Manual. MJK Data Transmitter 795. Station ID: 795 Type: 795 Serial no:

Size: px
Start display at page:

Download "Manual. MJK Data Transmitter 795. Station ID: 795 Type: 795 Serial no:"

Transcription

1 Manual MJK Data Transmitter 795 Valid from software version COMLI PROTOCOL MJK Automation A/S Byageren 7 DK-2850 Nærum Denmark Tel: Fax: Station ID: 795 Type: 795 Serial no: As our products are developed continuously, we reserve the right to make any changes without prior notice.

2 Konformitetserklæring Vi, MJK Automation A/S, DK-2850 Nærum, påtager os det fulde ansvar for at produktet Declaration of Conformity We, MJK Automation A/S, DK-2850 Nærum, declare under our sole responsibility that the product Konformitätserklärung Wir, MJK Automation A/S, DK-2850 Nærum, erklären in alleiniger Verantwortung, dass das Produkt som denne erklæring angår, er i overensstemmelse med følgende standard(er) eller andre normdokument(er). EN :1995 EN :1995 efter bestemmelserne i direktiv 89/336/EØF; 93/68/EØF MJK Data Transmitter 795 to which this declaration relates is in conformity with the following standard(s) or other normative document(s). EN :1995 EN :1995 following the provisions of Directive 89/336/EWG; 93/68/EWG auf das sich diese Erklärung bezieht mit der/den folgenden Nor me(en) oder normativen Dokument(en) übereinstimmt. EN :1995 EN :1995 Gemäss den Bestimmungen der Richtlinie 89/336/EWG; 93/68/EWG Declaration de conformite Nous, MJK Automation A/S, DK-2850 Nærum, déclarons sous notre seule responsabilité que le produit Dichiarazione di conformità Noi, MJK Automation A/S, DK-2850 Nærum, dichiariamo sotto la nostra esclusiva responsabilità che l apparecchio Declaración de Conformidad Nosotros, MJK Automation A/S, DK-2850 Nærum, declaramos bajo nuestra única responsabilidad que el producto auquel se réfère cette déclaration est conforme á la (aux) norme(s) ou autre(s) document(s) normatif(s) EN :1995 EN :1995 conformément aux dispositions de Directive 89/336/EWG; 93/68/EWG MJK Data Transmitter 795 al quale questa dichiarazione si riferisce, è conforme alla seguente normativa(e) standard o ad altri documenti di normativa(e) EN :1995 EN :1995 conformemente alla disposizioni della Direzione 89/336/EWG; 93/68/EWG al cual se refiere esta declaración, está en conformidad con la(s) siguente(e) norma(s) u otros documentos normativos EN :1995 EN :1995 según las disposiciones de la(s) directiva(s) 89/336/EWG; 93/68/EWG 2

3 Contents 1 Introduction Versions Communications protocols MJK-Link About this manual Safety instructions Product identification Standard versions Versions with built-in options 7 2 Mechanical mounting Mounting on a wall Electrical mounting Power supply In- and output signals I/O terminals, 8 DI/8 DO/4 AI I/O terminals, 12 DI/4 DO/4 AI I/O terminals, 16 DI/4 AI Connection examples Digital inputs Digital outputs Analogue inputs Connection of Pump Controller Connection of communications ports Communications port Built-in modem 12 4 The front panel Display and keys Menu structure Functional menus F0 - Program version, time and date F0 - Interlock, operation or alarm signal F0 - Internal flag, operation or alarm signal F0 - Limits, high/low F0 - Digital inputs, operation or alarm signal F1 - Digital inputs on/off F2 - Digital outputs on/off F2 - Internal flag on/off F3 - Limits - High/Low F4 - Analogue input value # F5 - Analogue input scaling F5 - Analogue input on Pump Controller F6 - Counter for inputs F7 - Counter for time F8 - Alarm / Alarm number F9.1 - Stormflow volume F9.2 - Stormflow calculation F# - Modem/Line status F* - Communication status Programming of main functions Select language Set time and date Automatic change between summer time and winter time Access code enabled/disabled Enter password Calculation of average values on analogue inputs Data logging interval Tone / pulse dialing Alarm call on power failure Number of incoming rings before answer ID. no. for the Data Transmitter Automatic reset of alarms Call on automatic alarm reset Start time for operational reports telephone number SMSC telephone number RS485 function Master ID number 18 7 Programming of analogue inputs Select analogue input or 4-20 ma input Scaling at 0 / 4 ma Scaling at 20 ma Monitoring of high limit Set high limit High limit operation / alarm Dialout on high limit Signal delay for exceeding high limit Monitoring of low limit Set low limit Low limit operation / alarm Dialout on high limit Signal delay for exceeding low limit Divisor Programming of digital inputs Select a digital input NO or NC Operational or alarm input Dialout on alarm Signal delay Programming of digital outputs Select a digital output NO or NC Time controlled output ON time Time before start 21 3

4 10 Programming of logical functions Select the output to receive the result of the logical function Select logical function Select signals for the logical function Operational or alarm signal on internal flag Dialout when alarm signal on internal flag Signal delay on internal flag Programming of interlock Interlock of this station Interlock interval Selection of substation Interlock active / inactive Start of interlock Stop interlock Receivers telephone / ID number Receiver's output Programming of Pump Controller(s) connected Call on alarm or system error on Programming of the internal Pump Controller Select level signal Start level for pump no Stop level for pump no Levels in use in Start level for pump no Stop level for pump no Alternation of pumps Telephone list for alarms Telephone number Number type Telephone number Enter pager message Enter SMS message Pause between calls Programming of 702 ComTroller Select Alarms Operational or alarm signal Alarm calls Reset of alarms Automatic reset of alarms Factory settings Signal lists Register list Menu structure Functional menus Programming menus...45 A Appendix A1 Technical specifications...50 A2 Number of signals available...50 A3 Inputs and outputs...50 A4 Dimensions...50 B Appendix B1 Maintenance...51 B2 Service codes...51 B2.2 Forced setup without reset of datalogger 51 B2.3 Forced setup including reset of datalogger 51 B2.4 Baud rate and communication method 51 B2.5 Activation of SIM card for GSM/GPRS modem 51 B2.6 Total reset 51 B3 Software upgrade...51 B4 SMSC telephone numbers...52 B5 Spare parts Programming of stormflow calculation Stormflow calculation Stormflow calculation in use Zero point input no Level signal for flow calculation Number of Q(h) points Height value [h] for level point Flow value [Q] for level point 28 4

5 1 Introduction Thank you for choosing an MJK Data Transmitter 795. A great effort has been put into developing a product, which complies with all demands. MJK Data Transmitter 795 is mounted in the field and with its digital in- and output and analogue input it is capable to receive and transmit most types of digital and analogue signals. From a built-in RS232 serial port, the MJK Data Transmitter 795 can communicate directly with other equipment i.e. a pc, PLC or a Scada system. MJK Data Transmitter 795 can with one click on the mouse or from a telephone call activate digital output and/or read in- and outputs, alarm signal type for the latest 9 alarms and all logged data. Display of a pumping station from a pc with the monitoring program MJK-Link. MJK Data Transmitter 795 can also be programmed to make a telephone call when there is an alarm and transmit the alarm as text to a pc or SCADA system and to a cell phone as SMS text. The Data Transmitter 795 has a bult in battery for telephone calls at power failure. All settings, alarms and logged data can be read in the display, from easy to use functionnal menus. MJK Data Transmitter 795 can be supplied in versions that communicates via a built-in GSM modem or telephone modem, or in versions for radio modem. MJK Data Transmitter 795 is easy to install and operate, but read the instruction manual carefully in order to make optimum use of the unit. You can allways contact your sales reprsentative or the MJK Automation Hotline in case of doubt or for guidance. Try also to log onto Versions MJK Data Transmitter 795 is as standard supplied in the following hardware versions: - 8, 12 or 16 digital inputs - 0,4 or 8 digital outputs - 4 analogue inputs - 1 or 2 RS232 ports The RS 232 ports is used as connection to MJK Pump Controller 704 and to connection of a PC for configuration or reading of data in the field for i.e. a portable PC or for configuration or reading of data, when the Data Transmitter 795 is used as data logger. 1.2 Communications protocols MJK Data Transmitter 795 can be connected to a distribution station either through a serial connection (RS232-RS 485), a built-in Hayes compatible telephone modem, a data radio or a GSM modem. Communication complies with one protocol which must be followed by master and slave. Data Transmitter 795 is always the slave, i.e. the Data Transmitter must receive a command before it can reply. MJK Data Transmitter 795 is supplied with Comli PLC-protocol as standard. The following historical data are available in this protocol: - Time counter on digital inputs, total, total today, total yesterday and the latest 24 hours, all with 1 hour interval. - Analogue values stored with 5 min. interval 24 hours back, and in the extended log with a user defined logging interval. An MJK Data Transmitter 795 with built-in modem can transmit alarms as SMS messages directly to the cell phone of employee on duty. 5

6 1.3 MJK-Link The Windows based program MJK-Link can be applied to monitor one or several MJK Data Transmitter 795. Via a PC with modem it is possible with MJK-Link to read values, modify setpoints and read datalogger for e.g. storm flow values. All settings in Data Transmitter 795 can be implemented via MJK-Link. Furthermore, MJK Link can be used to control the MJK Pump Comtroller 704. This facitily is used when e.g. MJK Data Transmitter 795 and MJK Pump Controller 704 is used together. This manual covers MJK Data Transmitter 795 in Comli versions for communication via telephone modem, GSM modem or closed radio networks. 1.4 About this manual The manual is divided into 4 main sections: 1: Introduction Presentation of Data Transmitter 795 and this manual. 2: Mounting Information for performing mechanical and electrical mounting. 3: Basic settings A look through the most common settings. 4: Field operation A look through all settings for special applications of Data Transmitter Safety instructions 1: Read this manual carefully. 2: Be aware of the environment on the installation site. Wear necessary protective equipment and follow all current safety regulations. 3: MJK Data Transmitter 795 can give out start signals to dangerous machinery. Therefore, it must be ensured that eventually connected machinery and other equipment are effectively being put out of service by i.e. removal of main fuses, lock main- and/or security switches in off position before commencing setting, fault finding, service and maintenance work etc. 4: There is a risk of lethal electrical shock from some of the terminals on Data Transmitter 795. Be careful not touch these while the unit is in operation. Repair 1: Repair must only be made by MJK or a representative approved by MJK. Explosion hazardous areas MJK Data Transmitter 795 is not approved for use in explosion hazardous areas. All current local and national standards and regulations regarding installation and use of Ex approved material, certifications and safety instructions for Ex equipment that have been used in connection with installation of Data Transmitter 795 must be strictly observed. 1.6 Product identification Check that the item(s) delivered corresponds to the ordered item(s). The item number is printed on a label that is sticked onto the packing. ➀ ➁ ➀ Item number ➁ Item description ➂ An identical marking can be found on the right hand side of the cabinet: ➃ ➂ Serial number ➃ Communications program 6

7 1.6.1 Standard versions This manual covers the following standard versions with Comli protocol: Item no.: In- and outputs: Communication: AI / 8 DI / 8 DO 2 RS232 w. modem AI / 12 DI / 4 DO 2 RS232 w. modem AI / 16 DI / 0 DO 2 RS232 w. modem AI / 8 DI / 8 DO 1 RS232 wo. modem AI / 12 DI / 4 DO 1 RS232 wo. modem AI / 16 DI / 0 DO 1 RS232 wo. modem Versions with built-in options The following type options can be built into Data Transmitter 795: Varenr.: Betegnelse: Galvanically insulated RS232 port Galvanically insulated RS485 port Galvanically insulated port for TP Galvanically insulated port for Niros UHF Galvanically insulated port for external modem GSM modem complete w. aerial GPRS modem complete w. aerial The factory mounted options can be determined read on the terminal box lid: MJK Data Transmitter 795 with 2 X RS232 and built-in telephone modem. (Item no /204511/204512) MJK Data Transmitter 795 delivered from factory with galvanically insulated communications port. MJK Data Transmitter 795 delivered from factory with built-in GSM-modem. For both types of option applies that the data transmitter is mounted and connected like a standard data transmitter. Please see separate documentation for the builtin options. MJK Data Transmitter 795 with 1 X RS232 and 1 x communications option port. (Item no /204521/204522) 7

