between all connected elements. A connection port on a switch represents a separate communications channel, and a switch may perform additional functions, such as port monitoring and communication (message) management. A switch is an integral part of a local area network (LAN), Statement of Problem and Substantiation for Public Comment With the addition of Class N, some terminology used to express telecommunications and network concepts specifically within the context of Class N were not defined. This change is to reduce ambiguity when this term is encountered both within the text of this document and within real-world application. Related Item First Correlating Revision No. 17-NFPA [Global Input] Submitter Information Verification Submitter Full Name: Jeff Silveira Organization: BICSI Street Address: City: State: Zip: Submittal Date: Wed May 14 13:13:59 EDT 2014

16 29 of 346 5/19/ :24 AM Public Comment No. 165-NFPA [ New Section after ] New Definition 3.x * uplink (class N): A cabling connection between switches in a network. An uplink may also be known as a "trunk" or backbone. Statement of Problem and Substantiation for Public Comment Substantiation (FCR 17) With the addition of Class N, some terminology used to express telecommunications and network concepts specifically within the context of Class N were not defined. This change is to reduce ambiguity when this term is encountered both within the text of this document and within real-world application. Related Item First Correlating Revision No. 17-NFPA [Global Input] Submitter Information Verification Submitter Full Name: Jeff Silveira Organization: BICSI Street Address: City: State: Zip: Submittal Date: Wed May 14 13:55:24 EDT 2014

17 6 of 346 5/19/ :24 AM Public Comment No. 56-NFPA [ Section No ] Performance-based design documentation for signaling line circuit zoning shall be in accordance with and (SIG-PRO) Statement of Problem and Substantiation for Public Comment CC NOTE: The following CC Note No. 3 appeared in the First Draft Report as First Revision No. 268, and is also related to Public Input No. 365 and 565. The correlating committee makes reference to introduced by FR 127. The correlating committee directs the SIG-PRO committee to reconsider the action on this FR to clear up the circular references that exist between and its reference to and the reference in back to Related Item First Revision No. 268-NFPA [Section No ] Public Input No. 365-NFPA [New Section after ] Public Input No. 565-NFPA [Section No ] Submitter Information Verification Submitter Full Name: CC on SIG-AAC Organization: CC on Signaling Systems for the Protection of Life and Property Street Address: City: State: Zip: Submittal Date: Wed Apr 30 09:13:21 EDT 2014

18 67 of 346 5/19/ :24 AM Public Comment No. 184-NFPA [ Section No ] Class N. A pathway shall be designated as Class N when it performs as follows: (1) * It includes two or more pathways where operational capability of the primary pathway and a redundant pathway to each device shall be verified through end-to-end communication. Exception: When only one device is served, only one pathway shall be required. (2) A loss of intended communications between endpoints shall be annunciated as a trouble signal. (3) A single open, ground, short, or combination of faults on one pathway shall not affect any other pathway. (4) (5) * Conditions that affect the operation of the primary pathway(s) and redundant pathway(s) shall be annunciated as a trouble signal when the system s minimal operational requirements cannot be met. * Primary and redundant pathways shall not be permitted to share traffic over the same physical segment. Statement of Problem and Substantiation for Public Comment This section and designation should either be delted or only included in Annex material. The code is specifying performance that isn't required by any codes or standards and can't be applied without the expnatory material of the Annex. The annex material should also be delted becasue it conflicts with the perofrmance criteria stated. The diagrams inthe Annex material show both redundant paths to converge in single switches which is lost would render both paths unusable. There is nothing to preclude a designer to design for this performance. It doesn't need to be incorproated in NFPA 72. Related Item First Revision No. 99-NFPA [New Section after ] Submitter Information Verification Submitter Full Name: Raymond Grill Organization: Arup Street Address: City: State: Zip: Submittal Date: Wed May 14 21:10:52 EDT 2014

19 89 of 346 5/19/ :24 AM Public Comment No. 158-NFPA [ Section No. A (1) ] A (1)

20 90 of 346 5/19/ :24 AM Class N consists of pathways between control equipment and devices. The pathways comprise metallic conductor communications cable, such as a 100 ohm balanced twisted-pair (e.g., Category 5E), including single-pair or multi-pair cable, or other communications media such as optical fiber cable or wireless transmission, or a combination of two or more of these. Pathways consist of uninterrupted communications media between control equipment and an endpoint device or of a network of multiple interconnected communications media pathway segments connecting multiple devices. Media pathway segments are created by the use of transmission equipment such as Ethernet switches, wireless repeaters, or media converters that interrupt an otherwise continuous pathway. Requirements for Class N pathway transmission equipment are not covered in Chapter 12 but by other chapters in NFPA 72. A network of pathway segments is also described as primary pathway segments, redundant pathway segments, or nondesignated pathway segments. Primary and redundant pathways, from control equipment to each device, are independently and continuously verified for their ability to support end-to-end communications to and from each endpoint device. Each device will be provided a primary pathway consisting of one or more pathway segments. For primary pathway segments that service more than one device, additional redundant pathway segments provide alternate verified communication pathways to the devices. Should any primary pathway segment fail, communication is supported by the redundant pathway segments. Should either a primary or redundant pathway segment fail, trouble will be indicated by virtue of the continuous verification of all primary and redundant pathway segments. The redundant pathway segments are generally independent and do not normally share media with the primary pathways. However, there are exceptions, such as different frequencies for wireless or ring topologies. [See A (5).] There is an opportunity to enhance the robustness of a Class N network by providing physically distinct pathway segments (i.e., an alternate conduit, or cable tray route, or wireless transmission frequency range, or a combination of distinct media). It is also permissible to provide other nondesignated pathway segments. Additional pathway segments in excess of the minimum requirements of Class N increase the overall robustness of the network and are often desirable. However, since these additional pathway segments exceed the minimum equipment standards, there is no intention to create an additional monitoring burden, so verification of these pathways is optional. For Class N, where a conductor-based media is used, it is not the intention to monitor faults on individual conductors but rather to monitor the operational capability and performance of the pathway as a whole. Unlike Class C, where multiple pathways are not required, for Class N some pathway segments that carry communications for multiple devices (such as Ethernet uplinks or backbones) will have redundant pathway segments present. The intention is that any one pathway segment can fail without a loss in operational capability to more than one device. For example, connections to control equipment (fire alarm control units, ACUs, or ECCUs), where any interruption in communications could potentially affect all devices, would have redundant pathway segments. Additionally, backbone and uplink pathway segments that support communications for more than one device and are positioned between transmission equipment would also have a redundant pathway segment. But the requirement for redundant pathway segments does not apply to those pathway segments used to service a single device [see Figure A (1)(a) ]. The term devices is used generically in this section to refer to endpoint devices, which include the following: (1) Input components such as alarm initiating switches, sensors (2) Output components such as Ethernet speakers (i.e., IEEE 802.3af PoE speakers), strobes, textual signage, audio amplifiers Transmission equipment (e.g., media converters, Ethernet switches, patch panels, cross-connects) are not considered devices with respect to Class N pathways. The audio amplifier example is included to explain a type of addressable device that can receive a digital audio input from the Class N pathway but provide a notification appliance circuit (NAC) output to support Class A, B, or X speaker connections. Other similar devices are also possible to provide alternate class pathway connections for strobes (NACs) or initiating devices (IDCs). From the perspective of the Class N pathway, this is considered an endpoint device. However, since these types of endpoints can support multiple notification appliance devices or initiating devices, they are subject to the redundant pathway segment requirement and are provided with dual pathway connections. Control equipment connected to a Class N network for communications with devices would generally utilize redundant pathway segments. Control equipment connected to other control equipment on a Class N network would utilize redundant pathway segments if the control equipment was dependent on any of the pathway segments so that a failure of a primary pathway segment in between control equipment could impair the operation of the control equipment [see Figure A (1)(b) ].

21 91 of 346 5/19/ :24 AM Another utilization of endpoints is permitted for devices providing two connection ports and supporting dual pathway segment connections. The description of endpoint devices is not intended to exclude devices that support dual pathway connections. Since these pathways are servicing a single device, only a single primary pathway connection is required. The second pathway connection exceeds minimum equipment standards and is therefore not required to be verified as a redundant pathway segment; it can be considered connected to a nondesignated pathway segment [see Figure A (1)(c) ]. Figure A (1)(a) Class N Pathway Block Diagram. Figure A (1)(b) Class N Pathway Block Diagram with Multiple Control Units. Figure A (1)(c) Class N Pathway Block Diagram with Device with Dual Pathway Connection.