8 2 Mechanical mounting Data Transmitter 795 must not be mounted in explosion hazardous areas! Data Transmitter 795 is IP65 enclosed, and can be mounted outdoors directly on a wall or a railing, eventually by means of MJK rain roof and MJK universal fitting Dimensional drawing for mounting screws. See also page 51. MJK rain roof mounted on pole with MJK universal bracket Data Transmitter 795 can also be mounted in a panel by means of MJK panel mounting kit Remove the terminal box lid to gain access to the two lower mounting holes. Data Transmitter 795 mounted in a panel with MJK panel mounting kit Mounting on a wall The cabinet is mounted using three screws. The upper screw is used for the suspension and the two lower screws is used to fix the cabinet. The distance between the mounting screws is shown on the dimensional drawing. Please observe minimum distance if more than one cabinet is mounted. You will find a jig in full size at the back of this manual. MJK Data Transmitter 795 must be mou ted vertically in order to comply with the IP68 standard. The cabinet is suspended by the upper screw and. fastened with the two lower screws. X Do not use a screw machine! 8

9 3 Electrical mounting Data Transmitter 795 must not be mounted in explosion hazardous areas! Data Transmitter 795 must not be connected to the power supply before all connections are made. Remove the terminal lid and the front panel to gain acces to all terminals. 3.1 Power supply Data Transmitter 795 can be supplied from both 230 V AC and 24 V DC. Terminal: Designation: Protective ground N 230 V AC neutral L 230 V AC live - 24 V DC negative + 24 V DC positive Please note, that 24 V DC will not be available on the terminals marked '24 V DC forsyning' unless the Data Transmitter is fed from the mains. 3.2 In- and output signals Data Transmitter 795 is delivered in 3 different I/O variants; 4AI / 8DI / 8DO, 4AI / 12DI / 4DO and 4AI / 16DI respectively. Specifications: DI: Passive with common negative, max. 24 V DC. (Optocoupler med 10 kω serial resistor) Trig voltage: < 1 V DC = Off, > 10 V DC = On, pulse length > 100 ms. DO: Voltage free relay contacts, max V DC / 0,5 48 V AC. AI: 0/4-20 ma or 0-1 V DC. Input impedance = 50 Ω I/O terminals, 8 DI/8 DO/4 AI DO 1 DO 2 DO 3 DO 4 DO 1/2/3/4 common - DO 5 DO 6 DO 7 DO 8 DO 5/6/7/8 common - Shield for RS232 to 704 Signal ground for RS232 to V DC out + 24 V DC out - DI 1 + DI 2 + DI 3 + DI 4 + DI 1/2/3/4 common - DI 5 + DI 6 + DI 7 + DI 8 + DI 5/6/7/8 common - AI 1 + AI 1 - AI 2 + AI 2 - AI 3 + AI 3 - AI 4 + AI 4 - Rx for RS232 to 704 Tx for RS232 to 704 9

10 3.2.2 I/O terminals, 12 DI/4 DO/4 AI DI 9 + DI 10 + DI 11 + DI 12 + DI 9/10/11/12 common - DO 1 DO 2 DO 3 DO 4 DO 1/2/3/4 common - Screen for RS232 to 704 Signal ground for RS232 to V DC out + 24 V DC out - DI 1 + DI 2 + DI 3 + DI 4 + DI 1/2/3/4 common - DI 5 + DI 6 + DI 7 + DI 8 + DI 5/6/7/8 common - AI 1 + AI 1 - AI 2 + AI 2 - AI 3 + AI 3 - AI 4 + AI 4 - Rx for RS232 to 704 Tx for RS232 to I/O terminals, 16 DI/4 AI DI 9 + DI 10 + DI 11 + DI 12 + DI 9/10/11/12 common - DI 13 + DI 14 + DI 15 + DI 16 + DI 13/14/15/16 common - Screen for RS232 to 704 Signal ground for RS232 to V DC out + 24 V DC out - DI 1 + DI 2 + DI 3 + DI 4 + DI 1/2/3/4 common - DI 5 + DI 6 + DI 7 + DI 8 + DI 5/6/7/8 common - AI 1 + AI 1 - AI 2 + AI 2 - AI 3 + AI 3 - AI 4 + AI 4 - Rx for RS232 to 704 Tx for RS232 to

11 3.3 Connection examples Digital inputs The digital inputs are passive, i.e. they need to be supplied from an external power source or from the terminals marked '24 V'. Note, that the inputs has common negative in groups of 4 inputs. A common installation error is that an input is not connected to the correct negative terminal! The inputs can be individually configured to be normally open (NO) or normally closed (NC) Analogue inputs The analog inputs are passive. i.e. they must be supplied from an external power source or from the terminals marked '24 V'. Every input have its own plus and negative terminal. A common installation fault is that an input is not connected to the correct negative terminal! The input range can be individually configured to 0-20 ma or 4-20 ma. Above diagram show an example of connecting two switches to DI1 and DI2. Note the common negative terminal! Digital outputs The digital outputs are voltage-free relay contacts with a capacity of max. 24 V DC / 1 A or max. 48 V AC / 0,5 A resistive load. The outputs can be individually configured to be normally open (NO) or normally closed (NC). A passive ma signal from a pressure transmitter. An active ma signal from a level transmitter. 11

12 3.3 Connection of Pump Controller 704 Only the RS232 port on the plug-in terminals of the Data Transmitter can be used for connecting a MJK Pump Controller 704. A screened, twisted pair cable must be used, and it should be connected as shown below: The shield must not be connected to the Pump Controller 704. Max. cable length is 15 metres. DO NOT CONNECT THE SHIELD IN THIS END! 3.4 Connection of communications ports (Only item no / 21 / 22.) Communications port All options listed in section is supplied with a flat cable, that just need to be mounted in the communications port socket on the lower PCB. See also separate documentation for the option in question Built-in modem The built-in modem can be connected to a telephone outlet with the enclosed RJ11 cable. If the modem should be connected to a terminal, the cable should be stripped and only the red og blue wire need to be connected. The two other wires are not used. 12

13 4 The front panel Display 2 x 24 digit backlit alphanumerical display for indication of user menus and measuring values. 4.1 Display and keys ESC. key This key is used to go back to the previous menu, or to cancel a selection. Press this key 2 or 3 times to revert to functional indication. MENU key This key is used to switch between main menus and submenus. Arrow keys The arrow keys are sed for altering the current setting. In a sub-menu the current selection is always shown in the upper line, and the alternative selection is shown in brackets in the lower line. The arrow keys are used to select an alternative setting. The arrow keys are also used to select input and output number. The key increase and the key decrease a value. Numerical keys The keys 0-9, #, * are used to enter telephone numbers, delays, analogue scaling etc. Functional key F The function key are used for selecting the different functional menus to be displayed. The illustration show the function menu F0 for program version, time and date. ENTER key The ENTER kry is used to change between the main menu and submenus and to go through the submenus. The ENTER kay is always used to confirm a selection in a submenu. 4.2 Menu structure INDICATION MENUS MAIN MENU MAIN MENU SUBMENU W. SELECTION SUBMENU W. SELECTION Above figure is an overview of the general function of the functional keys. See also page

14 5 Functional menus F0 - Program version, time and date Menu F0 displays date og and time. Moreover, it will display the current communications protocol and program version. 5.2 F1 - Digital inputs on/off Menu F1 indicates if the digital inputs are set ON or OFF. Up to 8 inputs are shown simultaneously F0 - Interlock, operation or alarm signal Menu F0 followed by 1 x 'down arrow' will display which signals that initiate the 9 programmable interlock sequences: 'A': alarm signal, '+': operation signal, '-': not in use F0 - Internal flag, operation or alarm signal Menu F0 followed by 2 x 'down arrow' will display which signals that are linked to the internal flags: If there are more than 8 inputs, the remaining inputs will be displayed by pressing one of the arrow keys: Note, that a delay period can be set for every digital input so that the digital input can go ON for a short period without triggering an eventual alarm. When the input is OFF, an empty field is shown. When the input goes ON, a flashing field is shown during the delay time, after which a field is shown constantly F2 - Digital outputs on/off Menu F2 displays whether the digital outputs are set ON or OFF: 'A': alarm signal, '+': operation signal, '-': not in use F0 - Limits, high/low Menu F0 followed by 2 x 'down arrow' will indicate which analogue inputs that are linked to a high/low alarm limit, and also if the limit will release an operational or alarm signal: 'A': alarm signal, '+': operation signal, '-': not in use F0 - Digital inputs, operation or alarm signal Menu F0 followed by 4 (and 5) x 'down arrow' display which digital inputs, that releases an operation or alarm signal: A delay period can be set for every digital output. This delay period must run out before the output are activated. When the output is OFF, an empty field is shown. When the output goes ON, a flashing field are shown during the delay time, after which a field are shown constantly F2 - Internal flag on/off Menu F2 followed by 1 x 'down arrow' will display the status for the internal flags. 'A': alarm signal, '+': operation signal, '-': not in use. 14

15 5.4 F3 - Limits - High/Low Menu F3 indicates if high and low limit is ON or OFF for the analogue inputs. The first four digits indicate if the high limit setting is exceeded and the last four digits indicate if the low limit setting is exceeded: F5 - Analogue input on Pump Controller 704 Menu F2 followed by 1 x 'down arrow' display the value of the analogue input on the Pump Controller 704 (if connected): A delay time can be set individually for each analogue input in that the the input can exceed the limit for a short period without activating an alarm. An empty square is displayed when the limit is not exceeded. When the limit is exceeded, a solid square is displayed. If a delay period is set, the square will flash during the delay period. 5.5 F4 - Analogue input value # Menu F4 indicates the value of the analogue inputs as a bargraph: Select the desired input with the arrow keys or the numeric keys F5 - Analogue input scaling Menu F5 indicates the value of an analogue input as a percentage and the ma signal and as a scaled value: Select the desired input with the arrow keys or the numeric keys. The scaled value is determined by the programming of the analogue input. If the value represents e.g. a level measurement in a tank, and the level normally varies between 2 m and 3 m, the analogue input will normally be programmed so 2 m corresponds with '200' (low value) and 3 m corresponds with '300' (high value). A level of 2,5 m will then give a scaled readout of 250 and 50 %. If the scaled value should be shown as '2,5', it is possible to set a divisor for each input. In this example the divisor should have the value 100. See also section 7. Please observe that the value is collected directly from the Pump Controller 704 and is not scaled. 5.6 F6 - Counter for inputs Whenever a digital input or an analogue high/low limit is active, it will be recorded by a counter. The number is displayed in menu F6: Use the arrow keys to change between: - digital input 1-8/12/16 - analogue high limit analogue low limit 1-4 In addition, the numerical keys 1-8 can be used to select the desired input. The selected counter can be reset by pressing the ENTER key. 5.7 F7 - Counter for time Menu F7 indicate for how long the digital input and the analogue high and low limits have been active. Time counters is running continuously such as if the input is set to OFF for some time and then is set to ON, the counter will count from the last value. The time is displayed in hours and minutes: Use the arrow keys to change between: - digital input 1-8/12/16 - analogue high limit analogue low limit 1-4 In addition, the numerical keys 1-8 can be used to select the desired input. The selected counter can be reset by pressing the ENTER key. 15

16 5.8 F8 - Alarm / Alarm number Menu F8 indicate if the last 9 alarms are ON or OFF: F9.2 - Stormflow calculation Whenever a stormflow occur, the flow is displayed as m 3 /h in menu F9-2: Each time a new alarm is activated, it will be recorded as alarm no. 1 and all other recorded alarms will move down one place and alarm 9 will be deleted. When the alarm for one input has been ON one time it must be set to OFF before a new alarm from the same input is accepted as an alarm. If the alarm has not been reset and another 9 alarms occur, i.e. the first alarm become no. 10 and therefore will become invisible in the alarm list, this alarm will be reset automatically. A flashing square is shown when an alarm goes ON. If the alarm are being reset but is still active, a solid square is shown constantly. When the alarm goes OFF again, a square is shown constantly. By means of the arrow keys or by entering the alarm number, the status, type and timestamps for on and off time can be displayed. Whenever an alarm goes ON, the input number and start time will be recorded. Similarly, when the alarm is reset, the reset time is recorded, and when the alarm goes OFF, the end time will be recorded: 5.10 F# - Modem/Line status (Only for versions with built-in telephone modem or GSM modem.) Menu F# displays the status of outgoing alarm calls or incoming calls: The following is displayed during an incoming call: The following is displayed during an outgoing alarm call to one of the telephone numbers in the telephone number list: When Data Transmitter 795 interlocks another Data Transmitter 795 i.e. in order to perform a remote start or stop of a pump, the following is displayed: 'ID' indicates the ID number of the Data Transmitter itself. If the Data Transmitter are configured as a Master in a multidrop system, the 'ID' can also be the ID number of a connected Slave unit. Return to normal operating display with the arrow keys or by prssing the '0' key F9.1 - Stormflow volume Menu F9 displays the recorded stormflow volume. The counter can be reset with the ENTER key F - Communication status * Menu F* indicate the communication status on the serial port, the port to Pump Controller 704, and the built-in telephone modem: 795 serial: R = Rx, T = Tx, CD = Carrier Detect, RTS = Request to send og CTS = Clear to send. 704: R = Rx, T = Tx and = Pump Controller 704 not interlocked / Pump Controller 704 interlocked. The Pump Controller 704 signal to the Data Transmitter that the Pump Controller 704 will not activate any control outputs, because the Pump Controller are interlocked. 16

17 6 Programming of main functions 6.1 Select language Select the desired language with the arrow keys and confirm with ENTER. 6.2 Set time and date Enter time and date with the numerical keys or the arrow keys. Confirm with ENTER: 6.5 Calculation of average values on analogue inputs The value of an analogue input is recorded every second, and every 5 minutes the values is logged. If averaging of the analogue values are selected, an average of the analogue value over the last 5 minutes will be calculated and logged. If averaging is not selected, the analogue value at the actual time will be logged. Just press ENTER at all entries if changes are not needed in order to proceed to the next menu. 6.3 Automatic change between summer time and winter time Select if the clock should change automatically between summer time and winter time: Use the arrow keys to select and confirm with ENTER. 6.6 Data logging interval The data logging interval is used for the extended logging function, where the value for the analogue input and the level from MJK Pump Controller 704 is stored. Use the arrow keys to select and confirm with ENTER. Just press ENTER at all entries if changes are not needed in order to proceed to the next menu: 6.4 Access code enabled/disabled Select if an access code is required to gain access to the remaining system menus. This function make it possible to protect the system configuration from unauthorized changes: The interval between loggings can be chosen amongst the following values: 30 sec. (00:30), 1 min. (01:00), 5 min. (05:00), 10 min. (10:00), 30 min. (30:00) and 1 hour (60:00). Use the arrow keys to select and confirm with ENTER. 6.7 Tone / pulse dialing Select between pulse or tone dialing from a telephone modem: Use the arrow keys to select and confirm with ENTER Enter password If access code protection is selected, a 4-digit access code is required in order to gain access to the remaining system menus. Use the arrow keys to select and confirm with ENTER. 6.8 Alarm call on power failure If alarm call at power failure is selected, the Data Transmitter will call the first telephone number in the telephone list when the power supply fail. A power failure will not be detected before the supply has been gone for minimum 30 sec. Hereby alarm calls on short power surges are avoided. Use the arrow keys to select and confirm with ENTER. 17

18 6.9 Number of incoming rings before answer Set the number of rings (1 to 5) before Data Transmitter 795 answer the call telephone number Enter the telephone number that the Data Transmitter is connected to. The number is used as ID no. in connection with transmission of SMS alarms through landlines. Use the arrow keys or numerical keys 1 to 5 to select and confirm with ENTER ID. no. for the Data Transmitter The ID number is used for identification of the individual data transmitters. Use the numerical keys and confirm with ENTER SMSC telephone number SMS messages need to be dialed to a specific SMS gateway, that will handle the further transmission through the cellphone network. Use the arrow keys or numerical keys and confirm with ENTER Automatic reset of alarms Select if incoming alarms should be automatically reset when the alarm condition disappears. If 'NO' are selected, all incoming alarms need to be reset manually Call on automatic alarm reset If 'Automatic reset of alarms' have been selected as described in the previous section, there will be an option to select if the Data Transmitter should perform a call, if an alarm condition disappear and therefore releases an automatic reset of an alarm Start time for operational reports Many plant managers want to have the operational reports displaced so they will elapse between i. e. 07:00 to 06:59. Enter the desired displacement counted from midnight: Use the numerical keys and confirm with ENTER. Telephone numbers to SMSC gateway can be found in Appendix B RS485 function This function is only available on Data Transmitter 795 with RS485 port. Select if this Data Transmitter 795 should be a Master (the unit sending out alarms), or if this Data Transmitter 795 should be a Slave which is interconnected to another Master via the RS485 port: Master ID number Select the Master ID for this Data Transmitter 795 if it is set to Master, or select the Slave ID for the unit in the multidrop cluster which should receive alarms and relay them via modem or radio: Use the arrow keys or numerical keys and confirm with ENTER. 18

19 7 Programming of analogue inputs 7.1 Select analogue input Select the desired analogue input with the arrow keys and confirm with ENTER or 4-20 ma input Set high limit Set the upper limit value that should cause a recording in the operational or alarm log - see also section 13, "Operational or alarm signal". In case the input are not scaled, 20 ma on the analogue input will correspond to Select input type with the arrow keys and confirm with ENTER. 7.3 Scaling at 0 / 4 ma Set the scaling of the low (0/4) ma value. NB! The setting for the low ma value must be lower than the setting for the high ma value! (See next section.) Use the arrow keys or numerical keys and confirm with ENTER High limit operation / alarm Select if a high limit excession should be recorded in the alarm log or the operational log - see also section 15, "Operational or alarm signal". Use the numerical keys and confirm with ENTER. 7.4 Scaling at 20 ma Set the scaling of the high ma value. NB! The setting for the high ma value must be higher than the setting for the low ma value! (See previous section.) Use the numerical keys and confirm with ENTER. 7.5 Monitoring of high limit Select if exceeding a high limit should be recorded or not Dialout on high limit Select if a high limit activation should cause a dialout attempt Signal delay for exceeding high limit Select the period in which the analogue value can exceed the high limit without activating an alarm: Use the arrow keys (double arrow for minutes and single arrow for seconds) and confirm with ENTER. 7.6 Monitoring of low limit Select if exceeding a low limit should be recorded or not. 19

20 7.6.1 Set low limit Set the lower limit value that should cause a recording in the operational or alarm log - see also section 13, "Operational or alarm signal". In case the input are not scaled, 0 / 4 ma on the analogue input will correspond to 0. Use the arrow keys or numerical keys and confirm with ENTER Low limit operation / alarm Select if a low limit excession should be recorded in the alarm log or the operational log - see also section 15, "Operational or alarm signal". Use the arrow keys or numerical keys and confirm with ENTER Dialout on high limit Select if a low limit activation should cause a dialout attempt. (Maximum period is 8 hours.) Signal delay for exceeding low limit Select the period in which the analogue value can exceed the low limit without activating an alarm: Use the arrow keys (double arrow for hours/ minutes and single arrow for seconds) and confirm with ENTER. 7.7 Divisor Set the desired divisor value for the analogue input. The divisor has only significance for displaying of analogue values in function menu F5, and not to the values that are transmitted to other data transmitters or SCADA systems. The divisor has no significance for the setting of high or low limits. 8 Programming of digital inputs 8.1 Select a digital input Select the desired digital input with the arrow keys and confirm with ENTER. 8.2 NO or NC Select if the input should be active (ON) when there is a signal on the input or passive (OFF) when there is no signal on the input. 8.3 Operational or alarm input Select if an activation of the input should be recorded in the alarm log or in the operational log - see also section 15, "Operational or alarm signal" Dialout on alarm Select if an activation of the digital input should cause a dialout attempt: 8.4 Signal delay Select the period in which the digital input can be active without causing an alarm or a recording of an operational signal: (Maximum period is 8 hours.) Use the arrow keys (double arrow for hours/ minutes and single arrow for seconds) and confirm with ENTER. Use the arrow keys or numerical keys and confirm with ENTER. 20

21 9 Programming of digital outputs 9.1 Select a digital output Select the desired digital output with the arrow keys and confirm with ENTER. 9.2 NO or NC Select if the relay contact should be open (NO) or closed (NC), when the output is not active. 9.3 Time controlled output Select if the output should go ON and stay ON when the Data Transmitter receive a start signal ('FIXED'), or if the output should go ON when the Data Transmitter receive a start signal and stay ON for a pre-set period of time ('TIME'). If 'FIXED' are selected, the Data Transmitter need a stop signal in order to deactivate the output. 10 Programming of logical functions This menu gives the possibility to program simple logical functions like AND, OR, and SET/RESET based on different digital signals in both Data Transmitter 795 and the Pump Controller 704 (if connected). Since it is also possible to set internal flags in Data Transmitter 795, it will be possible to make combina-tions of several logical function and thus obtain PLC-like logical functions in the Data Transmitter Select the output to receive the result of the logical function The result of a logical function can be sent to an internal flag or directly to a digital output. Select the desired signal with the arrow keys and confirm with ENTER Select logical function Select the desired logical function for the signal. 9.4 ON time Select the period in which the output should be active, if the output is set to be 'TIME' controlled. Use the arrow keys (double arrow for minutes and single arrow for seconds) and confirm with ENTER Time before start Select the delay time for activation of the output relay. The delay time is from the moment the Data Transmitter receive an ON command and until the relay output will be activated Select signals for the logical function Select the signals to be used for the logical function. In the left hand side of the display is shown the previous selected signal type to receive the result of the logical function together with the selected logical function. In the right hand side of the display is shown the input signals for the selected logical function. Use the arrow keys (double arrow for minutes and single arrow for seconds) and confirm with ENTER. 21

22 1: Select the upper input signal with the arrow keys and confirm with ENTER. 2: After that, select the lower input signal and confirm with ENTER. Please note, that DO1 and DO2 may be used by the pump controller function - see also section Operational or alarm signal on internal flag If the signal type is selected as internal flag it is possible to select if an internal flag should be an operational signal or alarm signal. 11 Programming of interlock With this function it will be possible for two Data Transmitters to send command to each other. E.g. one Data Transmitter can control a digital output on another Data Transmitter. Furthermore, if a Pump Controller 704 is connected to a Data Transmitter, the output relays on the Pump Controller 704 can be controlled by another Data Transmitter Interlock of this station This menu makes it possible to block remote commands from other Data Transmitters (substations) Dialout when alarm signal on internal flag Selct if the internal flag should release an alarm call attempt on an alarm Signal delay on internal flag This menu is used to set the period in which both input signals should be active in order to set the internal flag. Note, that interlock of a connected Pump Controller 795 also will be blocked. Use arrow keys and confirm with ENTER Interlock interval This menu is used to set the interval for how often other Data Transmitters should be dialed for remote control. The actual application and communication method is decisive for setting the interlock interval. As an example, in case communication are taking place through a dialed line, it would be expensive to exchange interlock commands between two Data Transmitters every 5 minutes, if it is about stopping a waste water pump in connection with an overrun. Use arrow keys and confirm with ENTER. The setting will be valid for all Data Transmitters (substations) that are being set to interlock in the following menus Selection of substation Select the Data Transmitter (substation) to be interlocked. Use arrow keys and confirm with ENTER.. 22

23 11.4 Interlock active / inactive Select if the previously chosen Data Transmitter (substation) should be interlocked. Use arrow keys and confirm with ENTER Start of interlock Select the signal initiating an interlock on the selected Data Transmitter (substation): The following signals are available: - internal flag digital input 1-8/12/16 - analogue limit HIGH analogue limit LOW system error - power failure output 1-2 As long as the signal is ON, all calls will take place in the interlock interval previously chosen. If the interlock interval is set to 10 minutes or more, the remote controlled output should be configured as time controlled with an ON-time set to more than 10 minutes (e.g. 15 minutes) to avoid a situation where the remote output is ON constantly caused by a communications error. (E.g. a broken telephone cable.) In this way it is ensured, that the output is switched OFF, if communications fail. On error-free communication the ON-timer on the remote controlled output will be initialized on every call, and with that the output will stay ON as long as the controlling signal is active. Use arrow keys and confirm with ENTER Stop interlock Select the digital signal that - when switched OFF - will cause the Data Transmitter to call the other Data Transmitter and set an output OFF: The following signals are available: - internal flag digital input 1-8/12/16 - analogue limit HIGH analogue limit LOW system error - power failure output 1-2 Only one call attemt will be made. In case the same signal are selected as both start condition and stop condition, the stop condition will be when the digital signal goes OFF Receivers telephone / ID number Enter the telephone number / ID number of the Data Transmitter to be interlocked. Enter the ID number if radio modems are used. If the receiver is another Data Transmitter which is directly connected to the same multidrop line via the RS485 port, the ID number of the Data Transmitter preceeded with a minus. (The F key is used to enter the minus character.) Ex.: Data Transmitter ID 001 is supposed to remote control Data Transmitter ID 003: Enter the ID number "- 003" into Data Transmitter 001. If the receiver is another Data Transmitter which is communicating via data radio, the Data Transmitter's ID-nummer should be entered without a preceeding minus. 23