22 92 of 346 5/19/ :24 AM with subsequent subsections and drawings should be replaced with attached PDF. This material was created by the TCC Task Group on Networks. Additional Proposed Changes File Name Description Approved Class_N_Annex_Submitted_by_Task_Group_May_13_.pdf Statement of Problem and Substantiation for Public Comment Revised for clarity and consistency with Code. Related Item Public Input No. 290-NFPA [New Section after A ] Submitter Information Verification A (1) text and drawings are included in PDF. Submitter Full Name: Daniel Horon Organization: CADgraphics, Incorporated Street Address: City: State: Zip: Submittal Date: Wed May 14 12:56:33 EDT 2014

23 A (1) The Class N pathway designation is added to specifically address the use of modern network infrastructure when used in fire alarm and emergency communication systems. Ethernet network devices are addressable, but with an important distinction from device addresses on a traditional SLC multi drop loop. A device with an Ethernet address is, in most cases, a physical endpoint connected to a dedicated cable. Traditional SLC devices are all wired on the same communication line (in parallel) similar to an old party line telephone system. By comparison, Ethernet s network switches direct each data packet to its intended recipient device like our modern phone systems. A fundamental technical difference of Class N from Class A, B or X is that it has no requirement to report a connection to ground unless the ground impairs the path. A practical concern, where using Ethernet, is that it is reliable and secure, especially when life safety systems share the same pathways. See Class N Shared Pathways. As a visual model, Class N could be likened to a Class X [backbone], allowed to have Class C branch paths to single endpoint devices. Therefore, every effort is made in this section to clearly distinguish the single endpoint device from the transport equipment required to have redundant paths, like Class X. Class N requires, redundant, monitored pathway segments to and from control equipment (fire alarm control units, ACUs, or ECCUs), where any interruption in communications could potentially affect multiple endpoint devices. Typically, interconnected communications equipment such as Ethernet switches, wireless repeaters, or media converters are used in combination to create pathways. Chapter 12 describes the required behavior of Class N pathways. All equipment must meet the requirements of other chapters in NFPA 72. Redundant pathways, isolated from ground, are actually common practice in robust Ethernet designs. Managed network switches commonly have specific uplink ports that are intended for load sharing and allow two parallel connections. For compliance with Class N, a trouble must be reported if either of these connections fails. [See Figure A (1)(a 1).] Class N networks may be specified for ancillary functions, but are not required for supplemental reporting described in [See Figure A ] Class N pathways may use metallic conductor communications cable, such as a 100 ohm balanced twisted pair (e.g., Category 5E), including single pair or multi pair cable, or other communications media such as optical fiber cable or wireless transmission, or a combination of two or more such transport mediums. Where a conductor based media is used for Class N, the intention is not to monitor faults on individual conductors, but rather to monitor the operational capability and performance of the pathway as a whole. Similar to Class C, end to end verification is used in Class N. Primary and required redundant pathways are independently and continuously verified for their ability to support end to end communications to and from each endpoint device and its associated control equipment. Pathway segments that service more than one device, must have at least one verified redundant pathway segment. Should any primary pathway segment fail, communication is supported by the redundant pathway segment(s.) Failure of either a primary or redundant pathway will indicate a trouble.

24 Redundant pathway segments are generally independent and do not normally share media with the primary pathways. However, there are exceptions, such as different frequencies for wireless components, or ring topologies. [See Figure A (5).] A Class N network may be made more reliable with physically distinct pathway segments (i.e., an alternate conduit, or cable tray route, or wireless transmission frequency range, or a combination of distinct media). In addition to the required primary segments and redundant segments, a Class N pathway is permitted to have nonrequired segments. [See Figure A (1)(a 3).] Additional nonrequired pathway segments are allowed to be connected and not independently monitored for integrity as long as two paths are monitored to meet the redundancy requirement of Class N. Figure A (1)(a) Class N Pathway Block Diagrams. 20 Feet maximum inside enclosure or raceway FACU, ACU, or ECCU Switch Switch 1 2 A redundant cable between two switches must have special functionality in order to monitor integrity when a secondary path is not in use. Figure A (1)(a-1) Endpoint Devices 20 Feet maximum inside enclosure or raceway FACU, ACU, or ECCU Switch Switch 1 2 Nonrequired redundant path segment Endpoint Devices Group H Switch Switch 4 3 Figure A (1)(a-2) Endpoint Devices Group K Endpoint Devices Group J

25 Traditionally, NFPA has used the word device for input components, and term appliance for components used in notification. With respect to Class N, the term device includes appliances and other intelligent, addressable components that perform a programmable input or output function. Examples of Class N devices include: (1) Input components such as alarm initiating modules switches and sensors, (2) Output components such as output modules, Ethernet speakers (i.e., IEEE 802.3af PoE speakers), intelligent strobes, textual signage, and intelligent audio amplifiers. Transmission equipment components (e.g., media converters, Ethernet switches, patch panels, cross connects) are connected to the Class N pathway merely to transport instructions between other equipment. As such, they are not considered devices with respect to Class N pathways. The audio amplifier listed above is an example of an addressable device that can receive a digital audio input from the Class N pathway and then provide a notification appliance circuit (NAC) output with Class A, B, or X pathways. Other endpoint devices may similarly provide alternate Class pathways for strobes (NACs) or initiating devices (IDCs). From the perspective of the Class N pathway, communications terminates at this endpoint device. However, since these types of endpoints can support multiple notification appliance devices or initiating devices, they are subject to the redundant pathway requirement. A single component may provide two distinct functions in a life safety system. For example, one component may house both a fire sensor and a notification device. Or, an addressable input module may provide for two distinct inputs from a waterflow switch and a tamper switch. Class N requires both a primary and redundant path to these dual purpose components. Class N connections between control equipment are required to have redundant monitored pathway segments if a failure of a primary pathway segment in between control equipment could impair the operation of the control equipment [see Figure A (1)(b) ]. Figure A (1)(b) Class N Pathway Block Diagram with Multiple Control Units. Switch 1 FACU, ACU, or ECCU (1) FACU, ACU, or ECCU Switch 2 (2) Switch 3 FACU, ACU, or ECCU Figure A (1)(b) (3)

26 Class N is also permitted to include dual port devices that provide both transmission and input/output functions. Endpoint devices may have multiple connection ports and support dual pathway segment connections; thus the term endpoint device is not intended to prohibit more than one connection to a device. Even with dual connections, where other devices depend on the path, primary and redundant paths are required. But, where an endpoint device has two connection ports, and when a secondary nonrequired connection is added, there is no requirement to separately supervise the nonrequired redundant pathway segment [see Figure A (1)(c)]. Figure A (1)(c) Class N Pathway Block Diagram with Device with Dual Pathway Connection. To FACU Switch Endpoint Devices A nonrequired redundant cable to an endpoint device is permitted, and does not require separate supervision. Figure A (1)(c) A (4) Operational conditions of the pathway include factors such as latency, throughput, response time, arrival rate, utilization, bandwidth, and loss. Life safety equipment connected to a Class N network actively monitors some or all of the pathway s operational conditions, so that an improperly installed or configured pathway, or a subsequently degraded pathway or segment is detected by the life safety equipment and reported as a trouble. The trouble condition is reported when operational conditions of the pathway(s) have deteriorated to the point where the equipment is no longer capable of meeting its minimum performance requirements, even if some level of communication to devices is still maintained. Performance requirements include the activation of an alarm within 10 seconds, the reporting of a trouble signal within 200 seconds, synchronization of strobes, and delivery of audio messages with required intelligibility. End to end communications might be operational under system idle conditions, but in the event of an alarm, the increased load on a degraded pathway could cause a partial or complete failure to deliver required life safety signals. Such predictable failure must be actively detected and reported. A (5) Devices with dual path connections are permitted to be connected in a daisy chain of devices on a ring. Again, where Class N pathway segments support multiple devices, verified redundant pathway segment(s) are required. This can be accomplished with a ring topology, as long as each segment of the ring is verified as functional, and the failure of any one segment does not result in the loss of functionality of more than one device. In this arrangement, primary and redundant pathway segments share the same media, and provide two possible directions of communications in a ring topology [see Figure A (5) ]. This daisy chain configuration is also permitted between multiple control units that require verified primary and redundant pathway segments.