24 Please note, that only a Master Data Transmitter can directly remote control other Data Transmitters belonging to other clusters. Eks.: Data Transmitter ID 001 is supposed to remote control Data Transmitter ID 003: Enter the ID number "003" into Data Transmitter 001. Use the numeric keys and confirm with ENTER Receiver's output Select the desired digital output on the interlocked Data Transmitter: If the receiving unit is another Data Transmitter which is communicating via telephone/gsm modem, the telephone number to the Data Transmitter is entered here. Ex.: Data Transmitter no. 1 is supposed to remote control the Data Transmitter no. 3: Enter the telephone number " " into Data Transmitter no. 1. If the receiving unit is a Data Transmitter belonging to another cluster of Data Transmitters, the ID number / telephone number belonging to the Master in the cluster should be entered followed by the ID number of the desired Data Transmitter in the cluster. Eks.: Data Transmitter 001 in the lower cluster is remote controlling Data Transmitter 003 in the upper cluster: Enter telephone / IDnumber " " into Data Transmitter no

25 12 Programming of Pump Controller(s) connected Select if a MJK Pump Controller 704 are connected to the Data Transmitter: Start level for pump no. 1 Select the desired start level for pump no. 1: 12.2 Call on alarm or system error on 704 Select if the Data Transmitter should perform a call caused by an alarm signal, a control signal or a system error signal from Pump Controller 704. Calls will be made to the telphone numbers entered in the telephone number list in Data Transmitter Stop level for pump no. 1 Select the desired stop level for the pump(s) Levels in use in 795 If 2 pumps are connected to Data Transmitter 795, two different start and stop levels are available Programming of the internal Pump Controller Select the number of pumps connected to Data Transmitter 795: Start level for pump no. 2 Select the desired start level for pump no. 2: Note, that DO1 and DO2 will be assigned to the internal pump controller. If '1' is selected, DO1 will be assigned as control relay for pump no. 1, and if '2' is selected, DO2 will also be assssigned as control relay (for pump no. 2) Select level signal Select the desired level signal: Stop level for pump no. 2 Select the desired stop level for pump no. 2: Alternation of pumps Select if the pumps should be alternated. Select between one of the analogue inputs on Data Transmitter 795 or the analogu input on Pump Controller

26 13 Telephone list for alarms (Not valid for versions with radio modem.) 13.1 Telephone number 1-9 This menu contain a list where up to 9 telephone numbers can be entered. The numbers in the list will be called in the same order they are entered. Use the numerical keys and confirm with ENTER Number type Select the telephone number type for the current entry. Select between SMS, ordinary telephone, pager or PC. Note, that 'PAGER' will only be available on versions with built-in modem Telephone number Enter the telephone number. The '#' key can be used to wait for dialing tone for calls from a local exchange. The '#' key can also give a 2 second break. E.g. 0# **39: Dial 0, wait for dialing tone from city line, call , wait 4 seconds, and then call 39. Use the numerical keys and confirm with ENTER. Max. number of digits is Enter pager message If a telephone number is selected as a pager number, a pager message/code (e.g. the Data Transmitter's own telephone number) of maximum 17 digits can be entered here. Use the numerical keys and confirm with ENTER. The message can be different for the individual telephone numbers. Pager messages will be displayed in the pager together with a code for the alarm type that have caused the call. An example: When digital input no. 5 on a Data Transmitter with telephone number receives an alarm input, the code will be sent to the pager. The alarm codes are: 01 : Digital input no : Digital input no : Digital input no : Digital input no : Digital input no : Digital input no : Digital input no : Digital input no : Digital input no. 9 (option) 10 : Digital input no. 10 (option) 11 : Digital input no. 11 (option) 12 : Digital input no. 12 (option) 13 : Digital input no. 13 (option) 14 : Digital input no. 14 (option) 15 : Digital input no. 15 (option) 16 : Digital input no. 16 (option) 21 : Analogue limit no. 1 LOW 22 : Analogue limit no. 2 LOW 23 : Analogue limit no. 3 LOW 24 : Analogue limit no. 4 LOW 31 : Analogue limit no. 1 HIGH 32 : Analogue limit no. 2 HIGH 33 : Analogue limit no. 3 HIGH 34 : Analogue limit no. 4 HIGH 40 : MJK 704 system error 41 : MJK 704 output no : MJK 704 output no : MJK 704 output no : MJK 704 output no. 4 51: Internal flag no. 1 52: Internal flag no. 2 53: Internal flag no. 3 54: Internal flag no. 4 55: Internal flag no. 5 56: Internal flag no. 6 57: Internal flag no. 7 58: Internal flag no : MJK 795 power failure 26

27 14 Programming of stormflow calculation Enter SMS message If the current telephone number type is selected as an SMS type, enter an SMS message/code of up to 8 digits: 14.1 Stormflow calculation Data Transmitter 795 can calculate the flow of an overrun via a digital input an an analogue input. Use the numerical keys and confirm with ENTER. If the message is entered via the keypad of the Data Transmitter, the message can only consist of numbers, but with MJK-Link it will be possible to enter text messages. The SMS message will be displayed on the cell phone with 'MJK 795' as headline followed by location and cause of the alarm and the SMS message. Test the SIM card in a cell phone if the SMS messages are not received. Also, check if the telephone number to the receiving SMS gateway is correct. Pager messages and SMS messages are delivered as telegraphic alarm to an external server, which implies that Data Transmitter 795 has no option to test that the telegraphic alarm has been received by the recipient Pause between calls Enter a pause between the call attempts to the telephone numbers on the telephone list: Use the numerical keys and confirm with ENTER. MJK 795 MJK 7062 MJK 501 In above example, MJK Pressure Transmitter 7062 provides the level signal to the Data Transmitter, and an MJK Level Electrode 501 is mounted where the stormflow starts. By this, the level measurement is set to zero and flow is calculated by means of the level signal. Usually, the Data Transmitter is connected to a Pump Controller 704 with a level transmitter with its measuring range adopted to the pump controller. The measuring range is normally higher than necessary for flow measurement, typically 10 m for the pump control and cm for flow calculation. The accuracy on the level measurement of the pump controller is as the total measuring range of the flow measurement. The Q/h curve of the weir must be entered in this menu such as the data transmitter can calculate the stormflow. Include as many Q(h) points as possible in order to obtain the highest possible calculation accuracy. Below is demonstrated Q(h) curve and Q(h) table for a rectangular weir with side contraction: Q(h) point no.: h[m] Q[m 3 ] 1 0,00 0,00 2 0,01 48,71 3 0,02 137,78 4 0,03 253,12 5 0,04 389,70 6 0,05 544,62 7 0,06 715,92 8 0,07 902,17 27

28 If these Q(h) values are entered in this menu, the resulting Q(h) curve will be as shown below, and the Data Transmitter will calculate the flow according to this curve: Number of Q(h) points In this menu the number of Q(h) points that are desired for the piece by piece linearization of the flow calculation. The number of Q(h) points can be set from 1 and 9, as the zero point value will be provided to be 0 m 3 /h. Use the arow keys and confirm with ENTER. Note, that Q MAX must be no more than m 3 / h Stormflow calculation in use Select if stormflow calculation should be used: Use the arow keys and confirm with ENTER Zero point input no. Select the input that the level electrode are connedted to. This input will activate the stormflow calculation Height value [h] for level point Enter the height [h] for the Q(h) point. The entered value MUST be higher than that for the previous Q(h) point. Use the numerical keys and confirm with ENTER Flow value [Q] for level point Enter the volume [Q] for the Q(h) point. Use the numerical keys and confirm with ENTER. The current flow value and the total stormflow value can be read in functional menu F9. See also section The following inputs can be selected: - 795: DI 1-8 / 12 / : High/low limit : Output Combi alarm 1-8 Use the arow keys and confirm with ENTER Level signal for flow calculation Select the input that provide the level signal for the stormflow calculation: The following inputs can be selected: - 795: Al : Level Use the arow keys and confirm with ENTER. 28

29 15 Programming of 702 ComTroller If one or more 702 ComTrollers is connected to the Data Transmitter as multidrop units on the RS485 port, they can all be programmed via the Data Transmitter's keyboard and display. (The Data Transmitter must be the Master in the cluster.) 15.1 Select 702 Enter the ID number for the desired 702 ComTroller: Use the arow keys and confirm with ENTER. The Data Transmitter will now attempt to establish a connection with the selected 702 ComTroller: If the selected 702 ComTroller does not respond, the connection attempt can be interrupted by pressing the key, whereafter another ComTroller can * be selected. When the selected 702 ComTroller responds, svarer, the Data Transmitter's display and keyboard can now be used for remote programming of the ComTroller: The function will be interrupted by pressing the * key. 29

30 16 Alarms 16.1 Operational or alarm signal The digital inputs can be set to be either a operational or alarm signals. An operational signal defines a non-critical condition, e.g. a signal that only need to be recorded in the operational log. It would typically be a signal indicating whether a pump is running or not. An alarm signal is a signal, which normally is not active and only becomes active when critical conditions occur, e.g. a thermal overload signal from a pump. Furthermore, an alarm signal has memory and reset, i.e. when the alarm signal becomes no-active, the previous active condition are remembered. This previous active condition must be reset by the user before a new change to active condition will be accepted as an alarm signal. For both types of signals are applied that both the number of changes to active condition and the period of time where the signal has been active will be recorded in the alarm record Alarm calls If 'Call on alarm' is selected, the Data Transmitter will call all the numbers in the telephone list starting with the first entry. Proceeding to the next number in the list will take place after a preset period of time -'Pause between calls'. See also section 13. If a call is made to a modem on a SCADA main station, it will be the main station's task to reset the alarm and stop the dialout routine. If call are made to a pager or telephone, the dialout routine is stopped by making a call to the Data Transmitter. A tone will be heard in the handset. This will not reset the alarms, but only stop the dialout routine. See also section If another alarm occur during the dialout routine, the dialout routine will continue, and the new alarm will be reported in to the next number in the telephone list. Versions with radio modem transmit all alarms to the main station (ID no. 0) Reset of alarms When an alarm signal becomes active, it will be visible in menu F8 (see section 5.8). Whenever a digital alarm signal becomes active, the alarm will be present in menu F8.1. This menu will show the alarm type and start time together with a flashing symbol ' '. The symbol will flash as long as the alarm has not been reset, and the symbol will appear solid when the alarm has been reset but still active. The symbol disappear when the alarm has been reset and the alarm signal is inactive. When the symbol disappear, the stop time for the alarm is displayed instead of the start time. In order to reset an alarm from the front panel of MJK Data Transmitter 795, the menu F8 must be shown. Then use the arrow keys to select the alarm to be reset. Reset the selected alarm by pressing ENTER. The symbol ' ' will then appear solid if the alarm signal is still active or disappear, if the alarm signal is no longer active. An alarm can also be reset from a SCADA system. An alarm signal must have been reset and change from non-active to active condition in order to be visible in the alarm list again. This means that if you do not want to receive the same alarm call several times on the SCADA station, the alarm should not be reset. The Data Transmitter will then stop further alarm calls concerning that particular alarm even if the alarm signal change from non-active to active condition Automatic reset of alarms If an alarm has not been reset, and another 9 alarms occur, meaning that the not yet reset alarm becomes no. 10 and therefore no longer will be visible in the alarm list, the alarm will be reset automatically, if the function 'Automatic reset of alarms' has been activated. See also section

31 17 Factory settings Main functions: Settings: Main functions: Settings: Language English No. of rings before answer 1 Autochange summer/winter time No ID no. for data transmitter 1 Access code No Automatic alarm reset No Averaging of analog inputs No Call on auto alarm reset No Datalogging interval 00:30 (30 sek.) Start time for operational report 00:00 Tone/Pulse dialing Tone 795 telephone number - Alarm call on power failure No SMSC telephone number - Analogue inputs: AI1: AI2: AI3: AI4: 0-20mA/4-20mA 4-20 ma 4-20 ma 4-20 ma 4-20 ma 0/4 ma ma High limit yes/no No No No No High limit value High limit operational/alarm Operational Operational Operational Operational Signal delay (sec.) Dialout on high limit No No No No Low limit yes/no No No No No Low limit value Low limit operational/alarm Operational Operational Operational Operational Signal delay (sec.) Dialout on high limit No No No No Divisor Digital inputs: NO/NC: Operational/Alarm Alarm call Signal delay: Digital indgang nr. 1-8/12/16 NO Operational No 0 Digital outputs: NO/NC: Time/Fixed: On time: Time before start: DO no. 1-4/8 NO Time 10 sec. 5 sec. Interlock: Setting: (Station 1-9) Interlock of this station No Interlock interval 5 min + 0 Start of interlock DI 1 Stop of interlock DI 1 Receivers tel/id no. 0 Receivers output DO 1 Pump control: Setting: 704 connected No 704 output alarm call No 704 system errror alarm call No 795 no. of pumps start level stop level level 2 in use No 795 start level stop level alternation No Telephone list: Type (PC/pager/ Telephone Pager/SMS Tel/SMS): number: message: Pause in min.: Telephone no. 1-9 Available

32 Storm flow calculation: Setting: In use Yes/No No Zero point DI1 Level signal 704 level No of Q(h) points 9 Q(h) point no. 1 Level: 10 ; Flow (m 3 /h) : 1.11 Q(h) point no. 2 Level: 10 ; Flow (m 3 /h) : 2.22 Q(h) point no. 3 Level: 10 ; Flow (m 3 /h) : 3.33 Q(h) point no. 4 Level: 10 ; Flow (m 3 /h) : 4.44 Q(h) point no. 5 Level: 10 ; Flow (m 3 /h) : 5.55 Q(h) point no. 6 Level: 10 ; Flow (m 3 /h) : 6.66 Q(h) point no. 7 Level: 10 ; Flow (m 3 /h) : 7.77 Q(h) point no. 8 Level: 10 ; Flow (m 3 /h) : 8.88 Q(h) point no. 9 Level: 10 ; Flow (m 3 /h) :

33 18 Signal lists g PUMP STATION NO: MJK 795 ID NO: PUMP CONTROLLER TYPE: NAME: SERIAL NO. MJK 795: CONTROLLER SERIAL NO.: TELEPHONE NO.: DATE: SENSOR SERIAL NO.: DATA TRANSMITTER MJK 795 MAIN FUNCTIONS CODE: ANALOG AVERAGING DIAL METHOD DIALOUT ON VOLTAGE ERROR YES NO TONE PULSE YES NO DATA LOGGING INTERVAL MM:SS NO. OF RINGS BEFORE ANSWER 1-5 ANALOG INPUT: AI 1-4 SIGNAL NAME: 0-20 ma 4-20 ma Zero Span AI 1 AI 2 AI 3 AI 4 ANALOG LIMITS: HIGH/LOW LIMIT SIGNAL ALARM SIGNAL DELAY MIN:SEK LOW LIMIT ANALOG INPUT HIGH LIMIT ANALOG INPUT

34 DIGITAL INPUTS DI 1-8 DI 1-12 DI 1-16 SIGNAL NAME: SIG- NAL ALARM NO NC SIGNAL DELAYED MIN:SEC DIAL VIA TEL.: DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8 DI 9 DI 10 DI 11 DI 12 DI 13 DI 14 DI 15 DI 16 DIGITAL OUTPUTS (@ 8 or 12 DI) SIGNAL NAME: TIME FIXED NO NC DELAY BEFORE START MIN:SEC ON-TIME MIN:SEC DO 1 DO 2 DO 3 DO 4 DO 5 DO 6 DO 7 DO 8 DO 9 DO 10 DO 11 DO 12 34

35 INTERLOCK START INTERLOCK STOP INTERLOCK RECEIVERS OUTPUT NO. RECEIVERS TEL NO.: PUMP CONTROLLER MJK 704 YES NO CONNECTED ALARM CALL OUTPUT 1 ALARM CALL OUTPUT 2 ALARM CALL OUTPUT 3 ALARM CALL OUTPUT 4 ALARM CALL ON SYSTEM ERROR TELEPHONE NUMBERS FOR ALARM CALLS TELEPHONE NUMBER PC: TEL.: PAGER: SMS: PAGE / SMS MESSAGE: NO. 1: NO. 2: NO. 3: NO. 4: NO. 5: NO. 6: NO. 7: NO. 8: NO. 9: 35

36 STORM FLOW CALCULATION IN USE: YES: NO: ZERO POINT: LEVEL MEASUREMENT: NO. OF Q(h) POINTS: LEVEL: FLOW: (M 3 /h) HEIGHT VALUE NO. 1: HEIGHT VALUE NO. 2: HEIGHT VALUE NO. 3: HEIGHT VALUE NO. 4: HEIGHT VALUE NO. 5: HEIGHT VALUE NO. 6: HEIGHT VALUE NO. 7: HEIGHT VALUE NO. 8: HEIGHT VALUE NO. 9: COMBI ALARMS IN USE: YES / NO ALARM SIGNALS: DELAY: (MM:SS) ALARM CALL: YES / NO COMBI ALARM 1: AND COMBI ALARM 2: AND COMBI ALARM 3: AND COMBI ALARM 4: AND COMBI ALARM 5: AND COMBI ALARM 6: AND COMBI ALARM 7: AND COMBI ALARM 8: AND 36

37 19 Register list ONLINE VALUES: I/O NO.: VALUE: DESCRIPTION: Digital output 1 0 read/write Digital outputs are READ and WRITE signals Digital output 2 1 read/write Digital output 3 2 read/write Digital output 4 3 read/write Digital output 5 4 read/write Digital output 6 5 read/write Digital output 7 6 read/write Digital output 8 7 read/write Digital input 1 10 read Digital inputs are READ ONLY signals. Digital input 2 11 read Digital input 3 12 read Digital input 4 13 read Digital input 5 14 read Digital input 6 15 read Digital input 7 16 read Digital input 8 17 read Digital input 9 20 read Digital input read Digital input read Digital input read Digital input read Digital input read Digital input read Digital input read Alarm input 1 30 read/reset Alarms are READ and RESET signals. Alarm input 2 31 read/reset Alarm input 3 32 read/reset Alarm input 4 33 read/reset Alarm input 5 34 read/reset Alarm input 6 35 read/reset Alarm input 7 36 read/reset Alarm input 8 37 read/reset Alarm input 9 40 read/reset Alarm input read/reset Alarm input read/reset Alarm input read/reset Alarm input read/reset Alarm input read/reset Alarm input read/reset Alarm input read/reset Limit relay (high)1 50 read The condition of the limit relays can be read. Limit relay (high)2 51 read Limit relay (high)3 52 read Limit relay (high)4 53 read Limit relay (low)1 54 read Limit relay (low)2 55 read Limit relay (low)3 56 read Limit relay (low)4 57 read Limit relay (high)1 60 read/reset Alarms can be set and reset (cancelled). Limit relay (high)2 61 read/reset (0-255) Limit relay (high)3 62 read/reset Limit relay (high)4 63 read/reset Limit relay (low)1 64 read/reset Limit relay (low)2 65 read/reset Limit relay (low)3 66 read/reset Limit relay (low)4 67 read/reset 704 output 1 70 read/write An output (pump) can be activated if the level is higher 704 output 2 71 read/write than the stop level, or an output can be deactivated 704 output 3 72 read/write if the level is lower than the start level. 704 output 4 73 read/write 704 alarm 1 74 read/reset Read or reset alarm 704 alarm 2 75 read/reset Læs eller afstil alarm 704 alarm 3 76 read/reset Læs eller afstil alarm 704 alarm 4 77 read/reset Reset 100 read/write 101 read/write Communication flag 102 read/write Bit 102 is set by the 795 on alarm transmission ans must be reset by the main station when the alarm has been received. Power failure 103 read/reset Reset 704 system error 104 read/reset Reset 105 read/write 704 Flow calculation possible 106 read/write Alarm bit for test alarm 107 read/reset Test alarm bit is set and reset on I/O read/write 111 read/write 112 read/write 113 read/write 114 read/write 115 read/write 704 Interlock status bit ( Read / Write bit) 37

38 ONLINE VALUES: I/O NO.: DESCRIPTION: 116 read/write 117 read/write Internal flag read/reset The Combi alarms are a combination of 2 signals ANDed together. The programming of the Combi alarms is made on the MJK Data transmitter 795. Internal flag read/reset The programming of the Combi alarms is made on the MJK Data transmitter 795. Internal flag read/reset All the Combi Alarms are READ or RESET bits Internal flag read/reset Internal flag read/reset Internal flag read/reset Internal flag read/reset Internal flag read/reset Test alarm 150 read/reset I/O150 activates a 2 min. timer which activates I/O 107 ONLINE VALUES: REG. NO.: VALUE: DESCRIPTION: Digital outputs The outputs can be read and set (0-255) Digital inputs Inputs can be read (0-255) Digital inputs Option Alarm inputs Read an reset (0-255) Alarm inputs Option Limit Switches Read (0-255) Alarm limits Read and reset (cancelled) (0-255) 704 output/alarm (Outputs can only be controlled bit-wise!) Control signals 8 Read and reset (795 voltage failure and 704 system error) 9 Cluster and ID no Read Status for internal flags 11 Read Alarms from internal flags 12 Read and reset Test register 13 Writing 1 to this register activates a test procedure. 14 Password 15 Enter 1795 to enable change in the setup page (page 2) Analogue indgang Analogue indgang Analogue indgang Analogue indgang ID no level (0-255) 795 stormflow m³/h Extended log interval 23 0=30 sec. 1=1 min. 2=5 min. 3=10 min. 4=30 min. 5=1 hour 704 P1 start level P2 start level P3 start level P4 start level P1 stop level P2 stop level P3 stop level P4 stop level Al1 high limit value Analog limits can be read and set Al2 high limit value Al3 high limit value Al4 high limit value Al1 low limit value Al2 low limit value Al3 low limit value Al4 low limit value ID number from Inter, Master 40 Interlock output P1 start level P2 start level P1 stop level P2 stop level

39 COUNTERS, 'TOTAL' REG. NO.: VALUE: DESCRIPTION: DI 1 pulse counter Pulse counter can be read and set. DI 2 pulse counter DI 3 pulse counter DI 4 pulse counter DI 5 pulse counter DI 6 pulse counter DI 7 pulse counter DI 8 pulse counter DI 9 pulse counter DI 10 pulse counter DI 11 pulse counter DI 12 pulse counter DI 13 pulse counter DI 14 pulse counter DI 15 pulse counter DI 16 pulse counter DI 1 time counter Time counters can be read and set. DI 2 time counter Time counters counts in whole hours. DI 3 time counter DI 4 time counter DI 5 time counter DI 6 time counter DI 7 time counter Di 8 time counter DI 9 time counter DI 10 time counter DI 11 time counter DI 12 time counter DI 13 time counter DI 14 time counter DI 15 time counter DI 16 time counter Limit 1 (high) pulse Pulse counters can be read and set. Limit 2 (high) pulse Limit 3 (high) pulse Limit 4 (high) pulse Limit 1 (low) pulse Limit 2 (low) pulse Limit 3 (low) pulse Limit 4 (low) pulse Limit 1 (high) time Time counters can be read and set. ( ) Limit 2 (high) time Time counters counts in whole hours. Limit 3 (high) time Limit 4 (high) time Limit 1 (low) time Limit 2 (low) time Limit 3 (low) time Limit 4 (low) time output 1 pulse Pulse counters can be read and set. 704 output 2 pulse output 3 pulse output 4 pulse output 1 time Time counters can be read and set. ( ) 704 output 2 time Time counters counts in whole hours. 704 output 3 time output 4 time stormflow counter m³ pumped value P pumped value P pumped value P pumped value P value total capacity P capacity P capacity P capacity P Analogue 1 max value total Analogue 2 max value total Analogue 3 max value total Analogue 4 max value total level max value total

40 COUNTERS, 'TODAY' REG. NO.: VALUE: DESCRIPTION: DI 1 pulse counter DI 2 pulse counter DI 3 pulse counter DI 4 pulse counter DI 5 pulse counter DI 6 pulse counter DI 7 pulse counter DI 8 pulse counter DI 9 pulse counter DI 10 pulse counter DI 11 pulse counter DI 12 pulse counter DI 13 pulse counter DI 14 pulse counter DI 15 pulse counter DI 16 pulse counter DI 1 time counter Time counters count in whole minutes. DI 2 time counter DI 3 time counter DI 4 time counter DI 5 time counter DI 6 time counter DI 7 time counter DI 8 time counter DI 9 time counter DI 10 time counter DI 11 time counter DI 12 time counter DI 13 time counter DI 14 time counter DI 15 time counter DI 16 time counter Limit 1 (high) pulse Limit 2 (high) pulse Limit 3 (high) pulse Limit 4 (high) pulse Limit 1 (low) pulse Limit 2 (low) pulse Limit 3 (low) pulse Limit 4 (low) pulse Limit 1 (high) time Time counters count in whole minutes. Limit 2 (high) time Limit 3 (high) time Limit 4 (high) time Limit 1 (low) time Limit 2 (low) time Limit 3 (low) time Limit 4 (low) time output 1 pulse output 2 pulse output 3 pulse output 4 pulse output 1 time Time counters count in whole minutes. 704 output 2 time output 3 time output 4 time stormflow counter m³ pumped value P pumped value P pumped value P pumped value P value total