27 Figure A (5) Class N Pathway Block Diagram with Daisy Chained Devices with Dual Pathway Connection. To FACU Switch 1 Switch 2 Endpoint Devices with dual pathway connectors Communications continues from either direction in a ring topology. Figure A (5) Figure A Supplemental Reporting Network To UL Listed Monitoring Computer 1 Fire Alarm Control Unit Brand X Proprietary SLC Communications To UL Listed Monitoring Ethernet Network Computer 2 Fire Alarm Control Unit Brand Y To UL Listed Monitoring Proprietary SLC Communications Handheld Fire Alarm Control Unit Brand Z Figure A Proprietary SLC Communications

28 51 of 346 5/19/ :24 AM Public Comment No. 174-NFPA [ Section No. A (1) ]

29 52 of 346 5/19/ :24 AM A (1)

30 Class N consists of pathways between control equipment and devices. The pathways comprise A (1) The Class N pathway designation is added to specifically address the use of modern network infrastructure when used in fire alarm and emergency communication systems. Ethernet network devices are addressable, but with an important distinction from device addresses on a traditional SLC multi-drop loop. A device with an Ethernet address is, in most cases, a physical endpoint connected to a dedicated cable. Traditional SLC devices are all wired on the same communication line (in parallel) similar to an old party-line telephone system. By comparison, Ethernet s network switches direct each data packet to its intended recipient device like our modern phone systems. A fundamental technical difference of Class N from Class A, B or X is that it has no requirement to report a connection to ground unless the ground impairs the path. A practical concern, where using Ethernet, is that it is reliable and secure, especially when life safety systems share the same pathways. See Class N Shared Pathways. As a visual model, Class N could be likened to a Class X [backbone], allowed to have Class C branch paths to single endpoint devices. Therefore, every effort is made in this section to clearly distinguish the single endpoint device from the transport equipment required to have redundant paths, like Class X. Class N requires, redundant, monitored pathway segments to and from control equipment (fire alarm control units, ACUs, or ECCUs), where any interruption in communications could potentially affect multiple endpoint devices. Typically, interconnected communications equipment such as Ethernet switches, wireless repeaters, or media converters are used in combination to create pathways. Chapter 12 describes the required behavior of Class N pathways. All equipment must meet the requirements of other chapters in NFPA 72. Redundant pathways, isolated from ground, are actually common practice in robust Ethernet designs. Managed network switches commonly have specific uplink ports that are intended for load sharing and allow two parallel connections. For compliance with Class N, a trouble must be reported if either of these connections fails. [See Figure A (1)(a-1).] Class N networks may be specified for ancillary functions, but are not required for supplemental reporting described in [See Figure A ] Class N pathways may use metallic conductor communications cable, such as a 100 ohm balanced twisted - pair (e.g., Category 5E), including single - pair or multi-pair cable, or other communications media such as optical fiber cable or wireless transmission, or a combination of two or more of these. Pathways consist of uninterrupted communications media between control equipment and an endpoint device or of a network of multiple interconnected communications media pathway segments connecting multiple devices. Media pathway segments are created by the use of transmission equipment such as Ethernet switches, wireless repeaters, or media converters that interrupt an otherwise continuous pathway. Requirements for Class N pathway transmission equipment are not covered in Chapter 12 but by other chapters in NFPA 72.A network of pathway segments is also described as primary pathway segments, redundant pathway segments, or nondesignated pathway segments. Primary and redundant pathways, from control equipment to each device, such transport mediums. Where a conductor-based media is used for Class N, the intention is not to monitor faults on individual conductors, but rather to monitor the operational capability and performance of the pathway as a whole. Similar to Class C, end-to-end verification is used in Class N. Primary and required redundant pathways are independently and continuously verified for their ability to support end -? to - 53 of 346 5/19/ :24 AM

31 ? end communications to and from each endpoint device. Each device will be provided a primary pathway consisting of one or more pathway segments. For primary pathway segments and its associated control equipment. Pathway segments that service more than one device, additional redundant pathway segments provide alternate verified communication pathways to the devices must have at least one verified redundant pathway segment. Should any primary pathway segment fail, communication is supported by the redundant pathway segments. Should segment(s.) Failure of either a primary or redundant pathway segment fail, trouble will be indicated by virtue of the continuous verification of all primary and redundant pathway segments. The redundant will indicate a trouble. Redundant pathway segments are generally independent and do not normally share media with the primary pathways. However, there are exceptions, such as different frequencies for wireless components, or ring topologies. [See Figure A (5).] There is an opportunity to enhance the robustness of a A Class N network by providing may be made more reliable with physically distinct pathway segments (i.e., an alternate conduit, or cable tray route, or wireless transmission frequency range, or a combination of distinct media). It is also permissible to provide other nondesignated pathway segments. Additional pathway segments in excess of the minimum requirements of Class N increase the overall robustness of the network and are often desirable. However, since these additional pathway segments exceed the minimum equipment standards, there is no intention to create an additional monitoring burden, so verification of these pathways is optional.for Class N, where a conductor-based media is used, it is not the intention to monitor faults on individual conductors but rather to monitor the operational capability and performance of the pathway as a whole. Unlike Class C, where multiple pathways are not required, for Class N some pathway segments that carry communications for multiple devices (such as Ethernet uplinks or backbones) will have redundant pathway segments present. The intention is that any one pathway segment can fail without a loss in operational capability to more than one device. For example, connections to control equipment (fire alarm control units, ACUs, or ECCUs), where any interruption in communications could potentially affect all devices, would have redundant pathway segments. Additionally, backbone and uplink pathway segments that support communications for more than one device and are positioned between transmission equipment would also have a redundant pathway segment. But the requirement for redundant pathway segments does not apply to those pathway segments used to service a single device [see In addition to the required primary segments and redundant segments, a Class N pathway is permitted to have nonrequired segments. [See Figure A (1)(a-2).] Additional nonrequired pathway segments are allowed to be connected and not independently monitored for integrity as long as two paths are monitored to meet the redundancy requirement of Class N. Figure A (1)(a) ] Class N Pathway Block Diagram. The term devices is used generically in this section to refer to endpoint devices, which include the following: With respect to Class N, the term device refers to an intelligent, addressable device that performs a programmable input or output function. Examples of Class N devices include: Input components such as alarm initiating modules switches and sensors, sensors (1) Output components such as output modules, Ethernet speakers (i.e., IEEE 802.3af PoE speakers), intelligent strobes, textual signage, and intelligent audio amplifiers. Transmission equipment components (e.g., media converters, Ethernet switches, patch panels, cross 54 of 346 5/19/ :24 AM

32 -? connects) are connected to the Class N pathway merely to transport instructions between other equipment. As such, they are not considered devices with respect to Class N pathways. The The audio amplifier example is included to explain a type of listed above is an example of an addressable device that can receive a digital audio input from the Class N pathway but and then provide a notification appliance circuit (NAC) output to support with Class A, B, or X speaker connections pathways. Other similar devices are also possible to provide alternate class pathway connections endpoint devices may similarly provide alternate Class pathways for strobes (NACs) or initiating devices (IDCs). From the perspective of the Class N pathway, communications terminates at this is considered an endpoint device. However, since these types of endpoints can support multiple notification appliance devices or initiating devices, they are subject to the redundant pathway segment requirement and are provided with dual pathway connections. Control equipment connected to a Class N network for communications with devices would generally utilize redundant pathway segments. Control equipment connected to other control equipment on a Class N network would utilize redundant pathway segments if the control equipment was dependent on any of the pathway segments so that Class N connections between control equipment are required to have redundant monitored pathway segments if a failure of a primary pathway segment in between control equipment could impair the operation of the control equipment [see Figure A (1)(b) ]. Another utilization of endpoints is permitted for devices providing two connection ports and supporting dual pathway segment connections. The description of endpoint devices is not intended to exclude devices that support dual pathway connections. Since these pathways are servicing a single device, only a single primary pathway connection is required. The second pathway connection exceeds minimum equipment standards and is therefore not required to be verified as a redundant pathway segment; it can be considered connected to a nondesignated pathway segment Figure A (1)(b) Class N Pathway Block Diagram with Multiple Control Units. Class N is also permitted to include dual port devices that provide both transmission and input/output functions. Endpoint devices may have multiple connection ports and support dual pathway segment connections; thus the term endpoint device is not intended to prohibit more than one connection to a device. Even with dual connections, where other devices depend on the path, primary and redundant paths are required. But, where an endpoint device has two connection ports, and when a secondary nonrequired connection is added, there is no requirement to separately supervise the nonrequired pathway segment [see Figure A (1)(c) ]. Figure A (1)(a) Class N Pathway Block Diagram. 55 of 346 5/19/ :24 AM

33 56 of 346 5/19/ :24 AM Figure A (1)(b) Class N Pathway Block Diagram with Multiple Control Units. Figure A (1)( c) Class N Pathway Block Diagram with Device with Dual Pathway Connection.