41 COUNTERS, 'YESTERDAY' REG. NO.: VALUE: DESCRIPTION: D1 1 pulse counter D1 2 pulse counter D1 3 pulse counter D1 4 pulse counter D1 5 pulse counter D1 6 pulse counter D1 7 pulse counter D1 8 pulse counter D1 9 pulse counter D1 10 pulse counter D1 11 pulse counter D1 12 pulse counter D1 13 pulse counter D1 14 pulse counter D1 15 pulse counter D1 16 pulse counter D1 1 time counter Time counters count in whole minutes. D1 2 time counter D1 3 time counter D1 4 time counter D1 5 time counter D1 6 time counter D1 7 time counter D1 8 time counter D1 9 time counter D1 10 time counter D1 11 time counter D1 12 time counter D1 13 time counter D1 14 time counter D1 15 time counter D1 16 time counter Limit 1 (high) pulse Limit 2 (high) pulse Limit 3 (high) pulse Limit 4 (high) pulse Limit 1 (low) pulse Limit 2 (low) pulse Limit 3 (low) pulse Limit 4(low) pulse Limit 1 (high) pulse Time counters count in whole minutes Limit 2 (high) pulse Limit 3 (high) pulse Limit 4 (high) pulse Limit 1 (low) pulse Limit 2 (low) pulse Limit 3 (low) pulse Limit 4 (low) pulse output 1 pulse output 2 pulse output 3 pulse output 4 pulse output 1 time Time counters count in whole minutes 704 output 2 time output 3 time output 4 time stormflow counter m³ pumped value P pumped value P pumped value P pumped value P value total

42 LOG, 24 h á 5 min: REG. NO.: VALUE: DESCRIPTION: Analogue input The lowest logged value. Analogue input The oldest logged value. Analogue input The lowest logged value. Analogue input The oldest logged value. Analogue input The lowest logged value. Analogue input The oldest logged value. Analogue input The lowest logged value. Analogue input The oldest logged value. 704 level 1440 The lowest logged value. 704 level 1727 The oldest logged value. LOG, 24 h á 1 h: REG. NO.: VALUE: DESCRIPTION: D1 1 pulse counter x time difference counters. D1 2 pulse counter x time difference counters. D1 3 pulse counter x time difference counters. D1 4 pulse counter x time difference counters. D1 5 pulse counter x time difference counters. D1 6 pulse counter x time difference counters. D1 7 pulse counter x time difference counters. D1 8 pulse counter x time difference counters. D1 9 pulse counter x time difference counters. D1 10 pulse counter x time difference counters. D1 11 pulse counter x time difference counters. D1 12 pulse counter x time difference counters. D1 1 time counter x time difference counters in minutes. D1 2 time counter x time difference counters in minutes. D1 3 time counter x time difference counters in minutes. D1 4 time counter x time difference counters in minutes. D1 5 time counter x time difference counters in minutes. D1 6 time counter x time difference counters in minutes. D1 7 time counter x time difference counters in minutes. D1 8 time counter x time difference counters in minutes. D1 9 time counter x time difference counters in minutes. D1 10 time counter x time difference counters in minutes. D1 11 time counter x time difference counters in minutes. D1 12 time counter x time difference counters in minutes. Limit 1 (high) pulse x time difference counters. Limit 2 (high) pulse x time difference counters. Limit 3 (high) pulse x time difference counters. Limit 4 (high) pulse x time difference counters. Limit 1 (low) pulse x time difference counters. Limit 2 (low) pulse x time difference counters. Limit 3 (low) pulse x time difference counters. Limit 4 (low) pulse x time difference counters. Limit 1 (high) time x time difference counters in minutes. Limit 2 (high) time x time difference counters in minutes. Limit 3 (high) time x time difference counters in minutes. Limit 4 (high) time x time difference counters in minutes. Limit 1 (low) time x time difference counters in minutes. Limit 2 (low) time x time difference counters in minutes. Limit 3 (low) time x time difference counters in minutes. Limit 4 (low) time x time difference counters in minutes. 704 output 1 pulse x time difference counters. 704 output 2 pulse x time difference counters. 704 output 3 pulse x time difference counters. 704 output 4 pulse x time difference counters. 704 output 1 time x time difference counters in minutes. 704 output 2 time x time difference counters in minutes. 704 output 3 time x time difference counters in minutes. 704 output 4 time x time difference counters in minutes. 795 stormflow pulse x time difference counters in minutes. 704 pumped value P x time difference counters in minutes. 704 pumped value P x time difference counters in minutes. 704 pumped value P x time difference counters in minutes. 704 pumped value P x time difference counters in minutes. 704 pumped value total x time difference counters in minutes. SPECIAL REGISTERS: REG. NO.: VALUE: DESCRIPTION: 795 Log interval in sec Read only 795 Log Pointer 3069 Read only Software Release 3070 Read only Data Page 3071 READ and WRITE Register. 0=standard Comli 1= 704 COMLI, 2=795 Setup parameters, 3=Datalogger for 704 level, 4-7=Datalogger for Analogue

43 43

44 20 Menu structure 20.1 Functional menus 44

45 20.2 Programming menus 45

46 46

47 47

48 48

49 49

50 Appendix Data Transmitter 795 A A1 Appendix Technical specifications Dimensions: 185 x 240 x 115 mm (h w d) Power supply: 230 / 115 V AC or 12 / 24 V DC Emergency power: Built-in accumulator for monitoring of power supply and emergency communication. Kapacitet for ca. 3 nødopkald pr. opladning á 12 timer. Power consumption: 15 VA (Approx.) Temperature range: C Material, housing: Polystyrol Material, lid: Makrolon Enclosure: IP 65 Ur: Real time clock with built-in battery backup Kommunikation Telephone / fax: GSM / GPRS: UHF: APL / owned lines: Accuracy: CE: Hayes compatible, auto dial, auto answer, 2400 / 4800 baud 900 / 1800 MHz GSM / GPRS modem Data radio via RS 232 port RS 485 for owned lines (multidrop) < ± ½ % for analogue inputs EN , EN A2 Number of signals available Number of possible signals on a standard Data Transmitter 795 I/O Limit relays Counters Time counters Alarms Analoge indgange Digitale indgange 8/12/16 8/12/16 8/12/16 8/12/16 Digitale udgange 8/4/0 Antal i alt /20/24 16/20/24 16/20/24 Alle værdier overføres som i dag, i går og totalværdier. A3 Inputs and outputs Analogue inputs: 0/4-20 ma or 0-1 V DC. Input voltage = 50 Ω. Digital inputs: Digital outputs: Digital I/O: Data communication: 8 / 12 / 16 DI, passive with common negative pole, max. 24 V DC. (Optocoupler with 10 kω serial resistor) Trig voltage: < 1 V DC = Off, > 10 V DC = On, pulse length > 100 ms. 0 / 4 / 8 DO, voltage free relay contacts, max. 1 A v. 24 V DC / 0,5 A v. 48 V AC. Total 16 DI + DO 2 x ports (RS 485 with item no built-in) A4 Dimensions 50

51 Appendix B Appendix B1 Maintenance In case the function 'Alarm call at power failure' is acticvated, it is recommended to exchange the built-in accumulator yearly. Beyond this, MJK Data Transmitter 795 require no particular maintenance. Check the accumulator by disconnecting the power and check if the Data Transmitter is able to perform a dialup sequence in order to transmit a power failure alarm. When the power is disconnected, the display backlight will disappear immediately. If 'Alarm call at power failure' is deacticvated, the display will be turned off completely after sec. If 'Alarm call at power failure' is acticvated, the Data Transmitteren will start to dial the phone numbers in the telephone list in a period of max. 5 minutes, and then the Data Transmitter will shut down. B2 Service codes Data Transmitter 795 are equipped with functions that should not be operated by the end user. Always contact MJK Hotline before the service codes are used! B2.1 Universal access code If the access code is unavailable, the acces code can always be used. B2.2 Forced setup without reset of datalogger If this code is used, the user will be forced to go through all settings. The logged data will not be erased. Enter F 0 followed by See also separate documentation for GSM/GPRS option. B2.6 Total reset This code give access to a TOTAL RESET. Enter F 0 and B3 Software upgrade The software is stored in EPROM, that just need to be exchanged for upgrading. When the EPROM is exchanged, all basic settings and all logdata will be preserved, if the old software are version and onwards. All basic settings and logdata will be lost when upgrading software versions before : Read first the instruction that came with the new EPROM. 2: Disable the function 'Alarm call at power failure'. See section : Disconnect the power supply to the Data Transmitteren. 4: Remove the front panel by unscrewing the 4 retaining screws in each corner and flip it out of the cabinet. Note: DO NOT withdraw the flat cable to the lower PCB! Note the notch in the EPROM! B2.3 Forced setup including reset of datalogger If this code is used, the user will be forced to go through all settings. All logdata will also be erased! Enter F 0 followed by B2.4 Baud rate and communication method This code give access to menus for setting the baud rate for the serial port and to select communication method (GSM/GPRS/Pager/ internal modem etc.). Enter F * followed by B2.5 Activation of SIM card for GSM/GPRS modem Enter F # followed by * * 0 5 *. 5: Remove the old EPROM. Mount the new EPROM in the socket marked 'IC4' (see illustration above). Make sure the EPROM is mounted in the correct orientation! 6: Reassemble the front and connect the power source to the Data Transmitter. 7: All basic setting must be confirmed. It is very important that the hardware setup settings are correct! Data Transmitter 795 is now ready for operation. 51

USING AND MAINTENANCE MANUAL FOR SELF-CONTAINED POWER BRUSH MACHINE FOR CARPET AND HARD FLOOR. Elite-Silent. Elite-Silent

USING AND MAINTENANCE MANUAL FOR SELF-CONTAINED POWER BRUSH MACHINE FOR CARPET AND HARD FLOOR. Elite-Silent. Elite-Silent USING AND MAINTENANCE MANUAL FOR SELF-CONTAINED POWER BRUSH MACHINE FOR CARPET AND HARD FLOOR Elite-Silent Elite-Silent READ CAREFULLY BEFORE USING THE MACHINE Version 08/02 Generalities The body of the

More information

The CE Marking Access to the European Market

The CE Marking Access to the European Market The CE Marking Access to the European Market The EU dictates the compliance of guidance and a CE marking for many industrial products, so that these products may attain to the market. The experts of Eurofins

More information

COMMUNICATOR ET08 / ET081

COMMUNICATOR ET08 / ET081 COMMUNICATOR ET08 / ET081 User Manual v1.2 Safety instructions Please read and follow these safety guidelines in order to maintain safety of operators and people around: GSM communicator ET08 / ET081 (further

More information

BCF1080 FORWARD PLATE COMPACTORS PARTS BOOK

BCF1080 FORWARD PLATE COMPACTORS PARTS BOOK BARTELL MORRISON INC. 375 Annagem Blvd., Mississauga, ON L5T 3A7 Telephone: 1-647-953-4100 Fax: 1-647-953-4101 BCF1080 FORWARD PLATE COMPACTORS Doc. # PB-B19017 Orig. Rel. 10/2013 Curr Rev. - 06 Bartell

More information

600 Range Dialer Installation Manual. Version 1.0

600 Range Dialer Installation Manual. Version 1.0 600 Range Dialer Installation Manual Version 1.0 The information contained is supplied without liability for any errors or omissions. No part may be reproduced or used except as authorised by contract

More information

DYGIZONE GJD910 Lighting Controller & Enunciator

DYGIZONE GJD910 Lighting Controller & Enunciator DYGIZONE GJD910 Lighting Controller & Enunciator MASTER WIRING IDENTIFICATION Power up to the DygiZone and you will see: All the LED s (red,yellow,green and blue buttons) will flash All the LCD icons will

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd Product Data Sheet Mx-4000 Series User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels The operation and functions described in the manual are available from Software Versions

More information

Operating Instructions for Liquid Level Transducer Model : MM Series

Operating Instructions for Liquid Level Transducer Model : MM Series Operating Instructions for Liquid Level Transducer Model : MM Series 1 Contents 1 Contents... 2 2 Note... 3 3 Instrument Inspection... 3 4 Regulation Use... 4 5 Float designs... 4 6 Operating Principle...

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

EG KONFORMITÄTSERKLÄRUNG EC DECLARATION AND MANUFACTURER S DECLARATION OF CONFORMITY CE DÉCLARATION DE CONFORMITÉ CE DICHIARAZIONE DI CONFORMITÀ

EG KONFORMITÄTSERKLÄRUNG EC DECLARATION AND MANUFACTURER S DECLARATION OF CONFORMITY CE DÉCLARATION DE CONFORMITÉ CE DICHIARAZIONE DI CONFORMITÀ Page 1 of 5 Manufacturer's Name: Business Address: Medical Device(s): Classification: GMDN Code and Term: Scope of Application: EG KONFORMITÄTSERKLÄRUNG EC DECLARATION AND MANUFACTURER S DECLARATION OF

More information

Operating Instructions

Operating Instructions Operating Instructions VCE2600D«««INDEX 001 TYROLIT No. 1099105912345678 de / dd.mm.yyyy19.04.2011 Congratulations! You have decided to purchase a tried and tested TYROLIT-Hydrostress unit and have thus

More information

CTC EcoMiniEl. Installation- and Maintenance Manual. External electric boiler. Providing sustainable energy solutions worldwide

CTC EcoMiniEl. Installation- and Maintenance Manual. External electric boiler. Providing sustainable energy solutions worldwide 161 505 34-3 2015-09-18 Providing sustainable energy solutions worldwide Installation- and Maintenance Manual External electric boiler 161 505 34-3 2015-09-18 Installation- and Maintenance Manual External

More information

SCAN200E USER S MANUAL

SCAN200E USER S MANUAL SCAN200E USER S MANUAL Code No. 2071 1052 rev. 1.4 Code No. 2071 1052 Rev. 1.4 Page 2/16 SCAN200E User s Manual Foreword This manual is for SCAN200E Controller running software version 2.03 or later. We

More information

MULTI-MAX. A) Application - Operating with wheels Do not work without protection cover

MULTI-MAX. A) Application - Operating with wheels Do not work without protection cover MULTI-MAX Manual 1 MULTI-MAX You have made a good decision buying our MULTI-MAX. This grinding and polishing machine can be universally used with wheels from our linear grinder (POLY-PTX ), all flap discs

More information

IRIS Touch Firmware Enhancements and Additions from Version to Version

IRIS Touch Firmware Enhancements and Additions from Version to Version Overview IRIS Touch Firmware Enhancements and Additions from Version 1.14.3 to Version 1.19.1 This document details enhancements to the feature set of the IRIS Touch from firmware Version 1.14.3 to Version

More information

HRX Technical Manual. Version 1.2

HRX Technical Manual. Version 1.2 HRX 5000 Technical Manual Version 1.2 Contents: Specification...2 Connectors...5 RS-485 Network Connectors (J6 and J7)...5 RS-232 to Printer (J19)...6 RS-232 to PC (J8)...7 TCP/IP...8 Power (J21)...9 Fire

More information

Any additional devices linked to the system ET08 (computer, sensors, relays etc.) must be approved by LST EN standard.

Any additional devices linked to the system ET08 (computer, sensors, relays etc.) must be approved by LST EN standard. COMMUNICATOR ET08 User Manual v1.0 Safety instructions Please read and follow these safety guidelines in order to maintain safety of operators and people around: GSM communicator (gateway) ET08 (further

More information

IRIS Touch 400 & 600 Range Installation Manual. Honeywell Galaxy Range. Version 2.0

IRIS Touch 400 & 600 Range Installation Manual. Honeywell Galaxy Range. Version 2.0 IRIS Touch 400 & 600 Range Installation Manual Honeywell Galaxy Range Version 2.0 Table of Contents 1 System Overview... 4 2 IRIS Touch 440 & 640 PCB Layout... 5 3 Connection & Configuration for Honeywell

More information

Operating instructions For Vibration level switch. Model NSV

Operating instructions For Vibration level switch. Model NSV Operating instructions For Vibration level switch Model NSV 1. Content 1. Content... 2 2. Note... 4 3. Instrument Inspection... 4 4. Regulation use... 4 5. Operating Principle... 5 6. Mechanical Connection...

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

ALARM SYSTEM USER S MANUAL Rev

ALARM SYSTEM USER S MANUAL Rev ALARM SYSTEM USER S MANUAL Rev.06 890-00011 Manufacturer: Viatron Electronics 3514 1st Street, St-Hubert (Quebec) Canada J3Y 8Y5 WARNINGS the warranty can be void if the Agri-Alert 2400 is used in a manner

More information

1. User features of the GSM dialer

1. User features of the GSM dialer 1. User features of the GSM dialer The JA60GSM dialer offers many useful features described in detail below. The installer should properly demonstrate the use of the system to the user after installation

More information

Universal fault annunciator for panel mounting

Universal fault annunciator for panel mounting Universal fault annunciator for panel mounting Communication over Ethernet USM - Universal-fault annunciator for panel mounting Low depth housing for panel mounting Versions with 8, 16, 32 or 48 inputs

More information

SMS GSM Alarm Messenger

SMS GSM Alarm Messenger SMS GSM Alarm Messenger Data Logging Alarm Input Relay Output Voice Temperature Humidity Analog Input Capture and Send Data via SMS Report triggered alarm via SMS Output triggered via SMS Auto pick up

More information

Inner Range FE3000S. Serial GSM Modem. P/No: INSTALLATION MANUAL

Inner Range FE3000S. Serial GSM Modem. P/No: INSTALLATION MANUAL Revision 1.0 October. 2014 1 Inner Range FE3000S Serial GSM Modem. P/No: 998306 INSTALLATION MANUAL IMPORTANT NOTE: This Installation Manual is only relevant to Serial GSM Modems utilizing the G-Link PCB.

More information

SCAN20 Series Gas Detection Controller

SCAN20 Series Gas Detection Controller SCAN20 Series Gas Detection Controller USER S MANUAL Code Number 2071 1022 SCAN20 USER S MANUAL Code no. 2071 1022 Page 1/14 Foreword This manual is made for SCAN20 Controllers equipped with the software

More information

HRX3000. Technical Manual

HRX3000. Technical Manual HRX3000 Technical Manual Contents: Specification...2 Connectors...3 Power (J21)...3 RS-485 Network Connectors (J6 and J7)...4 RS-232 to PC (J8)...5 Printer and Fire Alarm Panel (J19)...6 TCP/IP...8 Modem

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information

Lift Station Level Controller

Lift Station Level Controller Lift Station Level Controller Installation and Operation Manual 1 California Motor Controls, Inc. Benicia, CA Table of Contents 1. Features Product Overview... 4-6 Access Security... 7 Optional Features...

More information

Memcom Emergency Telephone

Memcom Emergency Telephone Memcom Emergency Telephone Installation Guide Ref No. 450 900 (GB) Version 2 + + Simple wiring for quick installation + + Integrated LCD display shows you what you have programmed + + All code based programming

More information

Sentient. Downloader Manual D4854

Sentient. Downloader Manual D4854 Sentient Downloader Manual D4854 Dycon Ltd Tel: +44 (0)1443 471 060 Fax: +44 (0)1443 479 374 Cwm Cynon Business Park Mountain Ash CF45 4ER - UK www.dyconsecurity.com sales@dyconsecurity.com TABLE OF CONTENTS

More information

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Page 2 of 16 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Contents 1. Introduction... 4 2. Product Features... 4 3. Package

More information

IP & SMS Alarm Communicator

IP & SMS Alarm Communicator Models: WGSMSC You deserve to feel safe, secure & protected IP & SMS Alarm Communicator Quick Start Guide Thank you for purchasing a Watchguard IP & SMS Alarm Communicator This Quick Start Guide covers

More information

Products no longer available

Products no longer available Technical data sheet MONICO-.. Turnkey automation station MONICO-.. Forms an efficient fire protection system together with the motorisation sets BF(G)24MP Completely wired controller in matching control

More information

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO User s Manual Copyright 2017 SELCO SELCO Betonvej 11 - DK-4000 Roskilde Denmark Phone: 45 7026 1122 - Fax: 45 7026 2522 e-mail: selco@selco.com www.selco.com Table of contents 1 INTRODUCTION...4 2 SOFTWARE

More information

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features. CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse

More information

GLOBAL. InstallatIon & operation manual

GLOBAL. InstallatIon & operation manual InstallatIon & operation manual INDEX 1. INTRODUCTION... 5 2. FEATURES AND FUNCTIONS 2.1 Reporting Options... 2.2 Interfaces... 2.3 Programming... 2.4 Indicators and Controls...... 6 6 6 6 6 3. INSTALLATION...

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

7 USE THE COMMANDS INTERNET VOICE MESSAGES RECORD VOICE MESSAGE DURATION OF VOICE MESSAGES 64

7 USE THE COMMANDS INTERNET VOICE MESSAGES RECORD VOICE MESSAGE DURATION OF VOICE MESSAGES 64 MANUAL FOR PROFORT GSM DEVICES 1 MANUAL FOR PROFORT GSM DEVICES 2 1.1 SPECIFICATIONS 2 1.2 FUNCTIONS 4 1.3 DESCRIPTION 6 1.4 SYSTEM ILLUSTRATION 7 2 MOUNTING 8 2.1 PREPARE THE UNIT 8 2.2 ELECTRIC MOUNTING

More information

Instructions manual. By-alarm. By-alarm Manager software

Instructions manual. By-alarm. By-alarm Manager software Instructions manual By-alarm By-alarm Manager software Index 1. Procedure for the complete programming of the By-alarm system 5 Operations to be carried out prior to the programming with By-Alarm Manager

More information

Manual GPRS Data Logger PCE-GPRS 2

Manual GPRS Data Logger PCE-GPRS 2 PCE Americas Inc. 711 Commerce Way Suite 8 Jupiter FL-33458 USA From outside US: +1 Tel: (561) 320-9162 Fax: (561) 320-9176 info@pce-americas.com PCE Instruments UK Ltd. Units 12/13 Southpoint Business

More information

A1UL PERS. Personal Emergency Response System. For Technical Support Please Contact Your Service Provider Or Distributor

A1UL PERS. Personal Emergency Response System. For Technical Support Please Contact Your Service Provider Or Distributor A1UL PERS Personal Emergency Response System TABLE OF CONTENTS 1. READ THIS FIRST... 1 2. SYSTEM OVERVIEW.. 1 3. COMPONENTS 2 4. UNIT OPERATION! Standby Mode.. 3! Emergency Activation. 3! Answering Incoming

More information

PERMACONN PM1030 Includes DI300. Installation Manual

PERMACONN PM1030 Includes DI300. Installation Manual PERMACONN PM1030 Includes DI300 Installation Manual Radio Data Comms Unit 5/20-30 Stubbs Street Silverwater NSW 2128 Telephone: 02 9352 1777 Facsimile: 02 9352 1700 Introduction The PERMACONN system provides

More information

Version 1.03 January-2002 USER S MANUAL

Version 1.03 January-2002 USER S MANUAL Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...

More information

DL/DLM. Operating instructions Manuel d instructions Instrucciones de uso

DL/DLM. Operating instructions Manuel d instructions Instrucciones de uso DL/DLM Operating instructions Manuel d instructions Instrucciones de uso Scope of delivery for DL/DLM: 1. DL/DLM 2. AAA batteries 3. Quick start guide 4. Device bag 1. 3. 2. 4. 2 DL/DLM operating manual

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Revision 4/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations. 1 P age Ezeio v9-120317 Eze Cloud Based Monitoring Systems. Created by Intech Instruments Ltd December 2014 Important Supplementary Manual to the main Ezeio manual. Ezeio Controller and the 2400-A16 input

More information

Monitoring Solutions

Monitoring Solutions GSM Systems Monitor: Temperature, Humidity, Power, Water, Smoke, Carbon Monoxide and More September 2016 Table of Contents GSM Systems... 3 Argon 100 GSM... 3 Ares 12 & 14 GSM... 4 Poseidon2 4002... 5

More information

AGRI-ALERT 9600 ALARM SYSTEM USER MANUAL

AGRI-ALERT 9600 ALARM SYSTEM USER MANUAL AGRI-ALERT 9600 ALARM SYSTEM USER MANUAL M 890-00279 rev. 14 K 895-00004 rev. 00 Manufacturer: Viatron Electronics 5200, Armand-Frappier St-Hubert (Quebec) Canada J3Z 1G5 WARNINGS The warranty can be void

More information

AUTODIALER SYSTEM FOR LIFTS MANUAL HELPY 2W-V

AUTODIALER SYSTEM FOR LIFTS MANUAL HELPY 2W-V AUTODIALER SYSTEM FOR LIFTS MANUAL HELPY 2W-V 05/06/2018 DESCRIPTION Autodialer to be fitted behind the cop or on top of the car / retrofit. A Connector for Esse-ti power supply (12 Vdc) B Micro SD Card

More information

Ref.1067/032 Ref.1067/042

Ref.1067/032 Ref.1067/042 DS1067-033A Mod. 1067 LBT8631 BUS CONTROL PANEL 8/32 INPUTS Ref.1067/032 Ref.1067/042 USER MANUAL TABLE OF CONTENTS 1 PREFACE... 5 2 COMMAND DEVICES... 6 2.1 1067/021 DISPLAY KEYPAD... 6 2.2 ELECTRONIC

More information

SC-F3G User Manual 1.0

SC-F3G User Manual 1.0 SC-F3G User Manual 1.0 Table of Contents 1. Introduction... 3 2. Functions... 3 3. Features... 3 4. Package Contents... 3 5. Device Configuration... 4 6. Status LED signals... 5 7. Before You Start...