34 57 of 346 5/19/ :24 AM Additional Proposed Changes Final_Class_N_Pathway_Block_Diagrams_1.png File Name Description Approved Figure A (1)(a-1) & Figure A (1)(a-2) Figure Final_Class_N_Pathway_Block_Diagram_with_Multiple_Control_Units_1.png A (1)(b) Final_Class_N_Pathway_Block_Diagram_with_Device_with_Dual_Pathway_Connection_1.png Figure A (1)(c) Final_A12.3.6_1_with_drawings.docx Statement of Problem and Substantiation for Public Comment Complete text and drawings for A12.3.6(1) in word format Editorial and organizational changes for improved readability and clarity. Drawing were changed to make the style more similar to Annex F. Added examples of a comparison between Class N and Class X and Class C. Also added a clarification that class N is not required for supplemental reporting.the proposal is the recommendation by the Correlating Committee Task Group members that was comprised of TC members from Chapters 10, 14, 23, 24 and 26 as well as individuals outside of the committees. Wayne Moore A.J. Capowski Joe L. Collins Dan Horon Vic Humm Michael Pallett Charles Pugh Robert Schifiliti Aviv Siegel Larry Shudak

35 58 of 346 5/19/ :24 AM Bob Elliott Paul Crowley Jeff Silveira Jeff Knight Andrew Berezowski Related Item Public Input No. 290-NFPA [New Section after A ] Submitter Information Verification This PC has not been submitted yet

36 A (1) The Class N pathway designation is added to specifically address the use of modern network infrastructure when used in fire alarm and emergency communication systems. Ethernet network devices are addressable, but with an important distinction from device addresses on a traditional SLC multi-drop loop. A device with an Ethernet address is, in most cases, a physical endpoint connected to a dedicated cable. Traditional SLC devices are all wired on the same communication line (in parallel) similar to an old party-line telephone system. By comparison, Ethernet s network switches direct each data packet to its intended recipient device like our modern phone systems. A fundamental technical difference of Class N from Class A, B or X is that it has no requirement to report a connection to ground unless the ground impairs the path. A practical concern, where using Ethernet, is that it is reliable and secure, especially when life safety systems share the same pathways. See Class N Shared Pathways. As a visual model, Class N could be likened to a Class X [backbone], allowed to have Class C branch paths to single endpoint devices. Therefore, every effort is made in this section to clearly distinguish the single endpoint device from the transport equipment required to have redundant paths, like Class X. Class N requires, redundant, monitored pathway segments to and from control equipment (fire alarm control units, ACUs, or ECCUs), where any interruption in communications could potentially affect multiple endpoint devices. Typically, interconnected communications equipment such as Ethernet switches, wireless repeaters, or media converters are used in combination to create pathways. Chapter 12 describes the required behavior of Class N pathways. All equipment must meet the requirements of other chapters in NFPA 72. Redundant pathways, isolated from ground, are actually common practice in robust Ethernet designs. Managed network switches commonly have specific uplink ports that are intended for load sharing and allow two parallel connections. For compliance with Class N, a trouble must be reported if either of these connections fails. [See Figure A (1)(a-1).] Class N networks may be specified for ancillary functions, but are not required for supplemental reporting described in [See Figure A ] Class N pathways may use metallic conductor communications cable, such as a 100 ohm balanced twisted pair (e.g., Category 5E), including single pair or multi pair cable, or other communications media such as optical fiber cable or wireless transmission, or a combination of two or more such transport mediums. Where a conductor based media is used for Class N, the intention is not to monitor faults on individual conductors, but rather to monitor the operational capability and performance of the pathway as a whole. Similar to Class C, end to end verification is used in Class N. Primary and required redundant pathways are independently and continuously verified for their ability to support end to end communications to and from each endpoint device and its associated control equipment. Pathway segments that service more than one device, must have at least one verified redundant pathway segment. Should any primary pathway segment fail, communication is supported by

37 Switch 2 Switch 1 the redundant pathway segment(s.) Failure of either a primary or redundant pathway will indicate a trouble. FACU, ACU, or ECCU Figure A (1)(b) FACU, ACU, or ECCU Redundant pathway segments are generally independent and do not normally share media with the (1) primary pathways. However, there are exceptions, such as different frequencies for wireless components, or ring topologies. [See Figure A (5).] A Class N network may be made more reliable with physically distinct pathway segments (i.e., an alternate conduit, or cable tray route, or wireless transmission frequency range, or a combination of distinct media). In addition to the required primary segments and redundant segments, a Class N (2) pathway is permitted to have nonrequired Switch segments. FACU, [See Figure A (1)(a-2).] Additional 3 ACU, or nonrequired pathway segments are allowed to be connected and not independently monitored for ECCU integrity as long as two paths are monitored to meet the redundancy requirement of Class N. Figure A (1)(a) Class N Pathway Block Diagrams. (3) 20 Feet maximum inside enclosure or raceway FACU, ACU, or ECCU Switch Switch 1 2 A redundant cable between two switches must have special functionality in order to monitor integrity when a secondary path is not in use. Figure A (1)(a-1) Endpoint Devices 20 Feet maximum inside enclosure or raceway FACU, ACU, or ECCU Switch Switch 1 2 Nonrequired redundant path segment Endpoint Devices Group H Switch Switch 4 3 Figure A (1)(a-2) Endpoint Devices Group K Endpoint Devices Group J

38 With respect to Class N, the term device refers to an intelligent, addressable device that performs a programmable input or output function. Examples of Class N devices include: (1) Input components such as alarm initiating modules switches and sensors, (2) Output components such as output modules, Ethernet speakers (i.e., IEEE 802.3af PoE speakers), intelligent strobes, textual signage, and intelligent audio amplifiers. Transmission equipment components (e.g., media converters, Ethernet switches, patch panels, crossconnects) are connected to the Class N pathway merely to transport instructions between other equipment. As such, they are not considered devices with respect to Class N pathways. The audio amplifier listed above is an example of an addressable device that can receive a digital audio input from the Class N pathway and then provide a notification appliance circuit (NAC) output with Class A, B, or X pathways. Other endpoint devices may similarly provide alternate Class pathways for strobes (NACs) or initiating devices (IDCs). From the perspective of the Class N pathway, communications terminates at this endpoint device. However, since these types of endpoints can support multiple notification appliance devices or initiating devices, they are subject to the redundant pathway requirement. Class N connections between control equipment are required to have redundant monitored pathway segments if a failure of a primary pathway segment in between control equipment could impair the operation of the control equipment [see Figure A (1)(b) ]. Figure A (1)(b) Class N Pathway Block Diagram with Multiple Control Units. Switch 1 FACU, ACU, or ECCU (1) FACU, ACU, or ECCU Switch 2 (2) Switch 3 FACU, ACU, or ECCU Figure A (1)(b) (3)

39 Class N is also permitted to include dual port devices that provide both transmission and input/output functions. Endpoint devices may have multiple connection ports and support dual pathway segment connections; thus the term endpoint device is not intended to prohibit more than one connection to a device. Even with dual connections, where other devices depend on the path, primary and redundant paths are required. But, where an endpoint device has two connection ports, and when a secondary nonrequired connection is added, there is no requirement to separately supervise the nonrequired redundant pathway segment [see Figure A (1)(c)]. Figure A (1)(c) Class N Pathway Block Diagram with Device with Dual Pathway Connection. To FACU Switch Endpoint Devices A nonrequired redundant cable to an endpoint device is permitted, and does not require separate supervision. Figure A (1)(c)

40

41

42

43 83 of 346 5/19/ :24 AM Public Comment No. 196-NFPA [ Section No. A (1) ]

44 84 of 346 5/19/ :24 AM A (1)

45 85 of 346 5/19/ :24 AM Class N consists of pathways between control equipment and devices. The pathways comprise metallic conductor communications cable, such as a 100 ohm balanced twisted-pair (e.g., Category 5E), including single-pair or multi-pair cable, or other communications media such as optical fiber cable or wireless transmission, or a combination of two or more of these. Pathways consist of uninterrupted communications media between control equipment and an endpoint device or of a network of multiple interconnected communications media pathway segments connecting multiple devices. Media pathway segments are created by the use of transmission equipment such as Ethernet switches, wireless repeaters, or media converters that interrupt an otherwise continuous pathway. Requirements for Class N pathway transmission equipment are not covered in Chapter 12 but by other chapters in NFPA 72. Addi onal informa on concerning cabling and cabling infrastructure for Class N systems can be found in standards, such as ANSI/BICI 005, Electronic Safety and Security (ESS) System Design and Implementa on Best Prac ces. A network of pathway segments is also described as primary pathway segments, redundant pathway segments, or nondesignated pathway segments. Primary and redundant pathways, from control equipment to each device, are independently and continuously verified for their ability to support end-to-end communications to and from each endpoint device. Each device will be provided a primary pathway consisting of one or more pathway segments. For primary pathway segments that service more than one device, additional redundant pathway segments provide alternate verified communication pathways to the devices. Should any primary pathway segment fail, communication is supported by the redundant pathway segments. Should either a primary or redundant pathway segment fail, trouble will be indicated by virtue of the continuous verification of all primary and redundant pathway segments. The redundant pathway segments are generally independent and do not normally share media with the primary pathways. However, there are exceptions, such as different frequencies for wireless or ring topologies. [See A (5).] There is an opportunity to enhance the robustness of a Class N network by providing physically distinct pathway segments (i.e., an alternate conduit, or cable tray route, or wireless transmission frequency range, or a combination of distinct media). It is also permissible to provide other nondesignated pathway segments. Additional pathway segments in excess of the minimum requirements of Class N increase the overall robustness of the network and are often desirable. However, since these additional pathway segments exceed the minimum equipment standards, there is no intention to create an additional monitoring burden, so verification of these pathways is optional. For Class N, where a conductor-based media is used, it is not the intention to monitor faults on individual conductors but rather to monitor the operational capability and performance of the pathway as a whole. Unlike Class C, where multiple pathways are not required, for Class N some pathway segments that carry communications for multiple devices (such as Ethernet uplinks or backbones) will have redundant pathway segments present. The intention is that any one pathway segment can fail without a loss in operational capability to more than one device. For example, connections to control equipment (fire alarm control units, ACUs, or ECCUs), where any interruption in communications could potentially affect all devices, would have redundant pathway segments. Additionally, backbone and uplink pathway segments that support communications for more than one device and are positioned between transmission equipment would also have a redundant pathway segment. But the requirement for redundant pathway segments does not apply to those pathway segments used to service a single device [see Figure A (1)(a)]. The term devices is used generically in this section to refer to endpoint devices, which include the following: (1) Input components such as alarm initiating switches, sensors (2) Output components such as Ethernet speakers (i.e., IEEE 802.3af PoE speakers), strobes, textual signage, audio amplifiers Transmission equipment (e.g., media converters, Ethernet switches, patch panels, cross-connects) are not considered devices with respect to Class N pathways. The audio amplifier example is included to explain a type of addressable device that can receive a digital audio input from the Class N pathway but provide a notification appliance circuit (NAC) output to support Class A, B, or X speaker connections. Other similar devices are also possible to provide alternate class pathway connections for strobes (NACs) or initiating devices (IDCs). From the perspective of the Class N pathway, this is considered an endpoint device. However, since these types of endpoints can support multiple notification appliance devices or initiating devices, they are subject to the redundant pathway segment requirement and are provided with dual pathway connections. Control equipment connected to a Class N network for communications with devices would generally utilize redundant pathway segments. Control equipment connected to other control equipment on a Class N network would utilize redundant pathway segments if the control equipment was dependent on any of the

46 86 of 346 5/19/ :24 AM pathway segments so that a failure of a primary pathway segment in between control equipment could impair the operation of the control equipment [see Figure A (1)(b)]. Another utilization of endpoints is permitted for devices providing two connection ports and supporting dual pathway segment connections. The description of endpoint devices is not intended to exclude devices that support dual pathway connections. Since these pathways are servicing a single device, only a single primary pathway connection is required. The second pathway connection exceeds minimum equipment standards and is therefore not required to be verified as a redundant pathway segment; it can be considered connected to a nondesignated pathway segment [see Figure A (1)(c)]. Figure A (1)(a) Class N Pathway Block Diagram. Figure A (1)(b) Class N Pathway Block Diagram with Multiple Control Units. Figure A (1)(c) Class N Pathway Block Diagram with Device with Dual Pathway Connection.

47 87 of 346 5/19/ :24 AM Statement of Problem and Substantiation for Public Comment This will provide an avenue for those wanting more information about the networking base of Class N without the need of creating additional Appendix material down the road. This Public Comment was submitted on behalf of Jeff Silveira of BICSI. Related Public Comments for This Document Related Comment Public Comment No. 174-NFPA [Section No. A (1)] Related Item Public Input No. 290-NFPA [New Section after A ] Relationship Class N Annex Material Submitter Information Verification Submitter Full Name: Michael Pallett Organization: Telecor Inc. Street Address: City: State: Zip: Submittal Date: Thu May 15 22:29:49 EDT 2014

48 88 of 346 5/19/ :24 AM Public Comment No. 197-NFPA [ Section No. A (1) ]

49 89 of 346 5/19/ :24 AM A (1)

50 90 of 346 5/19/ :24 AM Class N consists of pathways between control equipment and devices. The pathways comprise metallic conductor communications cable, such as a 100 ohm balanced twisted-pair (e.g., Category 5E), including single-pair or multi-pair cable, or other communications media such as optical fiber cable or wireless transmission, or a combination of two or more of these. Pathways consist of uninterrupted communications media between control equipment and an endpoint device or of a network of multiple interconnected communications media pathway segments connecting multiple devices. Media pathway segments are created by the use of transmission equipment such as Ethernet switches, wireless repeaters, or media converters that interrupt an otherwise continuous pathway. Requirements for Class N pathway transmission equipment are not covered in Chapter 12 but by other chapters in NFPA 72. A network of pathway segments is also described as primary pathway segments, redundant pathway segments, or nondesignated pathway segments. Primary and redundant pathways, from control equipment to each device, are independently and continuously verified for their ability to support end-to-end communications to and from each endpoint device. Each device will be provided a primary pathway consisting of one or more pathway segments. For primary pathway segments that service more than one device, additional redundant pathway segments provide alternate verified communication pathways to the devices. Should any primary pathway segment fail, communication is supported by the redundant pathway segments. Should either a primary or redundant pathway segment fail, trouble will be indicated by virtue of the continuous verification of all primary and redundant pathway segments. The redundant pathway segments are generally independent and do not normally share media with the primary pathways. However, there are exceptions, such as different frequencies for wireless or ring topologies. [See A (5).] There is an opportunity to enhance the robustness of a Class N network by providing physically distinct pathway segments (i.e., an alternate conduit, or cable tray route, or wireless transmission frequency range, or a combination of distinct media). It is also permissible to provide other nondesignated pathway segments. Additional pathway segments in excess of the minimum requirements of Class N increase the overall robustness of the network and are often desirable. However, since these additional pathway segments exceed the minimum equipment standards, there is no intention to create an additional monitoring burden, so verification of these pathways is optional. For Class N, where a conductor-based media is used, it is not the intention to monitor faults on individual conductors but rather to monitor the operational capability and performance of the pathway as a whole. Unlike Class C, where multiple pathways are not required, for Class N some pathway segments that carry communications for multiple devices (such as Ethernet uplinks or backbones) will have redundant pathway segments present. The intention is that any one pathway segment can fail without a loss in operational capability to more than one device. For example, connections to control equipment (fire alarm control units, ACUs, or ECCUs), where any interruption in communications could potentially affect all devices, would have redundant pathway segments. Additionally, backbone and uplink pathway segments that support communications for more than one device and are positioned between transmission equipment would also have a redundant pathway segment. But the requirement for redundant pathway segments does not apply to those pathway segments used to service a single device [see Figure A (1)(a)]. The term devices is used generically in this section to refer to endpoint devices, which include the following: Commonly, NFPA has used the word device for input components, and term appliance for components used in notification. With respect to Class N, the term device includes appliances and other intelligent, addressable components that perform a programmable input or output function. Examples of Class N devices include: (1) Input components such as alarm initiating switches, sensors (2) Output components such as Ethernet speakers (i.e., IEEE 802.3af PoE speakers), strobes, textual signage, audio amplifiers Transmission equipment (e.g., media converters, Ethernet switches, patch panels, cross-connects) are not considered devices with respect to Class N pathways. The audio amplifier example is included to explain a type of addressable device that can receive a digital audio input from the Class N pathway but provide a notification appliance circuit (NAC) output to support Class A, B, or X speaker connections. Other similar devices are also possible to provide alternate class pathway connections for strobes (NACs) or initiating devices (IDCs). From the perspective of the Class N pathway, this is considered an endpoint device. However, since these types of endpoints can support multiple notification appliance devices or initiating devices, they are subject to the redundant pathway segment requirement and are provided with dual pathway connections. Control equipment connected to a Class N network for communications with devices would generally utilize

51 91 of 346 5/19/ :24 AM redundant pathway segments. Control equipment connected to other control equipment on a Class N network would utilize redundant pathway segments if the control equipment was dependent on any of the pathway segments so that a failure of a primary pathway segment in between control equipment could impair the operation of the control equipment [see Figure A (1)(b)]. Another utilization of endpoints is permitted for devices providing two connection ports and supporting dual pathway segment connections. The description of endpoint devices is not intended to exclude devices that support dual pathway connections. Since these pathways are servicing a single device, only a single primary pathway connection is required. The second pathway connection exceeds minimum equipment standards and is therefore not required to be verified as a redundant pathway segment; it can be considered connected to a nondesignated pathway segment [see Figure A (1)(c)]. Figure A (1)(a) Class N Pathway Block Diagram. Figure A (1)(b) Class N Pathway Block Diagram with Multiple Control Units. Figure A (1)(c) Class N Pathway Block Diagram with Device with Dual Pathway Connection.