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

Preface. Thank you for purchasing our GSM Security Alarm System ( The System )! The System will keep your home and property safe around the clock.

Preface. Thank you for purchasing our GSM Security Alarm System ( The System )! The System will keep your home and property safe around the clock. Preface Thank you for purchasing our GSM Security Alarm System ( The System )! The System will keep your home and property safe around the clock. The GSM Security Alarm ( The Alarm ) adopts the most advanced

More information

ION Meter Alerts TECHNICAL NOTE NOVEMBER In This Document

ION Meter Alerts TECHNICAL NOTE NOVEMBER In This Document 70072-0125-01 TECHNICAL NOTE NOVEMBER 2006 ION Meter Alerts A PowerLogic ION meter can send alerts to indicate a user specified power system condition such as a power quality problem (including surges,

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 06401 807-0 Fax: 06401 807-59 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control

More information

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491 Bender Incorporated 700 Fox Chase, Coatesville PA 1930 Tel.: (800) 356-466 Fax: (610) 383-7100 Insulation fault evaluators EDS460/490 EDS461/491 Insulation fault evaluators with display and control function

More information

M1000 Alarm Annunciator

M1000 Alarm Annunciator Data Sheet Alarm Annunciator Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions

More information

with internal sensor (channel 1) with an external sensor (channel 2) A-Editor software, Professional AK20 version (not for version AK4)

with internal sensor (channel 1) with an external sensor (channel 2) A-Editor software, Professional AK20 version (not for version AK4) Examples of use Example Creating an SMS-based alarm with confirmation A project file must first be created using the A-Editor software. This project file is then stored in the alarm modem. The alarm modem

More information

With Magictrl, you can control MatiGard anytime & anywhere via your smartphone, even without data network.

With Magictrl, you can control MatiGard anytime & anywhere via your smartphone, even without data network. MatiGard User Guide 02 Menu Feature-------------------------------------------------------------- 05 Overviews---------------------------------------------------------- 07 Read Before Using-----------------------------------------------

More information

DualCom GradeShift UDL QUICK GUIDE & INSTRUCTION MANUAL

DualCom GradeShift UDL QUICK GUIDE & INSTRUCTION MANUAL DualCom GradeShift UDL QUICK GUIDE & INSTRUCTION MANUAL The most trusted brand in Alarm Signalling www.csldual.com @CSLDualCom CSL DualCom Limited Figure 1 - GradeShift UDL SIM card slot Service LED Aerial

More information

GMA200-MT. Operation Manual. Gas detection controller for mounting rail assembly

GMA200-MT. Operation Manual. Gas detection controller for mounting rail assembly Operation Manual GMA200-MT Gas detection controller for mounting rail assembly GfG GESELLSCHAFT FÜR GERÄTEBAU MBH KLÖNNESTRASSE 99 44143 DORTMUND, Germany TEL. +49 / (0)231 / 564 00 0 FAX +49 / (0)231

More information

3i SECURITY with i-mode Welcome to the future of security. Today with your i-mode telephone you have full control of your home and automobile even when you are not present. You may see directly on your

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide

Digiplex System V2.14 / V2.2ACC. Control Panel Programming Guide Digiplex System V2.14 / V2.2ACC Control Panel Programming Guide Table of Contents Getting Started...2 What Do I Do First?...2 How Do I Program the Control Panel?...2 Single Digit Entry Method...2 Multiple

More information

X64 Wireless Training

X64 Wireless Training X64 Wireless Training IDS Contents 1 Contents Features 3 Wireless Hardware 4 IDS & Duevi integration PCB 5 LED operation 5 Wireless Device Hardware setup 6 Location 260 7 LED Keypad Instructions 7 Adding

More information

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances _D00108_00_D_XXEN/05.2015 ISOSCAN Insulation fault locator for DC IT systems with high system leakage capacitances

More information

QBx Sub. Powered Subwoofer Owner s Manual

QBx Sub. Powered Subwoofer Owner s Manual QBx Sub Powered Subwoofer Owner s Manual IMPORTANT SAFETY INSTRUCTIONS WARNING: To reduce the risk of fire or electric shock, do not expose this product to rain or moisture. The lightning flash with arrowhead

More information

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems) ISOSCAN EDS460/490 EDS461/491 Insulation fault locators with control and display function for EDS systems (insulation fault location systems) EDS460-490_D00085_01_D_XXEN/01.2017 ISOSCAN EDS460/490 EDS461/491

More information

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0

IRIS Touch Quick Installation & Maintenance Guide. Version 1.0 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Page 2 of 16 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Contents 1. Introduction...4 2. Product Features...4 3. Package

More information

Sensaphone 400 Telemetry System Integration

Sensaphone 400 Telemetry System Integration Application Note 003 Version 001 07 Oct 2014 Sensaphone 400 Telemetry System Integration The Sensaphone Model 400 is an alarm dialer device that is capable of calling out to one or more telephone numbers

More information

1. Introduction. 2. Product overview

1. Introduction. 2. Product overview 1. Introduction The AG400011 GSM Alarm panel is a control panel that is compatible with other H-net security devices from Everspring, such as wireless sensors, remote keyfobs, tags, and keypad. With this

More information

Ontech GSM 9040/50. Reference Manual English -1 -

Ontech GSM 9040/50. Reference Manual English -1 - Ontech GSM 9040/50 Reference Manual English -1 - Content Welcome... 5 This manual... 5 Text styles... 5 Support... 5 Disclaimer... 5 Overview... 6 Accessories... 6 External temperature sensor 9901... 7

More information

HELPY CONTROLLER QUICK GUIDE

HELPY CONTROLLER QUICK GUIDE Alarm system for elevators compliant with the European Standard EN 81-28:2018 HELPY CONTROLLER QUICK GUIDE 05/04/2019 DESCRIPTION Autodialer specifically designed for installation on elevator controller.

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

Monitoring unit with alarm function and data collection AK-SM 350 REFRIGERATION AND AIR CONDITIONING. Manual

Monitoring unit with alarm function and data collection AK-SM 350 REFRIGERATION AND AIR CONDITIONING. Manual Monitoring unit with alarm function and data collection AK-SM 350 REFRIGERATION AND AIR CONDITIONING Manual Introduction The AK-SM 350 is a combined data collection and monitoring unit for use in refrigeration

More information

GSM Alarm System. User s Manual. Profile. MOBILE CALL GSM Alarm System

GSM Alarm System. User s Manual. Profile. MOBILE CALL GSM Alarm System MOBILE CALL GSM Alarm System GSM Alarm System System disarmed 11/26/2013 User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. CONTENTS

More information

RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL. USER MANUAL Read carefully before use

RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL. USER MANUAL Read carefully before use RS 0021 DIGITAL GAS DETECTION CONTROL UNIT FOR SENSORS WITH S-BUS PROTOCOL USER MANUAL Read carefully before use GENERAL INFORMATION This device is a gas control unit with RS485 serial communication, based

More information

P2267 NETWORK INTERFACE

P2267 NETWORK INTERFACE P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61

More information

Product Data Sheet. Remote Terminals. Features:

Product Data Sheet. Remote Terminals. Features: Remote Terminals Product Data Sheet Features: Based around two core products, the Mx- 4010 Remote Display Terminal (RDT) and the fully functional Mx-4020 Remote Control Terminal (RCT). Both remote terminals

More information

TYDOM 315. * _Rev.2* GSM domotics transmitter. 1. Presentation

TYDOM 315. * _Rev.2* GSM domotics transmitter. 1. Presentation TYDOM 5 GSM domotics transmitter ) Présentation. Presentation Delta Dore hereby declares that the equipment complies with the essential requirements and other relevant provisions of the R&TTE Directive

More information

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1 Operation Manual Fighter ProVision Software Version: 0.0 Revision: 1 TABLE OF CONTENTS 1. Introduction 5 2. Software Installation 5 3. PC Users 6 3.1 Introduction 6 3.2 Default Code 6 3.3 Edit PC User

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

Panel Mounted Fault Annunciator Series

Panel Mounted Fault Annunciator Series Panel Mounted Fault Annunciator Series BSM / USM Panel-mounted fault annunciator Annunciators for panel mounting with,,,, 0 and signal inputs Storage of the last state of inputs and sequence in the case

More information

MJK 704 Pump Controller

MJK 704 Pump Controller MJK 704 Pump Controller 1 As our products are developed continuously we reserve the right to make any change in the dimensions and the specifications. UL Approvals UL-CUL listed, File # E 194021 UL 508/c22:

More information

Insulation fault evaluator EDS460-DG

Insulation fault evaluator EDS460-DG Insulation fault evaluator for localising insulation faults in DC IT systems with a number of branch circuits where high system leakage capacitances are involved Preliminary data sheet TDB108021en/09.2008

More information

Fire Control Panel FS5100

Fire Control Panel FS5100 Fire Control Panel FS5100 INSTRUCTION MANUAL Revision 6/02.11 Contents 1. Introduction... 5 2. Terminology... 5 3. Function... 7 4. Technical data... 7 4.1. Modules... 7 4.1.1. Type of modules... 7 4.1.2.

More information

MG Partition 64-Zone Wireless Console with GPRS/GSM Version 1.6. Section Programming Guide

MG Partition 64-Zone Wireless Console with GPRS/GSM Version 1.6. Section Programming Guide MG6250 2-Partition 64-Zone Wireless Console with GPRS/GSM Version.6 Section Programming Guide Things You Need to Know About this Programming Guide The MG6250 All-in-one Wireless Console can be programmed

More information

EasyTronic III MANUAL SERVICE

EasyTronic III MANUAL SERVICE rev.6 EasyTronic III MANUAL SERVICE General characteristics: Power supply 24 Vac ±15% Max consumption at 24Vac 300mA Relay outputs 6 Maximum relay current 8 A res. Serial standard RS232 2 Serial standard

More information

CONTENT version Piccolo Object protection

CONTENT version Piccolo Object protection CONTENT version 1.14 1: PICCOLO - WIRELESS PROTECTION... 4 HOW THE PICCOLO SYSTEM WORKS... 4 SYSTEM DESCRIPTION... 4 DETECTORS... 4 ALARM RECEIVERS... 4 CENTRAL UNIT & PC... 4 FORWARDING ALARMS (INTERFACES)...

More information

Quick Alert Remote (QA216R)

Quick Alert Remote (QA216R) Quick Alert Remote (QA216R) Description The QA 216 Remote is used by AT&T to monitor tower lights and turned down facilities. It is a 16-bit alarm unit used to transport discrete alarms from a remote location

More information

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING Manual Contents Introduction...3 Valve compatibility...3 Features...3 Application examples...3 Ordering...3 Operating the EKC 347...4-5

More information

Profile. For a better understanding of this product, please read this user manual thoroughly before using it.

Profile. For a better understanding of this product, please read this user manual thoroughly before using it. Intelligent GSM Auto-Dial Alarm System User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. Contents Function Introduction (3) Alarm

More information

GSM RFID VOICE Alarm System

GSM RFID VOICE Alarm System GSM RFID VOICE Alarm System User s Manual For a better understanding of this product, please read this user manual thoroughly before using it. CONTENTS [Function Instruction] [Control Panel] Control Panel

More information

MO n : 12JMC rév A

MO n : 12JMC rév A CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES

More information

Gas Detection System TOX ALARM DG2000-Garage

Gas Detection System TOX ALARM DG2000-Garage Gas Detection System TOX ALARM DG2000-Garage Gas Detection System 32 independent programmable channels 2 programmable alarm levels for each gas = up to 6 for each channel LCD alphanumeric display of gas

More information

Odyssey. issue 01c. system manual

Odyssey. issue 01c. system manual dyssey issue 01c system manual SYSTEM MANUAL Table of Contents Technical Specification 1 Summary of Features 2 General Description 3 Control ptions 4 Description of Main Features 5 Control Schemes 6 Installation

More information

Halton SAFE / 7.14 user guide and installation instructions

Halton SAFE / 7.14 user guide and installation instructions Halton SAFE / 7.14 user guide and installation instructions VERIFIED SOLUTIONS BY H A LTO N Enabling Wellbeing Table of contents 1 System description 3 2 User Accounts 4 3 Main menu 7 3.1 Main menu - Change

More information

FCD-wire Contents. List of Figures

FCD-wire Contents. List of Figures FCD-wire Contents FCD-X21 Configuration 1 Introduction... 1 2 Opening the FCD Application... 1 3 FCD Window... 2 4 FCD LEDs... 3 5 Configuration Operations... 4 FCD Info...4 FCD System Info...5 FCD Interface

More information