52 92 of 346 5/19/ :24 AM Statement of Problem and Substantiation for Public Comment This proposal was submitted after an discussion by the Class N Correlating Committee Task Group members that was comprised of TC members from Chapters 10, 14, 23, 24 and 26 as well as individuals outside of the committees. There was no consensus reached on this proposal. Some suggested that unofficially, we have trended over the past 25 years to use device on the input side and appliance on the output side. Thus, initiating devices and notification appliances. And while this is true, it does not address the very many examples that can be found when the word "device" is used in some other context, including the context where both initiating devices and notification appliances are meant at the same time. In the code we already refer to UPS s as devices, radio transmitters as devices, circuit breaker locks as devices, overcurrent protection devices, emergency control interface devices, light output for signaling devices for hearing impaired, power supervisory devices, and generally fire alarm devices connected to fire alarm circuits. We also refer to devices for testing and maintenance requirements which is not limited to initiating devices only. There are also requirements for power supplied to devices over an SLC that are intended to cover both addressable initiating devices and notification appliances although the code only references these as devices. So there is no rule that devices always means initiating devices but if we want to state that traditionally or commonly the term is associated with initiating device it may be misleading and doing a disservice to generalize something that is not really true to people to who have not been deeply engaged with the code for many years. Related Public Comments for This Document Related Comment Public Comment No. 174-NFPA [Section No. A (1)] Public Comment No. 196-NFPA [Section No. A (1)] Related Item Public Input No. 290-NFPA [New Section after A ] Relationship Class N Annex Material Class N Annex Material Submitter Information Verification Submitter Full Name: Michael Pallett Organization: Telecor Inc. Street Address: City:

53 93 of 346 5/19/ :24 AM State: Zip: Submittal Date: Thu May 15 22:38:29 EDT 2014

54 75 of 346 5/19/ :24 AM Public Comment No. 191-NFPA [ Section No. A (4) ] A (4) The operational conditions of the pathway include factors such as latency, throughput, response time, arrival rate, utilization, bandwidth, and loss. It is intended that the life safety equipment connected to a Class N network actively monitor some or all of the pathway s operational conditions, so that an improperly installed or configured pathway, or a subsequently degraded pathway or network of pathway segments is detected by the life safety equipment and reported as a trouble. This monitoring is intended to be continuous so that a degradation of pathway performance over time is detected and reported. Trouble would be reported when operational conditions of the pathway(s) have deteriorated to the point where the equipment is no longer capable of meeting its minimum performance requirements, even if some level of communication to endpoint devices is still maintained. Examples of performance requirements include the activation of an alarm within 10 seconds, the reporting of a trouble signal within 200 seconds, synchronization of strobes, and delivery of audio messages with required intelligibility. It is possible to have a pathway where end-to-end communications are operational under system idle conditions, but in the event of an alarm, the increased load on a degraded pathway could cause a partial or complete failure to deliver required life safety signals. This is the situation that is intended to be actively detected and reported. Statement of Problem and Substantiation for Public Comment Editorial and organizational changes for improved readability and clarity. The proposal is the recommendation by the Correlating Committee Task Group members that was comprised of TC members from Chapters 10, 14, 23, 24 and 26 as well as individuals outside of the committees. Wayne Moore A.J. Capowski Joe L. Collins Dan Horon Vic Humm Michael Pallett Charles Pugh Robert Schifiliti Aviv Siegel Larry Shudak Bob Elliott Paul Crowley Jeff Silveira Jeff Knight Andrew Berezowski Related Public Comments for This Document Related Comment Public Comment No. 174-NFPA [Section No. A (1)] Related Item First Revision No. 103-NFPA [Global Input] Relationship Class N Annex material Submitter Information Verification Submitter Full Name: Michael Pallett Organization: Telecor Inc. Street Address: City:

55 76 of 346 5/19/ :24 AM State: Zip: Submittal Date: Thu May 15 18:08:06 EDT 2014

56 78 of 346 5/19/ :24 AM Public Comment No. 193-NFPA [ Section No. A (5) ]

57 79 of 346 5/19/ :24 AM A (5) Devices with dual path connections are permitted to be connected to create in a daisy? chain of devices on a ring. In this circumstance they cannot be considered endpoint devices because each pathway segment supports multiple devices; therefore Again, where Class N pathway segments support multiple devices, verified redundant pathway segments would be necessary segment(s) are required. This can be accomplished with a ring topology, as long as each segment of the ring is verified as functional, and the failure of any one segment does not result in the loss of functionality of more than one device. In this circumstance the requirements for Class N are satisfied by allowing the arrangement, primary and redundant pathway segments to share the same media by providing, and provide two possible directions of communications on in a ring topology [see Figure A (5) ]. This configuration is fully compliant with (5).The daisy daisy? chain configuration is also a permissible connection method for permitted between multiple control units that require verified primary and redundant pathway segments. Figure A Figure A (5) Class Class N Pathway Block Diagram with Dais Daisy Chained Devices with Dual Pathway Connection. Additional Proposed Changes

58 80 of 346 5/19/ :24 AM File Name Description Ap Final_Class_N_Pathway_Block_Diagram_with_Daisy_Chained_Devices_with_Dual_Pathway_Connection.png Figure a (5) Statement of Problem and Substantiation for Public Comment Editorial and organizational changes for improved readability and clarity. Drawing were changed to make the style more similar to Annex F. The proposal is the recommendation by the Correlating Committee Task Group members that was comprised of TC members from Chapters 10, 14, 23, 24 and 26 as well as individuals outside of the committees. Wayne Moore A.J. Capowski Joe L. Collins Dan Horon Vic Humm Michael Pallett Charles Pugh Robert Schifiliti Aviv Siegel Larry Shudak Bob Elliott Paul Crowley Jeff Silveira Jeff Knight Andrew Berezowski Related Public Comments for This Document Related Comment Public Comment No. 174-NFPA [Section No. A (1)] Public Comment No. 191-NFPA [Section No. A (4)] Related Item First Revision No. 103-NFPA [Global Input] Relationship Class N Annex Material Class N Annex Material Submitter Information Verification Submitter Full Name: Michael Pallett Organization: Telecor Inc. Street Address: City: State: Zip: Submittal Date: Thu May 15 21:41:54 EDT 2014

59 0 of 346 5/19/ :24 AM Public Comment No. 17-NFPA [ New Section after ] Where fire alarm control units are interconnected by an auxiliary alarm, supervisory, or trouble relay that uses clip-on or slide-on type terminals, the circuit shall be configured to provide supervision of the terminals so that their detachment from the auxiliary relay will result in a trouble indication at the master fire alarm control unit. EW CONTENT Type your content here... Additional Proposed Changes File Name Description Approved NFPA_571.pdf Clip-on terminal strip Statement of Problem and Substantiation for Public Comment Statement of Problem and Substantiation for Public Input Several fire alarm panel manufacturers utilize "slip-on" or "clip-on" terminal strips for ease of maintenance. When this type terminal strip is used on output contacts for circuits supervised by another panel, the terminal strip can be removed without generating a signal. If the terminal strip is removed to facilitate service, it could be accidentally left off and prevent the transmission of signals. Related Item Public Input No. 571-NFPA [New Section after ] Submitter Information Verification Submitter Full Name: Herbert Hurst Organization: Savannah River Nuclear Solutio Street Address: City: State: Zip: Submittal Date: Wed Mar 19 13:30:10 EDT 2014

60 To Master Fire Alarm Control Unit from Dedicated Function Fire Alarm Control Unit. Slip-on type terminal Strip TBX may be removed from circuit board with end-of line resistors in place. Although circuit is lifted the wiring configuration will not result in a trouble indication at the Master FACU. TBX TBX

61 0 of 346 5/19/ :24 AM Public Comment No. 60-NFPA [ Section No ] 21.1* Application. The provisions of Chapter 21 shall cover the minimum requirements and methods for emergency control function interfaces to fire alarm systems and emergency communications systems in accordance with this chapter The requirements of Chapters 7, 10, 17, 18, 23, 24, and 26 shall apply, unless they are in conflict with this chapter The requirements of Chapter 14 shall apply The requirements of this chapter shall not apply to Chapter 29 unless otherwise stated. Statement of Problem and Substantiation for Public Comment CC NOTE: The following CC Note No. 8 appeared in the First Draft Report as First Revision No. 222, and is also related to Public Input No The correlating committee makes reference to and the phrase ", unless they are in conflict with this chapter." Requirements should not conflict. Where deviations from the requirements of other chapters are warranted they should be identified and addressed through appropriate allowances in the code language. The correlating committee directs the SIG-PRO committee to review the requirements in Chapter 21 with consideration to resolving any identified conflicts with other chapters. Where changes are made they should be done without introducing new material in the second draft phase. In addition the committee should consider rewording to positive language. For example: The requirements of chapters x, y and z shall apply unless otherwise noted in this chapter. Related Item First Revision No. 222-NFPA [Section No. 21.1] Public Input No. 566-NFPA [Section No. 21.1] Submitter Information Verification Submitter Full Name: CC on SIG-AAC Organization: CC on Signaling Systems for the Protection of Life and Property Street Address: City: State: Zip: Submittal Date: Wed Apr 30 09:26:22 EDT 2014

62 5 of 346 5/19/ :24 AM Public Comment No. 28-NFPA [ Section No. A.21.1 ] A.21.1 Fire alarm systems, signaling systems, and emergency communications systems are often part of a large, integrated system serving a building or area. Figure A.21.1 shows examples of individual systems that might be part of an integrated system. A fire alarm system might monitor the status of one of the other individual systems or provide a form of output to control another individual system, such as a smoke control system or an elevator controller. In some cases, the fire alarm system shares information and control in two directions with another individual system. NFPA 72 covers only the fire alarm or signaling system in the circuits powered by it, not any part of the other individual systems. See NFPA 3 and NFPA 4 for additional information on integrated systems. Figure A.21.1 Integrated Systems. Statement of Problem and Substantiation for Public Comment NFPA 3 also addresses intergrated systems. Related Item First Revision No. 222-NFPA [Section No. 21.1] Submitter Information Verification Submitter Full Name: Kelly Nicolello Organization: Western Regional Fire Code Dev Street Address: City: State: Zip: Submittal Date: Tue Apr 01 18:29:00 EDT 2014

Agenda Technical Committee on Protected Premises Fire Alarm Systems September 9-11, 2013 Saint Louis, MO

Agenda Technical Committee on Protected Premises Fire Alarm Systems September 9-11, 2013 Saint Louis, MO Agenda Technical Committee on Protected Premises Fire Alarm Systems September 9-11, 2013 Saint Louis, MO Item No. Subject 13-9-1 Call to Order (8:00 A.M) 13-9-2 Roll Call 13-9-3 Approval of Agenda 13-9-4

More information

Using Ethernet and Networks for Fire Alarm and Emergency Communications Systems

Using Ethernet and Networks for Fire Alarm and Emergency Communications Systems Using Ethernet and Networks for Fire Alarm and Emergency Communications Systems Speeding into the 21 st century? Or Not? Wayne D. Moore, P.E., CFPS, SET Hughes Associates, Inc. 117 Metro Center Boulevard,

More information

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN Mr. Merton Bunker, Committee Chair, called the meeting to order at 8:05 on Wednesday September

More information

Page 1 of 40 First Correlating Revision No. 15-NFPA 72-2014 [ Global Input ] 10.5.4 Plans Examiners and Inspectors. 10.5.4.1 Fire alarm system and emergency communications system plans and specifications

More information

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Protected Premises Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Protected Premises Fire Alarm

More information

Call to Order Chair Jack Poole called the meeting to order at 8:00 AM on Monday, July 17, 2017.

Call to Order Chair Jack Poole called the meeting to order at 8:00 AM on Monday, July 17, 2017. NFPA 72 SIG-PRO Meeting Minutes NFPA Technical Committee on Protected Premises Fire Alarm Systems (SIG-PRO) Second Draft Meeting, July 17 19, 2017 Charlotte, North Carolina 17-7-1 Call to Order Chair Jack

More information

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

First Revision No. 158-NFPA [ Global Input ] Submitter Information Verification. Committee Statement of 326 11/21/2013 1:03 PM First Revision No. 158-NFPA 72-2013 [ Global Input ] Revise 2.3.1 to update UL 864 to "2003, revised 2012" and upate ANSI/ASME A17 to 2013. Submittal Date: Wed Sep 11 11:08:52

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Protected Premises

More information

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO Item No. Subject 13-6-1 Call to Order (8:00 A.M) 13-6-2 Roll Call 13-6-3 Approval

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Manuelita David (SIG-FUN), Jensen Hughes Warren Olsen (SIG-SSS), Fire Safety Consultants, Inc. Merton Bunker (SIG-AAC), EYP Architecture

More information

Agenda Technical Committee on Emergency Communications Systems June 24-25, 2014 La Jolla, CA

Agenda Technical Committee on Emergency Communications Systems June 24-25, 2014 La Jolla, CA Agenda Technical Committee on Emergency Communications Systems June 24-25, 2014 La Jolla, CA Item No. Subject 14-6-1 Call to Order (8:00 A.M) 14-6-2 Roll Call 14-6-3 Approval of Agenda 14-6-4 Approval

More information

NFPA Changes

NFPA Changes Chapter 12, Circuits and Pathways Summary. Chapter 12, Circuits and Pathways, is a new chapter. It brings together requirements that were formerly found in SIG-FUN, Fundamentals of Fire Alarm Systems regarding

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical on Fluidized Bed Boilers AGENDA Web/Teleconference 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of Members and Guests 3. Approval of Minutes from

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems

M E M O R A N D U M. Technical Committee on Supervising Station Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Supervising Station

More information

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: NFPA Correlating Committee on Signaling Systems for

More information

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Notification Appliances for

More information

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN) 4 of 326 11/21/2013 1:03 PM First Revision No. 161-NFPA 72-2013 [ Section No. 3.3.11 ] 3.3.11 Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

More information

First Revision No. 339-NFPA [ Section No. 2.2 ]

First Revision No. 339-NFPA [ Section No. 2.2 ] 8 of 326 11/21/2013 1:03 PM First Revision No. 339-NFPA 72-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 10, Standard

More information

26 of 128 9/23/2014 9:25 AM

26 of 128 9/23/2014 9:25 AM 26 of 128 9/23/2014 9:25 AM Second Revision No. 105-NFPA 72-2014 [ Global Comment ] Revise the Annex F figures that include a smoke detector symbol (hexagon with a whisp of smoke) so that the new smoke

More information

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems

MEMORANDUM. Technical Committee on Fundamentals of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Fundamentals of Fire Alarm

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Protected Premises

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Notification Appliances

More information

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016 TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES NFPA 610 First Draft Meeting October 17-18, 2016 Westin Kansas City at Crown Center 1 East Pershing Road Kansas City, MO, 64108 Conference Call Access:

More information

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement 10/20/ :03 AM

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement 10/20/ :03 AM of 496 10/20/2016 11:03 AM First Revision No. 2501-NFPA 72-2016 [ Global Input ] Any place in the body of Chapter 18 or its annex that the value 0.0375 lumens/ft 2 is used the metric equivalent shall be

More information

Proposed Changes to NFPA

Proposed Changes to NFPA 2017 NFPA Conference & Expo Proposed Changes to NFPA 72-2019 Presented by: Daniel O Connor (SIG-IDS), Jensen Hughes Robert Schifiliti (SIG-NAS), R.P. Schifiliti Associates William Koffel (SIG-ECS), Koffel

More information

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES Report on Comments

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM

First Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM 2 of 326 11/21/2013 1:03 PM First Revision No. 82-NFPA 72-2013 [ Section No. 2.3.4 ] 2.3.4 ISO Publications. International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56, CH-1211

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition

More information

Fire Alarm Wiring. Circuit types, styles and limitations

Fire Alarm Wiring. Circuit types, styles and limitations Fire Alarm Wiring Circuit types, styles and limitations What we will cover Types Classes Notification Appliance Circuits (NAC) Initiating Device Circuits (IDC) Signaling Line Circuits (SLC) Class A, B,

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

NFPA 101 SAF-RES PUBLIC COMMENTS

NFPA 101 SAF-RES PUBLIC COMMENTS Page 134 of 195 Public Comment No. 3-NFPA 101-2013 [ Section No. 28.7.6.1 ] 28.7.6.1 New draperies, curtains, and other similar loosely hanging furnishings and decorations shall be flame resistant as demonstrated

More information

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input of 201 1/13/2014 12:51 PM Public Input No. 88-NFPA 20-2013 [ New Section after 3.3.38.10 ] Add New Defination 3.3.28.11 Multiple Stage Multiple Port Pump. A single driver pump with multiple impellers operating

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Notification

More information

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018 Automatic FireAlarm Association SURVIVING SURVIVABILITY - A USER S GUIDE TO Larry D. Rietz, SET

More information

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fundamentals of Fire

More information

AGENDA TECHNICAL COMMITTEE ON CARBON MONOXIDE DETECTION OCTOBER 7, 2010 TELECONFERENCE (10:00 A.M. ET)

AGENDA TECHNICAL COMMITTEE ON CARBON MONOXIDE DETECTION OCTOBER 7, 2010 TELECONFERENCE (10:00 A.M. ET) AGENDA TECHNICAL COMMITTEE ON CARBON MONOXIDE DETECTION OCTOBER 7, 2010 TELECONFERENCE (10:00 A.M. ET) Item No. Subject 10-10-1 Call to Order (10:00 A.M.) 10-10-2 Roll Call 10-10-3 Staff Remarks 10-10-4

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing

More information

NFPA 79 - Second Draft Meeting July 8-10, DoubleTree Hotel, Portland, ME

NFPA 79 - Second Draft Meeting July 8-10, DoubleTree Hotel, Portland, ME National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NFPA TECHNICAL COMMITTEE ON ELECTRICAL EQUIPMENT OF INDUSTRIAL

More information

Page 1 of 198 Public Input No. 88-NFPA 20-2013 [ New Section after 3.3.38.10 ] Add New Defination 3.3.28.11 Multiple Stage Multiple Port Pump. A single driver pump with multiple impellers operating in

More information

Page 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,

More information

Chair Robert P. Schifiliti (R.P. Schifiliti Associates, Inc.) called the meeting to order at 8:00 AM ET. International Association of Fire Chiefs

Chair Robert P. Schifiliti (R.P. Schifiliti Associates, Inc.) called the meeting to order at 8:00 AM ET. International Association of Fire Chiefs Meeting Minutes of the Technical Correlating Committee on the Signaling Systems for the Protection of Life and Property September 21, 2010 (Indianapolis, IN) Item 10-9-1 Call to Order Chair Robert P. Schifiliti

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

Agenda Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems June 23-24, 2014 La Jolla, CA

Agenda Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems June 23-24, 2014 La Jolla, CA Agenda Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems June 23-24, 2014 La Jolla, CA Item No. Subject 14-6-1 Call to Order (8:00 A.M) 14-6-2 Roll Call 14-6-3 Approval

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

Technical Committee on Multiple Burner Boilers

Technical Committee on Multiple Burner Boilers Technical Committee on Multiple Burner Boilers AGENDA Salt River Project PERA Club 1 Continential Drive Tempe, AZ January 14-15, 2014 1. Chair s welcome, call to order, and opening remarks at 8:00 a.m.

More information

Public Comment No. 13-NFPA [ Section No ]

Public Comment No. 13-NFPA [ Section No ] Public Comment No. 13-NFPA 30-2013 [ Section No. 2.3.3 ] 2.3.3 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM A 395/A395M, Standard

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard

More information

Item Review Dates and Times for Future Meetings/Conference Calls

Item Review Dates and Times for Future Meetings/Conference Calls Agenda Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems (SIG-NAS) First Draft Meeting Salt Lake City, UT July 25-26, 2016 Item 16-7-1. Call to Order Item 16-7-2. Roll

More information

Technical Committee on Fluidized Bed Boilers

Technical Committee on Fluidized Bed Boilers Technical Committee on Fluidized Bed Boilers AGENDA NFPA Headquarters 1 Batterymarch Park Quincy, MA 02169 1. Chair s welcome, call to order, and opening remarks at 1:00 pm EST. 2. Self-Introduction of

More information

Public Comment No. 7-NFPA 30A-2013 [ Section No ]

Public Comment No. 7-NFPA 30A-2013 [ Section No ] Page 1 of 13 Public Comment No. 7-NFPA 30A-2013 [ Section No. 6.4.2 ] 6.4.2 Additional Proposed Changes Each pump shall have installed on the discharge side a listed leak detection device that will provide

More information

Print Specification. Publication. Instructions. Specific requirements. General requirements

Print Specification. Publication. Instructions. Specific requirements. General requirements Print Specification Publication GSA-CC1 Single Input Signal Module Installation Sheet P/N P-047550-1802-EN REV 04 ISS 23JUN15 Instructions This page is the print specification for the publication. It is

More information

Item Review Dates and Times for Future Meetings/Conference Calls

Item Review Dates and Times for Future Meetings/Conference Calls Agenda Technical Committee on Protected Premises Fire Alarm and Signaling Systems (SIG-PRO) First Draft Meeting Salt Lake City, UT July 25-27, 2016 Item 16-7-1. Call to Order Item 16-7-2. Roll Call and

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment NFPA 720 2015 Summary Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment TM, 7Oct14 CODE: Title, Standard, not Code Consistent with recent trend at NFPA, this document

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

Simplex ES Network. ES Net Network Applications, Communications, Options and Specifications. ES Net features. UL, ULC Listed*

Simplex ES Network. ES Net Network Applications, Communications, Options and Specifications. ES Net features. UL, ULC Listed* Simplex ES Network UL, ULC Listed* ES Net features ES Network (ES Net) is a high bandwidth (100 Mbps) IP based fire alarm network that supports up to 99 nodes and uses industry standard network technology

More information

M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014

M E M O R A N D U M. NFPA Technical Committee on Telecommunications. Elena Carroll, Administrator, Technical Projects. Date: July 8, 2014 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications

More information

Circulation Report for SIG-TMS Comments Document # 72

Circulation Report for SIG-TMS Comments Document # 72 1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15

More information

Page 1 of 190 Public Input No. 22-NFPA 55-2013 [ Global Input ] Throughout the document, delete ANSI from ANSI/ASME B31.3. Current Text: (multiple locations) ANSI/ASME B31.3 (found in Subsections: 2.3.2

More information

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

Correlating Committee on Automatic Sprinkler Systems

Correlating Committee on Automatic Sprinkler Systems Correlating Committee on Automatic Sprinkler Systems M E M O R A N D U M DATE: May 14, 2014 TO: FROM: Principal and Alternate Members of the Correlating Committee on Automatic Sprinkler Systems Matt Klaus,

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

SIGA-CC1 Single Input Signal Module Installation Sheet

SIGA-CC1 Single Input Signal Module Installation Sheet SIGA-CC1 Single Input Signal Module Installation Sheet Personality codes Use the personality codes described below to configure the SIGA-CC1 module. See Table 1 for listing information Table 1: Personality

More information

Unified Fire Authority - Fire Prevention Bureau

Unified Fire Authority - Fire Prevention Bureau Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

Technical Committee on Fundamentals of Combustion Systems Hazards

Technical Committee on Fundamentals of Combustion Systems Hazards Technical Committee on Fundamentals of Combustion Systems Hazards AGENDA Dec 4-6, 2013 Georgia Power Company Headquarters Banquet Room 241 Ralph McGill Blvd Atlanta, GA 1. Chair s welcome, call to order,

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 2 FROM: Kimberly Shea, Administrator,

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

Approval Meeting Minutes December 17, 2012 [Enclosure] Staff Remarks & Overview of New Process [Lee Richardson]

Approval Meeting Minutes December 17, 2012 [Enclosure] Staff Remarks & Overview of New Process [Lee Richardson] Agenda Correlating Committee on Signaling Systems for the Protection of Life and Property February 21, 2012 Teleconference (NFPA 72 Pre-First Draft Meeting) Item No. Subject 13-2-1 Call to Order (10:00

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the

More information

M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle)

M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Telecommunications

More information

Technical Committee on Mining Facilities First Draft Meeting - NFPA 120 and 122

Technical Committee on Mining Facilities First Draft Meeting - NFPA 120 and 122 Technical Committee on Mining Facilities First Draft Meeting - NFPA 120 and 122 Zurich Hosted 1400 America Lane Schaumburg, Illinois May 22 23, 2013 AGENDA 1. Chair Matt Bujewski calls meeting to order

More information

Second Correlating Revision No. 21-NFPA [ Global Input ]

Second Correlating Revision No. 21-NFPA [ Global Input ] Second Correlating Revision No. 21-NFPA 72-2017 [ Global Input ] Change "published manufacturer's instructions" and "manufacturer's instructions" to "manufacturer's published instructions" in accordance

More information

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Wayne D. Moore, P.E., CFPS, SET Vice President JENSEN HUGHES 117 Metro Center Boulevard, Suite 1002

More information

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification Public Comment No. 2-NFPA 73-2014 [ Section No. 4.1.3 ] 4.1.3 Unused Openings. 4.1.3.1 Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or

More information

Page 1 of 46 Public Input No. 17-NFPA 13E-2013 [ New Section after 3.2.4 ] New 3.2.5 Pressure-Reducing Valve. A valve designed for the purpose of reducing the downstream water pressure under both flowing

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems OPERATOR OPERATOR OR TROUBLE CONDITION: TO : FIRE PRIORITY 2SYSTEM SYSTEM SIGNALS POWER INDICATOR. SUPERVISORYTROUBLE SILENCED ON D. TO SILENCE SIGNALS: - PRESS " SILENCE". SUPV TBL SYSTEM ACK ACK ACK

More information

Report on First Revision November 2013 NFPA 731

Report on First Revision November 2013 NFPA 731 Report on First Revision November 2013 NFPA 731 731- Log #FR1 Final Action: (2.3.3) Submitter: Technical Committee Premises Security Recommendation: 2.3.3 UL Publications. Underwriters Laboratories Inc.,

More information

EOTec 2000 ControlNet Fiber Optic SHR/DSHR Communications Modules* With Support for Single and Dual Channel Self-Healing Rings

EOTec 2000 ControlNet Fiber Optic SHR/DSHR Communications Modules* With Support for Single and Dual Channel Self-Healing Rings EOTec 2000 ControlNet Fiber Optic SHR/DSHR Communications Modules* With Support for Single and Dual Channel Self-Healing Rings Key Features Single and Dual Channel Self Healing Rings for High Reliability

More information

TECHNICAL COMMITTEE ON FIRE PUMPS

TECHNICAL COMMITTEE ON FIRE PUMPS TECHNICAL COMMITTEE ON FIRE PUMPS MEMORANDUM TO: FROM: Technical Committee on Fire Pumps Joanne Goyette, on behalf of C. Duffy / R. P. Benedetti DATE: May 2, 2011 SUBJECT: Letter Ballot on Proposals to

More information

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic

More information

Innovative protection that combines power and flexibility

Innovative protection that combines power and flexibility Innovative protection that combines power and flexibility Desigo Fire Safety Modular outpaces industry standards and includes cutting-edge detection and communication capabilities usa.siemens.com/desigo-fs-modular

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single- and

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

SC-6 Six Supervised Control Module

SC-6 Six Supervised Control Module INSTALLATION AND MAINTENANCE INSTRUCTIONS SC-6 Six Supervised Control Module SPECIFICATIONS Normal Operating Voltage: Stand-By Current: Alarm Current: Temperature Range: Humidity: Dimensions: Accessories:

More information

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION Fike s CyberCat 254 (P/N 10-066) is a state-of-the-art true intelligent digital peer-to-peer modular fire alarm control system.

More information